Guidance on room integrity testing and its interpretation

Size: px
Start display at page:

Download "Guidance on room integrity testing and its interpretation"

Transcription

1 Guidance Note Guidance on room integrity testing and its interpretation

2 Guidance on room integrity testing and its interpretation 1. SCOPE INTRODUCTION AND BACKGROUND DEVELOPMENT OF INTEGRITY TESTING ENCLOSURE LEAKAGE CHARACTERISTICS STANDARDS FAN TEST PROCEDURE... 6 ANNEX A... 6 FAN TEST CHECK LIST... 6 ENCLOSURE GASEOUS SYSTEM FAN TEST PREPARATION CONDUCT FAN TEST CALCULATE ENCLOSURE LEAKAGE CALCULATE HOLD TIME ACTIONS HOLD TIME PASS ACTIONS HOLD TIME FAIL of 12

3 1. SCOPE This FIA guidance paper provides guidance and understanding on what is tested, how this is done and how to improve the outcome and achieve an acceptable result in relation to the door fan test. Note: Door Fan Test, Fan Test, and Room Integrity Test are used interchangeably within the industry. This document uses the term Door Fan Test. 2. INTRODUCTION AND BACKGROUND All gaseous fire extinguishing systems discharge their gas into an enclosure where the turbulent gas discharge creates a homogeneous mixture of the gas in air. During this process air and some gas is expelled from the enclosure due to over-pressurisation (caused but the injection of the volume of gas). The concentration of gas in air is at 30% greater than that needed to extinguish fire. Whilst this ensures that the fire is extinguished, the gas/air mixture provides little cooling of the source of the ignition, so the concentration of gas in air needs to be retained for a period after the end of discharge, sufficient to allow the ignition source to cool below its auto ignition temperature. This period is referred to in the gas system standards as the Hold Time Historical note: The failure of enclosures to retain the gas/air mixture for a sufficient period lead to fires re-igniting in Halon gas protected enclosures in the 1980s. The fire protection industry initially addressed this by performing discharge tests with concentration measurements to establish Hold Times. However, Halon was found to be one of the gases damaging the Ozone layer so Halon was phased out and the fire industry had to find another means of determining Hold Times for the gases which replaced Halon. Once the discharge has been completed the enclosure returns to normal atmospheric pressure filled with the homogeneous mixing of fire extinguishing gas and air. All these gases (with the exception of nitrogen) are heavier than air so the resultant gas /air mixture is also heavier than air thus producing a Column Pressure the pressure created at the base of the enclosure due to the weight of the gas/air mixture. As a result, the gas/air mixture escapes through lower level leaks and vent paths in the enclosure boundary. At the same time, air leaks into the upper part of the enclosure replacing the volume of gas/air as it escapes. Thus, the key to determining Hold Time is to establish the leakage characteristic of the enclosure. Annex A provides a check list of the steps to be taken in carrying out a door fan test Development of integrity Testing The energy conservation industry was, at the time of the Halon problem, already using variable speed fans to quantify the leaks in buildings for heat retention calculations so research was undertaken to seek correlations between enclosure leakage areas and the rate of loss of gas/air mixtures. The research showed that enclosure leak at different rates depending on: 3 of 12

4 The area of the openings The height of the openings The shape of the openings 2.2. Enclosure leakage characteristics Thus, it was determined that every enclosure had its own unique leakage characteristic which took the form: Q = C x Pn Where: Q = flow in litres /sec C = flow coefficient litres / sec P = column pressure pascals n = flow exponent These graphs are produced by taking a series of fan flow readings vs corresponding room pressures. Typically, the room pressures range from 10 to 60pa. This range is chosen because the upper limit is below that at which over pressure vents open and the lower one is above the pressure at which readings become unstable. The tests are carried out using pressurisation of the enclosure and repeated by depressurising the enclosure. The reason is that the pressurisation characteristic relates to the gas/air mixture flowing out, and the depressurisation characteristic relates to the air flowing in. It is usual to find that the two characteristics are different. The original research assumed that the gas/air mixture leaked from an enclosure similar to water draining from a tank, whereby the gas/air mixture was at the initial concentration where the mixture was present, and pure air above. This was referred to as sharp descending interface and used for the European and international standards. 4 of 12

5 Subsequent research found that, above the homogeneous layer, there formed a series of band layers of steadily decreasing gas concentration, which expended as the homogeneous layer descended. This was referred to as wide descending interface and used for the 2006 versions of the standards. It was also recognised that, in some enclosures, recirculating fans were not shut down prior to gas release and so continued to run providing continuous mixing of the gas and air in the enclosure. As a result, no descending interface is formed. 3. STANDARDS When the International Standards Organisation (ISO) formed its technical Committee to develop a standard for Gaseous Fire Extinguishing Systems Physical Properties and System Design, it chose the UK design guide (DD233) as its base document, which included a protocol for door fan testing and hold time modelling. This subsequently resulted in the publication of ISO Part 1 General Requirements with Annex E door fan test for determining minimum hold time. This was, in turn, adopted as the European standard EN with Annex C detailing the door fan test. (Both these were published in UK with BS prefixed i.e. BS ISO and BS EN ). In the 2000 editions of the ISO standard, the hold time pass criteria was for the extinguishing concentration at the height of the highest hazard in the enclosure. In the 2006 edition of the ISO standard and the 2008 edition of the EN standard this changed to 85% of the design concentration at 90% of the room height. This has changed again as, with both ISO and CEN agreeing to change to 85% of the design concentration at the height of highest hazard. This information is important because systems/enclosures are re-tested against the criteria which applied at the time the system was originally designed, installed, and the enclosure door fan tested. These annexes describe how the door fan test should be carried out but then provide the formulae to calculate the hold times under either descending interface or continuous mixing conditions. The gas/air mixture leaks out at its fastest rate when the leaks are equally divided between the top and the bottom of the enclosure. The ISO and EN standards provide formulae for both standard and non standard enclosures. Standard enclosures are those with a uniform horizontal cross sectional area and horizontal upper and lower boundaries. Non standard enclosures are those with a non uniform cross sectional area and non horizontal upper and/or lower cross sectional boundaries e.g. a room with a pitched roof. 5 of 12

