Project: Consultant : MEP Contractor: PREPARED BY: DORMAN SMITH SWITCHGEAR - DUBAI REVIEWED BY CONSULTANT : Page 1 of 15

Size: px
Start display at page:

Download "Project: Consultant : MEP Contractor: PREPARED BY: DORMAN SMITH SWITCHGEAR - DUBAI REVIEWED BY CONSULTANT : Page 1 of 15"

Transcription

1 PRCEDURES FR RUTINE TESTING F CAPACITR BANKS Consultant : MEP Contractor: Project: PREPARED BY: DRMAN SMITH SWITCHGEAR - DUBAI NAME: REVIEWED BY CNSULTANT : NAME: SIGNATURE: SIGNATURE: Page 1 of 15

2 Table of Contents Description SCPE PURPSE DEFINITIN RESURCES TEST INSTRUMENT MANPWER MANUFACTURER / VENDR / SPECIALIST LIAISN REFERENCE LIST F RUTINE TESTS TESTING METHDLGY RUTINE TESTS Page 2 of 15

3 1.0SCPE This Method Statement covers the routine testing of the Capacitor Banks to be supplied for in compliance with the specified tolerance and limitations outlined with IEC / EN standards, guidelines and with reference to project specifications, Dorman Smith test criteria / instructions and requirements of BSEN and Utility requirements 2.0PURPSE This procedure provides the methodology that will be used for routine testing of the LV Main power distribution boards / Sub-main distribution boards / Motor Control Centres as per the project specifications, manufacturer recommendations, relevant standards, and approved drawings. This procedure is a guideline and includes an internal routine test checklist to record & complete routine testing of the Equipment/Panel. 3.0DEFINITINS Main Consultant Contractor MS QAQC Lab. Tech TITLE DEFINITIN Method Statement Quality Assurance Quality Control 3 rd Party Laboratory Technician Page 3 of 15

4 4.0Resources 4.1 Measuring and Test equipment Digital Multifunction meter Insulation Resistance Tester (Megger) HV Test Kit Torque Wrench Electrician Hand tools 4.2 Personnel involved: Consultant (WSP) Contractor Representatives (TGEM) Manufacturer representatives.(ds) QA/QC Engineer. (DS) 4.3 Manufacturer / Vendor / Specialist Liaison Dorman Smith Switchgear Ltd. (DS) 4.4 Reference: Approved Shop Drawings Test equipment calibration certificates Internal Routine test certificate format (Annexure-1) Routine test checklists & Test Formats (Annexures 2-5) 4.5 List of Routine tests Visual Inspection Mechanical Functional test Electrical Functional test All internal pre-inspection checks & records carried out and maintained as per Internal Routine test format - Annexure-1. Tests carried out in the check lists being part of this document is for verification and record of pre-dispatch tests carried out in the presence of the Client / Contractor and cover test requirements of the BSEN / IEC standards Page 4 of 15

5 5.0TESTING METHDLGY 5.1General Requirements Ensure that all equipment and materials are as per approved shop drawing prior to the commencement of any testing All materials and documentation relevant to this testing works shall be checked by the responsible personnel prior to the commencement of testing activities Before any item of equipment is accepted for testing a visual inspection will be carried out on that equipment. Where defective equipment is found the same is to be reported to the concerned authority Test power supply availability Ensure all test equipment is calibrated. 5.2 Visual Check of Distribution Boards: As per Visual Inspection Checklist Annexure Mechanical Functional Test: As per Mechanical Function Checklist Annexure Random Torque test on Bus Bar Joints Annexure Electrical Functional test: As per Electrical Function Checklist Annexure - 5 Page 5 of 15

6 ANNEXURE - 1 INTERNAL RUTINE TEST DCUMENT Documents Attached : Format of Internal Routine test format Page 6 of 15

7 ANNEXURE - 2 Test: Visual Inspection Documents Attached : Check list for Visual Inspection Page 7 of 15

8 VISUAL INSPECTIN Equipment Type / Ref : Contractor : I Visual Inspection Test Test Description bservations / Results 1 Enclosures & General Arrangement of Capacitor Banks a Form of Construction as per approved drawing K NT K N/A b IP rating as per approved drawing K NT K N/A c General arrangement / Dimensions / No. of sections as per approved drawings K NT K N/A d Ratings / Mounting arrangements of CT s / Metering as per approved drawings K NT K N/A e Main labels / designation labels / Danger labels as per requirements K NT K N/A f Conformance of switchboard / panel board to distribution system rating K NT K N/A requirements Voltage / frequency / power g Neatness of Metal work and cut outs, paint finish K NT K N/A h Check door locking provisions / panel covers / enclosure ventilations K NT K N/A i Check lifting provisions / mounting plinth K NT K N/A J Check interlocking limit switch provisions on removable doors K NT K N/A 2 Bus bar System a Confirm main bus bar sizes and interconnections sizes as per approved K NT K N/A drawings b Check vertical bus bar sizes and interconnections as per approved drawings K NT K N/A c Check identification of color codes on phases, earth and neutral K NT K N/A d Protection shrouds / barriers against accidental access of LIVE parts K NT K N/A e Conformance of segregation to Form of construction as per requirement K NT K N/A f Check bus bar supports K NT K N/A g Check earthing bus bars / Neutral bus bars K NT K N/A 3 Incoming & utgoing Devices / Capacitors / Reactor / Control gear a Switchgear Devices mounting location as per approved drawings K NT K N/A b Switchgear Devices / Rating / Type / Trip unit as per approved drawings K NT K N/A c Check Incoming cable provisions (cable space) / bus bar extension links / K NT K N/A protective shrouding d Controlgear & Reactors, HRC Fuses, Capacitor Rating / Type as per approved K NT K N/A drawings e Check rotary handles / racking handles K NT K N/A f Check Identification / Designation / Danger labels K NT K N/A g Check cable glanding facility and gland plates (Al. / GI) as required K NT K N/A Page 8 of 15

