DWR6-205, DWR16-205, DWR6-206 Safety Pressure Limiters
|
|
- Steven May
- 5 years ago
- Views:
Transcription
1 Issue Datasheet EN Safety Pressure Limiters pplication Safety pressure limiters with mechanical locking (switch lock) are used in steam and hot water plants in accordance with TRD 604, DIN 4751, T.2 for maximum and/or minimum pressure limiting. Maximum pressure monitoring The control circuit is interrupted when the value exceeds the set limit. Unlocking using tools is only possible after the pressure has been reduced. pproved by TÜV (German ssociation for Technical Inspection) for maximum pressure monitoring, ID: Minimum pressure monitoring The control circuit is interrupted when the value falls below the set limit. Unlocking using tools is only possible after the pressure has been increased. pproved by TÜV for minimum pressure monitoring, ID: Content Page Important Information Regarding Product Safety...2 Item...3 Technical Data...3 Dimensions...4 Connection...4 Mounting...5 Removal...5 Installation...6 Setting the pressure limits...7 Unlocking...7 Änderungen vorbehalten - Contents subject to change - Sous réserve de modifications - Reservado el derecho a modificación - Wijzigingen voorbehouden - Con riserva di modifiche - Innehåll som skall ändras - Zmeny vyhradené - Změny vyhrazeny - Zmiany zastrzeżone - Возможны изменения - változtatások jogát fenntartjuk - Kieback&Peter GmbH & Co. KG Tempelhofer Weg 50, Berlin/Germany Telefon: , Telefax: info@kieback-peter.com
2 Datasheet EN Issue Important Information Regarding Product Safety Safety Instructions This data sheet contains information on installing and commissioning the product "DWR6-205, DWR16-205, DWR6-206". Each person who carries out work on this product must have read and understood this data sheet. If you have any questions that are not resolved by this data sheet, you can obtain further information from the supplier or manufacturer. If the product is not used in accordance with this data sheet, the protection provided will be impaired. pplicable regulations must be observed when installing and using the device. Within the EU, these include regulations regarding occupational safety and accident prevention as well as those from the VDE (ssociation for Electrical, Electronic & Information Technologies). If the device is used in other countries, it is the responsibility of the system installer or operator to comply with local regulations. Mounting, installation and commissioning work on the devices may only be carried out by qualified technicians. Qualified technicians are persons who are familiar with the described product and who can assess given tasks and recognize possible dangers due to technical training, knowledge and experience as well as knowledge of the appropriate regulations. Legend WRNING Indicates a hazard of medium risk which can result in death or severe bodily injury if it is not avoided. CUTION Indicates a hazard of low risk which can result in minor or medium bodily injury if it is not avoided.! CUTION Indicates a hazard of medium risk which can result in material damage or malfunctions if it is not avoided. NOTE Indicates additional information that can simplify the work with the product for you. Notes on Disposal For disposal, the product is considered waste from electrical and electronic equipment (electronic waste) and must not be disposed of as household waste. Special treatment for specific components may be legally binding or ecologically sensible. The local and currently applicable legislation must be observed. Page 2 / 8
3 Issue Datasheet EN Item DWR6-205 DWR DWR6-206 Safety pressure limiter for maximum pressure monitoring, range 0,5..6 bar Safety pressure limiter for maximum pressure monitoring, range bar Safety pressure limiter for minimum pressure monitoring, range 0,5..6 bar Technical Data Function Pressure limiting with mechanical locking DWR for maximum pressure monitoring DWR for minimum pressure monitoring Certification mark pproved VdTÜV pressure 100/1, issue Certificate number. DWR..205 ID: ; ID: DWR..206 ID: ; ID: Output 1-pole switch, locking Switching capacity 8 (5), 250V C Setting range DWR ,5..6 bar, sealing device can be retro-fitted DWR bar, sealing device can be retro-fitted DWR ,5..6 bar, sealing device can be retro-fitted Switching difference DWR6-205 approx. 0,4 bar (corresponds to the pressure change for unlocking) DWR approx. 