1 Water conditioning System. SOFTENER D-DF & D-UF Series INSTRUCTION MANUAL, OPERATION & MAINTENANCE

2 1. - PRESENTATION. In this manual, what is described are the required actions for the instalment, start up and maintenance of the D-DF and D-UF softener systems. It is important to read this manual carefully before installation and the start-up of the equipment. Keep this manual for future reference and if you have any doubt or question please contact your distributer s technical assistance service. The guarantee will be void in case of faulty installation or if it has not been done by a qualified service technician SOFTENENING PROCESS: SERVICE & REGENERATION Water softening in your system is done through an ion exchange process. To do so, resins which have ionic exchange are used, which the chemical ability to capture calcium (Ca) and magnesium (Mg) ions, eliminating them from the treated water. At the same time that the calcium and magnesium ions are captured by the resin, a sodium ion (Na) is released, which, due to its chemical characteristics, forms salts with a much higher solubility, avoiding problems associated hardness. It is important to take into account that as indicated above, softener systems increase the concentration of sodium in the treated water more so than that of the water that enters the system. Depending on the concentration of sodium and hardness in the water which enter the system, the value of sodium in the treated water can be above the values recommended in European Directive 98/83 CE If the water is to be consumed by people who must follow low sodium diets, it is recommended to install a reverse osmosis system SERVICE PHASE During treatment the water enters the valve through the inlet, flows into the top of the bottle, flowing through the resin bed in descending order thereby producing the ion exchange process. The treated water is sent through the outlet connection to the service REGENERATION PHASE. Once the resin bed has retained all of the calcium and magnesium ions they must be regenerated for a new cycle. The regeneration process consists of 4 steps aiming at the regeneration of the resin bed and its preparation for the new cycle. Softeners from the CURVE, D-UF and D-DF series automatically switch between operating and regeneration phases without the user having to manipulate the system. The final user should only keep the brine tank full of salt for softeners. 2

3 3. - GENERAL TECHNICAL CHARACTERISTICS. Working pressures: - Minimum pressure: 2,5 kg/cm² - Maximum pressure: 6 kg/cm² If the pressure is less than 2.5 Kg / cm² a pumping system must be installed to ensure the flow and pressure required. If the pressure is greater than 6 Kg / cm² a pressure reducer must be installed. Operating temperatures: - The equipment should not be supplied with hot water (T> 36 C). - The room temperature should be between 1-45 C. Component materials: - Valve: Reinforced Noryl. - Bottle: Wound of reinforced polyester with fiberglass. - Deposit: Made with P.E. Resin: - Softening cationic resin, regenerable with NaCl ASSEMBLY, INSTALLATION Previous warnings. The softening systems D-DF and D-UF series ARE NOT WATER PURIFYING SYSTEMS, there only purpose is to remove hardness. If the water supply does not come from public supply network or is from an unknown origin, performing a physical-chemical and bacteriological analysis will be necessary to ensure the proper functioning of the water softener equipment, please contact your dealer so they can advise you in these circumstances. The water supply must be suitably filtered, so installing sediment prefilter to facilitate the removal of suspended particles in order to protect internal parts of the valve affecting its operation is recommended Installation. The system operation can only be performed by technically qualified personnel. Instalment requirements & recommendations: Select the location of the instalment. The adequate place where you choose to put the system must have easy access to access the system and also to fill up the salt tank. The system must be placed on a flat surface, protected from direct sunlight, rain and humidity. The system (including the overflow and drain lines) must be placed where the temperature is not below 1ºC or above 49ºC. The system mustn t be installed near acid nor vapours, or be exposed to products derived from petroleum, to avoid the risks of deflagration and explosion. 3

4 The company HIDRO-WATER, S.L. will not be responsible, if the user fails to obey these recommendations and warnings. Water softeners must be installed and connected to the inlet, output and drain tubes according to the manufacturer's instructions and in compliance with current regulations on low voltage electrical and hydraulic installations. Do not install any unit between the outlet of the softener and the inlet of the water heater within less than 3m of piping. If there is a heating element in the system, a non-return valve must be installed to prevent the hot water damaging the water softener. COMPACT SOFTENER TREATED WATER UNTREATED WATER 1. By-pass valve. 2. Softener inlet valve 3. Softener outlet valve 4. Cabinet cover. 5. Cabinet (Bottle container and brine tank) 6. Clarifying filter. 7. Drain line. 8. Overflow line. 9. Drain. Figure 1. Compact softener installation diagram. 4

5 Connecting the system to the water line. Connecting the system to the mains water must be performed with the corresponding By-pass (figure 2), either by using the original by-pass or with 3 ball valves installed in the pipeline. Below is the diagram of the positions of the original by-pass ball valves which come with the system. Figure 2. Diagram of the original by-pass positions. BY-PASS POSITION IN SERVICE POSITION OUTLET INTLET OUTLET INLET With the valves in By-pass position, the water supply won t enter the softener. With the valves in the in service position, the water supply will enter the softener. Untreated water will be supplied to the system. Water will be supplied to the system through the softener. The inlet and outlet of the bypass are indicated by the corresponding arrows. WARNING: The water supply should be adequate to the flow of water to be treated, with a pressure between 2.5 and 4Kg/cm². If the pressure is less than 2.5Kg/cm² a pump system must be installed to ensure the required flow and pressure. If the pressure is greater than 6Kg/cm² a pressure 5 reducer must be installed. 5

6 The drain outlet provided in the softener s valve and the salt tank s overflow lead to the drain. These connections are independent of each other and have individual discharge to avoid any return. Connecting the equipment to pipelines must be done with flexible hoses, which must comply with current regulations, to prevent tensions and possible breakages in the valve s Noryl head Drain line connection The system should be located as close to a drain as possible. The drain level will be below softener s valve and less than 3 meters away. If this isn t the case, please consult our technical department. The drain line connection will be done with a flexible hose which has an interior diameter ( of 15mm. IMPORTANT: The drain hose mustn t be connected to a ditch, drain line or sewer. Always leave an air gap between the drain and the general drain to prevent the possibility of return through the drain. This could affect the system working properly. Figure 3. Drain line and overflow connections Brine line connection It will be necessary to install a brine tube and connect it to the suction inlet, on which will be screwed on. Insure that the filter, insert and cone which are supplied with the kit have been connected correctly Suction intake Filter Insert Cone Nut Connection description Check that all the fittings and couplings are tightened so that there is no air intake. 6

7 Overflow line connection The brine tank s safety overflow leads the overflow to the drain rather than it spilling all over the floor. It is ESSENTIAL to install the overflow attachment that comes with the system. To install the overflow line, the overflow attachment must be placed on the hole which is on the side of the brine tank, being fixed by the plastic nut and gasket as shown (Figure 4) For compact systems, the overflow attachment can be found in a bag and can be fitted on the corresponding side of the cabinet, depending on the location of the system. Fix a piece of tubing with an interior diameter ( of 15mm to the attachment and hang it so it reaches the drain. Connect a tube or flexible hose with an interior diameter ( of 15mm. Figure 4. Tank s overflow attachment Electrical connections. Once the previous connections have been made, the softener s valve programmer must be connected to the mains supply (220V-50Hz), via the transformer supplied with the system. The electrical installation of the equipment must be carried out following the appropriate wiring regulations. The power line must be foreseen by proper protection devices. (Breaker and differential). IMPORTANT: The system must be connected to a separate lighting line, 24 hours a day, NEVER to any line connected to motors. The company HIDRO-WATER, S.L. will not be held responsible if the user fails to obey the recommendations and warnings. 7

