TotalPac X Single interlock Preaction system Electric release
|
|
- Justina Cross
- 5 years ago
- Views:
Transcription
1 DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical and mechanical components of the system are contained in one single unit TOTALPAC X preaction systems are built around the Viking trim using deluge valves model E-3 for 1½" (40 mm) diameter and model E-1 for 2" (50 mm) diameter and up. Electrically operated preaction system use an electric solenoid valve controlled by an approved system control panel with a compatible detection system (provided by others). In fire condition, when the detection condition is satisfied the system control panel energizes the solenoid valve open, causing the deluge valve to open. If any sprinklers have opened, water will flow from the system. If sprinklers have not opened, water will be in the sprinkler system piping when the sprinkler operates. A sprinkler head must open before water flows from the system. Activation of a releasing device alone or operation of a sprinkler alone will sound an alarm but will NOT cause the system to fill with water. All the valves are rated up to a maximum of 250 psi WWP (1724 kpa) max. and are available in the following diameters: 1½" (40 mm) 3" (80 mm) 6" (150 mm) 2" (50 mm) 4" (100 mm) Standard features NEMA 3 or NEMA 4 construction Factory assembled and tested under ISO-9001 standards Prewired to a terminal block Easy and compact installation Viking conventional trim rated at 250 psi (1724 kpa) Galvanized trim piping Serial number for easy reference Wide door for easy access Quarter turn door latches Lockable door to protect against tampering Lifting lugs provided for safe and easy handling Corrosion resistant paint finish Water supply and drain through the bottom center of the unit to avoid freeze-up potential Single drain connection 1 of 12 FM-076D-0-21C
2 Cabinet NEMA 3 Enclosures constructed for either indoor or outdoor use to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow); and that will be undamaged by the external formation of ice on the enclosure. NEMA 4 Enclosures constructed for either indoor or outdoor use to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow, splashing water, and hose directed water); and that will be undamaged by the external formation of ice on the enclosure. NEMA 3X Enclosures constructed for either indoor or outdoor use to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow); that provides an additional level of protection against corrosion and that will be undamaged by the external formation of ice on the enclosure. NEMA 4X Enclosures constructed for either indoor or outdoor use to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow, splashing water, and hose directed water); that provides an additional level of protection against corrosion; and that will be undamaged by the external formation of ice on the enclosure. COMPARISON OF SPECIFIC NON-HAZARDOUS APPLICATIONS Type of enclosure Provide a degree of protection against the following environmental conditions 3 a 3X a 4 4X Incidental contact with enclosed equipment Rain, snow and sleet Hose down and splashing water Corrosive agents Ingress of solid foreign object (circulating or setting airborne dust, lint, fibers, and flyings) b Ingress of solid foreign objects (winblown dust, lint, fibers, and flyings) b a : these cabinet may be ventilated. b : these fibers and flyings are non hazardous materials and are not considered class III type ignitable fibers or combustible flyings. FM-076D-0-21C 2 of 12
3 Sequence of operation (see trim diagram) In a fire condition, when the detection condition is satisfied, system control panel (supplied by others) activates an alarm and energizes normally closed solenoid valve (F1) open. Pressure is released from the priming chamber of the deluge valve (A1) to the open drain manifold faster than it is supplied through the restricted orifice (B3). The Deluge Valve clapper opens to allow water to flow into the system piping and alarm devices, causing the alarm pressure switch (C1) and optional water motor alarm (C2) to activate. When a sprinkler head opens, water will flow from the system. When the deluge valve operates, the sensing end of the PORV (B9) is pressurized, causing the PORV to open. When the PORV opens, it drains the priming water pressure to the priming chamber, preventing the deluge valve (A1) from resetting, even if the open releasing devices close. The deluge valve can only be reset after the system is taken out of service, and the outlet chamber of the deluge valve and associated trim piping is depressurized and drained. Systems hydraulic limitations WARNING The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. Designers should refer to the appropriate NFPA Standards and any other applicable codes for their final design. Also refer to FireFlex Systems Inc. appropriate user manuals and to manufacturer's data sheets for additional details. Systems limitations indicated below are nominal flow limitations. Piping Equivalent Lengths w/o System size Usage Range shut off valve (in.) (gpm) (m.) (ft.) 1½ of 12 FM-076D-0-21C
