General Requirements of the NEC Advanced Course. Building Officials and Inspectors Educational Association

Size: px
Start display at page:

Download "General Requirements of the NEC Advanced Course. Building Officials and Inspectors Educational Association"

Transcription

1 General Requirements of the NEC Advanced Course Building Officials and Inspectors Educational Association

2 General Requirements -NEC Course Outcome Explain general requirements found in Article 110 of the National Electrical Code (NEC)

3 General Requirements -NEC You will have a better understanding: What is included in the NEC's general requirements The use of listed equipment How interrupting ratings and short-circuit current ratings address fault current The concept of "mechanical execution of work"

4 General Requirements -NEC You will have a better understanding: The importance of field equipment markings, including flash hazard warnings marking of available fault current identification of disconnects

5 General Requirements -NEC You will have a better understanding: labeling of switchboards and panelboards Indoor and outdoor enclosures Spaces for electrical equipment, including working spaces

6 Article 110 includes some of the broadest requirements in the National Electrical Code

7 The scope statement in Section says the article covers general requirements for the examination and approval, installation and use, access to and space about electrical conductors and equipment, enclosures intended for personnel entry and tunnel installation

8 Simply stated Article 110 covers: Approval of Equipment Installation and Use Access and spaces for equipment

9 Section 110.2: Very broad requiring that everything installed under the National Electrical Code must be acceptable to the authority having jurisdiction.

10 Section In itself specifies that conductors required or permitted by the Code are all required to be approved

11 Section 110.3(A) provides a list of eight considerations that should be used in Judging Equipment

12 The Authority Having Jurisdiction can use this list of eight criteria to determine whether or not materials or equipment should be approved.

13 Anyone who is seeking approval from the authority might also use this list to provide information to show that the issues in the list are all addressed somehow with regard to safe application and use of that particular item of equipment

14 The NEC requires that some equipment be listed, such as: Type NM Cable (Section 334.6) Flexible Metal Conduit (Section 348.6) Electrical Metallic Tubing (Section 358.6) All Luminaries (Section 410.6)

15 Some things like conduit straps or staples for cables may not be available as listed products.

16 Authorities Having Jurisdiction will require many items to be listed because they cannot properly evaluate the equipment on the field.

17 Section 110.3(B) Addresses a general requirement that all listed or labeled equipment must be installed in accordance with any instructions that are included in its listing or labeling

18 Section 110.3(B) Instructions that are included in the listing may not necessarily be found on the equipment itself.

19 Section 110.3(B) That may have to be sought from the listing agency by the Authority Having Jurisdiction or by the user.

20 Section 110.3(B) For example Underwriters Laboratory White Book contains a significant amount of information about the identification and use of various kinds of listed electrical equipment

21 Section 110.3(B) Equipment labeling on the other hand is usually readily available and may include a lot of information and instructions that must be followed

22 Section 110.3(B) Such as torque requirements and permitted sizes and types of conductors, as well as other information such as interrupting ratings and short circuit current ratings

23 Sections through address some very general issues that are applied throughout the National Electrical Code

24 Such as: Voltages that are used The requirements for voltage ratings of connected equipment Conductor sizes And Wiring methods that may be used

25 Section Describes conductors and establishes the assumption in the National Electrical Code that conductors will be copper unless specified otherwise

26 Section Describes conductor sizes as being specified in American Wire Gauge (AWG) sizes or in circular mils

27 Section Requires all wiring to be free of short circuits and ground faults, other than as permitted in the Code

28 Section States only the wiring methods that are approved and included in the Code are suitable and actually covered by the National Electric Code

29 Section is a more specific requirement than the previous sections

30 Section addresses interrupting ratings, which are the ratings of equipment intended to interrupt current at fault levels, as opposed to a switch or other device that is only intended to turn a piece of equipment on or off under normal currents

31 The definition of interrupting rating is found in Article 100: The highest current at rated voltage that a device is identified to interrupt under standard test conditions.

32 Equipment intended to interrupt current at other than fault levels may have its interrupting rating implied in other ratings, such as horsepower or locked rotor current

33 Fuses or circuit breakers that do not have adequate interrupting ratings could rupture while attempting to clear a short circuit. Interrupting ratings should not be confused with short circuit current ratings, which are further explained in Section

34 A fault current is excess current (also Called overcurrent) that goes through a circuit because something has gone wrong.

35 It can be one of three things: A short circuit occurs when two or more normal current carrying conductors make unintended contact

36 It can be one of three things: A ground fault occurs when an ungrounded conductor comes into contact with something grounded such as a conduit or the frame of some electrical equipment

37 It can be one of three things: A ground fault occurs when an ungrounded conductor comes into contact with something grounded such as a conduit or the frame of some electrical equipment

38 It can be one of three things: An overload occurs when equipment draws current over its normal rating, or conductors carry more current than their rated ampacity and the current persists for a sufficient length of time that it could cause damage or dangerous overheating

39 Faults

40 Overload

41 To prevent extensive damage from short circuits and ground faults, it is necessary to determine how much current could possibly flow in a circuit, based on the capacity of the source and the amount of impedance in the circuit up to the point of the fault

42 Based on how much current is actually available, equipment can be selected that is capable of interrupting that much fault current, such as a circuit breaker or a fuse. This type of equipment would be required if the intention is to interrupt as fault levels

43 Short circuits and ground faults typically occur because of some kind of damage to a conductor that keeps the insulation from working properly. In either case, a very high current results, because the impedance of the circuit is dramatically lowered

44 Overcurrent protective devices (such as fuses and circuit breakers) should be selected to ensure that the short circuit current rating of the system components is not exceeded should a short circuit or high level ground fault occur

45 Section Addresses the requirement for short circuit current ratings, which are essentially a measurement of the amount of current that can flow through equipment withour causing extensive damage

46 Section Short Circuit Current Rating The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding defined acceptance criteria

47 Section When a short circuit occurs, a particular piece of equipment might be damaged, or parts of it might have to be repaired or replaced, but the damage would not extend significantly beyond the equipment

48 Section The short circuit current rating indicates that the equipment will allow that much current to flow without a catastrophic failure

49 Section Some types of equipment are really only intended to interrupt normal levels of current, such as some toggle switch or contactor for controlling lighting.

