Bomb Blast Mitigation Test

Size: px
Start display at page:

Download "Bomb Blast Mitigation Test"

Transcription

1 7 June 2005 Bomb Blast Mitigation Test In this time and day of increased natural disasters and terrorist activities, windows have not been put to the test more. With the cries for safety film getting louder than ever before, Hüper Optik responded promptly by putting its 3 products of the safety film range through the ASTM F Standard Test Method for Glazing and Glazing Systems Subjected to Airblast Loadings and the US GSA Standard Test Method for Windows and Glazing Systems Subject to Dynamic Overpressure Loadings. A hefty sum was expended to have ABS Consulting co-ordinate the test in Suffield, Canada on 13 April With a charge as large as 1000lbs, all Hüper Optik films (4-mil and 8-mil) met the criteria for Bomb Blast Mitigation based on Medium protection level facilities as defined by the Interagency Security Committee (ISC). While all its 8-mil films achieved at least a performance condition of 3B, the Ceramic 50 Shield (Wet Glazed) attained an impressive performance condition of 2 indicating minimum- or no hazard to the occupant behind the window. Reports, videos and pictures will be made available to all distributors selling the safety range of films by the 3rd quarter. Kenneth Tan Technical Support Engineer Hüper Optik International Pte Ltd

2 BLAST TESTING FOR WINDOW SAFETY FILM AT DEFENSE RESEARCH ESTABLISHMENT SUFFIELD BY ABS CONSULTING MAY 19, 2005 ABSG Consulting, Inc San Pedro, Suite 215 San Antonio, TX USA Tel: Fax: I N T E R N A T I O N A L

3 Table of Contents 1. INTRODUCTION CRITERIA TEST SETUP RECORDED INFORMATION Video Information Blast Pressure Data RESULTS CONCLUSIONS...7 Appendix A - Photographs Appendix B - Window Data Sheets Appendix C - Composite Blast History Traces Appendix D - Individual Blast History Traces Appendix E - Summary Tables List of Figures Figure 1. ASTM F Performance Criteria...2 Figure 2. GSA Performance Conditions...2 Figure 3. Window Cubicles...3 Figure 4. Test Site Layout...4 Figure 5. Explosive Plastic Container...5 Figure 6. Pressure Gauge Locations...6 i

4 TEST PROGRAM FOR WINDOW SAFETY FILM SUBJECTED TO BLAST LOADS 1. Introduction Terrorist bombings in recent years have increased the awareness of government, industrial, and commercial interests in the effects of blast loads on buildings. As many of the bombings have shown, glass fragments represent one of the most significant prominent injury hazards to personnel both in the targeted building as well as adjacent facilities. In many cases, glass breakage occurs over a wide area including potentially hundreds of buildings. Window safety film can offer a significant reduction in glass fragment hazards greatly reducing risks to personnel during explosive events. Safety film can be installed in a retrofit application in a number of configurations providing a more cost effective hazard reduction than replacing the window unit. ABS Consulting was contracted to determine the effectiveness of window safety film in mitigating glass fragment hazards when subjected to blast loads. Two commonly used configurations were tested on annealed and thermally tempered glass to determine the response characteristics. The test program was conducted in accordance with the General Services Administration (GSA) and ASTM test protocols for the Interagency Security Committee (ISC) load criteria for Medium protection level buildings. Testing was conducted on April 13, 2005, 3:00 pm at the Defense Research Establishment Suffield (DRES) in Ralston, Alberta by ABS Consulting and its subcontractors the Canadian Explosives Research Laboratory (CERL), and DRES Criteria Testing was conducted in accordance with ASTM F1642, dated March 2004 and the GSA Standard Test Method for Windows and Glazing Systems Subject to Dynamic Overpressure Loadings dated January 1, and 2. The objective of the testing is to show the window and frame system performance and level of protection as defined by the two criteria. Blast loads were selected based on Medium protection level facilities as defined by the ISC, Security Design Criteria. Window response was compared to the hazard level criteria to determine glazing system performance under applied blast loads. Following each test, glass fragments were collected, measured and weighed by zone in the test enclosure. Fragments striking and embedding in the witness panel were collected and 1 US General Services Administration (GSA), GSA-TS , Standard Test Method for Glazing and Glazing Systems Subject to Dynamic Overpressure Loadings, GSA, January, ASTM Standard, F , Standard Test Method for Glazing and Glazing Systems Subject to Airblast Loadings, ASTM Book of ASTM Standards, Vol , March

5 documented. Frame deflections were recorded and performance of frame anchorage was documented. Performance conditions for each test item were assigned and recorded in accordance with ASTM and the GSA criteria as shown in Figure 1 and Figure 2, respectively. Cubicle Cross Section Blast Load Glass No Break/Hazard Minimal Hazard High Hazard Zone High Hazard Threshold 0.5 m Very Low Hazard Zone 1.0 m Low Hazard Threshold 2 m Low Hazard Zone Figure 1. ASTM F Performance Criteria Cubicle Cross Section Blast Load Glass A 3B 4 24 inches 40 inches 10 feet Figure 2. GSA Performance Conditions ABS Consulting, in consultation with members of the Blast Mitigation Action Group (BMAG) also developed a methodology to clarify damage level classification for the GSA criteria when stray fragments strike the witness panel. This methodology permits minor impacts of stray shards in Zone 5 provided they are low hazard fragments with minimal penetration. ABS Consulting also developed a methodology to clarify hazard level classification of glass 2

6 fragment mass in Zone 3A and 3B (as shown in Figure 2 above). A total mass in zone 3B less than or equal to 100 g is included in the zone 3A total glass mass. A light dusting of glass in the zone 3 area is not counted as glass mass for classification. This light dusting is defined as approximately 10 g in this methodology. These methods were employed in the GSA classification. 2. Test Setup An arena style field test was conducted where a bare explosive charge was placed centrally in the test field and test articles located at predetermined standoffs. Two steel construction window cubicles, shown in Figure 3, were placed 260-feet (79.3 m) from the explosive charge. Figure 4 shows a layout of the test area. Each test cubicle contains 6 test articles with gross dimensions of approximately 70-inches (1778 mm) tall by 57-inches (1448 mm) wide. The test cubicles are 10-feet deep (3-m) and completely enclosed with divider walls between each bay. Window locations were numbered as shown in Figure 4, from south to north. Every individual bay of each cubicle has a witness panel comprised of two layers of insulation board totaling 1.5-inches (381- mm). Nitromethane (NM) was used as the explosive for the testing. This liquid explosive material was placed in a plastic container and detonated with a 1.5-lb DM-12 explosive (see Figure 5). The NM provided a TNT equivalence of 1.0 based on review of side-on pressure gauge data. The charge weight used for the testing was 1000-lb NM (453.6-Kg). Figure 3. Window Cubicles 3

