Type 3 - PSA Nitrogen Generation System

Size: px
Start display at page:

Download "Type 3 - PSA Nitrogen Generation System"

Transcription

1 Type 3 - PSA Nitrogen Generation System Designed for: Dry or Pre-Action Fire Protection Systems (FPS) with a total capacity from 6,000 to 18,000 gallons 1.0 Nitrogen Generation Corrosion Inhibiting System 1.1 The Fire Sprinkler Contractor shall provide all required equipment, materials, labor and services needed to install a complete and operational Nitrogen Generation Corrosion Inhibiting System in order to service all dry and/or pre-action Fire Protection Systems (FPS), or as directed per the Design Engineer. Installation guidelines by the manufacturer shall be followed Nitrogen Generation System Nitrogen Generation System Feed Air (Compressor) Packages Leak Detection System Fire Protection System Gas Purging Device Supervisory Gas Monitoring Device Nitrogen Purity Senor Air Maintenance Device System Installation Protocol System Startup and Technical Training 2.0 Nitrogen Generation System 2.1 The Fire Sprinkler Contractor shall provide and install a MICBlast FPS - Type 3 PSA (Pressure Swing Absorption) Nitrogen Generation System per the Nitrogen Generator Sizing Chart (2.12) 2.2 A single MICBlast FPS - Type 3 PSA Nitrogen Generation System shall provide Supervisory Pressure between 0-60 PSI to no more than (10) zones (zone = sprinkler piping plumbed from a single riser). 2.3 The MICBlast FPS - Type 3 PSA Nitrogen Generation System (FPS-2000 & FPS-3000) cabinet shall be floor mounted, with dimensions of 63 H x 20 W x 24 D (730 lbs). 2.4 The MICBlast FPS - Type 3 PSA Nitrogen Generation System shall provide a minimum of 95% Nitrogen purity to the FPS. 2.5 The MICBlast FPS - Type 3 PSA Nitrogen Generation System shall include a set of Particulate, Coalescing, and Absorbing filters (within the cabinet), sized properly for the required Compressed Air IN flow rates. 2.6 The Nitrogen purity outputted by the MICBlast FPS - Type 3 PSA Nitrogen Generation System shall be monitored and verified via a hand held portable or wall mounted stationary Quick- Check - Nitrogen Purity Sensor (see section 6.0). 2.7 The MICBlast FPS - Type 3 PSA Nitrogen Generation System shall be powered by 120V AC requiring an 8 AMP circuit. 2.8 The Fire Sprinkler Contractor shall run a ½ copper, galvanized, or black steel pipe or approved flex hosing, rated at 175 PSI compressed air line from the Air Compressor to the MICBlast FPS - Type 3 PSA Nitrogen Generation System. 2.9 For each MICBlast FPS Type 3 PSA Nitrogen Generation System the manufacturer shall provide a single (80) gallon Nitrogen Storage Tank. The Nitrogen Storage Tank shall be DOT or ASME rated for 240 PSI and shall be provided with ASME rated 100 PSI Safety Relief valve, on/off valve, and ¼ NPT I/O fitting.

2 2.10 The MICBlast FPS Type 3 PSA Nitrogen Generation System and Nitrogen Storage Tank shall be plumbed by the Sprinkler Contractor using ½ copper, galvanized or black steel pipe or approved flex hosing, rated at 175 PSI per drawing (2.13) An Air Compressor shall be furnished and piped to provide feed air to the MICBlast FPS - Type 3 PSA Nitrogen Generation System. An air compressor by-pass shall also be installed so that either compressed air or Nitrogen can be sent to the Air Maintenance Device/s (see Drawing Set 2.13) The Air Compressor shall be sized to achieve the 30 minute fill per the NFPA 13 Requirements (see Air Compressor Sizing Chart 3.4) ½ copper, galvanized or black steel pipe or approved flex hosing, rated at 175 PSI shall be used when plumbing from MICBlast FPS - Type 3 PSA Nitrogen Generation System to the Nitrogen Storage Tank, then to the Air Maintenance Device/s Nitrogen Generator Sizing Chart (2.12) MICBlast - FPS "Type 3" Series Nitrogen Generator Feed Air Requirements MICBlast Model FPS gal Capacity* Dimensions Power Req. Amps SCFM Min. Working Pressure (PSI) FPS-2000 up to Gal 63 H x 20 W x 24 D 120V PSI FPS-3000 up to Gal 63 H x 20 W x 24 D 120V PSI * MICBlast Sizing: Add the gallons of each zone together to get the sum of all zones and then size the system accordingly Drawing Set (2.13) 2.14 Nitrogen Generation System Compliances The MICBlast - Nitrogen Generation Corrosion Inhibiting System shall be designed, installed, tested, inspected and maintained to comply with all codes and standards relevant to the following specifications:

3 NFPA 13 : Standard for Installation of Sprinkler Systems NFPA 25 : Standard for the Inspection, Testing and Maintenance of Water- Based Fire Protection Systems (FPS) All devices and products will be in compliance with Section (3) of NFPA13, Standard for the Installation of Sprinkler Systems, 2007 Edition. 3.0 Nitrogen Generation System Feed Air (Compressor) Packages 3.1 An Air Compressor shall be furnished and installed to both fill the largest zone of the FPS to pressure within 30 minutes per NFPA 13 Requirements and also provide clean, dry, oil free compressed feed air to the MICBlast FPS - Type 3 PSA Nitrogen Generation System The Air Compressor shall be sized to achieve the 30 minute fill per the NFPA 13 Requirements (see Air Compressor Sizing Chart in Section 3.4) The Air Compressor shall be oil bathed and provided with an aftercooler, automatic tank drain, coalescing filter and either a membrane or refrigerated air dryer package ½ copper, galvanized, black steel or approved flex hosing rated at 175 PSI shall be used when plumping the Air Compressor A bypass shall be installed when piping the Air Compressor and the MICBlast - Type 3 PSA Nitrogen Generation System to the Air Maintenance Device/s (see Drawing Set 2.13). Ball valves shall be installed in line with the piping going to the Air Maintenance Device/s so either air from the Air Compressor or Nitrogen from the MICBlast - Type 3 PSA Nitrogen Generation System can be used to provide Supervisory Pressure to the FPS. 3.2 The Air Compressor shall be provided with a pressure switch to be field adjusted. 3.3 Electrical shall be provided for the Air Compressor per the manufacturers specifications. 3.4 Air Compressor Sizing Chart (3.4) Air Compressor Options Feed Air** Min. Gal. filled in 30 Min. (NFPA 13) Air Compressor Class* Dimensions Power Requirements Amps SCFM Working Pressure to (20 PSI) S.P. to (40 PSI) S.P. STS-NF-C-1-J Standard 22"W x 37"L x 25"H V/60Hz/1ph 11.1 / PSI 400 Gal 200 Gal STS-NF-C-2-J Standard 22"W x 37"L x 30"H V/60Hz/1ph 10.6 / PSI 550 Gal 275 Gal STS-NF-C-3-J Standard 20"W x 39"L x 34"H V/60Hz/1ph 18.4 / PSI 1000 Gal 500 Gal STS-NF-C-4-J Standard 21"W x 39"L x 36"H 230V/60Hz/1ph PSI 2200 Gal 1100 Gal STS-NF-C-5-J Standard 22"W x 39"L x 38"H 230V/60Hz/1ph PSI 3400 Gal 1700 Gal STS-NF-C-6-J Standard 25"W x 63"L x 47"H 230V/60Hz/1ph PSI 4450 Gal 2225 Gal STS-NF-C-7-J Standard 25"W x 63"L x 47"H V/60Hz/3ph 25/ PSI 5700 Gal 2850 Gal STS-NF-C-2 Upgrade 23 W x 56 L x 50 H V/60Hz/3ph 15.8 / PSI 1400 Gal 700 Gal STS-NF-C-3 Upgrade 23 W x 56 L x 50 H V/60Hz/3ph 21.2/ PSI 2800 Gal 1400 Gal STS-NF-C-4 Upgrade 25 W x 60 L x 56 H V/60Hz/3ph 38.4/ PSI 4250 Gal 2125 Gal *Class: The Standard oil bathed piston operated Air Compressor option will provide pure, clean air to the MICBlast FPS Type 3 Series Nitrogen Generator however the Upgrade option is an industrial grade, low db (quiet), rotary screw oil lubricated compressor with refrigerated dryer. **Air Compressor Sizing: Air compressor must be sized to provide the minimum feed air requirements to the MICBlast FPS - Type 3 PSA Nitrogen Generation System. Also check to make sure that the air compressor complies with NFPA 13 requirements ( ), and will fill the largest zone to supervisory pressure within 30 minutes. If it does not comply, upsize air compressor accordingly.

4 4.0 Leak Detection System 4.1 The MICBlast FPS - Type 3 PSA Nitrogen Generation System shall be designed with an internal BlastOff - Leak Detection System containing an isolated dry contact rated up to 240VAC 16amps (NC&NO Contacts available). The Fire Sprinkler Contractor shall run a DC or AC signal line in ½ code approved electrical conduit from the MICBlast FPS - Type 3 PSA Nitrogen Generation System to the supervisory circuit on the Building Monitoring System The BlastOff - Leak Detection System is to send a signal to the Building Monitoring System should significant leaks develop within the FPS piping, prior to them becoming catastrophic and causing supervisory pressure to fall below specification. These leaks shall be addressed at that time by the Fire Sprinkler Contractor in order to minimize unnecessary runtime on the MICBlast - Type 3 PSA Nitrogen Generation System. 5.0 Fire Protection System Gas Purging Device 5.1 A single MICBlast - AutoPurge System shall be installed at the end of each Zone, at a high point within the FPS (see Drawing Set 5.6). 5.2 The AutoPurge System shall not require any electrical connection AC or DC. 5.3 The MICBlast - AutoPurge System shall have a connection allowing the Quick-Check - Portable or Fixed Nitrogen Purity Sensor to attach and sense the purity of Nitrogen within the FPS to ensure that proper Nitrogen purity levels have been attained. 5.4 The Fire Sprinkler Contractor shall adjust each MICBlast - AutoPurge System to purge the FPS per the MICBlast - AutoPurge System manufactures specifications outlined within the sizing chart located on the device. 5.5 The Fire Sprinkler Contractor shall confirm that the ball valve on each MICBlast - AutoPurge System is left in the open position during normal operation and shut off/taken out of service during hydro or static testing by turning the ball valve to the closed position. 5.6 Drawing Sets (5.6)