50 Section That type of equipment is not required to have an interrupting rating but is usually required to have a short circuit rating

51 Section Requires that the installation be done in a neat and workmanlike manner

52 Section What constitutes neat and workmanlike manner?

53 Section The informational note that follows refers to ANSI/NECA 1, Standard Practices for Good Workmanship in Electrical Contracting as an accepted industry standard

54 Section However while this is certainly a useful standard, following this is not required under the National Electrical Code and even this standard still leaves some room for judgement and opinion

55 Section (A) Requires that unused and unintended openings (such as knockouts in enclosures that may have been knocked out by accident or for a raceway or cable that was never installed) must be put back together to restore the integrity of the enclosure

56 Section (A) If the opening is intended for some purpose (perhaps drainage or mounting) then it is not required to be sealed up.

57 Section (A) The primary purpose of an enclosure is to protect electrical system from external influences, typical things like dirt and water, but also to protect from accidental contact.

58 Section (B) Addresses the integrity of electrical equipment and connections requiring that panel boards and other electrical parts be protected from the work of other trades.

59 Section (B) This section addresses contamination that would interfere with the electrical function of the equipment, but it does not address insignificant levels of contamination.

60 Section (B) For example, the bus bars of a panel board must not be painted or contaminated with various kinds of finish materials that are used during construction. It does not specify how protection is to be provided.

61 Section (B) For example, the bus bars of a panel board must not be painted or contaminated with various kinds of finish materials that are used during construction.

62 Section Requires the marking of the available fault current.

63 Section This fault current marking must: Indicate the date that the fault current calculation was performed.

64 Section This fault current marking must: Be durable enough to withstand whatever environment it is exposed to.

65 Section This fault current marking must: Be revised to indicate the new levels, as modifications are made that affect the maximum available fault current

66 Section The primary reason for this requirement is to facilitate enforcement of the requirements in Sections and to have interrupting ratings and short circuit current ratings that are adequate for the fault current that is available

67 Section This only applies to service equipment in non dwelling units. Although the requirement for interrupting ratings applies to all installations under the National Electrical Code

68 Section The markings are not intended for or adequate for determining the level of arc flash hazard.

69 Section Requires every disconnect to be legibly marked to indicate its use, that is, to indicate what it disconnects.

70 Section If there are multiple switches and multiple pieces of equipment, each switch must be identified to show what equipment it is intended to control or disconnect.

71 Section The one exception to the rule, where a disconnect does not require labeling, is when it s obvious what the switch controls, for example, if the switch is next to a single piece of equipment

72 Section

73 Section Section is similar, also requiring all switchboards and panelboards to have all their circuit devices marked to clearly indicate what circuit they control

74 Section

75 Section Simply identifying circuits as receptacles or lights are not permitted.

76 Section Disconnects must be identified specifically and in a way that distinguishes every circuit uniquely and does not use any conditions or transient occupancy

77 Section Describing the circuit as conference room lights or by a room number is acceptable. Identifying the circuit as Bob s Office is neither permitted or adequate because the person s occupancy of that particular office would be considered transient.

78 Section A general requirement that addresses enclosures for outdoor use and indoor use.

79 Section All enclosures are required to provide protection from incidental contact with the enclosed equipment

80 Section Indoor enclosures are required, at a minimum, to provide protection from falling dirt in addition to protection from whatever other environmental conditions that may be present

81 Section Outdoor enclosures are required to provide some protection from falling dirt, rain, snow and sleet, or even submersion, depending on the exposure.

82 Table Table covers enclosures for equipment rated 600 volts or less and describe what type of external environmental influence each type of enclosure is intended to withstand.

83 Table For example an indoor enclosure in a wet location might need to withstand a hose down for cleaning purposes, if that s something that it would be exposed to.

84 Table This table is valuable for selecting enclosures and for verifying that an appropriate enclosure has been selected. It can be used by the contractor, design professional or authority having jurisdiction

85 Table Table uses the term raintight and rainproof to describe various types of enclosures

86 Table A raintight or watertight enclosure will exclude water or rain

87 Table A rainproof or waterproof enclosure wouldn t necessarily exclude water entirely, but the enclosed equipment can continue to operate succesfully even with a small amount of rain or water entering the enclosure.

88 Section Covers spaces for electrical equipment. It begins with a very general requirement for adequate access and enough working space to permit ready and safe operation and maintenance of all electrical equipment

89 Section In some cases this space may be minimal, just enough to allow a worker to replace, maintain, lubricate, examine or otherwise service equipment

90 Section The general requirements apply to equipment that will be services only after it has been deenergized.

91 Section If the equipment will be serviced, maintained, examined or adjusted while energized, then the applicable section is (A) in which Subsections (1), (2) and (3) describe required minimal dimensions for a three dimensional space.

92 Section Equipment includes nearly all parts of an electrical installation. Article 100 defines equipment as: A general term term, including fittings, devices, appliances, luminaires, apparatus, machinery and the like used as part of or in connection with an electrical installation

93 Section The depth of the working space for energized equipment is described in section (A)(1), based on three conditions: There would be exposed live parts in front of the worker and no live or grounded parts behind

94 Section The depth of the working space for energized equipment is described in section (A)(1), based on three conditions: 1. There would be exposed live parts in front and parts considered to be grounded behind the worker

95 Section The depth of the working space for energized equipment is described in section (A)(1), based on three conditions: 2. There would be exposed live parts in both the front of and behind the worker

96 Section The depth of the working space for energized equipment is described in section (A)(1), based on three conditions: 3. There would be exposed live parts both in front and behind the worker

97 Section The depth required for working space for energized equipment is based on the voltage to ground

98 Section If the voltage to ground is volts, then all three conditions produce the same depth requirement which is 3 feet

99 Section If the voltage is between 150 and 600 volts to ground, then the dimension is greater for condition two 3 feet 6 inches and condition three 4 feet

100 Section Sections and Table (A)(1) cover 600 volts or less. If the voltage is higher than 600 volts, increasing depths for higher voltage are provided by Table (A)

101 Section Table (A) also uses conditions 1,2 and 3 and provides for voltage up to and above 75,000 volts

102 Section (A)(2) addresses the width of the working space to provide enough space for a typical person to stand freely in front of the equipment being worked on

103 Section (A)(2) The minimum width of the working space is the width of the equipment but the width cannot be less than 30 inches wide

104 Section (A)(2) If the equipment is wider than 30 inches, the width requirement equals the width of the equipment. For example if the width of the equipment is 42 inches the width of clear space must also be 42 inches

105 Section (A)(2) If the width of the equipment is less than 30 inches, the minimum width of the working space is still 30 inches.