4 Standard Equipment Deluge valve The Viking Model deluge valve is a quick-opening, differential diaphragm, flood valve with one moving mechanism. The deluge valve is used to control water flow in deluge and preaction sprinkler systems. The valve is held closed by system water pressure trapped in the priming chamber, keeping the outlet chamber and system piping dry. In fire conditions, when the releasing system operates, pressure is released from the priming chamber. The deluge valve clapper opens to allow water to flow into the system piping. Preaction riser check valve The Viking spring loaded In-Line check valve is a general purpose rubber-faced check valve approved for use in fireservice systems. The Spring Loaded In-Line check valve is manufactured with a brass body, brass seat, and a rubberfaced clapper assembly. The Viking Easy Riser Swing check valve is a general purpose rubber-faced check valve approved for use in fire service systems. The valve is for use in preaction system risers. Water supply control valve The water inlet control valve is a supervised, indicating butterfly valve. Purpose of this vale is to manually shutoff the preaction system. Alarm pressure switch The alarm pressure switch monitors the water flow within the sprinkler piping. Should the Deluge Valve clapper opens to allow water to flow into the sprinkler piping. The alarm pressure switch will activate, indicating a water flow signal. POTTER PS10-1A Low air supervisory switch The low pressure switches monitors the pressure within the sprinkler piping should a loss pressure of the air below 12PSI occurs. The pressure switch contacts transfer indicating supervisory signal. Solenoid valve The high pressure solenoid valve is a two-way type with one inlet and one outlet. It is a packless, internal pilot operated valve, suitable for use in releasing water pressure from the priming chamber of Viking deluge valves. The solenoid valve has floating diaphragm construction, which requires a minimum pressure drop across the valve to operate properly. POTTER PS40-1A IN OUT FM-076D-0-21C 4 of 12
5 Optional equipment Shut-off valve & sight glass option The Shut-off Valve & Sight Glass Option is intended to be used for applications where testing of the system operation without filling the sprinkler piping network is desirable and where it is critical that all functions of the preaction system be tested under actual discharge conditions. Shut-off valve (D4) Sight glass Point flashlight here Heater option Heater option is recommended where ambient temperatures can drop below 40 F (4.5 C). The cabinet s electric heater temperature cut-out point is set at 50 F (10 C). The heater option is equipped with a low temperature sensor that will activate a supervisory signal when temperature drops below 40 ±5 F (4.5 ±3 C). Heater option can be ordered in two supply voltage settings: 120Vac-60Hz. 400Watts. 220Vac-50Hz. 400Watts. Warning: TOTALPAC X cabinet is rated to provide freeze protection down to a minimum temperature of 14 F (-10 C). Insulated enclosure (standard with heater option) Insulation is made on foam core 2 thick R13 and have a foilfaced sheathing board composed of a uniform closed cell polyisocyanurate foam core bonded on each side to a triminate foil facer. One side has a foil reflective facer and the other side has a non-reflective foil facer. Low temperature sensor (standard with heater option) The low temperature sensor will close the normally open contact when the temperature drops below 40 F (4,5 C. The sensor will automatically reset to its normal state when the temperature rises above 40 F (4,5 C). Light option Optional fluorescent enclosure light is available for all cabinet configurations. Remote door switch activates the light when the door is opened. Light option can be ordered in two supply voltage settings: 120Vac-60Hz. 220Vac-50Hz. 5 of 12 FM-076D-0-21C
