Pressure transmitter. SITRANS P500 with HART. Operating Instructions 09/2010 SITRANS

Size: px
Start display at page:

Download "Pressure transmitter. SITRANS P500 with HART. Operating Instructions 09/2010 SITRANS"

Transcription

1 Pressure transmitter Operating Instructions 09/2010 SITRANS

2

3 Introduction 1 General safety notes 2 SITRANS Pressure transmitter Operating Instructions Description 3 Install 4 Connecting 5 Operate 6 Commissioning 7 Alarm, error and system messages 8 Service and maintenance 9 Technical data 10 Dimension drawings 11 A Appendix B List of abbreviations 7MF5**3 09/2010 A5E

4 Legal information Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken. CAUTION without a safety alert symbol, indicates that property damage can result if proper precautions are not taken. NOTICE indicates that an unintended result or situation can occur if the corresponding information is not taken into account. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation for the specific task, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be adhered to. The information in the relevant documentation must be observed. Trademarks All names identified by are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Industry Sector Postfach NÜRNBERG GERMANY order number: A5E P 03/2011 Copyright Siemens AG Technical data subject to change

5 Table of contents 1 Introduction Purpose of this documentation History Notes on warranty Product information Conformity with European directives General safety notes General information Correct usage Laws and directives Checking the consignment Transportation and storage Measures Qualified Personnel Description System configuration Application range Structure Structure of the nameplate and approval plate Functional principle Operation of the electronics Measuring cell operation Measuring cell for differential pressure and flow rate Measuring cell for level Remote seals SIMATIC PDM Install Safety notes for installation Instructions for installation Sealing connecting elements Installation (except level) Instructions for installation (except level) Assembly...31 Operating Instructions, 09/2010, A5E

6 Table of contents 4.5 "Level" installation Instructions for level installation Installation for level Connection of the negative pressure line Measurement in an open container Measurement in a closed container Measurement on closed vessels with heavy condensation "Remote seal" installation Remote seal installation Installation of the remote seal with the capillary line Rotating the measuring cell over the enclosure Rotating display Connecting Safety notes for connection Connecting the device Connecting the Han plug Connecting the M12 connector Operate Operation overview Display in measurement view Display in the navigation view Display in the parameter view Parameter description Overview of the menu structure "1 Quickstart" "1.1 Commissioning" "2 Setup" "2.1 Input" "2.2 Output" "2.3 Simulation" "2.4 Service" "2.5 Display" "2.6 Mechanical Construction" "3 Diagnostics" "3.1 Alarm list" "3.2 Identification" "3.3 Process Variables" "3.4 Hardware Exchanges" "3.5 Diagnostic Setup" "3.6 Operatinghours Counter" "3.7 MinMaxPointer" "3.8 Limiter" "3.9 Statistics" "3.10 Logbook" "4 Communication" "4.1 Protocol" " HART-Variable4" Operating Instructions, 09/2010, A5E

7 Table of contents "4.3 Analog Output" "4.21 HART Writeprotect" "4.22 Burst Mode" "5 Security" "5.1 " in preparation "5.2 Keypad Lock" "5.3 Access Management" "5.4 Auto Log Out" "6 Language" Description of the operating functions Operating functions through HART communication Selection of the measuring modes Overview of measuring modes Measuring mode "Pressure" Measuring mode "Level" Measuring mode "Volume" Measuring mode "Mass" "Volume flow" measurement type "Mass flow" measurement type "User" measurement type Setting zero point and limit point Flow characteristic Correction of the flow characteristic Setting the current limits Simulation Overview of simulation Simulation as fixed value Simulation with a ramp function Zero point calibration (position correction) sensor calibration Sensor calibration Trimming the sensor Current sensor trim Diagnostic functions Calibration timer and service timer Min/max indicator Limit monitor Process tag data Commissioning Safety notes for commissioning Instructions on commissioning Differential pressure and flow rate Safety notes for commissioning with differential pressure and flow rate Commissioning in gaseous environments Commissioning for liquids Commissioning with vapor Operating Instructions, 09/2010, A5E

8 Table of contents 8 Alarm, error and system messages Overview of messages and symbols Messages Service and maintenance Safety notice for maintenance Notes for servicing Notes for servicing of the remote seal Modular structure Return procedure Technical data Overview of technical data Input point Output Measuring accuracy Operating conditions Construction Display, keyboard and auxiliary power Certificates and approvals HART communication Dimension drawings SITRANS P500 for differential pressure, flow rate and absolute pressure from the differential pressure series SITRANS P500 for level A Appendix A.1 Certificate A.2 Literature and catalogs A.3 Overview A.4 Technical support B List of abbreviations Glossary Index Operating Instructions, 09/2010, A5E

9 Introduction Purpose of this documentation These instructions contain all information that you will require to commission and use the device. Read these instructions carefully prior to installation and commissioning. In order to use the device correctly, first make yourself acquainted with its principle of operation. The instructions are aimed both at persons mechanically installing the device, connecting it electronically, configuring the parameters and commissioning it as well as service and maintenance engineers. 1.2 History This history establishes the correlation between the current documentation and the valid firmware of the device. The documentation of this edition is applicable for the following firmware: Edition Firmware and hardware identity nameplate System integration Installation path for PDM Unpublished versions of the operating instructions 05 09/2010 1) to SP05 FW: HW: PDM 6.0 1) ; Dev. Rev.3 DD; Dev. Rev.1 SitransP500 Note 1.3 Notes on warranty The contents of this manual shall not become part of or modify any prior or existing agreement, commitment or legal relationship. The sales contract contains all obligations on the part of Siemens AG as well as the complete and solely applicable warranty conditions. Any statements regarding device versions described in the manual do not create new warranties or modify the existing warranty. The content reflects the technical status at the time of publishing. Siemens reserves the right to make technical changes in the course of further development. Operating Instructions, 09/2010, A5E

10 Introduction 1.4 Product information 1.4 Product information The programming manual is an integral part of the CD, which is either supplied or can be ordered. The programming manual is also available on the Siemens homepage. On the CD, you will also find the specification sheet with the ordering data, the Software Device Install for SIMATIC PDM for additional installation, and the required software. See also Product information on SITRANS P in the Internet ( Catalog process instrumentation ( 1.5 Conformity with European directives The CE mark on the device shows conformity with the provisions of the following European Directives: EMC 2004/108/EC ATEX 94/9/EC DGRL 97/23/EC Directive of the European Parliament and of the Council on the approximation of the laws of the Member States relating to electromagnetic compatibility and repealing Directive 89/336/EEC. Directive of the European Parliament and the Council on the approximation of the laws of the Member States concerning equipment and protective systems intended for use in potentially explosive atmospheres. Directive of the European Parliament and of the Council on the approximation of the laws of the Member States concerning pressure equipment. The standards applied and their associated versions can be found in the enclosed EC Declaration of Conformity. 8 Operating Instructions, 09/2010, A5E

11 General safety notes General information This device left the factory free from safety problems. In order to maintain this status and to ensure safe operation of the device, please observe the safety information and warnings contained in these instructions. Safety information and symbols must be observed without exception. They must not be removed and must be maintained in legible condition at all times. 2.2 Correct usage The device may only be used for the purposes specified in these instructions. Insofar as they are not expressly stated in these instructions, all changes to the device are the sole responsibility of the user. 2.3 Laws and directives Disregard of provisions and laws during connection and installation increases the risk of explosions and leaks dues to improper application. To avoid these risks during connection and installation, you should comply with the test certifications, provisions and laws applicable in your country. For hazardous areas, these are for example: IEC (international) National Electrical Code (NEC - NFPA 70) (USA) Canadian Electrical Code (CEC) (Canada) EN (previously VDE 0165, part 1) (EU) Working reliability regulation (Germany) Operating Instructions, 09/2010, A5E