7 8 N 8 Explosive Charge 1000-lb (453.6-Kg) P27 P28 P ft (79.3 m) 260 ft (79.3 m) P30 Free Field Pressure Gauges 8 High Speed Video Camera Hi 8 Video Camera P Cubicle B Cubicle A Figure 4. Test Site Layout 4

8 Figure 5. Explosive Plastic Container 2.1. Recorded Information Detailed information was recorded for test articles prior to testing. Photographs were taken of test specimens and the test setup prior to and following each test to document window performance. Appendix A contains all photographs taken of each specimen throughout the testing Video Information Six high-speed video cameras were located behind the test enclosure, recording the response of the test article throughout the test. Two regular speed cameras were located to the south and west of the test arena to record the overall view of the test (see Figure 4 for camera locations). A complete video history for each test is included on the enclosed VHS tape. All of the video records were converted to a digital video files and are included on the attached CD Blast Pressure Data Blast pressure gauges measuring reflected pressure were mounted on front face of both test cubicles facing the oncoming blast wave, with three or four gauges for each test specimen (see Figure 6). No blast gauges were mounted inside the test cubicle to measure internal incident blast pressure. 5

9 Cubicle A P1 P3 P5 P7 P9 P11 P13 P2 12 P4 11 P6 10 P8 9 P10 8 P12 7 Cubicle B P14 P15 P17 P19 P21 P23 P25 6 P16 5 P18 4 P20 3 P22 2 P24 1 P26 Figure 6. Pressure Gauge Locations 3. Results Appendix B contains a data sheet for each test specimen. The data sheets contain the following information: Detailed description of the unit including the frame, glazing, and anchorage into the cubicle. Description of the test conditions. Summary of peak pressure and impulse applied to test specimen Detailed description of the performance condition for both ASTM and GSA criteria. A pretest and post test photograph. A graph of the applied blast history. Sketches of the window. 6

10 Appendix C contains a summary of the blast pressure gauge data and a composite blast history graph for each test showing all pressure gauges. Appendix D contains a blast pressure history for each individual gauge for each test. 4. Conclusions This report contains the test conditions and results for the window film testing performed on April 13, Detailed specimen response information, blast pressure data, and test photographs are included in the appendices. 7

11 Blast Testing for Window safety Film at Defense Research Establishment Suffield on April 13, 2005 APPENDIX E

12 Blast Testing for Window Safety Film at Defense Research Establishment Suffield on April 13, 2005 Client: Hüper Optik WINDOW DESCRIPTION AND RESPONSE Peak Pressure and Impulse Information Test Date Specimen Number 1 4/13/2005 NM1 2 4/13/2005 NM2 3 4/13/2005 NM3 4 4/13/2005 NM4 5 4/13/2005 NM5 Client Window Number Ceramic 50 Shield (C50S) Klar 800 Shield (K800S) Ceramic 50 Shield (C50S) Klar 800 Shield (K800S) Ceramic 50 Shield (C50S) Glazing Description Glazing Thickness TTG 1/4" TTG 1/4" AG 1/4" AG 1/4" TTG 1/4" Upgrade Description Frame Width Frame Height GSA Damage Level ASTM F1642 Response LT LB RT RB Avg LT LB RT RB Avg Notes in in in psi psi psi psi psi psi-ms psi-ms psi-ms psi-ms psi-ms 8-mil film with 3/4" silicone glaze all around 8-mil film with 3/8" to 1/2" silicone glaze all around 8-mil film with 1/2" to 3/4" silicone glaze all around 8-mil film with 1/2" silicone glaze all around 8-mil film with 1/2" silicone glaze all around No Hazard N/A N/A N/A N/A A * Very Low Hazard Minimal Hazard* Glass released in upper right corner; glass loose but still in place in upper left and right bottom corners. No tear in film or silicone N/A N/A N/A N/A 36.1 Glazing stop is outside at 24.5" from cubicle B Low Hazard Minimal Hazard PEAK PRESSURE PEAK IMPULSE One small bracket from interior of framing located inside the cubicle after testing at 21.5" from window (dimension: 6.5" x 4" x 0.5", weight: 124 g), not part of glazing or film system. Glass fragment strike in witness panel without penetration. N/A N/A N/A N/A Diagonal tears in all four corners of film. 7 4/13/2005 NM7 Klar 800 Shield (K800S) TTG 1/4" 8-mil film - daylight applied B Very Low Hazard N/A N/A 26.4 Full sheet of glass was torn out of frame and located outside cubicle. 8 4/13/2005 NM8 Klar 800 Shield (K800S) AG 1/4" 8-mil film - daylight applied B Low Hazard 4.0 N/A N/A Full sheet of glass was torn out of frame and located inside cubicle. 10 4/13/2005 NM10 Ceramic 50 Shield (C50S) AG 1/4" 8-mil film with 3/4" silicone glaze all around Minimal Hazard Diagonal tears from all four corners of film/ 11 4/13/2005 NM11 Klar 400 Shield (K400S) AG 1/4" 4-mil film - daylight applied Low Hazard Full sheet of glass was torn out of frame and located inside cubicle, Glazing struck the witness panel in Zone /13/2005 NM12 Klar 400 Shield (K400S) TTG 1/4" 4-mil film - daylight applied B Low Hazard Full sheet of glass was torn out of frame and located outside cubicle. * Only thing in cubicle is small flat aluminum support for frame (this was not part of the film upgrade, nor would it have entered the structure if the sides had been secured. LT - Left Top gauge LB - Left Bottom gauge RT - Right Top gauge RB - Right Bottom gauge AVG - Average of four gauges

TEST REPORT. Solamatrix Inc. GLASS-GARD GGL1200 Multi-ply Window Film and Wetglaze Anchoring System on Single 6mm (1/4 ) Annealed Glass.

