CYCLIC PERFORMANCE PER ASTM E 330 TEST REPORT. Rendered to: TRUSEAL TECHNOLOGIES, LTD. PRODUCT TYPE: Fixed Window

Size: px
Start display at page:

Download "CYCLIC PERFORMANCE PER ASTM E 330 TEST REPORT. Rendered to: TRUSEAL TECHNOLOGIES, LTD. PRODUCT TYPE: Fixed Window"

Transcription

1 CYCLIC PERFORMANCE PER ASTM E 330 TEST REPORT Rendered to: TRUSEAL TECHNOLOGIES, LTD. PRODUCT TYPE: Fixed Window Report No.: Test Dates: 07/30/07 Through: 08/03/07 Report Date: 08/20/07 Expiration Date: 08/03/ Derry Court York, PA phone: fax:

2 CYCLIC PERFORMANCE PER ASTM E 330 TEST REPORT Rendered to: TRUSEAL TECHNOLOGIES, LTD. 260 Jackson Street West Hamilton, Ontario L8P 1M5 CANADA Report No.: Test Dates: 07/30/07 Through: 08/03/07 Report Date: 08/20/07 Expiration Date: 08/03/11 Project Summary: Architectural Testing, Inc. was contracted by TruSeal Technologies, Ltd. to perform testing on five fixed windows. The samples tested met the performance requirements set forth in the referenced test procedures for a Pa (-80.0 psf). Test specimen description and results are reported herein. The samples were provided by the client. Test Procedures: The test specimens were evaluated in accordance with the client provided test plan as well as in general accordance with ASTM E , Test Method for Structural Performance of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference. Test Specimen Description: Test Specimen #1: Spacer Type: Duraseal (Single Seal) Test Specimen #2: Spacer Type: Conventional Spacer System Test Specimen #3: Spacer Type: Duralite (Single Seal) Test Specimen #4: Spacer Type: Duraseal (Dual-Seal) Test Specimen #5: Spacer Type: Duralite (Dual-Seal) Product Type: Fixed Window The following descriptions apply to all specimens. Overall Size: 1524 mm (60") wide by 1829 mm (72") high Fixed Daylight Opening Size: 1448 mm (57") wide by 1753 mm (69") high 130 Derry Court York, PA phone: fax:

3 Page 2 of 10 Test Specimen Description: (Continued) Finish: All aluminum was painted. Glazing Details: The unit was glazed with 1" thick insulating glass constructed of two sheets of 1/4" thick clear tempered glass and a spacer system. The glass was set from the interior against hot melt glazing compound and secured with aluminum snap-in glazing bead with a four fin rubber compression gasket. Frame Construction: The frame was constructed of extruded aluminum. The corners were square-cut, sealed, and secured with #8 x 1-1/2" screws. Installation: The units were installed into a Spruce-Pine-Fir wood test buck. The nail fin was set against a bed of silicone and was secured with #6 x 1-1/4" screws through the nail fin into the buck, 3" from each corner and spaced 13" on center.

4 Page 3 of 10 Test Results: The temperature during testing was 27 C (80 F). The results are tabulated as follows: ASTM E 330, Air Pressure Cycling Test Unit #1: Duraseal (Single Seal) Design Pressure: Pa (-80.0 psf) Pressure Range Pa (psf) 0 to 3828 (0 to 80) 0 to 5742 (0 to 120) 3828 to 0 (80 to 0) 957 to 0 (20 to 0) Number of Cycles Average Cycle Time (Seconds) NEGATIVE PRESSURE Maximum Deflection at Indicator mm (inch) #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 # N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A (3) 4.6 (0.18) 4.6 (0.18) 26.7 (5) 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A (4) 19.1 (0.75) 14.7 (0.58) 5.3 (0.21) 4.1 (0.16) 3.1 (0.12) 6.4 () 5.6 (0.22) 5.6 (0.22) 9.7 (0.38) 8.4 (0.33) 7.6 (0.30) 29.0 (1.14) 22.1 (0.87) 17.8 (0.70) 3.3 (0.13) Observations: No damage was observed. Result: Pass Note: See Architectural Testing, Inc. Sketch #1 for indicator locations.

5 Page 4 of 10 Test Results: (Continued) ASTM E 330, Air Pressure Cycling Test Unit #2: Conventional Spacer System Design Pressure: Pa (-80.0 psf) Pressure Range Pa (psf) 0 to 3828 (0 to 80) 0 to 5742 (0 to 120) 3828 to 0 (80 to 0) 957 to 0 (20 to 0) Number of Cycles Average Cycle Time (Seconds) NEGATIVE PRESSURE Maximum Deflection at Indicator mm (inch) #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 # N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A (0.94) 5.1 (0.20) 6.1 (0.24) 3.8 (0.15) 26.2 (3) 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A (0.15) 4.1 (0.16) 2.8 (0.11) 24.9 (0.98) 18.5 (0.73) 6.6 (0.26) 4.8 (0.19) 3.8 (0.15) 6.9 (0.27) 4.6 (0.18) 4.6 (0.18) 27.2 (7) 19.8 (0.78) Observations: No damage was observed. Result: Pass Note: See Architectural Testing, Inc. Sketch #1 for indicator locations.

6 Page 5 of 10 Test Results: (Continued) ASTM E 330, Air Pressure Cycling Test Unit #3: Duralite (Single Seal) Design Pressure: Pa (-80.0 psf) Pressure Range Pa (psf) 0 to 3828 (0 to 80) 0 to 5742 (0 to 120) 3828 to 0 (80 to 0) 957 to 0 (20 to 0) Number of Cycles Average Cycle Time (Seconds) NEGATIVE PRESSURE Maximum Deflection at Indicator mm (inch) #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 # N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A (7) 6.1 (0.24) 3.1 (0.12) 5.8 (0.23) 27.4 (8) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A < (<0.01) 27.4 (8) 20.3 (0.80) 14.7 (0.58) 5.6 (0.22) 3.8 (0.15) 5.1 (0.20) 3.3 (0.13) 25.9 (2) 19.1 (0.75) 14.7 (0.58) 2.8 (0.11) Observations: No damage was observed. Result: Pass Note: See Architectural Testing, Inc. Sketch #1 for indicator locations.