9 h Check provisions for Neutral and Earth 4 Metering & Indications a Check mounting arrangements / front facia arrangements of meters / switches / K NT K N/A control devices / PF Regulators b Check CT provisions / mounting / control fuse provisions K NT K N/A c Check Indications K NT K N/A 5 Power & Control wiring K NT K N/A a Control voltage as per approved drawings K NT K N/A b Size and identification of control wires K NT K N/A c Terminal block provisions for control wiring / BMS provisions / Inter-panel wiring K NT K N/A / Identification of control cables d Check control cable dressing / routing of cables K NT K N/A Tests Conducted by Date Name : Signatur e : Page 9 of 15

10 ANNEXURE - 3 Test: Mechanical Functional Test Documents Attached : Check list for Mechanical functional test. Page 10 of 15

11 MECHANICAL FUNCTINAL TEST Equipment Type / Ref : Contractor : II Mechanical Functional Test Test Test Description bservations / Results 1 Enclosures A Checking of hinge operation, alignment of doors and door closing. K NT K N/A B Check door earthing cable and termination K NT K N/A C Check locking provisions / keys for doors K NT K N/A D Check transport joints of sections and busbars K NT K N/A E Check limit switch operation on removable doors K NT K N/A 2 Bus bar System A Check transport interconnection of bus bars and random torque tightness (record values) B Check all segregations and protective shrouds are in place and secured K K NT K N/A NT K N/A 3 Incoming & utgoing Devices / Capacitors / Reactor / Control gear A Check manual spring charging mechanism for ACB s (if applicable) K NT K N/A B Check racking mechanism for drawing out ACB (if applicable) K NT K N/A C Draw out ACB and check position interlock in Connected-Test-Isolated K NT K N/A positions. (if applicable) D Check the mechanical N-FF function for ACB. (if applicable) K NT K N/A E Check N-FF operation of all Non-Auto MCCB / Isolators extended K NT K N/A rotary handles and door interlock features. F Check mechanical N-FF-TRIP functions for MCCB devices. K NT K N/A 4 Metering & Indications A Check mechanical operation for all selector switches, pushbuttons K NT K N/A B Check all pointers in analog measurement instruments are set to 0 K NT K N/A C Check PF Regulator mounting K NT K N/A D Check kwh wiring / mounting and viewing provisions K NT K N/A Tests Conducted by Date : : Name : Signature Page 11 of 15

12 ANNEXURE - 4 Test: Random Torque Test on Bus bar Joints Documents Attached : Bus bar tightening torque test Record. Page 12 of 15

13 RANDM BUS BAR TIGHTENING TRQUE TEST RECRD Thread size Torque Required N-M Tested Torque N-M Remarks M M M M Remarks (if any) Tests Conducted by Date : Name : Signature : Page 13 of 15

14 ANNEXURE - 5 Electrical Functional Test Documents Attached : Check list for conducting Electrical Functional Test Page 14 of 15

15 ELECTRICAL FUNCTINAL TEST Equipment Type / Ref : Contractor : ELECTRICAL FUNCTINAL TEST Test Test Description bservations / Results 1 Service conditions A Check supply system parameters with a digital multi meter on the incoming cable K NT K N/A termination end.(voltage / Frequency / phase sequence) B Check auxiliary supply availability. K NT K N/A C Check fuses continuity and ensure all protection in place on auxiliary circuits K NT K N/A D Check limit switch electrical operation on removable doors K NT K N/A 2 Incoming & utgoing Devices / Capacitors / Reactor / Control gear A Manually charge spring for closing mechanism of ACB s / or through motor K NT K N/A mechanism if provided B Check and close the incoming device. Check supply availability on outgoing side of K NT K N/A incoming device C Check and close the outgoing devices. Check supply availability on outgoing side of K NT K N/A device. D Manually switch FF / TRIP all devices and check loss of supply on outgoing side of K NT K N/A all devices. E Close all devices to energize switchboard on completion of above sequence K NT K N/A F Check operation of capacitor contactors via manual switching operations of PF K NT K N/A Regulator G Check remote signalling (Volt free contact initiation) as applicable in devices K NT K N/A 3 Metering & Indications A Check Voltmeter / MFM readings direct / PF regulator etc via selector switches on K NT K N/A front facia of panel. B Check provisions for communication in metering as applicable K NT K N/A C Check all indication lamps K NT K N/A Tests Conducted by Date : Name : Signature : Page 15 of 15

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations C&G 2395-01 Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations Test instruments and recommended testing sequence 1 Outcomes of this Session describe the different

More information

References 6 k thermal overload relays, adjustable from 0.11 to 16 A

References 6 k thermal overload relays, adjustable from 0.11 to 16 A s 6 k thermal overload relays, adjustable from 0.11 to 16 A 3-pole relays with screw clamp terminals These overload relays are designed for the protection of motors. They are compensated and phase failure

More information

C&G 2395 Exam Paper June Section A-All questions carry equal marks. Answer all three questions. Show all calculations.