8 5. PROGRAMMING. Once the power supply adapter has been connected, the programmer must be programmed. Figure 5. Programmer Front panel. KEY ADVANCE. s the pointer to set the parameters. DESCRIPTION TIME & DAY. Access to programme the time and day. INCREASE VALUES AND CONFIRMATION. Increases the value of the parameters to configure. Confirms the programmed values. MODE. Access to configure regeneration mode. SET REGEN. Access to configure the parameters of the regeneration mode selected. SET CYCLE. Access to the configuration of the regeneration cycle times. MANUAL REGEN. Forced manual regeneration. 8

9 DAY & TIME CONFIGURATION. Steps to follow: Access to the configuration menu. the cursor over the clock to set the hour and minute. Increase value the cursor over the weekly calendar to set the day. Confirm Save the programmed values. 9

10 WORK MODE CONFIGURATION Valve D allows configuration of 4 different working modes: MODE 1: TIMED - Chronometrical regeneration Work Mode. The system will regenerate with the frequency of the days selected and the time established (01-99 days) Once programmed, the screen will show the following: TIME OF DAY DAY OF THE WEEK TIME UNTIL NEXT REGENERATION. STATE MODE 2: METER IMM Volumetric mode with immediate regeneration. The system will regenerate immediately when the volume of treated water has run out. Once programmed, the screen will show the following: TIME OF DAY DAY OF THE WEEK VOLUMETRIC CONTROL INDICATOR AVAILABLE VOLUME STATE MODE 3: WEEK Work mode with weekly chronometrical regeneration. The system will regenerate on the days of the week selected, at the time established. Once programmed, the screen will show the following: TIME OF DAY DAY OF THE WEEK TIME & DAY UNTIL NEXT REGENERATION STATE MODE 4: METER DELAY Volumetric mode with delayed regeneration. The system will regenerate at the programmed time once the volume of treated water has run out. Once programmed, the screen will show the following: TIME OF DAY DAY OF THE WEEK VOLUMETRIC CONTROL INDICATOR AVAILABLE VOLUME DELAYED REG. INDICATOR STATE 10

11 WORK MODE CONFIGURACION DEL: MODE 1 - TIMED. To access the Work Mode, press: Steps to follow: Access to the configuration menu. the cursor to the desired work configuration: (TIME). Confirm Save the programmed values TIMED CONFIGURATION & INTERVAL BETWEEN REGENERACIONS: MODE 1 - TIMED To access the Work Mode, press: Steps to follow: Access to the configuration menu. the cursor to the desired regeneration time. Increase value the cursor to set the number of days between regenerations. Increase value Save the programmed values. 11

12 WORK MODE CONFIGURATION: MODE 2- METER IMM. To access the Work Mode, press: Steps to follow: Access to the configuration menu. the cursor to the desired work configuration: (METER IMM). Confirm the cursor and confirm the desired measurement units: (L) Confirm Save the programmed values VOLUME OF TREATED WATER CONFIGURATION: MODE 2 - METER IMM. To access the Work Mode, press: Steps to follow: L L L Access to the configuration menu. the cursor to set the volume of water that can be treated by the softener s resin bed. Increase value SEE THE TABLE ATTACHED TO SET THE LITRES OF TREATED WATER. Save the programmed values. 12

13 WORK MODE CONFIGURATION: MODE 3 - WEEK To access the Work Mode, press: Steps to follow: Access to the configuration menu. the cursor to the desired work configuration: (WEEK). Increase value Save the programmed values REGENERACION TIME & DAY CONFIGURATION. MODE 3- WEEK To access the programming of the regeneration time, press:. Access to the configuration menu. the cursor to set the regeneration time desired. Increase value the cursor to set the days that we wish regenerations to happen on. Confirm regeneration days. Save the programmed values. 13

14 WORK MODE CONFIGURATION: MODE 4-METER DELAY To access the Work Mode, press: Steps to follow: Access to the configuration menu the cursor to set the regeneration time desired: (METERDELAY). Confirm the cursor and set the desired measurement Units: (L). Confirm Save the programmed values. 14

15 REGENERATION TIME & TRETED WATER VOLUME CONFIGURATION: METER DELAY To access the programming of the regeneration time, press:.. Access to the configuration menu. the cursor to set the regeneration time desired: Increase value the cursor to set the maximum number of days between regenerations. Increase value the cursor to set the volume that the softener s resin bed can treat. Increase value SEE THE TABLE ATTACHED TO SET THE VOLUME OF WATER TREATED DEPENDING ON THE SOFTENER S RESIN BED. Save the programmed values. SAVE THE VALUES 15

16 CALCULATION TABLE TO PROGRAMME THE VOLUME OF TREATED WATER BY A D-DF-M 3 SYSTEM DEPENDING ON THE RESIN AND HARDNESS OF THE WATER. HARDNESS ºHF FOR D-DF-M 3 SYSTEMS 50 ºHF Litres of resin 30 ºHF 40 ºHF 60 ºHF 70 ºHF 80 ºHF 90 ºHF 100 ºHF e.g.: for 30 litres of resin & 50 ºHF of hardness, programme: 3600 litres. - The values shown in the D-DF-M 3 table have been calculated for an exchange capacity established by HIDRO-WATER.. - Depending on the amount of salt used for regenerating, the values shown in the table may vary. CALCULATION TABLE TO PROGRAMME THE VOLUME OF TREATED WATER BY A D-UF-M 3 SYSTEM DEPENDING ON THE RESIN AND HARDNESS OF THE WATER. HARDNESS ºHF FOR D-UF-M 3 SYSTEMS 50 ºHF Litres of resin 30 ºHF 40 ºHF 60 ºHF 70 ºHF 80 ºHF 90 ºHF 100 ºHF e.g.: for 35 litres of resin & 50 ºHF of hardness, programme: 3150 litres. - The values shown in the D-UF-M³ table have been calculated for an exchange capacity established by HIDRO-WATER.. - Depending on the amount of salt used for regenerating, the values shown in the table may vary. 16

17 CONFIGURATION OF REGENERATION CYCLE TIMES. To access the programming of the regeneration time, press:. Access to the regeneration cycle times configuration menu. the cursor to set the minutes of each cycle. Increase value SEE THE TABLE ATTACHED TO SET THE VOLUME OF WATER TREATED DEPENDING ON THE SOFTENER S RESIN BED. Save the programmed values. 17

