DK46 - DK800 Supplementary instructions
|
|
- Anabel Harvey
- 6 years ago
- Views:
Transcription
1 DK46 - DK800 Supplementary instructions Variable area flowmeter Device category II2G with electrical internals Additional Ex manual KROHNE
2 CONTENTS DK46 - DK800 1 Safety instructions General EC conformity Security information Device description Device description Description code Marking Flammable products Equipment category Types of protection Ambient temperature / temperature classes Installation Installation Electrical connections Electrical connection Terminal assignment Connecting cable Earthing and equipotential bonding Operation Start-up Operation Static electricity Service Maintenance Dismantling
3 DK46 - DK800 SAFETY INSTRUCTIONS General These supplementary Ex instructions apply for explosion-protected designs of the variable area flowmeters DK.../../../..-Ex for the category II2G. They supplement the installation and operating instructions for non-explosion-protected designs. The information in these instructions contains only the data concerning the explosion protection of category 2. The technical details in the installation and operating instructions for the non-explosionprotected designs apply unchanged in as far as they are not excluded or replaced by these instructions. 1.2 EC conformity The manufacturer declares with the EC Declaration of Conformity on his own responsibility conformity with the protection goals of Directive 94/9/EC for use in hazardous areas with gas. The EC Type Examination Certificate of the Physikalisch Technische Bundesanstalt (PTB) forms the basis of the EC Declaration of Conformity: PTB 05 ATEX 2021 X If required the EC Type Test Certificate can be downloaded under. 1.3 Security information Assembly, installation, start-up and maintenance may only be performed by personnel trained in explosion protection! CAUTION! The operator respectively his agent is responsible to follow further standards, directives or laws if required due to operating conditions or place of installation. This applies particularly for the use of easy detachable process connections such as SMS or Clamp when measuring flammable mediums. 3
4 2 DEVICE DESCRIPTION DK46 - DK Device description Variable area flowmeters measure the volume flow of flammable and non-flammable gases and liquids. Up to two separately adjustable electrical limit switches can be mounted to the on-site display. 2.2 Description code The safety description code * consists of the following elements: 1 R - with integrated inlet pressure regulator (DKR46 only) 2 Device type: 46 - Overall length of measuring cone 65 mm 47 - Overall length of measuring cone 150 mm 48 - Overall length of measuring cone 300 mm Overall length of measuring cone 100 mm 3 Material for top and bottom fittings N - brass R - stainless steel PV - PVDF 4 Differential pressure regulators RE - inlet pressure regulator RA - outlet pressure regulator 5 K1 - one limit switch / K2 - two limit switches * positions which are not needed are omitted (no blank positions) 4
5 DK46 - DK800 DEVICE DESCRIPTION Marking The marking for the entire device is provided on the indicator part with the marking plate shown below. 1 Device type 2 Manufacturer 3 Notified ATEX body 4 Sizing data: temperature & pressure 5 PED data 6 Ex data 7 Electrical connection data 8 KROHNE website 9 Type of limit switch Additional markings on the measuring device SN - serial number SO - sales order / item Tag-No - Measuring point identifier MD - manufacturing date PA - KROHNE order Vx - product configurator code AC - article code 5
6 2 DEVICE DESCRIPTION DK46 - DK Flammable products Atmospheric conditions An explosive atmosphere is defined as a mixture of air and flammable gases, vapours, mists or dusts under atmospheric conditions with the values T atm = -20 C C / -4 F F and P atm = 0,8...1,1bar. Outside of this range, no key data are available as to ignition behaviour for most mixtures. Operating conditions Variable area flowmeters operate outside of atmospheric conditions, which means that explosion protection according to Directive 94/9/EC (ATEX) regardless of the zone assignment is fundamentally not applicable due to the lack of key safety data for the interior of the measuring unit. CAUTION! Operation with flammable products is only permissible if no explosive fuel/air mixture is formed on the interior of the flowmeter under operating conditions. The user is responsible for the safe operation of the flowmeter with regard to the temperatures and pressures of the products used. In case of operation with flammable products the measuring units must be included in the periodic pressure tests of the system. 2.5 Equipment category The flowmeters are designed in Category II 2G according to EN and EN for use in Zone Types of protection The circuits of the limit switches (ring sensors) are designed in Intrinsic Safety type of protection of Category ia. They can also be operated in Category ib. 6
