Flamco Flamco-Fill STA Flamco-Fill STM

Size: px
Start display at page:

Download "Flamco Flamco-Fill STA Flamco-Fill STM"

Transcription

1 STA STM Typ STA 5936 Typ STM 5937 GB Installation and operating instructions 1999,

2 2

3 Contents GB UK Limited P.O. Box 9, Washway Lane, St. Helens, Merseyside WA10 6FE United Kingdom Telephone: Fax: Chapter Page 1. General 3 2. Construction 4 3. Operation 4 4. Technical data 5 5. Placing and installation 5 6. Adjustment and commissioning 7 7. Maintenance and inspection 8 1. General The monitors the content in closed water central heating and cooling installations and makes up water loss as necessary. The make-up is done on the basis of pressure or level in an adjustable time interval. The prevents the ingress of air and the associated operational failure, and corrosion in the installation. With the use of the, there is no further requirement for manual make-up or the associated venting. The construction of the fulfils the requirements of DIN Fields of application type STA - for installations with pump- or compressor-controlled diaphragm expansion automats (including Flexcon M-K and Flexcon M-P), where the make-up pressure is at least 1.2 bar less than the pressure of the mains water supply. type STM - for installations with standard diaphragm expansion vessels with fixed fill pressure (including Flexcon M, Flexcon B, Pro-Flex, Flexcon and Contra-Flex), where the make-up pressure is at least 1.3 bar less than the pressure of the mains water supply. Note In installations where the individual pressure differences (pressure of the mains water supply - make-up pressure < 1.2 or 1.3 bar) do not allow the application of a type STA or type STM, pump-controlled make-up automats of the types PA or PM can be used. The is not to be used for a first or new filling! For UK installations, refer to UK Limited for special units to comply with Local Regulations. 3

4 2. Construction The types STA and STM consist of the following main parts: - hydraulic part - control - housing - pressure switch (only STM) type STA A. ball valve B. water meter C. strainer D. system separator (DVGW tested) E. solenoid valve F. control with indication fault signal display G. cable inlet and outlet 6034 Separate illustrations of the operating panel of the controls running time fuse in minutes defective water shortage fault fault remove ON/OFF type STA running time fuse in minutes defective water shortage fault fault remove ON/OFF type STM 3. Operation type STA - the control is activated by an external potential-free signal from the control of a pump- or compressor-controlled diaphragm expansion automat. - the solenoid valve is opened by the signal and water in the installation is made up until the pre-set level value on the control of the expansion automat is reached. type STM - the control is activated by a pressure switch with a fixed pressure difference (this pressure switch is part of the unit). - when the pressure in the installation falls to the pre-set value on the pressure switch, the solenoid valve is opened and water is made up until the switching differential that is set on the pressure switch is reached. If the make-up time that is set on the control is exceeded (this setting is specific for the installation), the solenoid valve is closed and the "fault" LED lights. The make-up installation is cut out, and can only be reset by pressing the "remove fault" pushbutton. It is recommended to check the installation first for leakages. If a fault occurs in the drinking water supply, the protection against running dry is activated, the "water shortage" LED is lit and the pump is switched off. If the "fuse defective" LED lights, a fault on the solenoid valve has activated a fuse. Please contact our customer service. 4

5 4. Technical data ➂ L D W ➁ ➀ ➀ water mains connection ➁ system connection ➂ drain connection of system separator 6132 General - max. supply pressure : 10 bar - max. operating temperature : 40 C - max. volume flow : 2.3 m 3 /h - max. adjustable make-up time : 120 min - mains voltage : 230 V/50 Hz - mains fuses : 250 V/6 A - secondary-side load fuse : 250 V/1.8 A (slow) - max. current for fault signal : 250 V/5 A AC - supply pipe-work connection : 1 /2 (inner screwthread) - system connection : 1 /2 (outer screwthread) - overflow connection : DN 40 (HT pipe) - dimensions : L x W x D = 600 x 200 x 120 mm Special for STA - minimum pressure difference between mains water pressure and system pressure: 1.2 bar - weight: 11 kg Special for STM - minimum pressure difference between mains water pressure and system pressure or selected switch-on pressure of the make-up: 1.3 bar - adjustment range of pressure switch: 0.5 to 6 bar - switching differential of the pressure switch: 0.3 bar - weight: 12 kg 5. Placing and installation The may only be installed in a frost-free area! First, the appropriate wall fixtures must be mounted on the wall. Then, the is aligned and mounted, whereby care must be taken that there is sufficient free space at the side for the hydraulic connections. All connections must be made according to locally applicable rules! Hydraulic connections The internal ball valves (item A on page 4) must be closed! First, the mains supply pipework and the system connection must be sealed. Before doing this, the mains supply pipe-work should be completely flushed out. After the appropriate drainage funnel of the system separator is attached, the drainage pipe-work (HT pipe DN 40) is fitted on site. With the STM, the appropriate pressure switch (connection 1 /2 AG) must be so installed that there can be no dynamic effects in operation (for example in the expansion pipe-work)! 5