C&G 2395 Exam Paper June Section A-All questions carry equal marks. Answer all three questions. Show all calculations. C&G 2395 Exam Paper June 2013 Section A-All questions carry equal marks. Answer all three questions. Show all calculations. 1. The electrical installation in an industrial unit is scheduled for a periodic

More information

SAFETY QUALITY TECHNOLOGY. Guidance on Safe Isolation Procedures

SAFETY QUALITY TECHNOLOGY. Guidance on Safe Isolation Procedures SAFETY QUALITY TECHNOLOGY Guidance on Safe Isolation Procedures Introduction Every year, people working on construction sites suffer electric shock and burn injuries some of which, tragically, are fatal.

More information

MaxSB - Low Voltage Switchboard

MaxSB - Low Voltage Switchboard BU 3101 Low Voltage Systems, March 2009 Low Voltage Systems MaxSB - Low Voltage Switchboard May 5, 2009 Slide 1 MaxSB Product Overview Description Value Rated Main bus current 1600A, 2000A, 3000A, 3200A,

More information

PSSI 3 High Voltage Metal-Enclosed Switchgear

PSSI 3 High Voltage Metal-Enclosed Switchgear 1. SCOPE This Safety Instruction applies the principles established by the ScottishPower Safety Rules (Electrical and Mechanical) and Company Safety Instructions to achieve Safety from the System for personnel

More information

IECEx Certificate of Conformity Annexe

IECEx Certificate of Conformity Annexe for Certificate No.: IECEx TSA 09.004X Issue No.: 1 Equipment description pertaining to Issue 0 of this Certificate: A range of electrical power distribution, control, protection and monitoring equipment

More information

London Underground - Section 12 approved Switch Disconnectors

London Underground - Section 12 approved Switch Disconnectors Introduction Following the Kings Cross fire of 1987, the resulting Fennell enquiry prompted the introduction of additional fire precautions for Sub-surface Railway Stations. These additional requirements

More information

It is essential that the maintenance staff is qualified for electrical works and follows safety procedures.

It is essential that the maintenance staff is qualified for electrical works and follows safety procedures. MAINTENANCE OF POWER FACTOR CORRECTION EQUIPMENTS Procedures, suggestions and traceability The purpose of this document is to propose a maintenance method that allows to identify the elements to be maintained

More information

To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy

To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy Annex I To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance 1. Introduction a. These Safety

More information

METROSIL CURRENT TRANSFORMER PROTECTION UNIT (CTPU) ENCLOSURES IEC COMPLIANT

METROSIL CURRENT TRANSFORMER PROTECTION UNIT (CTPU) ENCLOSURES IEC COMPLIANT IEC 649 COMPLIANT METROSIL CURRENT TRANSFORMER PROTECTION UNIT (CTPU) ENCLOSURES INTRODUCTION Current transformer open circuit protection with reliability, flexibility and expertise built-in. Current Transformer

More information

Inspection and Testing Pocket Notes

Inspection and Testing Pocket Notes Inspection and Testing Pocket Notes of Initial Verification Periodic Inspection Purpose of Information required by inspector 1. All equipment is correct type and complies with relevant British Standard

More information

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6 NEUTRAL GROUNDING RESISTORS INSTALLATION, OPERATION & MAINTENANCE MANUAL Contents 1- SAFETY INSTRUCTIONS... 3 1-1- Compliance with Instructions in this Manual. 3 1-2- Guidance Notes Installation.... 3

More information

IEC April Authorized Sole Agent : PT. Wisma Niagatama Perkasa. Phone : (031) Fax. : (031)

IEC April Authorized Sole Agent : PT. Wisma Niagatama Perkasa. Phone : (031) Fax. : (031) IEC 62271-200 April 2004 Authorized Sole Agent : PT. Wisma Niagatama Perkasa Phone : (031) 5041242 Fax. : (031) 5044580 IEC 62271-200 Introduction Scope This standard specifies requirements for factory-assembled

More information

Electrical Safety Program

Electrical Safety Program Electrical Safety Program For Adopted LC-1005 Rev. 06/16 Page 1 I. Introduction As part of Organization s overall safety and health program, an

More information

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073 Operating instructions Safety Rope Emergency Stop Switches UK ZB0052 / ZB0053 ZB0072 / ZB0073 7390878 / 02 03 / 2011 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4

More information

Inspection and Test Plan for Gas Circuit Breaker

Inspection and Test Plan for Gas Circuit Breaker Inspection and Test Plan for Gas Circuit Breaker No. Inspection and Test Plan Reference Document Acceptance Criteria Verifying Document Activity By Remark Manuf. TPI Client 1 Pre Inspection Meeting Spec.

More information

Inspection and Testing

Inspection and Testing Chapter 16 Inspection and Testing 16.1 INTRODUCTION The Purpose of Inspection, Testing and Certification or Reporting The fundamental reason for inspecting and testing an electrical installation is to

More information

Preparer: Owner: Approver: EHS Team Member TES Manager Site Manager

Preparer: Owner: Approver: EHS Team Member TES Manager Site Manager Procedure No.: BMEHS-002.033 Page: 1 of 10 Preparer: Owner: Approver: EHS Team Member TES Manager Site Manager Document Revision Change Table Revision Revision Description Revised Revision Number New By

More information

TeSys protection components

TeSys protection components Presentation, description -pole thermal overload relays TeSys D Presentation TeSys D thermal overload relays are designed to protect a.c. circuits and motors against: b overloads, b phase failure, b excessively

More information

Selection of Electrical PPE Tables

Selection of Electrical PPE Tables Selection of Electrical PPE Tables Instructions Table 1 - Starting with Table 1, select the task you plan to do (right-hand column) and the condition of the equipment you will be working on, (center column).

