Manual Instruction. Condor. Staging and sequencing control GLW 4 GLW 4, GLW 4 -S and GLW 4-S kompl.

Size: px
Start display at page:

Download "Manual Instruction. Condor. Staging and sequencing control GLW 4 GLW 4, GLW 4 -S and GLW 4-S kompl."

Transcription

1 Manual Instruction Condor Staging and sequencing control GLW 4 GLW 4, GLW 4 -S and GLW 4-S kompl.

2 GLW 4 GLW 4 without wiring, enclosure GLW 4 S GLW 4 in pre-wired plastic enclosure, (dimensions: 420x300 x170mm), DIN-Rail mounting, internal terminal blocks and wiring diagram. GLW 4-S complete GLW 4 in pre-wired plastic enclosure, (dimensions: 420x300 x170mm), DIN-Rail mounting, internal terminal blocks and wiring diagram. Additionally wired for 4 compressors: isolator, rotary switch bridge timer, rotary switch compressor 1-4, indicator lamps for voltage supply and compressors 1 4. Operating Manual GLW 4 / GLW 4S Condor Pressure Control GmbH Warendorfer Straße D Ennigerloh Phone: +49 (0) / 89-0 Telefax: +49 (0) / info@condor-cpc.com http: Please observe the safety guidelines in chapter 2 Doku.-Version: Data: Manual Instruction GLW Part No: (GLW 4); (GLW 4-S); (GLW 4-SK) SW-Version: V 1.01 HW-Version: V 3.00 Data: Page 2

3 Table of Contents 1 Introduction 4 2 Safety guidelines Marking of guidelines in the operating manual To be observed Additional documents 5 3 General 5 4 Hardware Pressure measuring methods Remote release input (I51) Compressor inputs (I11 up to I42) Alarm output (51/52/54) Time switch Bridging time switch (I61, I62) Ball valve/output K External pressure measurement (p+ / p-) 8 5 Programming First steps Front view Main menu Menu: Main menu Operating hours General settings General settings: Operating mode profiles General settings: External input General settings: Alarm pressure, Alarm time, Alarm relay General settings: Logic inputs General settings: Buzzer General settings: Ball valve/output K General settings: Immediate load changeover Menu: General settings Time switch program Menu: Time switch program Selecting profiles Standby-time (Waiting time) Load changeover time Monitoring time Menu: up to max. Profile Time delay start 16 7 State of delivery 16 8 Terminal connections 16 9 PC interface Technical data Conformity Connecting diagram GLW Connecting diagram GLW 4S Connecting diagram GLW K Programming example, page Programming example, page 22 Page 3

4 1 Introduction In applications where several compressors are used for an air pressure supply system, it is desirable to use a supervisory staging and sequencing control. This control has been realized for many years by the CONDOR GLW 16 and as of June 2004 by the GLW 4 (with many additional functions such as time switch, ball valve function, primary load/load changeover and much more). A staging and sequencing control regulates uniform distribution of the individual compressors hours and guarantees an optimal efficient and economical operation of several compressors. The individual compressor parameters can be programmed in up to 6 different profiles which, considering the general settings, are controlled by the internal time switch. 2 Safety guidelines This operating manual exclusively describes the control unit. It contains important references and warnings, and therefore should be read by the installer as well as by the relevant operator before installing and operating the unit. Note! Not only should the general safety references mentioned in this Safety guidelines section be observed, but also any special safety references referred to in the other sections of the manual. 2.1 Marking of guidelines in the operating manual Safety references contained in this operating manual, which can cause personal danger on failure to observe them, are marked with this general danger symbol. marked with this general danger warning symbol against electric voltage.. Page 4

5 2.2 To be observed The description and instructions in this operating manual relate to the GLW 4 control. This operating manual does not take into account either all possible design details, styles or all possible coincidences and incidents, which may occur during mounting, operation and maintenance. The control is to be used by professionally trained personnel (see EN ). In such case that not all of the information and instructions are found in this operating manual, please ask the manufacturer, Condor-Werke (address see page 2). CONDOR-WERKE Gebr. Frede GmbH & Co. KG takes no responsibility in case the operating manual is disregarded. Connecting and maintenance of the control may be carried out by qualified personnel only. Before operation, the GLW 4 must be installed in a suitable enclosure. Before operating, make sure that: The complete installation is voltage free and secured against power up when mounting and servicing, The terminals of the GLW 4 have been properly connected, The technical condition of the connected compressors are adjusted to the special settings of the GLW 4, The connections have been carried out with diligence, The installation has been professionally secured. 2.3 Additional documents In addition to this operating manual and depending on the layout of the switchgear, further documents and manuals may be attached to this operating manual and they are to be observed, such as: Switching and connecting diagrams Programming examples 3 General If several compressors are to be used in a in a pressurized air system, it is convenient to assign the primary and peak-demand load operating mode to the compressors. Primary load is the operation of a compressor on low air demand. Should the demand for air rise such that one compressor cannot meet the demand alone, then a second compressor is staged in order to cover the peak-load demand. The GLW 4 is a staging and sequencing control for up to 4 compressors! All settings, e.g. load changeover time and thresholds are programmed by means of three keys next to the LCD display without any special programming knowledge. All specific compressor data are programmed in so called profiles. The internal time switch can control up to 6 different profiles. Connection to the pressurized air system is not yet required. Page 5

6 Further Advantages For each compressor, cut-in and cut-out thresholds can be programmed. In case only two compressors need to be controlled, then the other two remaining switching hysteresis can be used for additional monitoring purposes. Besides the staging and sequencing features, the following special functions are available: - Freely programmable integrated time switch. - Free assignment of primary load and load changeover (i.e. the primary compressor runs always, the other compressors are sequenced) - Freely programmable ball valve function, with max. three compressors. - Four separate inputs for power up time, operating hours, errors or switching cycles. - Following completion of a preset stand-by time the next compressor, if desired, will be activated, even if it has not yet reached its own activation threshold - The function "release input", e.g. switches the GLW 4 off for servicing purposes, after reaching the next cut-out threshold. - Programming protection: programming is only possible if the password is known! - All settings can be deactivated separately! - Freely programmable voltage free SPDT as alarm output. With the GLW 4, CONDOR-WERKE offers an electronic solution for staging and sequencing up to max. 4 compressors. The GLW 4 is laid out for 35mm DIN-rail mounting according to DIN EN The system can be used to control piston as well as screw compressors. A rotation of the compressor starting sequence ensures that all connected compressors are equally used. Rotation of the pressure threshold points associated with each compressor is automatically carried out by entering the "load changeover time". A load changeover time of 0 to 999,9 can be programmed. When entering "", the load changeover is not carried out. By entering "primary load", the connected compressor will not be considered during rotation. Rotation only then takes place after both the load changeover time and the highest cut-in pressure setting have been reached. The possibility is also given to program all compressors with identical cut-off pressures. However, setting the same cut-in pressures is not possible. 4 Hardware The GLW 4 is a compressor control unit featuring an integrated relative pressure transducer (0-16 bar, quick connect ) for DIN-rail mounting, 6 optocoupler inputs, 5 voltage free SPDT's, an analog input (two wire, ma) for external pressure measurement, a graphic LCD display, 3 key operation and a V24 interface. The following technical points should be observed: Page 6