7 DK46 - DK800 DEVICE DESCRIPTION Ambient temperature / temperature classes Because of the influence of the temperature of the product, no permanent temperature class is assigned to variable area flowmeters. In fact, the temperature class of a device is a function of the temperature of both the product and the environment. There is no distinction between devices with one or two contacts. The classification is outlined in the following tables. The tables take into account the following parameters: Ambient temperature T amb. Product temperature T m Installed equipment Supply type (maximum value for Pi) INFORMATION! The maximum permissible product temperatures listed in the tables are valid under the following conditions: The measuring device is installed and operated in accordance with the installation instructions in the installation and operating manual. It must be ensured that the flowmeter is not heated by the effects of additional heat radiation (sunshine, neighbouring system components) and thus operated above the permissible ambient temperature range. Insulation must be limited to the piping. Unobstructed ventilation of the indicator part must be ensured. 7
8 2 DEVICE DESCRIPTION DK46 - DK800 Temperature table in C Type of limit switch Maximum permissible ambient / medium temperature in C Supply Temperature table in F Type 1 Type 2 Type 3 Temperature class T6 T5 T4...T1 T6 T5 T4...T1 T6 T5 T4...T1 RC N RC N0... RC N RC N I7R2010-N*** I7R2015-N*** I7R2010-NL*** I7R2015-NL*** The maximum lower ambient temperature is -20 C Type of limit switch Maximum permissible ambient / medium temperature in F Supply Type 1 Type 2 Type 3 Temperature class T6 T5 T4...T1 T6 T5 T4...T1 T6 T5 T4...T1 RC N RC N0... RC N RC N I7R2010-N*** I7R2015-N*** I7R2010-NL*** I7R2015-NL*** The maximum lower ambient temperature is -4 F These values may be limited by the data given in the Installation and Operating Instructions. The maximum values given in the Installation and Operating Instructions must be taken into consideration. 8
9 DK46 - DK800 INSTALLATION Installation Installation and setup must be carried out according to the applicable installation installation standards (e.g. EN ) by qualified personnel trained in explosion protection. The information given in the Installation and Operation Instructions and the Supplementary Installation and Operation Instructions must always be observed. Variable area flowmeters must be installed in such a way that There is no danger from mechanical impact effects. There are no external forces affecting the indicator part. The device is accessible for any visual inspections that are necessary, and can be viewed from all sides. The nameplate is clearly visible. It can be operated from a location with secure footing. CAUTION! The manufacturer is not liable for any damage resulting from improper use or use other than the intended purpose. This applies in particular to hazards due to insufficient corrosion resistance and suitability of the materials in contact with product. 9
10 4 ELECTRICAL CONNECTIONS DK46 - DK Electrical connection The built-in intrinsically safe NAMUR limit switches in the variable area flowmeter DK.../../../.. may only be connected to isolation switching amplifiers with separated intrinsically safe circuits to DIN with the following max. values: Maximum values of the power supply units Supply P i [mw] U i [V] I i [ma] Type Type Type When connecting to intrinsically safe circuits, take into consideration the following maximum values per circuit as a function of the limit switch (see plate on terminal box) for the energy stores. Type of limit switch C i [nf] L i [µh] RC N0.../RC N0... I7R2010-N***/I7R2015-N*** RC N3... I7R2010-NL*** RC N3... I7R2015-NL*** Terminal assignment Connect the built-in intrinsically safe components to terminals + / - in accordance with the following illustration and table. Connect one limit switch to each terminal block. Take note of the polarity indicated. Connection of limit switch - 2 wire NAMUR 1 Lower limit switch to terminal 1 2 Upper limit switch to terminal 2 The connection box includes an EMC filter unit. For devices with just one limit switch, the connection is on terminal 1. 10
11 DK46 - DK800 ELECTRICAL CONNECTIONS Connecting cable Select the connecting cables for the intrinsically safe circuits according to the valid wiring standard (e.g. EN ). Make sure that no residual current can form between different intrinsically safe circuits of the variable area flowmeter. Lay cables so as to ensure that there is sufficient distance between surfaces of the measuring unit and the connecting cable. 4.4 Earthing and equipotential bonding If the device is not adequately grounded electrostatically by way of the process piping, make an additional ground connection 1 by way of the ground connection. The location of the ground connection on the back rail is shown below. This connection merely ensures electrostatic connection of the device and does not meet the requirements for equipotential bonding. 11
12 5 OPERATION DK46 - DK Start-up 5.2 Operation Make the following checks before starting up the device: Suitability of the materials used for the measuring unit and for the gaskets for adequate resistance to corrosion from the process product. Correct connection of the built-in electrical components. Visual inspection of the single-core non-sheathed cables of the ring sensors, laid inside the indicator, for signs of damage. The limit switches can be set during operation. To do so, first remove the protective cover. Fix the limit switch 2 to the back rail 3 of the variable area flowmeter using the two clamping screws 1. Close the cover immediately after the limit switches have been set. CAUTION! Avoid pinching or damaging the single-core cable of the limit switches when setting the switches and closing the cover. It should be laid in the grooves of the back rail. If the cable is damaged in any way, the variable area flowmeter will need to be replaced! 12