6 Electrical connections The is wired in the factory. The abbreviations on the terminal block of the control have the following significance: wiring in the factory at installation PE earthing of solenoid valve and robust casing x PE earthing conductor of mains x N neutral conductor of mains x L live conductor of mains x S1 on and off switch of connection 1 x S1a on and off switch of connection 1a x S1b on and off switch of connection 1b x P/M solenoid valve connection x P/M solenoid valve connection x O fault signal - NC (break) x G fault signal - COMM (common) x S fault signal - NO (make) x E1b connection to potential-free input signal x E1a connection to potential-free input signal x E2b spare E2a spare A Schuko wall socket must be installed for the connection to the mains. The mains cable (length 2 m) that is connected to the control is fed through the cable grommet (see item G on page 4) and connected to the Schuko plug which is supplied with the installation. A possible alternative is a connection on the junction box. Special for STA The electrical connection to the expansion automat is made at installation with a 2-way cable with a cross-section of at least 2 x 0.75 mm 2. The connection to the control of the is made on the E1a and E1b terminals. For this purpose, the control must be removed by unscrewing both cylinder screws from the robust casing. Next, the control housing is screwed back on the front. The cable is fed through the cable grommet in the robust casing and fed through the PG screw connection in the control cabinet and connected. Now, the control is replaced in the reverse order to removal. The connection to the expansion automat is done according to the installation specification of the expansion automat. Special for STM The electrical connection to the pressure switch is made with a 2-way cable (length 4 m) that is connected to the control and fed through the cable grommet from the robust casing to terminals 1 and 2 of the Hirschmann plug of the pressure switch, where it is inserted and screwed tight. If necessary, the cable (cross-section of at least 2 x 0.75 mm 2 ) can be extended or shortened on installation. There is a potential-free change-over contact available for the telemetry fault signal, so that a suitable signal processing can be made on installation (make or break contact). The connection to the control is done as previously described. 6

7 Steuerautomat Examples of installations 1. STA in an installation with Flexcon M-P 6036 FLEXCON M - P expansion pipe-work 2. STM in an installation with Flexcon M 6037 FLEXCON M P expansion pipe-work 6. Adjustment and commissioning Following the inspection of all connections, the ball valves are slowly opened (first at the supply) and the robust casing is closed. Special for STA The differential pressure present is determined on the basis of the supply and system pressures. With this value, the make-up rate is read from the graph on page 8. The percentage values for switching the make-up installation on and off that are set on the control of the expansion automat are the basis for the calculation of the make-up volume. The division of the two values, increased by 10 minutes, gives the make-up time that must be set. Example: Supply pressure : 6 bar System pressure : 2 bar Expansion automat : Flexcon M-P 5000 Switch-on value of make-up : 07 % Switch-off value of make-up : 15 % Difference pressure : 4 bar Determined make-up requirement : 1450 l/h, or l/min Determined make-up volume : 8 % of 5000 l = 400 l Make-up time that must be set 400 l : l/min + 10 min = 27 min 7

8 Special for STM The switch-on pressure must be chosen slightly higher than the starting pressure of the expansion vessel. The difference of the mains supply pressure and the switch-on pressure increased by half the switching difference of the pressure switch (0.15 bar) gives the average differential pressure. The theoretically possible make-up volume is calculated on the basis of the vessel and expansion vessel volume and the pressure factor (values from design data). The division of the two values, increased by 10 minutes, again gives the make-up time that must be set. Example: Mains pressure : 5 bar Expansion vessel : Flexcon M bar Starting pressure : 1 bar Switch-on value of make-up : 1.1 bar Expansion volume : 600 l Pressure factor : 0.64 Average pressure difference : 3.75 bar Determined make-up rate : 1400 l/h, or l/min Determined make-up volume : 1200 l x l = 168 l Make-up time that must be set : 168 l + 10 min = 17 min l/min After setting the make-up time, with the type STM, the switch-on pressure of the pressure switch is also set. For this purpose, the black knurled nut on the top of the pressure switch is pulled off and replaced upside down. The switch-on pressure corresponds with the top of the needle. Next, the pressure switch is again pulled off and placed upside down. Now, the can be put into operation by switching the main switch on. Graph of the STA and STM make-up rate (small, system-specific deviations are possible) Make-up rate in l/h Difference pressure (STA) or average difference pressure (STM) in bar 7. Maintenance and inspection The sieve of the strainer (item C on page 4) must be cleaned once per year. The rest of the components do not require any maintenance. Every six months, the system separator (item D on page 4) must be tested by the operator or installation contractor, according to DIN 1988, Part 8. For this purpose, the ball valves on the output side and input side are slowly closed after each other. The pressure difference measured on the test ball valves between the front and middle chambers must be 0.2 bar and must be maintained

Flamco Flexcon M-P Pump automat

Flamco Flexcon M-P Pump automat Flexcon M-P Pump automat 0664 Flex MP-eps GB Installation and operating instructions 1999, Flamco 2 Installation and operating instructions Flexcon M-P pump automat Dear customer, GB With the purchase

More information

System Pressure Manager Standard & System Pressure Manager Plus

System Pressure Manager Standard & System Pressure Manager Plus System Pressure Manager Standard & System Pressure Manager Plus Installation, Commissioning & Servicing Instructions Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING,

More information

Installation, operating and maintenance Instructions for Seemag bypass level indicator

Installation, operating and maintenance Instructions for Seemag bypass level indicator Issue: S Date: 05-09-14 Type G35 General information The Seetru bypass magnetic level indicator, abbreviate SEEMAG, serves to show the filling level of fluids in tanks, basins, tubes etc. The Seemag operates