12 General safety notes 2.4 Checking the consignment 2.4 Checking the consignment 1. Check the packaging and the device for visible damage caused by inappropriate handling during shipping. 2. Report any claims for damages immediately to the shipping company. 3. Retain the damaged parts for clarification. 4. Check the scope of delivery by comparing the shipping documents with your order for correctness and completeness. WARNING Using a damaged or incomplete device Danger of explosion. Do not start up any damaged or incomplete devices. See also Technical data (Page 175) Return procedure (Page 174) 2.5 Transportation and storage To guarantee sufficient protection during transport and storage, observe the following: Keep the original packaging for subsequent transportation. Devices/replacement parts should be returned in their original packaging. If the original packaging is no longer available, please ensure that all shipments are properly packaged to provide sufficient protection during transport. Siemens cannot assume liability for any costs associated with transportation damages. CAUTION Insufficient protection during storage The packaging only provides limited protection against moisture and infiltration. Provide additional packaging as necessary. Special conditions for storage of the device are listed in section "Technical data (Page 175)". 10 Operating Instructions, 09/2010, A5E

13 General safety notes 2.6 Measures 2.6 Measures For the sake of safety, the following precautions must be observed: WARNING "Flameproof enclosure" type of protection Only open devices with type of protection "Flameproof enclosure" in hazardous areas when the power to the device is turned off, otherwise there is a risk of explosion. WARNING "Intrinsic safety" protection type Only connect the device to certified intrinsically safe circuits. These circuits must comply with the technical data indicated on the nameplate or in the certificates and approvals. If the circuits do not comply with the information in the certificates and approvals, the safety required for the approval is longer guaranteed. The "ia" protection level of the device is decreased to the "ib" protection level when intrinsically safe circuits having the "ib" protection level are connected. WARNING Type of protection "limited energy" nl (zone 2) Devices with "limited energy" type of protection may be connected and disconnected while in operation. Type of protection "non-sparking" na (zone 2) Devices with "non-sparking" protection may only be connected and disconnected when off circuit. WARNING Exposure to aggressive and hazardous process media The device can be operated both at high pressure and with aggressive and hazardous process media. Therefore, improper use of this device may lead to serious injury and or considerable damage to property. Above all, it must be noted when the device was in use and is to be exchanged. WARNING Explosion hazard through electrostatic charging To prevent electrostatic charges building up in a hazardous environment, the key cover must be closed during operation and the screws must be tightened. Temporary opening of the key cover for purposes of operating the transmitter may be performed at any time, even during operation; after which the screws should be tightened again. Operating Instructions, 09/2010, A5E

14 General safety notes 2.7 Qualified Personnel CAUTION Electrostatic Sensitive Devices (ESD) This device contains electrostatic sensitive devices. Electrostatic sensitive devices may be destroyed by voltages that are undetectable to a human. Voltages of this kind occur as soon as a component or an assembly is touched by a person who is not grounded against static electricity. The damage to a module as a result of overvoltage cannot usually be detected immediately. It may only become apparent after a long period of operation. Protective measures against discharge of static electricity: Make sure that no power is applied. Before you work with modules, first discharge any static charges from your body, for example by touching a grounded object. Devices and tools used must be free of static charge. Hold modules only by their edges. Do not touch connector pins or conductor tracks on a module with the ESD notice. 2.7 Qualified Personnel Qualified personnel are people who are familiar with the installation, mounting, commissioning, and operation of the product. These people have the following qualifications: They are authorized, trained or instructed in operating and maintaining devices and systems according to the safety regulations for electrical circuits, high pressures and aggressive as well as hazardous media. For explosion-proof devices: They are authorized, trained, or instructed in carrying out work on electrical circuits for hazardous systems. They are trained or instructed in maintenance and use of appropriate safety equipment according to the safety regulations. 12 Operating Instructions, 09/2010, A5E

15 Description System configuration Overview The pressure transmitter can be used in a number of system configurations: as a stand-alone version, supplied with the necessary auxiliary power as part of a complex system environment, e.g. SIMATIC S7 System communication Communication is via the HART protocol, using: HART Communicator (load Ω) PC with HART modem, on which appropriate software is installed, e.g. SIMATIC PDM (load Ω) Control system which can communicate via the HART protocol, e.g. SIMATIC PCS7 Figure 3-1 Possible system configurations Operating Instructions, 09/2010, A5E

16 Description 3.2 Application range 3.2 Application range Overview Depending on the variant, the pressure transmitter measures corrosive, non-corrosive and hazardous gases, vapors and liquids. With appropriate parameterization, you can also use the differential pressure transmitter for the following measurement types: Level Volume Mass Volume flow Mass flow The output signal is always a load-independent direct current between 4 and 20 ma upon which a HART protocol is superimposed. You can install the "Intrinsically safe" or "Flameproof enclosure" version of the transmitter in hazardous areas. The devices have an EC type-examination certificate and meet the regulations applicable to them, for example, the harmonized CENELEC standards in Europe. Transmitters with remote seals of different shapes can be delivered for special applications. For example, measuring high-viscosity substances is a special application. Differential pressure and flow rate This version measures corrosive, non-corrosive and hazardous gases, vapors and liquids. You can use this version for the following measurement types: Differential pressure Positive or negative relative pressure In combination with a restrictor device: flow rate q ~ p The smallest differential pressure span is 1.25 mbar (0.5 inh2o); the largest differential pressure span is 1250 mbar (502 inh2o). Level This version with mounting flange measures the level of non-corrosive, corrosive and hazardous liquids in open and closed containers. The smallest measuring span is 1.25 mbar (0.5 inh2o); the largest span is 1250 mbar (502 inh2o). The nominal diameter of the mounting flange is DN 80 or DN 100 or 3" or 4". The negative connection of the measuring cell is kept open when measuring the level of open containers. This measurement is referred to as "measurement against atmosphere". The negative connection is normally connected with the container when measuring the level of closed containers. This balances the static pressure. Wetted parts are made of various materials, depending on corrosion resistance requirements. 14 Operating Instructions, 09/2010, A5E

17 Description 3.3 Structure 3.3 Structure Depending on a customer-specific order, the device comprises different parts. 1 Approval plate 8 Measuring cell with process flanges 2 Safety latch 9 Cable inlet, optional with cable gland 3 Blanking plug 10 Electrical terminal compartment 4 Keys cover 11 Cover (rear) for electrical terminal compartment 5 Cover (front), optionally with an inspection window 12 Protective conductor connection 6 Display (optional) 13 Nameplate 7 Measuring point label 14 Retaining screws (both sides), twist proofing of the measuring cell in relation to the electronics enclosure Figure 3-2 Device view of the transmitter The electronic enclosure is made of aluminum die casting. The enclosure has a removable circular cover at the front and the back. Depending on the device version, the cover 5 is provided with an inspection window. Through the inspection window, the measured values can be read from the display (optional) 6. The user must not use the service connector located behind the display 6. The service plug is for the exclusive use of the manufacturer. The cable inlet 9 to the electrical terminal compartment on the left or right side can be used selectively. The corresponding unused opening is closed with a blanking plug 3. The protective conductor terminal 12 is located on the rear of the housing. The electrical terminal compartment 10 for power supply and shield is accessible when you unscrew the cover 11. Operating Instructions, 09/2010, A5E

18 Description 3.4 Structure of the nameplate and approval plate Underneath the electronics housing is the measuring cell with its pressure caps on which the process connections 8 are located. The modular structure of the pressure transmitter allows you to replace the measuring cell, application electronics, connection board, pushbutton module, and the optional display when required. On the upper face of the enclosure you can see crosshead screws which secure the cover 4, under which the 3 keys for local operation are located. 3.4 Structure of the nameplate and approval plate Nameplate structure The nameplate with the order number and other important data, such as the design details and technical data can be found on the side of the enclosure. SITRANS P500 Transmitter for differential pressure 7MF5603-1DA00-0AD1-Z +E00 F.-Nr. B1-F PED/SEP V H: DC V (non IS) 4-20 ma HART Mat.: Connec. Diaphr. O-ring Filling FKM (FPM) Silicone oil Measuring span : mbar Rated pressure : PN 160 Schutzart IP 65 SIEMENS AG twistlock screw D Karlsruhe made in France 0045 HW: / FW: Order number 2 Serial number 3 Firmware (FW) and hardware (HW) numbers Example of a nameplate 16 Operating Instructions, 09/2010, A5E