7 4.1 Pressure measuring methods The GLW 4 can measure pressure using two methods: a.) Internal pressure transducer The control is connected directly with the air pressure system by means of a quick connect for a 6 mm pneumatic tube (e.g. FESTO Type PAN 6X1). Measuring range: 0 to 16 bar b.) External pressure transducer A standard pressure transducer (two wire, ma) can be connected to p+ and p- terminals of the controller. It must be activated in the main menu under general settings "Pressure measurement external". The internal pressure sensor can only be used for a max. measuring range of bar. When connecting an external pressure transducer, please observe the polarity. 4.2 Remote release input (I51) (GLW 4: I51; GLW 4-S and GLW 4-SK: X2-4) In operating mode, a voltage (230 V AC) must be applied to terminal I51. As soon as the voltage on I51 is switched off (e.g. night time switchboard power down) the GLW 4 is powered down after exceeding the cut-in threshold 1. When the voltage is again applied to I 51, the GLW 4 will continue to operate. When using this function, all set times are not deleted but continue to function after powering up. The corresponding reference potential (generally the N conductor) must be applied to terminals I52/I Compressor inputs (GLW 4: I11 bis I42; GLW 4-S and GLW 4-SK: X2-6 bis 9) The input terminals I11 up to I42 can be used to additionally monitor the connected compressors (operating hours or error messages or switching cycles). The input logic (NO or NC) of the inputs can changed in the menu "Logic inputs" under general settings. NO = An action follows when applying a voltage. NC = An action follows when removing a voltage. This function requires the corresponding compressor inputs be connected. 4.4 Alarm output (GLW 4: 51/52/54; GLW 4-S and GLW 4-SK: X2-1 bis 3) If the system pressure sinks below the set alarm pressure and if the set monitoring time has elapsed and if the alarm relay in the menu has been set to ON, then an alarm is given over the alarm output (voltage free SPDT). Furthermore, an alarm is given when the cut-out pressures are exceeded as soon as the monitoring time has elapsed and the alarm relay in the menu has been activated (On). 4.5 Time switch Very often in compressor applications, timer functions are required. The timer functions are activated when under general settings, operating profiles, "Time switch" has been set. This means that the selected profiles in the timer program are executed. Before this, however, date and time under general settings should be checked and eventually updated. An automatic summer/winter changeover is not available. Page 7

8 4.6 Bridging time switch (GLW 4: I 61 and I52/I62; GLW 4-S: X2-5 and X1-N) The time switch function is switched off as soon as e.g., a 230 V AC voltage is applied to terminal I61 and the reference potential (generally the N conductor) has been connected to terminals I52/I62 and under general settings, function external input, the profile selected at the time has been programmed. 4.7 Ball valve/output K4 Once the function ball valve/output K4 has been programmed to "On", then only three compressors can be controlled while the fourth connection is used as a ball valve control. This means, e.g. that the fourth voltage free SPDT can be used to control a weekend disconnection, hereby reducing energy costs caused by air leakage in the pressure line(s). 4.8 External pressure measurement (GLW 4: p+ / p-; GLW 4-S and GLW 4-SK: X2-10 and 11) When selecting "external" for pressure measurement under general settings, the internal pressure transducer is deactivated and the external pressure transducer (two wire, ma) is activated. Furthermore, the corresponding measuring range end value must also be entered. Any standard two wire pressure transducer, ma, U B 18-21V DC can be used. Please observe the polarity when connecting an external pressure transducer! 5 Programming Programming is carried out using the 3 keys. In order to change a parameter, a password must be entered! The default password of the GLW 4 control is Changing the password can be carried out under general setting and should only be done with the necessary corresponding care. Reactivating the control is only possible by CONDOR WERKE Gebr. Frede GmbH & Co. KG upon loss of the password. Once the operating voltage is applied, the Condor Logo (a short acoustic signal can be heard) with the type designation GLW 4 and software version are displayed. When pressing one of the keys, the main display appears: Page 8

9 By pressing the OK key, the error messages (if available) and the status of the control are displayed in clear text. By pressing the arrow keys you can scroll through the main menu. Pressing the OK key will access the corresponding sub menu, use the arrow keys to scroll through the selected menu. 5.1 First steps In the general settings menu, all basic settings are carried out. In the first step, the "general settings" are entered: pressure measurement; unit; language; password; operating method profile, i.e. using the time switch or a specific profile; function of the external input; date, time; alarm settings; logic inputs of the compressors; ball valve function; direct load changeover or only upon reaching the cut-out threshold and the buzzer (on/off). Thereafter if required, the time switch settings in the menu "Time switch program" are carried out and the corresponding profiles specified. Finally, the respective profiles are programmed. Up to 6 different profiles can be programmed as long as the time switch is activated and the different profiles in the time switch program have been selected. 5.2 Front view Page 9

10 5.3 Main menu The arrow keys can be used to scroll through the main menu. When the OK key is pressed, a sub menu is accessed or it confirms the selected setting Menu: Main menu Delete errors; GLW 4 Status Operating Hours Power up time,operating hours, Errors,Switching cycles Menu Time Switch Program Menu Time Switch Program Select Profile Select Profile Profile 6 Profile 2 Page 10

11 5.4 Operating hours When in the main menu operating hours is selected by pressing the OK key, the respective monitoring data (mains power up time, operating hours, number of errors, switching cycles) is displayed. This, however, is only possible when the corresponding logic has been programmed. Pressing all three keys simultaneously, will delete the monitoring data. 5.5 General settings Basic settings are carried out in the general settings menu. All special sub-menu settings are explained below as follows: General settings: Operating mode profiles In this menu, the basic logic of the rules are programmed: The control is powered down. P1 up to P6 Only the selected profile is executed. Time switch The control executes the settings made in the time switch program General settings: External input In this menu, the basic logic of the rules are programmed: The control is powered down. P1 up to P6 Only the selected profile is executed. Time switch The control executes the settings made in the time switch program General settings: Alarm pressure, Alarm time, Alarm relay Under alarm pressure, the alarm level is set, how long the alarm should last and whether also the voltage free SPDT is active. An alarm is given as soon as the alarm time has elapsed and the set alarm level has still not been exceeded General settings: Logic inputs Here, the logic of the inputs for mains power up time, operating hours, errors and switching cycles can be programmed General settings: Buzzer When selecting "On", the internal alarm buzzer is activated General settings: Ball valve/output K4 When selecting "On", only three compressors can be controlled. With the fourth contact, an electric ball valve can be controlled (e.g. week end power down General settings: Immediate load changeover After the load change time has expired and upon reaching the next cut-out threshold, the chronological order of the compressors change. If "On" has been selected in the menu, the load changeover is carried out immediately without reaching the next cut-out threshold. Page 11

12 5.5.8 Menu: General settings Back to Pressure Measurement Internal Switch from internal sensor to external sensor connection. Alarm press bar Alarm time: 999sec Alarm relay: Change Values: Alarm pressure, Alarm time and status of Alarm relay Unit: bar Unit: psi Change unit from bar to psi Logic Inputs Operation/Errors... 1NO 2NO 3NO 4NO Change Logic of Inputs 1 to 4 Language:German/ English/Italian Change language: German, English, Italian Ball valve/output K4 On Change Logic of Compressor Output 4 (41,42,44): On, Change Password: **** **** Change of password Load Changeover Switch immediately Change Logic after Load Changeover: On: Rotation takes place immediately. : Rotation takes place only after reaching the next cut-off threshold. Operating Mode Profiles Time Switch Change logic: Time switch, P1 to P6, Buzzer Buzzer activation and interface release General Settings Function ext. Input No Function Change logic of input I61:, No function, OK P1 up to P6 Back to Back to Date/Time: Mo :44:32 Change Logic of Inputs 1 to 4 Pressure measurement Internal 5.6 Time switch program All specific compressor settings are entered in a so called profile. The time switch function is activated once the setting "Time switch" under general settings "Operating mode profile" has been selected. In the time switch program, a 7 day, 24 hour partition can be found. By programming the desired time periods and assigning the desired profiles, the GLW 4 operates only according to the time switch guidelines. Start and stop times for the following time periods are always the same. The start time period in the follow up menu is automatically given. By changing to a profile (P1 to P6) in "Operating mode Profile" under general settings, the time switch function is deactivated and only the programmed profile is then executed Page 12