More information

Check with local zoning official for property line distance requirements.

Check with local zoning official for property line distance requirements. RESIDENTIAL POOL PLAN SUBMITTAL GUIDELINES The following guidelines are intended to assist municipal residents with the permit acquisition process with regard to pools, spas and hot tubs for single family

More information

C&G 2395 Exam Paper April Section A - All questions carry equal marks. Answer all three questions. Show all calculations.

C&G 2395 Exam Paper April Section A - All questions carry equal marks. Answer all three questions. Show all calculations. C&G 2395 Exam Paper April 2013 Section A - All questions carry equal marks. Answer all three questions. Show all calculations. Q.1 The electrical installation in a small food retail outlet is scheduled

More information

i) Filtration machine, measuring equipment and other related machinery

i) Filtration machine, measuring equipment and other related machinery 5 MVA TRANSFORMER SERVICE AND MAINTENANCE FOR TATA CHEMICALS MAGADI. SAFETY MEASURES AND REQUIREMENTS i) A thorough site risk assessment to be done before commencement of work. ii) All personnel involved

More information

QPEO2/037N Credit Value: 15 QCF Level: 2 GLH: 68 Maintaining electrical equipment/systems

QPEO2/037N Credit Value: 15 QCF Level: 2 GLH: 68 Maintaining electrical equipment/systems Performing Engineering Operations QPEO2/037N Credit Value: 15 QCF Level: 2 GLH: 68 Maintaining electrical equipment/systems Learner Name: 2013 Excellence, Achievement & Learning Ltd EAL Assessment Route

More information

Ground Fault Circuit Interrupter(GFCI) Policy

Ground Fault Circuit Interrupter(GFCI) Policy NewStar Netronics, LLC American Products for the World Ground Fault Circuit Interrupter(GFCI) Policy 3926 East 3 rd Street Tulsa, OK 74112 Phone (918)894-5006 Fax (918)836-9909 tech@newstarnetronics.com

More information

Gas Network Craftsperson

Gas Network Craftsperson Gas Network Craftsperson Unit EIAU016 Carrying out Fault Diagnosis on Electrical Equipment and Circuits This assessment specification has been developed as part of the network maintenance craftsperson

More information

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance National Grid UK Electricity Transmission plc NATIONAL SAFETY INSTRUCTION and Guidance LOW VOLTAGE EQUIPMENT Copyright National Grid plc 2016, all rights reserved. No part of this publication may be reproduced,

More information

Electrical Shore Connections

Electrical Shore Connections RULES FOR CLASSIFICATION OF Ships / High Speed, Light Craft and Naval Surface Craft PART 6 CHAPTER 29 NEWBUILDINGS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS Electrical Shore Connections JULY 2014

More information

Maintaining electrical equipment/systems

Maintaining electrical equipment/systems Unit 037 Maintaining electrical equipment/systems Level: 2 Credit value: 15 NDAQ number: 500/9514/6 Unit aim This unit covers the skills and knowledge needed to prove the competences required to cover

More information

UNIVERSITY OF TOLEDO

UNIVERSITY OF TOLEDO UNIVERSITY OF TOLEDO SUBJECT: CONTROL OF HAZARDOUS ENERGY SOURCES Procedure No: S-08-014 (LOCK-OUT / TAGOUT) AND ELECTRICAL SAFE WORK PRACTICES PROCEDURE STATEMENT This program applies to all employees

More information

SECTION 51 NFPA 70E POLICY. Health & Safety Policy and Procedures Manual

SECTION 51 NFPA 70E POLICY. Health & Safety Policy and Procedures Manual SECTION 51 NFPA 70E POLICY Health & Safety Policy and 1. Protection Against Arc Flash A. Policy: An arc flash is a dangerous condition associated with the release of energy caused by an electric arc. An

More information

SEMEMI SQA Unit Code H2AP 04 Carrying out fault location on electrical equipment and circuits

SEMEMI SQA Unit Code H2AP 04 Carrying out fault location on electrical equipment and circuits Carrying out fault location on electrical equipment and circuits Overview This unit identifies the competences you need to locate faults on electrical equipment and circuits, in accordance with approved

More information

Further technical information is available on

Further technical information is available on 1 of 5 Manufacture address : Bartec Technor AS Dusavikveien 39 4007 Stavanger Norway Further technical information is available on www.bartec-technor.no Note on instructions When working in hazardous areas,

More information

SAINT MARY S COLLEGE OF CALIFORNIA STANDARD HAZARDOUS ENERGY CONTROL PROGRAM INCLUDING LOCKOUT/TAGOUT. Prepared by

SAINT MARY S COLLEGE OF CALIFORNIA STANDARD HAZARDOUS ENERGY CONTROL PROGRAM INCLUDING LOCKOUT/TAGOUT. Prepared by SAINT MARY S COLLEGE OF CALIFORNIA STANDARD 1.1.4 HAZARDOUS ENERGY CONTROL PROGRAM INCLUDING LOCKOUT/TAGOUT Prepared by SAINT MARY S COLLEGE OF CA MORAGA, California KAREN LAURICELLA Original Date: 1 JULY