6 The standards refer to this as an enclosure with a lower leakage fraction (the area of lower leaks divided by the total leakage area) of 0.5. As this produces the shortest hold time, the standards require that the initial hold time calculations are done on this assumption. If a pass is achieved no further action is required. However, if the required hold time is not achieved then remedial leak sealing is required. The door fan test can be useful in tracing leaks by pressurising the enclosure and using a smoke generator and following the smoke flows. Alternatively, ultrasonic leak detection may be used. Leaks should be sealed and the enclosure door fan test repeated. The need for remedial leak sealing is the responsibility of the client and not the fire protection contractor. The ISO and EN door fan test Annexes do allow for the door fan test engineer to measure/quantify upper/lower leakage areas to calculate a more accurate lower leakage fraction and to re-run the hold time calculation on this basis. Where the leakage areas are not equally split between upper and lower, the smaller openings will control the flow of the gas/air mixture and air at a slower rate than that for equal areas. 4. DOOR FAN TEST PROCEDURE a. Part 1 The doorway selected for the equipment will need to be open for the duration of the test, although it will be blocked off by an adjustable door frame. After carrying the equipment to the test enclosure, it is anticipated that the equipment set up will take approximately 1 hour. During this period, personnel would be free to walk in and out of the enclosure through any of the other entrances. A adjustable door frame (screen) is placed in the selected doorway/opening and a calibrated variable speed fan mounted in the screen opening, initially with the fan airway blanked off. Part of the set up involves running a small-bore flexible plastic tube from the protected enclosure to a reference area. (Usually this can be done in the room adjacent to the area under test). 6 of 12

7 After equipment set up, preparations for the actual test need to be finalised. This may involve opening and closing the other doors as required for the test. Signs should be posted to warn that the enclosure doors and associated doors are not to be opened/closed. Checks need to be made to ensure return air paths are open so that air that is venting from the enclosure during the tests flows back to the fan inlet so that no pressure differential exists between the fan inlet and enclosures adjacent to the protected enclosure. This may also require temporary removal of floor and ceiling tiles for the duration of the tests. 7 of 12

8 Prior to taking any readings, ensure all leakage areas are in the hold time condition by visual checking including the door closure or other opening selected for mounting the door fan. All air handling equipment that is expected to be shut down upon gas release must be shut down. At the very least, all air inlets and exhausts should be closed so that only fully re-circulating air is present. Readings of Bias Pressure will then be taken this is the pressure differential between the inside and outside of the enclosure with the fan unit sealed. The fan test readings are adjusted to take into account this pre-test pressure differential (This step will normally take 20 minutes.) Record the air temperatures inside and outside the enclosure (adjacent to the fan), and the local barometric pressure (these are required for the hold time calculations). However, if the bias pressure exceeds 3 Pa then remedial action is needed. The next step will require power to the fan equipment (120V or 240V A.C.). The fan is switched on, and varying quantities of air are blown into the protected enclosure to create positive pressures within the enclosure (These pressures will normally be in the range of pa). The quantity of air required to develop these pressures is recorded. Typically, 5 pressure stages should be taken to establish an accurate leakage characteristic. The fan should then be reversed and the tubing re-arranged for depressurization as below. In a reasonably well sealed enclosure, all readings will be completed in approximately 30 minutes (from the time the fresh air make-up is shut down). 8 of 12

9 b. Part 2 Following completion of the testing, the readings taken are entered into a computer along with details of the gas system, and the protected enclosure height and volume. The accuracy of the leakage characteristics should be checked i.e. the Correlation Coefficient should be better than A calculation of the predicted hold time at a required height is then carried out. A written report of the door fan test and the results and calculations should be provided. A typical report is provided at the end of this document. The enclosure should be provided with labels stating the date on which the door fan test was carried out. For larger and/or more leaky enclosures, two or more fans may be required to determine the leakage characteristics. c. Equivalent Leakage Area (E.L.A) The door fan test equipment and program are able to calculate the Equivalent Leakage Area of the enclosure. If all the leak paths in the enclosure boundary were consolidated into one hole this would be its area. This information can be used when determining the lower leakage fraction, and may also be used for overpressure vent area considerations. (See the FIA Guidance on the pressure relief and post discharge venting of enclosures protected by gaseous fire-fighting systems). N.B.: ISO definition of lower leakage fraction is: lower leakage fraction; effective leakage area of lower leaks divided by effective leakage area of all leaks d. Annual Re-testing The door fan test can be regarded as the gas system MOT for the enclosure. As such it applies to the enclosure and its associated gaseous fire extinguishing system on the day the door fan test was carried out. However, it is necessary to ensure that the gas system continues to provide effective protection throughout the service life of the protected risk. It is therefore essential that, as part of the routine inspection and maintenance procedures, the fan test and the hold time calculation is repeated annually (as required in ISO and EN standards) unless documentary evidence exists that no changes have been made to the protected enclosure. e. Remedial leak sealing Where an enclosure fails the door fan test, remedial sealing may be required. This may or may not be included in the scope of work of the organisation performing the door fan test. Where this is excluded, the test engineer may affect temporary seals as a means of establishing and quantifying the effects of leak paths; this for example may be by taping a sheet of paper over an open damper or grille or applying tape over the gaps around door openings. Any such temporary seals used to verify the effects of such openings must not be relied on as a permanent solution and must be removed for the final door fan test. 9 of 12

10 ANNEX A FAN TEST CONTRACTOR CHECK LIST Enclosure Enclosure name Measure enclosure height/volume Measure height of interest Ventilation shut down Y/N Temperature Leakage area of door used for test Gaseous System Agent type/quantity Design concentration System design continual mixing or descending interface Date of system installation or most recent modification British/International standard which system is designed to Standard or nonstandard enclosure equation Fan Test Preparation Equipment check/calibration Verify damper status open/closed Establish return air paths from leak openings back to the fan inlet (lift floor/ceiling tiles if required) Erect test signage (fan test in progress-do not enter) Mount fan test screen and fan in enclosure opening Replicate leakage area of test doorway Record temperature in enclosure and fan air inlet Record barometric pressure Measure bias pressures Conduct Fan Test Carry out pressurisation tests recording fan flows and enclosure pressures Carry out de-pressurisation tests recording fan flows and enclosure pressures 10 of 12