More information

Tightness controls TC 1 3 and TC 4

Tightness controls TC 1 3 and TC 4 Tightness controls TC 1 3 and TC 4 Test of both safety valves Short test period thanks to logical decision-making in the program sequence Adjustable test period which can be adapted to different systems

More information

USER S MANUAL BASIC HORIZONTAL OIL-LUBRICATED MICROCOMPRESSOR Reference: RCMPBH

USER S MANUAL BASIC HORIZONTAL OIL-LUBRICATED MICROCOMPRESSOR Reference: RCMPBH USER S MANUAL BASIC HORIZONTAL OIL-LUBRICATED MICROCOMPRESSOR Reference: RCMPBH THIS MANUAL IS INTENDED FOR TECHNICAL STAFF IN CHARGE OF THE INSTALLATION, THE OPERATION AND THE MAINTENANCE OF THIS PRODUCT

More information

Columbus Instruments

Columbus Instruments 0215-003M Portable O 2 /CO 2 /CH 4 Meter User s Manual Columbus Instruments 950 NORTH HAGUE AVENUE TEL:(614) 276-0861 COLUMBUS, OHIO 43204, USA FAX:(614) 276-0529 1 www.colinst.com TOLL FREE 1-800-669-5011

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Micro-S / Micro-S Digital Wall Hung Unit Please fulfil all listed requirements prior to and during

More information

Data sheet Pressure switch type CS December 2001 DKACT.PD.P10.A B1119

Data sheet Pressure switch type CS December 2001 DKACT.PD.P10.A B1119 Pressure switch type CS December 2001 DKACT.PD.P10.A2.02 520B1119 Introduction Pressure switch type CS is part of the Danfoss pressure control range. All CS pressure switches have a built-in pressure-operated,

More information

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25 Self-operated Pressure Regulators Differential Pressure Regulators (opening) Type 42-20 Type 42-25 Type 42-20 Differential Pressure Regulator Type 42-25 Differential Pressure Regulator Mounting and Operating

More information

AUTOMATIC GAS MANIFOLDS

AUTOMATIC GAS MANIFOLDS AUTOMATIC GAS MANIFOLDS Phoenix Pipeline Products Limited. Unit 8, McKenzie Industrial Park, Tel No.: 44 (0) 161 428 7200 Bird Hall Lane, Fax No.: 44 (0) 161 428 7010 Stockport, Email: info@p3-phoenix.com

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Models: EPS Single Pump EPT Twin Pump EPS-HP EPT-HP Single Pump High Pressure Twin Pump High Pressure

More information

Electronic Single and Twin Pump System Pressure Managers

Electronic Single and Twin Pump System Pressure Managers Electronic Single and Twin Pump System Pressure Managers Installation, Commissioning & Servicing Instructions Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING, OPERATING

More information

Installation, commissioning and servicing instructions

Installation, commissioning and servicing instructions 48323 www.caleffi.com Pre-adjustable pressure reducing valve with self-contained cartridge Copyright 2015 Caleffi 5350..H AUS series Installation, commissioning and servicing instructions Function Pressure

More information

Budget Range Operators Handbook

Budget Range Operators Handbook Budget Range Operators Handbook BAMBI AIR COMPRESSORS LTD 152 Thimble Mill Lane Heartlands Birmingham B7 5HT United Kingdom Tel: 0121 322 2299 Fax: 0121 322 2297 Email: sales@bambi-air.co.uk www.bambi-air.co.uk

More information

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION OCT2010 STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 020 87833050

More information

Flamco Flexcon M-K Compressor - automat expansion vessel

Flamco Flexcon M-K Compressor - automat expansion vessel Flexcon M-K Compressor - automat expansion vessel M-K EPS GB Installation and operating instructions 1999, Flamco 2 Flamco UK Limited P.O. Box 9, Washway Lane, St. Helens, Merseyside WA10 6FE United Kingdom

More information

TECHNICAL MANUAL HEAVY DUTY HORIZONTAL MICRO-COMPRESSOR Reference: RCMPH

TECHNICAL MANUAL HEAVY DUTY HORIZONTAL MICRO-COMPRESSOR Reference: RCMPH TECHNICAL MANUAL HEAVY DUTY HORIZONTAL MICRO-COMPRESSOR Reference: RCMPH THIS MANUAL IS INTENDED FOR TECHNICAL STAFF IN CHARGE OF THE INSTALLATION, THE OPERATION AND THE MAINTENANCE OF THIS PRODUCT CAUTION!

More information

4/2 way Pneumatic Solenoid Valve

4/2 way Pneumatic Solenoid Valve 4/2 way Pneumatic Solenoid Valve Compact design Push-over solenoid coil Exhaust air can be regulated Tube, threaded and sub-base connections Type combined with Seat valve version Type 2508 Type 2510/11

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Digital Range

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Digital Range Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Digital Range Models: DS 126 Single Pump / Single System DT 126 Twin Pump / Single System DS 160

More information

Pressure Reducing Valve for Steam Type 2333 A

Pressure Reducing Valve for Steam Type 2333 A Pressure Reducing Valve for Steam Type 2333 A Fig. 1 Type 2333 A 1. Design and principle of operation The pressure reducing valve consists of a balanced control valve and a closing actuator equipped with

More information

ENA. Flamco. Installation, maintenance and operating instructions. This manual must be passed to the end-user, and stored with the ENA.