More information

Session Seven: Arc Flash Hazard (AFH) Rio Tinto Bell Bay Site

Session Seven: Arc Flash Hazard (AFH) Rio Tinto Bell Bay Site Session Seven: Arc Flash Hazard (AFH) Rio Tinto Bell Bay Site Evgeniy Mitev and Trung Nguyen Electrical Engineer: Rio Tinto Aluminium Bell Bay Ltd Abstract This paper presents the engineering and technical

More information

Manual Power relay SR853

Manual Power relay SR853 Manual Power relay SR853 Rev. 0 SR853 manual page2 Safety Guidelines for explosion proof devices Application and Standards This instruction manual applies to explosion protected control systems of protection

More information

SEMEEE3-34 Carrying out functional tests on electrical equipment

SEMEEE3-34 Carrying out functional tests on electrical equipment Overview This standard identifies the competences you need to carry out functional tests on electrical equipment, in accordance with approved procedures. You will be required to carry out pre-test inspections

More information

Energy Control. Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: cell:

Energy Control. Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: cell: Energy Control Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: 905.577.0303 cell: 905.977.0210 consultant@staffaid.ca www.staffaid.com Safety, Energy Control, Power Lockout & Function Test Procedures

More information

Ventam 85 Installation & Commissioning Instructions

Ventam 85 Installation & Commissioning Instructions Ventam Systems Ltd Unit D4 Seedbed Business Centre Vanguard Way Shoeburyness Essex SS3 9QY Phone 01702 382 307 Fax 01702 382 340 Ventam 85 Installation & Commissioning Instructions 1 General The Ventam

More information

PRICE LIST Effective From January LV SWITCHGEAR. Be Switch. The Real Switchgear 230 V. SwitchTM INDUSTRIAL PIONEER VALUE CREATOR

PRICE LIST Effective From January LV SWITCHGEAR. Be Switch. The Real Switchgear 230 V. SwitchTM INDUSTRIAL PIONEER VALUE CREATOR PRICE LIST Effective From January - 0 LV SWITCHGEAR SwitchTM Be 0 V INDUSTRIAL PIONEER VALUE CREATOR TM BeC BeC BeC Be S w i t c h BeC - BeC AC POLE POWER CONTACTOR 0 AC Duty Ampere BeC - 00 / 00 AMP.

More information

SEMEM3-65 Servicing anaesthetic and ventilation equipment

SEMEM3-65 Servicing anaesthetic and ventilation equipment Overview This unit identifies the competences you need to carry out servicing activities on anaesthetic and ventilation equipment, in accordance with approved procedures. You will be required to service

More information

Operating Instructions

Operating Instructions Operating Instructions Light-metal Ex d enclosures / flameproof enclosure > 8265/0 Empty enclosure > 8265/4 Control panel, integrated in Ex e enclosure > 8265/5 Control panel Table of Contents 1 Table

More information

Leakage Current Testing Is it right for your application?

Leakage Current Testing Is it right for your application? Leakage Current Testing Is it right for your application? Introduction The Leakage Current test (LCT for short) is most often specified to be performed as a type test in a design or engineering laboratory

More information

AUTOMATIC GAS MANIFOLDS

AUTOMATIC GAS MANIFOLDS AUTOMATIC GAS MANIFOLDS Phoenix Pipeline Products Limited. Unit 8, McKenzie Industrial Park, Tel No.: 44 (0) 161 428 7200 Bird Hall Lane, Fax No.: 44 (0) 161 428 7010 Stockport, Email: info@p3-phoenix.com

More information

Low Voltage Electricity System Safety Rules & Associated Safety Guidance

Low Voltage Electricity System Safety Rules & Associated Safety Guidance Annex J To Loughborough University Facilities Management (FM) Health and Safety Policy Low Voltage Electricity System Safety Rules & Associated Safety Guidance 1. Introduction a. These Safety Rules are

More information

Single-Phase Pad-Mounted Distribution. Single-Phase Pad-Mounted Distribution Transformers KVA

Single-Phase Pad-Mounted Distribution. Single-Phase Pad-Mounted Distribution Transformers KVA 62-10 Single-Phase Pad-Mounted Distribution Catolog Transformers Section Howard Industries, Inc. Certifi ed to ISO 9001:2015 62-10 Single-Phase Pad-Mounted Distribution Transformers 5-500 KVA 10002179

More information

SEMAE3064 Installing aircraft visual display units and computer systems

SEMAE3064 Installing aircraft visual display units and computer systems Installing aircraft visual display units and computer systems Overview This standard identifies the competences you need to install aircraft visual display units and computer systems, in accordance with

More information

Electrical Safety in the Food Industry

Electrical Safety in the Food Industry Health and and Safety Executive Electrical Safety in the Food Industry John Chamberlain HM Principal Specialist Inspector (Electrical & Control Systems) Manchester CROWN COPYRIGHT What I ll cover Legal

More information

Pushbuttons, Indicating Light, and Rotary Switch Stations Series 4975

Pushbuttons, Indicating Light, and Rotary Switch Stations Series 4975 Series 4975 Series 4975 Pushbutton Stations are designed for shipboard control applications requiring heavy duty watertight master switches. Stations are available with one, two or three elements equipped

More information

Innovative Techniques for Mitigating Arc Flash Exposure

Innovative Techniques for Mitigating Arc Flash Exposure Innovative Techniques for Mitigating Arc Flash Exposure Presented at MEMSA 2009 Annual Meeting & Technical Symposium 2007 Eaton Corporation. All rights reserved. INTRODUCTION. As more and more industries