13 DK46 - DK800 OPERATION Static electricity Flow-induced static charge In variable area flowmeters, it is possible under field conditions for charge separation to occur in the measuring tube due to the transport of non-conductive fluids and/or when the flow comes into contact with non-conductive internals. In glass devices, it is basically possible for the electrostatic field generated inside the measuring tube to "punch through" to the outside of the device. For that reason, variable area flowmeters need to be permanently grounded by the operator by way of the process connections in order to allow discharge of electrostatic build-up. The operator is also responsible for extending the ground continuity of the process pipeline. If grounding cannot be made via the process connections, e.g. top and bottom connection blocks are made of plastic, the flowmeter should be connected to the local ground potential via the connection to ground. This connection only ensures electrostatic grounding of the device and does not meet the requirements for equipotential bonding. When dust-free gases or liquids are measured, the flow rate should not exceed 20 times the nominal flow rate. The max. allowable working pressure PS printed on the type nameplate is to be noted. 13
14 6 SERVICE DK46 - DK Maintenance The variable area flowmeter does not require any maintenance under normal operating conditions and when used for the intended purpose. Within the scope of checks required to be carried out in hazardous areas to maintain systems in proper working order, the following visual inspections should be carried out at regular intervals: Inspection of the housing, cable entries and incoming cables for signs of damage. Inspection of the measuring unit for leaks and signs of damage to the glass cone. Include the flowmeter in the periodic pressure testing of the process piping. 6.2 Dismantling Depending on application, however, the measuring function may in unfavourable cases become impaired through soiling of the measuring cone and/or float. The measuring unit should then be cleaned as described in the Installation and Operating Instructions for the non-hazardous-duty versions. In this connection, refer to the notes on dismantling. Electrical connection If at all possible, dismantling should be carried out after the flowmeter has been disconnected from supply. If not possible, observe the boundary conditions for intrinsic safety (e.g. no grounding or connection of different intrinsically safe circuits) during dismantling. Process connections CAUTION! Pressurized pipes to be depressurized before removing the flowmeter. Avoid uncontrolled discharge of residual fluid from the measuring unit. Where environmentally critical products are concerned, carefully decontaminate the wetted parts of the measuring tube after dismantling. Removal and installation are the responsibility of the operator. Maintenance Maintenance work of a safety-relevant nature within the meaning of explosion protection may only be carried out by the manufacturer, his authorised representative or under the supervision of authorised inspectors. 14
15 DK46 - DK800 SERVICE 6. 15
16 KROHNE product overview KROHNE - Subject to change without notice. Electromagnetic flowmeters Variable area flowmeters Ultrasonic flowmeters Mass flowmeters Vortex flowmeters Flow controllers Level meters Temperature meters Pressure meters Analysis products Products and systems for the oil & gas industry Measuring systems for the marine industry Head Office KROHNE Messtechnik GmbH Ludwig-Krohne-Str Duisburg (Germany) Tel.:+49 (0) Fax:+49 (0) info@krohne.de The current list of all KROHNE contacts and addresses can be found at:
VA FLOWMETERS Supplementary Instructions
VA FLOWMETERS Supplementary Instructions Variable area flowmeters without electrical built-ins Equipment category II 2 G, II 2 D KROHNE CONTENTS VA FLOWMETERS 1 General notes 3 2 Safety instructions 4
More informationSupplementary Installation and Operating Instructions. Variable Area Flow Meters SGK-1 Ex SGK-2 Ex SGK-3 Ex. Category: II 2G Ex IIC II 3G Ex IIC
Supplementary Installation and Operating Instructions Variable Area Flow Meters SGK-1 Ex SGK-2 Ex SGK-3 Ex Category: II 2G Ex IIC II 3G Ex IIC Contents 1 General safety directions...3 2 Main safety features...4
More informationMiniature flowmeters DK 46, DKR 46 DK 47, DK 48, DK 800
KROHNE 1/22 7.236.22. GR Miniature flowmeters DK 46, DKR 46 DK 47, DK 48, DK 8 Variable area flowmeters Vortex flowmeters Flow controllers Electromagnetic flowmeters Ultrasonic flowmeters Mass flowmeters
More informationDK48 - DK800. Quick Start. Variable area flowmeter
Quick Start Variable area flowmeter General safety notes You can find the newest and/or additional information in the handbook, the datasheet, special manuals, certificates and the download center at www.krohne.com.