106 Section (A)(2) The National Electric Code has no requirement that every piece of equipment have its own dedicated, discrete width in front of it, but simply that there be that much width in front of every piece of equipment

107 Section (A)(3) The height of the working space is the height of the equipment but not less than 6 and one half feet

108 Section (B) Once these three dimensional spaces are defined, Section (B) requires that the entire space be kept clear and not used for any kind of storage

109 Section (A)(3) In fact even other parts of the electrical installation are not permitted to occupy the working space, although Section (A)(3) does not allow other electrical equipment above or below the equipment requiring working space to extend up to 6 inches into that working space

110 Section (A)(3)

111 Section (D) Section (D) requires that the working space must be illuminated so work can be done safely and the person working in that space can see what they are doing

112 Section (D) Mandatory illumination is not required to be dedicated to just the working space, to general illumination for the area can be used, but control of the lighting may not be exclusively automatic

113 Section (D) The National Electric Code does not specify a level of illumination but other standards can provide recommendation

114 Section (C)(1) This Section requires at least one entrance of sufficient area for access and egress

115 Section (C)(2) Requires a continuous and unobstructed way of egress travel is subject to different interpretations

116 Section (C)(2) A common interpretation is that it means that the pathway is directly away from the equipment and there are no obstructions, other than a door.

117 Section (C)(2) The National Electric Code does not require or assume that there will be a door. The working space may be part of a larger open area.

118 Section Section requires that for some equipment over 600 volts a means of restricting access to only qualified persons

119 Section (C)(2) When the equipment is over 600 volts the requirement applies to doors within 25 feet of the working space without regard to the ampere rating or physical dimensions of the equipment

120 Review General requirements of the National Electrical Code are included in Article 110, which covers approval, installation and use, access and required space for equipment

121 Review All equipment installed under the National Electrical Code must be approved by the authority having jurisdiction.

122 Review The authority having jurisdiction will prefer that listed equipment be used when possible, because listing means the equipment has been evaluated by an independent agency

123 The National Electric Code addresses the need to interrupt unintended fault current by providing interrupting ratings and short circuit current ratings for equipment

124 Review The National Electric Code also addresses safety through the general requirements that installations must be made in a neat and workmanlike manner

125 Review Also requiring unused openings to be closed up and requiring equipment to be protected from damage from paint or other construction activities

126 Review Equipment must be marked to avoid various hazards, including warnings of flas hazard, marking of available fault current, identification of disconnecting means and accurate labeling of switchboards and panelboards

127 Review National Electrical Code requirements also cover indoor and outdoor equipment enclosures and space requirements for the areas in which equipment is housed.

128 Questions?

(1) Minimum Required. At least one entrance of sufficient area shall be provided to

(1) Minimum Required. At least one entrance of sufficient area shall be provided to (B) Clear Spaces. Working space required by this section shall not be used for storage. When normally enclosed live parts are exposed for inspection or servicing, the working space, if in a passageway

More information

Electrical. OSHA Office of Training and Education 1

Electrical. OSHA Office of Training and Education 1 Electrical OSHA Office of Training and Education 1 Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due

More information

GFCIs and Swimming Pools A Natural Fit

GFCIs and Swimming Pools A Natural Fit GFCIs and Swimming Pools A Natural Fit Swimming Pool Triangle Most of us have seen or read something about the figure commonly known as the fire triangle (oxygen, heat, and fuel), which is a working model

More information

Electrical Safety. Introduction

Electrical Safety. Introduction Electrical Safety 1 Introduction There are four main types of electrical injuries: Electrocution (death due to electrical shock) Electrical shock Burns Falls Around 300 workers were electrocuted in 2008

More information

Residential Swimming pools

Residential Swimming pools City of Republic Community Development Department Residential Swimming pools REVISION DATE: JANUARY 2017 Swimming Pool Safety Definitions: Barrier Requirements: A) Application All swimming pools over 24

More information

Florida Building Code 6 th Edition (2017) Residential. Broward County Edition Loose-leaf Supplement

Florida Building Code 6 th Edition (2017) Residential. Broward County Edition Loose-leaf Supplement Board of Rules and Appeals FBC 6 th Edition (2017)- Residential - Supplement No. 1 January 1, 2018 Florida Building Code 6 th Edition (2017) Residential File removed pages for reference. Broward County

More information

Swimming Pool Requirements

Swimming Pool Requirements Swimming Pool Requirements 8040 S. 6th Street Oak Creek, WI 53154 (414) 766-7000 www.oakcreekwi.org Revised: August 8. 2017 PERMITS A permit from the Inspection Department is required prior to putting

More information

Ground Fault Circuit Interrupter(GFCI) Policy

Ground Fault Circuit Interrupter(GFCI) Policy NewStar Netronics, LLC American Products for the World Ground Fault Circuit Interrupter(GFCI) Policy 3926 East 3 rd Street Tulsa, OK 74112 Phone (918)894-5006 Fax (918)836-9909 tech@newstarnetronics.com

More information

SWIMMING POOL REQUIREMENTS

SWIMMING POOL REQUIREMENTS PERMITS A permit from the Inspection Department is required prior to putting up a permanent pool. A permit is required for permanent pools, such as the following: SWIMMING POOL REQUIREMENTS The pool is

More information

PART I. GENERAL REQUIREMENTS FOR PERMANENTLY INSTALLED POOLS, STORABLE POOLS, OUTDOOR SPAS, OUTDOOR HOT TUBS, OR FOUNTAINS

PART I. GENERAL REQUIREMENTS FOR PERMANENTLY INSTALLED POOLS, STORABLE POOLS, OUTDOOR SPAS, OUTDOOR HOT TUBS, OR FOUNTAINS The overriding concern of Article 680 is to keep people and electricity separated. Some ways in which Article 680 accomplishes this include: References to other articles. Equipment Requirements. Any equipment

More information

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , , ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR 1910.331 335-29 CFR 1926.302, 1926.416, 1926.417 BASIS: The National Safety Council estimates that there are at least 300 deaths

More information

1 of 3 5/5/2014 2:20 PM NFPA STANDARDS DEVELOPMENT SITE FIRST DRAFT REPORT Closing Date: March 05, 2013 Welcome Kimberly Shea! NFPA 70E, Standard for Electrical Safety in the Workplace, 2012 Edition NOTE:

More information

Check with local zoning official for property line distance requirements.

