1 Exercise 4-1 Float Switches EXERCISE OBJECTIVE In this exercise, you will study the construction and operation of a magnetic reed float switch. You will use a float switch to limit the amount of liquid pumped into a column. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Introduction Reed switch float switches Industrial applications Advantages and limitations Installing the float switch DISCUSSION Introduction A float switch is a point-level detection device used to actuate another device when the level in a vessel rises above, or drops below, a set point. Like all pointlevel sensors, float switches allow level detection of a single discrete level. A float switch that stops a pump when a tank is full is an example of a typical float switch application. Figure 4-3 shows a point-level detection mechanism that uses a simple float switch. Figure 4-3. Float switch application. In this example, the float of a float switch is displaced when its buoyancy makes it move upward when it comes in contact with the liquid. The float can be linked mechanically to an actuator, such as in the example of Figure 4-3, or via another mechanism, such as a reed switch and magnet mechanism. The working principle of float switches using this type of mechanism is described in the section below. Festo Didactic

2 Ex. 4-1 Float Switches Discussion Reed switch float switches Reed switch float switches have two main components: a reed switch and a float with an encased magnet. Depending on its position along a stem, the float actuates (or does not actuate) the reed switch. The reed switches used in float switches usually have a single-pole, single-throw (SPST) or a single-pole, double-throw (SPDT) contact configuration. The reed switch in the float switch of the training system is of the SPST type. How a reed switch works The reed switch was invented in 1936 by Walter B. Ellwood from the Bell Telephone Laboratories. As stated in the original patent application, this device eliminates the complicated mechanical and magnetic structures of the usual electromagnetic relays. Figure 4-4 shows a typical reed switch diagram. This type of switch is named after the thin metal reeds enclosed in its glass capsule. The capsule is filled with an inert gas to prevent the reeds from rusting. The portions of the reeds that come in contact when the switch closes are plated with precious metal to ensure good conductivity. Glass capsule Reed Inert gas Terminal Gap Contact plating Figure 4-4. Reed switch. The working principle of a reed switch is simple. In the absence of an outside force, the reed switch is open. The gap between the two reeds isolates them and no current can flow through the switch. However, if a permanent magnet is placed close to the switch, the magnetic flux generated by the magnet draws the two reeds together. As shown in Figure 4-5, the plated tip of one of the reeds becomes a magnetic north pole, while the tip of the other reed becomes a magnetic south pole 1. Since the tips of the reeds have opposite magnetic poles, they attract each other and the two reeds snap together to close the electric circuit. When the magnet is removed from the proximity of the switch, the stiffness of the reeds brings them apart and the electrical circuit is open again. 1 Note that each reed also has an opposite pole at its other extremity. Magnetic poles always come in pairs; a magnetic monopole has never been observed. 162 Festo Didactic

3 Ex. 4-1 Float Switches Discussion Permanent magnet Magnetic flux S N N S N S Contact closed Figure 4-5. Actuated reed switch. The float and the stem In a float switch, the reed switch described above is located in the stem, a nonmagnetic tube. The stem is waterproof and protects the reed switch from water. The float has a cylindrical shape and the stem passes through a hole along its axis. The float is made of a material of a lesser density than water so that it floats. A permanent magnet is embedded in the float and, when the float moves along the stem, the magnet changes the state of the reed contact. Construction and operation The working principle of the float switch can be summarized as follows. The float is made of a material that is lighter than water and incorporates a permanent magnet. As the float rises and falls with the changes in the water level, it moves the magnet along the stem, thereby opening and closing the reed switch contact, which consists of two thin moveable blades of ferromagnetic metal. The free ends of the reeds are the contact points and form the actual reed contact. Float switches can be normally open or normally closed switches. For example, the factory default configuration for the float switch, Model 6570, is with the reed contact acting as a normally closed contact. With this configuration, the magnet in the float closes the reed contact when the level is below the float. When the level rises above the float, the magnet rises with the float and, because it is too far from the reed switch, its magnetic field is too weak to keep the reed switch contact closed. Thus, the two reeds separate from each other and the circuit opens. Figure 4-6 shows how a float switch operates in NC configuration. Festo Didactic

4 Ex. 4-1 Float Switches Discussion Stem Contact open Contact closed Float Lower stop Figure 4-6. Float switch (NC configuration). Industrial applications Float switches are mainly used to perform on/off control and to start sequential operations in batch processes. They are also used to trigger alarms when high or low liquid levels are detected in vessels. High levels can indicate unusual change in normal load demand due to clogged pipes or valves accidentally closing, while low levels can indicate pump or liquid supply failure. Advantages and limitations Float switches are relatively inexpensive, reliable, and require minimum maintenance. However, they are limited in their use as on/off control devices or alarm switches. They do not provide continuous measurement of the liquid level. Moreover, some types of float switches are not recommended for processes where dirty liquids are handled. For example, liquids that contain particles of ferrous metal can cause malfunction of magnetically operated float switches. Installing the float switch The float switch is not designed to operate in a pressurized column. To avoid damage to the equipment, be sure the column is open to atmosphere when using the float switch. 164 Festo Didactic