More informationVA40 - VA45 Technical Datasheet
VA40 - VA45 Technical Datasheet Variable area flowmeter Local indication without auxiliary power Adaptable to meet customers' requirements Replaceable mounting parts KROHNE CONTENTS VA40 - VA45 1 Product
More informationTechnical Data. Dimensions
0102 Model Number Features Comfort series 15 mm non-flush Stainless steel housing Accessories BF 30 Mounting flange, 30 mm Technical Data specifications Switching element function NAMUR, NC Rated operating
More informationOPTIBAR P 1010 C Technical Datasheet
Technical Datasheet Pressure transmitter with recessed diaphragm for general applications Wide variety thanks to modular design Measuring ranges up to 250 bar / 3750 psi High overload and temperature stability
More informationTechnical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm. Short-circuit protection
0102 Model Number Features Direct mounting on standard actuators Compact and stable housing with terminal compartment connection Fixed setting EC-Type Examination Certificate TÜV99 ATEX 1479X Usable up
More informationDimensions. Technical Data General specifications Switching element function Rated operating distance s n 5 mm
Dimensions M18x1 37 40 4 0102 24 LED Model Number Features 5 mm embeddable Usable up to SIL2 acc. to IEC 61508 Connection BN BU Accessories L+ L- EXG-18 Quick mounting bracket with dead stop BF 18 Mounting
More informationTechnical Data. General specifications. Rated operating distance s n 5 mm
0102 Model Number Features 5 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories EXG-18 Quick mounting bracket with dead stop BF 18 Mounting flange, 18 mm Technical Data specifications Switching
More informationDimensions. Technical Data General specifications Switching element function Rated operating distance s n 10 mm
Dimensions M30x1,5 5 40 37 0102 Model Number 36 LED Features Comfort series 10 mm embeddable Connection BN BU Accessories BF 30 Mounting flange, 30 mm L+ L- Technical Data specifications Switching element
More informationDimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm
Dimensions 65 9 5 40 35 14 11 9 5.4 M20 x 1.5 0102 Model Number Features Direct mounting on standard actuators Compact and stable housing with terminal compartment connection Fixed setting Satisfies machinery
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 2 mm
0102 Model Number Features 2 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories EXG-12 Quick mounting bracket with dead stop BF 12 Mounting flange, 12 mm Technical Data specifications Switching
More informationDimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm
Dimensions 65 GW2 40 35 9 5 GW1 14 11 9 5.4 M20 x 1.5 0102 Model Number S M12 x 1.5 Features 77.5 LED V Direct mounting on standard actuators Compact and stable housing with terminal compartment connection
More informationDimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm
Dimensions 65 9 5 14 40 35 11 9 5.4 M20 x 1.5 0102 S Model Number Features Direct mounting on standard actuators Compact and stable housing with terminal compartment connection Fixed setting Satisfies
More informationTechnical Data. General specifications. Rated operating distance s n 2 mm
0102 Model Number Features 2 mm flush Usable up to SIL 2 acc. to IEC 61508 Technical Data specifications Switching function Normally closed (NC) Output type NAMUR Rated operating distance s n 2 mm Installation
More informationTechnical Data. Dimensions
0102 Model Number Features 10 mm flush Shielded PUR cable for oil and gas sector Accessories BF 30 Mounting flange, 30 mm Technical Data specifications Switching function Normally closed (NC) Output type
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 1.5 mm
0102 Model Number Features 1.5 mm flush Accessories BF 8 Mounting flange, 8 mm Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 1.5 mm Installation flush
More informationGA24. GA24 Handbook. Variable-area flowmeter. KROHNE 02/ MA GA24 R01 en
GA24 Handbook Variable-area flowmeter KROHNE : IMPRINT :::::::::::::::::::::::::::::::::: All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without the prior written
More informationGA24 Technical Datasheet
GA24 Technical Datasheet Variable-area flowmeter Sturdy construction for several applications Local indication without auxiliary power Replaceable mounting parts KROHNE CONTENTS GA24 1 Product features
More informationVS18/26 with PROFINET and EtherNet/IP Interface. ATEX Installation Instructions
VS18/26 with PROFINET and EtherNet/IP Interface ATEX Installation Instructions INDEX 1. INTENDED USAGE 3 2. OPERATING MANUAL ATEX 4 2.1 General conditions 4 2.2 Installation 5 2.3 Operating 5 2.4 Failures
More informationTechnical Data. Dimensions
00 Model Number Features Comfort series 30 mm non-flush Accessories MHW 0 Modular mounting bracket V-G Female connector, M, 4-pin, field attachable V-W-N-M-PUR Female cordset, M, -pin, NAMUR, PUR cable
More informationTechnical Data. Dimensions
0102 Model Number Features 6 mm flush Usable up to SIL 3 acc. to IEC 61508 Application Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs,
More informationTechnical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm. Short-circuit protection
0102 Model Number Features Direct mounting on standard actuators Compact and stable housing Fixed setting EC-Type Examination Certificate TÜV99 ATEX 1479X Usable up to SIL2 acc. to IEC 61508 Accessories
More informationDK 37 M8. All-metal miniature flowmeters. For hazardous-duty devices, please refer to Supplementary Installation and Operating Instructions:
KROHNE 06/2005 7.02513.21.00 GR Installation and operating instructions DK 37 M8 All-metal miniature flowmeters For hazardous-duty devices, please refer to Supplementary Installation and Operating Instructions:
More informationVG5 Supplementary instructions
VG5 Supplementary instructions 2-wire / 10 GHz Radar (FMCW) Level Meter Supplementary Instructions for ATEX applications HYCONTROL CONTENTS VG5 1 General safety information 4 1.1 Scope of the document...