13 5.6.1 Menu: Time switch program Back to Time Switch Program Mo-Fr Day 06:00-17:00 Time setting and Logic:, Profiles 1 to 6 Note: Times in the follow up menu are automatically given! Time Switch Program Fr 17:00 to Sa 6:30 Time setting and Logic:, Profiles 1 to 6 Note: Times in the follow up menu are automatically given! Time Switch Program Fr 17:00 to Sa 6:30 Time setting and Logic:, Profiles 1 to 6 Note: Times in the follow up menu are automatically given! Time Switch Program Sa 06:30 to Su 19:11 Time setting and Logic:, Profiles 1 to 6 Note: Times in the follow up menu are automatically given! Time Switch Program Sa 09:00 to Sa 16:00 Time setting and Logic:, Profiles 1 to 6 Note: Times in the follow up menu are automatically given! Time Switch Program Sa 19:11 to Su 06:22 Time setting and Logic:, Profiles 1 to 6 Note: Times in the follow up menu are automatically given! Time Switch Program Su 06:22 to Su 21:15 Time setting and Logic:, Profiles 1 to 6 Note: Times in the follow up menu are automatically given! Time Switch Program Su 21:15 to Mo 06:00 Time setting and Logic:, Profiles 1 to 6 Note: Times in the follow up menu are automatically given! Back to Back to Page 13

14 5.7 Selecting profiles In the menu "Select profile" the individual compressor data are entered in the selected profile. Up to 6 different profiles can be programmed. Under "Select profile" "Operating mode", 3 different settings are possible. Primary load (the compressor is not considered when rotating), Load changeover (the compressor is considered when rotating) and OFF (no compressors connected). Finally, the cut-in and cut-out pressures of the individual compressors are programmed. All special settings are described below in detail as follows: Standby-time (Waiting time) In case the relevant compressor has not reached the programmed cut-out threshold after the standby-time (0 to 999 minutes) has elapsed, the next compressor in line is automatically staged. When selecting "0", this function is deactivated Load changeover time The load changeover time determines the actual rotation time period between the connected compressors! The changeover time is the time in which compressor 1 is triggered, i.e. the load changeover does not take place after e.g. 24 hours have elapsed but only when the relevant compressor has been triggered for the length of the programmed time. After the load changeover time has elapsed, the primary load changes then to the next compressor. A load change over time of 0 to 999 hours can be programmed. If under General Settings "Load changeover switch immediately" has been set to On, the load changeover is carried out immediately. If has been selected, then the load changeover is carried out when reaching the highest cut-in threshold. Please note that the load changeover time is the time during which the compressor is triggered! Monitoring time The monitoring time is initiated once the applied system pressure sinks below the set alarm pressure or rises above the highest cut-out threshold. If after the monitoring time has elapsed and the system pressure is still below the set alarm level (or above the highest cut-out threshold), then the alarm output is activated. Page 14

15 5.7.4 Menu: up to max. Profile 6 Back to Compressor 1 Operatingmode :Primary load Setting, compressor 1: Load change over or Primary load or Compressor 2 Operatingmode : Load changeover Setting, compressor 2: Load change over or Primary load or Compressor 3 Operatingmode : Setting, compressor 3: Load change over or Primary load or Compressor 4 Operatingmode : Setting, compressor 4: Load change over or Primary load or, Cut - in pressure 1:08,00bar 2:07, 80bar 3:07,60bar 4:xx,xxbar Profil 1: Cut - in pressure of compressor 1 to 4, Cut - out pressure 1:10,00bar 2:09, 80bar 3:09,60bar 4:xx,xxbar Profil 1: Cut - out pressure of compressor 1 to 4 Stand - by time Load changeover time 60min 24. 0h : Stand - by time 0 bis 999 minutes : Load changeover time 0 bis 999,9 hours Monitoring time: 999 sec : Monitoring time 0 to 999 seconds Back to Back to Page 15

16 6 Time delay start Due to existing safety standards, all programmed compressors are switched on after a delay time of 10 s when operating the control (system pressure: 0 bar). This setting cannot be switched off. 7 State of delivery When delivered, the time switch, external pressure sensor and ball valve functions are not activated. Bitte bedenken Sie die manuell erforderliche Umstellungen von Sommer- auf Winterzeit und umgekehrt. 8 Kurzanleitung GLW 4, für die Anwendung 230V-AC Folgende Schritte sind für einen ersten Betrieb mindestens zu erledigen und zu beachten: 1.) GLW 4: A1 und I51 an 230V-AC anschließen! 2.) GLW 4: A2 und I52/62 an N anschließen! 3.) Druckluft anschließen! 4.) Profil 1 programmieren, mit Passwort 0190 (Auslieferzustand)! 5.) Die Lastwechselzeit ist die reine Lastzeit, der Kompressoren! 6.) Die Eingänge I 11 bis I 41 sind nur für die Funktionen Betriebsstundenanzeige usw. verwendbar. Die Kompressoren werden über den jeweiligen potentialfreien Wechselkontakt (GLW 4: Klemmen 11/12/14, z. B. für Kompressor 1 und Klemmen 21/22/24 für Kompressor 2) angesteuert. Bei Fragen und technischen Problemen wenden Sie sich bitte an: Condor Pressure Control GmbH Warendorfer Straße Phone: +49 (0) D Ennigerloh Telefax: +49 (0) info@condor-cpc.com 9 Terminal connections GLW 4 Terminals Function A1 Mains voltage connection 230 V AC A2 Connection N conductor I11 Compressor 1 I12 Reference input I 11 (N conductor) I21 Compressor 2 I22 Reference input I 21 (N conductor) I31 Compressor 3 I32 Reference input I 31 (N conductor) I41 Compressor 4 I42 Reference input I 41 (N conductor) I51 Voltage connection alarm relays I52 / I62 Reference input I 51 / I 61 (N conductor) I61 Bridge time switch 11 / 12 / 14 Voltage free output compressor 1 21 / 22 / 24 Voltage free output compressor 2 31 / 32 / 34 Voltage free output compressor 3 41 / 42 / 44 Voltage free output compressor 4 51 / 52 / 54 Voltage free alarm output P+ /p- Externanl pressure transducer connecton (two wire) 10 PC interface The GLW 4 control features a V24 interface which allows programming of settings and more with a PC. The interface features a protective cap. This function is not yet active with the software version V1.00. Page 16