0,8 bar (corresponds to the pressure change for unlocking DWR6-206 approx. 0,3 bar (corresponds to the pressure change for unlocking) Operating pressure DWR6-205 max. 16 bar DWR max. 25 bar DWR6-206 max. 16 bar mbient temperature -25 C +70 C Medium temperature max. 70 C t higher medium temperatures, suitable measures must be taken to ensure that the maximum temperature at the safety pressure limiter is not exceeded. lso ensure that at low temperatures, condensate cannot form in the sensor or switch housing. Sensor Stainless steel Pressure connection Male thread G1/2 (pressure gauge thread) according to DIN Switch housing Die-cast aluminium Installation position Vertical and horizontal Degree of protection IP54 Weight 0,45 kg Page 3 / 8
4 Datasheet EN Issue Dimensions 4,6 46 ±2 9,4 20 ca ,5 DWR6-205: 30 DWR16-205: 24 DWR6-206: 30 G1/ ,5 Connection DWR6-205, DWR DWR DWR6-205 DWR If the pressure reaches the set pressure limit, the output contact switches from terminals 3 1 to 3 2 and locks. DWR6-206 If the pressure sinks to the set limit, the output contact switches from terminals 3 2 to 3 1 and locks. Page 4 / 8
5 Issue Datasheet EN Mounting WRNING Danger of death by electrocution. Mount or remove only when power is switched off.! The safety pressure limiter must be mounted in an accessible location without vibrations in compliance with the technical data. The safety pressure limiter can be mounted directly either vertically or horizontally on the pipeline (pressure gauge thread G1/2), or to an even surface with 2 screws (Ø 4 mm). For direct pipeline mounting: secure the pressure limiter only to the hexagon screw on the pressure connection with a wrench. CUTION Do not use the housing or the plug as a lever arm. The pressure connection is to be sealed with a suitable sealing material. If a flat gasket is used, the supplied centering screw is to be screwed into the female thread of the pressure connection, see diagram. Removal WRNING Danger of death by electrocution. Mount or remove only when power is switched off. Page 5 / 8
6 Datasheet EN Issue Installation The device is connected via the right angled plug of the safety pressure limiter. Remove the retaining screws from the right angled plug and remove the plug insert (3) from the plug housing (4). Insert a screwdriver into the slot and press down. Insert the cable through the cable gland in the plug housing (4) and connect to the plug insert (3). Press the plug insert back into the housing. Place the supplied plug seal (2) onto the device connection (1) and secure the right angled plug with the retaining screw. Tighten the cable gland. The cable outlet can be rotated 90. Rotate the plug insert ( 3) and insert into the plug housing (4). Page 6 / 8
7 Issue Datasheet EN Setting the pressure limits! CUTION The safety pressure limiter may only be set by qualified technicians, e.g. the commissioning technician. Before setting, loosen the safety screw above the calibration scale by approx. 2 turns (unlock). The safety pressure limiter is set at the adjusting spindle using a screw driver. The exact limit value is set with a pressure gauge. The scale on the pressure limiter serves as a nominal value. fter setting, re-tighten the safety screw (lock). Unlocking If the pressure reaches the set limit, the output contact switches and locks. Unlocking can occur only when the pressure sinks below the limit value (DWR6-205, DWR16-205) or is exceeded (DWR6-206). The change of pressure required to switch back can be found in the technical data; see the section on switching difference. To unlock, press the release button (a red dot on the side of the scale, see diagram). Page 7 / 8
8 Datasheet EN Issue Page 8 / 8
ATH2070 Safety Temperature Limiter. Application. Product Description. ATH2070 Safety Temperature Limiter
Issue 2013-03-18 Datasheet 1.10-43.823-01-EN pplication The safety monitors/limiters are DIN type-tested and are used for monitoring and limiting the temperature in heating and ventilation system pipelines.
More informationInstruction Manual Contact Pressure Vacuum Gauge
MS10 Instruction Manual Contact Pressure Vacuum Gauge Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance
More informationInstruction Manual Contact Pressure Gauge
MS11 Instruction Manual Contact Pressure Gauge Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance 7.