18 LITRES OF RESIN TIMING PROGRAMME FOR D-DF-M³ SYSTEMS BACKWASH BRINE DRAW RAPID RINSE REFILL 5 5 min 60 min 5 min 5 min 8 5 min 60 min 5 min 8 min 10 5 min 60 min 5 min 8 min 12 5 min 60 min 5 min 10 min 15 5 min 60 min 5 min 10 min 20 5 min 60 min 5 min 15 min 30 5 min 65 min 5 min 20 min min 65 min 10 min 25 min min 65 min 10 min 15 min min 65 min 10 min 20 min min 65 min 10 min 15 min min 65 min 10 min 15 min min 65 min 10 min 20 min TIMING PROGRAMME FOR D-UF-M³ SYSTEMS LITRES OF RESIN BACKWASH BRINE DRAW RAPID RINSE REFILL 14 5 min 60 min 5 min 4 min 18 5 min 60 min 5 min 6 min 22 5 min 60 min 5 min 8 min 35 5 min 60 min 5 min 12 min min 60 min 10 min 10 min min 60 min 10 min 15 min min 65 min 10 min 10 min min 65 min 10 min 15 min 18

19 6. - SOFTENER START-UP Once the hydraulic circuit has been realised, connected to a power source and the microprocessor has been programmed, the system can be started up. Follow the steps as described below: How to start up the softener. Bleed the air bottle - - Make sure that the softener s inlet and outlet valves are closed and the bypass is open to assure that there is water in the system. - Hold the MANUAL REGENRATION button for 5 seconds; after so a manual regeneration will begin. The controller will send an order so that the piston moves to the CYCLE 1 position, BACKWASH. Keep in mind that the motor takes a while to move onto the next cycle, and it is indicated that is moving with the flashing message "GO TO NEXT CYCLE NAME". Until that message disappears from the screen, you cannot advance to the next cycle - Once the piston is allocated in the backwash position, open the inlet valve very slowly a ¼ of the way allowing water to enter the system. - Allow all of the air to be released from the resins bottle. Once all of the air has been bled (Water starts flowing slowly through the drain), slowly open the supply valve fully. - Let the water drain away until it turns completely clear. WARNING: If the valve is opened too much or too quickly resin can be lost. In this position you must hear how the air escapes slowly through the drain line. Start up - Next, PRESS & RELEASE the MANUAL REGENERATION button to manually advance the regeneration cycles. Repeat this operation until you reach CYCLE 4, REFILL in order to bleed the brine line of air. Let the water flow and bleeds all of the air bubbles from the suction line. Once bled: - Let the system fill the brine tank itself. Afterwards, advance the cycle to SERVICE. - Next, you must check that the system is sucking. In the SERVICE position, press the MANUAL REGENERATION button for 5 seconds to start another regeneration and advance the cycles to CYCLE 2, BRINE, just as we ve described before. Visually verify the system is sucking water from the salt tank and is able to remove the water from the brine tank completely. The suction must be constant and the water level in the tank must go down. For a further good subsequent performance, it is critical to check this. If you take air in the suction line, cancel the regeneration by advancing the cycles to SERVICE, review and tighten the components of the suction line and then perform the check. 19

20 - Once the system has been checked that it s sucking correctly, replace the volume of water that had been sucked by setting the system to REFILL & and allow it to go to SERVICE by itself. - The display will show the following information according to the mode set: MODE 1: TIME MODE 2: WEEK MODE 3: METER IMM MODE 4: METER DELAY - Fill the brine tank with salt specifically for softeners either in tablets or type-3 grain and the system is ready for operation. - - At this time and you can have softened water, close the bypass and open the softener's outlet valve. - Check that the turbine works correctly by opening a tap (faucet) and check that the treated water on the display decreases. Softened water regulation - For domestic consumption, a residual hardness of 8 to 10ºF is recommended. To adjust the hardness, half open the built-in mixing controller which is on the same valve. - Check the hardness by analyzing the water from the outlet of the softener. Figure 6. Detailed mixing screw. If the system is without use for a period of a month or more, it must be disinfected with the HW*77 product. Likewise, it is recommended that the system is disinfected every 6 months with the HW*77 product. Consult the technical department at HIDRO-WATER, S.L. 20

21 7. - MENSAGES SHOWN ON THE SCREEN AUTOMATIC LOCK. When the programmer s keyboard hasn t been used for a while, an automatic lock is activated, turning the light off to save electric consumption. By pressing any key, the following message will appear on the display. To unlock the controller press sequentially & as indicated above RETURNING TO THE INITIAL SETTING DUE TO A FAILURE IN THE POWER SUPPLY. When a power failure has occurred during the regeneration process, upon recovering the supply the programmer performs an internal reset, to retrieve the set values and return to the position where it stopped. During this period the programmer shouldn't be handled, the display will show: System error. When the programmer detects an internal error, the following error is displayed. Disconnect & reconnect the programmer and if the message persists, contact your provider. 21

22 8. - INFORMATION DISPLAYED ON THE SCREEN DURING SERVICE PHASE, DEPENDING ON THE CONFIGURATION SELECTED CONFIGURATION: TIMED: Delayed clockwork. TIME OF DAY DAY OF THE WEEK TIME UNTIL THE NEXT REGENERATION STATE CONFIGURATION: WEEK: weekly clockwork. TIME OF DAY DAY OF THE WEEK TIME & DAY UNTIL THE NEXT REGENERATION STATE CONFIGURATION: METER IMM: Immediate Volumetric. TIME DAY OF OF DAY THE WEEK VOLUMETRIC CONTOL AVAILABLE VOLUME STATE CONFIGURATION: METER DELAY: Delayed volumetric. TIME OF DAY DAY OF THE WEEK VOLUMETRIC CONTOL AVAILABLE VOLUME DELAYED REG. STATE When the meter reaches zero the display will show the following. TIME OF DAY DAY OF THE VOLUMETRIC WEEK CONTROL TIME AND DAY UNTIL THE NEXT REGENERATION STATE 22

23 9. - PARTS. 23

24 24

25 10. - DIMENSIONS Mm (Inches) 25

26 11. - FAULTS, POSSIBLE CAUSES AND POSSIBLE SOLUTIONS. CAUTION: Those service procedures require that the system pressure is off, are marked with a symbol. When service work is finished, reconnect the water pressure to the system and perform the system start-up. Problem Probable cause Solution 1. The display won t turn on. a. Transformer power cord unplugged. b. No power at the socket. c. The transformer is defective. d. Defective circuit. a. b. c. d. Connect the power Repair the outlet or use one that works. Replace the transformer. Replace the timer. 2. The flow indicator is not flashing when water flows. 3. The control regenerates at the wrong time. a. The diverter valve is in the bypass position. b. The measuring probe is disconnected or is not well connected to the turbine c. The rotation of the turbine is restricted due to foreign matter in the meter. d. Faulty circuit board. a. Power cuts. b. The clock was set to the wrong time. a. b. c. d. a. b. Change to normal service position. Insert the probe fully into its housing. Remove the turbine and rinse with water. The turbine should spin freely, and if not you have to change the meter. Replace the programmer. Set the clock to the correct time. Set the clock to the correct time. 4. Continuous regeneration. a. Faulty programmer. a. Replace the programmer. 5. The control does not regenerate automatically but does regenerate when the button is pressed. a. If the water flow indicator does not work, refer to point No. 5 of the table. b. Faulty circuit board. c. Hardness and capacity are set incorrectly. a. b. c. As the same as point 2 of this manual. Replace the programmer. Set correct values. See the programming section. 6. The water comes out hard between regenerations. a. Wrong regenerating. b. Softener resin dirty. c. Incorrect salt dosage. d. Graduation hardness or wrong capacity. e. Increase in water hardness. f. Restricted rotation of the turbine due to foreign particles in the meter. g. Excessive use of water. a. b. c. d. e. f. g. Repeat the regeneration, verifying that there is the correct dosage of salt. Use a resin cleaner 1. Review system programming depending on the litres of resin. Set correct values. See the programming section. Setting a new hardness value. See the programming section. Remove and unlock the turbine and rinse with clean water. DO NOT REMOVE THE TURBINE FROM THE METRE HOUSING. The turbine should spin freely, and if not, replace the meter. Repair pipes and / or fittings leaking. 7. No brine is drawn. a. Low water pressure. b. Clogged drain line and obstructed aspiration. c. Blocked injector. d. Faulty injector. a. b. c. Set correctly according to instructions. Remove the obstructing matter. Clean injector and screen. d. Replace injector and its lid. 26