ENA. Flamco. Installation, maintenance and operating instructions. This manual must be passed to the end-user, and stored with the ENA. VENT/TOP-UP APPLIANCE ENA This manual must be passed to the end-user, and stored with the ENA. VEN2302 Dear customer, In purchasing the ENA, you have chosen a quality product. This patented vent/top-up

More information

Standard Operating and Maintenance Instructions for Pumping System Model PS-90

Standard Operating and Maintenance Instructions for Pumping System Model PS-90 Standard Operating and Maintenance Instructions for Pumping System Model PS-90 High Pressure Equipment Company 2955 West 17th Street, Suite 6 PO Box 8248 Erie, PA 16505 USA 814-838-2028 (phone) 814-838-6075

More information

KTM 50 (DN ) Installation, maintenance and operating instructions

KTM 50 (DN ) Installation, maintenance and operating instructions 52 762-306 09.2014 KTM 50 (DN 100-200) Installation, maintenance and operating instructions General High-performing and compact, these pressure-independent control valves for variable flow heating and

More information

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN Differential Pressure Regulator Type 45-6 Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN Edition March 2008 Contents Contents Page 1 Design and principle of operation...................

More information

Installation, commissioning and servicing instructions

Installation, commissioning and servicing instructions 488.03 www.reece.com.au Pressure reducing s Installation, commissioning and servicing instructions Function Pressure reducing s are installed in residential water systems to reduce and stabilise inlet

More information

Valve Proving System VDK 200 A S06*

Valve Proving System VDK 200 A S06* Valve Proving System VDK 200 A S06* Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter

More information

VIESMANN. Service instructions VITOSOL 200-T, 300-T. for contractors. Vitosol 200-T, 300-T. For applicability, see the last page

VIESMANN. Service instructions VITOSOL 200-T, 300-T. for contractors. Vitosol 200-T, 300-T. For applicability, see the last page Service instructions for contractors VIESMANN Vitosol 200-T, 300-T For applicability, see the last page VITOSOL 200-T, 300-T 12/2008 Please keep safe. Safety instructions Safety instructions Please follow

More information

Valve Proving System VDK 200 A S02

Valve Proving System VDK 200 A S02 Valve Proving System VDK 200 A S02 Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter

More information

MD R a n g e O p e r a t o r s H a n d b o o k

MD R a n g e O p e r a t o r s H a n d b o o k MD R a n g e O p e r a t o r s H a n d b o o k Covering Models:- MD35/20 MD75/80 MD75/0 MD75/0V MD75/250 MD75/250V MD0/500 MD225/1000 BAMBI AIR COMPRESSORS LTD 2 Thimble Mill Lane Heartlands Birmingham

More information

Automatic Valve Proving Control

Automatic Valve Proving Control ISO 9001 Automatic Valve Proving Control 7 696 LDU11 UL recognized FM approved Features Performs leak test of the gas shut-off valves before start-up and/or immediately after burner shut-down No inlet

More information

matrix installation guide

matrix installation guide matrix installation guide Matrix pressurisation units These installation, commissioning and servicing instructions are intend for use with the matrix compact and standard pressurisation units. efore commencing

More information

Standard Operating and Maintenance Instructions for Pumping System Model PS-150

Standard Operating and Maintenance Instructions for Pumping System Model PS-150 Standard Operating and Maintenance Instructions for Pumping System Model PS-150 High Pressure Equipment Company, LLC 2955 West 17th Street, Suite 6 PO Box 8248 Erie, PA 16505 USA 814-838-2028 (phone) 814-838-6075

More information

OPERATING INSTRUCTIONS AND PARTS LIST AUTOMATIC FILLING MACHINE DE-401-GB-AUTO

OPERATING INSTRUCTIONS AND PARTS LIST AUTOMATIC FILLING MACHINE DE-401-GB-AUTO OPERATING INSTRUCTIONS AND PARTS LIST AUTOMATIC FILLING MACHINE DE-401-GB-AUTO www.adceng.co.za P O BOX 5413, JOHANNESBURG 2000 Phone: 011 493-8209 Fax: 011 493-1459 Email: adceng@mweb.co.za P O BOX 83,

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

553 Series.

553 Series. 38467.03 www.caleffi.com Pre-adjustable filling units Copyright 01 Caleffi 3 Series Function The automatic filling valve is a device consisting of a pressure reducing valve with compensating seat, visual

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The LDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS 0/05 OPERATING INSTRUCTIONS for gas pressure regulators PN0 with integrated slam shut valve (SSV) and integrated limited capacity safety relief valve (RV) MR 25 F0, MR 25 SF0 p e 20 kpa - 0 MPa (0,2-0

More information

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03 INSPIRED EF F ICIENCY PRESSURISATION UNITS MAXI P R ESSUR I SAT I O N U NI T S T E CH N I CAL D O CUMEN T A T I O N I SSUE 1 0 /1 7 R e v. 0 1 TABLE OF CONTENTS 1. 2. 3. 4. 5. 6. 7. 8. 9. Technical Data

More information

TANDEM MODULATOR FOR OUTLET GAS FLOW: STEPPED (836 TANDEM) - CONTINUOUS (837 TANDEM) SERVO-CONTROLLED PRESSURE REGULATOR

TANDEM MODULATOR FOR OUTLET GAS FLOW: STEPPED (836 TANDEM) - CONTINUOUS (837 TANDEM) SERVO-CONTROLLED PRESSURE REGULATOR SIT Group 836-837 TANDEM MULTIFUNCTIONAL GAS CONTROL MODULATOR FOR OUTLET GAS FLOW: STEPPED (836 TANDEM) - CONTINUOUS (837 TANDEM) SERVO-CONTROLLED PRESSURE REGULATOR ALL ADJUSTMENTS ACCESSIBLE FROM ABOVE