More informationPressure Switches Application Guideline
Pressure Switches Application Guideline Product Overview The Fema Pressure Switch product portfolio provides devices suitable for many applications. The portfolio contains Special functions and equipment
More informationMounting and Operating Instructions EB 2172 EN. Series 43 Temperature Regulators. Type 43-5 and Type Type Type 43-6
Series 43 Temperature Regulators Type 43-5 and Type 43-7 Type 43-6 Type 43-6 Type 43-7 with flanged valve body, DN 32 to 50 Type 43-5 Type 43-7 with welding ends Mounting and Operating Instructions EB
More informationMechanical Pressure Switches for overpressure, vacuum pressure and differential pressure
Mechanical Pressure Switches for overpressure, vacuum pressure and differential pressure Switching range: -250 +100 mbar, 1 16 mbar to 16 63 bar Temperature: max. 70 C Material: Copper, brass, stainless
More informationInstruction Manual Differential Pressure Transmitter
DE61 Instruction Manual Differential Pressure Transmitter Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance
More informationQPL... Pressure Switches. Siemens Building Technologies HVAC Products
7 221 Pressure Switches QPL... The pressure switches are used for monitoring gas or air pressures. When the pressure falls below the switching point, the associated electrical circuit will open or switch
More informationMechanical Pressure Switches for overpressure, vacuum pressure and differential pressure
Mechanical Pressure Switches for overpressure, vacuum pressure and differential pressure Switching range: -250 +100 mbar, 1 16 mbar to 16 63 bar Temperature: max. 70 C Material: Copper, brass, stainless
More informationMechanical Pressure Switches for overpressure, vacuum pressure and differential pressure
Mechanical Pressure Switches for overpressure, vacuum pressure and differential pressure Switching range: -250 +100 mbar, 1 16 mbar to 16 63 bar Temperature: max. 70 C Material: Copper, brass, stainless
More informationPROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road
PROPORTIONING VALVE Model 150 INSTRUCTION MANUAL March 2017 IMS Company 10373 Stafford Road Telephone: (440) 543-1615 Fax: (440) 543-1069 Email: sales@imscompany.com 1 Introduction IMS Company reserves
More informationType 2000 INOX. Quickstart. English Deutsch Français. 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies
Type 2000 INOX 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies Quickstart English Deutsch Français Contents 1 QUICKSTART... 2 2 CONTACT ADDRESS... 2 3 INTENDED USE...
More informationCompact pressure switches for gas and air
Compact pressure es for gas and air / 5.0 Printed in Germany Edition 0.8 Nr. 9 544 6 Technical description The pressure is an adjustable compact pressure according to EN 854 for combustion plants. The
More informationBourdon tube pressure gauge for diaphragm seals
Bourdon tube pressure gauge for diaphragm seals and switch function, Type series BR42.. Features Bourdon tube pressure gauge for diaphragm seal and switch function Nominal range -1 3 bar to -1 15 bar,
More informationMechanical Pressure Switches for overpressure, vacuum pressure and differential pressure
Mechanical Pressure Switches for overpressure, vacuum pressure and differential pressure Switching range: -250 +100 mbar, 1 16 mbar to 16 63 bar Temperature: max. 70 C Material: Copper, brass, stainless
More informationPressure Switch Pressure Limiter
Assembly and Operating Instructions Pressure Switch Pressure Limiter Basic models Additional functions DCM......-203 DNM......-205 DNS......-206 VCM...,VNM......-307 VNS......-213 Important safety information!
More informationInstruction Manual Differential Pressure Transmitter
DE13 Instruction Manual Differential Pressure Transmitter Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance
More informationPull-rope emergency stop switch Type HENEX and SEGEX OPERATING INSTRUCTIONS
Pull-rope emergency stop switch Type OPERATING INSTRUCTIONS Legal Notice (Translation of the original) Document No.: 94.058 816.191 Pull-rope emergency stop switch, Type HENEX and SEGEX Product number:
More informationType Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.
2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies We reserve the right to make technical changes without notice. Technische Änderungen vorbehalten. Sous réserve de modifications techniques.