17 11 Technical data The GLW 4 is a compressor control unit featuring an integrated relative pressure transducer (0-16 bar, quick connect ) for DIN-rail mounting, 6 optocoupler inputs, 5 voltage free SPDT's, an analog input (two wire, ma) for external pressure measurement, a graphic LCD display, 3 key operation and a V24 interface (at the moment without function). Programming is carried out with the use of three keys and the help of the LCD-Display. Internal pressure sensor (Relative pressure transducer) Pneumatic tube cross-section 6mm, suitable tube: FESTO PAN 6X1 Cu-in and cu-out pressure in bar/psi 1 to 16 bar ( psi) Max. permissible pressure 25 bar (363 psi) Error (at 25 C) typically +/-0.2 bar +/- 1 digit Operational data Power supply (A1/A2) 90 to 265 V-AC, 50/60 Hz Duty factor 100% Permissible ambient and media temperature 0 C up to + 50 C Permissible ambient air humidity 10%-90% relative humidity, non condensing Permissible storage temperature -40 C up to + 80 C Air and creepage distances according to DIN VDE Mounting position optional Power consumption max. 10 VA Housing data Dimensions Material Mounting Degree of protection, housing IP 40 Shock protection according to VBG 4 Number of Terminals x 90 x 59 mm PC GF, light gray Snap-On DIN-rail mounting, 35 mm, according to EN Connection unloseable clamp screws, Philips Max. connecting cross-section 2 x 2,5 mm 2 2x 1,5 mm 2 wire DIN /-2/-3/-4 Max. current (Relay contact) max. 250 V-AC / 5A AC1 max. 30 V-DC / 2A Digital Inputs Analog input for external pressure sensor optocoupler, 250V-AC1 / 30V-DC U B 18 up to 21 V-DC, two-wire, ma 12 Conformity The staging and sequencing control type GLW 4 corresponds to the following directives/standards: EMI/Directive Low Voltage Direction 2004 / 108 / EG EN (2007) EN (2007) EN (2010) 2006 / 9S / EG EN (2007) We want you to use only state of the art products, therefore we reserve the right to make any necessary technical changes without prior warning. Page 17

18 13 Connecting diagram GLW Input compressor 1 Input compressor 2 Input compressor 3 Warning! When connecting the GLW 4, the Technical Data under Chapter 10 are to be observed Input compressor 4 Input: Remote release Input: Bridge time switch Output compressor 1 Output compressor 2 Output compressor 3 Output compressor 4 Output Alarm relay Connection: External pressure transducer Qucik connect Page 18

19 14 Connecting diagram GLW 4-S Compressor 1 Compressor 2 Compressor 3 Compressor 4 Output alarm relay Output extern Pressure transducer Page 19

20 15 Connecting diagram GLW 4-SK OPERATING Compressor 4 Compressor 3 Compressor 2 Compressor 1 Main Input Compressor 4 Input Compressor 3 Input Compressor 2 Input Compressor 1 Bridging time switch Voltage connection alarm relays Connecting extern Pressure transducer Series terminals X2 Output Alarm relay Compressor 4 Compressor 3 Compressor 2 Compressor 1 Compressor 4 Compressor 3 Compressor 2 Compressor 1 GLW 4 Series terminals X1 Page 20 Bridging time switch ON / OFF

21 16 Programming example, page 1 Operating Hours s. Pos 13 Pressure measurement Internal Unit: bar Unit: psi Language: German/English/ Italian Password change **** **** Back to Operating mode profile Time switch Programming example, functions: - Timeswitch Mo.-Fr. and a. - Bridge time switch, then Profile 6 i.e. the compressors are operating according to the time switch settings and as soon as voltage is applied to input I61, the compressors will continue to operate without the time switch settings! All menus can be viewed. To change a parameter, entering a password is required. If after 90 sec. no values are entered, the GLW 4 returns to the Main. Menu and the validity of the password is void. Function ext. input P6 Date/Time: Mo :44:32 Alarm press bar Alarm time: 999 sec Alarm relay: Logic Inputs Operating/Errors... 1NO 2NO 3NO 4NO Pressing the <OK> key in the Main Menu deactivates the Buzzer and the Alarm relay. Error! shown in the Main Display Alternating with main display in case of error Note: End time and start time of the following time perios are always the same. The starting time is automatically given. Ball valve/output K4 On Load changeover switch immediately Buzzer Interface Back to Page 21

22 16.1 Programming example, page 2 s. Pos 13 Time Switch Prog. Select Profile Select Profile Profile 6 s. Pos 13 Time Switch Prog. Mo-Fr Day 06:00-17:00 Compressor 1 Operating Mode: Primary load Profile 6 Compressor 1 Operating Mode: Primary load Time Switch Prog. Mo-Fr Night 17:00-06:00 Compressor 2 Operating Mode: Load changeover Profile 6 Compressor 2 Operating mode: Load changeover Time Switch Prog. Fr 17:00 to Sa 6:30 Compressor 3 Operating mode: Load changeover Profile 6 Compressor 3 Operating mode: Load changeover Time Switch Prog. Sa 06:30 to Su 19:11 Compressor 4 Operating mode: Profile 6 Compressor 4 Operating mode: Time Switch Prog. Sa 09:00 to Sa 16:00 Cut-in pressure 1:08,00bar 2:07,80bar 3:07,60bar 4:XX,XXbar Profile 6 Cut-in pressure 1:08,00bar 2:07,80bar 3:07,60bar 4:XX,XXbar Time Switch Prog. Sa 19:11 to Su 06:22 Cut-out pressure 1:10,00bar 2:09,80bar 3:09,60bar 4:XX,XXbar Profile 6 Cut-out pressure 1:10,00bar 2:09,80bar 3:09,60bar 4:XX,XXbar Time Switch Prog. Su 06:22 to Su 21:15 Stand-by time 60min. Profile 6 Stand-by time 60min. Time Switch Prog. Su 21:15 to Mo 06:00 Load changeover time 24.0h Profile 6 Load changeover 24.0h Back to Monitoring time 999sec. Profile 6 Monitoring time 999sec. Copying Profile P1 -> Pn <CR> Profile 6 Copying Profile P6 -> Pn <CR> Back to Back to Page 22

23 Condor Pressure Control GmbH Warendorfer Straße D Ennigerloh Phone: +49 (0) / 89-0 Telefax: +49 (0) / info@condor-cpc.com http: Page 23

24 Page 24

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

Operating instructions Electrical switching facility pco

Operating instructions Electrical switching facility pco Operating instructions Electrical switching facility pco from software version V1.33 on TABLE OF CONTENTS 1. Before you start... 4 1.1 Brief description... 4 1.2 Using this manual... 4 2. pco integrated

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The LDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

WF STEUERUNGSTECHNIK GMBH. INFORMATION and TECNICAL DESCRIPTION

WF STEUERUNGSTECHNIK GMBH. INFORMATION and TECNICAL DESCRIPTION 1 INFORMATION and TECNICAL DESCRIPTION 14 2 AIRLEADER Professional Compressor Management + Compressed Air Visualisation + Alarm Service Management + AIRLEADER - has been the effective answer for compressed

More information

Touch Screen Guide. OG-1500 and OG Part # T011

Touch Screen Guide. OG-1500 and OG Part # T011 Touch Screen Guide OG-1500 and OG-2000 Part # 9000000.T011 Effective 11/2010 External View Internal View 1. Transducer Banks 2. Oxygen Sensor 3. PLC These are the two manifolds with three (3) transducers

More information

CONSOLE-320 ENGLISH. 230A: CONSOLE-320 with cable data output Item 230B: CONSOLE-320 with cable + wireless radio data output

CONSOLE-320 ENGLISH. 230A: CONSOLE-320 with cable data output Item 230B: CONSOLE-320 with cable + wireless radio data output CONSOLE-320 Item 230A: CONSOLE-320 with cable data output Item 230B: CONSOLE-320 with cable + wireless radio data output Table of contents 1. INTRODUCTION...2 1.1 Power supply...2 1.2 Connections...2 1.3