5 6.0 Supervisory Gas Monitoring Device Nitrogen Purity Sensor 6.1 Furnish either (1) Quick-Check - Portable Hand Held Nitrogen Purity Sensor per MICBlast FPS - Type 3 PSA Nitrogen Generation System and/or (1) Quick-Check - Fixed Mount Nitrogen Purity Sensor per Riser Room (to be installed on the largest zone) The battery operated Quick-Check - Portable Hand Held Nitrogen Purity Sensor is to be connected during periodic inspections to the end of the MICBlast - AutoPurge System (see Drawing Set 5.6) to obtain a quick purity reading of the Nitrogen content within the FPS The Quick-Check - Fixed Mount Nitrogen Purity Sensor shall be wall mounted within 5 of a MICBlast - AutoPurge System located near the end of the largest zone (the Design Engineer can choose to recommend (1) of these devices per Zone if desired) The Fire Sprinkler Contractor shall provide 110V AC power to the Quick- Check - Fixed Mount Nitrogen Purity Sensor and also a single twisted pair signal line in ½ code approved electrical conduit for an isolated dry contact rated up to 240VAC 16amps (NC&NO contacts available) to the supervisory circuit on the Building Monitoring System. 7.0 Air Maintenance Device (Note: Supplied by the Sprinkler Contractor) 7.1 The Air Maintenance Device shall be equipped with an adjustable pressure regulator (sized to meet Supervisory Pressure settings) for setting the maximum pressure on the FPS. 7.2 The Air Maintenance Device shall not contain a pressure switch. 7.3 The Air Maintenance Device shall be installed per the manufacturer s specifications. 8.0 System Installation Protocol 8.1 As specified by the Design Engineer, a MICBlast FPS Type 3 PSA Nitrogen Generation System shall be installed. Installation instructions as directed by the manufacturer shall be followed. An optional Corrosion Monitoring System is available upon request and shall be installed by the Sprinkler Contractor. The BlastOff, Quick-Check and MICBlast - AutoPurge System accessories shall be installed by the Sprinkler Contractor and no party shall remove or tamper with the devices The following services to be completed during installation of the Nitrogen Generation System: Installation: MICBlast FPS Type 3 PSA Nitrogen Generation System Related products (see 3.0 thru 7.0) As required, all piping, fittings, valves etc System compliance and pressure (leak) testing 8.2 Operating pressure range of the Dry or Pre-Action FPS shall be determined by the Fire Sprinkler Contractor. The Fire Sprinkler Contractor shall also set the system Air Maintenance Device accordingly for each zone to the proper setting. Final settings shall be implemented with input from the manufacturer. 8.3 The Fire Sprinkler Contractor shall confirm that all connections between Quick-Check Purity Sensors and the specified connection points have been successfully achieved as indicated by the manufacturer.

6 8.4 Following the installation of the Nitrogen Generation Corrosion Inhibiting System, the Fire Sprinkler Contractor will test the FPS leak rate to ensure that it conforms to NFPA 13 requirements ( ). Note: For more information regarding any of these products, contact South-Tek Systems, 2940 Orville Wright Way, Suite 600, Wilmington, NC, 28405, phone: System Startup and Technical Training 9.1 South-Tek Systems shall provide on-site guidance and training following the installation of the Nitrogen Generation Corrosion Inhibiting System. 9.2 Contact South-Tek Systems, 2940 Orville Wright Way, Suite 600, Wilmington, NC, 28405, Phone: for further information.

Type 1 - Nitrogen Generation System. Designed for: Dry or Pre-Action Fire Protection Systems (FPS) with a total capacity up to 750 gallons

Type 1 - Nitrogen Generation System. Designed for: Dry or Pre-Action Fire Protection Systems (FPS) with a total capacity up to 750 gallons Type 1 - Nitrogen Generation System Designed for: Dry or Pre-Action Fire Protection Systems (FPS) with a total capacity up to 750 gallons 1.0 Nitrogen Generation Corrosion Inhibiting System 1.1 The Fire

More information

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS)

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS) South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System Designed for: Dry or Preaction Fire Protection Systems (FPS) 1.0 Description of Work 1.1 The Fire Sprinkler Contractor shall provide

More information

NGP-250/500 Nitrogen Generator Quick Start Guide

NGP-250/500 Nitrogen Generator Quick Start Guide NGP-250/500 Nitrogen Generator Quick Start Guide Version: A July 2013 Potter Electric Signal Company, LLC 5757 Phantom Dr., Suite 125 P. O. Box 42037 Hazelwood, MO 63042 Phone: (314) 595-6900 Document

More information

ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E)

ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E) ECS Protector PGEN-30 (PGEN-30E) Specifications For use under U.S. Patents 8,720,591, 9,144,700 and 9,186,533 Dimensions (cabinet): 24.5 (W) x 52.5 (H) x 8.5 (D) (622mm(W) x 1,334mm(H) x 216mm(D)) Dimensions

More information

Potter Nitrogen Generators

Potter Nitrogen Generators Potter Nitrogen Generators What is nitrogen? Nitrogen the inert gas Earth s atmosphere the air we breathe is composed of nitrogen, oxygen, and water vapor. While this atmosphere is great for life, it is

More information

The Expanding Role of High Purity Nitrogen in Fire Protection

The Expanding Role of High Purity Nitrogen in Fire Protection The Expanding Role of High Purity Nitrogen in Fire Protection By Clint Williamson SOUTH-TEK SYTEMS, INC WILMINGTON, NC 28405 cwilliamson@southteksystems.com 910-332-4173 x104 Compressed air is out. Nitrogen