11 Calculate Enclosure Leakage Input enclosure name, date, and name of test engineer Input pressurisation test data fan flows and enclosure pressures Input de-pressurisation test data fan flows and enclosure pressures Input bias pressures Input barometric pressure Input temperatures within enclosure and at the fan inlet. Input standard or nonstandard enclosure classification Calculate enclosure pressurization leakage characteristic Calculate enclosure de-pressurization leakage characteristic Calculate average enclosure leakage characteristic Calculate Equivalent leakage Area (ELA) Check n value is between 0.5 and 1 Check correlation coefficients are above 0.99 Calculate Hold Time Input enclosure name, date, and name of test engineer Input agent type/quantity Input design concentration Input system design continual mixing or descending interface Input date of system installation or most recent modification Input required hold time Input F (Lower Leakage Fraction = 0.5 for initial calculation) Input height of interest Input system design continual mixing or descending interface Input enclosure leakage characteristics Calculate the hold time 11 of 12

12 Actions Hold Time Pass Calculated hold time exceeds required hold time no remedial action required Remove fan and fan screen Remove test signage Re-instate test specific enclosure changes made. Provide test report Record date of test Actions Hold Time Fail Locate major leak paths

Clean Agent Enclosure Design for ISO & AS4212

Clean Agent Enclosure Design for ISO & AS4212 Clean Agent Enclosure Design for ISO 14520 & AS4212 rev-2013-03-05 The Clean Agent Discharge Clean agent fire suppression systems are required in enclosures where a sprinkler system would cause damage

More information

Air Leakage Detailing & Awareness Services

Air Leakage Detailing & Awareness Services Tel: 08456 808048 Mob: 07866 948200 www.aldas.co.uk Info@aldas.co.uk Report on the Repeat Air Permeability Testing of the Passivhaus Refurbishment of: 57 Portfield Street, Hereford 16 th July 2010 Address:

More information

Overview ASTATT2. Prepare building for air tightness. testing

Overview ASTATT2. Prepare building for air tightness. testing Overview This standard is for those who carry out air tightness and/or change rate of buildings of any size or complexity. It covers those activities carried out to prepare the building for the conduct

More information

Guidance on the pressure relief and post discharge venting of enclosures protected by gaseous fire fighting systems

Guidance on the pressure relief and post discharge venting of enclosures protected by gaseous fire fighting systems Guidance on the pressure relief and post discharge venting of enclosures protected by gaseous fire fighting systems FIA Guidance for the Fire Protection Industry This Guidance Note is intended as a general

More information

Report on Pre-improvement Air Leakage Testing, in compliance with ATTMA TSL1 (2010)

Report on Pre-improvement Air Leakage Testing, in compliance with ATTMA TSL1 (2010) 54 Melville Road Churchdown Gloucester GL3 2RG Mob: 07866 948200 Report on Pre-improvement Air Leakage Testing, in compliance with ATTMA TSL1 (2010) Result: Unsatisfactory Site address: 8 Benson Place,

More information

This test shall be carried out on all vehicles equipped with open type traction batteries.

This test shall be carried out on all vehicles equipped with open type traction batteries. 5.4. Determination of hydrogen emissions page 1 RESS-6-15 5.4.1. This test shall be carried out on all vehicles equipped with open type traction batteries. 5.4.2. The test shall be conducted following

More information

Overview ASTATT3. Carry out air tightness testing for single dwellings and other small buildings

Overview ASTATT3. Carry out air tightness testing for single dwellings and other small buildings Overview This standard is for those who carry out air tightness and/or change rate testing of single dwellings and small up to a gross internal volume of 4000m³ inside the thermal line as defined by EN13829

More information

ASTATT10 Carry out air tightness testing on large and complex, high rise and phased hand over zonal buildings

ASTATT10 Carry out air tightness testing on large and complex, high rise and phased hand over zonal buildings Carry out air tightness testing on large and complex, high rise and phased Overview This standard is for those who carry out air tightness testing and inspection of large and complex buildings, high rise

More information

Airtightness Testing in Large Buildings: NESEA 2016

Airtightness Testing in Large Buildings: NESEA 2016 Airtightness Testing in Large Buildings: NESEA 2016 Dr John Straube, P.Eng. Associate Professor, University of Waterloo Principal, RDH Building Science This session: why would one invest in airtightness

More information

Field Evaluation of ASTM E in Relation to Control Room Habitability Testing and Boundary Maintenance in Nuclear Power Plants.

Field Evaluation of ASTM E in Relation to Control Room Habitability Testing and Boundary Maintenance in Nuclear Power Plants. Field Evaluation of ASTM E741-00 in Relation to Control Room Habitability Testing and Boundary Maintenance in Nuclear Power Plants. Presented By Clinton B. Summers Eric M. Banks NUCON International, Inc.

More information

Air Pressure Test to EN13829:2000

Air Pressure Test to EN13829:2000 Air Pressure Test to EN13829:2000 16 Kilgarron Park Enniskerry Co. Wicklow 2014-03-04 Pre-Renovation Test Directors: G Ó Sé, J Uí Shé 1 Table of Contents Introduction... 3 Pressure Test Result Summary...

More information

Health and Safety Executive/Local Authorities Enforcement Liaison Committee (HELA)

Health and Safety Executive/Local Authorities Enforcement Liaison Committee (HELA) Health and Safety Executive/Local Authorities Enforcement Liaison Committee (HELA) Local Authority Circular Subject: Food Industry Open Government Status: Open LAC Number: 31/2 Rev 1.0 Keywords: Fire and

More information

Report on the Preliminary Air Leakage Testing of 8 Benson Place in Oxford, in compliance with ATTMA TSL1 (2010)

Report on the Preliminary Air Leakage Testing of 8 Benson Place in Oxford, in compliance with ATTMA TSL1 (2010) Report on the Preliminary Air Leakage Testing of 8 Benson Place in Oxford, in compliance with ATTMA TSL1 (2010) Result: Satisfactory Site address: 8 Benson Place, Oxford, OX2 6QH Test Reference No.: ALDAS,