More informationLevel transmitter LT 100
KROHNE 09/2001 7.02363.21.00 GR/PRINTO Level transmitter LT 100 Status: 10/99 Variable area flowmeters Vortex flowmeters Flow controllers Electromagnetic flowmeters Ultrasonic flowmeters Mass flowmeters
More informationInductive slot sensor
0102 Model Number Features 3.5 mm slot width Usable up to SIL 3 acc. to IEC 61508 Nonferrous targets Application Danger! In safety-related applications the sensor must be operated with a qualified fail
More informationLiquid level instruments BM 24 /BM 51
KROHNE 09/2001 7.02362.21.00 GR/PRINTO Liquid level instruments / Status: 10/99 Variable area flowmeters Vortex flowmeters Flow controllers Electromagnetic flowmeters Ultrasonic flowmeters Mass flowmeters
More informationTechnical Data. Dimensions
00 Model Number Features mm flush Usable up to SIL acc. to IEC 6508 Accessories V-G Female connector, M, -pin, field attachable V-W Female connector, M, -pin, field attachable V-G-N-M-PUR Female cordset,
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 5 mm
00 Model Number Features 5 mm flush Usable up to SIL acc. to IEC 6508 Accessories V-G Female connector, M, -pin, field attachable V-W Female connector, M, -pin, field attachable V-G-N-M-PUR Female cordset,
More informationDimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm
Dimensions 7 36 5 33.5 9 5.4 30 65 0102 Model Number Features Direct mounting on standard actuators Fixed setting Satisfies machinery directive Compact and stable housing EC-Type Examination Certificate
More informationLiquid level switch BM 34
KROHNE 09/2001 7.02370.21.00 GR/PRINTO Liquid level switch Status: 10/99 Variable area flowmeters Vortex flowmeters Flow controllers Electromagnetic flowmeters Ultrasonic flowmeters Mass flowmeters Level
More informationMagnetic level switch type MR783 Instruction Manual
Magnetic level switch Magnetic level switch type MR783 1. DESCRIPTION page 3 1.1 Operation page 3 1.2 Application page 3 1.3 Description page 3 2. SPECIFICATIONS page 3 2.1 Service Conditions page 4 2.2
More informationTechnical Data. Dimensions
0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable
More informationTechnical Data. Dimensions
0102 Model Number Features 2 mm flush Usable up to SIL2 acc. to IEC 61508 Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 2 mm Installation flush Output
More informationLMP 307. Stainless Steel Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % / 0.
LMP 07 Stainless Steel Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0.5 % / 0. % FSO Nominal pressure from 0... mho up to 0... 50 mho Output signals -wire: 4... 0 ma -wire: 0...
More informationTechnical Data. Dimensions
0102 Model Number Features Comfort series 5 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories BF 18 Mounting flange, 18 mm EXG-18 Quick mounting bracket with dead stop Technical Data specifications
More informationTechnical Data Sheet. OPTIMASS 7000 Custody Transfer Mass Flowmeter
Technical Data Sheet KROHNE 12/2004 7.02516.21.00 CH/GR OPTIMASS 7000 Custody Transfer Mass Flowmeter with single straight measuring tube OIML R117 Pattern Approval Accuracy classes 0.3 / 0.5 / 1.0 / 1.5
More informationH250 M9 Supplementary instructions
H250 M9 Supplementary instructions Variable area flowmeter Safety manual acc. to IEC 61508:2010 KROHNE CONTENTS H250 M9 1 Introduction 3 1.1 Fields of application... 3 1.2 User benefits... 3 1.3 Relevant
More informationEnglish. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING
Contents All Products... Gb-1 Control Valves... Gb-2 Control Valve Actuators... Gb-3 Regulators... Gb-3 Relief Valves... Gb-4 Instruments, Switches, and Accessories... Gb-4 Products Covered by Battery
More informationPressure Switches Application Guideline
Pressure Switches Application Guideline Product Overview The Fema Pressure Switch product portfolio provides devices suitable for many applications. The portfolio contains Special functions and equipment
More informationRTD temperature probes
RTD temperature probes Ex i for use in areas with an explosion hazard (Ex areas) Persons concerned: Experienced professional electricians as per EU Directive 1999/92/EC and trained personnel Operating
More informationType 0404 / /2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation
Type 0404 / 5404 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation 1 OPERATING INSTRUCTIONS The operating instructions
More informationDMK 458. Pressure Transmitter for Marine and Offshore. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.25 % FSO option: 0.