Check with local zoning official for property line distance requirements. RESIDENTIAL POOL PLAN SUBMITTAL GUIDELINES The following guidelines are intended to assist municipal residents with the permit acquisition process with regard to pools, spas and hot tubs for single family

More information

ELECTRICAL SAFETY PROGRAM

ELECTRICAL SAFETY PROGRAM 0. INTRODUCTION 0.1 PURPOSE The purpose of this program is to provide a practical safe working area for employees relative to the hazards arising from the use of electricity. 0.2 SCOPE This program addresses

More information

Management Plan for Electrical Safety ISD #535

Management Plan for Electrical Safety ISD #535 Management Plan for Electrical Safety ISD #535 Health & Safety Office Maintenance Service Building 10 SE 9 ½ Street Rochester, MN 55904 507-328-4507 MANAGEMENT PLAN FOR ELECTRICAL SAFETY Table of Contents

More information

Advances in Low Voltage Motor Control Center (MCC) Technology Help Reduce Arc-Flash Hazards and Minimize Risks

Advances in Low Voltage Motor Control Center (MCC) Technology Help Reduce Arc-Flash Hazards and Minimize Risks Advances in Low Voltage Motor Control Center (MCC) Technology Help Reduce Arc-Flash Hazards and Minimize Risks Selecting the right MCC equipment leads to improved plant safety, helping protect people and

More information

Electrical Safety Program

Electrical Safety Program Safety Manual Page 1 of 53 1. Purpose A. The purpose of the USPL (the Program ) is to provide a practical, safe working environment for USPL employees and contractors regarding the hazards arising from

More information

Recent changes in workplace safety regulations have heightened the awareness of hazards associated with electrical arcs.

Recent changes in workplace safety regulations have heightened the awareness of hazards associated with electrical arcs. Recent changes in workplace safety regulations have heightened the awareness of hazards associated with electrical arcs. The hazard level must be quantified and workers properly protected before entering

More information

Electrical Safety Work Practices

Electrical Safety Work Practices Work Practices I. SCOPE This program covers any SOUTHWESTERN COMMUNITY COLLEGE employee that may work or be exposed to exposed electrical systems: To assure that employees are not exposed to potentially

More information

PART Q CONTROL OF HAZARDOUS ENERGY (LOCKOUT-TAGOUT)

PART Q CONTROL OF HAZARDOUS ENERGY (LOCKOUT-TAGOUT) PART Q CONTROL OF HAZARDOUS ENERGY (LOCKOUT-TAGOUT) WAC Page 296-307-320 Control of hazardous energy (lockout-tagout). 1 296-307-32001 What does this section cover? 1 296-307-32003 When does this section

More information

Selection of Electrical PPE Tables

Selection of Electrical PPE Tables Selection of Electrical PPE Tables Instructions Table 1 - Starting with Table 1, select the task you plan to do (right-hand column) and the condition of the equipment you will be working on, (center column).

More information

ES18 Security Theory/Regulations Answer Schedule

ES18 Security Theory/Regulations Answer Schedule ES18 Security Theory/Regulations Answer Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The marker

More information

DUQUESNE UNIVERSITY LOCKOUT/TAGOUT PROGRAM

DUQUESNE UNIVERSITY LOCKOUT/TAGOUT PROGRAM DUQUESNE UNIVERSITY LOCKOUT/TAGOUT PROGRAM Prepared by: Environmental Health and Safety Department TABLE OF CONTENTS Page Purpose 1 Scope 1 Introduction 2 Regulatory Requirements 2 Protective Materials

More information

Why do I need to do an Arc-Flash Analysis?

Why do I need to do an Arc-Flash Analysis? Why do I need to do an Arc-Flash Analysis? Presented By Tom Norwood for Alexander Nizov, P.E. Principal/Manager Electrical Engineering Division TRAINING INSTITUTE, INC. A SUBSIDIARY OF MEGGER Hazards Analysis

More information

Electrical Safety Program

Electrical Safety Program Electrical Safety Program For Adopted LC-1005 Rev. 06/16 Page 1 I. Introduction As part of Organization s overall safety and health program, an

More information

MISSOURI UNIVERSITY OF SCIENCE & TECHNOLOGY Procedure: 3.6

MISSOURI UNIVERSITY OF SCIENCE & TECHNOLOGY Procedure: 3.6 Procedure This electrical safety procedure structures safety procedures to meet the requirements of the NFPA-70E Standard. The program is designed for qualified employees who occasionally must perform

More information

Safe Schools: A Health and Safety Check

Safe Schools: A Health and Safety Check Name of School: Optional Information Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: Use of Electrical Equipment Self-Inspection Checklist Guidelines: This checklist covers

More information

Lockout / Tag out Program

Lockout / Tag out Program Lockout / Tag out Program Presented by DOSHTI www.doshti.com You will learn Purpose of Lockout- Tag out Requirements for LOTO Types of Hazardous Energy Procedures for LOTO The OSHA Standard for the Control

More information

SWIMMING POOLS CHAPTER 41

SWIMMING POOLS CHAPTER 41 CHAPTER 41 SWIMMING POOLS SECTION E4101 GENERAL E4101.1 Scope. The provisions of this chapter shall apply to the construction and installation of electric wiring and equipment associated with all swimming

More information

2100 ELECTRICAL SAFETY PROGRAM

2100 ELECTRICAL SAFETY PROGRAM 2100 ELECTRICAL SAFETY PROGRAM Document History Version Date Comments 0.1 For Internal Review 1.0 May 13, 2016 Final Version 2.0 May 10, 2017 Annual Review 2.1 July 21, 2017 Formatting changes. Updated