27 8. The brine tank overflows. a. b. c. Uncontrollable filling flow. Air intake in the brine line. Improper drain control for the injector. a. Remove and clean salt variable controller and sphere. b. Check all connections on the brine line for leaks. Refer to the instructions. c. Check the controller is correct. d. Drain control clogged with resin or other debris. d. Clean the drain. a. Set the value correctly 9. The system is using more or less salt than was set. a. b. c. Value set incorrectly. Foreign matter in the control which makes incorrect flows. Faulty control. b. Remove the salt regulator and wash the dirt off. Manually programme the system to brine extraction to clean the salt regulator. (After this, set the controller to "Vacuum" to remove the brine from the tank.). c. Replace the faulty parts. 10. Intermittent or erratic brine removal. a. b. Water pressure too low. Faulty injector. a. Set the pump to maintain at least 2.5 kg / cm² in the softener. b. Replace the injector and its lid. 11. No conditioned water after regeneration. a. b. The system didn t regenerate. There s no salt in the brine tank a. Check there is a power supply. b. Add salt in the brine tank. c. Dirty injector. c. Remove and rinse the injector and mesh. NOTE 1: The use of the resins cleaner HW77 (registered trademark by HYDRO-WATER, SL) is recommended. Warning: Use of resins cleaners in unventilated ambient can damage the timer. 27

Commercial Softeners. Installation, Operation & Maintenance Guide. Manual 002.1

Commercial Softeners. Installation, Operation & Maintenance Guide. Manual 002.1 Commercial Softeners Installation, Operation & Maintenance Guide Manual 002.1 Contents Page 1. Unpacking Instructions 3 2. Installation 3 Pre-installation checks Fitting the bottom distribution system

More information

Installation and Instructions 2. Product Features 3-6. Key Pad Functions 7. Distributor Information Programming Guide 8. Master Programming Guide 9-14

Installation and Instructions 2. Product Features 3-6. Key Pad Functions 7. Distributor Information Programming Guide 8. Master Programming Guide 9-14 Installation and Instructions 2 Product Features 3-6 Key Pad Functions 7 Distributor Information Programming Guide 8 Master Programming Guide 9-14 Dimensional Drawing 15 D-STC & D-SMM Valve Assembly 16-17

More information

NORMAL OPERATING DISPLAYS GENERAL OPERATION

NORMAL OPERATING DISPLAYS GENERAL OPERATION SunTapWat e rsys t e ms WS1Cl ac kwat e rsof t ne r Owne r smanual MAIN COMPONENTS Your water treatment system is a point of entry (POE) system composed of three components: A. The control valve and computer

More information

Duplex Commercial Softeners

Duplex Commercial Softeners Duplex Commercial Softeners Installation, Operation & Maintenance Guide Manual 003.1 Contents Page 1. Unpacking Instructions 3 2. Installation 4 Pre-installation checks Fitting the bottom distribution

More information

The ultimate in water softening

The ultimate in water softening Calming troubled waters Metered Water Softener Specification MODEL: CALSOFT M The ultimate in water softening Due to Calmag s commitment to new product development the photographs contained within these

More information

DRS4-RM Manual. Set Up Instructions for DRS4 Series Single Tank

DRS4-RM Manual. Set Up Instructions for DRS4 Series Single Tank Set Up Instructions for DRS4 Series Single Tank Inspect the packaging of the equipment to confirm that nothing was damaged during shipping. (Figure 1) Remove the resin tank(s) and valve(s) from the packaging.

More information

Easy Nest Kits. Installation Suggestions

Easy Nest Kits. Installation Suggestions Easy Nest Kits Installation Suggestions 2 General Recommendations Hydraulics Vacuum breakers should be installed to prevent siphoning. Flexible connectors should follow FRP tank manufacturers recommendations.

More information

AQUAMATIC EASY NEST KITS INSTALLATION SUGGESTIONS

AQUAMATIC EASY NEST KITS INSTALLATION SUGGESTIONS AQUAMATIC EASY NEST KITS INSTALLATION SUGGESTIONS TABLE OF CONTENTS TABLE OF CONTENTS...2 GENERAL RECOMMENDATIONS...2 TROUBLESHOOTING GUIDE...3 EXISTING EASY NEST SYSTEM TROUBLESHOOTING GUIDE...4 COMPONENT

More information

INSTRUCTION MANUAL. Automatic Water Softener System. Model: PSE-08. Xsential Water Filtration Systems

INSTRUCTION MANUAL. Automatic Water Softener System. Model: PSE-08. Xsential Water Filtration Systems INSTRUCTION MANUAL Automatic Water Softener System Model: PSE-08 Xsential Water Filtration Systems 78 Daly Street Ascot Western Australia 6104 Ph: 1300 366 295 Fax: (08) 9277 2266 www.xsential.com.au Welcome

More information

Performa Cv Twin Alternating and High Flow Systems. Manual Supplement

Performa Cv Twin Alternating and High Flow Systems. Manual Supplement Performa Cv Twin Alternating and High Flow Systems Manual Supplement Table of Contents 1.0 Installation and Start-Up.............. 3 Water Line Connection Brine Tank Turbine Connection Connecting Manifold

More information

Autotrol Performa ProSoft

Autotrol Performa ProSoft Autotrol Performa ProSoft With 960 Series Control 5-Cycle Conditioner 5-Cycle FA Filter Water Conditioning Control System Installation, Operation and Maintenance Manual Table of Contents Installation.....................................

More information

Autotrol Performa Filter Valve Series

Autotrol Performa Filter Valve Series TM Autotrol Performa Filter Valve Series 440i Control 940F Control 960F Control Water Conditioning Control System Installation, Operation and Maintenance Manual Table of Contents Installation............................