5 Ex. 4-1 Float Switches Discussion The float switch is designed to be installed in the column, through the opening at the top of the column. Use Figure 4-7 and the instructions below to install the float switch on your system. a. Loosen the positioning lock of the mounting screw on the float switch. b. Insert the float switch all the way into the column. Secure the float switch to the column by tightening its mounting screw fully. c. By making the float switch slide within the column, adjust its position so that the bottom of its float is aligned with the desired mark on the graduated ruler of the column. Lock the float switch into position by tightening its positioning lock fully. Positioning lock Mounting screw (a) (b) (c) Figure 4-7. Installing the float switch. Festo Didactic

6 Ex. 4-1 Float Switches Procedure Outline PROCEDURE OUTLINE The Procedure is divided into the following sections: Set up and connections Level regulation End of the exercise PROCEDURE Set up and connections 1. Set up the system shown in Figure 4-8. In this circuit, the float switch is used to limit the amount of water that can be pumped into the column. Adjust the position of the float switch so that the bottom of the float is aligned with the 52 cm (20.5 in) mark on the graduated ruler of the column. Overflow hose Plug Figure 4-8. Using a float switch to limit the amount of water pumped into a column. a The overflow hose causes the column to be open to atmosphere through the reservoir of the pumping unit. 2. Make sure the reservoir of the pumping unit is filled with about 12 liters (3.2 gallons) of water. Make sure the baffle plate is properly installed at the bottom of the reservoir. 3. On the pumping unit, adjust pump valves HV1 to HV3 as follows: Open HV1 completely. Close HV2 completely. Set HV3 for directing the full reservoir flow to the pump inlet. 4. Turn on the pumping unit. 166 Festo Didactic

7 Ex. 4-1 Float Switches Procedure Level regulation 5. Make the pump rotate at maximum speed. 6. Observe the water level as it rises within the column. What happens when the level reaches the activation level of the float switch? Explain. 7. What causes the pump to alternately start and stop? Explain. 8. Note and record the level of the water in the column when the float switch activates and when it deactivates. 9. Stop the pump. 10. Reposition the float switch tube so that the bottom of the float is aligned with the 47 cm (18.5 in) mark on the graduated ruler of the column. 11. Restart the pump at maximum speed. Does the float switch activate and deactivate at the levels recorded in step 8? Explain. 12. Set pump speed to 50%. Do you observe a difference in the levels at which the float switch activates and deactivates? Explain. Festo Didactic

8 Ex. 4-1 Float Switches Conclusion End of the exercise 13. Stop the pump and turn off the pumping unit. 14. Disconnect the circuit. Return the components and hoses to their storage location. 15. Wipe off any water from the floor and the training system. CONCLUSION In this exercise, you used a float switch to limit the amount of water pumped into a column. You saw that the float switch automatically turned off the pump when the water level approached the top of the column. It automatically restarted the pump after the water level had returned below the activation point of the switch. REVIEW QUESTIONS 1. What are the most common functions for the float switches? 2. Name one advantage of using a reed switch. 3. Explain how a reed switch works. 4. Why is the reed switch glass capsule filled with an inert gas? 168 Festo Didactic

9 Ex. 4-1 Float Switches Review Questions 5. Name one advantage and one limitation of float switches. Festo Didactic

10

The Discussion of this exercise covers the following points: Range with an elevated or suppressed zero Suppressed-zero range Elevated-zero range

The Discussion of this exercise covers the following points: Range with an elevated or suppressed zero Suppressed-zero range Elevated-zero range Exercise 4-3 Zero Suppression and Zero Elevation EXERCISE OBJECTIVE In this exercise, you will learn the effect that mounting a pressure transmitter above or below the reference level has on the hydrostatic

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 3-2 Orifice Plates EXERCISE OBJECTIVE In this exercise, you will study how differential pressure flowmeters operate. You will describe the relationship between the flow rate and the pressure drop

More information

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler. Exercise 5-2 Bubblers EXERCISE OBJECTIVE Learn to measure the level in a vessel using a bubbler. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Bubblers How to measure

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 5-3 Wet Reference Leg EXERCISE OBJECTIVE Learn to measure the level in a vessel using a wet reference leg. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Measuring

More information

Float Operated Level Controllers

Float Operated Level Controllers CONTENTS Float Operated Level Controllers IM0015 Nov. 2014 PAGE Introduction 1 Scope 1 Description 1 Specification 1 Control Installation 2 INTRODUCTION Side Mount Back Mount Prior to installing, the instructions

More information

Reverse Osmosis System Installation Guide and Operation Manual.

Reverse Osmosis System Installation Guide and Operation Manual. Reverse Osmosis System Installation Guide and Operation Manual. Table of Contents 1 Introduction...2 2 Installation...3 2.1 Feed water connection...3 2.2 Permeate and concentrate plumbing...3 2.3 Electrical

More information

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump.