TEST REPORT. Solamatrix Inc. GLASS-GARD GGL1200 Multi-ply Window Film and Wetglaze Anchoring System on Single 6mm (1/4 ) Annealed Glass. TEST REPORT Solamatrix Inc. GLASS-GARD GGL1200 Multi-ply Window Film and Wetglaze Anchoring System on Single 6mm (1/4 ) Annealed Glass. Class 3B US General Services Administration Explosion Resistant Standard

More information

CYCLIC PERFORMANCE PER ASTM E 330 TEST REPORT. Rendered to: TRUSEAL TECHNOLOGIES, LTD. PRODUCT TYPE: Fixed Window

CYCLIC PERFORMANCE PER ASTM E 330 TEST REPORT. Rendered to: TRUSEAL TECHNOLOGIES, LTD. PRODUCT TYPE: Fixed Window CYCLIC PERFORMANCE PER ASTM E 330 TEST REPORT Rendered to: TRUSEAL TECHNOLOGIES, LTD. PRODUCT TYPE: Fixed Window Report No.: Test Dates: 07/30/07 Through: 08/03/07 Report Date: 08/20/07 Expiration Date:

More information

3M: Anchored Safety Film Blast Tests

3M: Anchored Safety Film Blast Tests fgsdfg Report PAGE 1 Prepared by Benjamin Fry, BSc AMInstP Engineer TPS Ltd Simon Volpe, MEng Engineer TPS Ltd ADDRESS Centre Tower Whitgift Centre Croydon CR9 0AU CONTACT T 020 8256 4000 F 020 8256 4082

More information

Injury Based Glass Hazard Assessment

Injury Based Glass Hazard Assessment 2004-10001BW 10 pages Injury Based Glass Hazard Assessment By Sarah Meyer, Lyn Little, and Ed Conrath 1 Introduction In a blast scenario, glass fragmentation is a major cause of injuries. Physical security

More information

1688 Jean-Berchmans-Michaud Drummondville, Quebec. J2C 8E9. Mr. Marc-Etienne Mathieu,ing.

1688 Jean-Berchmans-Michaud Drummondville, Quebec. J2C 8E9. Mr. Marc-Etienne Mathieu,ing. EVALUATION OF FRAMED WALL CONSTRUCTION SECTIONS UTILIZING SOPREMA S SOPRASEAL STICK 1100T SELF-ADHERED AIR BARRIER SYSTEM IN ACCORDANCE WITH CAN/ULC S742-11 Report to: Soprema 1688 Jean-Berchmans-Michaud

More information

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A STRUCTURAL PERFORMANCE TEST REPORT SUMMARY RENDERED TO:

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A STRUCTURAL PERFORMANCE TEST REPORT SUMMARY RENDERED TO: AAMA/WDMA/CSA 101/I.S.2/A440-05 AAMA/WDMA/CSA 101/I.S.2/A440-08 STRUCTURAL PERFORMANCE TEST REPORT SUMMARY RENDERED TO: ALL SEASONS DOOR & WINDOW, INC. 28 EDGE ROAD EAST BRUNSWICK, NJ 08816 MODEL/ A-200

More information

The Science of Quantitative Risk Assessment for Explosives Safety

The Science of Quantitative Risk Assessment for Explosives Safety The Science of Quantitative Risk Assessment for Explosives Safety By John Tatom (Manager, Explosives Safety Group, A-P-T Research, Inc. Quantitative risk assessment (QRA) tools, as described in the QRA

More information

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina TEST REPORT Report No.: G4124.02-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Sun Tunnel Skylight SERIES/MODEL: TCC 022 SPECIFICATION(S): Occupational Safety and Health

More information

ASTM E1886 and ASTM E1996 TEST REPORT. Report No.: E Rendered to: 3M COMPANY St. Paul, Minnesota 55144

ASTM E1886 and ASTM E1996 TEST REPORT. Report No.: E Rendered to: 3M COMPANY St. Paul, Minnesota 55144 ASTM E1886 and ASTM E1996 TEST REPORT Report No.: E6587.01 201 44 Rendered to: 3M COMPANY St. Paul, Minnesota 55144 PRODUCT TYPE: Safety and Security Window Film SERIES/MODEL: 3M Safety and Security Film

More information

PERFORMANCE TEST REPORT FOR AIR LEAKAGE AND DURABILITY OF BARRIER PRODUCTS ASTM E Rendered to: BAUTEX SYSTEMS

PERFORMANCE TEST REPORT FOR AIR LEAKAGE AND DURABILITY OF BARRIER PRODUCTS ASTM E Rendered to: BAUTEX SYSTEMS Architectural Testing PERFORMANCE TEST REPORT FOR AIR LEAKAGE AND DURABILITY OF BARRIER PRODUCTS ASTM E 2357 Rendered to: BAUTEX SYSTEMS SERIES/MODEL: AMB 20-WN PRODUCT TYPE: Air Barrier System Report

More information

A comparison of existing standards for testing blast resistant glazing and windows

A comparison of existing standards for testing blast resistant glazing and windows A comparison of existing standards for testing blast resistant glazing and windows ERNCIP Thematic Group Resistance of structures to explosion effects Editor: Alexander Stolz Authors: Chiara Bedon Kevin

More information

LATICRETE International Inc. One LATICRETE Park North Bethany, CT USA

LATICRETE International Inc. One LATICRETE Park North Bethany, CT USA EVALUATION OF FRAMED WALL CONSTRUCTION SECTIONS UTILIZING LATICRETE INTERNATIONAL S LATICRETE BUILDING ENVELOPE SYSTEM AIR BARRIER SYSTEM IN ACCORDANCE WITH CAN/ULC S742-11 Report to: LATICRETE International

More information

Comparison of Large-Scale Vented Deflagration Tests to CFD Simulations for Partially Congested Enclosures

Comparison of Large-Scale Vented Deflagration Tests to CFD Simulations for Partially Congested Enclosures Comparison of Large-Scale Vented Deflagration Tests to CFD Simulations for Partially Congested Enclosures Peter A. Diakow, Project II Consultant, Baker Engineering and Risk Consultants, Inc. J. Kelly Thomas,

More information

OE Barricade Guide Development. Michelle Crull, PhD, PE Wallace Watanabe James Manthey, PE Charles Barker, PE

OE Barricade Guide Development. Michelle Crull, PhD, PE Wallace Watanabe James Manthey, PE Charles Barker, PE OE Barricade Guide Development by Michelle Crull, PhD, PE Wallace Watanabe James Manthey, PE Charles Barker, PE U.S. Army Engineering and Support Center, Huntsville ATTN: CEHNC-ED-CS-S P.O. Box 1600 Huntsville,

More information

TABLE OF CONTENTS International Racquetball Federation officially approved specifications. Copyright 01/13/1983; rev.