6 Air supply Direct air compressor (Style A ) Used only for the sprinkler piping network of the preaction system. Air supply style "A" includes the air compressor mounted inside the TOTALPAC X cabinet with its supervisory trim and options. Compressors are of the tankless, oiless piston type and are factory piped to the sprinkler system riser, all within the TOTALPAC X cabinet. Air Pressure Maintenance Device (Style B ) Used only for the sprinkler piping network of the preaction system, when an external air supply is provided by others (tank mounted compressor, plant air or dry nitrogen cylinders) and piped to the air inlet port of the unit. Air supply style "B" provides an Air Pressure Maintenance Device (APMD) trim, factory mounted in the TOTALPAC X cabinet. Note: Direct air compressor is available only with NEMA 3, 3X cabinet. Compressors are available in four (4) sizes; 1/6HP 1/3HP 1/2HP 1HP Direct air, external compressor (Style D ) Mainly used with Preaction systems protecting refrigerated spaces and freezers, where a special dry external air supply unit is piped directly to the system riser inside the freezer itself, as shown in NFPA-13. Air supply Style "D" provides only an air supervisory and shut-off trim. Note: The external air supply must be restricted to insure that it cannot replace air as fast as it escapes when a releasing device or sprinkler operates. Air compressor selection Table: H.P. 40 psi 120Vac System capacity (gallon) to Pump to 40 psi in 30 Minutes 220Vac System capacity (gallon) to Pump to 40 psi in 30 Minutes 1/ / / Warning: When air supplies style "B" or "D" is selected, the air supply should be provided and installed by the sprinkler contractor OUTSIDE of the TOTALPAC X cabinet. It is NOT provided with the unit. Compressor Amp rating Compressor Size Amp. Rating at (HP) 120Vac 60Hz Amp. Rating at 220Vac 50Hz 1/6 6.6 A 3.3 A 1/3 6.6 A 3.3 A 1/2 8 A 4 A A 6.2 A FM-076D-0-21C 6 of 12
7 Details & field wiring diagrams Cabinet with main components, shown without door FM-076Z-0-40A 7 of 12 FM-076D-0-21C
8 Trim diagram Components: A1 Deluge valve B1 Priming valve B2 Strainer B3 1/16" Restricted orifice B4 Spring loaded check valve B5 Alarm test valve B6 Flow test valve B7 Drip check valve B8 Drain check valve B9 Pressure operated relief valve (PORV) B10 Emergency release valve B11 Prime pressure water gauge & valve B12 Water supply pressure gauge & valve B13 Clapper check valve C1 C2 D1 D2 D3 F1 Alarm pressure switch Connection to water motor gong (strainer supplied by contractor) Water supply control valve Riser check valve Main drain valve N.C Solenoid Valve 24Vdc FM-076D-0-21C 8 of 12
9 Wirring diagram TBA Waterflow Alarm switch 1 2 heater(optional) Light (optional) 3 4 TBB Low air Sup'v switch Main valve Sup'v switch M Compresseur(optionel) 11 Factory wired N.C. solenoid valve (See table below for details) Low temperature Sup'v switch (optional) Shut-off valve Sup'v switch (optional) Factory wired NOTES: - ALL DEVICES ARE SHOWN IN THEIR NORMAL SUPERVISORY STATE. - DRY CONTACTS RATINGS: PRESS. SWITCHES: 2.0A. 30VDC / 10A. 125/250 VAC SUPV. SWITCHES: 0.5A. 125 VDC /.025A. 250 VAC / 10A 125/250VAC USE ONLY WITH POWER LIMITED CIRCUITS - USE END-OF-LINE DEVICES COMPATIBLE WITH THE RELEASE CONTROL PANEL USED (NOT INCLUDED). SOLENOID VALVE ELECTRICAL RATINGS Viking P/N Description Voltage Watts DC Amps N.C. 24 DVC 10 DC 416mA Pressure Rating 300 psi (2068 kpa) Notes: 1. Solenoid Valve is UL Listed as Fire Protection Special System Water Control Release Service (UL 429A Product category VLTR). 2. Voltage Drop: For proper operation, make sure that voltage at the solenoid valve is at least 85% of nameplate rating. FM-076Z-0-30A 9 of 12 FM-076D-0-21C
10 Dimensions B FACE VIEW S R A = Water inlet diameter B = Sprinkler riser diameter C = Drain diameter Q G SIDE VIEW K DRAIN - SCH.40 GROOVED OUTLET C WATER INLET SCH.40 GROOVED A M E O F D FM-076Z-0-54B L H N X J BOTTOM VIEW M O TOP VIEW V W NN Dimensions are nominal and may vary ±¼". Size A B C D E F G H J K L M N NN O Q R S T U V W X Y 1.5" 2" 1.5" 2" 50" 24.5" 14.5" 74" 11.5" 11" 68" 25" 5.5" 25" 25" 11" 60" 4.75" 6" 9.5" 10.5" 4" 5" 9.5" 7.75" 2" 2" 2" 2" 50" 23" 12" 74" 12" 11" 68" 25" 5" 25" 25" 11" 60" 4.75" 6" 9.5" 10.5" 4" 5" 9.5" 8" 3" 4" 3" 2" 50" 23" 12.5" 74" 8.5" 11" 68" 25" 5.5" 28.5" 22" 11" 60" 4.75" 6" 9.5" 10.5" 4" 5" 9.5" 8.5" 4" 4" 4" 2" 50" 22.5" 12.5" 74" 8" 12" 68" 25" 5.5" 25.5" 25.5" 12" 60" 4.75" 6" 9.5" 10.5" 4" 5" 9.5" 9" 6" 6" 6" 2" 50" 21" 12" 74" 8" 12" 68" 25" 5" 25" 25" 12" 60" 4.75" 6" 9.5" 10.5" 4" 5" 9.5" 9" 4.5" 4.5" 9/16" DIAM. (4 HOLES) 4.5" 4.5" FLOOR ANCHORING TEMPLATE FM-076D-0-21C 10 of 12
11 11 of 12 FM-076D-0-21C
12 1935, Lionel-Bertrand Blvd. Boisbriand QC Canada J7H 1N8 Tel.: Fax: Toll Free: Web: FM-076D-0-21C 12 of 12
N2 BLAST Datasheet Preaction single interlock electric c/w N 2 Blast Nitrogen generating system Remote controlled unit
(System shown is a self contained unit) FireFlex N 2 Blast description The FIREFLEX N2 Blast integrated system consists of an integrated single interlock Electric release preaction automatic sprinkler
More informationTECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE
1 of 10 1. DESCRIPTION (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system
More informationTECHNICAL DATA. Trimpac 257a. September 16, 2013
September 16, 2013 Trimpac 257a 1. DESCrIpTION DESCRIPTION The Viking Double SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-2 and D-2B used with either a Model E or F Deluge Valve (A.1), a Viking
More informationTECHNICAL DATA. Q = C v P S