More information

Gas Pressure Regulator HON 300

Gas Pressure Regulator HON 300 Product information serving the gas industry worldwide Applications, characteristics, technical data Applications direct acting gas pressure regulator, for systems in accordance with DVGW working instruction

More information

Alhambra Arabic design, British engineering

Alhambra Arabic design, British engineering Alhambra Arabic design, British engineering A UNIQUE STYLE FOR ANY ENVIRONMENT / 036 / /// Unique inspiration and expertise Inspired by the original decorations of the Alhambra Palace in Granada, Spain,

More information

Tightness control TC. Product brochure GB 3 Edition AGA

Tightness control TC. Product brochure GB 3 Edition AGA Tightness control TC Product brochure GB 3 Edition 07.14 AGA Test of two safety valves Short test period thanks to logical decision-making in the program sequence Adjustable test period which can be adapted

More information

AutoChanger Installation & User Guide Issue 2

AutoChanger Installation & User Guide Issue 2 1 INDEX Page 1. Introduction... 3 2. AutoChanger Components Guide 4 3. Installation. 5-11 a) Installation Guidelines.. 5 b) Installation Retrofit... 6-11 c) Installation New... 11 4. AutoChanger User Guide

More information

Instruction Manual Contact Pressure Vacuum Gauge

Instruction Manual Contact Pressure Vacuum Gauge MS10 Instruction Manual Contact Pressure Vacuum Gauge Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance

More information

Installation, use and maintenance instructions. Gas burner (5)

Installation, use and maintenance instructions. Gas burner (5) Installation, use and maintenance instructions Gas burner MODEL GAS 4 TYPE 516 T80 291 (5) TECHNICAL FEATURES Thermal output 180-470 kw 154.800-404.200 kcal/h Fuel Natural gas Pci 8-10 kwh/m 3 = 7000-8600

More information

PROVENGAS AUTOMATIC PROVING SYSTEMS FOR GAS INSTALLATION

PROVENGAS AUTOMATIC PROVING SYSTEMS FOR GAS INSTALLATION PROVENGAS AUTOMATIC PROVING SYSTEMS FOR GAS INSTALLATION Provengas Labsafe PGLS001 Provengas Cooksafe PGCS003 2 Provengas Labsafe has been designed as a gas pressure proving system for use in schools and

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 348a 1. Description Viking supervised Surefire Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated Viking G-6000P Valve comes complete

More information

Manual Actuated Boiler Blowdown Valves

Manual Actuated Boiler Blowdown Valves Manual Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Operation 5. Maintenance 6. Spare parts p.1 1. Safety

More information

Installation, Operation & Maintenance Instructions

Installation, Operation & Maintenance Instructions Installation, Operation & Maintenance Instructions Please leave this instruction booklet with the home owner as it contains important guarantee, maintenance and safety information Read this manual carefully

More information

for Building facilities Industrial facilities etc.,multipurpose Pilot operated type(high capacity)

for Building facilities Industrial facilities etc.,multipurpose Pilot operated type(high capacity) for Building facilities Industrial facilities etc.,multipurpose Pilot operated type(high capacity This is a Pilot operated pressure reducing valve. It is suitable to install in the steam lines with the

More information

Installation, Operating and Maintenance Manual Overflow Regulator Type 94/ 94 E

Installation, Operating and Maintenance Manual Overflow Regulator Type 94/ 94 E Installation, Operating and Maintenance Manual Overflow Regulator Type 94/ 94 E Table of content 1. General information on installation, operating and maintenance instructions 1.1 Hazard notices 1.2 Qualified

More information

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10 LK product no: PCS 1-10 Article no: 74503 Revision:8 Article no: 74503 Revision: 8 2 (23) Contents 1. General information... 5 2. Safety precautions... 5 2.1 Significance of symbols... 5 2.2 Explanatory

More information

ELADOS EDP L Diaphragm Metering Pump Type

ELADOS EDP L Diaphragm Metering Pump Type ELADOS EDP L Diaphragm Metering Pump Type 04800-06700 Motor-driven diaphragm pump with integrated frequency converter High reserves due to a powerful asynchronous motor High flexibility due to variably

More information

Quantum Contract Pressurisation Unit Operation & Maintenance Manual. Model: QC-35

Quantum Contract Pressurisation Unit Operation & Maintenance Manual. Model: QC-35 Quantum Contract Pressurisation Unit Operation & Maintenance Manual Model: QC-35 1: nstallation Location The following should be considered when choosing the position of the pump set: The area should be

More information

Safety. Operating instructions Solenoid valve for gas VG 10/15 VG 65 DANGER. Contents WARNING CAUTION. Changes to edition 11.14

Safety. Operating instructions Solenoid valve for gas VG 10/15 VG 65 DANGER. Contents WARNING CAUTION. Changes to edition 11.14 2 Elster GmbH Edition. Translation from the German 22 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Solenoid valve for gas G / G Contents Solenoid valve for gas G / G....