More information

N2 BLAST Datasheet Preaction single interlock electric c/w N 2 Blast Nitrogen generating system Remote controlled unit

N2 BLAST Datasheet Preaction single interlock electric c/w N 2 Blast Nitrogen generating system Remote controlled unit (System shown is a self contained unit) FireFlex N 2 Blast description The FIREFLEX N2 Blast integrated system consists of an integrated single interlock Electric release preaction automatic sprinkler

More information

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE 1 of 10 1. DESCRIPTION (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system

More information

ECS Protector Nitrogen Inerting Vent (PAV-WN)

ECS Protector Nitrogen Inerting Vent (PAV-WN) ECS Protector (PAV-WN) U.S. Pat. No. 8,636,023, 9,526,933 and 9,717,935 B2 Specifications Stock Number: Service Pressure: Regulator Setting: System Connection: Temperature Range: Dimensions: Weight: Clear

More information

DESIGN DATA. Dry 105a. September 5, 2008

DESIGN DATA. Dry 105a. September 5, 2008 September 5, 2008 Dry 105a 1. Description Dry and Preaction Systems require a dependable source of clean dry air under the proper pressure. The air supply must be adequate to restore normal air pressure

More information

TECHNICAL DATA. Trimpac 257a. September 16, 2013

TECHNICAL DATA. Trimpac 257a. September 16, 2013 September 16, 2013 Trimpac 257a 1. DESCrIpTION DESCRIPTION The Viking Double SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-2 and D-2B used with either a Model E or F Deluge Valve (A.1), a Viking

More information

TECHNICAL DATA. Dry 132a. October 1, 2008

TECHNICAL DATA. Dry 132a. October 1, 2008 October 1, 2008 Dry 132a 1. Description Viking High Pressure (HP) Dry Systems utilize a Viking Model E or Model F Deluge Valve to control the water supply to system piping equipped with closed sprinklers.

More information

Nitrogen Advantage. Better Tire Pressure Retention. Improved Fuel Economy. Extended Tread Life. Elimination of Oxidation. Reduction in Tire Failures

Nitrogen Advantage. Better Tire Pressure Retention. Improved Fuel Economy. Extended Tread Life. Elimination of Oxidation. Reduction in Tire Failures Nitrogen Advantage nitrogen tire inflation system, 4/7/14/21 CFM Better Tire Pressure Retention Improved Fuel Economy Extended Tread Life Elimination of Oxidation Reduction in Tire Failures 2 The Nitrogen

More information

TECHNICAL DATA. Trimpac 247a_Euro. September 16, 2013

TECHNICAL DATA. Trimpac 247a_Euro. September 16, 2013 September 16, 2013 Trimpac 247a_Euro 1. DESCRIPTION DEsCrIpTIoN TRIMPAC Model B-11 LPCB Type 1 is a factory assembled trim package for a single interlocked electric release module in a metal enclosure.

More information

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013 Spetember 16, 2013 Trimpac 251a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-6 and B-6B is a factory assembled trim package for a double interlocked preaction system with an electric/pneu-lectric release

More information

TECHNICAL DATA. Trimpac 256a. October 31, 2013

TECHNICAL DATA. Trimpac 256a. October 31, 2013 October 31, 2013 Trimpac 256a 1. DESCRIPTION The Viking SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-1 and D- 1B used with either a Model E or F Deluge Valve (A.1), a Viking Easy Riser check valve

More information

DEOX FPS 1 CORRISION INHIBITING SYSTEM O&M MANUAL. Revision 2 Date 02/04/16

DEOX FPS 1 CORRISION INHIBITING SYSTEM O&M MANUAL. Revision 2 Date 02/04/16 DEOX FPS 1 CORRISION INHIBITING SYSTEM O&M MANUAL Revision 2 Date 02/04/16 Copyrighted All Rights Reserved 2016 REVISION HISTORY Revision Revision Approved Approval # Date By Date 0 2/27/15 J. Nguyen 3/2/15

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE April 9, 2009 Preaction 326a 1. DESCRIPTION Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilizing the Viking G-4000P Deluge Valve. The small profi le, lightweight,

More information

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13 Page 1 of 13 1. Description The Viking 2 Model G-2000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

LPS Product Guide. LPS Series Nitrogen Generators. N2-GEN LPS TM - Layup Protection System Copyrighted All Rights Reserved

LPS Product Guide. LPS Series Nitrogen Generators. N2-GEN LPS TM - Layup Protection System Copyrighted All Rights Reserved LPS Product Guide N2-GEN LPSTM LPS Series Nitrogen Generators N2-GEN LPS TM - Layup Protection System Copyrighted All Rights Reserved - 2014 p 888 526 6284 e info@southteksystems.com w www.southteksystems.com

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Preaction 346a 1. Description The 6 Model G-6000P Electric Release Preaction System Riser Assembly can be used as a Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 348a 1. Description Viking supervised Surefire Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated Viking G-6000P Valve comes complete

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 333a 1. Description Viking supervised Surefire Preaction Systems Utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated Viking G-3000P Valve comes complete