7 Page 6 of 10 Test Results: (Continued) ASTM E 330, Air Pressure Cycling Test Unit #4: Duraseal (Dual-Seal) Design Pressure: Pa (-80.0 psf) Pressure Range Pa (psf) 0 to 3828 (0 to 80) 0 to 5742 (0 to 120) 3828 to 0 (80 to 0) 957 to 0 (20 to 0) Number of Cycles Average Cycle Time (Seconds) NEGATIVE PRESSURE Maximum Deflection at Indicator mm (inch) #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 # N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A (0.99) 5.1 (0.20) 3.6 (0.14) 5.3 (0.21) 25.6 (1) 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A (0) 18.8 (0.74) 18.8 (0.74) 6.1 (0.24) 4.6 (0.18) 4.6 (0.18) 5.8 (0.23) 4.1 (0.16) 4.1 (0.16) 25.2 (0.99) 18.5 (0.73) 18.5 (0.73) Observations: No damage was observed. Result: Pass Note: See Architectural Testing, Inc. Sketch #1 for indicator locations.

8 Page 7 of 10 Test Results: (Continued) ASTM E 330, Air Pressure Cycling Test Unit #5: Duralite (Dual-Seal) Design Pressure: Pa (-80.0 psf) Pressure Range Pa (psf) 0 to 3828 (0 to 80) 0 to 5742 (0 to 120) 3828 to 0 (80 to 0) 957 to 0 (20 to 0) Number of Cycles Average Cycle Time (Seconds) NEGATIVE PRESSURE Maximum Deflection at Indicator mm (inch) #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A (1) 5.1 (0.20) 5.3 (0.21) 25.4 (0) 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A (4) 19.8 (0.78) 14.7 (0.58) 5.6 (0.22) 4.1 (0.16) 2.8 (0.11) 6.1 (0.24) 4.1 (0.16) 2.8 (0.11) 26.7 (5) 19.6 (0.77) 15.0 (0.59) Observations: No damage was observed. Result: Pass Note: See Architectural Testing, Inc. Sketch #1 for indicator locations. Conclusion: Five insulating glass spacer systems were tested for cyclic wind pressure performance in accordance to the client provided test plan. During the testing and at the conclusion of the testing, all five spacer systems performed in a similar manner. It is our opinion that there is no difference in performance of the five insulating glass spacer systems tested.

9 Page 8 of 10 Test Equipment: Cycling Mechanism: Computer controlled centrifugal blower with electronic pressure measuring device Deflection Measuring Device: Linear transducers Tape and film were not used to seal against air leakage during structural testing. Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing, Inc. and are representative of the test specimen reported herein. List of Official Observers: Name Werner Lichtenberger, P.E. Stephen D. Shank Tim McGill Michael D. Stremmel, P.E. Jeremy R. Bender Company TruSeal Technologies, Ltd. Architectural Testing, Inc. Architectural Testing, Inc. Architectural Testing, Inc. Architectural Testing, Inc.

10 Page 9 of 10 Detailed drawings, data sheets, representative samples of test specimens, a copy of this report, or other pertinent project documentation will be retained by Architectural Testing, Inc. for a period of four years from the original test date. At the end of this retention period, such materials shall be discarded without notice and the service life of this report will expire. Results obtained are tested values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC. Jeremy R. Bender Technician Michael D. Stremmel, P.E. Senior Project Engineer JRB:vlm Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Sketch (1)

11 Page 10 of 10 Revision Log Rev. # Date Page(s) Revision(s) 0 08/20/07 N/A Original report issue 1 09/27/07 Page 1, 3, 5, 6, 7 Page 8 Changed Dura-Seal and Dura-Lite to Duraseal and Duralite Added P.E. to Werner Lichtenberger This report produced from controlled document template ATI 00165, revised 07/23/07.

12 Appendix A Sketch

13

ASTM E1886 and ASTM E1996 TEST REPORT. Report No.: E Rendered to: 3M COMPANY St. Paul, Minnesota 55144

ASTM E1886 and ASTM E1996 TEST REPORT. Report No.: E Rendered to: 3M COMPANY St. Paul, Minnesota 55144 ASTM E1886 and ASTM E1996 TEST REPORT Report No.: E6587.01 201 44 Rendered to: 3M COMPANY St. Paul, Minnesota 55144 PRODUCT TYPE: Safety and Security Window Film SERIES/MODEL: 3M Safety and Security Film

More information

PERFORMANCE TEST REPORT FOR AIR LEAKAGE AND DURABILITY OF BARRIER PRODUCTS ASTM E Rendered to: BAUTEX SYSTEMS

PERFORMANCE TEST REPORT FOR AIR LEAKAGE AND DURABILITY OF BARRIER PRODUCTS ASTM E Rendered to: BAUTEX SYSTEMS Architectural Testing PERFORMANCE TEST REPORT FOR AIR LEAKAGE AND DURABILITY OF BARRIER PRODUCTS ASTM E 2357 Rendered to: BAUTEX SYSTEMS SERIES/MODEL: AMB 20-WN PRODUCT TYPE: Air Barrier System Report

More information

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina TEST REPORT Report No.: G4124.02-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Sun Tunnel Skylight SERIES/MODEL: TCC 022 SPECIFICATION(S): Occupational Safety and Health

More information

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A STRUCTURAL PERFORMANCE TEST REPORT SUMMARY RENDERED TO:

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A STRUCTURAL PERFORMANCE TEST REPORT SUMMARY RENDERED TO: AAMA/WDMA/CSA 101/I.S.2/A440-05 AAMA/WDMA/CSA 101/I.S.2/A440-08 STRUCTURAL PERFORMANCE TEST REPORT SUMMARY RENDERED TO: ALL SEASONS DOOR & WINDOW, INC. 28 EDGE ROAD EAST BRUNSWICK, NJ 08816 MODEL/ A-200

More information

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: NORTH EAST WINDOWS, USA, INC.