More information

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST OIL-LESS TYPE IMPORTANT: PLEASE READ CAREFULLY BEFORE STARTING OPERATIONS. THE CONTENTS ARE FOR GENERAL INFORMATION OF ALL THE SIMILAR MODELS. Record

More information

With 960 Series Control Water Conditioning Control System Installation, Operation and Maintenance Manual

With 960 Series Control Water Conditioning Control System Installation, Operation and Maintenance Manual With 960 Series Control Water Conditioning Control System Installation, Operation and Maintenance Manual Part# AP-5100 AP-5125 AP-5150 Manufactured by: Good Water Warehouse Inc. 1700 E. Walnut Ave Fullerton,

More information

Installation and Maintenance Manual. ECO Filtration Unit with 6-way-Top-Mount-Valve. Art. Nr

Installation and Maintenance Manual. ECO Filtration Unit with 6-way-Top-Mount-Valve. Art. Nr Installation and Maintenance Manual ECO Filtration Unit with 6-way-Top-Mount-Valve Art. Nr. 300100 300101 300102 Important Details: - Using of this filtration unit for swimming pools and its guard band

More information

O&M Receiving and Inspection. Storage of Water Treatment Media

O&M Receiving and Inspection. Storage of Water Treatment Media O&M 105.1 Receiving and Inspection 1. Equipment should be checked against the Bill of Lading to verify that the number of pieces received matches those shipped. 2. Equipment should be carefully inspected

More information

265 Series Valve Operation Manual

265 Series Valve Operation Manual 265 Series Valve Operation Manual Note: 1. Read all instructions carefully before operation. 2. Avoid pinched o-rings during installation by applying (provided with install kit) NSF certified lubricant

More information

Softeners Clack Model V125DTH Medical / Industrial Series Operation and Service Manual

Softeners Clack Model V125DTH Medical / Industrial Series Operation and Service Manual Softeners Clack Model V125DTH Medical / Industrial Series Operation and Service Manual www.ameriwater.com 800-535-5585 AmeriWater LLC 3345 Stop 8 Rd. Dayton, OH 45414 Clack Softener Manual, 98-0180 Rev.

More information

Chloramines Removal Filter CLF20 and CLF35 Models

Chloramines Removal Filter CLF20 and CLF35 Models Chloramines Removal Filter CLF20 and CLF35 Models Operating and Maintenance Manual #51793 Rev. 6/09 Performance and Specifications Recommended Mineral Installation Shipping Item Model Media Flow Rate Tank

More information

WATER SOFTENER. Instructions Manual Use and Maintenance

WATER SOFTENER. Instructions Manual Use and Maintenance WATER SOFTENER Instructions Manual Use and Maintenance Thank you for purchasing the H+WS WATER SOFTENER from HYDROCARE... Thanks to the water softener, your water system, heating system, boiler as well

More information

Owners Manual Models: 075-AQF-CX. Aquatrol Backwashing Catalytic Carbon Filter. Visit us online at.

Owners Manual Models: 075-AQF-CX. Aquatrol Backwashing Catalytic Carbon Filter.  Visit us online at. Visit us online at www.uswatersystems.com Aquatrol Backwashing Catalytic Carbon Filter Owners Manual Models: 075-AQF-CX REVISION # 1.0 REVISION DATE October 11, 2017 US Water Systems, Inc. 1209 Country

More information

UsER manual for Watersens ph -REDOX

UsER manual for Watersens ph -REDOX UsER manual for Watersens -REDOX Cl 8 1 2 6 3 3 7 7 4 4 4 4 Parts List 1 Redox Probe 1 x 2 PH Probe 1 x 5 Tube Weight 2 x 6 Connection Valve 1 x chlorine 3 Chlorine and Pumps 2 x 7 Dosing Valve 2 x 5 5

More information

WARNING! Equipment for treatment of water intended for human consumption (Directive 98/83 CE).

WARNING! Equipment for treatment of water intended for human consumption (Directive 98/83 CE). WARNING! Equipment for treatment of water intended for human consumption (Directive 98/83 CE). The equipment must be used only for the utilization for which they have been designed, as shown in the technical

More information

User's Manual. MixRite TF 10. Edition 05.08

User's Manual. MixRite TF 10. Edition 05.08 User's Manual MixRite TF 10 Edition 05.08 1 Tefen MixRite TF 10 fertilizer and chemicals Injector Congratulations on your purchase of one of Tefen s high quality products. To get the best results from

More information

ACTIVATE YOUR WARRANTY BY REGISTERING YOUR PRODUCT AT

ACTIVATE YOUR WARRANTY BY REGISTERING YOUR PRODUCT AT OWNER'S MANUAL MAX Specialty Series with Triton Metered and Timered Electronic Control Valves ACTIVATE YOUR WARRANTY BY REGISTERING YOUR PRODUCT AT www.watertech.com or call 888-254-8412 Dealer Contact

More information

Operation Manual. Carbon Filtration Industrial Drive, Orlinda, TN fax

Operation Manual. Carbon Filtration Industrial Drive, Orlinda, TN fax Operation Manual Carbon Filtration 615-654-4441 sales@specialtyh2o.com 615-654-4449 fax TABLE OF CONTENTS Section 1 GENERAL 1.1 Warnings and Cautions... 1 1.2 Theory of Operation... 2 1.3 System Illustration...

More information

Installation of Your SprayMaster System

Installation of Your SprayMaster System Installation of Your SprayMaster System 1. At the installation site, remove all equipment from the corrugated box and the polyethylene drum and replace the drum lid. Check the picture to identify each

More information

OXYGEN MINERALE ABSOLUTE RANGE OWNER S MANUAL OXY MINERALE 600/1000 SERIES

OXYGEN MINERALE ABSOLUTE RANGE OWNER S MANUAL OXY MINERALE 600/1000 SERIES PURAPOOL OXYGEN MINERALE ABSOLUTE RANGE OWNER S MANUAL OXY MINERALE 600/1000 SERIES 1. PARTS IDENTIFICATION LIST 1. 5. 2. 4. 3. 6. 6. Figure 1.1 1. OXYGEN Minerale Power pack with timer option (x1) 2.

More information

OWNER S MANUAL NMB SERIES

OWNER S MANUAL NMB SERIES OWNER S MANUAL NMB SERIES NMB Manual V2.0.doc 1. PARTS IDENTIFICATION LIST 1. 5. 2. 4. 3. 6(a). 6(b). Figure 1.1 1. Powerpack with timer option (x1) 2. Cell (x1) 3. Cell Housing (x1) 4. O-ring (x1) 5.

More information

Iron Filter Installation / Operation Manual

Iron Filter Installation / Operation Manual Iron Filter Installation / Operation Manual BrassMaster and BrassMaster Plus Technical Video Library: http://watercontrolinc.com/residential-technical-support/residential-technical-videos BrassMaster technical

More information

E L E C T R O N I C S X T

E L E C T R O N I C S X T 1 - VAV OPRATO Regeneration button. ervice indicator: - Valve in service: lighted icon - ight regeneration: flashing icon nformation indicator, viewed in Diagnostic & rror modes ndicator in programmation

More information

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289 3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for

More information

RAM 4021-DPX Operation Manual

RAM 4021-DPX Operation Manual RAM 4021-DPX Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS ABL 4021-DPX / RAM 4021-DPX For Your Safety... 3 Description... 3 Setup Mode... 4 Lights/Alarms... 4 Operation...