More information

N2-BLAST NITROGEN GENERATOR FPS-1750, FPS-3000 & FPS-6000 O&M MANUAL. Revision 6 Date 05/24/16

N2-BLAST NITROGEN GENERATOR FPS-1750, FPS-3000 & FPS-6000 O&M MANUAL. Revision 6 Date 05/24/16 N2-BLAST NITROGEN GENERATOR FPS-1750, FPS-3000 & FPS-6000 O&M MANUAL Revision 6 Date 05/24/16 Copyrighted All Rights Reserved 2016 VERSION HISTORY Revision Implemented Revision Approved Approval Reason

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY Page 1 of 13 1. DESCRIPTION The Viking 3 Model G-3000 Dry Valve Riser Assembly is equipped with a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 331a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 347a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated

More information

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which January 27, 2012 307a 1. (Refer to Figures 1-3.) A Viking Non-Interlocked Preaction system utilizes a Viking Deluge Valve to control water flow into system piping equipped with closed sprinklers. Under

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B September 16, 2013 Trimpac 250a 1. DESCRIPTION DEsCRIPTIoN is a factory assembled trim package for a ed an electric/pneumatic release module in a metal enclosure. The standard trim normally required on

More information

TECHNICAL DATA. Trimpac 244a. September 16, 2013

TECHNICAL DATA. Trimpac 244a. September 16, 2013 September 16, 2013 Trimpac 244a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-1 and B-1B is a factory-assembled trim package with an electric release module in a metal enclosure. The standard trim normally

More information

Nitrogen Generators. PMNG Commercial Series. Section 50 Bulletin A -20

Nitrogen Generators. PMNG Commercial Series. Section 50 Bulletin A -20 Nitrogen Generators PMNG Commercial Series Section 50 Bulletin A -20 2 All nitrogen generators Whatever the problem; Pneumatech has the solution. are not created equal. Some may cost less and appear great

More information

TECHNICAL DATA. Q= Cv S

TECHNICAL DATA. Q= Cv S Page 1 of 13 1. DESCRIPTION The Viking 4 inch Model G-4000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

Materials Performance November Nitrogen generator inhibits corrosion within fire protection systems

Materials Performance November Nitrogen generator inhibits corrosion within fire protection systems Materials Performance November 2014 Nitrogen generator inhibits corrosion within fire protection systems When dry and pre-action fire protection systems experience internal corrosion in their piping network,

More information

ASSE International Product (Seal) Listing Program

ASSE International Product (Seal) Listing Program ASSE International Product (Seal) Listing Program ASSE 1070-2015 / ASME A112.1070-2015 / CSA B125.70-15 Performance Requirements for Water Temperature Limiting Devices Manufacturer: Contact Person: E-mail:

More information

Oxygen Generating Systems Ozone Medical Welding Glassblowing Aquaculture Pulp & Paper Wastewater

Oxygen Generating Systems Ozone Medical Welding Glassblowing Aquaculture Pulp & Paper Wastewater Oxygen Generating Systems General Information Extract oxygen directly from the atmosphere and deliver it to any medical or industrial application with an OGSI oxygen generator. Our standard line of Pressure

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION Installation, Operation, and Maintenance Balston 75-96 and 75-98 Nitrogen Generation System Tower Pressure Gauge 5'-1" 3'-6" 7'-4" 6'-10 1/2" PLAN VIEW Figure 1 - Balston 75-96 and

More information

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor)

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1. According to NFPA 99, SCFM is an acronym for. a) Surface Conditions at Fahrenheit Mercury b) Standard Conditions

More information

Marschalk Model # 94000

Marschalk Model # 94000 Marschalk Model # 94000 12-volt DC Portable oil-less Air Compressor Operation Manual 27250006 REV 1 9/13/05 Table of Contents CHAPTER 1: SYSTEM DESCRIPTION... 5 FUNCTION AND THEORY... 5 SYSTEM COMPONENTS...

More information

TotalPac X Single interlock Preaction system Electric release

TotalPac X Single interlock Preaction system Electric release DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical and mechanical

More information

Workhorse-15 Oxygen Generator

Workhorse-15 Oxygen Generator 11436 Sorrento Valley Road, San Diego CA 92121 USA 858-558-0202 Fax 858-558-1915 Workhorse-15 Oxygen Generator Model No. 5719, 5727, 5735 for Domestic and International Units Part number 1432 Revision

More information

Model DDX-LP Dry Pipe Valve System 8 (200mm) Features. Differential latching clapper-type, lighweight, dependable construction.

Model DDX-LP Dry Pipe Valve System 8 (200mm) Features. Differential latching clapper-type, lighweight, dependable construction. Bulletin 335 Model DDX-LP Dry Pipe Valve System 8 (200mm) Bulletin 335 Features 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Differential latching clapper-type, lighweight, dependable construction. Low Air Pressurized

More information

FireLock NXT Dry Valve. System No. Submitted By Spec Sect Para Location Date Approved Date

FireLock NXT Dry Valve. System No. Submitted By Spec Sect Para Location Date Approved Date The patent-pending Victaulic Series 768 FireLock NXT is a low differential, latched clapper valve that uses a unique direct acting diaphragm to separate system water supplies from dry-pipe sprinkler systems.