19 Description 3.4 Structure of the nameplate and approval plate Structure of the approval plate The approval plate is located on the side opposite the nameplate. For the Ex-version of the transmitter, the information on the respective certificate is also listed. SITRANS P500 II 1/2 G Ex d ia IIC T4/T6 T a : C ( F) Temperature class T4 T a : C ( F) Temperature class T6 U=45V BVS09ATEXE027 Observe EC-Type Examination Certificate! SIEMENS AG D Karlsruhe twistlock screw Figure 3-3 Example of an approval plate 1 1a 1b 1c 1d Characteristics of the hazardous area Category of the operating range Type of protection Group (gas, dust) Maximum surface temperature (temperature class) Operating Instructions, 09/2010, A5E

20 Description 3.5 Functional principle 3.5 Functional principle Operation of the electronics Description 1 Measuring cell sensors 7 HART modem 2 Measuring amplifier 8 Buttons (local operation) 3 Analog-to-digital converter 9 Display 4 Microcontroller 5 Digital-to-analog converter IA Output current 6 Each with an EEPROM in the measuring UH Auxiliary power cell and in the electronics Figure 3-4 Operation of electronics with HART communication, simplified illustration Function The input pressure is converted into an electrical signal by the sensor 1. This signal is amplified by the measuring amplifier 2 and converted in an analog-todigital converter Operating Instructions, 09/2010, A5E

21 Description 3.5 Functional principle The digital signal is analyzed in a microcontroller 4 and corrected with regard to linearity and thermal characteristics. It is then converted in a digital-to-analog converter 5 to the output current of 4 to 20 ma. A diode circuit provides reverse polarity protection. The measuring cell specific data, electronics data and parameterization data are saved in two EEPROM 6. One EEPROM is located in the measuring cell, the other is incorporated in the electronics. Operation Use the keys 8 to navigate and set different parameters. If your device has a display 9, you can perform the parameter settings locally and track messages from the device visually. Other settings can be implemented with a computer using a HART modem Measuring cell operation CAUTION Toxic and hot media leaks If the measured signal fails because of sensor breakage, the seal diaphragm and the overload system may also be destroyed. In the worst case scenario of devices with a destroyed seal diaphragm, the process medium leaks on the side ventilated with reference pressure. In case of sensor breakage, deactivate the lines to the device or depressurize the lines. In the following sections, the process variable to be measured is called general inlet pressure. Overview The following principles of operation are described: Differential pressure and flow rate Level The following process connections are available, for example: ¼ - 18 NPT Flanged connection In accordance with EN Operating Instructions, 09/2010, A5E

22 Description 3.5 Functional principle Measuring cell for differential pressure and flow rate 1 Silicon pressure sensor 6 Overload diaphragm 2 Inlet pressure P+ 7 Filling liquid 3 Process flange with process connection 8 Seal diaphragm 4 O-ring 9 Inlet pressure P- 5 Measuring cell body Figure 3-5 Function diagram of the measuring cell for differential pressure and flow rate The differential pressure is transmitted via the seal diaphragm 8 and the fill fluid 7 to the silicon pressure sensor 1. If the measuring limits are exceeded, the seal diaphragm 8 is displaced so far that it lies against the bodies of the measuring cell 5. This protects the silicon pressure sensor 1 against overload. Differential pressure causes the measuring diaphragm of the silicon pressure sensor to be displaced. The displacement changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the differential pressure. 20 Operating Instructions, 09/2010, A5E

23 Description 3.5 Functional principle Measuring cell for level 1 Process flange with process connection 6 Filling liquid of the measuring cell 2 O-ring 7 Seal diaphragm in the measuring cell 3 Silicon pressure sensor 8 Capillary tube with the fill fluid of the mounting flange 4 Measuring cell bodies 9 Flange with a tube 5 Overload diaphragm 10 Seal diaphragm on the mounting flange Figure 3-6 Function diagram of the measuring cell for level The input pressure (hydrostatic pressure) acts hydraulically on the seal diaphragm at the mounting flange 10 on the measuring cell. The differential pressure existing at the measuring cell is transmitted via the fill fluid 6 to the silicon pressure sensor 3. If the measuring limits are exceeded, the seal diaphragm on the measuring cell 7 is displaced so far that it lies against the bodies of the measuring cells 4. This protects the silicon pressure sensor 3 against overload. Differential pressure causes the measuring diaphragm of the silicon pressure sensor to be displaced. The displacement changes the resistance value of the four doped piezo resistors arranged in a bridge circuit in the measurement diaphragm. The change in resistance causes the bridge output voltage to vary in proportion to the differential pressure. Operating Instructions, 09/2010, A5E

24 Description 3.5 Functional principle Remote seals Product description A remote seal measuring system comprises the following elements: Remote seal Transmission line, e.g. capillary line Measuring device NOTICE Malfunction of the remote seal measuring system If you separate the components of the remote seal measuring system, this results in malfunctioning of the system. Do not separate the components under any circumstances. The measuring system based on a hydraulic principle is used to transfer pressure. The capillary line and the remote seal diaphragm are the most sensitive components in the remote seal measuring system. The material thickness of the remote seal diaphragm is only 0.1 mm. The smallest of leakages in the transmission system leads to the loss of transmission fluid. The loss of transmission fluid results in inaccuracies in the measurement and failure of the measuring system. In order to avoid leaks and measuring errors, please observe the installation and maintenance instructions in addition to the safety notes. 22 Operating Instructions, 09/2010, A5E

25 Description 3.6 SIMATIC PDM 3.6 SIMATIC PDM SIMATIC PDM is a software package for configuring, parameter assignment, commissioning, diagnostics and maintenance of this device and other process devices. SIMATIC PDM offers simple monitoring of process values, alarms, and device status information of the transmitter. SIMATIC PDM allows the process device data to be: displayed set modified saved diagnosed checked for plausibility managed simulated Operating Instructions, 09/2010, A5E

26 Description 3.6 SIMATIC PDM 24 Operating Instructions, 09/2010, A5E

27 Install Safety notes for installation You can install the transmitter in different areas of application. Depending on the area of application and the system configuration, there may be differences in the installation. For all devices WARNING Destruction of device If external loads act on the device, it could be destroyed. In the worst case, process medium could escape. It is therefore essential to prevent external loads from acting on the device. WARNING Protection against incorrect use of the measuring instrument Make sure that the selected materials for the wetted parts of the measuring instrument are suitable for the process media used in order to ensure both the safety of the personnel and the device. Use the device only within the measuring spans for pressure, overload pressure limits and voltage limits specified on the nameplate. Otherwise, hot and toxic media may leak and lead to personal injury. CAUTION Risk of burns Install additional touch protection for surface temperatures > 70 C. The touch protection must be designed in such a way that the maximum permissible ambient temperature at the device is not exceeded. The permissible ambient temperatures for the device can be found in the technical data or on the nameplate. Operating Instructions, 09/2010, A5E

28 Install 4.1 Safety notes for installation CAUTION Risk of injury Install the device such that automatic emptying is ensured and the entire process medium is drained. Otherwise, the residual process media may cause damage. For example, do not install the device at the bottom of the tank, install it on its side, instead. CAUTION Improper installation or modification can damage the device and thus invalidate the approval. Do not modify the device. In particular, use the cable entries, which are certified for the corresponding approval, for the cable connection. NOTICE The electrical terminal compartment may only be opened for installation, to make electrical connections, or for maintenance. NOTICE If the device is partially or completely open, the degree of protection specified in the technical data is no longer guaranteed. Mount the device as specified. The properties associated with the degree of protection are not guaranteed unless the device is properly mounted. General explosion protection WARNING Use You may only use this device in combustible and/or hazardous areas if it is marked for this use. Special explosion protection WARNING Flame penetration distances Following device installation, all flame penetration distances must have a clearance of at least 30 mm from stationary parts that are not part of the device. Otherwise, the safety of the flameproof device is not guaranteed. 26 Operating Instructions, 09/2010, A5E