More information

Rigel 601 CHECKBOX. Instruction Manual. 348A551 Issue 2.0. April Seaward Electronic Ltd. Issue 2.0

Rigel 601 CHECKBOX. Instruction Manual. 348A551 Issue 2.0. April Seaward Electronic Ltd. Issue 2.0 Rigel 601 CHECKBOX Instruction Manual 348A551 Issue 2.0 April 2006 2006 Seaward Electronic Ltd. Issue 2.0 Limited Warranty & Limitation of Liability Rigel Medical guarantees this product for a period of

More information

MP15 Jockey Pump Controller

MP15 Jockey Pump Controller Setup and Operating Instructions MP15 Jockey Pump Controller This manual provides general information, installation, operation, maintenance, and system setup information for Metron Model MP15 Jockey Pump

More information

Inspection Recommendations

Inspection Recommendations S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Styles Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Inspection

More information

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , , ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR 1910.331 335-29 CFR 1926.302, 1926.416, 1926.417 BASIS: The National Safety Council estimates that there are at least 300 deaths

More information

TWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3

TWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3 TWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3 The following tasks parallel the Jr. Tech (JT-1, 2, 3) description and development plan and use the Refrigeration and Air conditioning

More information

enclosed product catalogue 2010 isolating switches main/emergency off switches changeover switches insulated stainless steel mild steel

enclosed product catalogue 2010 isolating switches main/emergency off switches changeover switches insulated stainless steel mild steel enclosed product catalogue 2010 isolating switches main/emergency off switches changeover switches insulated stainless steel mild steel kraus & Naimer enclosed switch catalogue Contents This catalogue

More information

Why do I need to do an Arc-Flash Analysis?

Why do I need to do an Arc-Flash Analysis? Why do I need to do an Arc-Flash Analysis? Presented By Tom Norwood for Alexander Nizov, P.E. Principal/Manager Electrical Engineering Division TRAINING INSTITUTE, INC. A SUBSIDIARY OF MEGGER Hazards Analysis

More information

ES18 Security Theory/Regulations Answer Schedule

ES18 Security Theory/Regulations Answer Schedule ES18 Security Theory/Regulations Answer Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The marker

More information

Best Practice Guide, Servomex 2700

Best Practice Guide, Servomex 2700 For full installations details refer to the. Best Practice Guide, Servomex 2700 Mounting: General Guidelines: Servomex 2700 Control Units and air supplies (utilities units) should, ideally, be mounted

More information

Technical News. The evolution of Switchboard Standards

Technical News. The evolution of Switchboard Standards Issue #78 - Summer 2018 Technical News Specialists in electrical and automation products, systems and solutions The evolution of Switchboard Standards Educational paper outlining standards updates and

More information

DuPage County Environmental, Safety, Health & Property Loss Control Program Hazardous Energy Control (Lockout/Tagout)

DuPage County Environmental, Safety, Health & Property Loss Control Program Hazardous Energy Control (Lockout/Tagout) Purpose: To provide the minimum requirements for the lockout or tagout of energy isolating devices whenever work is performed or servicing is done on County of DuPage machinery, equipment, vehicles and

More information

General Requirements of the NEC Advanced Course. Building Officials and Inspectors Educational Association

General Requirements of the NEC Advanced Course. Building Officials and Inspectors Educational Association General Requirements of the NEC Advanced Course Building Officials and Inspectors Educational Association General Requirements -NEC Course Outcome Explain general requirements found in Article 110 of the

More information

Management Plan for Electrical Safety ISD #535

Management Plan for Electrical Safety ISD #535 Management Plan for Electrical Safety ISD #535 Health & Safety Office Maintenance Service Building 10 SE 9 ½ Street Rochester, MN 55904 507-328-4507 MANAGEMENT PLAN FOR ELECTRICAL SAFETY Table of Contents

More information

Safety Regulations and Procedures

Safety Regulations and Procedures Safety Regulations and Procedures for PowerLabDK, DTU Lyngby Campus (for High Voltage testing additional regulation apply) 1. SAFETY REGULATIONS 1.1 Purpose To prevent accidents Contribute to make the

More information

! Warning, refer to accompanying documents.

! Warning, refer to accompanying documents. About this Manual To the best of our knowledge and at the time written, the information contained in this document is technically correct and the procedures accurate and adequate to operate this instrument

More information

REPORT EN :2007+AC:2011 Low voltage switchgear and controlgear - Part 1:General rule

REPORT EN :2007+AC:2011 Low voltage switchgear and controlgear - Part 1:General rule age 1 of 25 REORT E60947-1:2007+AC:2011 Low voltage switchgear and controlgear - art 1:General rule Report Report reference o.... : SCC(15)-41104A-63-10-LVD Tested by(+ signature)... : Reviewed by(+ signature)...