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump. Exercise 2-3 Centrifugal Pumps EXERCISE OBJECTIVE In this exercise, you will become familiar with the operation of a centrifugal pump and read its performance chart. You will also observe the effect that

More information

PREVIEW COPY. Level Measurement. Table of Contents. Principles of Level Measurement...3. Electrical Instruments Pressure Head Instruments...

PREVIEW COPY. Level Measurement. Table of Contents. Principles of Level Measurement...3. Electrical Instruments Pressure Head Instruments... Level Measurement Table of Contents Lesson One Lesson Two Lesson Three Principles of Level Measurement...3 Electrical Instruments...21 Pressure Head Instruments...37 Lesson Four Solid Level Measurement...53

More information

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES I N S T R U C T I O N - M A N U A L CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES FUNCTION: Conductivity level limit switches are based on the principle of measuring level through the electrical

More information

Instrumentation & Data Acquisition Systems

Instrumentation & Data Acquisition Systems Instrumentation & Data Acquisition Systems Section 3 -Level Robert W. Harrison, PE Bob@TheHarrisonHouse.com Made in USA 1 Level Section Question Which level measuring technology is the best solution when

More information

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow Model: FP 450-80 Installation Operation Maintenance PAGE 1 OF 5 1. Safety First BERMAD believes that the safety of personnel

More information

CCT-7320/ROC-2313 Reverse Osmosis Controller

CCT-7320/ROC-2313 Reverse Osmosis Controller CCT-7320/ROC-2313 Reverse Osmosis Controller 1 General The instrument is a combined control instrument of a reverse osmosis controller and an on-line conductivity instrument. It can perform the operation

More information

COMPACT TRIPLE WALL OUTLET STATION MODEL INSTALLATION AND OPERATING INSTRUCTIONS

COMPACT TRIPLE WALL OUTLET STATION MODEL INSTALLATION AND OPERATING INSTRUCTIONS COMPACT TRIPLE WALL OUTLET STATION MODEL 6255-1 INSTALLATION AND OPERATING INSTRUCTIONS To assure safe operation and conformation to local fire codes, all Porter Outlet Stations are designed to be used

More information

Heat Pump Connections and Interior Piping

Heat Pump Connections and Interior Piping Job Sheet 3 Heat Pump Connections and Interior Piping OBJECTIVES In this job sheet, you will observe how the presence of air in the ground loop affects the geothermal heat pump performance. You will also

More information

Module No. # 01 Lecture No. # 6.2 HAZOP (continued)

Module No. # 01 Lecture No. # 6.2 HAZOP (continued) Health, Safety and Environmental Management in Petroleum and Offshore Engineering Prof. Srinivasan Chandrasekaran Department of Ocean Engineering Indian Institute Of Technology, Madras Module No. # 01

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER TRANSPORTABLE CRUDE OIL CONTAINER

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER TRANSPORTABLE CRUDE OIL CONTAINER INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER TRANSPORTABLE CRUDE OIL CONTAINER MODEL TCC-5 DRAWING NUMBERS AD417CO AD557CO MANUAL NUMBER IOM-197 REVISION Rev. 0, 12/20/2016 TABLE OF CONTENTS

More information

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y INSTALLATION and INSTRUCTION MANUAL for QUALITY AIR BREATHING SYSTEMS Model 50 Systems Outfitted with ABM-725 Monitor M A R T E C H S E R V I C E S C O M P A N Y OFFICE: (507) 843-4700 P.O. BOX 7079 Toll

More information

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10 LK product no: PCS 1-10 Article no: 74503 Revision:8 Article no: 74503 Revision: 8 2 (23) Contents 1. General information... 5 2. Safety precautions... 5 2.1 Significance of symbols... 5 2.2 Explanatory

More information

Installation Instructions / Operating & Maintenance Manual Midi-Fill Digital Pressurisation Unit Models MFD15 & MFD22

Installation Instructions / Operating & Maintenance Manual Midi-Fill Digital Pressurisation Unit Models MFD15 & MFD22 Arrow Valves Ltd Installation Instructions / Operating & Maintenance Manual Midi-Fill Digital Pressurisation Unit Models MFD15 & MFD22 Tel 01442 823 123 Fax 01442 823 234 www.arrowvalves.co.uk Model shown

More information

LAB 7. ROTATION. 7.1 Problem. 7.2 Equipment. 7.3 Activities

LAB 7. ROTATION. 7.1 Problem. 7.2 Equipment. 7.3 Activities LAB 7. ROTATION 7.1 Problem How are quantities of rotational motion defined? What sort of influence changes an object s rotation? How do the quantities of rotational motion operate? 7.2 Equipment plumb

More information

Pressure Dump Valve Service Kit for Series 2300 Units

Pressure Dump Valve Service Kit for Series 2300 Units Instruction Sheet Pressure Dump Valve Service Kit for Series 00 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00 applicator tanks when the unit

More information

MUELLER. A Wall Type. Indicator Post. Reliable Connections. General Information 2. Technical Data/ Dimensions 3. Installation 4-5.