TABLE OF CONTENTS International Racquetball Federation officially approved specifications. Copyright 01/13/1983; rev. Racquetball Court Specifications TABLE OF CONTENTS International Racquetball Federation officially approved specifications. Copyright 01/13/1983; rev. 1988; 1997, 2013 SECTION ONE: Performance and Specifications

More information

LIGHTWEIGHT COMPOSITE BOMB CONTAINMENT DEVICE

LIGHTWEIGHT COMPOSITE BOMB CONTAINMENT DEVICE LIGHTWEIGHT COMPOSITE BOMB CONTAINMENT DEVICE Document Prepared By: June 22, 2007 Alan J. Hannibal Composiflex, Inc. 8100 Hawthorne Drive Erie, PA 16509 P: (814) 866-8616 F: (814) 866-0563 E: info@composiflex.com

More information

Class 1 (Explosive) Hazmat: The Hazardous Materials Table. Hazard Classifications Used in Hazmat Table, Column 3

Class 1 (Explosive) Hazmat: The Hazardous Materials Table. Hazard Classifications Used in Hazmat Table, Column 3 Hazard Classifications Used in Hazmat Table, Column 3 Class Number None None Division Number (if any) Name of class or division... Forbidden Material... Forbidden Explosives Class 1 (Explosive) Known hazards

More information

American Chemical Society (ACS) 246th ACS National Meeting Indianapolis, Indiana September 9, 2013

American Chemical Society (ACS) 246th ACS National Meeting Indianapolis, Indiana September 9, 2013 American Chemical Society (ACS) 246th ACS National Meeting Indianapolis, Indiana September 9, 2013 J. Kelly Thomas, Ph.D. Baker Engineering and Risk Consultants San Antonio, TX (KThomas@BakerRisk.com)

More information

DEVELOPMENT OF PRIMARY FRAGMENTATION SEPARATION DISTANCES FOR CASED CYLINDRICAL MUNITIONS

DEVELOPMENT OF PRIMARY FRAGMENTATION SEPARATION DISTANCES FOR CASED CYLINDRICAL MUNITIONS DEVELOPMENT OF PRIMARY FRAGMENTATION SEPARATION DISTANCES FOR CASED CYLINDRICAL MUNITIONS by William H. Zehrt, Jr., P. E. and Michelle M. Crull, PhD, P. E. U. S. Army Engineering and Support Center, Huntsville

More information

IGUMA - IGU Design Limitations

IGUMA - IGU Design Limitations 1/5 IGUMA - IGU Design Limitations Introduction Insulating Glass Units (IGU s) are being used more frequently in domestic and commercial buildings to provide improved insulation, comfort, condensation

More information

Calculating Contained Firing Facility (CFF) Explosive Firing Zones

Calculating Contained Firing Facility (CFF) Explosive Firing Zones UCRL-ID- 132204 Rev 1 Calculating Contained Firing Facility (CFF) Explosive Firing Zones J. W. Lyle February 3,1999 \ This is an informal report intended primarily for internal or limited external distribution.

More information

Explosive Fittings Testing

Explosive Fittings Testing Explosive Fittings Testing BFM Global Ltd. May 2012 EXCELLENCE IS A MINIMUM REQUIREMENT Contents 1. Summary... 3 2. Description of Samples... 4 3. Equipment... 4 4. Test Plan and Methodology... 5 4.1.

More information

REPORT NUMBER: G COQ-004 rev 1 ORIGINAL ISSUE DATE: May 18, 2010 REVISION DATE: June 7, 2010

REPORT NUMBER: G COQ-004 rev 1 ORIGINAL ISSUE DATE: May 18, 2010 REVISION DATE: June 7, 2010 TEST REPORT REPORT NUMBER: G100017878COQ-004 rev 1 ORIGINAL ISSUE DATE: May 18, 2010 REVISION DATE: June 7, 2010 EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C.

More information

FL200 Monochromatic Architectural Spot and Floodlight

FL200 Monochromatic Architectural Spot and Floodlight DATE: TYPE: COMPANY: PROJECT: 360 375mm 14.7in 463mm 18.2in 269mm 10.7in 421mm 16.6in 77mm 3.0in *SM bracket mounting option shown. See page 2 for more mounting options. FEATURES: OPTIONS: Over 16,500

More information

5. STRUCTURAL ANALYSIS

5. STRUCTURAL ANALYSIS 5. STRUCTURAL ANALYSIS The skeletal structure of the experiment casing is constructed from UNISTRUT with all experiment equipment mounted by UNISTRUT provided fasteners. All maximum loads for nuts, bolts,

More information

TESTING APPLICATION STANDARD (TAS)

TESTING APPLICATION STANDARD (TAS) TESTING APPLICATION STANDARD (TAS) No. 00(A)-9 TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE AND/OR INCREASED WINDSPEED RESISTANCE OF SOFFIT VENTILATION STRIP AND CONTINUOUS OR INTERMITTENT VENTILATION

More information

TUBE SIGN POST PRODUCTS

TUBE SIGN POST PRODUCTS Western Canada TUBE Products Ltd. SIGN POST PRODUCTS Company Profile With over 100 years of experience on staff and the largest inventory in Western Canada, we have the ability to meet all your sign support

More information

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 4.5 THE PROPAGATION

More information

Adib R. Farsoun. U.S. Army Engineer Division, Huntsville 106 Wynn Dr. Huntsville, AL ABSTRACT

Adib R. Farsoun. U.S. Army Engineer Division, Huntsville 106 Wynn Dr. Huntsville, AL ABSTRACT EVALUATION OF OPERATOR PROTECTION FROM REMOTE OPERATIONS IN EXISTING BUILDINGS WITH 1-INCH SUBSTANTIAL DIVIDING WALLS (SDWS) Adib R. Farsoun U.S. Army Engineer Division, Huntsville 1 Wynn Dr. Huntsville,

More information

PRO-50 Instrument Supply Regulator

PRO-50 Instrument Supply Regulator Features CRN Approved The PRO-50 Regulator has been granted a Canadian Registration Number. Sour Service Capability Available in NACE configurations that comply with NACE MR0175/MR0103. Environmental limits

More information

USE OF THE EXCEEDANCE CURVE APPROACH IN OCCUPIED BUILDING RISK ASSESSMENT

USE OF THE EXCEEDANCE CURVE APPROACH IN OCCUPIED BUILDING RISK ASSESSMENT USE OF THE EXCEEDANCE CURVE APPROACH IN OCCUPIED BUILDING RISK ASSESSMENT Kieran J Glynn, Advisor Major Accident Risk, BP, UK The exceedance curve approach was developed following the issue of the 2003

More information

CONTENTS 1. INTRODUCTION DESCRIPTION OF TEST SAMPLE TEST RIG GENERAL ARRANGEMENT TEST SEQUENCE...7

CONTENTS 1. INTRODUCTION DESCRIPTION OF TEST SAMPLE TEST RIG GENERAL ARRANGEMENT TEST SEQUENCE...7 Page 2 of 22 CONTENTS 1. INTRODUCTION...3 2. DESCRIPTION OF TEST SAMPLE...4 3. TEST RIG GENERAL ARRANGEMENT...6 4. TEST SEQUENCE...7 5. SUMMARY AND CLASSIFICATION OF TEST RESULTS...8 6. WATERTIGHTNESS