More informationInstallation and Operating Instructions Bypass Flow Meter DST
Installation and Operating Instructions Bypass Flow Meter DST DST_gb_A4_1.0.doc Version 1.0 1 von 10 Contents 1. Foreword... 3 2. Safety... 3 2.1. Symbol and meaning... 3 2.2. General safety directions
More informationMounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25
Self-operated Pressure Regulators Differential Pressure Regulators (opening) Type 42-20 Type 42-25 Type 42-20 Differential Pressure Regulator Type 42-25 Differential Pressure Regulator Mounting and Operating
More informationInstallation, operating and maintenance Instructions for Seemag bypass level indicator
Issue: S Date: 05-09-14 Type G35 General information The Seetru bypass magnetic level indicator, abbreviate SEEMAG, serves to show the filling level of fluids in tanks, basins, tubes etc. The Seemag operates
More informationCAST IRON SAFETY VALVE TYPE 6301
CHARACTERISTICS The 6301 safety valve is dedicated to protect the equipment from potential overpressure. This is an automatic device that closes when the pressure conditions are back to normal. It is a
More informationINSTRUCTION MANUAL Pressure Relief Device LPT
INSTRUCTION MANUAL Pressure Relief Device LPT 5COV475800 LPT REV00 CONTENT: 1 SAFETY 1.1 Safety instructions 2 1.2 Specified applications 2 1.3 Safety notes on the equipment operation 2 2 PRESSURE RELIEF
More informationSolenoid gas valve. The solenoid gas valve is also applicable as a main gas valve Pilot gas valve for forced draft burners
7 634 VGS1... with AGA67 connector VGS2... with AGA67 connector Solenoid gas valve VGS The solenoid gas valve is also applicable as a main gas valve Pilot gas valve for forced draft burners The VGS and
More informationPressure switch with bourdon tube
Pressure switch with bourdon tube for plants requiring special supervision,type series BN4 Features Pressure switch with bourdon tube for plants requiring special supervision, Nominal ranges -1...0 bar
More informationOperating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073
Operating instructions Safety Rope Emergency Stop Switches UK ZB0052 / ZB0053 ZB0072 / ZB0073 7390878 / 02 03 / 2011 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4
More informationSafety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC
05 Elster GmbH Edition 0.5 Translation from the German 058 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Linear flow control VFC Linear flow control with actuator IFC Contents
More informationHydraulic hand spindle pump Models CPP1000-M, CPP1000-L
Calibration Hydraulic hand spindle pump Models CPP1000-M, CPP1000-L WIKA data sheet CT 91.05 for further approvals see page 2 Applications Calibration service companies and service industry Calibrations
More informationMechanical Pressure Switches for overpressure, vacuum pressure and differential pressure
Mechanical Pressure Switches for overpressure, vacuum pressure and differential pressure measuring monitoring analysing Switching range: -250 +100 mbar, 1 16 mbar to 16 63 bar Temperature: max. 70 C Material:
More informationType /2-Way Globe Valve 3/2-Wege-Geradsitzventil Vanne à siège droit 3/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation
3/2-Way Globe Valve 3/2-Wege-Geradsitzventil Vanne à siège droit 3/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation We reserve the right to make technical changes without notice.
More informationEG15*... SERIES. SOLENOID GAS VALVES WITH 1/2 CONNECTION AND OPERATING PRESSURE UP TO 500 mbar DESCRIPTION
EG15*... ERIE OLENOID G VLVE WITH 1/2 CONNECTION ND OPERTING PREURE UP TO 500 mbar DECRIPTION This series of solenoid gas valves are of normally closed type, suitable for civil and industrial applications,
More informationSafety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC
07 Elster GmbH Edition 06.7 Translation from the German 058 D GB F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Linear flow control VFC Linear flow control with actuator IFC
More informationLED 14W POLO BULKHEAD WITH MICROWAVE SENSOR
INTRODUCTION The LED 14W POLO Bulkhead is a modern lowcost and energy efficient fitting ideal for domestic and utility applications. SPECIFICATION LED 1150lm IP54 220-240V IK09 4000K 50/ 60Hz >82 Ra 14W
More information* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22.
*09005087* DB_BA_EN_ME01_S Rev.A 12/16 *09005087* d e v e l o p i n g s o l u t i o n s Data Sheet and Operating Manual ME01 Digital manometer Table of Contents ME01 ## # 87 # HL S#### Dust explosion protection
More informationDifferential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN
Differential Pressure Regulator Type 45-6 Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN Edition March 2008 Contents Contents Page 1 Design and principle of operation...................