More information

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT OVERVIEW ASSESSING THE RISK RELATIONSHIP BETWEEN FIRES AND EXPLOSIONS CLASSIFYING HAZARDOUS AREAS INTO ZONES

More information

NZQA unit standard version 5 Page 1 of 5. Describe, develop, and maintain basic ventilation systems for an underground coal mine

NZQA unit standard version 5 Page 1 of 5. Describe, develop, and maintain basic ventilation systems for an underground coal mine Page 1 of 5 Title Describe, develop, and maintain basic ventilation systems for an underground coal mine Level 4 Credits 15 Purpose People credited with this unit standard are able to: describe the basic

More information

OCTOBER 2017 ISSUE Page 1 of 7

OCTOBER 2017 ISSUE Page 1 of 7 Field testing is performed on fully assembled pipelines for the purpose of determining pipeline acceptability. Following visual acceptance of joints and pipeline components, pressure pipelines in their

More information

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1 HANDBOOK Ed. 2017 DS-ED 01/2017 - ENG 1 CHAPTER 9 BURSTING DISC DEVICES IN SERIES 3070 SCOPE Use: protection against possible overpressure of the apparatuses listed below, with regard to the operating

More information

CTG Certification Protocol -- Version 3.0 SUMMARY

CTG Certification Protocol -- Version 3.0 SUMMARY Date of Test: Test Report Number: SUMMARY Date of Prior Certification: Certified by: Re-certification Due Date: Unit Description: Make : Model: Serial Number: Location: CERTIFIER INFORMATION Name: Client

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations

Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations Grzegorz Kubicki, Ph.D. Department of Environmental Engineering, Warsaw University of Technology

More information

Operation Manual. Software. FanTestic Integrity (complying with NFPA 2001) rev

Operation Manual. Software. FanTestic Integrity (complying with NFPA 2001) rev Operation Manual rev-2017-04-26 Software FanTestic Integrity (complying with NFPA 2001) Copyright 2017 Retrotec All rights reserved. This document contains materials protected under International and Federal

More information

4 Testing Agency Guide. 4.1 U.S. Army Corps of Engineers (USACE) Standard for Air Leakage

4 Testing Agency Guide. 4.1 U.S. Army Corps of Engineers (USACE) Standard for Air Leakage 10 4 Testing Agency Guide 4.1 U.S. Army Corps of Engineers (USACE) Standard for Air Leakage The USACE requires all new buildings and major renovation projects to pass an air leakage test where the results

More information

NSAI Agrément Approval Scheme for. Certified Air Tightness Tester Scheme Master Document

NSAI Agrément Approval Scheme for. Certified Air Tightness Tester Scheme Master Document NSAI Agrément Document Title Air Tightness Tester Page Page 1 of 10 Scheme NSAI Agrément Approval Scheme for Certified Master Document to I.S. EN ISO 9972:2015 - Thermal Performance of Buildings - Determination

More information

NZQA unit standard New US 1Non-coal of 7145 version 1 Page 1 of 5

NZQA unit standard New US 1Non-coal of 7145 version 1 Page 1 of 5 Page 1 of 5 Title Design and maintain effective ventilation systems for a non-coal underground operation Level 5 Credits 20 Purpose People credited with this unit standard are able to: explain the principles

More information

Gas Accumulation Potential & Leak Detection when Converting to Gas

Gas Accumulation Potential & Leak Detection when Converting to Gas Gas Accumulation Potential & Leak Detection when Converting to Gas Coal to Gas / PCUG Conference Chattanooga, TN October 29, 2013 Robert G. Mudry, P.E. Airflow Sciences Corporation Introduction Coal to

More information

TECHNICAL STANDARD L1. MEASURING AIR PERMEABILITY OF BUILDING ENVELOPES (DWELLINGS) October 2010 Issue

TECHNICAL STANDARD L1. MEASURING AIR PERMEABILITY OF BUILDING ENVELOPES (DWELLINGS) October 2010 Issue TECHNICAL STANDARD L1. MEASURING AIR PERMEABILITY OF BUILDING ENVELOPES (DWELLINGS) October 2010 Issue The Air Tightness Testing & Measurement Association c/o the British Institute of Non-Destructive Testing

More information

USING HAZOP TO IDENTIFY AND MINIMISE HUMAN ERRORS IN OPERATING PROCESS PLANT

USING HAZOP TO IDENTIFY AND MINIMISE HUMAN ERRORS IN OPERATING PROCESS PLANT USING HAZOP TO IDENTIFY AND MINIMISE HUMAN ERRORS IN OPERATING PROCESS PLANT Chris Lyth, Tracerco, Billingham, Cleveland, UK Ian Bradby, ABB Engineering Services, Billingham Cleveland, UK This joint paper

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

The evolution of the Ex-proof flame path

The evolution of the Ex-proof flame path April 2017 The evolution of the Ex-proof flame path As written in previous dissertation, the most critical part of a flameproof enclosure 'Ex d' is the flame path. Although the Standards are divided into

More information

Working Environment Safety Assessment

Working Environment Safety Assessment For your own safety and/or safety of your workforce, and to improve the efficiency of your business practices, you should be aware of, and be up to date with, the key safety issues and good practices relevant

More information

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply 4.1.1 General The primary function of a system for handling fuel oil is to transfer oil from the storage tank to the oil burner at specified conditions

More information

VENTILATION OF PROTECTED AREAS IN ROAD TUNNELS

VENTILATION OF PROTECTED AREAS IN ROAD TUNNELS - 187 - VENTILATION OF PROTECTED AREAS IN ROAD TUNNELS ABSTRACT Zumsteg F., Steinemann U. US+FZ Beratende Ingenieure, CH-5600 Lenzburg P. Wildi Civil Eng. Dept. Canton Grisons, CH-7000 Chur During the

More information

ACCUMULATION OF HYDROGEN RELEASED INTO A VENTED ENCLOSURE - EXPERIMENTAL RESULTS

ACCUMULATION OF HYDROGEN RELEASED INTO A VENTED ENCLOSURE - EXPERIMENTAL RESULTS ACCUMULATION OF HYDROGEN RELEASED INTO A VENTED ENCLOSURE - EXPERIMENTAL RESULTS Hooker, P. 1, Willoughby, D. 2, Hall, J. 3 and Hoyes, J. 4 1 Major Hazards Unit, HSL, Harpur Hill, Buxton, SK17 9JN, U.K,