MUELLER. A Wall Type. Indicator Post. Reliable Connections. General Information 2. Technical Data/ Dimensions 3. Installation 4-5. Installation Instructions manual MUELLER table of contents PAGE A-20814 Wall Type General Information 2 Technical Data/ Dimensions Installation 4-5 Maintenance 6 Parts 7 Indicator Post! WARNING: 1. Read

More information

Model 130M Pneumatic Controller

Model 130M Pneumatic Controller Instruction MI 017-450 May 1978 Model 130M Pneumatic Controller Installation and Operation Manual Control Unit Controller Model 130M Controller is a pneumatic, shelf-mounted instrument with a separate

More information

ACCESSORY KIT INSTALLATION MANUAL

ACCESSORY KIT INSTALLATION MANUAL ACCESSORY KIT INSTALLATION MANUAL LP (PROPANE) CONVERSION KIT 1NP0366 FOR USE WITH MODELS: G8C & GF8 This conversion kit shall be installed by a qualified service agency in accordance with these instructions

More information

STINGER SERIES INLET ISOLATION VALVES

STINGER SERIES INLET ISOLATION VALVES STINGER SERIES INLET ISOLATION VALVES Installation, Operation and Maintenance Manual Edition: 2.4, Dec, 01, 2017 TM Patent Pending AIR POLLUTION CONTROL Camfil APC 3505 S. Airport Road, Jonesboro, AR 72401

More information

WARNING: FOR OUTDOOR USE ONLY

WARNING: FOR OUTDOOR USE ONLY Certified to CSA International 4.96 US For Outdoor Gas Fireplaces A HIGHER STANDARD IN QUALITY AND APPEARANCE SAFE AND BEAUTIFUL OUTDOOR LARGO FIRE PIT FOR PROPANE AND *NATURAL GAS OWNER S MANUAL WARNING:

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Welker The information in this manual has been carefully checked for accuracy and is intended to be used as a guide for the installation, operation, and

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Micro-S / Micro-S Digital Wall Hung Unit Please fulfil all listed requirements prior to and during

More information

Model PSI Compressor with 3-Gallon Air Tank 12VDC

Model PSI Compressor with 3-Gallon Air Tank 12VDC Model 6350 150 PSI Compressor with 3-Gallon Air Tank 12VDC IMPORTANT: It is essential that you and any other operator of this product read and understandd the contents of this manual before installing

More information

444C DUAL PERFORMANCE VALUE PACK

444C DUAL PERFORMANCE VALUE PACK (Chrome) PART NO. 44432 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using this product. SAVE THIS MANUAL

More information

450P AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES

450P AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES EXTREME SERIES PART NO. 45043 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using this product. SAVE THIS

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Models: EPS Single Pump EPT Twin Pump EPS-HP EPT-HP Single Pump High Pressure Twin Pump High Pressure

More information

Exercise 2-3. Flow Rate and Velocity EXERCISE OBJECTIVE C C C

Exercise 2-3. Flow Rate and Velocity EXERCISE OBJECTIVE C C C Exercise 2-3 EXERCISE OBJECTIVE C C C To describe the operation of a flow control valve; To establish the relationship between flow rate and velocity; To operate meter-in, meter-out, and bypass flow control

More information

INSTRUCTION MANUAL. FLOAT TYPE LEVEL TRANSMITTER HT-100R Series HITROL CO., LTD.

INSTRUCTION MANUAL. FLOAT TYPE LEVEL TRANSMITTER HT-100R Series HITROL CO., LTD. HITROL CO., LTD. HEAD OFFICE.FACTORY.R&D INSTITUDE HITROL CO.,LTD 141, Palhakgol-gil, Jori-eup Paju-si, Gyeonggi-do, Korea TEL. : (00)-82-31-950-9700 FAX. : (00)-82-31-943-5600 www.hitrol.com INSTRUCTION

More information

TEST SPECIFICATION NYT-909-C

TEST SPECIFICATION NYT-909-C 748 Starbuck Ave, Watertown, NY 13601 Phone: +1-315-786-5200 Engineering Fax: +1-315-786-5673 TEST SPECIFICATION NYT-909-C CODE OF TESTS FOR TESTING "AB" TEST RACK P/N 702546 & 702612 ISSUE NO. 5 1.0 THE

More information

Exercise 3-2. Two-Wire and Three-Wire Controls EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Two-wire control

Exercise 3-2. Two-Wire and Three-Wire Controls EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Two-wire control Exercise 3-2 Two-Wire and Three-Wire Controls EXERCISE OBJECTIVE Construct two-wire and three-wire control circuits and understand their principles. DISCUSSION OUTLINE The Discussion of this exercise covers

More information

OPERATING AND MAINTENANCE MANUAL

OPERATING AND MAINTENANCE MANUAL Series 4300 Engineered Performance TABLE OF CONTENTS 0 INTRODUCTION 1 1 Scope 1 2 Description 1 3 Specifications 1 0 INSTALLATION 1 1 Mounting 1 2 Piping 1 1 Connecting Process Pressure 2 2 Vent Connections