More information

Leader s Guide ERI Safety Videos

Leader s Guide ERI Safety Videos 1419 SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E Leader s Guide ERI Safety Videos SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E This easy-to-use Leader s Guide is provided to assist in conducting a

More information

Electrical Safety Management for Facility / Operations Work Environments

Electrical Safety Management for Facility / Operations Work Environments Page #: 1 of 8 Last Reviewed/Update Date: 3/25/09 Electrical Safety Management for Facility / Operations Work Environments 1. Purpose / Background Purpose: The purpose of this SOP is to describe requirements

More information

Electrical Safety Program February 2, 2016

Electrical Safety Program February 2, 2016 Electrical Safety Program February 2, 2016 1. INTRODUCTION 1.1. Purpose Indiana University Environmental Health and Safety (IUEHS) has developed the Electrical Safety Program to protect employees from

More information

Nottingham Township 909 Sugar Run Road Eighty Four PA (724) Fax (724)

Nottingham Township 909 Sugar Run Road Eighty Four PA (724) Fax (724) Nottingham Township 909 Sugar Run Road Eighty Four PA 15330 (724) 348-5622 Fax (724) 348-8822 Swimming Pool Application Requirements SWIMMING POOL Any structure intended for swimming or recreational bathing

More information

Original Date of Issue: 04/09

Original Date of Issue: 04/09 POLICIES AND PROCEDURES DEPARTMENT: Environmental Health and Safety SUBJECT: Electrical Safety Program Original Date of Issue: 04/09 Reviewed 12/2011 Revised 12/2011 BACKGROUND ELECTRIC SHOCK It is well

More information

Electrical Safety For Managers Updated For E. ElectricalTrainingPro.com

Electrical Safety For Managers Updated For E. ElectricalTrainingPro.com Electrical Safety For Managers Updated For 2018 70E Daryn Lewellyn daryn@electricaltrainingpro.com ElectricalTrainingPro.com 877.393.9901 1 Fatalities From Exposure To Electricity 1992-334 Bureau of Labor

More information

2. The purpose of this program is to achieve the following objectives:

2. The purpose of this program is to achieve the following objectives: Section 16A. Lockout and Tagout Program 1. In the course of their duties, personnel at the TFREC may need to secure controls, switches, and equipment in order to prevent injury caused by the sudden, unexpected

More information

Welding With Arc Welding Equipment

Welding With Arc Welding Equipment Optional Information Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: Welding With Arc Welding Equipment Self Inspection Checklist Guidelines: This checklist

More information

SWIMMING POOL PERMITS ARE ABOUT HEALTH AND SAFETY

SWIMMING POOL PERMITS ARE ABOUT HEALTH AND SAFETY SWIMMING POOL PERMITS ARE ABOUT HEALTH AND SAFETY Swimming Pool Booklet Washington County, Maryland Published 2004 Revised 03/10/05 Revised 02/10/06 Department of Permits & Inspections 80 West Baltimore

More information

Energy Control. Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: cell:

Energy Control. Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: cell: Energy Control Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: 905.577.0303 cell: 905.977.0210 consultant@staffaid.ca www.staffaid.com Safety, Energy Control, Power Lockout & Function Test Procedures

More information

Definitions found in several locations:

Definitions found in several locations: Definitions found in several locations: NFPA 70 - National Electric Code NFPA 70B Recommended Practice for Electrical Equipment Maintenance. NFPA 70E Electrical Safety in the Workplace OSHA 1910 Subpart

More information

LOCKOUT/TAGOUT PROGRAM

LOCKOUT/TAGOUT PROGRAM 0 Appendix C OCCUPATIONAL SAFETY AND HEALTH PROGRAM LOCKOUT/TAGOUT PROGRAM Hazardous Energy Control Lockout/Tagout Program TABLE OF CONTENTS Section Page I. Purpose and Scope. 1 II. Definitions 1 III.

More information

Figure Source:

Figure Source: In the Fall of 2018, EPRI opened a test facility to the public so that they could witness testing at the EPRI swimming pool assessment infrastructure within EPRI s laboratory in Lenox, Massachusetts. Those

More information

ARKANSAS TECH UNIVERSITY FACILITIES MANAGEMENT HEALTH AND SAFETY MANUAL (LOCKOUT/TAGOUT) 30.0

ARKANSAS TECH UNIVERSITY FACILITIES MANAGEMENT HEALTH AND SAFETY MANUAL (LOCKOUT/TAGOUT) 30.0 () 30.0 The purpose of the Energy Control Policy (Lockout/Tagout) is to ensure that before any employee performs any servicing and/or maintenance on machinery or equipment, where the unexpected energizing,

More information

Electrical Safety Management for Research Work Environments

Electrical Safety Management for Research Work Environments Page #: 1 of 8 Last Reviewed/Update Date: 3/15/12 Electrical Safety Management for Research Work Environments 1. Purpose / Background Purpose: The purpose of this SOP is to describe requirements and procedures

More information

Electrical. Version 1.0

Electrical. Version 1.0 This document is intended to provide basic safety guidelines for the Physical Plant Department at Community College of Allegheny County. The information provided in this guide may vary by site. Version

More information

Swimming Pool Installation

Swimming Pool Installation Swimming Pool Installation The following information is provided to assist in the planning and installation of swimming pools and hot tubs within the City of Vandalia, OH. Zoning, Fence and Electric Permits

More information

Preview to the 2018 NFPA 70E, the Standard for Electrical Safety in the Workplace

Preview to the 2018 NFPA 70E, the Standard for Electrical Safety in the Workplace Preview to the 2018 NFPA 70E, the Standard for Electrical Safety in the Workplace Preview to the 2018 NFPA 70E, the Standard for Electrical Safety in the Workplace Technical Committee Members James Dollard,

More information

PERMANENT POOLS. Location

PERMANENT POOLS. Location Community Development Department 211 Walnut Street - PO Box 426 Neenah, WI 54957-0426 Phone: (920) 886-6130 Fax: (920) 886-6129 Web site: www.ci.neenah.wi.us PERMANENT POOLS A pool is any man-made structure,