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: NORTH EAST WINDOWS, USA, INC. NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT (Revised) Rendered to: NORTH EAST WINDOWS, USA, INC. SERIES/MODEL: DH990 Double Hung Report Number: Original Report Date: Revised

More information

QUANEX BUILDING PRODUCTS TEST REPORT

QUANEX BUILDING PRODUCTS TEST REPORT QUANEX BUILDING PRODUCTS TEST REPORT SCOPE OF WORK DUAL PANE INSULATING GLASS UNIT PERFORMANCE & GAS EVALUATION REPORT NUMBER H1690.01-119-28 R0 TEST DATE(S) 05/24/17-09/28/17 ISSUE DATE 10/18/17 RECORD

More information

Bomb Blast Mitigation Test

Bomb Blast Mitigation Test 7 June 2005 Bomb Blast Mitigation Test In this time and day of increased natural disasters and terrorist activities, windows have not been put to the test more. With the cries for safety film getting louder

More information

1688 Jean-Berchmans-Michaud Drummondville, Quebec. J2C 8E9. Mr. Marc-Etienne Mathieu,ing.

1688 Jean-Berchmans-Michaud Drummondville, Quebec. J2C 8E9. Mr. Marc-Etienne Mathieu,ing. EVALUATION OF FRAMED WALL CONSTRUCTION SECTIONS UTILIZING SOPREMA S SOPRASEAL STICK 1100T SELF-ADHERED AIR BARRIER SYSTEM IN ACCORDANCE WITH CAN/ULC S742-11 Report to: Soprema 1688 Jean-Berchmans-Michaud

More information

Laboratory Report H

Laboratory Report H Air Permeance Testing of in accordance with ASTM E2178 Prepared for: 6797 Thoreau Lane Baltimore, OH 43105 Date of Issuance: January 16, 2013 Page 2 of 5 CLIENT INFORMATION: TRINITY ERD PROJECT: 6797 Thoreau

More information

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any

More information

The following drawings are concerned of this measure, which will be considered in the next revision of the documents as well as in LogiKal.

The following drawings are concerned of this measure, which will be considered in the next revision of the documents as well as in LogiKal. Based on an much easier assembly of the sealing frame insulating block on fixed glazings the sealing frame has been increased from 7 mm to 9 mm in the system FRAME + 75 WI. This measure has no impact on

More information

OS2 F R A M E S E R I E S

OS2 F R A M E S E R I E S P E R F O R M A N C E S P E C I F I C A T I O N S. F R A M E S E R I E S Window - Single OR Double Sash (Inswing Casement) Assessment of ification 4 Joint Permeability 0.75 m³/hm Overall Area Permeability

More information

FEATURES. Welded Sash and Main Frame. Swiggle or DuraSeal Spacer System on Fixed Units. 3-1/4" Frame Depth. True Sloped Sill. Integral J Channel

FEATURES. Welded Sash and Main Frame. Swiggle or DuraSeal Spacer System on Fixed Units. 3-1/4 Frame Depth. True Sloped Sill. Integral J Channel FEATURES Welded Sash and Main Frame 7/8" Intercept Insulated Glass with Optional Grids; Low-E, Tempered, Obscure, and Argon Gas Available Swiggle or DuraSeal Spacer System on Fixed Units Integral Nailing

More information

LATICRETE International Inc. One LATICRETE Park North Bethany, CT USA

LATICRETE International Inc. One LATICRETE Park North Bethany, CT USA EVALUATION OF FRAMED WALL CONSTRUCTION SECTIONS UTILIZING LATICRETE INTERNATIONAL S LATICRETE BUILDING ENVELOPE SYSTEM AIR BARRIER SYSTEM IN ACCORDANCE WITH CAN/ULC S742-11 Report to: LATICRETE International

More information

CONTENTS 1. INTRODUCTION DESCRIPTION OF TEST SAMPLE TEST RIG GENERAL ARRANGEMENT TEST SEQUENCE...7

CONTENTS 1. INTRODUCTION DESCRIPTION OF TEST SAMPLE TEST RIG GENERAL ARRANGEMENT TEST SEQUENCE...7 Page 2 of 22 CONTENTS 1. INTRODUCTION...3 2. DESCRIPTION OF TEST SAMPLE...4 3. TEST RIG GENERAL ARRANGEMENT...6 4. TEST SEQUENCE...7 5. SUMMARY AND CLASSIFICATION OF TEST RESULTS...8 6. WATERTIGHTNESS

More information

Test Report. Test Report Smart Systems Limited Incorporating Smart Extrusions. Page 1 of 78

Test Report. Test Report Smart Systems Limited Incorporating Smart Extrusions. Page 1 of 78 Test Report 8365614. Smart Systems Limited Incorporating Smart Extrusions Page 1 of 78 Introduction. This report has been prepared by Adam Pearce and relates to the activity detailed below: Job/Registration

More information

Mott Manufacturing Limited

Mott Manufacturing Limited Mott Manufacturing Limited 452 Hardy Road, Brantford, Ontario, Canada, N3T 5L8. Telephone: 519-752-7825 Fax: 519-752-2895 Web Site: www.mott.ca Fume Hood Performance Test Test Date: 9-Sep-08 Model Number:

More information

TABLE OF CONTENTS International Racquetball Federation officially approved specifications. Copyright 01/13/1983; rev.

TABLE OF CONTENTS International Racquetball Federation officially approved specifications. Copyright 01/13/1983; rev. Racquetball Court Specifications TABLE OF CONTENTS International Racquetball Federation officially approved specifications. Copyright 01/13/1983; rev. 1988; 1997, 2013 SECTION ONE: Performance and Specifications

More information

SECTION BUTTERFLY VALVES

SECTION BUTTERFLY VALVES SECTION 15112 BUTTERFLY VALVES PART 1 GENERAL 1.01 SUMMARY A. All butterfly valves shall be of the tight closing, rubber seated type and fully comply with the latest revision of AWWA Standard C504, Class

More information

Intertek Testing Services Building Products. Enterdoor AB ubv

Intertek Testing Services Building Products. Enterdoor AB ubv TEST REPORT EN 14351-1:2006 + A1:2010 Windows and doors Product standard, performance characteristics- Part 1: Windows and external pedestrian doorsets without resistance to fire and/or smoke leakage characteristics

More information

PFS Test Report TL-109

PFS Test Report TL-109 PFS Test Report TL-109 Laboratory Services Testing Research Consulting Model Code Qualifications Quality Assurance Design Calculations Sampling Witnessing ENGINEERED WOOD PRODUCTS MDF panels, I-Joists,