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW, DOWNFLOW, UPFLOW/HORIZONTAL & HORIZONTAL ONLY INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this

More information

Mooney * Noise Controller Installation, Operation, and Maintenance Manual

Mooney * Noise Controller Installation, Operation, and Maintenance Manual GE Oil & Gas Mooney * Noise Controller Installation, Operation, and Maintenance Manual imagination at work Scope This manual provides instructions for installation, operation and maintenance of the Mooney

More information

Method Statement: Testing Dry Riser System

Method Statement: Testing Dry Riser System Method Statement: Testing Dry Riser System Page 1 of 6 Scope of work Test dry riser system in accordance with BS 5306. Definitions For the purposes of this document, the following definitions apply Rising

More information

ISO INTERNATIONAL STANDARD. Small craft Liquefied petroleum gas (LPG) systems

ISO INTERNATIONAL STANDARD. Small craft Liquefied petroleum gas (LPG) systems INTERNATIONAL STANDARD ISO 10239 Second edition 2008-02-15 Small craft Liquefied petroleum gas (LPG) systems Petits navires Installations alimentées en gaz de pétrole liquéfiés (GPL) Reference number ISO

More information

USER MANUAL. 1. Principle of operation. 2. Delivery condition. SPRING-LOADED SAFETY VALVES zarmak. Edition: 07/2016 Date: V (ex.

USER MANUAL. 1. Principle of operation. 2. Delivery condition. SPRING-LOADED SAFETY VALVES zarmak. Edition: 07/2016 Date: V (ex. ZETKAMA Sp. z o.o. ul. 3 Maja 12 PL 57-410 Ścinawka Średnia SPRING-LOADED SAFETY VALVES zarmak USER MANUAL 782V (ex. 782) Edition: 07/2016 Date: 01.07.2016 TABLE OF CONTENTS 1. Principle of operation 2.

More information

Report on Air Leakage Testing, in compliance with ATTMA TSL1 (2010) Site address: Cropthorne Autonomous House, WL10 3LZ. Autonomous House, Evesham

Report on Air Leakage Testing, in compliance with ATTMA TSL1 (2010) Site address: Cropthorne Autonomous House, WL10 3LZ. Autonomous House, Evesham Report on Air Leakage Testing, in compliance with ATTMA TSL1 (2010) Result: Satisfactory The Gaia Group 12/1 Gayfield Street Edinburgh EH1 3NR T: 0131 557 9191 M: 07866 948200 M: 07984 805 163 sandy@gaiagroup.org

More information

NZQA unit standard 7145 version 9 Page 1 of 5. Design and maintain effective ventilation systems for an underground coal mine

NZQA unit standard 7145 version 9 Page 1 of 5. Design and maintain effective ventilation systems for an underground coal mine Page 1 of 5 Title Design and maintain effective ventilation systems for an underground coal mine Level 5 Credits 20 Purpose People credited with this unit standard are able to, for an underground coal

More information

Operation Manual. rev Software. Clean Agent Retrotec Inc.

Operation Manual. rev Software. Clean Agent Retrotec Inc. Operation Manual rev-2013-12-02 Software Clean Agent 2001 Retrotec Inc. CleanAgent 2001 Version 2 Software License Agreement and Limited Warranty This is a legal agreement between you, the user of CleanAgent

More information

Valve Inspection & Testing

Valve Inspection & Testing Inspection & Testing in accordance with API 598 Valve Inspection & Testing Shell Test (Body Hydro Test): - Each valve shall be tested in accordance with ASME B 16.34 for ASME valves. Shell test pressure

More information

System Pressure Manager Standard & System Pressure Manager Plus

System Pressure Manager Standard & System Pressure Manager Plus System Pressure Manager Standard & System Pressure Manager Plus Installation, Commissioning & Servicing Instructions Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING,

More information

CORESTA RECOMMENDED METHOD N 6

CORESTA RECOMMENDED METHOD N 6 CORESTA RECOMMENDED METHOD N 6 DETERMINATION OF VENTILATION DEFINITIONS AND MEASUREMENT PRINCIPLES (2015 Revision September 2016) 1. SCOPE This CORESTA Recommended Method specifies a method for the determination

More information

METHOD 25A - DETERMINATION OF TOTAL GASEOUS ORGANIC CONCENTRATION USING A FLAME IONIZATION ANALYZER

METHOD 25A - DETERMINATION OF TOTAL GASEOUS ORGANIC CONCENTRATION USING A FLAME IONIZATION ANALYZER 1250 METHOD 25A - DETERMINATION OF TOTAL GASEOUS ORGANIC CONCENTRATION USING A FLAME IONIZATION ANALYZER 1.0 Scope and Application. 1.1 Analytes. Analyte CAS No. Sensitivity Total Organic Compounds N/A

More information

Getting the Most From Your Duct Blaster

Getting the Most From Your Duct Blaster Bob Davis, Ecotope Bruce Manclark, Delta T The Duct Blaster, made by the Energy Conservatory, or similar devices like it, is a durable, versatile calibrated fan/flexible duct assembly that accurately measures

More information

Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems

Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems Name of Property: Address: Phone Number: Inspector: Contract No.: Date: This Report Covers: Monthly Quarterly Annual Other

More information

Standard Pneumatic Test Procedure Requirements for Piping Systems

Standard Pneumatic Test Procedure Requirements for Piping Systems the pressure equipment safety authority Standard Pneumatic Test Procedure Requirements for Piping Systems AB-522 Edition 2, Rev. 1 Issued 2016-10-24 Table of Contents FOREWORD... 1 1.0 INTRODUCTION...