More information

Standard Operating Procedure #COE-SOP-0001 Chemical Fume Hood Operation

Standard Operating Procedure #COE-SOP-0001 Chemical Fume Hood Operation Standard Operating Procedure # Chemical Fume Hood Operation Facility: NMSU College of Engineering Laboratories Written by: Juanita Miller, Safety Specialist, miljgh@nmsu.edu (575)-646-1292 Scope: This

More information

ELECTRICAL SAFETY PROCEDURE

ELECTRICAL SAFETY PROCEDURE ELECTRICAL SAFETY PROCEDURE 1 Table of Contents 1 PURPOSE... 3 2 PROGRAM COMPLIANCE... 3 3 SCOPE... 3 4 DEFINITIONS... 3 5 RESPONSIBILITES... 3 6 ELECTRICA HAZARDS... 4 7 TRAINING... 4 8 PORTABLE ELECTRICAL

More information

POOL AND HOT TUB/SPA REGULATIONS A BUILDING PERMIT IS REQUIRED BEFORE THE INSTALLATION OF A POOL.

POOL AND HOT TUB/SPA REGULATIONS A BUILDING PERMIT IS REQUIRED BEFORE THE INSTALLATION OF A POOL. CITY OF NEENAH Department of Community Development (Inspection Department) 211 Walnut Street Phone (920) 886-6130 website: www.ci.neenah.wi.us POOL AND HOT TUB/SPA REGULATIONS A BUILDING PERMIT IS REQUIRED

More information

Sizing Enclosures for SCR Power Controllers

Sizing Enclosures for SCR Power Controllers INTRODUCTION Application Note 1002 Sizing Enclosures for SCR Power Controllers Author - George A. Sites, AMETEK HDR Power Systems Most applications for SCR Power Controllers require some type of enclosure.

More information

2012 NFPA 70E: Electrical Safety In The Workplace

2012 NFPA 70E: Electrical Safety In The Workplace ERI Safety Videos Preventing Injuries Through Employee Training 2984 2012 NFPA 70E: Electrical Safety In The Workplace Leader s Guide ERI Safety Videos 2012 NFPA 70E: Electrical Safety In The Workplace

More information

LOCK-OUT/TAG-OUT (LO/TO) SAFETY PROGRAM

LOCK-OUT/TAG-OUT (LO/TO) SAFETY PROGRAM LOCK-OUT/TAG-OUT (LO/TO) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR 1910.147 BASIS: Approximately three million workers in the United States face risks from uncontrolled energy when servicing machinery

More information

Hazardous Energy Control (Lockout-Tagout)

Hazardous Energy Control (Lockout-Tagout) Hazardous Energy Control (Lockout-Tagout) The purpose of this program is to prevent inadvertent operation or energization of machines, equipment, or processes in order to protect employees and establish

More information

2017 NWHA TECHNICAL SEMINAR. Arc Flash Hazard Awareness MIKE BRENDLE LLC

2017 NWHA TECHNICAL SEMINAR. Arc Flash Hazard Awareness MIKE BRENDLE LLC 2017 NWHA TECHNICAL SEMINAR Arc Flash Hazard Awareness WHAT IS ARC FLASH Arc Flash is a short circuit that flashes from one exposed live part to another, or to ground The result is ionized air that creates

More information

Electrical Hazards: Overhead and underground power lines. tools. Ungrounded electrical systems and tools. in wet/damp environments

Electrical Hazards: Overhead and underground power lines. tools. Ungrounded electrical systems and tools. in wet/damp environments ELECTRICAL SAFETY Electrical hazards pose a serious threat to worker safety. Many workers are unaware of the potential electrical hazards present in their work environment which makes them more vulnerable

More information

This training session covers electrical safety for unqualified persons. Unqualified persons are machine operators, operators of powered industrial

This training session covers electrical safety for unqualified persons. Unqualified persons are machine operators, operators of powered industrial This training session covers electrical safety for unqualified persons. Unqualified persons are machine operators, operators of powered industrial trucks, construction workers, and others who are not qualified

More information

LO/TO LOCKOUT/TAGOUT PROGRAM

LO/TO LOCKOUT/TAGOUT PROGRAM LO/TO LOCKOUT/TAGOUT PROGRAM April 2017 CONTENTS Section 1: Introduction...1 Section 2: Purpose... 1 Section 3: Application... 1 Section 4: Definitions... 2 Section 5: Roles and Responsibilities... 4 Section

More information

SAFE-WORK PRACTICES Working On Or Near Energized Electrical Equipment CAT A-1 SOP #4

SAFE-WORK PRACTICES Working On Or Near Energized Electrical Equipment CAT A-1 SOP #4 SUNCOR ENERGY PRODUCTS DISTRIBUTION TERMINAL OPERATING MANUAL STANDARD OPERATING PROCEDURE SAFE-WORK PRACTICES Working On Or Near Energized Electrical Equipment Lifesaving Rules Supporting Document Verify

More information

SECTION 51 NFPA 70E POLICY. Health & Safety Policy and Procedures Manual

SECTION 51 NFPA 70E POLICY. Health & Safety Policy and Procedures Manual SECTION 51 NFPA 70E POLICY Health & Safety Policy and 1. Protection Against Arc Flash A. Policy: An arc flash is a dangerous condition associated with the release of energy caused by an electric arc. An

More information

AMITY TWP POOL REQUIREMENTS

AMITY TWP POOL REQUIREMENTS AMITY TWP POOL REQUIREMENTS Construction In-ground, Above-ground and Storable pools and Spas shall be designed and constructed in conformance with International Swimming Pool & Spa Code (ISPSC) Location

More information

: Electric Power Generation, Transmission, and Distribution. Region IV - OSHA

: Electric Power Generation, Transmission, and Distribution. Region IV - OSHA 1910.269: Electric Power Generation, Transmission, and Distribution Region IV - OSHA Scope This standard covers the operation and maintenance of electric power generation, control, transformation transmission,

More information

CONTINUING EDUCATION FOR WISCONSIN ELECTRICIANS NEC Article Hours

CONTINUING EDUCATION FOR WISCONSIN ELECTRICIANS NEC Article Hours 3 CONTINUING EDUCATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 680 3 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