More information

LAMINATED SAND FILTERS Filtering Equipment. Manufactured in Spain for PQS Piscinas y Consumo SA

LAMINATED SAND FILTERS Filtering Equipment. Manufactured in Spain for PQS Piscinas y Consumo SA LAMINATED SAND FILTERS Filtering Equipment Manufactured in Spain for PQS Piscinas y Consumo SA LAMINATED SAND FILTERS Filtering Equipment Filtration is an impotant part of pool maintenance. However, a

More information

Instructions for SILEX 1C Mixed bed cartridge filter

Instructions for SILEX 1C Mixed bed cartridge filter D01B-30A-UK1 January 2017 Instructions for SILEX 1C Mixed bed cartridge filter With conductivity sensor Gravity flow or pressure installation SILHORKO-EUROWATER A/S Phone +45 86 57 12 22 DK-8660 Skanderborg

More information

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION OCT2010 STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 020 87833050

More information

AUTOMATIC TIRE INFLATOR # MW-60, MW-60-4WAY & MW-64HP

AUTOMATIC TIRE INFLATOR # MW-60, MW-60-4WAY & MW-64HP USER MANUEL AUTOMATIC TIRE INFLATOR # MW-60, MW-60-4WAY & MW-64HP TIRE EQUIPMENT MANUFACTURER 1.866.409.RACK WWW.MARTINSINDUSTRIES.COM info@martinsindustries.com PARTS Verify that the following components

More information

Arcadia Spas User Manual

Arcadia Spas User Manual Arcadia Spas User Manual Dear Spa Buyer, Congratulations on your purchase of a new Arcadia Spa. You now possess the ultimate passport to tranquility a miniature vacation at home, ready and waiting for

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! INLET PRESS TAP WHITE-RODGERS 36E93-304 Delay-Opening Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY

More information

AUTOMATIC SOFTENERS SERIES: AM/DT AM/RDT AM/DV AM/RDV AM/D METER AM/RD METER INSTRUCTIONS MANUAL WARNING!

AUTOMATIC SOFTENERS SERIES: AM/DT AM/RDT AM/DV AM/RDV AM/D METER AM/RD METER INSTRUCTIONS MANUAL WARNING! AUTOMATIC SOFTENERS SERIES: AM/DT AM/RDT AM/DV AM/RDV AM/D METER AM/RD METER INSTRUCTIONS MANUAL WARNING! The equipment must be used only for the utilization for which they have been designed, as shown

More information

After filling the pool with clean water in the summer, two basic factors can take place due to the exposure of water to the sun and the air.

After filling the pool with clean water in the summer, two basic factors can take place due to the exposure of water to the sun and the air. ENGLISH WHAT HAPPENS TO THE WATER IN YOUR POOL? This should be a question of prime consideration for all pool owners. In the past some pools did not use filtering systems, the owner was faced with the

More information

Model 130M Pneumatic Controller

Model 130M Pneumatic Controller Instruction MI 017-450 May 1978 Model 130M Pneumatic Controller Installation and Operation Manual Control Unit Controller Model 130M Controller is a pneumatic, shelf-mounted instrument with a separate

More information

Hurlcon KX Siesta Above Ground Salt Water Chlorinator by AstralPool Australia

Hurlcon KX Siesta Above Ground Salt Water Chlorinator by AstralPool Australia Hurlcon KX Siesta Above Ground Salt Water Chlorinator by AstralPool Australia OPERATING INSTRUCTIONS AstralPool Australia Pty. Limited. A.B.N. 97 007 284 504 Melbourne: Ph: (03) 8796 8600 Fax: (03) 8796

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

Ventam 85 Installation & Commissioning Instructions

Ventam 85 Installation & Commissioning Instructions Ventam Systems Ltd Unit D4 Seedbed Business Centre Vanguard Way Shoeburyness Essex SS3 9QY Phone 01702 382 307 Fax 01702 382 340 Ventam 85 Installation & Commissioning Instructions 1 General The Ventam

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Models: EPS Single Pump EPT Twin Pump EPS-HP EPT-HP Single Pump High Pressure Twin Pump High Pressure

More information

INSTALLATION & START-UP INSTRUCTIONS. Clack WS1 & WS1.25 METER WATER SOFTENER SYSTEMS

INSTALLATION & START-UP INSTRUCTIONS. Clack WS1 & WS1.25 METER WATER SOFTENER SYSTEMS INSTALLATION & START-UP INSTRUCTIONS Clack WS1 & WS1.25 METER WATER SOFTENER SYSTEMS 1999-2009 QualityWaterForLess.com - 1 - info@qualitywaterforless.com Preface: Thank you for your purchase of a new Water

More information

Vortex Spas User Manual

Vortex Spas User Manual Vortex Spas User Manual Dear Spa Buyer, Congratulations on your purchase of a new Vortex Spa. You now possess the ultimate passport to tranquility a miniature vacation at home, ready and waiting for you

More information

Vessel Installation and Operating Manual

Vessel Installation and Operating Manual For In-ground and Aboveground Pools Vessel Installation and Operating Manual Important Safety Information Please read this manual prior to installation. Nature 2 Express is designed to sanitize in-ground

More information

SPECIFICATIONS APCEPH1

SPECIFICATIONS APCEPH1 APCEPH1 ph CONTROLLER SPECIFICATIONS APCEPH1 Input voltage 120 Volts AC Maximum amperage 14.5 amps @ 120 VAC ph Accuracy +/- 0.2 ph ph Control range Adjustable 4.5 8.5 ph Weight < 1 lbs Dimensions 3" x

More information

US Water Systems Synergy Model 9000/9100/9500 Service Manual

US Water Systems Synergy Model 9000/9100/9500 Service Manual US Water Systems Synergy Model 9000/9100/9500 Service Manual IMPORTANT: Fill in Pertinent Information on Page 3 for Future Reference IMPORTANT PLEASE READ: The information, specifications and illustrations

More information

USE AND MAINTENANCE MANUAL V360

USE AND MAINTENANCE MANUAL V360 USE AND MAINTENANCE MANUAL V360 S.I.A.T.A. S.r.l Società Italiana apparecchiature trattamento acqua MAN0031 BOZZA Pag. 1 of Document Revision Revision note Date MAN0031 A Draft S.I.A.T.A. S.r.l Società

More information

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For Your Safety... 2 Description.... 2 Setup Mode.... 2 Lights/Alarms.... 3 Operation.... 4 Calibration....

More information

Owner s Manual. R&M Water Group TM. Models: SA-TECH PLUS 40 DB SA-TECH PLUS 48 DB

Owner s Manual. R&M Water Group TM. Models: SA-TECH PLUS 40 DB SA-TECH PLUS 48 DB TM Owner s Manual Models: SA-TECH PLUS 40 DB SA-TECH PLUS 48 DB R&M Water Group TM Water Conditioning & Purification Systems A Division of Water Technologies, Inc. 28 South 1550 West, Lindon, Utah 84042

More information

USER MANUAL. JET TST and JET TST S.