Preaction 346a 1. Description The 6 Model G-6000P Electric Release Preaction System Riser Assembly can be used as a Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction
More informationTECHNICAL DATA. Q = C v P S
January 6, 2012 Preaction 333a 1. Description Viking supervised Surefire Preaction Systems Utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated Viking G-3000P Valve comes complete
More informationTECHNICAL DATA. Q = C v P S
January 6, 2012 Preaction 348a 1. Description Viking supervised Surefire Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated Viking G-6000P Valve comes complete
More informationTECHNICAL DATA. Q = C v P S
January 6, 2012 Preaction 331a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated
More informationTECHNICAL DATA. Trimpac 251a. Spetember 16, 2013
Spetember 16, 2013 Trimpac 251a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-6 and B-6B is a factory assembled trim package for a double interlocked preaction system with an electric/pneu-lectric release
More informationTECHNICAL DATA OBSOLETE
April 9, 2009 Preaction 326a 1. DESCRIPTION Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilizing the Viking G-4000P Deluge Valve. The small profi le, lightweight,
More informationTECHNICAL DATA. Trimpac 256a. October 31, 2013
October 31, 2013 Trimpac 256a 1. DESCRIPTION The Viking SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-1 and D- 1B used with either a Model E or F Deluge Valve (A.1), a Viking Easy Riser check valve
More informationTECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which
January 27, 2012 307a 1. (Refer to Figures 1-3.) A Viking Non-Interlocked Preaction system utilizes a Viking Deluge Valve to control water flow into system piping equipped with closed sprinklers. Under
More informationTECHNICAL DATA. Q = C v P S
January 6, 2012 Preaction 347a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated
More informationTECHNICAL DATA. Dry 132a. October 1, 2008
October 1, 2008 Dry 132a 1. Description Viking High Pressure (HP) Dry Systems utilize a Viking Model E or Model F Deluge Valve to control the water supply to system piping equipped with closed sprinklers.
More informationTECHNICAL DATA. Trimpac 244a. September 16, 2013
September 16, 2013 Trimpac 244a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-1 and B-1B is a factory-assembled trim package with an electric release module in a metal enclosure. The standard trim normally
More informationTECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13
Page 1 of 13 1. Description The Viking 2 Model G-2000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler
More informationTECHNICAL DATA. Q = C v P S
Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler
More informationTECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY
Page 1 of 13 1. DESCRIPTION The Viking 3 Model G-3000 Dry Valve Riser Assembly is equipped with a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry
More informationTECHNICAL DATA. Q= Cv S
Page 1 of 13 1. DESCRIPTION The Viking 4 inch Model G-4000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry
More informationTECHNICAL DATA. than the water inlet pressure to the concentrate
Foam102a 1. DESCRIPTION The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with 3M foam concentrates. This system consists of a standard wet pipe sprinkler
More informationTECHNICAL DATA. TRIMPAC Model B-5 & B-5B
September 16, 2013 Trimpac 250a 1. DESCRIPTION DEsCRIPTIoN is a factory assembled trim package for a ed an electric/pneumatic release module in a metal enclosure. The standard trim normally required on
More informationTECHNICAL DATA. Trimpac 247a_Euro. September 16, 2013
September 16, 2013 Trimpac 247a_Euro 1. DESCRIPTION DEsCrIpTIoN TRIMPAC Model B-11 LPCB Type 1 is a factory assembled trim package for a single interlocked electric release module in a metal enclosure.
More informationTECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)
Page 1 of 8 1. DESCRIPTION The Viking Model F-1 Deluge Valve is a quick opening, differential diaphragm, flood valve with one moving mechanism. The Deluge Valve is used to control water flow in Deluge
More informationModel DDX-LP Dry Pipe Valve System 8 (200mm) Features. Differential latching clapper-type, lighweight, dependable construction.
Bulletin 335 Model DDX-LP Dry Pipe Valve System 8 (200mm) Bulletin 335 Features 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Differential latching clapper-type, lighweight, dependable construction. Low Air Pressurized
More informationTECHNICAL DATA. Inlet Type Outlet Type OBSOLETE. 4. TECHNICAL DATA Approvals:
February 11, 2005 Deluge Valves 218 a 1. PRODUCT NAME Viking Model F-1 Deluge Valve 8" - Manufactured since 2002 4" & 6" - Manufactured since 2003 2-1/2" & 3" - Manufactured since 2004 2. MANUFACTURER
More informationTECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.