More information

PERIODIC INSPECTION REPORT FOR AN ELECTRICAL INSTALLATION

PERIODIC INSPECTION REPORT FOR AN ELECTRICAL INSTALLATION For explanatory notes relating to software endorsement, see Notes for Recipients A. DETAILS OF THE CLIENT Client: PERIODIC INSPECTION REPORT FOR AN ELECTRICAL INSTALLATION Issued in accordance with British

More information

The definition of a competent person given in the Electricity at Work Regulations 1989 (EWR) is as follows:

The definition of a competent person given in the Electricity at Work Regulations 1989 (EWR) is as follows: Electrical Safety Guidance Note 1 - General Guidance Competent Person The definition of a competent person given in the Electricity at Work Regulations 1989 (EWR) is as follows: "A person in the possession

More information

Arran LED Floodlight Luminaire

Arran LED Floodlight Luminaire Arran LED Floodlight Luminaire INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Important: Please read these instructions carefully before installing or maintaining this equipment. Good electrical

More information

Code of Practice for the Inspection and Testing of Portable Electrical Equipment (PAT)

Code of Practice for the Inspection and Testing of Portable Electrical Equipment (PAT) Code of Practice for the Inspection and Testing of Portable Electrical Equipment (PAT) Reviews and Revisions Action Date Reason Reviewer Updated details of External PAT Contractor 17/02/16 New contract

More information

Inspection and Testing of Signalling Inspection and Testing Principles

Inspection and Testing of Signalling Inspection and Testing Principles Discipline: Engineering (Signalling) Category: Standard Inspection and Testing of Signalling Inspection and Testing Principles ESC-21-03 Applicability ARTC Network Wide CRIA (NSW CRN) Primary Source SCP

More information

Lockout/Tagout - Energy Control Program

Lockout/Tagout - Energy Control Program Lockout/Tagout - Energy Control Program Lockout and Tagging of ELECTRICAL Circuits This portion of the K.R. Miller Contractors, Inc. safety program has been created to maintain a written copy of procedures

More information

Digital Melting Point Apparatus

Digital Melting Point Apparatus Digital Melting Point Apparatus Heating Plateau Ramping Start/Stop Plateau set Ramp stop Hold User Guide Version 1.1 Heating Viewing tube Sample Chamber IEC power inlet socket Power on/off Temperature

More information

Equipment Accuracy / Selection

Equipment Accuracy / Selection Revision 5.0: Included the PPP program for clarification. Revision 6.0: Update references for CTL PDSH 251B to CTL DSH 251E" Added leakage current tolerances for values above 5KHz For Client Labs Purpose

More information

The invisible killer - electrical safety in the food and drink industry

The invisible killer - electrical safety in the food and drink industry The invisible killer - electrical safety in the food and drink industry Jackie Wooldridge Head of Health & Safety 2 Sisters Food Group A game of chance? - Introduction to electrical hazards 1. Take turns

More information

Landlord Report Operational limitations including the reasons (see page No. ) N/A

Landlord Report Operational limitations including the reasons (see page No. ) N/A Installer s Reference Number IRN/ A. DETAILS OF THE CLIENT Client: Rosen Rentals ltd UNKNOWN Address: Issued in accordance with British Standard 7671 Requirements for Electrical Installations by an ELECSA

More information

Construction & Building Industry Safety Guideline. Electrical Isolations

Construction & Building Industry Safety Guideline. Electrical Isolations Construction & Building Industry Safety Guideline Electrical Isolations Disclaimer This Guideline contains information regarding work health and safety. It includes some of your obligations under the work

More information

MSA Latchways Ladder System

MSA Latchways Ladder System Systems overview 1 of 13 Important information Individuals or organisations carrying out the installation of a MSA Latchways ladder fall protection system shall read, understand and follow these instructions

More information

Recent changes in workplace safety regulations have heightened the awareness of hazards associated with electrical arcs.

Recent changes in workplace safety regulations have heightened the awareness of hazards associated with electrical arcs. Recent changes in workplace safety regulations have heightened the awareness of hazards associated with electrical arcs. The hazard level must be quantified and workers properly protected before entering

More information

SWMS No 007 Samark North Qld Pty Ltd ABN : Electrical Contractors License C37121 Page 2 of 6

SWMS No 007 Samark North Qld Pty Ltd ABN : Electrical Contractors License C37121 Page 2 of 6 Samark North Qld Pty Ltd SWMS Manual SWMS No 007 Samark North Qld Pty Ltd ABN : 99 082 958 487 Electrical Contractors License C37121 Page 2 of 6 Safe Work Method Statement Title: SWMS:007 WORKING ON ENERGISED

More information

SCIENCE LAB UTILITY CONTROLS

SCIENCE LAB UTILITY CONTROLS SCIENCE LAB UTILITY CONTROLS INCORPORATING GAS PRESSURE PROVING GAS PRESSURE PROVING EQUIPMENT - ENGINEERED TO DELIVER EXCEPTIONAL LEVELS OF SAFETY THE MERLIN RANGE DESIGNED FOR EDUCATIONAL LABORATORIES

More information

Operating Instructions

Operating Instructions Operating Instructions Ex d Enclosures in Light Metal / Flameproof Encapsulation > 8265/0 Empty Enclosure > 8265/4 controller, installed in Ex e enclosure > 8265/5 controller Contents 1 Contents 1 Contents...2

More information

Postal Service Practice Exam Sample Exam # 5 Exam # 955E

Postal Service Practice Exam Sample Exam # 5 Exam # 955E Postal Service Practice Exam Sample Exam # 5 Exam # 955E Copyright 2017 All rights reserved Customer Support: support@postaljobssourcewcs.com About Exam 955E This exam is only used for a few positions,

More information

Miniature controls. Contactors. Overload relays. Starters. Control relays

Miniature controls. Contactors. Overload relays. Starters. Control relays Contactors Overload relays Starters Control relays Description General features Wiring terminations available include plugon connectors, wire pins for PC board mounting and solder connections Low power

More information

UL TEST REPORT AND PROCEDURE

UL TEST REPORT AND PROCEDURE Issue Date: 2015-01-30 Page 1 of 24 Report Reference # E186249-A270-UL UL TEST REPORT AND PROCEDURE Standard: Certification Type: CCN: Product: Model: Rating: UL 60950-1, 2nd Edition, 2014-10-14 (Information

More information

Electrical Safety Program

Electrical Safety Program Electrical Safety Program The University Of Iowa Environmental Health & Safety 122 Grand Avenue Court Iowa City, IA 52242-1000 Phone: 319-335-8501 Date Revised/Reviewed: 6/8/2018 Table of Contents 1. Summary...