More information

Kestrel Aluminium Systems Limited. Product Manual Section 10 Thermal Framing System. Manual Version

Kestrel Aluminium Systems Limited. Product Manual Section 10 Thermal Framing System. Manual Version Kestrel luminium Systems Limited Product Manual Section 10 Manual Version 23.0.1 Kestrel luminium Systems Section 10.01 Product Specification 10.01.01 sheet 1 Product specification 10.01.01 sheet 2 Product

More information

ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR MAGOULA ATTIKIS GREECE

ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR MAGOULA ATTIKIS GREECE TEST REPORT Report Number 0602 Report Date 21 / 02 / 2006 Client Specimen description ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR 190 18 MAGOULA ATTIKIS Curtain Wall Specimen With three

More information

Code Compliance Research Report CCRR-0145

Code Compliance Research Report CCRR-0145 Code Compliance Research Report CCRR-0145 Issued: 11-16-2009 Renewal Due: 11-18-2018 Revised: 11-28-2017 DIVISION: 05 - Metals Section: 05 50 00 Metal Fabrications MARSHALL STAMPING COMPANY 355 Glade Mills

More information

Code Compliance Research Report CCRR-0145

Code Compliance Research Report CCRR-0145 Code Compliance Research Report CCRR-0145 Issue Date: 11-16-2009 Revision Date: 11-29-2018 Renewal Date: 11-18-2019 DIVISION: 05 - Metals Section: 05 50 00 Metal Fabrications Marshall Stamping Company

More information

CE conform applications according to EN Windows without thermal break Systems Forster presto and Forster norm

CE conform applications according to EN Windows without thermal break Systems Forster presto and Forster norm CE conform applications according to EN 14351-1 Windows without thermal break Systems Forster presto and Forster norm 2 Properties Table 1 Window Operating forces Resistance to wind load Air permeability

More information

Evidence of Performance. Class 4. Class 5A. Class C5 / B5. Test Report No PR01. ift Rosenheim

Evidence of Performance. Class 4. Class 5A. Class C5 / B5. Test Report No PR01. ift Rosenheim Evidence of Performance Test Report No 16-002359-PR01 (PB-A01-02-en-01) Client Product Designation Performance-relevant product details Overall dimensions (W x H) Special features - / - SUNCE Marinkovic

More information

Perma-Shield Gliding Windows (1971 to 1992)

Perma-Shield Gliding Windows (1971 to 1992) Perma-Shield Gliding Windows (1971 to 1992) Parts Catalog Main Menu Section TOC Search What s in This Section Standard Units.................................................... Page 3 Parts Illustration...........................................................

More information

ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR MAGOULA ATTIKIS GREECE

ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR MAGOULA ATTIKIS GREECE TEST REPORT Report Number 0601 Report Date 10 / 02 / 2006 Client Specimen description ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR 190 18 MAGOULA ATTIKIS Curtain Wall Specimen With four

More information

Committee C21 on Ceramic Whitewares and Related Products Subcommittee C21.06 on Ceramic Tile. Research Report C

Committee C21 on Ceramic Whitewares and Related Products Subcommittee C21.06 on Ceramic Tile. Research Report C This Research Report is issued under the fixed designation RR: C21-1005. You agree not to reproduce or circulate or quote, in whole or part, this document outside of ASTM International Committee/Society

More information

FILE - RE CAULKING WINDOWS AND DOORS EBOOK

FILE - RE CAULKING WINDOWS AND DOORS EBOOK 23 June, 2018 FILE - RE CAULKING WINDOWS AND DOORS EBOOK Document Filetype: PDF 492.45 KB 0 FILE - RE CAULKING WINDOWS AND DOORS EBOOK How Often Do I Need to Caulk Doors, Windows. The houses in our area

More information

Technical Report. Title: Product weathertightness testing of a sample of W.G.Ltd 500 series Curtain Walling for The Window Glass Company Limited

Technical Report. Title: Product weathertightness testing of a sample of W.G.Ltd 500 series Curtain Walling for The Window Glass Company Limited Technical Report Title: Product weathertightness testing of a sample of W.G.Ltd 500 series Curtain Walling for Limited Report No: N950-3-670 Report number N950-3-670 CONTENTS INTRODUCTION...4 2 SUMMARY

More information

Argonomics. Low emissivity coatings Argon gas fills Warm edge design FIGURE 1 ADD ARGON ADD INTERCEPT SPACER ADD SINGLE STACK LOW E COATING

Argonomics. Low emissivity coatings Argon gas fills Warm edge design FIGURE 1 ADD ARGON ADD INTERCEPT SPACER ADD SINGLE STACK LOW E COATING The name of the game in today s window systems is performance. When you look back only 10 to 15 years and track the evolution of energy efficient windows, the improvements are impressive. The overall R-values

More information

CLEANROOM GEL GRID CEILING SYSTEM PRODUCT DATA Division

CLEANROOM GEL GRID CEILING SYSTEM PRODUCT DATA Division 5023 HAZEL JONES ROAD, BOSSIER CITY, LA 71111 888.315.1561 800.877.8746 FAX SALES@GORDONCLEANROOM.COM GORDONCLEANROOM.COM AN EMPLOYEE OWNED COMPANY CLEANROOM GEL GRID CEILING SYSTEM PRODUCT DATA Division

More information

Mott Manufacturing Limited

Mott Manufacturing Limited Mott Manufacturing Limited 452 Hardy Road, PO Box 1120, Brantford, Ontario, Canada, N3T 5T3. Telephone: 519-752-7825 Fax: 519-752-2895 Web Site: www.mott.ca Fume Hood Performance Test Test Date: January

More information

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Series Smoke Seals in Accordance with BS 476: Part 31, Section 31.