More information

EFFECTS OF EXPLOSIONS ON HUMANS

EFFECTS OF EXPLOSIONS ON HUMANS Guidelines for Evaluating the Characteristics of Vapor Cloud Explosions, Flash Fires, and BLEVEs by Center for Chemical Process Safety Copyright 1994 American Institute of Chemical Engineers APPENDIX C

More information

Blast Damage Consideratons for Horizontal Pressure Vessel and Potential for Domino Effects

Blast Damage Consideratons for Horizontal Pressure Vessel and Potential for Domino Effects A publication of CHEMICAL ENGINEERING TRANSACTIONS VOL. 26, 2012 Guest Editors: Valerio Cozzani, Eddy De Rademaeker Copyright 2012, AIDIC Servizi S.r.l., ISBN 978-88-95608-17-4; ISSN 1974-9791 The Italian

More information

PFS Test Report TL-109

PFS Test Report TL-109 PFS Test Report TL-109 Laboratory Services Testing Research Consulting Model Code Qualifications Quality Assurance Design Calculations Sampling Witnessing ENGINEERED WOOD PRODUCTS MDF panels, I-Joists,

More information

PROVIDING QUALITY SOLUTIONS FOR THE AUDIOMETRIC INDUSTRY

PROVIDING QUALITY SOLUTIONS FOR THE AUDIOMETRIC INDUSTRY PROVIDING QUALITY SOLUTIONS FOR THE AUDIOMETRIC INDUSTRY PRODUCT OPTIONS AMB Portable Series: Booths consist of 2 or 3 inch panels with integrated ventilation in the roof and floor. AMB 410: Consists

More information

Committee C21 on Ceramic Whitewares and Related Products Subcommittee C21.06 on Ceramic Tile. Research Report C

Committee C21 on Ceramic Whitewares and Related Products Subcommittee C21.06 on Ceramic Tile. Research Report C This Research Report is issued under the fixed designation RR: C21-1005. You agree not to reproduce or circulate or quote, in whole or part, this document outside of ASTM International Committee/Society

More information

1 Overview. Pressure Measurement Transmitters for basic requirements. 1/16 Siemens FI SITRANS P220 for gauge pressure

1 Overview. Pressure Measurement Transmitters for basic requirements. 1/16 Siemens FI SITRANS P220 for gauge pressure Siemens AG 204 Overview The pressure transmitter SITRANS P220 measures the gauge pressure of liquids, gases and vapors. Stainless steel measuring cell, fully welded Measuring ranges 2.5 to 600 bar (36.3

More information

SECTION 48 - TRAFFIC STRIPES AND PAVEMENT MARKINGS TABLE OF CONTENTS

SECTION 48 - TRAFFIC STRIPES AND PAVEMENT MARKINGS TABLE OF CONTENTS SECTION 48 - TRAFFIC STRIPES AND PAVEMENT MARKINGS TABLE OF CONTENTS Section Page 48-1 GENERAL...48.1 48-2 THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS...48.1 48-3 PAINTED TRAFFIC STRIPES AND PAVEMENT

More information

This versatile, quick drying, easy to apply and sand primer may be applied as a conventional spray filler or primer surfacer.

This versatile, quick drying, easy to apply and sand primer may be applied as a conventional spray filler or primer surfacer. (National Rule) Product Description: GLOBAL REFINISH SYSTEM 2K A-Chromatic Surfacers (D8001 White, D8005 Gray, D8007 Black) are premium quality primer surfacers suitable for the wide range of repair work

More information

Item 404 Driving Piling

Item 404 Driving Piling Item Driving Piling 1. DESCRIPTION Drive piling. 2. EQUIPMENT 2.1. Driving Equipment. Use power hammers for driving piling with specified bearing resistance. Use power hammers that comply with Table 1.

More information

PHASE 1 WIND STUDIES REPORT

PHASE 1 WIND STUDIES REPORT PHASE 1 WIND STUDIES REPORT ENVIRONMENTAL STUDIES AND PRELIMINARY DESIGN FOR A SUICIDE DETERRENT SYSTEM Contract 2006-B-17 24 MAY 2007 Golden Gate Bridge Highway and Transportation District Introduction

More information

DEVICES FOR FIELD DETERMINATION OF WATER VAPOR IN NATURAL GAS Betsy Murphy MNM Enterprises 801 N. Riverside Drive Fort Worth, Texas 76111

DEVICES FOR FIELD DETERMINATION OF WATER VAPOR IN NATURAL GAS Betsy Murphy MNM Enterprises 801 N. Riverside Drive Fort Worth, Texas 76111 INTRODUCTION Water vapor in natural gas has more than a substantial effect on the quality of the gas stream. Without quality measurement of water vapor the gas is basically not saleable. Contracts are

More information

SECTION SHOWER AND BATH ENCLOSURES. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

SECTION SHOWER AND BATH ENCLOSURES. Display hidden notes to specifier by using Tools / Options / View / Hidden Text. SECTION 10185 SHOWER AND BATH ENCLOSURES Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Bathtub wall enclosures. B. Shower wall

More information

DX2/DXX Operating Instructions

DX2/DXX Operating Instructions CHECK LINE BY ELECTROMATIC DX2/DXX Operating Instructions CHECK LINE INSTRUMENTS ELECTROMATIC E Q U I P M E N T C O., I N C. 600 Oakland Ave., Cedarhurst, NY 11516 U.S.A. TEL: 516-295-4300 FAX: 516-295-4399

More information

DBI SALA Advanced Hoist Systems

DBI SALA Advanced Hoist Systems DBI SALA 8518008 Advanced Hoist Systems CONTENTS History of Unique Concepts Limited... 2 Uni-Anchor Plates & Lugs... 3 Portable Uni-Anchor & Beam Clamp... 3 Mast Assembly... 4 Options... 5 Features...

More information

Type Testing Procedure for Crankcase Explosion Relief Valves

Type Testing Procedure for Crankcase Explosion Relief Valves (Jan 2005) (Corr.1 Nov 2005) (Rev.1 Oct 2006) (Corr.1 Mar 2007) (Rev.2 Sept 2007) (Corr.1 Oct 2007) (Rev.3 Jan 2008) Type Testing Procedure for Crankcase Explosion Relief Valves 1. Scope 1.1 To specify

More information

OS2 F R A M E S E R I E S

OS2 F R A M E S E R I E S P E R F O R M A N C E S P E C I F I C A T I O N S. F R A M E S E R I E S Window - Single OR Double Sash (Inswing Casement) Assessment of ification 4 Joint Permeability 0.75 m³/hm Overall Area Permeability

More information

THE NEW DDESB BLAST EFFECTS COMPUTER

THE NEW DDESB BLAST EFFECTS COMPUTER THE NEW DDESB BLAST EFFECTS COMPUTER prepared by Michael M. Swisdak, Jr. Indian Head Division/Naval Surface Warfare Center and Dr. Jerry M. Ward Department of Defense Explosives Safety Board ABSTRACT In