29 Install 4.1 Safety notes for installation WARNING For operation in Zone 0 The transmitter corresponds to category 1/2 and may be installed in Zone 0. The EC-type examination certificate applies to installation of the device in the walls of containers and pipelines in which explosive gas/air or vapor/air mixtures occur only under atmospheric conditions; for pressure: 0.8 to 1.1 bar (11.6 to 19.9 psi); temperature: -20 to +60 C (-4 to +140 F) The permissible ambient temperature range for the transmitter is: see nameplate or technical data. The operator may use the device under non-atmospheric conditions outside the limits specified in the EC-type examination certificate (or the certification applicable in the country of use) at the operator's own risk if safety measures which may be necessary in accordance with use conditions (explosive mixture) have been taken. Make sure to comply with the limit values specified in the general technical data in all cases. The installation must be sufficiently tight (IP67 according to EN 60529). For instance, an industry standard (e.g. DIN, NPT) threaded connector is suitable for the IP67 degree of protection. Operating Instructions, 09/2010, A5E

30 Install 4.2 Instructions for installation 4.2 Instructions for installation Note Protect the transmitter against: Direct thermal radiation Rapid temperature fluctuations Heavy contamination Mechanical damage The installation location should satisfy the following criteria: easily accessible as close as possible to the measurement location free from vibration within the permitted ambient temperature values Note Perform position error correction After installation of the transmitter, perform a position error correction, so as to compensate for any work offset arising from the installation location. See "1.1.4 Trim Mounting Offset" (Page 59) Note Work offset The work offset arising from the installation position can be found in the technical data. See Measuring accuracy (Page 178). 28 Operating Instructions, 09/2010, A5E

31 Install 4.3 Sealing connecting elements 4.3 Sealing connecting elements Siemens optionally delivers a metric thread M20 x 1.5 or a conical thread 1/2-14 NPT for the cable gland or the blanking plug. The metric threads are sealed using O-rings as standard. If you are using flat gaskets for a M20 x 1.5 thread, improper mounting can result in sealing problems. Instructions for the sealing methods: Thread sealant For metric and tapered threads To seal the thread, use suitable liquid sealant, e.g. Loctite. Completely remove all the sealant residue when resealing the threads following disassembly. Check the thread for possible damage and replace the damaged parts. During installation, make sure that the cable gland or the blanking plug is completed screwed in. Teflon tape For tapered thread only Make sure that you do not wrap the Teflon tape around threads more than two to three times. We recommend using tape with a thickness of 0.1 mm. If you use thicker tape, you must reduce the number of wraps. Count the threads in the engagement length. Make sure that when you screw in the cable gland with Teflon tape that the total number of threads has not been reduced by more than one thread. Flat gasket For metric thread only Make sure that the flat gasket has a maximum thickness of a thread lead. For example, the flat gasket for a M20 x 1.5 thread has a maximum thickness of 1.5 mm (0.06"). Count the threads in the engagement length. Make sure that when you screw in the cable gland with the flat gasket that the total number of threads has not been reduced by more than one thread. Operating Instructions, 09/2010, A5E

32 Install 4.4 Installation (except level) 4.4 Installation (except level) Instructions for installation (except level) Conditions NOTICE Compare the desired operating data with the data on the nameplate. Note Protect the transmitter against: Direct heat radiation Rapid temperature fluctuations Heavy contamination Mechanical damage The installation location is to be as follows: Easily accessible As close as possible to the measuring point Vibration-free Within the permitted ambient temperature values Installation configuration The transmitter may in principle be configured above or below the pressure tapping point. The recommended configuration depends on the aggregate state of the medium. Installation configuration for gases Install the transmitter above the pressure tapping point. Lay the pressure tubing with a constant gradient to the pressure tapping point, so that any condensation produced can drain in the main line and thereby avoid corruption of the measured values. Installation configuration for vapor and liquid Install the transmitter below the pressure tapping point. Lay the pressure tubing with a constant gradient to the pressure tapping point so that any gas pockets can escape in the main line. 30 Operating Instructions, 09/2010, A5E

33 Install 4.4 Installation (except level) Assembly Fastening without the mounting bracket You can fasten the transmitter directly on both pressure caps. Fastening with the mounting bracket You can use a tube clamp to fasten the mounting bracket to a horizontal or vertical mounting tube of diameter 50 mm (2 "). Alternatively you can attach the mounting bracket to the wall. Fasten the transmitter mounting bracket using the four screws provided. Figure 4-1 Fastening the transmitter on the mounting bracket with horizontal differential pressure lines Figure 4-2 Fastening the transmitter on the mounting bracket with vertical differential pressure lines Operating Instructions, 09/2010, A5E

34 Install 4.5 "Level" installation 4.5 "Level" installation Instructions for level installation Conditions NOTICE Compare the desired operating data with the data on the nameplate. Note Protect the transmitter against: Direct heat radiation Rapid temperature fluctuations Heavy contamination Mechanical damage Note Select the height of the mounting flange such that the pressure transmitter is always mounted below the lowest fill height to be measured. The installation location is to be as follows: Easily accessible The measuring point must be as close as possible Vibration-free Within the permitted ambient temperature values Installation for level Note Seals are required for the installation. The seals must be compatible with the medium to be measured. Seals are not included in the delivery. 32 Operating Instructions, 09/2010, A5E

35 Install 4.5 "Level" installation Procedure To install the transmitter for level, proceed as follows: 1. Attach the seal to the container's mating flange. Ensure that the seal is centrically positioned and that it does not restrict the movement of the flange's seal diaphragm in any way as otherwise the tightness of the process connection is not guaranteed. 2. Screw on the transmitter's flange. 3. Observe the installation position Connection of the negative pressure line Measurement in an open container Connection of the negative line is not necessary when measuring in an open container, since the negative side is connected to the atmosphere. Formula: Start of scale value pma = ρ g hu Full scale value pme = ρ g ho + hu Start of scale value ΔpMA Start of scale value to be adjusted ho Full scale value ΔpME Full scale value to be adjusted p Pressure ρ Density of the measured medium in the container g Acceleration due to gravity Measurement assembly on an open container Operating Instructions, 09/2010, A5E

36 Install 4.5 "Level" installation Measurement in a closed container When taking measurements in a closed container without or with little condensation formation, the negative pressure line is not filled. Formula: Start of scale value ΔpMA = ρ g hu Full scale value ΔpME = ρ g ho hu Start of scale value ΔpMA Start of scale value to be adjusted ho Full scale value ΔpME Full scale value to be adjusted p Pressure ρ Density of the measured medium in the container g Acceleration due to gravity Measurement assembly on a closed container: no or little condensation separation When taking measurements in a closed container with strong condensation formation, you must fill the negative pressure line (mostly with the condensation of the measured medium) and install a condensation pot. For measurement on open vessels there is no need to connect the minus pipework, since the minus side is open to the atmosphere. 34 Operating Instructions, 09/2010, A5E

37 Install 4.5 "Level" installation Measurement on closed vessels with heavy condensation When taking measurements in a closed container with strong condensation formation, you must fill the negative pressure line (mostly with the condensation of the measured medium) and install a condensation pot. You can shut off the device e.g. using a two-way valve block 7MF9411-5AA. Formula: Start of scale value ΔpMA = g (hu ρ - hv ρ') Full scale value ΔpME = g (ho ρ - hv ρ') ' - hu Start of scale value ΔpMA Start of scale value to be set ho Full scale value ΔpME Full scale value to be set hv Gland distance ρ Density of the medium in the vessel p Pressure ρ ' Density of fluid in the negative pressure line, corresponds to the temperature prevailing there. g Acceleration due to gravity Measurement assembly on a closed container: strong condensation formation The process connection on the negative side is a female thread 1 /4-18 NPT. Lay the line for the negative pressure using a seamless steel tube 12 mm x 1.5 mm. Operating Instructions, 09/2010, A5E