USER MANUAL. JET TST and JET TST S. USER MANUAL JET TST and JET TST S www.sisteven.com Types of Jet fans: JET TST UNI: Impulse axial fan single direction JET TST S UNI: Impulse axial fan single direction (short case) JET TST REV: Impulse

More information

6900 Maintenance Instruction System Flush

6900 Maintenance Instruction System Flush Equipment Required FA74005 Damper Drain Tube FA16005 Cover Removal Tool FA900005 Beaker 0.25 Litre FA900003 Solvent Cleaning Bottle FA940021 Syringe Polypropylene 50 ml as required FA999045 Gloves Latex

More information

INSTALLATION & START-UP INSTRUCTIONS FLECK 9100SXT METER TWIN ALTERNATING WATER SOFTENER SYSTEMS

INSTALLATION & START-UP INSTRUCTIONS FLECK 9100SXT METER TWIN ALTERNATING WATER SOFTENER SYSTEMS INSTALLATION & START-UP INSTRUCTIONS FLECK 9100SXT METER TWIN ALTERNATING WATER SOFTENER SYSTEMS 1999-2007 QualityWaterForLess.com - 1 - info@qualitywaterforless.com Preface: Thank you for your purchase

More information

RAM 4021-PR. Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

RAM 4021-PR. Operation Manual. Worldwide Manufacturer of Gas Detection Solutions RAM 4021-PR Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021-PR For Your Safety... 2 Description.... 2 Setup Mode.... 2 Lights/Alarms.... 3 Operation.... 4

More information

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For Your Safety... 2 Description.... 2 Setup Mode.... 2 Lights/Alarms.... 3 Operation.... 4 Calibration....

More information

ORB-400 BUBBLE/HAZE MACHINE. Item ref: UK User Manual

ORB-400 BUBBLE/HAZE MACHINE. Item ref: UK User Manual ORB-400 BUBBLE/HAZE MACHINE Item ref: 160.462UK User Manual Caution: Please read this manual carefully before operating Damage caused by misuse is not covered by the warranty Introduction Thank you for

More information

PRAHER PLC-MP AQUASTAR MANAUL 2009

PRAHER PLC-MP AQUASTAR MANAUL 2009 PRAHER PLC-MP AQUASTAR MANAUL 2009 1. Copyrights This Operating Manual contains copyright-protected information. All rights reserved to Praher Kunststofftechnik GmbH. This Operating Manual is designed

More information

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WHITE-RODGERS 36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

IWT 565 Series HTO Series Operation Manual

IWT 565 Series HTO Series Operation Manual IWT 565 Series HTO Series Operation Manual Note: 1. Read all instructions carefully before operation. 2. Avoid pinched o-rings during installation by applying (provided with install kit) NSF certified

More information

Operating Instructions Part No

Operating Instructions Part No DIGITAL AUTOMATIC TYRE INFLATOR Operating Instructions Part No. 11.0578 Thank you for selecting this Jamec Pem Automatic Tyre Inflator. Please read this manual before carrying out any installation or service

More information

OPERATING AND MAINTENANCE MANUAL GOLD LINE EXTRACTION CLEANERS M14-M26

OPERATING AND MAINTENANCE MANUAL GOLD LINE EXTRACTION CLEANERS M14-M26 OPERATING AND MAINTENANCE MANUAL GOLD LINE EXTRACTION CLEANERS M14-M26 Made For: Spitwater Australia Pty Ltd 953 Metry St North Albury, NSW, Australia WARNING: FAILURE TO FOLLOW OPERATING, SAFETY AND MAINTENANCE

More information

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WTE-RODGERS 36E96-314 DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL

More information

Installation Operation Maintenance Manual

Installation Operation Maintenance Manual Installation Operation Maintenance Manual Simplex Water Softeners With WS1, 1.5 & 2 Series Valve Models 20 ltr - 750 ltr SIMPWS1 REV3 13/07/11 PAGE 1 OF27 1.0 PARTS LIST...3 1.1 BASIC PARTS LIST...3 1.2

More information

1020 Industrial Drive, Orlinda, TN fax

1020 Industrial Drive, Orlinda, TN fax Operation Manual Tank Distribution System A-UPT Series 615-654-4441 sales@specialtyh2o.com 615-654-4449 fax TABLE OF CONTENTS Section 1 GENERAL 1.2 Warnings and Cautions... 1 1.2 Theory of Operation...

More information

Logix 764 Operation Manual. Models: 255 Twin Alternating Twin Parallel Single with Remote Regeneration Start Multi-Single Tank with Lockout

Logix 764 Operation Manual. Models: 255 Twin Alternating Twin Parallel Single with Remote Regeneration Start Multi-Single Tank with Lockout Logix 764 Operation Manual Models: 255 Twin Alternating Twin Parallel Single with Remote Regeneration Start Multi-Single Tank with Lockout 2 Table of Contents Safety Information 4 How To Use This Manual

More information

CCT-7320/ROC-2313 Reverse Osmosis Controller

CCT-7320/ROC-2313 Reverse Osmosis Controller CCT-7320/ROC-2313 Reverse Osmosis Controller 1 General The instrument is a combined control instrument of a reverse osmosis controller and an on-line conductivity instrument. It can perform the operation

More information

WPB 5 / 7 / 10 INSTALLATION, OPERATION, & MAINTENANCE

WPB 5 / 7 / 10 INSTALLATION, OPERATION, & MAINTENANCE PACIFIC LIQUID & AIR SYSTEMS WPB 5 / 7 / 10 INSTALLATION, OPERATION, & MAINTENANCE IN THE BEGINNING Before installing or operating this system, familiarize yourself with these instructions. You should

More information

SpectraPure PUMPED RO SYSTEMS (PSP) User s Manual for PSP-1500 Systems

SpectraPure PUMPED RO SYSTEMS (PSP) User s Manual for PSP-1500 Systems SpectraPure PUMPED RO SYSTEMS (PSP) User s Manual for PSP-1500 Systems 2 3 PSP-1500 SYSTEM DESCRIPTION Reverse Osmosis RO Reverse Osmosis utilizes the unique properties of a semi-permeable membrane to

More information

VX Series Salt Chlorinator S Model

VX Series Salt Chlorinator S Model VX Series Salt Chlorinator S l OPERATING INSTRUCTIONS HURLCON Manufacturing & sales Pty. Limited. A.B.N. 97 007 284 504 www.hurlcon.com.au service@hurlcon.com.au Information and specifications subject

More information

OC Panel High Limit Aquastat Kit, Manual Reset p/n

OC Panel High Limit Aquastat Kit, Manual Reset p/n OC Panel High Limit Aquastat Kit, Manual Reset p/n 233202 Instruction Sheet APPLICATION The OC (Option Control) Panel High Limit Aquastat Kit provides electronic temperature sensing in a UL limit-rated

More information

Series 180. Commercial/Industrial Control System Installation, Operation and Maintenance Manual

Series 180. Commercial/Industrial Control System Installation, Operation and Maintenance Manual Series 180 Commercial/Industrial Control System Installation, Operation and Maintenance Manual Table of Contents Installation............................ 3 Plumbing Inlet and Outlet Piping Drain Line Piping

More information

CAN 565 Series. Softener Manual

CAN 565 Series. Softener Manual CAN 565 Series Softener Manual Note: 1. Read all instructions carefully before operation. 2. Avoid pinched o-rings during installation by applying (provided with install kit) NSF certified lubricant to

More information

Prestige Water Equipment Ltd.