More information

ARA PROJECT Prepared by: Peter T. Dzwilewski Applied Research Associates, Inc Shaffer Parkway Littleton, Colorado 80127

ARA PROJECT Prepared by: Peter T. Dzwilewski Applied Research Associates, Inc Shaffer Parkway Littleton, Colorado 80127 ARA PROJECT 001974 WATER SHOCK PREDICTION FOR EXPLOSIVE REMOVAL OF OFFSHORE STRUCTURES: UNDERWATER CALCULATOR (UWC) VERSION 2.0 UPDATE BASED UPON FIELD DATA Prepared by: Peter T. Dzwilewski Applied Research

More information

Product Information D822

Product Information D822 AUTOMOTIVE REFINISH Product Information D822 Corrosion Resistant Primer Sealer Product Description D822 Corrosion Resistant Primer is a two-pack sealer for use under Global topcoat colours. It must be

More information

PEAK ALUMINUM FENCING AQUATINE Review for compliance with 2015 International Swimming Pool and Spa Code

PEAK ALUMINUM FENCING AQUATINE Review for compliance with 2015 International Swimming Pool and Spa Code PEAK ALUMINUM FENCING AQUATINE Review for compliance with 2015 International Swimming Pool and Spa Code Peak Products USA Corporation December 21, 2015 RJC No. VAN.106169.0012 Prepared for: Peak Products

More information

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any

More information

The following drawings are concerned of this measure, which will be considered in the next revision of the documents as well as in LogiKal.

The following drawings are concerned of this measure, which will be considered in the next revision of the documents as well as in LogiKal. Based on an much easier assembly of the sealing frame insulating block on fixed glazings the sealing frame has been increased from 7 mm to 9 mm in the system FRAME + 75 WI. This measure has no impact on

More information

U S F O S B u o y a n c y And Hydrodynamic M a s s

U S F O S B u o y a n c y And Hydrodynamic M a s s 1 U S F O S B u o y a n c y And Hydrodynamic M a s s 2 CONTENTS: 1 INTRODUCTION... 3 2 ACCURACY LEVELS... 3 2.1 LEVEL-0... 3 2.2 LEVEL-1... 3 2.3 PANEL MODEL... 3 3 EX 1. SINGLE PIPE. NON FLOODED... 4

More information

Discussion and guidance on the definition and qualification of porous loads

Discussion and guidance on the definition and qualification of porous loads SUMMARY Porous Loads requiring Sterilisation are often a Critical Control Point for the manufacture of Sterile products. Particularly Aseptically filled products. Regulatory guidance in this area is not

More information

Product Information D822

Product Information D822 GLOBAL REFINISH SYSTEM AUTOMOTIVE REFINISH Product Information D822 Corrosion Resistant Primer Product Description D822 Corrosion Resistant Primer is a two-pack primer for use under Global topcoat colours.

More information

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS Page 1 of 5 GUIDELINES FOR CONDUCTING 1. Definition of Hydrogenation and Hydrogenolysis Reactions Hydrogenation reactions are synthetic transformations involving hydrogen, metallic catalysts (such as nickel,

More information

Barrier Development and Evaluation Methodology. D.S. Musgrave 1 1 Thermal Visions, Inc., Granville, USA

Barrier Development and Evaluation Methodology. D.S. Musgrave 1 1 Thermal Visions, Inc., Granville, USA Barrier Development and Evaluation Methodology D.S. Musgrave 1 1 Thermal Visions, Inc., Granville, USA 1. Introduction: Vacuum insulation is now a rapidly expanding market and technical advances are being

More information

SEI Certification Program Manual

SEI Certification Program Manual Schedule of Initial s- Footwear Label Content (Structural) Label Content (Proximity) 5.1 & 5.2; Specific content and height. English. 5.1 & 5.3; Specific content and height. English. Checklist $35 1 copy

More information

Wallace & Tiernan Flow Measurement Equipment

Wallace & Tiernan Flow Measurement Equipment Water Technologies Wallace & Tiernan Flow Measurement Equipment Glass Tube Varea-Meter Units Features Rugged, One-Piece Enclosure The welded, deep-formed frame is heavy gauge 302 stainless steel. It protects

More information

Standard Recommended Practice. Field Measurement of Surface Profile of Abrasive Blast-Cleaned Steel Surfaces Using a Replica Tape

Standard Recommended Practice. Field Measurement of Surface Profile of Abrasive Blast-Cleaned Steel Surfaces Using a Replica Tape NACE Standard RP0287-2002 Item No. 21035 Standard Recommended Practice Field Measurement of Surface Profile of Abrasive Blast-Cleaned Steel Surfaces Using a Replica Tape This NACE International standard

More information

2016 International Perforating Symposium May Galveston, Texas

2016 International Perforating Symposium May Galveston, Texas IMESAFR - QRA Tool Perforating Gun Safety Analysis 2016 International Perforating Symposium May 9-11 - Galveston, Texas Who is the Institute of Makers of Explosives? Safety and Security Association for

More information

Bourdon tube pressure gauge, stainless steel For extremely low ambient temperatures down to -70 C Model PG23LT, with case filling

Bourdon tube pressure gauge, stainless steel For extremely low ambient temperatures down to -70 C Model PG23LT, with case filling Pressure Bourdon tube pressure gauge, stainless steel For extremely low ambient temperatures down to -70 C Model PG23LT, with case filling WIKA data sheet PM 02.22 for further approvals see page 3 Applications

More information

Proof Testing of an Explosion Containment Vessel

Proof Testing of an Explosion Containment Vessel Proof Testing of an Explosion Containment Vessel by Edward D. Esparza, P.E. Engineering Consultant San Antonio, Texas and Howard Stacy Jerry Wackerle Los Alamos National Laboratory Los Alamos, New Mexico

More information

Why do I need to do an Arc-Flash Analysis?

Why do I need to do an Arc-Flash Analysis? Why do I need to do an Arc-Flash Analysis? Presented By Tom Norwood for Alexander Nizov, P.E. Principal/Manager Electrical Engineering Division TRAINING INSTITUTE, INC. A SUBSIDIARY OF MEGGER Hazards Analysis

More information

SECTION 48 - TRAFFIC STRIPES AND PAVEMENT MARKINGS TABLE OF CONTENTS

SECTION 48 - TRAFFIC STRIPES AND PAVEMENT MARKINGS TABLE OF CONTENTS SECTION 48 - TRAFFIC STRIPES AND PAVEMENT MARKINGS TABLE OF CONTENTS Section Page 48-1 GENERAL... 48.1 48-2 THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS... 48.1 48-3 PAINTED TRAFFIC STRIPES AND

More information

County of Sacramento Standard Construction Specifications January 1, 2008 TECHNICAL PROVISIONS

County of Sacramento Standard Construction Specifications January 1, 2008 TECHNICAL PROVISIONS County of Sacramento Standard Construction Specifications January 1, 2008 TECHNICAL PROVISIONS SECTION 48 TRAFFIC STRIPES AND PAVEMENT MARKINGS 48-1 GENERAL Traffic stripes and pavement markings shall

More information

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: NORTH EAST WINDOWS, USA, INC.