38 Install 4.6 "Remote seal" installation 4.6 "Remote seal" installation Remote seal installation General installation instructions Keep the measuring system in the factory packing until it is installed in order to protect it from mechanical damage. When removing from the factory packing and installing: ensure that damage to and mechanical deformations in the membrane are prevented. Never loosen the sealed filling screws on the remote seal and the measuring instrument. Do not cause damage to the remote separating membrane; scratches on the remote separating membrane, e.g. due to sharp-edged objects, are the main starting points for corrosion. Select suitable gaskets for sealing. Use a gasket having an adequately large inner diameter for flanging. Insert the gasket concentrically; contact with the membrane leads to deviations in measurements. When using gaskets made of soft materials or PTFE: follow the guidelines of the gasket manufacturer, especially regarding the tightening torque and setting cycles. At the time of installation, use suitable fastening components such as screws and nuts that are compliant with fitting and flange standards. Excessive tightening of screwed joints on the process connection may displace the zero point on the pressure transmitter. Note Commissioning If a shut-off valve exists, open the shut-off valve slowly when commissioning in order to avoid pressure surges. Note Permissible ambient and operating temperatures Install the pressure measuring device such that the permissible limits of ambient and measured medium temperatures are not overshot or undershot even with the consideration of the effect of convection and heat radiation. Note the effect of temperature on the measuring accuracy. When selecting the remote seals, ensure that fittings and flange components have adequate pressure-temperature resistance by selecting suitable materials and pressure ratings. The pressure rating specified on the remote seal applies to reference conditions according to IEC For the maximum permissible pressure at higher temperatures, please refer to the standard specified on the remote seal. 36 Operating Instructions, 09/2010, A5E

39 Install 4.6 "Remote seal" installation Using remote seals with pressure measuring device for hazardous areas: When using remote seals with pressure measuring device for hazardous areas, the permissible limits of ambient temperatures for the transmitter must not be exceeded. Hot surfaces on the cooling section (capillaries or cooling elements) are a possible source of ignition. Initiate suitable measures. When remote seals with a flame arrestor are used, the pressure measuring instrument determines the permissible ambient temperature. In the case of potentially explosive gaseous atmosphere, the temperature around the flame arrestor must not exceed +60 C Installation of the remote seal with the capillary line Notes Do not rest the measurement assembly on the capillary line. Do not bend capillary lines; risk of leakages and/or risk of considerable increase in the response time of the measuring system. Owing to the risk of bending and breakages, pay attention to mechanical overloads at the joints such as capillary line-remote seal and capillary line-measuring instrument. Unwinding the excess capillary lines with a radius of at least 150 mm. Fasten the capillary line such that there are no vibrations. Permissible height differences: When installing the pressure measuring instrument above the measuring point, keep the following in mind: in the case of remote seal measuring systems with silicone, glycerin or paraffin oil filling, the maximum height difference of H1max = 7 m must not be exceeded. If halocarbon oil is used as a fill fluid, this maximum height difference is H1max = 4 m, see installation type G. If negative overpressure is observed during measurements, reduce the permissible height difference accordingly. Operating Instructions, 09/2010, A5E

40 Install 4.6 "Remote seal" installation Installation type for differential pressure and flow rate measurements Installation type D Start of scale value: pma = pstart - ρoil * g * HV Full scale value: pme = pend - ρoil * g * HV Legend pma pme pstart pend ρoil g HV Start of scale value to be adjusted Full scale value to be adjusted Start of scale value Full scale value Density of the filling oil in the capillary line of the remote seal Local gravitational acceleration Gland distance Installation types for level measurements (closed containers) Installation type E Start of scale value: pma = ρfl * g * HU - ρoil * g * HV Full scale value: pme = ρfl * g * HU - ρoil * g * HV 38 Operating Instructions, 09/2010, A5E

41 Install 4.6 "Remote seal" installation Legend pma pme ρfl ρoil g HU HO HV Start of scale value to be adjusted Full scale value to be adjusted Density of the measured medium in the container Density of the filling oil in the capillary line of the remote seal Local gravitational acceleration Start of scale value Full scale value Gland distance Installation type G H1 7 m (23 ft), for halocarbon oil, however only H1 4 m(13.1 ft) Start of scale value: pma = ρfl * g * HU - ρoil * g * HV Full scale value: pme = ρfl * g * HO - ρoil * g * HV Pressure transmitter for differential pressure above the upper measuring point, no vacuum Installation type H Start of scale value: pma = ρfl * g * HU - ρoil * g * HV Full scale value: pme = ρfl * g * HO - ρoil * g * HV Below the lower measuring point Operating Instructions, 09/2010, A5E

42 Install 4.6 "Remote seal" installation Installation type J H2 7 m (23 ft), for halocarbon oil, however only H1 4 m(13.1 ft) Start of scale value: pma = ρfl * g * HU - ρoil * g * HV Full scale value: pme = ρfl * g * HO - ρoil * g * HV Between the measuring points, no vacuum Legend pma Start of scale value to be adjusted pme Full scale value to be adjusted ρfl Density of the measured medium in the container ρoil Density of the filling oil in the capillary line of the remote seal g Local gravitational acceleration HU Start of scale value HO Full scale value HV Gland distance 40 Operating Instructions, 09/2010, A5E

43 Install 4.7 Rotating the measuring cell over the enclosure 4.7 Rotating the measuring cell over the enclosure You can rotate the pressure transmitter housing by approximately 370 relative to the the measuring cell. Rotating the transmitter, for example, when it is installed at an angle, facilitates its operation. This keeps the keys and the power supply connection in a position where they can still be operated Measuring cell Retaining screw (both sides) Transmitter housing Figure 4-3 Range of rotation with transmitters for differential pressure Twisting procedure CAUTION Device damage Avoid damaging the device by not twisting the transmitter past the end stops. 1. Loosen both retaining screws 2 (hexagon socket-head screw 2.5 mm). 2. Twist the transmitter housing 3 against the measuring cell Tighten both retaining screws 2 (torque: 3.4 to 3.6 Nm). Operating Instructions, 09/2010, A5E

44 Install 4.8 Rotating display 4.8 Rotating display The display in the electronics housing can be rotated in increments of 90. Procedure WARNING Danger Only open devices with type of protection "Flameproof enclosure" in hazardous areas when the power to the device is turned off, otherwise there is a risk of explosion. Proceed as follows: 1. Unscrew the cover of the electronics housing. 2. Loosen the two screws on the display and remove it towards the front. 3. The digital display can be rotated in steps of 90. Rotate the display to the desired position. 4. Mount the display, and secure it using the two screws. 5. Screw the cover back on as far as it will go. 42 Operating Instructions, 09/2010, A5E

45 Connecting Safety notes for connection For all devices WARNING If auxiliary power is required, check that it corresponds with that on the nameplate and with the test certification valid for your country. CAUTION Incorrect measurement values due to incorrect grounding It is not permissible to ground the device using the "+" connection. This can lead to malfunctions with permanent damage to the device. If necessary, ground the device using the "-" connection. General explosion protection WARNING Risk of explosion Non-compliance with the stipulations and laws during connection and installation increases the risk of explosion due to improper use. When connecting and installing, follow only the test certifications, stipulations and laws applicable in your country in order to avoid the risk of explosion. For example, for hazardous areas these are: IEC (international) National Electrical Code (NEC - NFPA 70) (USA) Canadian Electrical Code (CEC) (Canada) EN (earlier VDE 0165, T1) (EU) Ordinance on Industrial Safety and Health (Germany) Operating Instructions, 09/2010, A5E