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Series Smoke Seals in Accordance with BS 476: Part 31, Section 31. Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Air Leakage Performance of

More information

3M: Anchored Safety Film Blast Tests

3M: Anchored Safety Film Blast Tests fgsdfg Report PAGE 1 Prepared by Benjamin Fry, BSc AMInstP Engineer TPS Ltd Simon Volpe, MEng Engineer TPS Ltd ADDRESS Centre Tower Whitgift Centre Croydon CR9 0AU CONTACT T 020 8256 4000 F 020 8256 4082

More information

Report No. 371/ This report consists of 6 pages

Report No. 371/ This report consists of 6 pages Test Report This report consists of 6 pages Licence/Certificate No. KM 578199 Client Super Sealed Units Ltd 35 Lovett Way Woodside Industrial Estate Dunstable LU5 4TU Authority & date BSI Service Management

More information

SOLAR ENERGY. solutions. adhesives, sealants, and Potting encapsulants For solar energy applications

SOLAR ENERGY. solutions. adhesives, sealants, and Potting encapsulants For solar energy applications SOLAR ENERGY solutions adhesives, sealants, and Potting encapsulants For solar energy applications Micro-inverters charge controllers J-Box Potting Batteries Bonding / sealing EPIC RESINS quality SolutIoNS

More information

Insulated Cabin Flat Roof

Insulated Cabin Flat Roof A L L P U R P O S E I N S U L A T E D C A B I N S Insulated Cabin Flat Roof OWNER S MANUAL / Instructions for Assembly Size 0 Ft x 3 Ft / 3. Mtr. x 4.0 Mtr. (Approx.) Ver. : 3.0 Customer Service Hotline

More information

Diaphragm pop-pop engine

Diaphragm pop-pop engine Diaphragm pop-pop engine By Jean-Yves Based on some knowledge got from previous engines we decided to build a new one in order to test various diaphragms. Therefore, where the diaphragm is usually pinched

More information

Duralite and Duraseal Gas Filling Manual

Duralite and Duraseal Gas Filling Manual Insulating Glass Systems Duralite and Duraseal Gas Filling Manual Disclaimer: Quanex provides this Gas Filling Manual as a service to customers in order to assist customers in the proper use of Quanex

More information

EN1279 part 3 assessment of insulating glass: IGU with Duralite sealant

EN1279 part 3 assessment of insulating glass: IGU with Duralite sealant TNO Quality Services BV TNO report De Rondom 1 P.O. Box 6235 5600 HE Eindhoven The Netherlands TQS-RAP-07-271 EN1279 part 3 assessment of insulating glass: IGU with Duralite sealant Date February 7, 2007

More information

Sample Procurement Specifications for Aluminum Traffic Control Signs and Components

Sample Procurement Specifications for Aluminum Traffic Control Signs and Components Sample Procurement Specifications for Aluminum Traffic Control Signs and Components These sample procurement Specifications were prepared by the American Traffic Safety Services Association (ATSSA) Sign

More information

DIVISION: 06--WOOD AND PLASTICS SECTION: Wood, Plastic and Composite Fastenings

DIVISION: 06--WOOD AND PLASTICS SECTION: Wood, Plastic and Composite Fastenings DIVISION: 06--WOOD AND PLASTICS SECTION: 060523 -- Wood, Plastic and Composite Fastenings REPORT HOLDER: ITW BUILDING COMPONENTS GROUP, INC. 2400 LAKE ORANGE DRIVE, SUITE 150 ORLANDO, FLORIDA 32837 (800)

More information

everest efficiency weather tightness durability er tightness durability energy efficiency royalplast.ca

everest efficiency weather tightness durability er tightness durability energy efficiency royalplast.ca everest royalplast.ca lity energy efficiency weather tightness efficiency weather tightness durability er tightness durability energy efficiency everest frame m The Everest patio door is offered with a

More information

SAN ANTONIO WATER SYSTEM I.H. 10 Ground Storage Tank Rehabilitation and Painting Project SAWS Job No Solicitation No.

SAN ANTONIO WATER SYSTEM I.H. 10 Ground Storage Tank Rehabilitation and Painting Project SAWS Job No Solicitation No. SAN ANTONIO WATER SYSTEM I.H. 10 Ground Storage Tank Rehabilitation and Painting Project SAWS Job No. 13-0118 Solicitation No. B-16-014-GC September 1, 2016 TO BIDDER OF RECORD: The following changes,

More information

P.68 VARIANTS. SERVICE BULLETIN No. 221 Rev. 5

P.68 VARIANTS. SERVICE BULLETIN No. 221 Rev. 5 vulcanair spa via g. pascoli, 7 80026 casoria (na) italia Tel +39 081 5918111 Fax +39 081 5918172 info@vulcanair.com www.vulcanair.com P.68 VARIANTS Approved by the Vulcanair Design Organisation The technical

More information

Water Management Residential Podium Construction BSC Experts Session Overview. Overview

Water Management Residential Podium Construction BSC Experts Session Overview. Overview Building Science Experts' Seminar Water Management Residential Podium December 11-12, 2013 Peter Baker, P.Eng. Water Management Residential Podium BSC Experts Session 2013 Overview Building Enclosure Commissioning

More information

IGUMA - IGU Design Limitations

IGUMA - IGU Design Limitations 1/5 IGUMA - IGU Design Limitations Introduction Insulating Glass Units (IGU s) are being used more frequently in domestic and commercial buildings to provide improved insulation, comfort, condensation

More information

User-Calibration of Mettler AT200 Analytical Balance

User-Calibration of Mettler AT200 Analytical Balance UCRL-ID- 132292 User-Calibration of Mettler AT200 Analytical Balance J. Estill July 2,1996 This is an informal report intended primarily for internal or limited external distribution. The opinions and

More information

Originally Issued: 10/08/2010 Revised: 10/30/2015 Valid Through: 10/31/2016

Originally Issued: 10/08/2010 Revised: 10/30/2015 Valid Through: 10/31/2016 EVALUATION SUBJECT: ITW ALPINE HANGERS AND ANCHORS REPORT HOLDER: ITW Building Components Group Inc. 13825 W. Business Center Dr. Unit A Lake Forest, IL 60045 (800) 521-9790 www.alpineitw.com CSI Division:

More information

BOAT WINDOWS AND SHOWERS Price List June 2017 Tel/Fax:

BOAT WINDOWS AND SHOWERS Price List June 2017 Tel/Fax: DOUBLE LA ZED WINDOWSGW ITH A TH ERMAL BREA K BOAT WINDOWS AND SHOWERS Price List June 2017 Tel/Fax: 01636 704363 WESLEY MARINE WINDOWS LTD BOAT WINDOWS AND SHOWERS Tel/Fax: 01636 704363 INDEX Page 3-6

More information

Perma-Shield Gliding Windows

Perma-Shield Gliding Windows Perma-Shield Gliding Windows Parts Catalog Main Menu Section TOC Search What s in This Section Standard Units.................................................... Page 3 Parts Illustration...........................................................