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: NORTH EAST WINDOWS, USA, INC. NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT (Revised) Rendered to: NORTH EAST WINDOWS, USA, INC. SERIES/MODEL: DH990 Double Hung Report Number: Original Report Date: Revised

More information

Permitted MSS Emissions Tracking, Recordkeeping, and Reporting. Presented by ACES April 24, 2008

Permitted MSS Emissions Tracking, Recordkeeping, and Reporting. Presented by ACES April 24, 2008 Permitted MSS Emissions Tracking, Recordkeeping, and Reporting Presented by ACES April 24, 2008 1 Agenda Introductions Overview of Current MSS Permitting Program Status Discussion of Model MSS Permit Requirements

More information

Enhanced Fragmentation Studies for a 40mm Dual Purpose Grenade

Enhanced Fragmentation Studies for a 40mm Dual Purpose Grenade Enhanced Fragmentation Studies for a 40mm Dual Purpose Grenade NDIA Joint Armaments Conference 16 May 2012 Paul A. Shipley AAI Corporation Hunt Valley, MD Richard Mills Textron Defense Systems Wilmington,

More information

An Overview of Confined Space Rescue Course Objectives

An Overview of Confined Space Rescue Course Objectives An Overview of Confined Space Rescue 1 Course Objectives Provide the attendee with the basic understanding of the requirements of Confined Space Rescue so that the attendee can go to the next step of becoming

More information

Course Objectives. An Overview of Confined Space Rescue

Course Objectives. An Overview of Confined Space Rescue An Overview of Confined Space Rescue 1 Course Objectives Provide the attendee with the basic understanding of the requirements of Confined Space Rescue so that the attendee can go to the next step of becoming

More information

LED LIGHTING FIXTURES FOR CONTROLLED ENVIRONMENTS

LED LIGHTING FIXTURES FOR CONTROLLED ENVIRONMENTS LED LIGHTING FIXTURES FOR CONTROLLED ENVIRONMENTS cleanled sets new standards for controlled environment lighting systems Edge-lit LED optics eliminates glare and minimizes shadows Innovative housing design

More information

Breathing Air Purifiers. Comply with European Pharmacopoeia and International Breathing Air Standards

Breathing Air Purifiers. Comply with European Pharmacopoeia and International Breathing Air Standards Breathing Air Purifiers Comply with European Pharmacopoeia and International Breathing Air Standards 1 Breathing Air Purifiers domnick hunter Breathing Air Purifiers provide air 1,000,000 times cleaner

More information

Series Environmental Chambers

Series Environmental Chambers 3119-600 Series Environmental Chambers Challenges in Non-Ambient Testing Testing at non-ambient temperatures adds another layer of challenges to your testing laboratory. Ensuring you get accurate and stable

More information

RESISTORS, HEATERS, FLEXIBLE, SINGLE AND DOUBLE LAYER. ESCC Detail Specification No. 4009/002

RESISTORS, HEATERS, FLEXIBLE, SINGLE AND DOUBLE LAYER. ESCC Detail Specification No. 4009/002 Page 1 of 16 RESISTORS, HEATERS, FLEXIBLE, SINGLE AND DOUBLE LAYER ESCC Detail Specification Issue 8 February 2018 Document Custodian: European Space Agency see https://escies.org PAGE 2 LEGAL DISCLAIMER

More information

E10 E10 E10 E10 E10 E10 E10 E10 E10 E10 E10 E10 E10 E10. Cable gland Series 8161/7, 8161/8. Installation Equipment and Accessories E10/1.

E10 E10 E10 E10 E10 E10 E10 E10 E10 E10 E10 E10 E10 E10. Cable gland Series 8161/7, 8161/8. Installation Equipment and Accessories E10/1. > Explosion protection type "Increased safety" > Degree of protection IP68 > Ex e and Ex i versions > Integrated blind plug (accessory) for closing unused cable glands > Cable diameter ranges from 1 to

More information

PACIFIC SHORING, LLC ALUMINUM SHORING PRODUCTS PSH HEAVY DUTY HYDRAULIC WALER RAIL SYSTEM. TABULATED DATA Effective December 10, 2013

PACIFIC SHORING, LLC ALUMINUM SHORING PRODUCTS PSH HEAVY DUTY HYDRAULIC WALER RAIL SYSTEM. TABULATED DATA Effective December 10, 2013 1 HEAVY DUTY HYDRAULIC WALER RAIL SYSTEM Effective December 10, 2013 PSH 265 Roberts Avenue Santa Rosa, Ca. 95407 (707) 575-9014 Construction Engineering Resource 1837 Wright Street Santa Rosa, Ca. 95404

More information

PACIFIC SHORING, LLC ALUMINUM SHORING PRODUCTS HEAVY DUTY HYDRAULIC WALER RAIL SYSTEM. TABULATED DATA Effective August 25, 2015

PACIFIC SHORING, LLC ALUMINUM SHORING PRODUCTS HEAVY DUTY HYDRAULIC WALER RAIL SYSTEM. TABULATED DATA Effective August 25, 2015 1 HEAVY DUTY HYDRAULIC WALER RAIL SYSTEM Effective August 25, 2015 PSH 265 Roberts Avenue Santa Rosa, Ca. 95407 (707) 575-9014 Construction Engineering Resource 1837 Wright Street Santa Rosa, Ca. 95404

More information

Mechanical Pressure Measurement

Mechanical Pressure Measurement Mechanical Pressure Measurement Differential Pressure Gauges Model GDP, Universal Version, with Diaphragm Element High Overpressure Safety PN 40, 100, 250 or 400 Applications Differential pressure measurement

More information

Experimental Study of Hydrogen Release Accidents in a Vehicle Garage

Experimental Study of Hydrogen Release Accidents in a Vehicle Garage Experimental Study of Hydrogen Release Accidents in a Vehicle Garage Erik Merilo Mark Groethe James Colton Seiki Chiba Poulter Laboratory SRI International 3rd International Conference on Hydrogen Safety