46 Connecting 5.1 Safety notes for connection WARNING Explosion protection Connect the device to the equipotential bonding. Free cable ends are not permitted in hazardous areas. Use suitable protection types, e.g., flameproof enclosure Ex "d" or increased safety Ex "e", to protect the free cable ends. For shielded cables in hazardous areas, note that only end is permitted to be grounded. Install a potential equalising cable if grounding on both ends is required. WARNING Cable glands The cables must be matched to the cable glands. If you use the cable glands M20 x 1.5 and ½-14" NPT, which can be ordered separately, only the cables having a diameter of 6 to 12 mm must be laid into the device. After installation, make sure that the cables are positioned securely and that the seals are in the correct position. Type of protection "na", "nl", "ic" In the case of devices with type of protection "na", "nl" and "ic" (Zone 2), only use cables having a diameter of 8 to 12 mm owing to the required tensile strength, or use a suitable cable gland in case of smaller diameters. CAUTION Cable damage Insulation on cables can be damaged if they are used in elevated ambient temperatures. For this reason, if cables are to be operated in an ambient temperature T 60 C, use heat-resistant cables approved for an ambient temperature at least 20 K higher. Also, ensure that you use appropriate cables for operation in low temperatures. WARNING The inlet openings for the electrical connections must be sealed. For this purpose, use only cable glands or plugs that are suitable for the type of protection that is required. 44 Operating Instructions, 09/2010, A5E

47 Connecting 5.1 Safety notes for connection Special explosion protection WARNING Intrinsically safe circuits Only connect the device to certified intrinsically safe circuits. These circuits must comply with the technical data indicated on the nameplate or in the certificates and approvals (e.g., EC type-examination certificates). If the circuits do not comply with the information in the certificates and approvals, the safety required for the approval is longer guaranteed. Cables for use in hazardous areas in Zones 1 and 2 or 20, 21 and 22 must satisfy the requirements for having a test voltage 500 V AC applied between the conductor/ground, conductor/shield and shield/ground. Note To improve the reliability: Install the signal cable separately from cables with voltages > 60 V. Use cable with twisted strands. Stay away from large electrical systems. Use shielded cable to guarantee the full specification according to HART. Connect a load resistor of at least 230 Ω into the signal circuit in series in order to guarantee fault-free HART communication. When power supply isolators are used for HART transmitters, e.g. SITRANS I, a load resistor is already installed in the device. Operating Instructions, 09/2010, A5E

48 Connecting 5.2 Connecting the device 5.2 Connecting the device Procedure 1. Unscrew the cover of the electrical cable compartment. This side of the housing is marked "FIELD TERMINALS". 2. Insert the connecting cable through the cable gland. 3. Connect the device to the existing protective bonding circuit. 4. Connect the wires to the connecting terminals "+" and "-". Observe the polarity when doing this. If necessary, ground the device using the "-" connection. 5. If necessary, ground the shield to the screw of the ground terminal. This is electrically connected with the external protective conductor connection. 6. Screw the cover back on as far as it will go. 1 Power supply isolator with installed load resistor 4 Connecting terminals 2 Auxiliary power 5 Protective conductor connector/equipotential bonding terminal 3 Ground terminal 6 Cable entry for auxiliary power/analog output Figure 5-1 Schematic electrical connection 46 Operating Instructions, 09/2010, A5E

49 Connecting 5.3 Connecting the Han plug 5.3 Connecting the Han plug WARNING The connector may only be used for Ex ia devices and non-ex devices; otherwise the safety required for the approval is not guaranteed. Note Observe the protection class of the Han plug when defining the protection class. The contact parts for the coupling socket are also supplied. Procedure 1. Slide the sleeve and the screwed joint on the cable. 2. Strip approx. 8 mm of the cable ends. 3. Crimp the contact parts on the cable ends. 4. Assemble the coupling socket. IA Output current UH Auxiliary power Connector pin assignment with Han 7D or Han 8D plug Operating Instructions, 09/2010, A5E

50 Connecting 5.4 Connecting the M12 connector 5.4 Connecting the M12 connector Procedure CAUTION A conductive connection must not exist between the shield and the connector housing. WARNING The connector may only be used for Ex ia devices and non-ex devices; otherwise the safety required for the approval is not guaranteed. Note Observe the protection class of the M12 connector when defining the protection class. For devices in which a connector is already available on the housing, the connection is established using a cable jack. 1. Thread the parts of the cable jack as described by the connector manufacturer. 2. Strip approximately 18 mm of the bus cable Twist the shield. 4. Thread the shield in the insulating sleeve. 5. Draw 8 mm of shrink sleeve over the cable, wires and shield up to the reference edge Screw the cable ends and the shield in the pin insert. 7. Fix the parts of the cable jack as described by the connector manufacturer. Figure 5-2 Preparing the connecting cable 1 Reference edge for stripping 3 Insulating sleeve over the shield 2 Reference edge for the dimension 4 Shrink sleeve specifications for cable assembly 48 Operating Instructions, 09/2010, A5E

51 Connecting 5.4 Connecting the M12 connector Pin assignment Layout for M12 connector Layout for M12 jack 1 M12 x 1 thread 1 Positioning slot 2 Positioning catch Not connected 2 Not connected Shield 4 Shield Middle jack not assembled Operating Instructions, 09/2010, A5E

52 Connecting 5.4 Connecting the M12 connector 50 Operating Instructions, 09/2010, A5E

53 Operate Operation overview General information The following description contains and overview of the operating functions which you can perform on the device and the safety instructions which you have to adhere to in the process. You can operate the device via the local user interface or via HART communication. Local user interface The local user interface consists of a display and three keys. Keys Display Description of the display and functionality of the keys To deactivate the key block, keep the key depressed for two seconds. Note Temperature dependency of the display If you operate the pressure transmitter at temperatures below -10 C, the liquid crystal display will become sluggish. There are three different view types: Measured value view Navigation view Parameter view Operating Instructions, 09/2010, A5E

54 Operate 6.1 Operation overview Table 6-1 Display of the menu navigation Measured value view Navigation view Parameter view The key takes you up and down again. The functions of the buttons depend on the current view. The types of view and the functions of the buttons in the various types of views are described in the following. Zero-point adjustment The legend "ZERO" on the device identifies which keys should be pressed for the zero-point adjustment. Keep both the keys depressed for exactly as long as the set damping. See also Zero point calibration (position correction) (Page 150) "1.1.5 Damping" (Page 59) 52 Operating Instructions, 09/2010, A5E

55 Operate 6.1 Operation overview Display in measurement view Figure 6-1 Measured value unit Measured value 2nd, 3rd or 4th display value Measurement type (PV) Example display in measurement view In the measurement view you can read the current measured value 2, the selected measurement type 4 in the defined units 1. If the 2nd, 3rd and 4th display values are selected, these are also displayed alternatively. Manual switching between the 2nd, 3rd and 4th display values with the keys and. Change measured value view into the main menu using key. Icon Designation Description/meaning Data exchange Display when the HART communication is activated Characteristic Display when a user-specific characteristic is used. Characteristic Display when a root extraction characteristic is used. Operating Instructions, 09/2010, A5E

56 Operate 6.1 Operation overview Display in the navigation view Select the six main menu items with the corresponding assigned submenus. Navigate within the menus with the buttons and. Select submenus using the key. Note If, with the top menu item highlighted, you press the key, you switch back to the measurement view. Or if no further sub-menu is available, when the is pressed, the display switches back to the parameter view. Figure 6-2 Example of display in the navigation view Display in the parameter view In parameter view you can set a value for the previously selected parameter or read the current value. Manually changing the parameters that can be set using the and keys. Accept value or change parameter view into navigation view using the key. 1 Parameter name 4 Adjustable value 2 Parameter number 5 Parameter limits 3 Old value Figure 6-3 Example of display in the parameter view Icon Designation Description/meaning Write protection ON Display if a parameter is read-only. 54 Operating Instructions, 09/2010, A5E

SITRANS P310 with HART SITRANS. Pressure transmitter SITRANS P310 with HART. Introduction. Safety instructions. Description 3. Installing/mounting 4

SITRANS P310 with HART SITRANS. Pressure transmitter SITRANS P310 with HART. Introduction. Safety instructions. Description 3. Installing/mounting 4 Introduction 1 Safety instructions 2 SITRANS Pressure transmitter Operating Instructions Description 3 Installing/mounting 4 Connecting 5 Operation 6 Operating functions through HART 7 Commissioning 8

More information

SITRANS. Pressure transmitter SITRANS P, Z series for gauge and absolute pressure. Introduction. Safety instructions 2.