Pressure Transmitter for Marine and Offshore Ceramic Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0. % FSO Nominal pressure from 0... 40 mbar up to 0... 0 bar Output signals -wire:
More informationx act i Precision Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to IEC 60770: 0.
Precision Pressure Transmitter for Food ndustry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to EC 60770: 0. % FSO Nominal pressure from 0... 400 mbar up to 0... 40 bar Output
More informationx act i Precision- Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor
Precision- Pressure Transmitter for Food ndustry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to EC 60770: 0. % FSO Nominal pressure from 0... 400 mbar up to 0... 40 bar Output
More informationElectropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765
Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765 Application Single-acting positioner for attachment to pneumatic control valves. Supplied with either an electric input signal from
More information* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22.
*09005087* DB_BA_EN_ME01_S Rev.A 12/16 *09005087* d e v e l o p i n g s o l u t i o n s Data Sheet and Operating Manual ME01 Digital manometer Table of Contents ME01 ## # 87 # HL S#### Dust explosion protection
More informationPressure switch KP-E. Data sheet
Data sheet Pressure switch KP-E KP-E pressure switches for use in refrigeration and air conditioning systems are equipped with SPDT gold plated contacts and stainless steel bellows. The high pressure switches
More informationInstallation and Operating Instructions Bypass Flow Meter DST
Installation and Operating Instructions Bypass Flow Meter DST DST_gb_A4_1.0.doc Version 1.0 1 von 10 Contents 1. Foreword... 3 2. Safety... 3 2.1. Symbol and meaning... 3 2.2. General safety directions
More informationPressure Measurement Single-range transmitters for general applications
Siemens A 207 Overview Application The SITRANS P Compact pressure transmitter is designed for the special requirements of the food, pharmaceutical and biotechnology industries. The use of high-grade materials
More informationSITRANS. Pressure transmitter SITRANS P, Z series for gauge and absolute pressure. Introduction. Safety instructions 2.
Introduction 1 Safety instructions 2 SITRANS Pressure transmitter SITRANS P, Z series for gauge and absolute pressure 7MF1564 Description 3 Assembly and connection 4 Technical data 5 Dimensional drawings
More informationD10S/D20S Wall/Post Mount Inflator Quick Start Manual
PART NUMBER SERIAL NUMBER D10S/D20S Wall/Post Mount Inflator Quick Start Manual Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product
More informationII 2G EEx ia IIC T6. Ignition protection class
ATEX General information According to 94/9/EC, a device that is to be used in an environment at risk of explosion may only be brought into the market if it satisfies the standards specified in the norm.
More informationElectropneumatic Positioner and Pneumatic Positioner Type 3760 JIS
Electropneumatic Positioner and Pneumatic Positioner Type 3760 Application Single-acting positioners for direct attachment to pneumatic control valves. Supplied with an electric input signal of 4 to 20
More informationPressure control, differental pressure control and thermostat Type RT
MAKING MODERN LIVING POSSIBLE Technical brochure Pressure control, differental pressure control and thermostat Type RT Hydrocarbons www.danfoss.com/hydrocarbons Contents Page Introduction...3 Approvals...3
More informationLTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc.
LTB013EN Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc. to IECEx scheme Subject to technical modification Bachofen AG Ackerstrasse 42
More information1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/16 Siemens FI US Edition
Siemens AG 206 Overview Design Device structure without explosion protection The pressure transmitter consists of a piezoresistive measuring cell with a diaphragm installed in a stainless steel enclosure.
More informationBourdon tube pressure gauge for diaphragm seals
Bourdon tube pressure gauge for diaphragm seals and switch function, Type series BR42.. Features Bourdon tube pressure gauge for diaphragm seal and switch function Nominal range -1 3 bar to -1 15 bar,
More informationOperating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Brass Check Valve RDL
Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU FAS Brass Check Valve RDL Please read these operating instructions carefully to ensure a safe operation and keep the same
More informationdeltaflowc deltaflowc Venturi or Probe
deltaflowc Mass Flowmeter for Gases - Multivariable with ultra fast dp, p and T-sensors - Compact, accurate and user-friendly - Ideal for OEMs deltaflowc Venturi or Probe Precise mass flow metering deltaflowc
More informationCertificate of Compliance
Certificate of Compliance Certificate: 2419437 Master Contract: 203012 Issued to: ABB Automation Products GmbH 72 Schillerstrasse Minden, 32425 Germany Attention: Ralf Schaffer The products listed below
More informationSAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER
SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SUPPLIMENT TO eom IMPORTANT READ THIS MANUAL BEFORE PRODUCT INSTALLATION, OPERATION, INSPECTION & MAINTENANCE Tougher and more rigid guidelines are being established
More information1 Overview. Pressure Measurement Transmitters for basic requirements. 1/16 Siemens FI SITRANS P220 for gauge pressure
Siemens AG 204 Overview The pressure transmitter SITRANS P220 measures the gauge pressure of liquids, gases and vapors. Stainless steel measuring cell, fully welded Measuring ranges 2.5 to 600 bar (36.3
More information2 Overview. SITRANS P measuring instruments for pressure. Transmitters for gage and absolute pressure. Z series for gage pressure
Z series for gage pressure Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and electronics plate Process connection Electrical connection
More informationType Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.