More information

SG36KTL-M Quick Installation Guide. 1 Unpacking and Inspection

SG36KTL-M Quick Installation Guide. 1 Unpacking and Inspection SG36KTL-M Quick Installation Guide This guide provides a general instruction of the installation procedures of SG36KTL-M. In no case shall this guide substitute for the user manual or related notes on

More information

GAS PRESSURE CONTROL UNIT TYPE 132

GAS PRESSURE CONTROL UNIT TYPE 132 GAS PRESSURE CONTROL UNIT TYPE 132 OUR DIVERSITY IS YOUR PROFIT. Gas Pressure Regulator Type 132 Scope of Application Scope of type 132 gas pressure regulator is to maintain the output pressure at a constant

More information

11. Spare Parts. applications since applications since

11. Spare Parts. applications since applications since 2 8 2 6 20 2 8 0 5 6 8 9 2 2 25 7 8 9 5 0 2 2 7 . Spare Parts * C0 C02 C06 C0 C7 C C0 C5 C58 Article No. Description B-26 B-2009 Steam generation Steam cylinder CY DN20 compl. with electrodes and hand

More information

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions BAC 13310 IM-P133-42 ST Issue 2 M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning 5.

More information

Latvin Luxury Shower Panel. Telephone Product Specification. ~ Minimum Working Pressure 1.0 bar ~ Maximum Working Pressure 3.

Latvin Luxury Shower Panel. Telephone Product Specification. ~ Minimum Working Pressure 1.0 bar ~ Maximum Working Pressure 3. Product Specification ~ Minimum Working Pressure 1.0 bar ~ Maximum Working Pressure 3.0 bar Latvin Luxury Shower Panel ~ Fixing Centres 150mm +/- 10mm ~ Outlet size 1/2" Bottom Outlet Always maintain a

More information

INSTALLATION OPERATION MAINTENANCE

INSTALLATION OPERATION MAINTENANCE Bermad Electrically Controlled On-Off Deluge Valve Model: 400E-3D INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 1. Safety First BERMAD believes that the safety of personnel working

More information

Installation Instructions / Operating & Maintenance Manual Midi-Fill Digital Pressurisation Unit Models MFD15 & MFD22

Installation Instructions / Operating & Maintenance Manual Midi-Fill Digital Pressurisation Unit Models MFD15 & MFD22 Arrow Valves Ltd Installation Instructions / Operating & Maintenance Manual Midi-Fill Digital Pressurisation Unit Models MFD15 & MFD22 Tel 01442 823 123 Fax 01442 823 234 www.arrowvalves.co.uk Model shown

More information

Chesil - Electronic Pressurisation Unit

Chesil - Electronic Pressurisation Unit Chesil - Electronic Pressurisation Unit Equipment For Commercial/Light Industrial Central Heating Installations. Installation, Commissioning and Servicing Instructions IMPORTANT NOTE THESE INSTRUCTIONS

More information

JET Mini Mechanical Pressurisation Equipment

JET Mini Mechanical Pressurisation Equipment JET Mini Mechanical Pressurisation Equipment Mini Models (130HL, 230HL) Operation & Maintenance Manual Rev 2.2 We reserve the right to change designs and technical specifications of our products. Rev 2.2

More information

Pressure relief valve DHV 716 set range: 0,5-10,0 bar

Pressure relief valve DHV 716 set range: 0,5-10,0 bar Pressure relief valve DHV 7 set range: 0,5-0,0 bar Advantage pressure setting possible at any time, also during operation optimum monitoring valves high reproducibility of the set pressure high level of

More information

14. Exploded View. Page 68

14. Exploded View. Page 68 14. Exploded View Page 68 15. View of housing Page 69 11. Spare Parts HY05 HY13 55 E-2124010 Keys for safety, set=2pc. 54 E-2124012 Safety lock incl. 2 keys 1 B-3204031 1 B-2204101 1 B-2204111 1 2 B-2204105

More information

SG33KTL-M Quick Installation Guide. 1 Unpacking and Inspection

SG33KTL-M Quick Installation Guide. 1 Unpacking and Inspection SG33KTL-M Quick Installation Guide This guide provides a general instruction of the installation procedures of SG33KTL-M. In no case shall this guide substitute for the user manual or related notes on

More information

VIESMANN. Service instructions VITOSOL-F. for contractors. Vitosol-F. For applicability, see the last page GB 3/2009 Please keep safe.

VIESMANN. Service instructions VITOSOL-F. for contractors. Vitosol-F. For applicability, see the last page GB 3/2009 Please keep safe. Service instructions for contractors VIESMANN Vitosol-F For applicability, see the last page VITOSOL-F 3/2009 Please keep safe. Safety instructions Safety instructions Please follow these safety instructions

More information

Contents. Operating instructions. Pressure switch, heavy-duty version Model PSM-520

Contents. Operating instructions. Pressure switch, heavy-duty version Model PSM-520 Operating instructions Contents EN Pressure switch, heavy-duty version Model PSM-520 1. General information 2. Design and function 3. Safety 4. Transport, packaging and storage 5. Commissioning, operation

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 333a 1. Description Viking supervised Surefire Preaction Systems Utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated Viking G-3000P Valve comes complete

More information

TECHNICAL DATA. Trimpac 257a. September 16, 2013

TECHNICAL DATA. Trimpac 257a. September 16, 2013 September 16, 2013 Trimpac 257a 1. DESCrIpTION DESCRIPTION The Viking Double SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-2 and D-2B used with either a Model E or F Deluge Valve (A.1), a Viking