More information

400C & 450C DUAL PERFORMANCE VALUE PACKS

400C & 450C DUAL PERFORMANCE VALUE PACKS (Chrome) PART NO. 40013 (Silver) PART NO. 45012 (Chrome) PART NO. 45013 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before

More information

Geotech 1.66 Auto-Reclaimer

Geotech 1.66 Auto-Reclaimer Geotech 1.66 Auto-Reclaimer Installation and Operation Rev 9 8/31/06 Part # 16600165 TABLE OF CONTENTS CHAPTER 1: SYSTEM DESCRIPTION... 3 FUNCTION AND THEORY... 3 SYSTEM COMPONENTS... 4 CHAPTER 2: SYSTEM

More information

Geotech 1.66 Auto-Reclaimer Installation and Operation

Geotech 1.66 Auto-Reclaimer Installation and Operation Geotech 1.66 Auto-Reclaimer Installation and Operation Rev 10/19/12 Part # 16600165 TABLE OF CONTENTS CHAPTER 1: SYSTEM DESCRIPTION... 3 FUNCTION AND THEORY... 3 SYSTEM COMPONENTS... 4 CHAPTER 2: SYSTEM

More information

Level MEASUREMENT 1/2016

Level MEASUREMENT 1/2016 Level MEASUREMENT 1/2016 AGENDA 2 A. Introduction B. Float method C. Displacer method D. Hydrostatic pressure method E. Capacitance method G. Ultrasonic method H. Radar method I. Laser method J. Level

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS 1NP0680 - PROPANE CONVERSION FOR USE WITH MODELS: PM8, PC8, PM9, PC9, FL9M, FL9C, FC9M, FC9C This conversion kit is to be installed by a qualified service agency

More information

CONGRATULATIONS ON YOUR PURCHASE OF YOUR THUNDER COMPRESSOR For your personal safety please read, understand and follow the information provided in

CONGRATULATIONS ON YOUR PURCHASE OF YOUR THUNDER COMPRESSOR For your personal safety please read, understand and follow the information provided in CONGRATULATIONS ON YOUR PURCHASE OF YOUR THUNDER COMPRESSOR For your personal safety please read, understand and follow the information provided in this instruction manual. 1 CONTENTS 3. Safety Precautions

More information

User Manual MFCS TM -EZ

User Manual MFCS TM -EZ User Manual MFCS TM -EZ Version 6A_December 2016 1. INTRODUCTION 5 2. GENERAL INFORMATION 6 2.1 General functioning 6 2.2 Different MFCS TM 6 3. PACKAGE CONTENT 8 4. MFCS TM -EZ DESCRIPTION 9 5. CONNECTIONS

More information

VACUUM REGULATORS CONTENTS

VACUUM REGULATORS CONTENTS CAD drawing data catalog is available. ACCESSORIES GENERAL CATALOG AIR TREATMENT, AUXILIARY, VACUUM, AND FLUORORESIN PRODUCTS CONTENTS Small Regulators Features 759 Specifications, Order Codes, Flow Rate

More information

256 Pneumatic Pressure Indicator

256 Pneumatic Pressure Indicator 256 Pneumatic Pressure Indicator 51425699 Copyright 2002 Slope Indicator Company. All Rights Reserved. This equipment should be installed, maintained, and operated by technically qualified personnel. Any

More information

Accu-Tab PowerBase 3012AT by Axiall Corporation

Accu-Tab PowerBase 3012AT by Axiall Corporation Accu-Tab PowerBase 3012AT by Axiall Corporation Installation and Operating Instructions DANGER: DO NOT MIX CHEMICALS! The PowerBase 3012AT chlorinator system is designed for use with Axiall Corp. approved

More information

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions BAC 13310 IM-P133-42 ST Issue 2 M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning 5.

More information

450P- RV AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES

450P- RV AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES 450P- RV AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES PART NO. 45053 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing

More information

System Pressure Manager Standard & System Pressure Manager Plus

System Pressure Manager Standard & System Pressure Manager Plus System Pressure Manager Standard & System Pressure Manager Plus Installation, Commissioning & Servicing Instructions Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING,

More information

Model 7989T Steel Pipe Squeezer Sch. 40 & Sch. 80. Operations Manual

Model 7989T Steel Pipe Squeezer Sch. 40 & Sch. 80. Operations Manual 10-12 Steel Pipe Squeezer Sch. 40 & Sch. 80 Operations Manual 1.0 Introduction This manual is issued as a basic operation manual covering the Regent Model 7989T, Pipe Squeezer and Pump as manufactured

More information

MUELLER A A Non-Adjustable. Vertical Indicator Posts. Reliable Connections. General Information 2. Technical Data 3.