2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies We reserve the right to make technical changes without notice. Technische Änderungen vorbehalten. Sous réserve de modifications techniques.
More informationOperating Instructions
Operating Instructions Ex d Enclosures in Light Metal / Flameproof Encapsulation > 8265/0 Empty Enclosure > 8265/4 controller, installed in Ex e enclosure > 8265/5 controller Contents 1 Contents 1 Contents...2
More informationType 2000 INOX. Quickstart. English Deutsch Français. 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies
Type 2000 INOX 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies Quickstart English Deutsch Français Contents 1 QUICKSTART... 2 2 CONTACT ADDRESS... 2 3 INTENDED USE...
More information7000 Series OPTIMASS Mass Flowmeters. Titanium Hastelloy Stainless Steel
KROHNE 04/2003 7.02445.71.00 GR 7000 Series OPTIMASS Mass Flowmeters with single straight measuring tube Titanium Hastelloy Stainless Steel One tube no limits No limits with tube material No limits with
More informationSafety Instructions Liquiphant FailSafe FTL80, FTL81, FTL85
XA01537F-A/00/EN/01.16 71333275 Products Solutions Services Safety Instructions Liquiphant FailSafe FTL80, FTL81, FTL85 0Ex ia IIC T6 Ga X Ga/Gb Ex ia IIC T6 X Document: XA01537F-A Safety instructions
More informationPressure switch, Differential pressure switch and Thermostat RT-E
Data sheet Pressure switch, Differential pressure switch and Thermostat RT-E The RT-E series consist of pressure and differential pressure switches as well as thermostats. The units are designed for industrial
More informationSITRANS P measuring instruments for pressure
SITRANS P measuring instruments for pressure Z series for gage pressure Siemens AG 008 Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and
More informationMonitoring device NTS 30
P R O D U C T I N F O R M A T I O N Electronic level- and temperature monitoring device Monitoring device NTS 30 Contents Description Description... 2 Operating... 3 Design and electrical data... 4 Circuit
More informationGas density monitor With integrated transmitter Model GDM-100-TI
SF 6 gas solutions Gas density monitor With integrated transmitter Model GDM-100-TI grid Products WIKA data sheet SP 60.05 for further approvals see page 5 Applications Gas density monitoring of closed
More informationATEX VACUUM PUMPS AND GAUGES CHEMICALLY RESISTANT, OIL-FREE AND SAFE
ATEX VACUUM PUMPS AND GAUGES CHEMICALLY RESISTANT, OIL-FREE AND SAFE ATEX CHEMISTRY DIAPHRAGM PUMPS. ATEX VARIO CHEMISTRY DIAPHRAGM PUMPS. Chemistry diaphragm pumps, vacuum systems and gauges for use in
More informationCompact differential pressure switch Flameproof enclosure Ex d Models DE, DEC
Mechatronic pressure measurement Compact differential pressure switch Flameproof enclosure Ex d Models DE, DEC WIKA data sheet PV 35.41 Process Compact Series Applications Differential pressure monitoring
More informationVALFONTA INSTRUCTIONS: OPERATION AND INSTALLATION PRESSURE REDUCING VALVE MODEL M2
INSTRUCTIONS: OPERATION AND INSTALLATION PRESSURE REDUCING VALVE MODEL M2 Pressure Reducing Valve M2 - Operation and Installation - 1 - M2-13E-ENG FEBRUARY 2017 ÍNDICE PÁGINA 1 IDENTIFICATION PLATE LEGEND
More informationManual Power relay SR853
Manual Power relay SR853 Rev. 0 SR853 manual page2 Safety Guidelines for explosion proof devices Application and Standards This instruction manual applies to explosion protected control systems of protection
More informationAir Sensor. SAC Ex. Manual ATEX. AQ Elteknik AB
Air Sensor SAC Ex Manual AQ Elteknik AB ATEX Air Sensor SAC Ex ATEX Certified model Manual version 2.1 April 2014 AQ Elteknik AB 2 Table of contents 1. Manufacturer information... 4 Manufacture Declaration
More informationOperating instructions for variable area flow meter with needle valve. Model: UVR/UTR
Operating instructions for variable area flow meter with needle valve Model: UVR/UTR 1. Contents 1. Contents... 2 2. Note... 3 3. Instrument inspection... 3 4. Regulation use... 3 5. Operating principle...