More information

SCSA3812SL - CRL Satin Anodized 120" http://www.crlaurence.com/crlapps/showline/offerpage.aspx?productid=23944&groupi... Page 1 of 2 9/10/2014 C.R. Laurence Co., Inc. Sign On Your Account View Cart Help

More information

TEST REPORT TS EN : TS EN A1 Windows and doors - Product standard. Testing Reference. : BM 72 Gizli Kanat Pencere (Hidden Vent Window)

TEST REPORT TS EN : TS EN A1 Windows and doors - Product standard. Testing Reference. : BM 72 Gizli Kanat Pencere (Hidden Vent Window) TEST REPORT TS EN 12153 Testing Reference : TS EN 14351-1 +A1 Windows and doors - Product standard Product / Project : BM 72 Gizli Kanat Pencere (Hidden Vent Window) Prepared by : Nilay BULUT Accreditation

More information

Warranty The VELUX promise

Warranty The VELUX promise Warranty The VELUX promise 20 year limited warranty VELUX insulating glass (a)(b) For a period of (20) twenty years from the date of purchase, VELUX warrants to the End-user (c) that the insulated glass

More information

Design of a Solid Wall Transonic Wind Tunnel

Design of a Solid Wall Transonic Wind Tunnel Design of a Solid Wall Transonic Wind Tunnel David Wall * Auburn University, Auburn, Alabama, 36849 A solid wall transonic wind tunnel was designed with optical access from three sides to allow for flow

More information

Now with SUPREME FRAMING SYSTEM! PRODUCT TECHNICAL GUIDE. Steel Stud Manufacturers Association

Now with SUPREME FRAMING SYSTEM! PRODUCT TECHNICAL GUIDE. Steel Stud Manufacturers Association Now with SUPREME FRAMING SYSTEM! PRODUCT TECHNICAL GUIDE Steel Stud Manufacturers Association 2507 3064P Product Identification "S" and "SFS" - C-STUD/JOIST S and SFS-SECTIONS* * For "S" and "SFS" members,

More information

IAN BENNIE & ASSOCIATES PTY. LTD.

IAN BENNIE & ASSOCIATES PTY. LTD. TEST CERTIFICATE No. 2009-098-C1 9 November 2010 FCM 4646 0004B AS 4285-2007 (refer below 9 November 2009 2009-098-S5 The system was nominally 1300mm x 1300mm OD secured to a metal base and metal flashing.

More information

Architectural Railing Systems

Architectural Railing Systems Architectural Railing Systems Hand Rails, Guard Rails, Railing, Windscreens and Much More... New Products Designed and Engineered for Commercial and Residential Needs Component and Accessory Items Complement

More information

Originally Issued: 10/08/2010 Revised: 10/27/2017 Valid Through: 10/31/2018

Originally Issued: 10/08/2010 Revised: 10/27/2017 Valid Through: 10/31/2018 ITW BUILDING COMPONENTS GROUP INC. ITW ALPINE HANGERS AND ANCHORS CSI Section: 06 05 23 Wood, Plastic and Composite Fastenings 1.0 RECOGNITION ITW Alpine Hangers and Anchors recognized in this report has

More information

RESIDENTIAL BUILDING PLAN REVIEW CHECKLIST

RESIDENTIAL BUILDING PLAN REVIEW CHECKLIST RESIDENTIAL BUILDING PLAN REVIEW CHECKLIST PERMIT # THREE (3) SETS OF PLANS REQUIRED. ONE (1) SET OF DIGITAL PLANS REQUIRED FOR ALL NEW STRUCTURES Plans Examiner: Date: Owner: Permit #: Contractor: Phone

More information

1800CPB2 Service Regulators Maximum Inlet Pressure 125 PSIG

1800CPB2 Service Regulators Maximum Inlet Pressure 125 PSIG A C E D SB-8520.2 1800CPB2 Service Regulators Maximum Inlet 125 PSIG AMC Quality System QMI is Accredited by: C R E D I T ISO 9001 Certified Certificate #006697 R E ANSI RAB G I S T R A R Dutch Council

More information

2 COUNTY OF SUFFOLK STATE OF NEW YORK X 4 HISTORIC PRESERVATION COMMISSION

2 COUNTY OF SUFFOLK STATE OF NEW YORK X 4 HISTORIC PRESERVATION COMMISSION 1 1 VILLAGE OF GREENPORT 2 COUNTY OF SUFFOLK STATE OF NEW YORK 3 ----------------------------------------X 4 HISTORIC PRESERVATION COMMISSION 5 REGULAR SESSION 6 ----------------------------------------X

More information

REPORT NUMBER: G COQ-004 rev 1 ORIGINAL ISSUE DATE: May 18, 2010 REVISION DATE: June 7, 2010

REPORT NUMBER: G COQ-004 rev 1 ORIGINAL ISSUE DATE: May 18, 2010 REVISION DATE: June 7, 2010 TEST REPORT REPORT NUMBER: G100017878COQ-004 rev 1 ORIGINAL ISSUE DATE: May 18, 2010 REVISION DATE: June 7, 2010 EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C.

More information

Product Guide. Latitude Series High-Performance Exterior Metal Wall Panels for Horizontal and Vertical Concealed Clip Application

Product Guide. Latitude Series High-Performance Exterior Metal Wall Panels for Horizontal and Vertical Concealed Clip Application Product Guide Latitude Series High-Performance Exterior Metal Wall Panels for Horizontal and Vertical Concealed Clip Application Blank Text www.imetco.com (800) 646-3826 Page 2 Contents Standard Profile...