More information

Piped Air SCBA Refilling System Standard

Piped Air SCBA Refilling System Standard WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Piped Air SCBA Refilling System Standard SCOPE: This specification

More information

NGP-300D. Installation, Operation, & Service Manual

NGP-300D. Installation, Operation, & Service Manual NGP-300D Installation, Operation, & Service Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com/corrosion

More information

CORROSION AT THE AIR-WATER INTERFACE REMOVE THE GAS

CORROSION AT THE AIR-WATER INTERFACE REMOVE THE GAS CORROSION AT THE AIR-WATER INTERFACE There are three (3) physical attributes of oxygen that explain why almost all corrosion in wet pipe fire sprinkler systems occurs in close proximity to trapped air

More information

Workhorse 8 Oxygen System Model No 5665, 5673, 5679

Workhorse 8 Oxygen System Model No 5665, 5673, 5679 11436 Sorrento Valley Road, San Diego CA 92121 USA 858-558-0202 Fax 858-558-1915 Workhorse 8 Oxygen System Model No 5665, 5673, 5679 Part Number 1815 Revision B SeQual Technologies San Diego, CA USA Cautions,

More information

N2-BLAST FPS-650 & FPS-1250 O&M MANUAL. Revision 4 Date 04/27/16

N2-BLAST FPS-650 & FPS-1250 O&M MANUAL. Revision 4 Date 04/27/16 N2-BLAST FPS-650 & FPS-1250 O&M MANUAL Revision 4 Date 04/27/16 Copyrighted All Rights Reserved 2016 VERSION HISTORY Revision Implemented Revision Approved Approval Reason # By Date By Date 1 J. Nguyen

More information

Data Sheet Issue A

Data Sheet Issue A Features 1. Differential latching clappertype, lighweight, dependable construction. 2. Low Air Pressurized System, 8 psi -to- 26 psi (0,6 bar to- 1,8 bar) 3. Reset externally. Cover removal is not required.

More information

OPERATION MANUAL NTF-15

OPERATION MANUAL NTF-15 OPERATION MANUAL NTF-15 Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81235-00 (Rev B) TABLE

More information

OPERATING INSTRUCTIONS Pressure Control System PCS-20 through PCS-100

OPERATING INSTRUCTIONS Pressure Control System PCS-20 through PCS-100 107 W. Main Street Worthington, PA 16262 Phone: 724.297.3416 Fax: 724.297.5189 http://www.airtak.com OPERATING INSTRUCTIONS Pressure Control System PCS-20 through PCS-100 12-2007 TABLE OF CONTENTS PAGE

More information

Air Amplifiers & SYSTEMS

Air Amplifiers & SYSTEMS Air Amplifiers & SYSTEMS We Accept VISA, MasterCard and American Express Air Amplifiers Point-of-Use Air Solutions Maximator air amplifiers are designed to boost plant air pressure or increase the supply

More information

Model PSI Compressor with 3-Gallon Air Tank 12VDC

Model PSI Compressor with 3-Gallon Air Tank 12VDC Model 6350 150 PSI Compressor with 3-Gallon Air Tank 12VDC IMPORTANT: It is essential that you and any other operator of this product read and understandd the contents of this manual before installing

More information

Technical Information

Technical Information Technical Information Installation, Operation, Installation, Operation and Maintenance and Maintenance Manual Manual Balston Model 75700-K728 Nitrogen Generator Figure 1-75700-K728 Overall Dimensions These

More information

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity WATER HEATER THERMAL EXPANSION TANKS Owner s Manual Safety Instructions Installation Maintenance Warranty Models: 2-5 Gallon Capacity Thank You for purchasing this Thermal Expansion Tank. Properly installed

More information

Features. Model DDX-LP Dry Pipe Valve System 4 (100mm), 6 (150mm) & 165mm Sizes

Features. Model DDX-LP Dry Pipe Valve System 4 (100mm), 6 (150mm) & 165mm Sizes Bulletin 357 Rev. E Model DDX-LP Dry Pipe Valve System 4 (100mm), 6 (150mm) & 165mm Sizes Bulletin 357 Rev. E Features 1. 2. 3. 4. 5. 6. 7. 8. 9. Differential-type valve, lightweight, dependable construction.

More information

NGP-1000D-M1/M2/M3. Installation, Operation, & Service Manual

NGP-1000D-M1/M2/M3. Installation, Operation, & Service Manual NGP-1000D-M1/M2/M3 Installation, Operation, & Service Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com/corrosion

More information

Nitrogen Tyre Inflator Owner s Manual

Nitrogen Tyre Inflator Owner s Manual Nitrogen Tyre Inflator Owner s Manual Model:PN-8890 Please read this manual carefully before attempting assembly or use. 1 Suit for: Motorcycle, Car, Light Truck, Bus Manual Model Nitrogen Tyre Inflation

More information

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate December 6, 2010 Foam 31a 1. Description With Multiple Pilot Pressure Regulating Foam/Water Deluge Systems Supplied by a Bladder Tank, multiple pilot pressure regulating foam risers can be supplied from

More information

AIR DRIVEN. Gas Boosters & SYSTEMS. Accepting VISA, MasterCard and American Express

AIR DRIVEN. Gas Boosters & SYSTEMS. Accepting VISA, MasterCard and American Express AIR DRIVEN Gas Boosters & SYSTEMS Accepting VISA, MasterCard and American Express Gas Boosters AIR DRIVEN FROM 30 PSI TO 21,750 PSI MAXIMATOR Maximator gas boosters are an excellent alternative to high