More information

Pneumatic high-pressure controller Model CPC7000

Pneumatic high-pressure controller Model CPC7000 Calibration technology Pneumatic high-pressure controller Model CPC7000 WIKA data sheet CT 27.63 Applications Automotive and avionics industry Industry (laboratory, workshop and production) Transmitter

More information

Pneumatic high-pressure controller Model CPC7000

Pneumatic high-pressure controller Model CPC7000 Calibration technology Pneumatic high-pressure controller Model CPC7000 WIKA data sheet CT 27.63 Applications Healthcare and avionics industry Industry (laboratory, workshop and production) Transmitter

More information

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES I N S T R U C T I O N - M A N U A L CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES FUNCTION: Conductivity level limit switches are based on the principle of measuring level through the electrical

More information

Solenoid gas valve. The solenoid gas valve is also applicable as a main gas valve Pilot gas valve for forced draft burners

Solenoid gas valve. The solenoid gas valve is also applicable as a main gas valve Pilot gas valve for forced draft burners 7 634 VGS1... with AGA67 connector VGS2... with AGA67 connector Solenoid gas valve VGS The solenoid gas valve is also applicable as a main gas valve Pilot gas valve for forced draft burners The VGS and

More information

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073 Operating instructions Safety Rope Emergency Stop Switches UK ZB0052 / ZB0053 ZB0072 / ZB0073 7390878 / 02 03 / 2011 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4

More information

JOLLY2. Installation user s manual. 6 different operating modes selectable. version 3.3. DATA TO BE FILLED OUT BY THE INSTALLER (Page 1)

JOLLY2. Installation user s manual. 6 different operating modes selectable. version 3.3. DATA TO BE FILLED OUT BY THE INSTALLER (Page 1) ENGLISH ENGLISH ENGLISH ENGLISH Installation user s manual Warning! electrical scheme modified JANUARY 2005 version 3.3 JOLLY2 DATA TO BE FILLED OUT BY THE INSTALLER (Page 1) 6 different operating modes

More information

SonoMeter 30 Energy Meters

SonoMeter 30 Energy Meters Data Sheet SonoMeter 30 Energy Meters Description The Danfoss SonoMeter 30 is a range of ultrasonic, compact energy meters intended for measuring energy consumption in heating and cooling applications

More information

Tightness controls TC 1 3 and TC 4

Tightness controls TC 1 3 and TC 4 Tightness controls TC 1 3 and TC 4 Test of both safety valves Short test period thanks to logical decision-making in the program sequence Adjustable test period which can be adapted to different systems

More information

Manual Oxygen Analyzer A4009T

Manual Oxygen Analyzer A4009T Manual Oxygen Analyzer A4009T Revision 01-EN DIVIZE B.V.- info@divize.com November 25, 2014 Contents 1 Measuring principle 3 2 Safety 4 3 Installation 5 3.1 Mounting................................................

More information

COMPRESSOR PACK SUCTION CONTROLLER TYPE: LP41x

COMPRESSOR PACK SUCTION CONTROLLER TYPE: LP41x Electrical Installation Requirements Care should be taken to separate the power and signal cables to prevent electrical interference and possible damage due to inadvertent connection. SUPPLY E L N LN2

More information

SSR. Smart Valve Positioner.

SSR. Smart Valve Positioner. Smart Valve Positioner Smartest valve control device meeting a dynamic performance and a precise setting with a piezoelectric technology and an optimized auto-calibration program Features Auto-Calibration

More information

MP15 Jockey Pump Controller

MP15 Jockey Pump Controller Setup and Operating Instructions MP15 Jockey Pump Controller This manual provides general information, installation, operation, maintenance, and system setup information for Metron Model MP15 Jockey Pump

More information

Level control technology

Level control technology Level control technology Level control Industries Level measurement methods P. 103 PSN ENP ENR Float switches which turns On and Off depending on the cable length Electronic pump control Single and dual

More information

ECL Comfort 110, application 131 (valid as of software version 2.00)

ECL Comfort 110, application 131 (valid as of software version 2.00) Operating Guide ECL Comfort 110, application 131 (valid as of software version 2.00) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

Pressure switch Type BCP

Pressure switch Type BCP Data sheet Pressure switch Type BCP The BCP type is a series of dedicated switches for safety and monitoring of steam and hot water boilers. The BCP incorporates a single-pole changeover microswitch where

More information

SSL. Smart Valve Positioner.

SSL. Smart Valve Positioner. Smart Valve Positioner Smartest valve control device meeting a dynamic performance and a precise setting with a piezoelectric technology and an optimized auto-calibration program Features Auto-Calibration

More information

Contents. Operating instructions. Pressure switch, heavy-duty version Model PSM-520

Contents. Operating instructions. Pressure switch, heavy-duty version Model PSM-520 Operating instructions Contents EN Pressure switch, heavy-duty version Model PSM-520 1. General information 2. Design and function 3. Safety 4. Transport, packaging and storage 5. Commissioning, operation

More information

FTC130 Transmitter. Operating Manual

FTC130 Transmitter. Operating Manual Seite 1 von 11 FTC130 Transmitter Fast Thermal Conductivity Analyzer Operating Manual 1.09KD180724CWI1V05 Messkonzept GmbH Seite 2 von 11 1. Intended Use... 3 2. Description... 4 3. Measuring gases and

More information

HyperSecureLink V6.0x User Guide

HyperSecureLink V6.0x User Guide HyperSecureLink V6.0x User Guide Note: This software works with the LS-30 Version (06.0x or later) 1, Hardware Installation: 1-1, Connection Diagram for USB or RS-232 Computer Interface To LS-30 CM1 To

More information

EPP4 Pressure Regulator Basic G 1/4"

EPP4 Pressure Regulator Basic G 1/4 EPP4 Pressure Regulator Basic G 1/4" Flow Curve 1/4" Dimensions Outlet pressure - bar 9 8 7 6 5 4 3 2 1 0 0 20 40 60 70 80 100 120 Flow rate - Nm 3 /h The male connector adopted on the EPP4 is a standard

More information

Installation and Operation Manual

Installation and Operation Manual Manual Static pressure transducer with controller Differential static pressure transducer with analog output and optional PI control mode Large diaphragm element with differential transformer Transducer

More information

Installation & Maintenance Instructions TEC-11N TIMER. Analogue electronic timer 02/09

Installation & Maintenance Instructions TEC-11N TIMER. Analogue electronic timer 02/09 Installation & Maintenance Instructions TEC-11N TIMER Analogue electronic timer 02/09 GENERAL OPERATION The TEC-11N timer is produced using SMT (Surface Mounting Technology), ensuring improved performance

More information

BAROMETER PRESSURE STANDARD PRESSURE CONTROLLER

BAROMETER PRESSURE STANDARD PRESSURE CONTROLLER BAROMETER PRESSURE STANDARD PRESSURE CONTROLLER Features ±0.01% FS Measurement & Control Accuracy ±0.001% /ºC Thermal Stability Pressure Ranges from ±1 psid to 1200 psia Applications Barometric Measurement

More information

Hand-held pressure calibrator with integrated pump Model CPH6600

Hand-held pressure calibrator with integrated pump Model CPH6600 Calibration technology Hand-held pressure calibrator with integrated pump Model CPH6600 WIKA data sheet CT 16.01 Applications Calibration service companies and service industry Measurement and control

More information

Safety Manual VEGAVIB series 60

Safety Manual VEGAVIB series 60 Safety Manual VEGAVIB series 60 NAMUR Document ID: 32005 Contents Contents 1 Functional safety... 3 1.1 General information... 3 1.2 Planning... 4 1.3 Adjustment instructions... 6 1.4 Setup... 6 1.5 Reaction

More information

Intelligent SUNTEX DC-5310(RS) Dissolved Oxygen Transmitter

Intelligent SUNTEX DC-5310(RS) Dissolved Oxygen Transmitter Intelligent SUNTEX DC-5310(RS) Dissolved Oxygen Transmitter Overview C % ppm 4~20mA Analog Output ppb Power Supply 100~240 VAC mg/l Dimensions 96 x 96 x 132mm RS-485 Digital Output (for DC-5310-RS only)

More information

KERN EG/EW Version /02

KERN EG/EW Version /02 E KERN EG/EW Version 1.5 07/02 Operating Instructions Electronic Precision Balances Contents 1 TECHNICAL DATA... 20 2 UNPACKING AND STANDARD ACCESSORIES... 23 3 SETTING UP THE BALANCE... 23 4 EXTERNAL

More information

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars.