Page 1 of 8 1. DESCRIPTION A Viking Pilot Pressure Regulated Deluge System utilizes a Viking flow control valve to control water flow into the deluge system. The flow control valve must be installed with
More informationWet pipe low flow foam/water system
December 6, 2010 Foam 14a 1. The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with Viking supplied foam concentrates. This system consists of a standard
More informationFireLock NXT Dry Valve. System No. Submitted By Spec Sect Para Location Date Approved Date
The patent-pending Victaulic Series 768 FireLock NXT is a low differential, latched clapper valve that uses a unique direct acting diaphragm to separate system water supplies from dry-pipe sprinkler systems.
More informationFeatures. Model DDX-LP Dry Pipe Valve System 4 (100mm), 6 (150mm) & 165mm Sizes
Bulletin 357 Rev. E Model DDX-LP Dry Pipe Valve System 4 (100mm), 6 (150mm) & 165mm Sizes Bulletin 357 Rev. E Features 1. 2. 3. 4. 5. 6. 7. 8. 9. Differential-type valve, lightweight, dependable construction.
More informationFeatures. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200)
Features 1. Differential latching clapper-type, lightweight, dependable construction. 2. Low Air Pressurized System, psi -to- 2 psi (0,6 bar -to- 1,9 bar) Max 3. Reset externally. Cover removal is not
More informationTECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY PNEUMATIC RELEASE. 1. DESCRIPTION (Refer to Figures 1, 2 or 3.
Page 1 of 8 1. DESCRIPTION A Viking Pilot Pressure Regulated Deluge System utilizes a Viking Flow Control Valve to control water flow into the deluge system. The flow control valve must be installed with
More informationTECHNICAL DATA. Deluge Valves 211a. November 30, 2007 DELUGE VALVE MODEL E-1 ANGLE STYLE 3 (DN80), 4 (DN100) & 6 (DN150)
November 30, 2007 Deluge Valves 211a DESCRIPTION The Viking Model E-1 Deluge Valve is a quick-opening, differential diaphragm, fl ood valve with one moving mechanism. The deluge valve is used to control
More informationTECHNICAL DATA DELUGE VALVE, MODEL F-1 STRAIGHT THROUGH STYLE
Page 1 of 10 1. DESCRIPTION The Viking Model F-1 Deluge Valve is a quick opening, differential diaphragm and flood valve with one moving mechanism. The Deluge Valve is used to control water flow in Deluge
More informationTECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.
Foam 302 a 1. DESCRIPTION (Refer to Figure 1 on page 302 e.) The Viking Low-Flow Foam/Water Proportioning System is a UL Listed and FM Approved system, for use with 3M and Viking brand foam concentrate.
More informationFeatures. Model DDX-LP Dry Pipe Valve System 2 (50 mm), 2½ (65 mm), 3 (80 mm), 76 mm, 4 (100 mm), 6 (150 mm), 165 mm & 8 (200mm) Listings & Approvals
Bulletin 337 Rev. A Model DDX-LP Dry Pipe Valve System 2 (50 mm), 2½ (65 mm), 3 (0 mm), 76 mm, 4 (100 mm), 6 (150 mm), 5 mm & (200mm) Bulletin 337 Rev. A Features 1. Differential latching clapper-type,
More informationFM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate
December 6, 2010 Foam 31a 1. Description With Multiple Pilot Pressure Regulating Foam/Water Deluge Systems Supplied by a Bladder Tank, multiple pilot pressure regulating foam risers can be supplied from
More informationData Sheet Issue A
Features 1. Differential latching clappertype, lighweight, dependable construction. 2. Low Air Pressurized System, 8 psi -to- 26 psi (0,6 bar to- 1,8 bar) 3. Reset externally. Cover removal is not required.
More informationDESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE
February 9, 1998 Foam 101a A BLADDER TANK WITH 1. DESCRIPTION A Wet Pipe Bladder Tank Foam/Water System is a standard wet pipe automatic sprinkler system capable of discharging a foam/water solution automatically
More informationTECHNICAL DATA OBSOLETE
August 2, 2006 Foam 70a 1. DESCRIPTION A Hi-Expansion Foam System is a standard deluge system capable of discharging a foam/water solution automatically through open Hi-Ex Generators. A Hi-Expansion Foam
More informationTECHNICAL DATA. Table 1 - Specifications
Page 1 of 6 1. DESCRIPTION Model A-3 Pilot Operated Pressure Control Valves are factory assembled units. Each unit consists of a Model H-2 Halar coated Flow Control Valve, a Speed Control Valve, a Model
More informationINSTALLATION OPERATION MAINTENANCE
Bermad Electrically Controlled On-Off Deluge Valve Model: 400E-3D INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 1. Safety First BERMAD believes that the safety of personnel working
More informationTECHNICAL DATA Q= C. Table 1 - Specifications
September 25, 2013 Pressure Regulation 537a 1. Description The Model B-3 Pilot Operated Pressure Control Valve is a factory assembled unit. The unit consists of a Model J-2 Halar coated Flow Control Valve,
More informationOBSOLETE. Wet pipe low flow manifold system
June 1, 2008 Foam 15a 1. Description Multiple risers can be supplied from a single proportioning device. A riser manifold is installed with various riser types and sizes that are to supply foam solution
More informationTECHNICAL DATA. Deluge Valves 218a. November 30, 2007 DELUGE VALVE MODEL F-1 STRAIGHT THROUGH STYLE 2-1/2 (DN65) - 8 (DN200)
November 30, 2007 Deluge Valves 218a DESCRIPTION The Viking Model F-1 Deluge Valve is a quick opening, differential diaphragm and fl ood valve with one moving mechanism. The Deluge Valve is used to control
More informationTECHNICAL DATA. Pressure Regulation 531a. April 24, 2009
April 24, 29 Pressure Regulation 531a 1. DESCRIPTION The Viking Regulating Valve is a direct-acting, single-seated, spring-loaded diaphragm valve. When installed as a pilot regulating valve on a Viking
More informationTECHNICAL DATA. Page 1 of 12
Page 1 of 12 1. DESCRIPTION The Viking Regulating Valve is a direct-acting, single-seated, spring-loaded diaphragm valve. When installed as a pilot regulating valve on a Viking Model H or J Flow Control
More informationTECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1
November 30, 1994 534 a 1. PRODUCT NAME VIKING 2" (50mm), 3" (75mm), 4" (100mm), 6" (150mm) 2. MANUFACTURER THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone:
More informationSouth-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS)
South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System Designed for: Dry or Preaction Fire Protection Systems (FPS) 1.0 Description of Work 1.1 The Fire Sprinkler Contractor shall provide
More informationPreaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Electric Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Electric Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description
More informationTechnical Data. UL Listing is based on the following criteria:
Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve with Trim Inch and 6 Inch (DN and DN5) General Description The TYCO DV-5 Deluge Valve with Trim is a diaphragm-style valve that depends upon water
More informationTECHNICAL DATA CAUTION
Page 1 of 12 1. DESCRIPTION The Viking Model C-2 Pilot Pressure Regulating Valve is a direct-acting, single-seated, spring-loaded diaphragm valve. When installed as a pilot regulating valve on a Viking
More informationTECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1
Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a
More informationFM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate
December 6, 2010 Foam 21a 1. Description With Multiple Foam/Water Deluge Systems Supplied by a Bladder Tank, multiple deluge foam risers can be supplied from a single foam concentrate source. Where a bladder
More informationMODEL RCW NON-INTERLOCK PREACTION SYSTEM
0 Airpark Dr. Standish, MI 8658 989-86-58 www.globesprinkler.com Technical Support 989--00 techservice@globesprinkler.com MODEL RCW NON-INTERLOCK PREACTION SYSTEM GENERAL DESCRIPTION The Globe Model RCW
More informationPreaction System with DV-5 Deluge Valve Single Interlock, Supervised Electric Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description
Worldwide Contacts www.tycofire.com Preaction System with DV5 Deluge Valve Single Interlock, Supervised Electric Actuation / thru 8 Inch (DN thru DN00) General Description The TYCO DV5 Supervised Single
More informationNGP-250/500 Nitrogen Generator Quick Start Guide
NGP-250/500 Nitrogen Generator Quick Start Guide Version: A July 2013 Potter Electric Signal Company, LLC 5757 Phantom Dr., Suite 125 P. O. Box 42037 Hazelwood, MO 63042 Phone: (314) 595-6900 Document
More informationInert Air (N2) Systems Manual
INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing
More informationPreaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General
More informationFire Protection Equipment
123456 Fire Protection Equipment #SVL500 Model F Preaction Valves "Automatic" Sprinkler 150 Gordon Drive Exton, PA 19341 USA Tel: (610) 3631400 8006262682 Fax: (610) 5249073 8008586857 www.kiddefire.com
More informationPreaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Dry Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Dry Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General
More informationDESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection
February 9, 1998 Foam 201a 1. DESCRIPTION A Deluge Bladder Tank Foam/Water System is a standard deluge system capable of discharging a foam/water solution automatically through open sprinklers, spray nozzles,
More informationGENERAL DESCRIPTION MODEL RCW DRY SYSTEM CONFIGURATION. Technical Support Airpark Dr. Standish, MI 48658
077 Airpark Dr. Standish, MI 8658 989-8-583 www.globesprinkler.com Technical Support 989-1-00 MODEL RCW DRY SYSTEM GENERAL DESCRIPTION The Globe Model RCW* dry valve is a hydraulically operated external
More informationFireLock NXT Preaction Valve with Series 798 Pneumatic/Pneumatic Actuator
(DOUBLE-INTERLOCKED, PNEUMATIC/PNEUMATIC RELEASE) HANG THESE INSTRUCTIONS ON THE INSTALLED VALVE FOR EASY FUTURE REFERENCE WARNING WARNING Failure to follow instructions and warnings can cause product
More informationDESIGN DATA. Dry 105a. September 5, 2008
September 5, 2008 Dry 105a 1. Description Dry and Preaction Systems require a dependable source of clean dry air under the proper pressure. The air supply must be adequate to restore normal air pressure
More informationData Sheet Issue A
Features 1. Differential-type valve, lightweight, dependable construction. 2. Low Air Pressurized System, 10 psi -to- 26 psi (0,7 bar -to- 1,8 bar). 3. Reset externally.cover removal is not required. 4.