Prestige Water Equipment Ltd. The Prestige range of water softeners complements the range of water pre-treatment products and services. Use of water softening minimises the problems caused by hard water scale such as reduced heat transfer

More information

Maximum 0.85 MPa pressure setting Long-life, high flow perfect for balancer applications

Maximum 0.85 MPa pressure setting Long-life, high flow perfect for balancer applications Outstanding performance in extremely low pressure and low pressure ranges from 0.003 to. Realizing high performance, energy saving, and compact size. Realize precise pressure control in a pressure range

More information

VX Series Salt Chlorinator T Model

VX Series Salt Chlorinator T Model VX Series Salt Chlorinator T Model OPERATING INSTRUCTIONS www.hurlcon.com.au email: service@hurlcon.com.au Information and specifications subject to change without notice. Melbourne: Ph: (03) 9765 9700

More information

36H SERIES Combination Gas Valve

36H SERIES Combination Gas Valve FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION The 36H series combination gas valve is

More information

Appendix A. Imbrium Systems Jellyfish Filter Inspection and Maintenance Information

Appendix A. Imbrium Systems Jellyfish Filter Inspection and Maintenance Information Appendix A Imbrium Systems Jellyfish Filter Inspection and Maintenance Information Jellyfish Filter Inspection and Maintenance Regular inspection and maintenance are proven, cost-effective ways to maximize

More information

Page INDEX SAFETY INSTRUCTIONS... 2 HOW YOUR AQUASPHERE CHLORINATOR WORKS... 3 AQUASPHERE CHLORINATOR OPERATION... 4 CONTROL PANEL FUNCTIONS...

Page INDEX SAFETY INSTRUCTIONS... 2 HOW YOUR AQUASPHERE CHLORINATOR WORKS... 3 AQUASPHERE CHLORINATOR OPERATION... 4 CONTROL PANEL FUNCTIONS... Instruction Manual INDEX Page SAFETY INSTRUCTIONS... 2 HOW YOUR AQUASPHERE CHLORINATOR WORKS... 3 AQUASPHERE CHLORINATOR OPERATION... 4 CONTROL PANEL FUNCTIONS... 4 AUTOMATIC OPERATION... 5 INDICATOR LIGHTS:

More information

RAM Operation Manual

RAM Operation Manual RAM 4021-1 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021-1 For Your Safety... 2 Description... 2 Setup Mode... 3 Lights/Alarms... 3 Operation... 4 Calibration...

More information

Endo-Flush Order # ZUTR30004 OPERATION MANUAL. Zutron Medical, LLC W 98 th St #40-27 Lenexa, KS Phone Fax

Endo-Flush Order # ZUTR30004 OPERATION MANUAL. Zutron Medical, LLC W 98 th St #40-27 Lenexa, KS Phone Fax OPERATION MANUAL Zutron Medical, LLC 17501 W 98 th St #40-27 Lenexa, KS 66219 Phone 877-343-5873 Fax 913-967-5944 ZUT-Lab-004-30004 REV. 03312017 Table of Contents 2 Introduction 1. Intended Use 2. Labels,

More information

Installation and Operating Manual

Installation and Operating Manual Safety Instructions Important Information Please read prior to installation ATTENTION! ELECTRICAL HAZARD FOR INGROUND POOLS AND ABOVEGROUND POOLS Installation and Operating Manual IMPORTANT Pool Owner,

More information

GM Series Dual-Block Multi-Function Gas Control Valves

GM Series Dual-Block Multi-Function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series

More information

INSTALLATION AND OPERATION INSTRUCTIONS

INSTALLATION AND OPERATION INSTRUCTIONS "GEO-PULSE" THE HEART BEAT OF YOUR GEOTHERMAL SYSTEM This manual is to assist you in your installation and operation of your new "GEO-PULSE" geothermal pumping module. Read the manual thoroughly before

More information

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment 1. Application Emergency eyewash and eye/face wash equipment are prescribed first aid installations for workplaces

More information

Pressure Dump Valve Service Kit for Series 2300 Units

Pressure Dump Valve Service Kit for Series 2300 Units Instruction Sheet Pressure Dump Valve Service Kit for Series 00 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00 applicator tanks when the unit

More information

G92 Series BASOTROL Automatic Pilot Gas Valve

G92 Series BASOTROL Automatic Pilot Gas Valve Installation Instructions Issue Date September 17, 2008 G92 Series BASOTROL Automatic Pilot Gas Valve Installation IMPORTANT: Only qualified personnel should install or service BASO Gas Products. These

More information

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1. 2 GALLON TWIN STACK AIR COMPRESSOR Model: 9526 DO NOT RETURN TO STORE. Please CALL 800-348-5004 for parts and service. CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or

More information

G7S Hand Pump Owner s Manual

G7S Hand Pump Owner s Manual G7S Hand Pump Owner s Manual Copyright Air Venturi 2018 Version 4-18 Specifications 24.80 inches long closed 43.31 inches long extended 4500 psi/310 bar max pressure Features Integral manometer (pressure

More information

AutoChanger Installation & User Guide Issue 2

AutoChanger Installation & User Guide Issue 2 1 INDEX Page 1. Introduction... 3 2. AutoChanger Components Guide 4 3. Installation. 5-11 a) Installation Guidelines.. 5 b) Installation Retrofit... 6-11 c) Installation New... 11 4. AutoChanger User Guide

More information

RAM 4021 Operation Manual

RAM 4021 Operation Manual RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For your safety...3 Description...3 Set-up mode...4 Annunciator lights/alarms...4 Operation...5 Calibration...6

More information

FX134, FX1234, FX3030 Problem and Solutions

FX134, FX1234, FX3030 Problem and Solutions FX134, FX1234, FX3030 Problem and Solutions Unit Will Not Power Up Turn the power switch on. The unit LCD will display revision program and filter life within 3 to 5 seconds after turning on unit. If this

More information

Installation Operation Maintenance Manual

Installation Operation Maintenance Manual Installation Operation Maintenance Manual Duplex Water Softeners With WS1, 1.5 & 2 Series Valve Models 20 ltr - 750 ltr 1.0 PARTS LIST... 3 1.1 BASIC PARTS LIST... 3 1.2 MISSING OR DAMAGED GOODS... 3 2.0

More information

SF SERIES CNG COMPRESSOR MODEL HF-4MH. 4 Nm3/Hour Displacement OPERATION MANUAL

SF SERIES CNG COMPRESSOR MODEL HF-4MH. 4 Nm3/Hour Displacement OPERATION MANUAL SF SERIES CNG COMPRESSOR MODEL HF-4MH 4 Nm3/Hour Displacement OPERATION MANUAL 1 Content 1. General Description...3 2. Main technical parameters...3 3. Structural principle...4 3.1Main structure...4 3.2Compressor

More information

Part IV: Troubleshooting

Part IV: Troubleshooting Part IV: Troubleshooting Excessive Oil Carryover Pump-Up Time Test Excessive oil carryover can have adverse effects on the performance of pneumatic climate control systems. Although some oil entrainment

More information

Assembling & Installing your Pool Cleaner

Assembling & Installing your Pool Cleaner Assembling & Installing your Pool Cleaner STEP 1: Check Contents of the Box Remove the Badu Clean Supreme body and all parts from the box and check that the following components are included. Refer to

More information

Operation and Maintenance Manual for GENTEC Model 881VR Continuous/Intermittent Digital Suction Regulators

Operation and Maintenance Manual for GENTEC Model 881VR Continuous/Intermittent Digital Suction Regulators Operation and Maintenance Manual for GENTEC Model 881VR Continuous/Intermittent Digital Suction Regulators Genstar Technologies Co., Inc. 4525 Edison Avenue Chino, CA 91710 USA TEL 909-0-272 FAX 909-0-485

More information