More information

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection 1170850/1 IM-P117-36 ST Issue 1 MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection Installation and Maintenance Instructions 1. Safety information 2. General product information

More information

Particularly with regard to CHAPTER 5 MEASURES TO BE TAKEN AGAINST AIR POLLUTION CAUSED BY TWO OR THREE- WHEEL MOTOR VEHICLES

Particularly with regard to CHAPTER 5 MEASURES TO BE TAKEN AGAINST AIR POLLUTION CAUSED BY TWO OR THREE- WHEEL MOTOR VEHICLES German-Dutch-Swedish proposal for EC amending Directives 97/24/EC, 2002/24/EC and 2003/77/EC of the European Parliament and of the Council which relating to evaporative emission control of two- or three-wheel

More information

A Rationale for Pressure Relief Device(s) Qualification Requirements (LH2)

A Rationale for Pressure Relief Device(s) Qualification Requirements (LH2) UN-GTR PART A INSERTION Stand 09.02.2011, 17:20 Uhr A.3.3 HYDROGEN STORAGE SYSTEM The hydrogen storage system consists of all components that form the primary pressure boundary of the stored hydrogen in

More information

Report on the Acceptance Air Leakage Testing of Rectory Cottage in Langattock, Powys, in compliance with ATTMA TSL1 (2010)

Report on the Acceptance Air Leakage Testing of Rectory Cottage in Langattock, Powys, in compliance with ATTMA TSL1 (2010) Report on the Acceptance Air Leakage Testing of Rectory Cottage in Langattock, Powys, in compliance with ATTMA TSL1 (2010) Site address: Rectory Cottage, Langattock, Crickhowell, Powys NP8 1PH Test Reference

More information

M-06 Nitrogen Generator (Nitrogen Making Machine)

M-06 Nitrogen Generator (Nitrogen Making Machine) Guideline No.M-06 (201510) M-06 Nitrogen Generator (Nitrogen Making Machine) Issued date: 20 th October, 2015 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains

More information

Leak testing of Valves. Standards for acceptable Rates of Valve Leakage

Leak testing of Valves. Standards for acceptable Rates of Valve Leakage Leak testing of Valves Standards for acceptable Rates of Valve Leakage American Petroleum Institute (API) The API standard 598: Valve Inspection and Testing, covers the testing and inspection requirements

More information

1 Scope... 2 Functions of cementing float equipment... 3 Definitions... 4 Calibration... 5 Test Categories... 6 General...

1 Scope... 2 Functions of cementing float equipment... 3 Definitions... 4 Calibration... 5 Test Categories... 6 General... American Petroleum Institute Contents Page 1 Scope... 2 Functions of cementing float equipment... 3 Definitions... 4 Calibration... 5 Test Categories... 6 General... 7 Apparatus and Materials... 8 High-temperature/high-pressure

More information

Kansas State University Fume Hood Operation

Kansas State University Fume Hood Operation FUME HOODS 2009, PAGE 1 FUME HOODS Kansas State University Fume Hood Operation One of the primary safety devices in a laboratory is a chemical fume hood. A well-designed hood, when properly installed and

More information

Validation of a Neutral Pressure Isolation Room

Validation of a Neutral Pressure Isolation Room Validation of a Neutral Pressure Isolation Room Andrew Fletcher, William Booth and Blanca Beato Arribas BSRIA Ltd., UK Corresponding email: Andrew.Fletcher@bsria.co.uk SUMMARY The principles behind a new

More information

HYPOXIC AIR FIRE PREVENTION SYSTEM TECHNICAL SPECIFICATION

HYPOXIC AIR FIRE PREVENTION SYSTEM TECHNICAL SPECIFICATION HYPOXIC AIR FIRE PREVENTION SYSTEM TECHNICAL SPECIFICATION Introduction: Hypoxic Air Fire Prevention System is a revolutionary fire prevention technology. It has the unique ability to create a breathable

More information

FXT. FXT Cooling Tower RIGGING & ASSEMBLY INSTRUCTIONS

FXT. FXT Cooling Tower RIGGING & ASSEMBLY INSTRUCTIONS FXT FXT Cooling Tower RIGGING & ASSEMBLY INSTRUCTIONS FXT Cooling Towers should be rigged and assembled as outlined in this bulletin. These procedures should be thoroughly reviewed prior to the actual

More information

ACS.CoNGLP1 SAFETY ASSESSMENT CRITERIA INITIAL & RE-ASSESSMENT DOMESTIC NATURAL GAS TO LPG GENERIC

ACS.CoNGLP1 SAFETY ASSESSMENT CRITERIA INITIAL & RE-ASSESSMENT DOMESTIC NATURAL GAS TO LPG GENERIC ACS.CoNGLP1 SAFETY ASSESSMENT CRITERIA INITIAL & RE-ASSESSMENT DOMESTIC NATURAL GAS TO LPG GENERIC Issue 4.2 ACS. SMB 1 CoNGLP1 INITIAL & RE-ASSESSMENT Range All LPG fittings. Comprises: 2. Gas emergency

More information

Module 6. Tightness Testing

Module 6. Tightness Testing Module 6 Tightness Testing IGE / UP / 1B New Tightness Testing Procedure Covers pipework up to 35mm and installation volumes of 0.035m3 Objectives By the end of Module 6, Tightness Testing and Direct Purging

More information

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS 1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS EXPLOSION PROTECTION In addition to the type approval and certification of industrial weighing systems concerned with accuracy, equipment that is also

More information

Smart Water Application Technologies (SWAT) TM

Smart Water Application Technologies (SWAT) TM Smart Water Application Technologies (SWAT) TM Equipment Functionality Test Protocol Version 2.3 June 2014 SWAT Committee 8280 Willow Oaks Corporate Drive Suite 400 Fairfax, VA 22031 www.irrigation.org

More information

AIR CONDITIONING AND PRESSURIZATION CONTROLS AND INDICATORS

AIR CONDITIONING AND PRESSURIZATION CONTROLS AND INDICATORS AIR CONDITIONING AND PRESSURIZATION CONTROLS AND INDICATORS Air conditioning control panel 1 MIN MAX Page 1 Air conditioning control panel 2 MIN MAX Page 2 Air conditioning control panel 3 MIN MAX Page

More information

IDEM Indiana Department of Environmental Management Office of Land Quality P.O. Box 6015 Indianapolis, IN OLQ PH: (317)

IDEM Indiana Department of Environmental Management Office of Land Quality P.O. Box 6015 Indianapolis, IN OLQ PH: (317) IDEM Indiana Department of Environmental Management Office of Land Quality P.O. Box 6015 Indianapolis, IN 46206-6015 OLQ PH: (317) 232-8941 Information SUBPART CC AIR EMISSION STANDARDS (40 CFR 264.1080