More informationOperating Instructions
Operating Instructions Light-metal Ex d enclosures / flameproof enclosure > 8265/0 Empty enclosure > 8265/4 Control panel, integrated in Ex e enclosure > 8265/5 Control panel Table of Contents 1 Table
More informationMechanical pressure switches
18 Technical features / Advantages Diecast aluminium housing IP 54 or IP 65 version also available Wall mounting or directly on the pressure line Switching element (microswitch) Lead sealable setpoint
More informationFurther technical information is available on
1 of 5 Manufacture address : Bartec Technor AS Dusavikveien 39 4007 Stavanger Norway Further technical information is available on www.bartec-technor.no Note on instructions When working in hazardous areas,
More informationVALFONTA INSTRUCTIONS: OPERATION AND INSTALLATION PRESSURE REDUCING VALVE MODEL PRV44
INSTRUCTIONS: OPERATION AND INSTALLATION PRESSURE REDUCING VALVE MODEL PRV44 Pressure Reducing Valve PRV44 - Operation and Installation - 1 - manual PRV44-16-ENG JULY 2016 INDEX PAGE 1 IDENTIFICATION PLATE
More informationPressure switch with bourdon tube
Pressure switch with bourdon tube for plants requiring special supervision,type series BN4 Features Pressure switch with bourdon tube for plants requiring special supervision, Nominal ranges -1...0 bar
More informationTemperature gauge Installation Guide
Temperature gauge Installation Guide improper functioning, or damage. Additional information can be found at: CAUTION: Read this installation guide carefully before unpacking the temperature gauge. Improper
More informationMeasurement accessories METPOINT OCV for the measurement in systems up to 40 bar
EN - english Instructions for installation and operation Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar Dear customer, Thank you for deciding in favour of the METPOINT
More information3000 Series OPTIMASS Mass Flowmeter. Stainless Steel Hastelloy
KROHNE 07/2005 7.02446.25.00 GR 3000 Series OPTIMASS Mass Flowmeter with single Z-shaped measuring tube Stainless Steel Hastelloy Status: 10/99 One tube no limits No limits with tube material No limits
More informationIntrinsically safe solenoid valves on/off controls - ATEX certification
www.atos.com Table E130-17/E Intrinsically safe solenoid valves on/off controls - ATEX certification valve body valve spool intrinsically safe solenoid electrical connector manual override DHW-0611/WP/6
More informationPressure Measurement. Transmitters for basic requirements SITRANS P Z for gauge pressure. 2/4 Siemens FI Overview
f gauge pressure Siemens AG 010 Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and electronics plate Process connection Electrical connection
More information6-5 Maintenance Manual
Non Return Valve 6-5 Maintenance Manual Contents 1. PRODUCT DESCRIPTION... 1 1.1 How it works... 1 1.2 Overall dimensions... 3 1.3 Technical datasheet... 4 1.3.1 Push flow situation... 4 1.3.2 Pull flow
More informationsitrans p Operating Instructions (de/en) Edition 03/2004
(de/en) Edition 03/2004 sitrans p Messumformer für Food, Pharma und Biotechnik Transmitters for food, pharmaceuticals and biotechnologgy 7FM8010 Contents Information for the operator...27 Important security
More information1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI US Edition
Siemens AG 07 SITRANS LH00 Transmitter for hydrostatic level Overview Function U const. p U I EM The pressure transmitter SITRANS LH00 is a submersible sensor for hydrostatic level measurement. The pressure
More informationPilot HON 625. Entwurf. Product information. serving the gas industry worldwide
Pilot HON 62 Entwurf Product information serving the gas industry worldwide Pilot HON 62 Application, characteristics Application Pilot for the gas pressure regulator HON 02 Pilot for outlet pressure control
More information1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI
Siemens AG 06 SITRANS LH00 Transmitter for hydrostatic level Overview Function U const. p U I EM The pressure transmitter SITRANS LH00 is a submersible sensor for hydrostatic level measurement. The pressure
More informationType BBS-03, BBS-05, BBS-06, BBS-25
Type BBS-03, BBS-05, BBS-06, BBS-25 Sterile connection elements Sterile Verbindungselemente Raccords union stériles Operating Instructions Bedienungsanleitung Manuel d utilisation 1. THE OPERATING INSTRUCTIONS
More informationElectropneumatic Positioner and Pneumatic Positioner Type 3760 JIS
Electropneumatic Positioner and Pneumatic Positioner Type 3760 Application Single-acting positioners for direct attachment to pneumatic control valves. An electric standardized signal of 4 to 20 ma or
More informationInstruction Manual Contact Pressure Vacuum Gauge
MS10 Instruction Manual Contact Pressure Vacuum Gauge Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance
More informationMounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25
Self-operated Pressure Regulators Differential Pressure Regulators (opening) Type 42-20 Type 42-25 Type 42-20 Differential Pressure Regulator Type 42-25 Differential Pressure Regulator Mounting and Operating
More information