More information

DESIGN FOR INTERNAL QUASI-STATIC PRESSURES FROM PARTIALLY CONFINED EXPLOSIONS

DESIGN FOR INTERNAL QUASI-STATIC PRESSURES FROM PARTIALLY CONFINED EXPLOSIONS DESIGN FOR INTERNAL QUASI-STATIC PRESSURES FROM PARTIALLY CONFINED EXPLOSIONS 28 th DDESB Seminar, Orlando FL, August 1998 James E. Tancreto, C.E., S.E. Naval Facilities Engineering Service Center 1100

More information

Tex-616-J, Construction Fabrics

Tex-616-J, Construction Fabrics Contents: Section 1 Overview... Section s...3 Section 3 Archived Versions...10 Texas Department of Transportation 1 06/00 1/07 Section 1 Overview Effective dates: June 000 December 007. Section 1 Overview

More information

PTFE-SINGLE GLASS FLOW METERS

PTFE-SINGLE GLASS FLOW METERS PTFE-SINGLE GLASS FLOW METERS T GENERAL DESCRIPTION Model T fl ow meters incorporate the principles of traditional variable area fl ow technology. PTFE 150mm with MVT TM Valve These rugged PTFE-Glass flow

More information

D8150 EU-139. Performance Clearcoat. Preparation of Substrate:

D8150 EU-139. Performance Clearcoat. Preparation of Substrate: Product Description: GLOBAL REFINISH SYSTEM Performance Clearcoat is a premium quality high solids clear specifically formulated for today s high production shops. The exceptionally short bake cycle and

More information

"STEEL FRAMED" ALUMINUM PANEL SHIELDS

STEEL FRAMED ALUMINUM PANEL SHIELDS "STEEL FRAMED" ALUMINUM PANEL SHIELDS MANUFACTURE S TABULATED DATA 3330 S. Sam Houston Pkwy Houston, Texas 77047 (713)943-0750 USA Toll Free 1-800-231-6662 Fax (713)943-8483 Www.speedshore.com PRINTED

More information

Internal Explosion Methodologies

Internal Explosion Methodologies 2006 Baker Engineering and Risk Consultants, Inc. Internal Explosion Methodologies Presented October 18, 2006 A.J. Pierorazio, P.Eng. J.K. Thomas, Ph.D. M. Kolbe M.L. Goodrich BAKER ENGINEERING ANDRISKCONSULTANTS

More information

Improvement of an Artificial Stall Warning System for Sailplanes

Improvement of an Artificial Stall Warning System for Sailplanes Improvement of an Artificial Stall Warning System for Sailplanes Loek M. M. Boermans and Bart Berendsen Delft University of Technology, Faculty of Aerospace Engineering P.O.Box 5058, 2600 GB Delft, The

More information

G238. G238 Family 3 & 4 Point Bend Fixtures Modular & Configurable. Features

G238. G238 Family 3 & 4 Point Bend Fixtures Modular & Configurable. Features G238 G238 Family 3 & 4 Point Bend Fixtures Modular & Configurable The G238 features a unique modular design enabling it to expand to a variety of test scenarios from a standard 3 point bend test to 4 point

More information

NEW BIRD NET DESIGN FOR OFFSHORE CAGE FARMING

NEW BIRD NET DESIGN FOR OFFSHORE CAGE FARMING NEW BIRD NET DESIGN FOR OFFSHORE CAGE FARMING Experimental Study under influence of waves Presented by : ALESSANDRO CIATTAGLIA Sales & Marketing Manager BADINOTTI GROUP Spa TABLE OF CONTENT Experimental

More information

Haynes 214 (UNS N07214)

Haynes 214 (UNS N07214) Haynes 214 (UNS N07214) Haynes 214 is a Nickel-Iron-Chromium-Aluminum alloy that offers elevated temperature oxidation resistance up to 1750oF. It is a wrought heat resistant alloy that is used in electronic

More information

enclosures to ATEX and enclosures for special custom design (EEx p and NEMA cabinets)

enclosures to ATEX and enclosures for special custom design (EEx p and NEMA cabinets) enclosures to ATEX and enclosures for special custom design (EEx p and NEMA cabinets) Stainless steel and plastic enclosures for use in potentially explosive environments R Rittal system partners Perfect

More information

The following statement is to be added as section 12.1 General and section 14.1 General: This chapter shall apply to new and existing laboratories.

The following statement is to be added as section 12.1 General and section 14.1 General: This chapter shall apply to new and existing laboratories. of 48 4/7/2014 2:41 PM Second Revision No. 35-NFPA 45-2014 [ Global Comment ] The following statement is to be added as section 12.1 General and section 14.1 General: This chapter shall apply to new and

More information

Residential Garage Door WARNING

Residential Garage Door WARNING Residential Garage Door INFORMATION EZ-SET TORSION S TORSION S EXTENSION S Improper Installation or Door Position Can Result in Serious Injury or Death. Read and understand all instructions before you

More information

Intertek Testing Services Building Products. Enterdoor AB ubv

Intertek Testing Services Building Products. Enterdoor AB ubv TEST REPORT EN 14351-1:2006 + A1:2010 Windows and doors Product standard, performance characteristics- Part 1: Windows and external pedestrian doorsets without resistance to fire and/or smoke leakage characteristics

More information

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/16 Siemens FI US Edition

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/16 Siemens FI US Edition Siemens AG 206 Overview Design Device structure without explosion protection The pressure transmitter consists of a piezoresistive measuring cell with a diaphragm installed in a stainless steel enclosure.

More information

Evolution. Radiant Panels. Radiant panel system LPHW up to 90 C Suspended ceiling grid or sofit mounting Vertical wall surface mounting

Evolution. Radiant Panels. Radiant panel system LPHW up to 90 C Suspended ceiling grid or sofit mounting Vertical wall surface mounting Evolution Radiant Panels Radiant panel system LPHW up to 90 C Suspended ceiling grid or sofit mounting Vertical wall surface mounting Contents IDENTIFICATION DESCRIPTION Page STYLE CG 3-7 STYLE CS, FC

More information

APPENDIX B TESTING PROTOCOLS. Method A: Straight Test Method B: Angular Deflection Test. Method C: Shear Load Test

APPENDIX B TESTING PROTOCOLS. Method A: Straight Test Method B: Angular Deflection Test. Method C: Shear Load Test APPENDIX B TESTING PROTOCOLS Method A: Straight Test Method B: Angular Deflection Test Method C: Shear Load Test B.1 METHOD A. STRAIGHT PIPE JOINT TEST In order to simulate the straight pipe-joint condition

More information

Page 1 of 1 04/19/13 SBR

Page 1 of 1 04/19/13 SBR Office of Roadway Engineering - Plan Insert Sheets Number Title Date Number Title Date Number Title Date 201015 Extension of Anchor Bolts 07/20/12 207000 Bikeway Pavement Marking Details 01/18/13 202010

More information