Arc Flash 101. presented by Arc Flash Blaster LLC

Arc Flash 101. presented by Arc Flash Blaster LLC Arc Flash 101 presented by Arc Flash Blaster LLC ARC FLASH? ARC FLASH INCIDENT STANDARDS AND REGULATIONS Arc flash accidents... 35,000 F Molten Metal Pressure Waves Sound Waves Copper Vapour: (Solid to

More information

Health and Fire Safety Review 2/15

Health and Fire Safety Review 2/15 Health and Fire Safety Review 2/15 1 TABLE OF CONTENTS Page 3 Scope 3 Control of Hazardous Energy (Introduction) 3 Authorized Employee 3 Employer Responsibility 4 Tagout Devices 4 Lockout Devices 5 General

More information

Bulletin Swimming pool, hot tub and spa installations Rules , , , , , and

Bulletin Swimming pool, hot tub and spa installations Rules , , , , , and Bulletin 68-7-11 Swimming pool, hot tub and spa installations Rules 68-000, 68-056, 68-058, 68-064, 68-068, 68-302 and 68-404 Scope (1) Swimming pools - general (2) Grounding & bonding (a) Bonding for

More information

Types 749B and R130 Changeover Manifolds

Types 749B and R130 Changeover Manifolds Instruction Manual MCK-1179 Types 749B and R130 June 2012 Types 749B and R130 Changeover Manifolds TYPE HSRL-749B TYPE 64SR/122 TYPE R130/21 TYPE 749B/21 Figure 1. Changeover Manifolds and Regulator Assemblies

More information

Lighting Contactors. 4.1 UL Rated AC Contactors

Lighting Contactors. 4.1 UL Rated AC Contactors Electrically Held Lighting Contactors.1 Product Description....................................... Application Description.................................... Standards and Certifications................................

More information

Swimming Pool Electrical Safety

Swimming Pool Electrical Safety Swimming Pool Electrical Safety The information contained in this document is intended for informational purposes. Further interest or questions should be directed to the appropriate code or standard,

More information

LOCKOUT-TAGOUT PROGRAM

LOCKOUT-TAGOUT PROGRAM LOCKOUT-TAGOUT PROGRAM Please Note: This material, or any other material used to inform employers/employees of compliance requirements of OSHA standards through simplification of the regulations should

More information

Product Information Report Lockout/Tagout Hazardous Energy Control

Product Information Report Lockout/Tagout Hazardous Energy Control Overview A properly implemented (LOTO) program is designed to protect workers involved in the maintenance and servicing of equipment from the dangerous effects of hazardous energy caused by the unexpected

More information

CONTROL OF HAZARDOUS ENERGY LOCKOUT/TAGOUT PROGRAM

CONTROL OF HAZARDOUS ENERGY LOCKOUT/TAGOUT PROGRAM CONTROL OF HAZARDOUS ENERGY LOCKOUT/TAGOUT PROGRAM 1.0 REGULATORY AUTHORITY Code of Federal Regulations, 29 CFR 1910.147; California Code of Regulations, Title 8, Sections 2320.1 and 3314; CSU, Fullerton

More information

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073 Operating instructions Safety Rope Emergency Stop Switches UK ZB0052 / ZB0053 ZB0072 / ZB0073 7390878 / 02 03 / 2011 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4

More information

SAFETY QUALITY TECHNOLOGY. Guidance on Safe Isolation Procedures

SAFETY QUALITY TECHNOLOGY. Guidance on Safe Isolation Procedures SAFETY QUALITY TECHNOLOGY Guidance on Safe Isolation Procedures Introduction Every year, people working on construction sites suffer electric shock and burn injuries some of which, tragically, are fatal.

More information

MARIPOSA COUNTY LOCKOUT/TAGOUT PROGRAM

MARIPOSA COUNTY LOCKOUT/TAGOUT PROGRAM MARIPOSA COUNTY LOCKOUT/TAGOUT PROGRAM INTRODUCTION Mariposa County ( County ) facilities have equipment and systems that must be deenergized to allow for safe cleaning, repairing, servicing, setting-up,

More information

Gettysburg College. Energy Control Program

Gettysburg College. Energy Control Program Gettysburg College Energy Control Program Adopted October 2009 Reviewed and Updated February 2015 Reviewed and Updated July 2015 I. Energy Control Procedures Table of Contents A. General Lockout Procedures

More information

C&G 2395 Exam Paper June Section A-All questions carry equal marks. Answer all three questions. Show all calculations.

C&G 2395 Exam Paper June Section A-All questions carry equal marks. Answer all three questions. Show all calculations. C&G 2395 Exam Paper June 2013 Section A-All questions carry equal marks. Answer all three questions. Show all calculations. 1. The electrical installation in an industrial unit is scheduled for a periodic

More information

Definitions for swimming pools, fountains, and similar installations in article 680

Definitions for swimming pools, fountains, and similar installations in article 680 Definitions for swimming pools, fountains, and similar installations in article 680 Dry-Niche Luminaire. A luminaire intended for installation in the floor or wall of a pool, spa, or fountain in a niche

More information

D Square Construction LLC

D Square Construction LLC D Square Construction LLC Lock Out-Tag Out (LOTO) and Zero Voltage Verification (ZVV) Process and Plan Energized Work Process and Permit - 1 - Table of Contents 1) Instruction for using Decision Tree Analysis

More information

Swimming Pools, Spas & Hot Tubs Construction requirements for outdoor private swimming pools (in-ground and above-ground), spas and hot tubs

Swimming Pools, Spas & Hot Tubs Construction requirements for outdoor private swimming pools (in-ground and above-ground), spas and hot tubs PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Swimming Pools, Spas & Hot Tubs Construction requirements for outdoor private swimming pools (in-ground and above-ground), spas and hot tubs November December

More information

$ Plan Review Fee when Permit Application is submitted HOT TUBS AND SPAS BUILDING PERMIT APPLICATION. COST: $80.