More informationMechanical Pressure Switches for overpressure, vacuum pressure and differential pressure
Mechanical Pressure Switches for overpressure, vacuum pressure and differential pressure measuring monitoring analysing Switching range: -250 +100 mbar, 1 16 mbar to 16 63 bar Temperature: max. 70 C Material:
More informationPressure regulator for water
Pressure regulator for water rass version with VGW and international drinking water approvals Stainless steel version with VGW approval Compact plastic version Manometer port at pressure output The water
More informationPressure switch and Thermostat CAS
Data sheet Pressure switch and Thermostat CAS The CAS Series consists of a series of pressure controlled switches and temperature controlled switches. In this series, special attention has been given to
More informationMounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator
Self-operated Pressure Regulators Type 2357-31 Pressure Build-up Regulator with safety function and integrated excess pressure valve Type 2357-31 with non-return unit at port C Ports A and B with soldering
More informationMounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2
Self-operated Pressure Regulator Pressure Reducing Valve Type M 44-2 Type M 44-2, connection G 1 4, K VS = 0.15 Type M 44-2, connection G 1, K VS = 6 Fig. 1 Type M 44-2 Pressure Reducing Valve Mounting
More informationNote: the lock-out circuit must be in accordance with Section 8.7 of DIN/VDE Twin thermostats ATH.-SW-2020 ATH.-SW-2070 ATH.
M. K. JUCHHEIM GmbH & Co Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 3603 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-60 E-mail: mail@jumo.net Internet: www.jumo.net
More informationSeated valves VRB 3, VRG 3
Data sheet Seated valves VRB 3, VRG 3 Description VRB, VRG valves provide a quality, cost effective solution for most water and chilled applications. These valves may be used with glycol concentrations
More informationLTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc.
LTB013EN Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc. to IECEx scheme Subject to technical modification Bachofen AG Ackerstrasse 42
More informationBSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions
1843950/3 IM-P184-03 ST Issue 3 BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation
More informationLimit switches OsiSense XC Special For material handling applications, type XC1 AC
Presentation For material handling applications, type XC C b XC C with slow break contacts v With head for linear movement () 00_ 00_ 000_ Page / 00_ 00_ XCC XCC Page / XCC XCC / General characteristics
More informationATS430 turbidity sensor Retractable insertion assembly
A MEASUREMENT & ANALYTICS INSTRUCTION ATS430 turbidity sensor Retractable insertion assembly Measurement made easy 1 Introduction This publication details installation procedures for the retractable insertion
More informationActuating elements for ComEx
Description A large number of variants and versions of actuating elements are available for the ComEx control and indicator units. All actuating elements are made of high-quality thermoplastic and conform
More information2-Port Seat Valves with Flange, PN 16
4 40 2-Port Seat Valves with Flange, PN 6 VVF4... Grey cast iron EN-GJL-250 valve body DN 50...50 k vs 9...00 m /h Can be equipped with SQX- electromotoric or SKD...-, SKB...- or SKC...- electrohydraulic
More informationThin pressure gauge. G401-W Series. Symbol Descriptions. A Connection A A. B Pressure display [MPa] P04 0 to 0.4MPa P10 0 to 1.
Thin pressure gauge G401-W Series Thin, compact design ideal for incorporating devices. Suitable for filter regulator, regulator, and pressure switch (P4000-W). onnection: O ring seal, set screw G401-W
More informationPressure Measurement Single-range transmitters for general applications
Siemens A 207 Overview Application The SITRANS P Compact pressure transmitter is designed for the special requirements of the food, pharmaceutical and biotechnology industries. The use of high-grade materials
More informationFPD20 Series. Gear wheel flow sensor
. FPD20 Series Gear wheel flow sensor Series FPD20-2 - M-5455/0315 Series FPD20 Table of contents page 0 About this operating manual... 4 1 Device description... 5 1.1 Intended use... 5 1.2 Exclusion of
More informationSafety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14
15 Elster GmbH Edition 7.15 Translation from the German 519 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Solenoid valve for gas VG VG 15/1 Contents Solenoid valve for gas
More information2-port seat valves PN25 with externally threaded connections
4 379 2-port seat valves PN25 with externally threaded connections VVG55.. Valve body bronze CC491K (Rg5) DN 15...25 (½...1 ") kvs 0.25...6.3 m3/h Stroke 5.5 mm Sets of ALG.. with threaded and ALS.. with
More informationC-Flow Coriolis Mass Flow Meters
Coriolis Mass Flow Meters Ready for Take Off The New Compact C-Flow Küppers Elektromechanik GmbH The C-Flow The C-Flow Coriolis Mass Meters consist of two components: KCE Transmitter KCM Transducer 2 KEM
More informationPressure Switches. Assembly and Operating Instructions. Important safety information!