More information

DK46 - DK800 Supplementary instructions

DK46 - DK800 Supplementary instructions DK46 - DK800 Supplementary instructions Variable area flowmeter Device category II2G with electrical internals Additional Ex manual KROHNE CONTENTS DK46 - DK800 1 Safety instructions 3 1.1 General... 3

More information

CONTROL VALVE SEAT LEAKAGE

CONTROL VALVE SEAT LEAKAGE ANSIIFCI 70-2-2006 AMERICAN NATIONAL STANDARD CONTROL VALVE SEAT LEAKAGE \D o N I N I o ~ H U ~ H [/) ~ Fluid Controls Institute, Inc. Spo~sor: Fluid Controls institute, inc. 1300 Sumner Ave Cleveland,

More information

Assembly and Installation Procedures

Assembly and Installation Procedures Assembly and Installation Procedures for Pall Supracap 100 Capsules 1. Introduction The following procedures must be followed for the installation of Pall Supracap 100 Capsules. The instructions contained

More information

Getting the Most From Your Diagnostic Equipment

Getting the Most From Your Diagnostic Equipment Getting the Most From Your Diagnostic Equipment Tuesday, February 20, 2007 2007 Annual RESNET Conference San Diego, CA Joe Kuonen Building Performance Institute Learning Objectives Diagnostic tools and

More information

TEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125

TEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125 TEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125 Model: VC-40-VYC Table of contents 1. - Installing the test bench 1.1.1- Connecting the compressed air / nitrogen source 1.1.2- Maximum test pressure according

More information

Informal document regarding progress of CEN standards for reference in RID/ADR

Informal document regarding progress of CEN standards for reference in RID/ADR Joint Meeting of the RID Safety Committee and the Working Party on the Transport of Dangerous Goods (Berne, 13-24 March 2000) Informal document regarding progress of CEN standards for reference in RID/ADR

More information

Pressure Piping Code-Industrial Piping. Part 6: Safeguarding

Pressure Piping Code-Industrial Piping. Part 6: Safeguarding ICS 23.040 J74 National Standard of the People's Republic of China GB/T 20801.6-2006 Pressure Piping Code-Industrial Piping Part 6: Safeguarding ffi1jtfil~ju1t1 I~tfil ~6$?t: ~~~1? Issued on: December

More information

Specific Accreditation Criteria Calibration ISO IEC Annex. Mass and related quantities

Specific Accreditation Criteria Calibration ISO IEC Annex. Mass and related quantities Specific Accreditation Criteria Calibration ISO IEC 17025 Annex Mass and related quantities January 2018 Copyright National Association of Testing Authorities, Australia 2014 This publication is protected

More information

STANDARD PROCEDURE OF A TIGHTNESS TEST OF A SOLAR COLLECTOR BOX. (EUROSUN 2000 SOLAR CONGRESS)

STANDARD PROCEDURE OF A TIGHTNESS TEST OF A SOLAR COLLECTOR BOX. (EUROSUN 2000 SOLAR CONGRESS) STANDARD PROCEDURE OF A TIGHTNESS TEST OF A SOLAR COLLECTOR BOX. (EUROSUN 2000 SOLAR CONGRESS) Ole Holck and Svend Svendsen Department of Buildings and Energy, Technical University of Denmark Building

More information

CONTROL VALVE TESTING

CONTROL VALVE TESTING The optimal functioning of the Control valve not only exists of sufficient body & seat tightness, but more important, the total "performance" of the valve and its controls! For an accurate and reliable

More information

Workhorse-15 Oxygen Generator

Workhorse-15 Oxygen Generator 11436 Sorrento Valley Road, San Diego CA 92121 USA 858-558-0202 Fax 858-558-1915 Workhorse-15 Oxygen Generator Model No. 5719, 5727, 5735 for Domestic and International Units Part number 1432 Revision

More information

Instruction Manual Dräger MSI P7 and MSI P7 plus

Instruction Manual Dräger MSI P7 and MSI P7 plus Dräger MSI GmbH Rohrstraße 32 58093 Hagen Tel.: +49-2331 / 9584-0 Fax: +49-2331 / 9584-29 e-mail: info@draeger-msi.de D 923; Edition 2011-01-01 Content 1. General Hints Page 4 2. The Instrument 2.1 Front

More information

Government of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE

Government of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE Government of Bermuda Department of Maritime Administration 2015 027 BERMUDA SHIPPING NOTICE Maintenance and Inspection of Fixed Carbon Dioxide Fire Extinguishing Systems Ref: SOLAS 74/88 as amended, Regulation

More information

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE - 247 - AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE J D Castro a, C W Pope a and R D Matthews b a Mott MacDonald Ltd, St Anne House,

More information

Improving Accuracy of Frequency Estimation of Major Vapor Cloud Explosions for Evaluating Control Room Location through Quantitative Risk Assessment

Improving Accuracy of Frequency Estimation of Major Vapor Cloud Explosions for Evaluating Control Room Location through Quantitative Risk Assessment Improving Accuracy of Frequency Estimation of Major Vapor Cloud Explosions for Evaluating Control Room Location through Quantitative Risk Assessment Naser Badri 1, Farshad Nourai 2 and Davod Rashtchian

More information

INOGATE Technical Secretariat UK Experience European Standards Implementation Key Expert Phil Winnard Session 2 Georgia, October 2015

INOGATE Technical Secretariat UK Experience European Standards Implementation Key Expert Phil Winnard Session 2 Georgia, October 2015 INOGATE Technical Secretariat UK Experience European Standards Implementation Key Expert Phil Winnard Session 2 Georgia, October 2015 BUILDING PARTNERSHIPS FOR ENERGY SECURITY www.inogate.org EN 12186

More information

LNG Marine Loading Arms and Manifold Draining, Purging and Disconnection Procedure

LNG Marine Loading Arms and Manifold Draining, Purging and Disconnection Procedure LNG Marine Loading Arms and Manifold Draining, Purging and Disconnection Procedure i The Society of International Gas Tanker and Terminal Operators (SIGTTO) The Society of International Gas Tanker and