$ Plan Review Fee when Permit Application is submitted HOT TUBS AND SPAS BUILDING PERMIT APPLICATION. COST: $80. Community Development 1050 W Romeo Rd, Romeoville, IL 60446-1530 (815) 886-7200 Fax #: (815) 886-2724 Email: buildinginspections@romeoville.org HOT TUBS AND SPAS BUILDING PERMIT APPLICATION Application

More information

LOCKOUT / TAGOUT PROGRAM

LOCKOUT / TAGOUT PROGRAM LOCKOUT / TAGOUT PROGRAM Developed in accordance with the OSHA Control of Hazardous Energy Standard, 29 CFR 1910.147 DECEMBER 7, 2017 SKIDMORE COLLEGE 815 NORTH BROADWAY, SARATOGA SPRINGS, NY 12866 Table

More information

SAFETY DIRECTIVE 2.0 DEPARTMENTS AFFECTED. This Administrative Directive shall apply to all Town of Marana departments and employees.

SAFETY DIRECTIVE 2.0 DEPARTMENTS AFFECTED. This Administrative Directive shall apply to all Town of Marana departments and employees. SAFETY DIRECTIVE Title: Control of Hazardous Energy Lock-out/Tag-out/Try-out Issuing Department: Town Manager s Safety Office Effective Date: July 1, 2014 Approved: Gilbert Davidson, Town Manager Type

More information

11/2/2017. Course Objectives. Overview

11/2/2017. Course Objectives. Overview Course Objectives The objective of this CBT module is to insure that personnel receive basic training in electrical safety. Every employee's work involves electricity. This may vary from typical electrical

More information

GENERAL NOTES FOR SWIMMING POOLS AND SPAS

GENERAL NOTES FOR SWIMMING POOLS AND SPAS GENERAL NOTES FOR SWIMMING POOLS AND SPAS 1. Buried Poly Ethylene (PE) pipe gas lines shall be 18 below finish grade or in an approved recessed channel with 14 gauge insulated tracer wire; Galvanized malleable

More information

Norrsken Family Booklet

Norrsken Family Booklet Section 1: Introduction Low Energy Designs produce efficient and effective LED based lighting products for commercial, retail and industry purposes. Each product may contain specific details on its operation

More information

Responsibilities: Effective Date: November Revision Date: May 1, VP, Facilities and Construction Management. Issuing Authority:

Responsibilities: Effective Date: November Revision Date: May 1, VP, Facilities and Construction Management. Issuing Authority: Title: Electric Power Generation, Transmission, and Distribution Procedure Effective Date: November 2005 Revision Date: May 1, 2017 Issuing Authority: Responsible Officer: VP, Facilities and Construction

More information

100 Questions on Electrical Safety Study Guide

100 Questions on Electrical Safety Study Guide 100 Questions on Electrical Safety Study Guide Be advised that only 95 of 100 questions are presented here for the purpose of discouraging cheating on the final exam. 1. Why is electrical safety important?

More information

OSHA Subpart I Tools - Hand & Power

OSHA Subpart I Tools - Hand & Power OSHA Subpart I Tools - Hand & Power 1926.300 General Requirements (b) Guarding (1) When power operated tools are designed to accommodate guards, they shall be equipped with such guards when in use. Guards

More information

Electrical Safety Program

Electrical Safety Program Electrical Safety Program 6300-3.1 Associated OHS Process: General Industry and Construction Safety The master copy of this document resides in electronic format. Printed copies of this document are for

More information

SAINT MARY S COLLEGE OF CALIFORNIA STANDARD HAZARDOUS ENERGY CONTROL PROGRAM INCLUDING LOCKOUT/TAGOUT. Prepared by

SAINT MARY S COLLEGE OF CALIFORNIA STANDARD HAZARDOUS ENERGY CONTROL PROGRAM INCLUDING LOCKOUT/TAGOUT. Prepared by SAINT MARY S COLLEGE OF CALIFORNIA STANDARD 1.1.4 HAZARDOUS ENERGY CONTROL PROGRAM INCLUDING LOCKOUT/TAGOUT Prepared by SAINT MARY S COLLEGE OF CA MORAGA, California KAREN LAURICELLA Original Date: 1 JULY

More information

Electrical Safety Program

Electrical Safety Program Facilities Operations and Development Environmental Health and Safety 1314 Kinnear Road #106 Columbus, OH 43212-1168 614-292-1284 Phone 614-292-6404 Fax www.ehs.osu.edu Electrical Safety Program Prepared

More information

D E L U X E S E R I E S. Your Hot Tub Pre-Delivery Guide D E L U X E

D E L U X E S E R I E S. Your Hot Tub Pre-Delivery Guide D E L U X E Your Hot Tub Pre-Delivery Guide live better feel better D E L U X E Service Center divinehottubsdeluxe.com Toll Free 1-877-483-1606 customerservice @ divinehottubsdeluxe.com divine hot tubs DLX pre-delivery,

More information

Doc No: ELECTRIC Midland Engineering Co., Inc. Initial Issue Date 12/14/15 Safety Management System

Doc No: ELECTRIC Midland Engineering Co., Inc. Initial Issue Date 12/14/15 Safety Management System Revision Page 1 of PURPOSE The purpose is to eliminate unsafe conditions involving electrical equipment and tools, including faulty insulation, improper grounding, loose electrical connections, defective

More information

Piped Air SCBA Refilling System Standard

Piped Air SCBA Refilling System Standard WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Piped Air SCBA Refilling System Standard SCOPE: This specification

More information

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. Table of Contents

More information

Title: NFPA 70E Effective Date: 12/8/2014 Control Number: THG_0053 Revision Number: 1 Date: 10/26/2015 Annual Review Completed: 5/13/2015 NFPA 70E

Title: NFPA 70E Effective Date: 12/8/2014 Control Number: THG_0053 Revision Number: 1 Date: 10/26/2015 Annual Review Completed: 5/13/2015 NFPA 70E Title: NFPA 70E Effective Date: 12/8/2014 Control Number: THG_0053 Revision Number: 1 Date: 10/26/2015 Annual Review Completed: 5/13/2015 CONTENTS NFPA 70E I. INTRODUCTION II. PURPOSE III. SCOPE IV. ENGINEERING

More information

Lockout Tagout Policy

Lockout Tagout Policy Office of Environmental Health & Safety www.moreheadstate.edu/ehs 606-783-2584 Lockout Tagout Policy PURPOSE To establish procedures for the de-energization and isolation of energy sources or the lockout

More information