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars. Simply a question of better measurement SCHMIDT Flow Sensor SS 20.261 The cost-effective alternative in pressurised systems up to 10 bars. Compressed air technology Industrial processes A cost analysis

More information

Safety Manual. Process pressure transmitter IPT-1* 4 20 ma/hart. Process pressure transmitter IPT-1*

Safety Manual. Process pressure transmitter IPT-1* 4 20 ma/hart. Process pressure transmitter IPT-1* Safety Manual Process pressure transmitter IPT-1* 4 20 ma/hart Process pressure transmitter IPT-1* Contents Contents 1 Functional safety 1.1 General information... 3 1.2 Planning... 4 1.3 Instrument parameter

More information

A TECHNICAL REFERENCE

A TECHNICAL REFERENCE A TECHNICAL REFERENCE FOR CAREL DCM CONTROLLERS DIGITAL COMPRESSOR MODULE CANADIAN HEAD OFFICE AND FACTORY USA HEAD OFFICE AND FACTORY CANADIAN EASTERN FACTORY 1401 HASTINGS CRES. SE CALGARY, ALBERTA T2G

More information

Valve Proving System VDK 200 A S06*

Valve Proving System VDK 200 A S06* Valve Proving System VDK 200 A S06* Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter

More information

Controller for boilers Galan - regulator for management of heating elements and circuit SolarSentinel-DBTW User guide

Controller for boilers Galan - regulator for management of heating elements and circuit SolarSentinel-DBTW User guide Controller for boilers Galan - regulator for management of heating elements and circuit SolarSentinel-DBTW User guide SHORT DESCRIPTION: 1. Device is applicable to: Burners, Electric boiler, Electric heaters,

More information

* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22.

* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22. *09005087* DB_BA_EN_ME01_S Rev.A 12/16 *09005087* d e v e l o p i n g s o l u t i o n s Data Sheet and Operating Manual ME01 Digital manometer Table of Contents ME01 ## # 87 # HL S#### Dust explosion protection

More information

MEGAS 2.0. Gas analysis with direct C-Level Calculation and Bus-Connection. Data sheet

MEGAS 2.0. Gas analysis with direct C-Level Calculation and Bus-Connection. Data sheet Data sheet MEGAS 2.0 Gas analysis with direct C-Level Calculation and Bus-Connection Mesa Industrie-Elektronik GmbH Neckarstraße 19, D-45768 Marl info@mesa-gmbh.de +49 (0) 2365-97 45 1-0 +49 (0) 2365-97

More information

SAPCON. User Manual. Capacitance Continuous Level Indicator. . Introduction. . General Description. . Principle of Operation. .

SAPCON. User Manual. Capacitance Continuous Level Indicator. . Introduction. . General Description. . Principle of Operation. . User Manual Capacitance Continuous Level Indicator Comprehensive User s Manual. Introduction. General Description. Principle of Operation. Specifications. Connection Diagrams. Quick Calibration Chart.

More information

LTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc.

LTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc. LTB013EN Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc. to IECEx scheme Subject to technical modification Bachofen AG Ackerstrasse 42

More information

QPL... Pressure Switches. Siemens Building Technologies HVAC Products

QPL... Pressure Switches. Siemens Building Technologies HVAC Products 7 221 Pressure Switches QPL... The pressure switches are used for monitoring gas or air pressures. When the pressure falls below the switching point, the associated electrical circuit will open or switch

More information

ACV-10 Automatic Control Valve

ACV-10 Automatic Control Valve ACV-10 Automatic Control Valve Installation, Operation & Maintenance General: The Archer Instruments ACV-10 is a precision automatic feed rate control valve for use in vacuum systems feeding Chlorine,

More information

Operating instructions. FOCUS compressor control for screw compressors

Operating instructions. FOCUS compressor control for screw compressors Operating instructions compressor control for screw compressors Table of contents Operating instructions compressor control for screw compressors BOGE KOMPRESSOREN Postfach 10 07 13 D-33507 Bielefeld Germany

More information

OPERATOR s MANUAL AHCON PCI 3000

OPERATOR s MANUAL AHCON PCI 3000 OPERATOR s MANUAL AHCON PCI 3000 1 INDEX Page Manufacturer s Information 3 Warnings 4 Risks and Labelling 5 Safety Precautions 5 Warranty 6 Dimensions and Weight 7 Shipping Dimensions 7 Connection 8 Operation

More information

Control units. Installation and operating instructions Series: DP-Control

Control units. Installation and operating instructions Series: DP-Control Control units Installation and operating instructions Series: DP-Control Table of Contents 1 Manual introduction 1.1 Preface... 4 1.2 Icons and symbols... 4 2 Identification, service and technical support

More information

Operating Instructions Part No

Operating Instructions Part No DIGITAL AUTOMATIC TYRE INFLATOR Operating Instructions Part No. 11.0545 Thank you for selecting this Jamec Pem Automatic Tyre Inflator. Please read this manual before carrying out any installation or service

More information

Tightness control TC. Product brochure GB 3 Edition AGA

Tightness control TC. Product brochure GB 3 Edition AGA Tightness control TC Product brochure GB 3 Edition 07.14 AGA Test of two safety valves Short test period thanks to logical decision-making in the program sequence Adjustable test period which can be adapted

More information

Proportional pressure regulators VPPE

Proportional pressure regulators VPPE Proportional pressure regulators VPPE Proportional pressure regulators VPPE Product range overview Function Version Pneumatic connection Proportional pressure regulator Nominal size for pressurisation/

More information

Operating instructions. FOCUS compressor control for piston compressors

Operating instructions. FOCUS compressor control for piston compressors Operating instructions FOCUS compressor control for piston compressors Operating instructions FOCUS compressor control for piston compressors BOGE KOMPRESSOREN Postfach 10 07 13 33507 Bielefeld Otto-Boge-Straße

More information

Valve Proving System VDK 200 A S02

Valve Proving System VDK 200 A S02 Valve Proving System VDK 200 A S02 Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter

More information

A4s Operation Manual

A4s Operation Manual A4s Operation Manual Safety Instruction Please read this manual carefully, also with related manual for the machinery before use the controller. For installing and operating the controller properly and

More information

Measuring range Δp (span = 100%) Pa

Measuring range Δp (span = 100%) Pa 4.4/ RLE 5: Volume-flow controller, continuous How energy efficiency is improved Enables demand-led volume flow control for the optimisation of energy consumption in ventilation systems. Areas of application

More information

Application of CHE100 in Frequency Conversion Alteration of Air Compressor System