Assembly and Operating Instructions Pressure Switches Basic models Additional functions DCM... -203-574 DNM... -205-575 DNS... -206-576 VCM..., VNM... -307-577 VNS... -213-513 DDCM... -217...-563 Ex-...
More informationSafety. Operating instructions Solenoid valve for gas VG 10/15 VG 65 DANGER. Contents WARNING CAUTION. Changes to edition 11.14
2 Elster GmbH Edition. Translation from the German 22 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Solenoid valve for gas G / G Contents Solenoid valve for gas G / G....
More informationBall Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65
Data Sheet 819346-02 Issue Date: 05/17 Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300, 50, 65 UNA 45hl MAX, UNA 46hl MAX, UNA 46Ahl MAX UNA 45v MAX with cover for mounting electrode
More informationMounting and Operating Instructions EB EN. Type Supply Pressure Regulator. with increased air capacity
Type 4708-45 Supply Pressure Regulator with increased air capacity Translation of original instructions Mounting and Operating Instructions EB 8546-1 EN Edition March 2016 Note on these mounting and operating
More informationManual Actuated Boiler Blowdown Valves
Manual Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Operation 5. Maintenance 6. Spare parts p.1 1. Safety
More informationGasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-300-VEF MBC-700-VEF MBC-1200-VEF
GasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-00-VEF 7.03 Max. operating pressure 30 mbar Compact design High flow values Low weight Low power consumption
More informationCertified according to DIN EN ISO 9001 Technical Datasheet TRICOR Series Mass Flow Meters
www.kem-kueppers.com info@kem-kueppers.com Certified according to DIN EN ISO 9001 Technical Datasheet TRICOR Series Mass Flow Meters Description The Tricor Mass Flow Meters measure simultaneously mass
More informationHydraulic comparison test pump Models CPP1000-X, CPP1600-X
Calibration Hydraulic comparison test pump Models CPP1000-X, CPP1600-X WIKA data sheet CT 91.12 for further approvals see page 2 Applications Calibration service companies and service industry Maintenance
More informationMagnetic level switch type MR783 Instruction Manual
Magnetic level switch Magnetic level switch type MR783 1. DESCRIPTION page 3 1.1 Operation page 3 1.2 Application page 3 1.3 Description page 3 2. SPECIFICATIONS page 3 2.1 Service Conditions page 4 2.2
More informationINSTRUCTION MANUAL BOURDON TUBE PRESSURE SWITCHES
BOURDON TUBE PRESSURE SWITCHES WEATHERPROOF: SERIES BW EXPLOSIONPROOF: SERIES BAX B B A A A pressure attachment A pressure attachment B cable entry B cable entry WEIGHT 2 kg dimensions in mm WEIGHT 3,7
More informationPower Valve: Precision Regulator. High precision, large capacity relief regulator
Power Valve: Precision Regulator Series VEX High precision, large capacity relief regulator port large exhaust capacity pressure reducing valve which utilizes a nozzle flapper mechanism available as air
More information2-Port Seat Valves with Flange, PN 16
4 45 2-Port Seat Valves with Flange, PN 6 VVF45... dular cast iron EN-GJS-400-5 valve body DN 50...50 k vs 9...00 m /h Can be equipped with SKB...- or SKC...- electrohydraulic actuators Use For use in
More informationOPTIBAR P 1010 C Technical Datasheet
Technical Datasheet Pressure transmitter with recessed diaphragm for general applications Wide variety thanks to modular design Measuring ranges up to 250 bar / 3750 psi High overload and temperature stability
More informationOperating Instructions. Ball valve fitting according to ZB For pressure transmitter VEGABAR 82. Document ID: 50027
Operating Instructions Ball valve fitting according to ZB 2553 For pressure transmitter VEGABAR 82 Document ID: 50027 Contents Contents 1 About this document 1.1 Function... 3 1.2 Target group... 3 1.3
More informationCALEFFI. Ball zone valves. series /03 GB
all zone valves series cert. n ISO / Function Zone valves are used to automatically shut-off the flow of carrier fluid distributed to a system. Specifically: -In central heating systems, they support the
More informationInstruction Manual Differential Pressure Gauge
DA09 Instruction Manual Differential Pressure Gauge Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance
More informationPneumatic pressure switch 20DD
Sensor system: stainless steel 0,2 to 6 bar Microswitch with gold plated contacts (suitable for intrinsically safe operation) High accuracy (max. scattering < 1,5%) Excellent sealing properties (better
More informationPKP Prozessmesstechnik GmbH. Borsigstrasse 24. D Wiesbaden-Nordenstadt. Tel: / Fax: / Operating Instructions
PKP Prozessmesstechnik GmbH Borsigstrasse 24 D-65205 Wiesbaden-Nordenstadt Tel: 06122 / 7055-0 Fax: 06122 / 7055 50 Operating Instructions PMR02 / PMR04 Bourdon Tube Pressure Gauge Contents 1 Introduction
More informationMounting instructions. Strain transducer SLB-700A. B 26.SLB700A.10 e
Mounting instructions Strain transducer SLB-700A B 26.SLB700A.10 e SLB700A 3 Contents Page Safety instructions.............................................. 4 1 Applications..................................................