More information

The Protection of Silos From Over. Pressurisation During Filling

The Protection of Silos From Over. Pressurisation During Filling SHAPA Technical Bulletin No.11 The Protection of Silos From Over Pressurisation During Filling Page 1 of 8 August 2005 The Protection of Silos From Over Pressurisation During Filling By James Duggleby,

More information

Drum / cylinder handling

Drum / cylinder handling Page 1 of 8 Drum / cylinder handling This Technical Measures Document covers the storage and handling of toxic and flammable substances in drums and cylinders and refers to relevant codes of practice and

More information

Steam Trap BK 15 (DN40, DN 50) Original Installation Instructions English

Steam Trap BK 15 (DN40, DN 50) Original Installation Instructions English Steam Trap BK 15 (DN40, DN 50) EN English Original Installation Instructions 810682-03 1 Contents Page Important Notes Usage for the intended purpose... 4 Safety note... 4 Danger... 4 Attention... 4 Application

More information

CAST IRON SAFETY VALVE TYPE 6301

CAST IRON SAFETY VALVE TYPE 6301 CHARACTERISTICS The 6301 safety valve is dedicated to protect the equipment from potential overpressure. This is an automatic device that closes when the pressure conditions are back to normal. It is a

More information

DNVGL-CP-0187 Edition March 2016

DNVGL-CP-0187 Edition March 2016 CLASS PROGRAMME Type approval DNVGL-CP-0187 Edition March 2016 The electronic pdf version of this document, available free of charge from http://www.dnvgl.com, is the officially binding version. FOREWORD

More information

VACUVENT Valve functions - benefits - flowpath - VG series - Sewage

VACUVENT Valve functions - benefits - flowpath - VG series - Sewage 01 VG Series air release and vacuum break valves Operation and benefits The topic of sizing and placement is significant and complex the purpose of this document is simply to point out important considerations

More information

Chapter 7. Coal Cargoes. Properties and Characteristics 7.1

Chapter 7. Coal Cargoes. Properties and Characteristics 7.1 Chapter 7 Coal Cargoes This chapter, and all of the chapters in Part 2, should be read in conjunction with the booklet Carrying Solid Bulk Cargoes Safely (Reference 16), published by Lloyd s Register/UK

More information

MEDICAL REGULATOR RANGE (MEDIREG RANGE)

MEDICAL REGULATOR RANGE (MEDIREG RANGE) MEDICAL REGULATOR RANGE (MEDIREG RANGE) Medireg Dialreg Flowreg INSPECTION Remove the Medireg from the packaging and inspect for damage. If there is any damage, DO NOT USE, and contact Therapy Equipment

More information

New Hampshire Public Utilities Commission CFR 49 Part 192 Regulations. MINIMUM Pipeline Safety Regulations

New Hampshire Public Utilities Commission CFR 49 Part 192 Regulations. MINIMUM Pipeline Safety Regulations New Hampshire Public Utilities Commission CFR 49 Part 192 Regulations MINIMUM Pipeline Safety Regulations Application for Jurisdictional LPG Operators 1 Pipeline Safety Regulations 49 CFR Part 192 (NOTE:

More information

High-Pressure Boiler Inspection Procedures: A Complete Checklist

High-Pressure Boiler Inspection Procedures: A Complete Checklist High-Pressure Boiler Inspection Procedures: A Complete Checklist Inspecting high-pressure boilers is a complex process requiring preparation, planning, and a multitude of safety precautions. Regular inspections

More information

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV 16-1 INTRODUCTION 16-1.1 Purpose. The purpose of this chapter is to familiarize divers with the techniques used to mix divers breathing gas. 16-1.2 Scope. This chapter

More information

Oxygen Dialflow Meter. Instructions for Use

Oxygen Dialflow Meter. Instructions for Use Oxygen Dialflow Meter Instructions for Use 702-0031.9 May 2014 1. Symbols Warning! Caution! Indicates a potentially hazardous situation which, if not avoided, could result in personal injury to the user

More information

SMOKE CONTROL DOORS AND SHUTTERS

SMOKE CONTROL DOORS AND SHUTTERS FIRE AND SECURITY EGOLF WORKSHOP Hosted by The January 30th and 31th 2018, Copenhagen, Denmark SMOKE CONTROL DOORS AND SHUTTERS There are several problematic issues in standard EN 1634-3. See the enclosed

More information

Transport of gas tanks for motor vehicles

Transport of gas tanks for motor vehicles United Nations Secretariat ST/SG/AC.10/C.3/2016/51 Distr.: General 30 August 2016 Original: English Committee of Experts on the Transport of Dangerous Goods and on the Globally Harmonized System of Classification

More information

METHODS TO PREVENT THE PREMATURE ACTIVATION OF RELIEF DEVICES ON TRANSPORT TANKS

METHODS TO PREVENT THE PREMATURE ACTIVATION OF RELIEF DEVICES ON TRANSPORT TANKS METHODS TO PREVENT THE PREMATURE ACTIVATION OF RELIEF DEVICES ON TRANSPORT TANKS IGC Doc 184/14/E EUROPEAN INDUSTRIAL GASES ASSOCIATION AISBL AVENUE DES ARTS 3-5 B 1210 BRUSSELS Tel: +32 2 217 70 98 Fax:

More information

Assessing Permeation of Gas through Polyethylene Pipe

Assessing Permeation of Gas through Polyethylene Pipe Assessing Permeation of Gas through Polyethylene Pipe REPORTS Introduction Gas Distribution Networks (GDNs) regularly review the Shrinkage and Leakage model (SLM) to further enhance the reporting of Shrinkage

More information

ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN

ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN (This page intentionally blank) ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN TABLE OF CONTENTS O- Definitions... O- Objective... O- Design

More information

AC : MEASUREMENT OF HYDROGEN IN HELIUM FLOW

AC : MEASUREMENT OF HYDROGEN IN HELIUM FLOW AC 2010-2145: MEASUREMENT OF HYDROGEN IN HELIUM FLOW Randy Buchanan, University of Southern Mississippi Christopher Winstead, University of Southern Mississippi Anton Netchaev, University of Southern Mississippi

More information