Application of CHE100 in Frequency Conversion Alteration of Air Compressor System Application of CHE100 in Frequency Conversion Alteration of Air Compressor System Abstract: This paper describes application of CHE100 in frequency conversion alteration of the air compressor system and

More information

Flamco Flexcon M-P Pump automat

Flamco Flexcon M-P Pump automat Flexcon M-P Pump automat 0664 Flex MP-eps GB Installation and operating instructions 1999, Flamco 2 Installation and operating instructions Flexcon M-P pump automat Dear customer, GB With the purchase

More information

Certified according to DIN EN ISO 9001 Technical Datasheet TRICOR Series Mass Flow Meters

Certified according to DIN EN ISO 9001 Technical Datasheet TRICOR Series Mass Flow Meters www.kem-kueppers.com info@kem-kueppers.com Certified according to DIN EN ISO 9001 Technical Datasheet TRICOR Series Mass Flow Meters Description The Tricor Mass Flow Meters measure simultaneously mass

More information

Guidelines to the standard IEC60601

Guidelines to the standard IEC60601 EUROPEAN POWER SUPPLY MANUFACTURERS ASSOCIATION (Visit the EPSMA website at www.epsma.org) Medical Approvals for Power Supplies Guidelines to the standard IEC60601 Revision Date: 2009-09-12 This document

More information

Datasheet: K-30 ASCII Sensor

Datasheet: K-30 ASCII Sensor Datasheet: K-30 ASCII Sensor The K30 ASCII sensor is a low cost, infrared and maintenance free transmitter module intended to be built into different host devices that require CO2 monitoring data. The

More information

Vortex Flow Sensor VA Di Ex-d for flow measurement in gases; with integrated, configurable transducer UVA in Ex-d housing

Vortex Flow Sensor VA Di Ex-d for flow measurement in gases; with integrated, configurable transducer UVA in Ex-d housing Vortex Flow Sensor VA Di Ex-d Vortex Flow Sensor VA Di Ex-d for flow measurement in gases; with integrated, configurable transducer UVA in Ex-d housing Drawing 1 Measurable variables actual flow rate actual

More information

A4 Operation Manual. Fig.1-1 Controller Socket Diagram

A4 Operation Manual. Fig.1-1 Controller Socket Diagram A4 Operation Manual Safety Instruction Please read this manual carefully, also with related manual for the machinery before use the controller. For installing and operating the controller properly and

More information

REASONS FOR THE DEVELOPMENT

REASONS FOR THE DEVELOPMENT 7 Series 7 Series +24VDC VDC OUTPUT MICROPROCESS. E P IN EXH OUT 7 Series 7 ø,8 8 7 Series 9 5 8 9 7 Series Display features The proportional regulator has a 3 /2 digit display and a three-pushbutton

More information

Built-in Purge Control Functions

Built-in Purge Control Functions Built-in Purge Control Functions Why clean a sensor? As the velocity sensor was calibrated clean, operating it clean also preserves the best calibration. Any build up of material on a thermal sensor tends

More information

Helium Level Measurement Unit

Helium Level Measurement Unit Helium Level Measurement Unit HLMU User Manual Version 002 The information in this manual may be altered without notice. BRUKER BIOSPIN accepts no responsibility for actions taken as a result of use of

More information

Pneumatic spool valve islands

Pneumatic spool valve islands Pneumatic spool valve islands P7.GB.R MEGA SPOOL VALVE ISLANDS MEGA pneumatic spool valve islands offer maximum performance along with flexibility, easy installation and simple operation. Due to their

More information

Data Sheet T 8389 EN. Series 3730 and 3731 Types , , , and. EXPERTplus Valve Diagnostic

Data Sheet T 8389 EN. Series 3730 and 3731 Types , , , and. EXPERTplus Valve Diagnostic Data Sheet T 8389 EN Series 3730 and 3731 Types 3730-2, 3730-3, 3730-4, 3730-5 and Type 3731-3 Electropneumatic Positioners EXPERTplus Valve Diagnostic Application Positioner firmware to detect potential

More information

Precision digital pressure gauge Model CPG1000

Precision digital pressure gauge Model CPG1000 Calibration technology Precision digital pressure gauge Model CPG1000 WIKA data sheet CT 10.01 Applications Oil and gas industry Maintenance and service facilities Calibration service companies and service

More information

Electrical operating instructions

Electrical operating instructions en Electrical operating instructions Door control panel TS 980 (Design and functions subject to change) 51171150 - b 07.2007 OPERATING AND INSTALLATION INSTRUCTIONS PAGE SAFETY DIRECTIONS...4 ENCLOSURE

More information

AUTOMATIC TIRE INFLATOR # MW-60, MW-60-4WAY & MW-64HP

AUTOMATIC TIRE INFLATOR # MW-60, MW-60-4WAY & MW-64HP USER MANUEL AUTOMATIC TIRE INFLATOR # MW-60, MW-60-4WAY & MW-64HP TIRE EQUIPMENT MANUFACTURER 1.866.409.RACK WWW.MARTINSINDUSTRIES.COM info@martinsindustries.com PARTS Verify that the following components

More information

Autocalibration Systems For In Situ Oxygen Analyzers

Autocalibration Systems For In Situ Oxygen Analyzers Product Data Sheet PDS 106-340AC SPS 4000, IMPS 4000, and MPS 3000 January, 1999 Autocalibration Systems For In Situ Oxygen Analyzers Cost-effective autocalibration systems for installations ranging from

More information

GAS FUEL VALVE FORM AGV5 OM 8-03

GAS FUEL VALVE FORM AGV5 OM 8-03 ALTRONIC AGV5 OPERATING MANUAL GAS FUEL VALVE FORM AGV5 OM 8-03 WARNING: DEVIATION FROM THESE INSTALLATION INSTRUCTIONS MAY LEAD TO IMPROPER ENGINE OPERATION WHICH COULD CAUSE PERSONAL INJURY TO OPERATORS

More information

Standard Chiller 1/4 compressors Manual version: /10/96

Standard Chiller 1/4 compressors Manual version: /10/96 Application program for Macroplus II Standard Chiller 1/4 compressors Manual version: 1.4-18/10/96 Program code: EP000ECH02 Rif.: 68EM Contents 0$,1)($785(6 HARDWARE...2 FUNCTIONS OF THE SYSTEM...3 PROTECTIONS...3

More information

CONTROL LOGIC DESCRIPTION DOCUMENT IC-410ND

CONTROL LOGIC DESCRIPTION DOCUMENT IC-410ND Configuration # : 41G20F0 CONTROL LOGIC DESCRIPTION DOCUMENT IC-410ND Input/output table: Inputs Qty Outputs Qty Inside Temperature Probe 3 Inflatable Balloon 8 Chimney Temperature Probe 1 Chimney Activator

More information

MAESTRO USER S MANUAL TIP00G-105 AIR COMPRESSORS

MAESTRO USER S MANUAL TIP00G-105 AIR COMPRESSORS AIR COMPRESSORS MAESTRO USER S MANUAL TIP00G-105 ING. ENEA MATTEI SpA Strada Padana Superiore 307 20090 VIMODORONE (MI) Tel +39 02253051 (16 lines) Fax +39 0225305243 E-mail: info@mattei.it - www.matteiaircompressors.com

More information

Technical Data Sheet MF010-O-LC

Technical Data Sheet MF010-O-LC Technical Data Sheet MF010-O-LC - 1 - 1. Properties The oxygen measuring system MF010-O-LC determines the oxygen content in gas mixtures up to a temperature of 250 C. It is particularly suitable for the