More information

SEQUENTIAL SHOWER VALVE INSTRUCTION MANUAL PLEASE LEAVE THIS MANUAL WITH THE END USER

SEQUENTIAL SHOWER VALVE INSTRUCTION MANUAL PLEASE LEAVE THIS MANUAL WITH THE END USER SEQUENTIAL SHOWER VALVE INSTRUCTION MANUAL PLEASE LEAVE THIS MANUAL WITH THE END USER CONTENTS 1. INTRODUCTION & SAFETY 1 2. DIMENSIONS 2 3. TECHNICAL DATA 3 4. OPERATION 4 5. COMPONENTS 5 6. SITE INSTALLATION

More information

Booster Regulator/Air Tank

Booster Regulator/Air Tank Booster Regulator/Air Tank Increase factory air pressure by up to 4 times! Air-only operation requires no power supply, reduces heat generation, and Boost pressure allows easy installation. NEW Renewed

More information

Instructions for SILEX 1C Mixed bed cartridge filter

Instructions for SILEX 1C Mixed bed cartridge filter D01B-30A-UK1 January 2017 Instructions for SILEX 1C Mixed bed cartridge filter With conductivity sensor Gravity flow or pressure installation SILHORKO-EUROWATER A/S Phone +45 86 57 12 22 DK-8660 Skanderborg

More information

Hydro Dome GRUNDFOS INSTRUCTIONS

Hydro Dome GRUNDFOS INSTRUCTIONS GRUNDFOS INSTRUCTIONS Hydro Dome Installation and operating instructions Montage- und Betriebsanleitung Notice d installation et d entretien Istruzioni di installazione e funzionamento Instrucciones de

More information

1. PARTS INTRODUCTION ELECTRICAL NOTES INSTALLATION 5/6. 5. START UP 6/7. 6. MAINTENANCE 7/8/9. 7. PRESSURE SWITCH ADJUSTMENTS 9/10.

1. PARTS INTRODUCTION ELECTRICAL NOTES INSTALLATION 5/6. 5. START UP 6/7. 6. MAINTENANCE 7/8/9. 7. PRESSURE SWITCH ADJUSTMENTS 9/10. CONTENTS 1. PARTS 3. 2. INTRODUCTION 4. 3. ELECTRICAL NOTES 5. 4. INSTALLATION 5/6. 5. START UP 6/7. 6. MAINTENANCE 7/8/9. 7. PRESSURE SWITCH ADJUSTMENTS 9/10. 8. ELECTRICAL CONNECTIONS 10/11. 9. SPECIFICATIONS

More information

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment 1. Application Emergency eyewash and eye/face wash equipment are prescribed first aid installations for workplaces

More information

TECHNICAL DATA. Trimpac 256a. October 31, 2013

TECHNICAL DATA. Trimpac 256a. October 31, 2013 October 31, 2013 Trimpac 256a 1. DESCRIPTION The Viking SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-1 and D- 1B used with either a Model E or F Deluge Valve (A.1), a Viking Easy Riser check valve

More information

Pressure Reducing Valve DMV 755

Pressure Reducing Valve DMV 755 Pressure Reducing Valve DMV 755 Nominal size DN 10 50 Nominal size 3/8 2 Nominal pressure PN 10 bar Features pressure setting range 1 to 9 bar control valve for reliable reduction of system pressures to

More information

INSTRUCTION MANUAL FOR MODEL 7360V VERTICAL CURING CHAMBER Revision E May

INSTRUCTION MANUAL FOR MODEL 7360V VERTICAL CURING CHAMBER Revision E May INSTRUCTION MANUAL FOR MODEL 7360V VERTICAL CURING CHAMBER Revision E May 2015 98-0520 S/N 2001 N. Indianwood Ave. Tulsa, Oklahoma 74012 U.S.A. TEL: (918) 250-7200 FAX: (918) 459-0165 E-mail: chandler.sales@ametek.com

More information

RP series Rotor Pumps

RP series Rotor Pumps ontact etails RP series Rotor Pumps Nomenclature Features Low noise Substantial reduction of the operation noise, by to db (comparison with aikin products), and improved sound quality are achieved by adopting

More information

KESSEL Aqadive Rainwater Management System with Control Unit Aqatronic and with Assembly package Aqaset

KESSEL Aqadive Rainwater Management System with Control Unit Aqatronic and with Assembly package Aqaset Installation, Operation and Maintenance Instructions KESSEL Aqadive Rainwater Management System with Control Unit Aqatronic and with Assembly package Aqaset Aqadive with Control Unit Aqatronic S Art.No.

More information

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES I N S T R U C T I O N - M A N U A L CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES FUNCTION: Conductivity level limit switches are based on the principle of measuring level through the electrical

More information

Pressure Relief Valve DHV 718

Pressure Relief Valve DHV 718 Advantages frictionless components low maintenance low pressure increase up to fully opened valve constant low vibration controlling hermetically sealed by diaphragm for oscillating pumps for viscous media

More information

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual Model GP-2000 PRESSURE REDUCING VALVE Installation & Operation Manual Please read this bulletin thoroughly before using the pressure reducing valve, so that you may do so correctly and safely. Please carefully