More information

List all key terms and acronyms used in the procedure, and their definitions.

List all key terms and acronyms used in the procedure, and their definitions. Purpose The purpose of this procedure is to provide guidelines for electrical safety in general within Seqwater in compliance with the Electrical Safety Act 2002, Industry Codes of Practice, Regulations,

More information

WESTERN CONNECTICUT STATE UNIVERSITY LOCKOUT/TAGOUT PROCEDURE S-107

WESTERN CONNECTICUT STATE UNIVERSITY LOCKOUT/TAGOUT PROCEDURE S-107 WESTERN CONNECTICUT STATE UNIVERSITY LOCKOUT/TAGOUT PROCEDURE S-107 Draft Issued 12/97 Revised 11/00 Please direct any questions or comments about the applicability of this document to Luigi Marcone, WCSU

More information

Part 3: Safety Rules for the Installation and Maintenance of Underground Electric Supply and Communication Lines

Part 3: Safety Rules for the Installation and Maintenance of Underground Electric Supply and Communication Lines Part 3: Safety Rules for the Installation and Maintenance of Underground Electric Supply and Communication Lines Charles Bleakley Chair, Subcommittee 7 PART 3 UNDERGROUND LINES 2 313. Inspection and tests

More information

Appendix A: Energized Work Permit

Appendix A: Energized Work Permit Appendix A: Energized Work Permit Part I: To be completed by the Supervisor Description of Circuit & Equipment: Job Location: Description of Work to Be Done: Justification of why the circuit cannot be

More information

IECEx Certificate of Conformity

IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification Scheme for Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Certificate No.: IECEx CML 14.0034X Issue No:

More information

Standard. Extra High Voltage (EHV) Indoor Gas Insulated Switchgear Standard R Version 1.0, June 2018

Standard. Extra High Voltage (EHV) Indoor Gas Insulated Switchgear Standard R Version 1.0, June 2018 Standard Extra High Voltage (EHV) Indoor Gas Insulated Switchgear Standard R565990 Version 1.0, June 2018 Tasmanian Networks Pty Ltd (ABN 24 167 357 299) Authorisations Action Name and title Date Prepared

More information

6 lockout operations every electrician MUST perform and respect

6 lockout operations every electrician MUST perform and respect 6 lockout operations every electrician MUST perform and respect 6 lockout operations to respect when working in power substation (on photo: Lockout arm for ACTI9 MCB; credit: cirlock.com.au) Lockout operations

More information

E2.14 Control of Hazardous Energy. Effective Date: 03/01/2018

E2.14 Control of Hazardous Energy. Effective Date: 03/01/2018 University Policy Volume E2: Environment, Health, Safety and Security E2.14 Control of Hazardous Energy Responsible Office: Facilities Management Responsible Officer: Safety Officer POLICY STATEMENT All

More information

MANAGING ARC FLASH: A Risk Management Approach. Steve Williams Engineers Australia - Electrical College 14 June 2017, Brisbane

MANAGING ARC FLASH: A Risk Management Approach. Steve Williams Engineers Australia - Electrical College 14 June 2017, Brisbane MANAGING ARC FLASH: A Risk Management Approach Steve Williams Engineers Australia - Electrical College 14 June 2017, Brisbane 1 ARC FLASH RELEVANCE? Higher Safety Awareness & OHS Legislation Statistics

More information

Pneumatic spool valve islands

Pneumatic spool valve islands Pneumatic spool valve islands P7.GB.R MEGA SPOOL VALVE ISLANDS MEGA pneumatic spool valve islands offer maximum performance along with flexibility, easy installation and simple operation. Due to their

More information

Health & Safety: Electrical safety

Health & Safety: Electrical safety NEWLANDS GIRLS SCHOOL POLICY DOCUMENT Health & Safety: Electrical safety Last Updated By N Piggott Nov 2015 Last Reviewed by N Piggott Jan 2017 Policy Type Review Frequency Statutory Annually Responsible

More information

GOST R CERTIFICATION SYSTEM FEDERAL AGENCY OF TECHNICAL REGULATION AND METROLOGY CERTIFICATE OF CONFORMITY

GOST R CERTIFICATION SYSTEM FEDERAL AGENCY OF TECHNICAL REGULATION AND METROLOGY CERTIFICATE OF CONFORMITY CERTIFICATE OF CONFORMITY No. ROSS US.GB05.V03061 Valid from 8/12/2010 through 8/12/2013 No. 0422555 CERTIFICATION AGENCY ROSS RU.0001.11GB05 NONPROFIT INDEPENDENT RESEARCH ORGANIZATION (), CERTIFICATION

More information

Electrical. Version 1.0

Electrical. Version 1.0 This document is intended to provide basic safety guidelines for the Physical Plant Department at Community College of Allegheny County. The information provided in this guide may vary by site. Version

More information