More information

STANDARD OPERATING PROCEDURES

STANDARD OPERATING PROCEDURES PAGE: 1 of 9 CONTENTS 1.0 SCOPE AND APPLICATION 2.0 METHOD SUMMARY 3.0 SAMPLE PRESERVATION, CONTAINERS, HANDLING AND STORAGE 3.1 Canister Receipt 3.2 Canister Storage 4.0 INTERFERENCE AND POTENTIAL PROBLEMS

More information

INTRODUCTION. Disclaimer

INTRODUCTION. Disclaimer 3 INTRODUCTION The Steel Framing Industry Association (SFIA) was formed with the objective of assisting companies having interests in the cold-formed steel framing industry to be more successful by unifying

More information

STANDARD OPERATING PROCEDURES

STANDARD OPERATING PROCEDURES PAGE: 1 of 14 CONTENTS 1.0 SCOPE AND APPLICATION 2.0 METHOD SUMMARY 3.0 SAMPLE PRESERVATION, CONTAINERS, HANDLING AND STORAGE 4.0 INTERFERENCE AND POTENTIAL PROBLEMS 5.0 EQUIPMENT/APPARATUS 6.0 REAGENTS

More information

Air Leakage Detailing & Awareness Services

Air Leakage Detailing & Awareness Services Tel: 08456 808048 Mob: 07866 948200 www.aldas.co.uk Info@aldas.co.uk Report on the Repeat Air Permeability Testing of the Passivhaus Refurbishment of: 57 Portfield Street, Hereford 16 th July 2010 Address:

More information

UNIVERSITY OF ROCHESTER MEDICAL CENTER

UNIVERSITY OF ROCHESTER MEDICAL CENTER 1. Purpose/Scope: This procedure defines the operation, maintenance and calibration of the Beckman 2. General Policy: The HIC will adhere to the specific guidelines recommended by Beckman Coulter s instruction

More information

Equipment Accuracy / Selection

Equipment Accuracy / Selection Revision 5.0: Included the PPP program for clarification. Revision 6.0: Update references for CTL PDSH 251B to CTL DSH 251E" Added leakage current tolerances for values above 5KHz For Client Labs Purpose

More information

Ti-Pure TITANIUM DIOXIDE DETERMINATION OF OIL ABSORPTION (OA) METHOD: T WP

Ti-Pure TITANIUM DIOXIDE DETERMINATION OF OIL ABSORPTION (OA) METHOD: T WP Ti-Pure TITANIUM DIOXIDE DETERMINATION OF OIL ABSORPTION (OA) METHOD: T4400.010.06.WP 1 TITANIUM DIOXIDE (Ti-Pure ) Determination of Oil Absorption I. Principle The oil absorption of a sample of titanium

More information

REPORT HOLDER: FRAMECAD LICENSING LTD. POST OFFICE BOX 1292 AUCKLAND 1140 NEW ZEALAND EVALUATION SUBJECT: COLD FORMED STEEL C SHAPES AND TRACKS

REPORT HOLDER: FRAMECAD LICENSING LTD. POST OFFICE BOX 1292 AUCKLAND 1140 NEW ZEALAND EVALUATION SUBJECT: COLD FORMED STEEL C SHAPES AND TRACKS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2361 Reissued 05/2017 This report is subject to renewal 05/2019. DIVISION: 05 00

More information

SUPPLY OF ISOLATION AND APPLIANCE VALVES PTS - APPLIANCE BALL VALVE

SUPPLY OF ISOLATION AND APPLIANCE VALVES PTS - APPLIANCE BALL VALVE PTS - APPLIANCE BALL VALVE 2 30.06.17 Issued for Tender AS ADE GS 1 12.04.17 Issued for Tender AS AD GS 0 06.03.17 Issued for Client s Comments AS AD GS Rev. Date Subject of revision Author Checked Approved

More information

Insulated Cabin Flat Roof

Insulated Cabin Flat Roof A L L P U R P O S E I N S U L A T E D C A B I N S Insulated Cabin Flat Roof OWNER S MANUAL / Instructions for Assembly Size 0 Ft x Ft with Extension Kits (0 Ft x 6 / Ft /. Mtr. x Mtr.) (Approx.) Ver. :

More information

PTC INSTRUMENTS 2301 Federal Ave Los Angeles CA Phone: Model 500 Automatic Operating Stand Type 3

PTC INSTRUMENTS 2301 Federal Ave Los Angeles CA Phone: Model 500 Automatic Operating Stand Type 3 The Model 500 automatic operating stand provides constant load, controlled rate-of-descent, and application velocity, through a geared electric motor and braking mechanism that alternately lowers the durometer

More information

Dean Pump Self-Priming Chemical Process Pumps

Dean Pump Self-Priming Chemical Process Pumps Bulletin C 1.2.34.7 Dean Pump Self-Priming Chemical Process Pumps php Series HEAD CAPACITY RANGE CHARTS php Self Primer - 2 Pole 3500 RPM 500 CAPACITY M 3 /HR 2900 RPM 50 HERTZ 25 50 75 125 150 400 TOTAL

More information

ALPHA TETRA Stencil Frame System

ALPHA TETRA Stencil Frame System SM814-2 ALPHA TETRA Stencil Frame System DESCRIPTION ALPHA TETRA is a revolutionary patented precision stencil mounting system that eliminates the need for a dedicated frame for each stencil, unlike traditional

More information

TUBE SIGN POST PRODUCTS

TUBE SIGN POST PRODUCTS Western Canada TUBE Products Ltd. SIGN POST PRODUCTS Company Profile With over 100 years of experience on staff and the largest inventory in Western Canada, we have the ability to meet all your sign support

More information

Freescale Semiconductor MMA6222AEG ±20/20g Dual-Axis Medium-g Micromachined HARMEMS Accelerometer

Freescale Semiconductor MMA6222AEG ±20/20g Dual-Axis Medium-g Micromachined HARMEMS Accelerometer Freescale Semiconductor MMA6222AEG ±20/20g Dual-Axis Medium-g Micromachined HARMEMS Accelerometer MEMS Process Review For comments, questions, or more information about this report, or for any additional

More information

Item 404 Driving Piling

Item 404 Driving Piling Item Driving Piling 1. DESCRIPTION Drive piling. 2. EQUIPMENT 2.1. Driving Equipment. Use power hammers for driving piling with specified bearing resistance. Use power hammers that comply with Table 1.