More informationPreaction System with DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description
Worldwide Contacts www.tycofire.com Preaction System with DV5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation /2 thru 8 Inch (DN thru DN200) General Description The DV5 Supervised Single
More informationSpeed control assembly model A-1
Pressure Regulation 533a 1. DESCRIPTION The Viking Speed Control Assembly provides adjustment of the opening speed of Viking Deluge Valves, and adjustment of both the opening and closing speed of Viking
More informationInstructions for Installation, Operation, Care and Maintenance
Model B1 Accelerator with Integral Accelo-Check Bulletin 323 Rev. E Bulletin 323 Rev. E Instructions for Installation, Operation, Care and Maintenance Features 1. Quickens the operation of dry pipe valves.
More informationGW DRY PIPE VALVE INSTALLATION & OPERATION 100mm (4 ) 150mm (6 )
Read in conjunction with Dry Valve Set Schematic (section 7). 1. PRINCIPLE OF OPERATION. Primary functions of the Angus Type D dry alarm valve station: 1.1. To maintain a dry sprinkler pipework system
More informationBUBBLER CONTROL SYSTEM
BUBBLER CONTROL SYSTEM Description: The LDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air
More informationOBSOLETE DESIGN DATA. Foam 301a. February 9, 1998
February 9, 1998 Foam 301a A BLADDE TANK WITH HYDAULICALLY ACTUATED DELUGE CONCENTATE CONTOL VALVE 1. DESCIPTION A Preaction Bladder Tank Foam/Water System is a standard preaction system capable of discharging
More informationMEDICAL EQUIPMENT CATALOG
THE MOST TRUSTED MEDICAL EQUIPMENT IN NORTH AMERICA MEDICAL EQUIPMENT CATALOG Total Components Including Bulk Oxygen Supply, Back up and Delivery Equipment Designs for High Pressure, Liquid or Bulk Applications
More informationWater Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems
Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems Name of Property: Address: Phone Number: Inspector: Contract No.: Date: This Report Covers: Monthly Quarterly Annual Other
More informationTECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4
Page 1 of 5 Telephone: 29-95-9501 Technical Services: 877-8-5 Fax: 29-8-0 Email: techsvcs@vikingcorp.com Model F Dry Valve with Trim Valve Size Part Number 17PTR 175PTR 17PTR Standard Trim Sets include
More informationTECHNICAL DATA CAUTION
Page 1 of 6 1. DESCRIPTION The Viking Model D-2 Accelerator is a quick-opening device, with an integral anti-flood assembly, used to increase the operating speed of a differential type dry pipe valve.
More informationBUBBLER CONTROL SYSTEM
BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air
More informationValve Proving System VDK 200 A S02
Valve Proving System VDK 200 A S02 Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter
More informationValve Proving System VDK 200 A S06*
Valve Proving System VDK 200 A S06* Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter
More informationMODEL RCW DRY SYSTEM VALVE
077 Airpark Dr. Standish, MI 8658 989-86-583 www.globesprinkler.com Technical Support 989-1-2600 techservice@globesprinkler.com MODEL RCW DRY SYSTEM VALVE GENERAL DESCRIPTION The Globe Model RCW* dry valve
More informationHorizontal Bladder Tanks
DATA SHEET Horizontal Bladder Tanks Features UL Listed and FM Approved for use with various ANSUL proportioners and foam concentrates 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationTECHNICAL DATA ACCELERATOR MODEL E-1
Page 1 of 10 1. PRODUCT DESCRIPTION The Viking Model E-1 Accelerator is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating
More informationECS Protector Nitrogen Generator PGEN-30 (PGEN-30E)
ECS Protector PGEN-30 (PGEN-30E) Specifications For use under U.S. Patents 8,720,591, 9,144,700 and 9,186,533 Dimensions (cabinet): 24.5 (W) x 52.5 (H) x 8.5 (D) (622mm(W) x 1,334mm(H) x 216mm(D)) Dimensions
More informationVertical Bladder Tanks
DATA SHEET Vertical Bladder Tanks Features UL Listed and FM Approved for use with various ANSUL proportioners and foam concentrates 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationFireLock NXT Dry Valve. System No. Submitted By Spec Sect Para Location Date Approved Date FIRE PROTECTION PRODUCTS DEVICES