MUELLER A A Non-Adjustable. Vertical Indicator Posts. Reliable Connections. General Information 2. Technical Data 3. Installation Instructions manual MUELLER table of contents PAGE A-20808 General Information 2 Technical Data 3 Dimensions 4 A-20809 Non-Adjustable Installation 5-6 Parts 7 Maintenance 8 Vertical Indicator

More information

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 9 ACCUMULATORS The material needed for outcome 2 is very extensive so there are

More information

NC MAGNETIC FLOAT SWITCHES FOR LIQUIDS

NC MAGNETIC FLOAT SWITCHES FOR LIQUIDS NC MAGNETIC FLOAT SWITCHES FOR LIQUIDS Flow Pressure Level Temperature measurement monitoring control N Available Materials: Brass, Stainless Steel, Buna-N, Polypropylene and PVC Maximum Pressure: 400

More information

TABLE OF CONTENTS SAFETY FIRST!...3 BASIC OPERATION...4 ADJUSTMENTS...5. Cocking Pressure...5. Three-Way Valve Adjustment...6

TABLE OF CONTENTS SAFETY FIRST!...3 BASIC OPERATION...4 ADJUSTMENTS...5. Cocking Pressure...5. Three-Way Valve Adjustment...6 TABLE OF CONTENTS SAFETY FIRST!...3 BASIC OPERATION...4 ADJUSTMENTS...5 Cocking Pressure...5 Three-Way Valve Adjustment...6 External Three-Way adjustment...6 In-Line Regulator...6 Ram to Cocking Block

More information

Smooth Vent Valve. Series XVD XL XL Q D- XVD XGT CYV

Smooth Vent Valve. Series XVD XL XL Q D- XVD XGT CYV Smooth Vent Valve Series Valve / needle valve integrated construction requires only 1/4 the piping space of previous models. Particulates significantly reduced through the use of a metal diaphragm in the

More information

Aquashield to Mitigate Water Ingress of Gas Pipes

Aquashield to Mitigate Water Ingress of Gas Pipes IGEM Young Persons Paper Competition 2017 Aquashield to Mitigate Water Ingress of Gas Pipes Assistant Engineer Technical Development Section, Distribution Operation Department The Hong Kong and China Gas

More information

Smooth Vent Valve. XVD Series

Smooth Vent Valve. XVD Series Smooth Vent Valve Series Valve / needle valve integrated construction requires only 1/4 the piping space of previous models. Particulates significantly reduced through the use of a metal diaphragm in the

More information

NC MAGNETIC FLOAT SWITCHES FOR LIQUIDS

NC MAGNETIC FLOAT SWITCHES FOR LIQUIDS NC MAGNETIC FLOAT SWITCHES FOR LIQUIDS Flow Pressure Level Temperature measurement monitoring control N1 Available Materials: Brass, Stainless Steel, Buna-N, Polypropylene and PVC Maximum Pressure: 400

More information

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS. This work covers part of outcome 2 of the Edexcel standard module:

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS. This work covers part of outcome 2 of the Edexcel standard module: FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS This work covers part of outcome 2 of the Edexcel standard module: UNIT 21746P APPLIED PNEUMATICS AND HYDRAULICS The material needed for outcome

More information

Operation Manual Guillotine Cutter RC-5

Operation Manual Guillotine Cutter RC-5 Operation Manual Guillotine Cutter RC-5 Technical Specifications General Safety/Operating Instructions Using the Guillotine Cutter/Crimper Blade Change Instructions Maintenance Instructions This is a detailed

More information

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For Your Safety... 2 Description.... 2 Setup Mode.... 2 Lights/Alarms.... 3 Operation.... 4 Calibration....

More information

AQUARIUS. Operating Instructions for the. Type 70 Electrolytic Gas Soldering / Welding Unit. Table of Contents

AQUARIUS. Operating Instructions for the. Type 70 Electrolytic Gas Soldering / Welding Unit. Table of Contents AQUARIUS Operating Instructions for the Type 70 Electrolytic Gas Soldering / Welding Unit Table of Contents 1. Important General Remarks 2 2. Safety Instructions 2 3. Description of the Soldering Unit

More information

Basic Pneumatics. Module 8: Pressure control valves. Academic Services PREPARED BY. April 2012

Basic Pneumatics. Module 8: Pressure control valves. Academic Services PREPARED BY. April 2012 Basic Pneumatics Module 8: Pressure control valves PREPARED BY Academic Services April 2012 Applied Technology High Schools, 2012 Module 8: Pressure control valves Module Objectives After the completion

More information

HANDBOOK. Squeeze Off Unit SOU 400. Please refer any queries to:

HANDBOOK. Squeeze Off Unit SOU 400. Please refer any queries to: HANDBOOK Squeeze Off Unit SOU 400 Please refer any queries to: Hy Ram Engineering Co Ltd Pelham Street Mansfield Nottinghamshire NG18 2EY Telephone No: (01623) 422982 Please note all queries should state

More information

PRO SINK -R 1 and 2. Dilution system CONTENTS

PRO SINK -R 1 and 2. Dilution system CONTENTS PRO SINK -R 1 and 2 Dilution system CONTENTS 1.0 Product description 2 2.0 Warnings.. 3 3.0 Installation procedure 4 4.0 Plumbing connections 4 5.0 Technical features.. 5 6.0 Maintenance... 6 7.0 Troubleshooting......6