More information

SUPPLY OF ISOLATION AND APPLIANCE VALVES PTS - ISOLATION BALL VALVE

SUPPLY OF ISOLATION AND APPLIANCE VALVES PTS - ISOLATION BALL VALVE PTS - ISOLATION BALL VALVE 2 30.06.17 Issued for Corrigendum#1 AS ADE GS 1 12.04.17 Issued for Tender AS AD GS 0 06.03.17 Issued for Client s Comments AS AD GS Rev. Date Subject of revision Author Checked

More information

SUMMARY STEPS TO CERTIFY ACOUSTIC DUCT SILENCER PERFORMANCE UNDER AMCA INTERNATIONAL S CERTIFIED RATINGS PROGRAM

SUMMARY STEPS TO CERTIFY ACOUSTIC DUCT SILENCER PERFORMANCE UNDER AMCA INTERNATIONAL S CERTIFIED RATINGS PROGRAM AMCA International Member Logo cannot be used in catalogs containing performance data. AMCA International Corporate Identity Logo can only be used by AMCA International, Inc. SUMMARY STEPS TO CERTIFY ACOUSTIC

More information

IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC PURPOSE

IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC PURPOSE INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC 157-20067 1 PURPOSE 1.1 The purpose of this standard is to establish an acceptable standard

More information

Laboratory and Satellite Rodent Housing

Laboratory and Satellite Rodent Housing University of Louisville Institutional Animal Care and Use Committee Policies and Procedures Laboratory and Satellite Rodent Housing Policy: Although strongly discouraged, the IACUC acknowledges that there

More information

CERTIFICATE OF COMPLIANCE FOR RADIOACTIVE MATERIAL PACKAGES

CERTIFICATE OF COMPLIANCE FOR RADIOACTIVE MATERIAL PACKAGES 9319 1 71-9319 USA/9319/B(U)F-96 1 OF 6 2. PREAMBLE a. This certificate is issued to certify that the package (packaging and contents) described in Item 5 below meets the applicable safety standards set

More information

Applying 3M Graphic Films With Comply Performance

Applying 3M Graphic Films With Comply Performance Instruction Bulletin 5.31 Release D, Effective May 2002 Black bar in margin indicates a change Applying 3M Graphic Films With Comply Performance Table of Contents General Information.....................................

More information

BIOME DESIGN TECHNICAL DATA

BIOME DESIGN TECHNICAL DATA March 03, 2006 BIOME DESIGN TECHNICAL DATA 1) Dimensions: Each biome has the following clear interior dimensions: length 6,096 m, width: 3,404 m Interior clearance throughout: 4,268 m (floor to underside

More information

IEC Test Report for mini-box.com Report No. NF September 29, Test Report

IEC Test Report for mini-box.com Report No. NF September 29, Test Report Test Report Report No NF0693-1 Client mini-box.com 4031 Clipper Ct Fremont, CA 94538 Items tested WRAP-BOX-2A-1E Specifications IEC 60529 IP65 Rating Results As detailed within this report Prepared by

More information

for Cold-Formed Steel Framing Products

for Cold-Formed Steel Framing Products Technical Guide for Cold-Formed Steel Framing Products Technical Data in this publication is applicable to the following SFIA Member Company: For a complete directory of SFIA Members who are certified

More information

IAPMO IS PUBLIC REVIEW DRAFT Thrust Blocking for Rubber Gasketed and Solvent Cement Joints

IAPMO IS PUBLIC REVIEW DRAFT Thrust Blocking for Rubber Gasketed and Solvent Cement Joints IAPMO IS 33-2019 PUBLIC REVIEW DRAFT Thrust Blocking for Rubber Gasketed and Solvent Cement Joints IAPMO Standard IAPMO IS 33 2019 Published: Month Year Published by International Association of Plumbing

More information

l DESCRIPTION l FEATURES l LIMITATIONS l TYPICAL APPLICATIONS l MATERIAL SPECIFICATIONS TECHNICAL MANUAL SECTION 2.3 PAGE 1 / 6

l DESCRIPTION l FEATURES l LIMITATIONS l TYPICAL APPLICATIONS l MATERIAL SPECIFICATIONS TECHNICAL MANUAL SECTION 2.3 PAGE 1 / 6 www.ucanfast.com TECHNICAL MANUAL SECTION 2.3 PAGE 1 / 6 l DESCRIPTION The UCAN WAG anchor is a fully threaded torque controlled expansion anchor assembled with a three segment expansion clip. All parts

More information

Section GATE VALVES

Section GATE VALVES Section 02521 PART 1 GENERAL 1.01 SUMMARY This Section includes the furnishing and installation of gate valves for isolation and dead-end service as shown on Plans and as specified herein. 1.02 MEASUREMENT

More information

TO THE DRAWINGS AND THE PROJECT MANUAL

TO THE DRAWINGS AND THE PROJECT MANUAL NO. TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Duncanville I.S.D. Safety, Security & Maintenance Package 2 CLIENT NAME: Duncanville I.S.D. LOCATION: Duncanville, Texas PROJECT NUMBER: 688-05

More information

2 in. 18 Gauge Brad Nailer. User manual

2 in. 18 Gauge Brad Nailer. User manual 8504342 2 in. 18 Gauge Brad Nailer User manual Technical Data Capacity....100pcs Nail length... 15-50mm( 5/8-2 ) Fastener size....18gauge (1.25 1.00mm) Operation pressure 70-110PSI(4.8-7.5bar) Air inlet....1/4

More information

Heat Engine. Reading: Appropriate sections for first, second law of thermodynamics, and PV diagrams.

Heat Engine. Reading: Appropriate sections for first, second law of thermodynamics, and PV diagrams. Heat Engine Equipment: Capstone, 2 large glass beakers (one for ice water, the other for boiling water), temperature sensor, pressure sensor, rotary motion sensor, meter stick, calipers, set of weights,

More information

Cardboard Boat Basics

Cardboard Boat Basics Georgetown Wooden Boat Show 2016 What Floats Your Boat Cardboard Boat Basics 1 Construction Rules (Equal Opportunity) The ENTIRE BOAT must be built of CARDBOARD Only exceptions are the decorations Use

More information

OP CHECKLIST FOR 1D CONSOLIDATION LABORATORY TEST

OP CHECKLIST FOR 1D CONSOLIDATION LABORATORY TEST Page 1 of 5 WORK INSTRUCTIONS FOR ENGINEERS NHB Compiled by : LSS Checked by : GSS Approved by : OP-3-31. CHECKLIST FOR 1D CONSOLIDATION LABORATORY TEST Page 2 of 5 31.0 CHECKLIST ITEMS *(refer to respective

More information