More informationOperating Instructions
Operating Instructions Light-metal Ex d enclosures / flameproof enclosure > 8265/0 Empty enclosure > 8265/4 Control panel, integrated in Ex e enclosure > 8265/5 Control panel Table of Contents 1 Table
More informationInstallation and Maintenance Instruction Manual
Installation and Maintenance Instruction Manual Bi-metal Thermometer Model A and E in a configuration - pursuant to ASME B40.200: ##=E#=### or ##=ERT#=### - pursuant to EN 13190: ###=A#=### or ##=ART#=###
More informationTwo-port valves, male threaded, PN25
4 379 Two-port valves, male threaded, PN25 VVG55... Two-port valves, externally threaded, PN25 Bronze Rg5 DN15... 25 mm (½"... 1") k vs 0.25... 6.3 m 3 /h Stroke 5.5 mm Suitable for type SQS35... or SQS65...
More informationMechanical pressure switches Tested to PE Directive 97/23/EC. Maximum pressure limiters for liquid gas installations
Tested to PE Directive 97/23/EC FD Maximum pressure limiters for liquid gas installations Pressure limiters of the FD series are constructed in accordance with the special directives for liquid gas engineering.
More informationPressure switch Type BCP
Data sheet Pressure switch Type BCP The BCP type is a series of dedicated switches for safety and monitoring of steam and hot water boilers. The BCP incorporates a single-pole changeover microswitch where
More informationOperating Instructions Rope Pull Switches RPS...
Safety rope pull switch RPS Correct use In accordance with EN 60947-5-5, EN ISO 13850, it must be ensured that parts of or complete industrial machines or installations can be stopped as quickly as possible
More informationTechnical data sheet. Type overview. Technical data. Safety notes. T5-R2.. Open-close en v Subject to changes 1 / 3
Technical data sheet R2.. Open-close ball valves, 2-way, with internal thread for open and closed cold and warm water systems for shut-off functions on the water side and 2-point controls in air-handling
More informationPressure Measurement. Transmitters for basic requirements SITRANS P Z for gauge pressure. 2/4 Siemens FI Overview
f gauge pressure Siemens AG 010 Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and electronics plate Process connection Electrical connection
More informationWide opening parallel grippers Series CGLN
CATALOGUE > s 202 Wide opening parallel grippers Series CGLN > Grippers Series CGLN Magnetic Sizes: ø 0-6 - 20-25 - 32 mm» High flexibility during mounting» High grip force» Rack and pinion synchronized
More information3G Operating instructions. Digital Purge Gas Valve 3G Type: Document no.: D0001 Version: 01. July 2011/Rev.
3G Operating instructions Type: 03-5110-00.. Document no.: 03-5110-7D0001 Version: 01. July 2011/Rev. 0 Operating Instructions Type: 03-5110-00.. Document no.: 03-5110-7D0001 Version: 1 July 2011 / Rev.
More informationSCH. Mechanical Pressure Switches. for overpressure, vacuum pressure and differential pressure
Mechanical Pressure Switches for overpressure, vacuum pressure and differential pressure measuring monitoring analysing SCH P3 OO Switching range: -1... + 0.1 bar - 250... +100 mbar, 1... 16 mbar a 16...