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

Flow controller Type ED/CCB311 Instruction manual

Flow controller Type ED/CCB311 Instruction manual Flow measurement Flow controller Type ED/CCB311 1. GENERAL DESCRIPTION page 4 2. DETAILED DESCRIPTION page 4 3. PIPE - EXPLOITATION page 5 4. PREVENTIVE MAINTENANCE page 5 5. REPLACEMENT OF THE CONTACT

More information

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION OCT2010 STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 020 87833050

More information

Compact Triple Cabinet Outlet Station Model Installation and Operating Instructions

Compact Triple Cabinet Outlet Station Model Installation and Operating Instructions Compact Triple Cabinet Outlet Station Model 6258-1 Installation and Operating Instructions The Porter Compact Triple Outlet Station (6258-1) provides a quick, safe, and reliable method of connection to

More information

Installation and Maintenance Manual. ECO Filtration Unit with 6-way-Top-Mount-Valve. Art. Nr

Installation and Maintenance Manual. ECO Filtration Unit with 6-way-Top-Mount-Valve. Art. Nr Installation and Maintenance Manual ECO Filtration Unit with 6-way-Top-Mount-Valve Art. Nr. 300100 300101 300102 Important Details: - Using of this filtration unit for swimming pools and its guard band

More information

Pneumatic switch module 3/2-way valve (On/Off) Types P Types FP Function tested for use of the float in Ex-zone 0

Pneumatic switch module 3/2-way valve (On/Off) Types P Types FP Function tested for use of the float in Ex-zone 0 Operating Manual LTIA3E Pneumatic switch module 3/2-way valve (On/Off) Types P Types FP Function tested for use of the float in Ex-zone 0 Contents 1. Safety Instructions 2. Conformity to standards 3. Technical

More information

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock or Electrocution: MODEL NUMBER: 20008 200 PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank IMPORTANT: It is

More information

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road PROPORTIONING VALVE Model 150 INSTRUCTION MANUAL March 2017 IMS Company 10373 Stafford Road Telephone: (440) 543-1615 Fax: (440) 543-1069 Email: sales@imscompany.com 1 Introduction IMS Company reserves

More information

Inert Air (N2) Systems Manual

Inert Air (N2) Systems Manual INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing

More information

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only) 42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) 42047 Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only) 45052 Constant Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor

More information

MODEL NUMBER: P-A AUTOMATIC PORTABLE COMPRESSOR

MODEL NUMBER: P-A AUTOMATIC PORTABLE COMPRESSOR MODEL NUMBER: 45043-450P-A AUTOMATIC PORTABLE COMPRESSOR IMPORTANT: It is essential that you and any other operator of the product read and understand the contents of this manual before installing and

More information

Operation, Assembly & Maintenance Manual

Operation, Assembly & Maintenance Manual AutoSparge tm Operation, Assembly & Maintenance Manual Congratulations on your purchase, and thank you for selecting the AutoSpargetm lauter tun level control from Blichmann Engineering. We are confident

More information

Installation, operating and maintenance Instructions for Seemag bypass level indicator

Installation, operating and maintenance Instructions for Seemag bypass level indicator Issue: S Date: 05-09-14 Type G35 General information The Seetru bypass magnetic level indicator, abbreviate SEEMAG, serves to show the filling level of fluids in tanks, basins, tubes etc. The Seemag operates

More information

MUELLER. A A Adjustable. Vertical Indicator Posts. Reliable Connections. General Information 2. Technical Data 3.

MUELLER. A A Adjustable. Vertical Indicator Posts. Reliable Connections. General Information 2. Technical Data 3. Installation Instructions manual MUELLER table of contents PAGE A-20806 A-20807 Adjustable General Information 2 Technical Data 3 Dimensions 4 Installation 5-6 Parts 7 Maintenance 8 Vertical Indicator

More information

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE MODEL NUMBER: M20005 AIR SOURCE KIT 30% Duty Compressor on 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE USER MANUAL IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock

More information

HOLLISTER-WHITNEY ROPE GRIPPER

HOLLISTER-WHITNEY ROPE GRIPPER HOLLISTER-WHITNEY ROPE GRIPPER Instructions for Model #620GA1, 620GA2 (Patented worldwide, other patents pending) WARNING: KEEP HANDS CLEAR OF ROPE GRIPPER. FORCES CREATED CAN CRUSH FINGERS. Figure 1 ROPE

More information

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED VULCAN 36RB 36IRB WOLF C36RB C36IRB This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not

More information

Basic Hydraulics. Module 4: Flow Control Valves & Pressure Relief Valves. Academic Services PREPARED BY. January 2012

Basic Hydraulics. Module 4: Flow Control Valves & Pressure Relief Valves. Academic Services PREPARED BY. January 2012 Basic Hydraulics Module 4: Flow Control Valves & Pressure Relief Valves PREPARED BY Academic Services January 2012 Applied Technology High Schools, 2011 ATM 1122 Basic Hydraulics Module 4: Flow control