More information

book : t95575.fm Seite 1 Mittwoch, September 20, :10 AM. Avensys. Exposed Single Lever Mixer

book : t95575.fm Seite 1 Mittwoch, September 20, :10 AM. Avensys. Exposed Single Lever Mixer 955751.book : t95575.fm Seite 1 Mittwoch, September 20, 2000 10:10 AM Avensys Exposed Single Lever Mixer 33 389 33 396 Installation Instructions and Operating Guide Please leave this document with the

More information

Twin & Triple Control Concealed Thermostatic Shower Valve

Twin & Triple Control Concealed Thermostatic Shower Valve Twin & Triple Control Concealed Thermostatic Shower Valve Installation & Operating Guide Please leave this installation & user guide with the end user CONTENTS: 1. Introduction & Safety 1 2. Dimensions

More information

VERTICAL AIR COMPRESSORS

VERTICAL AIR COMPRESSORS VERTICAL AIR COMPRESSORS MODEL NO: VE11C150, VE15C150, VE18C150 PART NO: 2226005, 2226000, 2226015 OPERATION & MAINTENANCE INSTRUCTIONS LS0615 INTRODUCTION Thank you for purchasing this CLARKE Vertical

More information

BIMBAR INFLATABLE PACKERS AND ACCESSORIES

BIMBAR INFLATABLE PACKERS AND ACCESSORIES BIMBAR INFLATABLE PACKERS AND ACCESSORIES Geopro supplies a complete range of inflatable packers in nine different diameters from 28 up to 170mm. All our packers made of BIMBAR rubber technology are reinforced

More information

WE SAY: CLEANLY SEPARATED SYSTEMS = ELKO-MAT EDER!

WE SAY: CLEANLY SEPARATED SYSTEMS = ELKO-MAT EDER! elko-mat BACKFLOW PREVENTER WE SAY: CLEANLY SEPARATED SYSTEMS = ELKO-MAT EDER! Technical datasheet Ver.02/2017-en 1. Safety guidelines Follow the installation instructions Use the appliance according to

More information

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WTE-RODGERS 36E96-314 DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL

More information

Proportional Pressure-Relief Cartridge Valve, Size 2...4

Proportional Pressure-Relief Cartridge Valve, Size 2...4 Proportional Pressure-Relief Cartridge Valve, Size... Q max = l/min (6 gpm), p max = bar (58 psi) Direct acting, electrically operated Description proportional pressure-relief valves are direct acting

More information

SPIROVENT VACUUM DEGASSERS

SPIROVENT VACUUM DEGASSERS SPIROVENT VACUUM DEGASSERS S P I R O V E N T A I R S U P E R I O R FLUID AND GAS There are always a certain amount of gasses in a fluid, dependent on pressure and temperature. The British physicist William

More information

Pressure switches for air and water CS

Pressure switches for air and water CS Data sheet Pressure switches for air and water CS CS pressure switches have a built-in pressure operated, three-pole switch. The contact position of which depends on the pressure in the connector and the

More information

GRUNDFOS DATA BOOKLET. Hydro Solo-E. Complete pressure boosting systems 50/60 Hz

GRUNDFOS DATA BOOKLET. Hydro Solo-E. Complete pressure boosting systems 50/60 Hz GRUNDFOS DATA BOOKLET Complete pressure boosting systems 5/6 z Contents Product data Performance range 3 Operating conditions Inlet pressure Type key Product range 5 Construction 5 Installation 5 Mechanical

More information

AIR COMPRESSOR MANUAL INSTALLATION, OPERATION AND MAINTENANCE GUIDE

AIR COMPRESSOR MANUAL INSTALLATION, OPERATION AND MAINTENANCE GUIDE AIR COMPRESSOR MANUAL INSTALLATION, OPERATION AND MAINTENANCE GUIDE 1. DESCRIPTION The compressor is a reciprocating air pump mounted on and driven by an electric induction motor. Mounted on a sturdy frame

More information

Types and approvals. Page 1/6. Data Sheet

Types and approvals. Page 1/6. Data Sheet Page 1/6 Panel-mounting Thermostats EM Series as: Protection temperature monitor STW (STB) Protection temperature limiter STB tested to DIN 3440 and Pressure Equipment Directive 97/23/EC Brief description

More information

ServicePlus S21R & S27R Series 2 Installation Instructions

ServicePlus S21R & S27R Series 2 Installation Instructions ServicePlus S21R & S27R Series 2 Installation Instructions Horstmann Controls ServicePlus two channel service interval programmers have been developed to facilitate compliance with the Gas Safety (Installation

More information

Installation & Maintenance Instructions TEC-11N TIMER. Analogue electronic timer 02/09

Installation & Maintenance Instructions TEC-11N TIMER. Analogue electronic timer 02/09 Installation & Maintenance Instructions TEC-11N TIMER Analogue electronic timer 02/09 GENERAL OPERATION The TEC-11N timer is produced using SMT (Surface Mounting Technology), ensuring improved performance

More information

24L OIL FREE AIR COMPRESSOR MODEL NO: TIGER 7/250 PART NO: OPERATION & MAINTENANCE INSTRUCTIONS LS10/13

24L OIL FREE AIR COMPRESSOR MODEL NO: TIGER 7/250 PART NO: OPERATION & MAINTENANCE INSTRUCTIONS LS10/13 24L OIL FREE AIR COMPRESSOR MODEL NO: TIGER 7/250 PART NO: 2244030 OPERATION & MAINTENANCE INSTRUCTIONS LS10/13 INTRODUCTION Thank you for purchasing this product. Before attempting to use this product,

More information