More informationINSTRUCTION MANUAL COMPACT PRESS. SWITCHES SERIES PCS & PCA
COMPACT PRESS. SWITCHES SERIES PCS & PCA WEATHERPROOF SERIES PCS SERIES PCA EXPLOSIONPROOF B B A A B = Cable entry A = Pressure connection WEIGHT 1kg dimensions in mm B = Cable entry A = Pressure connection
More informationInstallation & Maintenance Instructions TEC-11N TIMER. Analogue electronic timer 02/09
Installation & Maintenance Instructions TEC-11N TIMER Analogue electronic timer 02/09 GENERAL OPERATION The TEC-11N timer is produced using SMT (Surface Mounting Technology), ensuring improved performance
More informationINSTALLATION INSTRUCTIONS PUSH BAR PULLMAN PANIC BOLT DEVICE TO EN 1125 : 2008
INSTALLATION INSTRUCTIONS PUSH BAR PULLMAN PANIC BOLT DEVICE TO EN 1125 : 2008 0376/448/00 ISSUE 01 EMERGENCY PUSH PAD PULLMAN BOLT DEVICE TO EN 179 : 2008 1000mm MAXIMUM CLEAR OPENING HEIGHT WITH PUSH
More informationOperating manual for the pressure transducer unit CCS 1000
Operating manual for the pressure transducer unit CCS 1000 Please read the operating manual before using the device. 1 Content: 1. General description 2. Technical data 3. Operation 4. Scope of supply
More informationTEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125
TEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125 Model: VC-40-VYC Table of contents 1. - Installing the test bench 1.1.1- Connecting the compressed air / nitrogen source 1.1.2- Maximum test pressure according
More informationHigh-performance submersible pressure transmitter For level measurement Model LH-10
Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-10 WIKA data sheet PE 81.09 Applications Level measurement in rivers and lakes Deep well
More informationBall Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6"
Data Sheet 819584-00 Issue Date: 01/17 Ball Float Steam Trap UNA 43 PN 16/C 125/JIS 10K UNA 46 PN 40/C 150/C 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6" UNA 43 hl, UNA 46 hl UNA 43 v, UNA 46 v with
More informationInstallation, commissioning and servicing instructions
488.03 www.reece.com.au Pressure reducing s Installation, commissioning and servicing instructions Function Pressure reducing s are installed in residential water systems to reduce and stabilise inlet
More informationMounting and Operating Instructions EB 3017 EN. Self-operated Regulators
Self-operated Regulars Flow and Differential Pressure Regular Type 42-37 Flow and Differential Pressure or Flow and Pressure Regular Type 42-39 Type 42-37 Type 42-39 Fig. 1 Flow and differential pressure
More informationExpansion Thermometers Stainless Steel Series, Model 70
Mechanical Temperature Measurement Expansion Thermometers Stainless Steel Series, Model 70 WIKA Data Sheet TM 81.01 Applications General-purpose temperature measuring instruments for gaseous, liquid and
More informationSiphon vessel / Priming aid
Manufacturer: sera GmbH sera-straße 1 34376 Immenhausen Germany Tel.: +49 5673 999-00 Fax: +49 5673 999-01 info@sera-web.com Keep the operating manual for future use! Record the exact type and serial number
More informationSeated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange
Data sheet Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange Description VF 2 VF 3 VF 2 and VF 3 valves provide a quality, cost effective solution for most water and chilled applications.
More informationSITRANS P measuring instruments for pressure
SITRANS P measuring instruments for pressure Z series for gage pressure Siemens AG 008 Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and
More informationDeclaration of Conformity as per Directive 97/23/EC
Declaration of Conformity as per Directive 97/23/EC The manufacturer declares that:, 47906 Kempen, Germany Multi-way diverting valves Series 29a and Series 29b, with packing with lever 1. The valves are
More informationOperating Manual * * Pressure Transmitter. Table of Content. 1 Safety Guidelines. 1.3 Risks due to Non-Observance of Safety Instructions
*09005184* BA_EN_ME11 Rev.B 09/15 *09005184* d e v e l o p i n g s o l u t i o n s ME11 Operating Manual Pressure Transmitter Table of Content 1 Safety Guidelines 2 Application Purpose 3 Description of
More information