More information

System Pressure Manager Standard & System Pressure Manager Plus

System Pressure Manager Standard & System Pressure Manager Plus System Pressure Manager Standard & System Pressure Manager Plus Installation, Commissioning & Servicing Instructions Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING,

More information

OPERATION MANUAL NTF-60 Plus

OPERATION MANUAL NTF-60 Plus OPERATION MANUAL NTF-60 Plus Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81264-00 (Rev A)

More information

KKT Training Series: ECO Series, Preventative Maintenance

KKT Training Series: ECO Series, Preventative Maintenance KKT Training Series: ECO Series, Preventative Maintenance p.m. process The preventative maintenance is a scheduled event with one hour of downtime. We must ensure the following procedure is performed:

More information

Inert Air (N2) Systems Manual

Inert Air (N2) Systems Manual INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing

More information

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289 3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for

More information

/ /

/ / GN 4- kw/5.5-0 hp Dual Output Compressors (Air/Nitrogen) Driving Nitrogen Forward GN: the dual output solution From cargo blanketing in LNG vessels to the inflation of Formula tires, nitrogen is used in

More information

OBSOLETE. Wet pipe low flow manifold system

OBSOLETE. Wet pipe low flow manifold system June 1, 2008 Foam 15a 1. Description Multiple risers can be supplied from a single proportioning device. A riser manifold is installed with various riser types and sizes that are to supply foam solution

More information

Corrosion Protection in Dry-Pipe Systems Article and photos by Gregory Havel, except where noted. May 21, 2018

Corrosion Protection in Dry-Pipe Systems Article and photos by Gregory Havel, except where noted. May 21, 2018 Corrosion Protection in Dry-Pipe Systems Article and photos by Gregory Havel, except where noted May 21, 2018 Corrosion in automatic fire sprinkler systems is a concern to those who design, install, and

More information

Features. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200)

Features. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200) Features 1. Differential latching clapper-type, lightweight, dependable construction. 2. Low Air Pressurized System, psi -to- 2 psi (0,6 bar -to- 1,9 bar) Max 3. Reset externally. Cover removal is not

More information

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4 Page 1 of 5 Telephone: 29-95-9501 Technical Services: 877-8-5 Fax: 29-8-0 Email: techsvcs@vikingcorp.com Model F Dry Valve with Trim Valve Size Part Number 17PTR 175PTR 17PTR Standard Trim Sets include

More information

INS-1500/2000 (EU) Nitrogen Generators Installation, Operation, and Instruction Manual

INS-1500/2000 (EU) Nitrogen Generators Installation, Operation, and Instruction Manual INS-1500/2000 (EU) Nitrogen Generators Installation, Operation, and Instruction Manual St. Louis, MO 800-325-3936 www.pottersignal.com Manual #5403653 - A 02/19 Potter Electric Signal Company, LLC St.

More information

444C DUAL PERFORMANCE VALUE PACK

444C DUAL PERFORMANCE VALUE PACK (Chrome) PART NO. 44432 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using this product. SAVE THIS MANUAL

More information

Anti-flood device Model B-1

Anti-flood device Model B-1 December 4, 2009 Dry Systems 123a 1. DESCRIPTION The Anti-flood Device is required when Viking accelerators are installed on dry systems according to Viking Model E-1 Accelerator Trim Charts. In the SET

More information

VERTICAL BLADDER TANK

VERTICAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Tight Spaces UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO 250C-IG COMPRESSOR KIT 12V PART NO. 25050 250C-IG COMPRESSOR KIT 24V PART NO. 25058 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual

More information

Compressors for Paintball and Air Guns Catalog. The most convenient, efficient and effective way to fill your high pressure tanks.

Compressors for Paintball and Air Guns Catalog. The most convenient, efficient and effective way to fill your high pressure tanks. Compressors for Paintball and Air Guns Catalog The most convenient, efficient and effective way to fill your high pressure tanks. Rev. 0.19 TABLE OF CONTENTS Ordering... 1 High Pressure Compressors Coltri

More information

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE February 9, 1998 Foam 101a A BLADDER TANK WITH 1. DESCRIPTION A Wet Pipe Bladder Tank Foam/Water System is a standard wet pipe automatic sprinkler system capable of discharging a foam/water solution automatically

More information

4-7 kw/ hp. Dual Output Compressors (Air/Nitrogen) Driving Nitrogen Forward

4-7 kw/ hp. Dual Output Compressors (Air/Nitrogen) Driving Nitrogen Forward GN 4-7 kw/5.5-10 hp Dual Output Compressors (Air/Nitrogen) Driving Nitrogen Forward Total capability, total responsibility Right at the heart of your business, Atlas Copco delivers quality compressed air

More information

Horizontal Bladder Tanks

Horizontal Bladder Tanks DATA SHEET Horizontal Bladder Tanks Features UL Listed and FM Approved for use with various ANSUL proportioners and foam concentrates 175 psi (12.1 bar) maximum allowable working pressure (design pressure)

More information

HORIZONTAL BLADDER TANK

HORIZONTAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Low Ceilings UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

M-06 Nitrogen Generator (Nitrogen Making Machine)

M-06 Nitrogen Generator (Nitrogen Making Machine) Guideline No.M-06 (201510) M-06 Nitrogen Generator (Nitrogen Making Machine) Issued date: 20 th October, 2015 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains

More information

Nitrogen Supply System

Nitrogen Supply System ATMOSCOPE Nitrogen Supply System NS500 Users Guide Copyright 2001 EDSYN, INC. ATMOSCOPE Nitrogen Supply Systems TABLE OF CONTENTS Introduction............................. 3 General Information.......................