More information

Magnetic Level Gauges

Magnetic Level Gauges Bulletin B 03 04 Magnetic Level Gauges Remote Reading Systems Magnetic Level Switches Magnetic level gauges OPERATING PRINCIPLE The operation of the magnetic level gauge is based on some elementary physical

More information

User's Manual. MixRite TF 10. Edition 05.08

User's Manual. MixRite TF 10. Edition 05.08 User's Manual MixRite TF 10 Edition 05.08 1 Tefen MixRite TF 10 fertilizer and chemicals Injector Congratulations on your purchase of one of Tefen s high quality products. To get the best results from

More information

200 PSI FAST-FILL AIR SOURCE KIT

200 PSI FAST-FILL AIR SOURCE KIT 200 PSI FAST-FILL AIR SOURCE KIT 55% Duty Compressor on 2.0 Gallon Air Tank PART NO. 20007 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of

More information

200 PSI HIGH-FLOW AIR SOURCE KIT

200 PSI HIGH-FLOW AIR SOURCE KIT 200 PSI HIGH-FLOW AIR SOURCE KIT 50% Duty Compressor on 2.0 Gallon Air Tank PART NO. 20008 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of

More information

Smooth Vent Valve XVD. Series

Smooth Vent Valve XVD. Series Smooth Vent Valve Series Valve / needle valve integrated construction requires only 1/4 the piping space of previous models. Particulates significantly reduced through the use of a metal diaphragm in the

More information

Booster Pump PB4-60 Replacement Kits

Booster Pump PB4-60 Replacement Kits Booster Pump PB4-60 Replacement Kits FOR YOUR SAFETY - This product must be installed and serviced by a contractor who is licensed and qualified in pool equipment by the jurisdiction in which the product

More information

INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT

INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT P.O. Box 1058 1058 West Industrial Avenue Guthrie, OK 73044-1058 405-282-5200 FAX: 405-282-8105 www.autoquip.com Item # 830ABS Version 1.0 07/2001

More information

N2 Blanketing Valve DST100 / DST200 TYPE INSTRUCTION MANUAL CONTENTS K.S.P.C. General Description Operation. Installation Maintenance

N2 Blanketing Valve DST100 / DST200 TYPE INSTRUCTION MANUAL CONTENTS K.S.P.C. General Description Operation. Installation Maintenance DST100 / DST200 TYPE N2 Blanketing Valve INSTRUCTION MANUAL CONTENTS General Description Operation Installation Maintenance K.S.P.C 488-1 Wolha-ro, Tongjin-eup, Gimpo-si, Gyeonggi-Do, Korea Tel : +82-31-998-3825~7

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The LDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

R E D I C O N T R O L S

R E D I C O N T R O L S R E D I C O N T R O L S Operation & Maintenance Manual Portable Service Purger for Low Pressure Chillers Model: PSP-LP-1B For Refrigerants R-11, R-113, R-114 & R-123 & Other Similar Refrigerants File Literature

More information

WARNING: READ THE GENERAL INFORMATION MANUAL INCLUDED FOR OPERATING AND SAFETY PRECAUTIONS AND OTHER IMPORTANT INFORMATION.

WARNING: READ THE GENERAL INFORMATION MANUAL INCLUDED FOR OPERATING AND SAFETY PRECAUTIONS AND OTHER IMPORTANT INFORMATION. GSR500 Ram Assembly General Description The GSR500 single post lift / ram uses a 3-1/4 air powered cylinder, which is welded to a heavy gauge base. It is normally used to raise and lower a fluid handling

More information

Goulds 3296 EZMAG. Chemical Process Pump

Goulds 3296 EZMAG. Chemical Process Pump Goulds 3296 EZMAG Chemical Process Pump 3296 EZMAG Chemical Process Pump Capacities to 700 gpm (160 m3/h) Heads to 620 ft (189 m) Temperatures to 535 F (280 C) Pressures to 275 PSIG Performance Features

More information

VERTICAL BLADDER TANK

VERTICAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Tight Spaces UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

GV Standard X-Vent. Setup, Commissioning & Installation Guide

GV Standard X-Vent. Setup, Commissioning & Installation Guide GV Standard X-Vent Setup, Commissioning & Installation Guide Technical experts in the design, manufacture and supply of precision engineered, architectural rooflights for residential and commercial buildings.

More information

SPECIFICATIONS ATTENTION

SPECIFICATIONS ATTENTION VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane

More information

Operating Instructions Models and Hydrostatic Test Pumps

Operating Instructions Models and Hydrostatic Test Pumps Operating Instructions Models 33100 and 33101 Hydrostatic Test Pumps 33100 DIMENSIONS: WEIGHT: PUMP: MOTOR: CONTROL: GAUGE: DISCHARGE HOSE: 16 (40cm) L x 22 (55cm) W x 18 (45cm) H 87 lbs., 39.5 kg Triplex

More information