* * * * ME: 248-98-E CSFM: 7770-0531-117 VNIIPO The patent-pending Victaulic Series 768 FireLock NXT is a low differential, latched clapper valve that uses a unique direct acting diaphragm to separate
More informationInstructions for Installation, Operation, Care and Maintenance
Instructions for Installation, Operation, Care and Maintenance Double Interlock Preaction System Type F 8 (200 mm) Size Bulletin 745 Available with 75 psi (2, bar) or 250 psi (7,2 bar) Pneumatic Pressure
More informationInstructions for Installation, Operation, Care, and Maintenance
., Bulletin 728 Rev.E Double Interlock Preaction System 4" (00mm), 6" (50mm) & 65mm Sizes Bulletin 728 Rev.E Instructions for Installation, Operation, Care, and Maintenance 0 PSI (0,7 bar) Pneumatic Supervising
More informationInstructions for Installation, Operation, Care, and Maintenance
Bulletin 737 Rev. B Double Interlock Preaction System - Type D 2" (50mm), 2-1/2" (65mm), 3" (80mm) & 76mm Sizes Bulletin 737 Rev. B Instructions for Installation, Operation, Care, and Maintenance 10 PSI
More informationFIRE SPRINKLER PRODUCTS PRODUCT CATALOG
AGF Manufacturing Inc. FIRE SPRINKLER PRODUCTS PRODUCT CATALOG CAT-AGF_2018 3/18 Reliability, Versatility, Code Compatibility All orders MUST be received by AGF Manufacturing, Inc. in a written format
More informationDouble Interlock Preaction System - Type F 2"(50mm), 2-1/2"(65mm), 3" (80mm) & 76mm Sizes
Instructions for Installation, Operation, Care, and Maintenance 10-26 PSI (0,7 1,8 bar) Pneumatic Supervising Pressure With Electric / Pneumatic Actuation Type F System Bulletin 738 Rev. B Double Interlock
More informationInstructions for Installation, Operation, Care and Maintenance
Bulletin 737 Rev. C Double Interlock Preaction System - Type D 2 (50mm), 2-1/2 (65mm), 3 (80mm) & 76mm Sizes Bulletin 737 Rev. C Instructions for Installation, Operation, Care and Maintenance Available
More informationModel MTB-ASME Horizontal Bladder Tanks
DATA SHEET Model MTB-ASME Horizontal Bladder Tanks Features n UL Listed and FM Approved for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure
More informationAnti-flood device Model B-1
December 4, 2009 Dry Systems 123a 1. DESCRIPTION The Anti-flood Device is required when Viking accelerators are installed on dry systems according to Viking Model E-1 Accelerator Trim Charts. In the SET
More informationSPECIFICATIONS ATTENTION
VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane
More informationI-769P.AC/ELEC.PNEU FireLock NXT AutoConvert Preaction Valve
HANG THESE INSTRUCTIONS ON THE INSTALLED VALVE FOR EASY FUTURE REFERENCE WARNING WARNING Failure to follow instructions and warnings can cause product failure, resulting in serious personal injury and
More informationData Sheet Issue A
Instructions for Installation, Operation, Care and Maintenance Available with 175psi (12,1 bar) or 250 psi (17,2 bar) Rated Solenoid Valve Externally Resettable Clapper One Main Drain 10-26 PSI (0,7-1,8
More informationModel MTB-ASME Vertical Bladder Tanks
DATA SHEET Model MTB-ASME Vertical Bladder Tanks Features n UL Listed for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationTECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION
Page 1 of 6 1. DESCRIPTION The Model B-1 Anti-flood Device is required when Viking accelerators are installed on dry systems according to Viking Model E-1 Accelerator Trim Charts. In the SET condition,
More informationSINGLE VALVE WITH LOW-FLOW BYPASS
CONTROL VALVES Pressure Reducing Valve Sizing Guide Sizing pilot operated reducing valves is not a complicated process. It starts with determining requirements and following these guidelines in valve size
More informationECS Protector Nitrogen Inerting Vent (PAV-WN)
ECS Protector (PAV-WN) U.S. Pat. No. 8,636,023, 9,526,933 and 9,717,935 B2 Specifications Stock Number: Service Pressure: Regulator Setting: System Connection: Temperature Range: Dimensions: Weight: Clear
More informationFIRE PROTECTION PRODUCTS
AGF Manufacturing Inc. FIRE PROTECTION PRODUCTS PRODUCT CATALOG CAT-AGF_V002 1/15 Reliability, Versatility, Code Compatibility AGF Product Catalog Table of Contents COLLECTa ndrain Auxiliary Drains Model
More informationModel MTB-ASME Vertical Bladder Tanks
DATA SHEET Model MTB-ASME Vertical Bladder Tanks Features n UL Listed for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More information