More information

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves. Powers Controls RV 201 Pressure Reducing Valves Description Features Product Numbers Dual Pressure PRV Technical Instructions Document No. 155-049P25 RV 201-1 Single Pressure PRV The RV 201 Pressure Reducing

More information

Gas Boosters & Systems

Gas Boosters & Systems DRIVEN Gas Boosters & Systems SINGLE ACTING - SINGLE STAGE PRESSURES UP TO 10,875 psi DOUBLE ACTING- SINGLE STAGE PRESSURES UP TO 21,750 psi TWO STAGE PRESSURES UP TO 21,750 psi DOUBLE HEAD - SINGLE AND

More information

Compressed Air - Food/Bev. Presented By: Adam Zimmerman

Compressed Air - Food/Bev. Presented By: Adam Zimmerman Compressed Air - Food/Bev Presented By: Adam Zimmerman Meeting Summary Metro Air Treatment Compressor Types & Selection Measurment Questions Metropolitan Air Compressor Co., Inc. Serving the Michigan Market

More information

Vertical Bladder Tanks

Vertical Bladder Tanks DATA SHEET Vertical Bladder Tanks Features UL Listed and FM Approved for use with various ANSUL proportioners and foam concentrates 175 psi (12.1 bar) maximum allowable working pressure (design pressure)

More information

Portable Oil Lube Air Compressors

Portable Oil Lube Air Compressors Portable Oil Lube Air Compressors 8003631 8003632 0410149 8018968 8018940 Owner s Manual Read and understand operating instructions before use Safety definitions The information listed below should be

More information

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION Page 1 of 6 1. DESCRIPTION The Model B-1 Anti-flood Device is required when Viking accelerators are installed on dry systems according to Viking Model E-1 Accelerator Trim Charts. In the SET condition,

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

ASSE International Product (Seal) Listing Program

ASSE International Product (Seal) Listing Program Manufacturer Contact Person Address ASSE International Product (Seal) Listing Program ASSE 07-05 / ASME A.9.07-05 / CSA B5.7-5 Pressurized Flushing Devices for Plumbing Fixtures Laboratory File Number

More information

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO 97C COMPRESSOR KIT 12V PART NO. 00097 97C COMPRESSOR KIT 24V PART NO. 02497 98C COMPRESSOR KIT PART NO. 00098 97C 98C IMPORTANT: It is essential that you and any other operator of this product read and

More information

GAS COMPRESSION SYSTEM

GAS COMPRESSION SYSTEM GAS COMPRESSION SYSTEM The gas compression system at HI 376 A consists of two natural gas turbine-driven Compressors (CBA-4020/4070). Both Compressors are needed for the volume of gas being compressed.

More information

TANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel

TANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel TANK MANAGER FOR TWO TANKS OPERATING MANUAL 10/31/11 C-More T6C L color touch panel 1 TABLE OF CONTENTS GENERAL...3 INSTALLATION...4 STONE TEST PROCEDURE...7 OPERATIONAL SUMMARY...7 AUTO CARBONATION...10

More information

200 PSI COMPRESSORS - MODEL NUMBERS

200 PSI COMPRESSORS - MODEL NUMBERS 200 PSI COMPRESSORS - MODEL NUMBERS 380C AIR COMPRESSOR KIT PART NO. 38033 480C AIR COMPRESSOR KIT PART NO. 48043 380C 480C IMPORTANT: It is essential that you and any other operator of this product read

More information

Presented to the IAPMO Standards Review Committee on March 7, 2016

Presented to the IAPMO Standards Review Committee on March 7, 2016 Summary of Substantive Changes between the 2015 edition of ASSE 1070/ASME A112.1070/CSA B125.70, Water Temperature Limiting Devices, the 2004 edition of ASSE 1070, Water Temperature Limiting Devices, and

More information

Master Control Systems, Inc. Variable Speed Fire Pump Controllers

Master Control Systems, Inc. Variable Speed Fire Pump Controllers Master Control Systems, Inc. Variable Speed Fire Pump Controllers Meets NFPA 20-2019 UL/FM Listed and Approved for fire protections * Pressure Limiting Control * Suction Limiting Control Why Variable Speed?

More information

100C Air Compressor Kit

100C Air Compressor Kit 10010 100C Air Compressor (standard mounting bracket, CE Spec) 10014 100C Air Compressor (no leader hose or check valve, CE Spec) 10016 100C Air Compressor (with Omega Bracket, CE Spec) IMPORTANT: It is

More information

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1048 - REVISED: 2009 Double Check Detector Fire Protection Backflow Prevention Assemblies Separate, complete laboratory

More information

SPECIFICATIONS TABLE Maximum Air Pressure 115 PSI Air Tank Capacity 20 Gallons

SPECIFICATIONS TABLE Maximum Air Pressure 115 PSI Air Tank Capacity 20 Gallons SPECIFICATIONS TABLE Maximum Air Pressure 115 PSI Air Tank Capacity 20 Gallons Air Flow Capacity 6.2 CFM at 40 PSI 5.2 CFM at 90 PSI Motor 2.5 HP Working / 4 HP Peak 120 Volt / 60 Hz / 13 A / 1-Phase Required

More information