More information

Burner Management System DEMO Operating instructions

Burner Management System DEMO Operating instructions Burner Management System DEMO Operating instructions Burner Management System DEMO Operating Instructions Startup Summary - Normal startup is accomplished in four basic steps: 1. Leak Test a. Safety Valve

More information

JUMO dtrans O2 01 Two-wire Transmitter for dissolved oxygen (DO)

JUMO dtrans O2 01 Two-wire Transmitter for dissolved oxygen (DO) Data Sheet 202610 Page 1/12 JUMO dtrans O2 01 Two-wire Transmitter for dissolved oxygen (DO) with optional terminal box or operating unit Type 202610 Two-wire transmitter JUMO dtrans O2 01 Brief description

More information

D62 - D63 Directional Control Valve l/min

D62 - D63 Directional Control Valve l/min D62 - D63 Table of Contents 1 1.1 1.2 Product Description... 2 Function... 2 Properties... 2 2 Technical Data... 3 3 3.1 3.2 Ordering Information... 4 Type code... 4 Versions currently available... 4 4

More information

Electronic gas volume corrector model DGVC-04

Electronic gas volume corrector model DGVC-04 Electronic gas volume corrector model DGVC-04 1. Introduction The following user s manual gives information about the installation, configuration, usage and storage of the electronic gas volume corrector

More information

CCT-7320/ROC-2313 Reverse Osmosis Controller

CCT-7320/ROC-2313 Reverse Osmosis Controller CCT-7320/ROC-2313 Reverse Osmosis Controller 1 General The instrument is a combined control instrument of a reverse osmosis controller and an on-line conductivity instrument. It can perform the operation

More information

Flow and check valves Logic valves series 551. Brochure

Flow and check valves Logic valves series 551. Brochure Flow and check valves Logic valves series 551 Brochure 2 Flow and check valves Logic valves series 551 3/2-directional valve, low pressure operated Qn = 2-120 l/min 3 3/2-directional valve, Qn = 120 l/min

More information

Roller AC Servo System

Roller AC Servo System Safely Instruction Roller AC Servo System HMI-15 User Manual Please read this manual carefully, also with related manual for the machinery before use the controller. For installing and operating the controller

More information

MACON R70 FOR 1 OR 2 COMPRESSORS

MACON R70 FOR 1 OR 2 COMPRESSORS MACON R70 FOR 1 OR 2 COMPRESSORS GENERAL CHARACTERISTICS Application to chiller and heat pumps. INPUTS 5 Analogical inputs for temperature measuring in range - 50 +99 C. 3 for the first circuit Nο1. Water

More information

RS D RSF D with direct drive

RS D RSF D with direct drive Screw compressors RS 2-75 109 D RSF 87 127 D with direct drive Made in Germany Motor power: 75 127 kw RENNER GmbH Kompressoren success rooted in tradition. RENNER GmbH Kompressoren have been known for

More information

Control Units for Oil+Air Lubrication

Control Units for Oil+Air Lubrication Control Units for Oil+Air Lubrication 1-1700-3-US Universal Control Unit The control units described in this leaflet are used for timeor pulse-dependent control of oil+air systems. The overview shows the

More information

Design Envelope Booster. Sequence of operation

Design Envelope Booster. Sequence of operation Design Envelope Booster Sequence of operation File No: 62.835 Date: february 11, 2015 Supersedes: 62.835 Date: july 11, 2014 sequence of operation Design Envelope Booster 2 general The packaged domestic

More information

DPS-400 SERIES DPH-100 SERIES

DPS-400 SERIES DPH-100 SERIES 745 Dual Display Digital Pressure Sensor For Gas DPS-400 SERIES SERIES General terms and conditions... F- guide... P.699~ Related Information Glossary of terms... P.156~ General precautions... P.1566 PHOTO

More information

RS 2-75 D 109 D RSF 87 D 127 D with direct drive

RS 2-75 D 109 D RSF 87 D 127 D with direct drive Screw compressors RS 2-75 D 109 D RSF 87 D 127 D with direct drive Made in Germany Motor size: 75 127 kw RENNER GmbH Kompressoren Success Rooted in Tradition. RENNER GmbH Kompressoren have been known for

More information

AHE58/59 AC Servo System

AHE58/59 AC Servo System AHE58/59 AC Servo System HMI-12 User Manual Safely INstruction Please read this manual carefully, also with related manual for the machine head before use. For perfect operation and safety, installing

More information

Automatic Valve Proving Control

Automatic Valve Proving Control ISO 9001 Automatic Valve Proving Control 7 696 LDU11 UL recognized FM approved Features Performs leak test of the gas shut-off valves before start-up and/or immediately after burner shut-down No inlet

More information

Instruction Manual AD 1000 / BA 1000 Absolute Pressure Sensor

Instruction Manual AD 1000 / BA 1000 Absolute Pressure Sensor Instruction Manual AD 1000 / BA 1000 Absolute Pressure Sensor halstrup-walcher GmbH Stegener Straße 10 D-79199 Kirchzarten Phone: +49 (0) 76 61/39 63 0 Fax: +49 (0) 76 61/39 63 99 E-Mail: info@halstrup-walcher.com

More information

Autocalibration Systems for In Situ Oxygen Analyzers

Autocalibration Systems for In Situ Oxygen Analyzers Product Data Sheet PDS 106-340AC.A01 February, 2006 SPS 4001B, IMPS 4000 and MPS 3000 Autocalibration Systems for In Situ Oxygen Analyzers Cost-effective autocalibration systems for installations ranging

More information

SPECIFICATIONS ATTENTION

SPECIFICATIONS ATTENTION VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane

More information

Instruction Manual Differential Pressure Transmitter

Instruction Manual Differential Pressure Transmitter DE61 Instruction Manual Differential Pressure Transmitter Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance

More information

Ultima. X Series Gas Monitor

Ultima. X Series Gas Monitor Ultima X Series Gas Monitor Safety Manual SIL 2 Certified " The Ultima X Series Gas Monitor is qualified as an SIL 2 device under IEC 61508 and must be installed, used, and maintained in accordance with

More information

OC Panel High Limit Aquastat Kit, Manual Reset p/n

OC Panel High Limit Aquastat Kit, Manual Reset p/n OC Panel High Limit Aquastat Kit, Manual Reset p/n 233202 Instruction Sheet APPLICATION The OC (Option Control) Panel High Limit Aquastat Kit provides electronic temperature sensing in a UL limit-rated

More information

Proportional Pressure-Relief Cartridge Valve, Size 2...4

Proportional Pressure-Relief Cartridge Valve, Size 2...4 Proportional Pressure-Relief Cartridge Valve, Size... Q max = l/min (6 gpm), p max = bar (58 psi) Direct acting, electrically operated Description proportional pressure-relief valves are direct acting

More information

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies We reserve the right to make technical changes without notice. Technische Änderungen vorbehalten. Sous réserve de modifications techniques.

More information

Mass Flow Controller (MFC) for Gases

Mass Flow Controller (MFC) for Gases Mass Flow Controller (MFC) for Gases Type 8713 can be combined with... Direct flow measurement by MEMS- Technology for nominal flow rates from 1 ml N /min to 8 l N /min (N 2 ) High accuracy and repeatability

More information

Safety Manual VEGAVIB series 60

Safety Manual VEGAVIB series 60 Safety Manual VEGAVIB series 60 Contactless electronic switch Document ID: 32002 Contents Contents 1 Functional safety... 3 1.1 General information... 3 1.2 Planning... 4 1.3 Adjustment instructions...

More information