SITRANS. Pressure transmitter SITRANS P, Z series for gauge and absolute pressure. Introduction. Safety instructions 2. Introduction 1 Safety instructions 2 SITRANS Pressure transmitter SITRANS P, Z series for gauge and absolute pressure 7MF1564 Description 3 Assembly and connection 4 Technical data 5 Dimensional drawings

More information

SITRANS P DS III/P410 with. FOUNDATION Fieldbus FF SITRANS. Pressure transmitter SITRANS P DS III/P410 with FOUNDATION Fieldbus FF.

SITRANS P DS III/P410 with. FOUNDATION Fieldbus FF SITRANS. Pressure transmitter SITRANS P DS III/P410 with FOUNDATION Fieldbus FF. SITRANS P DS III/P410 with FOUNDATION Fieldbus FF SITRANS Pressure transmitter SITRANS P DS III/P410 with FOUNDATION Fieldbus FF Operating Instructions Introduction 1 Safety instructions 2 Description

More information

Operating Instructions Edition 06/2005. Transmitter SITRANS P300 with HART communication. pressure. measurement

Operating Instructions Edition 06/2005. Transmitter SITRANS P300 with HART communication. pressure. measurement Operating Instructions Edition 06/2005 Transmitter SITRANS P300 with HART communication pressure measurement Introduction 1 General safety instructions 2 Pressure measurement technology Transmitter SITRANS

More information

SITRANS P DS III/P410 with PROFIBUS PA SITRANS. Pressure transmitter SITRANS P DS III/P410 with PROFIBUS PA. Introduction 1. Safety information

SITRANS P DS III/P410 with PROFIBUS PA SITRANS. Pressure transmitter SITRANS P DS III/P410 with PROFIBUS PA. Introduction 1. Safety information SITRANS P DS III/P410 with PROFIBUS PA SITRANS Pressure transmitter SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions Introduction 1 Safety information 2 Description 3 Installing / mounting

More information

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken. Getting started 1 Introduction 2 SITRANS P Pressure transmitter SITRANS P320/P420 with 4 to 20 ma/hart Compact Operating Instructions Safety instructions 3 Installing/mounting 4 Connecting 5 Commissioning

More information

Pressure transmitter. SITRANS P, DS III Series with PROFIBUS PA. Operating Instructions 09/2012 SITRANS. Answers for industry.

Pressure transmitter. SITRANS P, DS III Series with PROFIBUS PA. Operating Instructions 09/2012 SITRANS. Answers for industry. Pressure transmitter SITRANS P, DS III Series with PROFIBUS PA Operating Instructions 09/2012 SITRANS Answers for industry. Introduction 1 Safety information 2 SITRANS Pressure transmitter SITRANS P,

More information

SITRANS P measuring instruments for pressure

SITRANS P measuring instruments for pressure SITRANS P measuring instruments for pressure Z series for gage pressure Siemens AG 008 Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and

More information

Pressure Measurement Single-range transmitters for general applications

Pressure Measurement Single-range transmitters for general applications Siemens A 207 Overview Application The SITRANS P Compact pressure transmitter is designed for the special requirements of the food, pharmaceutical and biotechnology industries. The use of high-grade materials

More information

2 Overview. SITRANS P measuring instruments for pressure. Transmitters for gage and absolute pressure. Z series for gage pressure

2 Overview. SITRANS P measuring instruments for pressure. Transmitters for gage and absolute pressure. Z series for gage pressure Z series for gage pressure Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and electronics plate Process connection Electrical connection

More information

Pressure Measurement Single-range transmitters for general applications

Pressure Measurement Single-range transmitters for general applications Siemens AG 07 Overview Function U const. p U I EM Sensor Connection for auxiliary power supply Vent pipe with humidity filter Protective conductor connection/ Equipotential bonding Diaphragm The pressure

More information

OPTIBAR P 1010 C Technical Datasheet

OPTIBAR P 1010 C Technical Datasheet Technical Datasheet Pressure transmitter with recessed diaphragm for general applications Wide variety thanks to modular design Measuring ranges up to 250 bar / 3750 psi High overload and temperature stability

More information

1 Overview. Pressure Measurement Transmitters for basic requirements. 1/16 Siemens FI SITRANS P220 for gauge pressure

1 Overview. Pressure Measurement Transmitters for basic requirements. 1/16 Siemens FI SITRANS P220 for gauge pressure Siemens AG 204 Overview The pressure transmitter SITRANS P220 measures the gauge pressure of liquids, gases and vapors. Stainless steel measuring cell, fully welded Measuring ranges 2.5 to 600 bar (36.3

More information

sitrans p Operating Instructions (de/en) Edition 03/2004

sitrans p Operating Instructions (de/en) Edition 03/2004 (de/en) Edition 03/2004 sitrans p Messumformer für Food, Pharma und Biotechnik Transmitters for food, pharmaceuticals and biotechnologgy 7FM8010 Contents Information for the operator...27 Important security

More information

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI US Edition

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI US Edition Siemens AG 07 SITRANS LH00 Transmitter for hydrostatic level Overview Function U const. p U I EM The pressure transmitter SITRANS LH00 is a submersible sensor for hydrostatic level measurement. The pressure

More information

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/16 Siemens FI US Edition

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/16 Siemens FI US Edition Siemens AG 206 Overview Design Device structure without explosion protection The pressure transmitter consists of a piezoresistive measuring cell with a diaphragm installed in a stainless steel enclosure.

More information

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI Siemens AG 06 SITRANS LH00 Transmitter for hydrostatic level Overview Function U const. p U I EM The pressure transmitter SITRANS LH00 is a submersible sensor for hydrostatic level measurement. The pressure

More information

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator Self-operated Pressure Regulators Type 2357-31 Pressure Build-up Regulator with safety function and integrated excess pressure valve Type 2357-31 with non-return unit at port C Ports A and B with soldering

More information

DK46 - DK800 Supplementary instructions

DK46 - DK800 Supplementary instructions DK46 - DK800 Supplementary instructions Variable area flowmeter Device category II2G with electrical internals Additional Ex manual KROHNE CONTENTS DK46 - DK800 1 Safety instructions 3 1.1 General... 3

More information

* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22.

* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22. *09005087* DB_BA_EN_ME01_S Rev.A 12/16 *09005087* d e v e l o p i n g s o l u t i o n s Data Sheet and Operating Manual ME01 Digital manometer Table of Contents ME01 ## # 87 # HL S#### Dust explosion protection

More information

IDL01. Battery Powered Precision Digital Gauge for Leak Testing. Stainless Steel Sensor. class 0.05

IDL01. Battery Powered Precision Digital Gauge for Leak Testing. Stainless Steel Sensor. class 0.05 IDL0 Battery Powered Precision Digital Gauge for Leak Testing Stainless Steel Sensor class 0.05 Nominal pressure from 0 00 mbar up to 0... 00 bar Special characteristics modular sensor concept data logger

More information

SIL Safety Manual. ULTRAMAT 6 Gas Analyzer for the Determination of IR-Absorbing Gases. Supplement to instruction manual ULTRAMAT 6 and OXYMAT 6

SIL Safety Manual. ULTRAMAT 6 Gas Analyzer for the Determination of IR-Absorbing Gases. Supplement to instruction manual ULTRAMAT 6 and OXYMAT 6 ULTRAMAT 6 Gas Analyzer for the Determination of IR-Absorbing Gases SIL Safety Manual Supplement to instruction manual ULTRAMAT 6 and OXYMAT 6 ULTRAMAT 6F 7MB2111, 7MB2117, 7MB2112, 7MB2118 ULTRAMAT 6E

More information

Gas density monitor With integrated transmitter Model GDM-100-TI

Gas density monitor With integrated transmitter Model GDM-100-TI SF 6 gas solutions Gas density monitor With integrated transmitter Model GDM-100-TI grid Products WIKA data sheet SP 60.05 for further approvals see page 5 Applications Gas density monitoring of closed

More information

How to specify a product. Process Sensors and Mechanical Instruments

How to specify a product. Process Sensors and Mechanical Instruments How to specify a product Process Sensors and Mechanical Instruments Keep the overview. Here is some guideline information on how to specify our products. Intended as supplementary help to specification

More information

Differential Pressure Transmiter

Differential Pressure Transmiter Differential Pressure Transmiter Description The is an economical alternative to established differential pressure transmitters. It combines state of the art electronics and a high performance sensor;

More information

sitrans p Instruction Manual Edition 10/2003

sitrans p Instruction Manual Edition 10/2003 Instruction Manual Edition 10/2003 sitrans p Transmitters for pressure, differential pressure and flow, level, absolute pressure from pressure series 7MF4*33-... s 7MF4*33-... Edition 10/2003 Instruction

More information

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING Contents All Products... Gb-1 Control Valves... Gb-2 Control Valve Actuators... Gb-3 Regulators... Gb-3 Relief Valves... Gb-4 Instruments, Switches, and Accessories... Gb-4 Products Covered by Battery

More information

PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING

PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING Please Note: Ranges above 500mbar are designed and manufactured in accordance with sound engineering

More information

Operating Instructions. Ball valve fitting according to ZB For pressure transmitter VEGABAR 82. Document ID: 50027

Operating Instructions. Ball valve fitting according to ZB For pressure transmitter VEGABAR 82. Document ID: 50027 Operating Instructions Ball valve fitting according to ZB 2553 For pressure transmitter VEGABAR 82 Document ID: 50027 Contents Contents 1 About this document 1.1 Function... 3 1.2 Target group... 3 1.3

More information

2600T Series Pressure Transmitter Models 264DC Differential and 264HC Gage Level Transmitters. Kent-Taylor

2600T Series Pressure Transmitter Models 264DC Differential and 264HC Gage Level Transmitters. Kent-Taylor INDUSTRIAL INSTRUMENTS AND CONTROLS SPECIALIST Kent-Taylor 2600T Series Pressure Transmitter Models 264DC Differential and 264HC Gage Level Transmitters Features Include Base accuracy : ±0.075% Span limits

More information

Pressure Measurement. Transmitters for basic requirements SITRANS P Z for gauge pressure. 2/4 Siemens FI Overview

Pressure Measurement. Transmitters for basic requirements SITRANS P Z for gauge pressure. 2/4 Siemens FI Overview f gauge pressure Siemens AG 010 Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and electronics plate Process connection Electrical connection

More information

x act i Precision Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to IEC 60770: 0.

x act i Precision Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to IEC 60770: 0. Precision Pressure Transmitter for Food ndustry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to EC 60770: 0. % FSO Nominal pressure from 0... 400 mbar up to 0... 40 bar Output

More information

DM01. Please visit our website: Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05

DM01. Please visit our website:  Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05 DM0 Battery Powered Stainless Steel Sensor class 0.05 Nominal pressure from 0 00 mbar up to 0... 00 bar Special characteristics modular sensor concept data logger graphic display stainless steel housing

More information

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN Differential Pressure Regulator Type 45-6 Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN Edition March 2008 Contents Contents Page 1 Design and principle of operation...................

More information

Instruction Manual Contact Pressure Vacuum Gauge

Instruction Manual Contact Pressure Vacuum Gauge MS10 Instruction Manual Contact Pressure Vacuum Gauge Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance

More information

ETd 04. Battery Powered Precision Digital Gauge. Stainless Steel Sensor. Type: ETd 04. class 0.05

ETd 04. Battery Powered Precision Digital Gauge. Stainless Steel Sensor.  Type: ETd 04. class 0.05 Battery Powered Stainless Steel Sensor class 0.05 Nominal pressure from 0 100 mbar up to 0... 400 bar Special characteristics modular sensor concept data logger graphic display stainless steel housing

More information

Electro-Pneumatic Converter YT-940 SERIES

Electro-Pneumatic Converter YT-940 SERIES Electro-Pneumatic Converter YT-940 SERIES PRODUCT MANUAL VERSION 1.00 Contents 1. Introduction 3 1.1 General information for the users. 3 1.2 Manufacturer Warranty 3 1.3 Explosion Proof Warning. 4 2. Product

More information

Type BBS-03, BBS-05, BBS-06, BBS-25

Type BBS-03, BBS-05, BBS-06, BBS-25 Type BBS-03, BBS-05, BBS-06, BBS-25 Sterile connection elements Sterile Verbindungselemente Raccords union stériles Operating Instructions Bedienungsanleitung Manuel d utilisation 1. THE OPERATING INSTRUCTIONS

More information

Pressure Measurement Single-range transmitters for general applications

Pressure Measurement Single-range transmitters for general applications Siemens AG 206 Overview Design Device structure without explosion protection The pressure transmitter consists of a piezoresistive measuring cell with a diaphragm installed in a stainless steel enclosure.

More information

Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar

Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar EN - english Instructions for installation and operation Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar Dear customer, Thank you for deciding in favour of the METPOINT

More information

x act i Precision- Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor

x act i Precision- Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor Precision- Pressure Transmitter for Food ndustry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to EC 60770: 0. % FSO Nominal pressure from 0... 400 mbar up to 0... 40 bar Output

More information

Operating Instructions

Operating Instructions Operating Instructions Light-metal Ex d enclosures / flameproof enclosure > 8265/0 Empty enclosure > 8265/4 Control panel, integrated in Ex e enclosure > 8265/5 Control panel Table of Contents 1 Table

More information

Operating Manual VSA100A. tina29e1 ( )

Operating Manual VSA100A. tina29e1 ( ) Operating Manual Incl. EU Declaration of Conformity Vacuum Switch VSA100A tina29e1 (2017-05) 1 Product Identification In all communications with INFICON, please specify the information on the product nameplate.

More information

PX3005. Rangeable Industrial Pressure Transmitter M-5721/1018

PX3005. Rangeable Industrial Pressure Transmitter M-5721/1018 PX3005 Rangeable Industrial Pressure Transmitter INTRUCTION HEET -5721/1018 hop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info ! Pressure / differential pressure

More information

Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765

Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765 Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765 Application Single-acting positioner for attachment to pneumatic control valves. Supplied with either an electric input signal from

More information

Temperature gauge Installation Guide

Temperature gauge Installation Guide Temperature gauge Installation Guide improper functioning, or damage. Additional information can be found at: CAUTION: Read this installation guide carefully before unpacking the temperature gauge. Improper

More information

DM01. Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05

DM01. Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05 Battery Powered Stainless Steel Sensor class 0.05 Nominal pressure from 0 00 mbar up to 0... 00 bar Special characteristics modular sensor concept data logger graphic display stainless steel housing Ø

More information

Pressure Switches Application Guideline

Pressure Switches Application Guideline Pressure Switches Application Guideline Product Overview The Fema Pressure Switch product portfolio provides devices suitable for many applications. The portfolio contains Special functions and equipment

More information

AMS 6916 Board mount pressure sensor with ratiometric analog output

AMS 6916 Board mount pressure sensor with ratiometric analog output FEATURES Piezoresistive pressure sensor with amplified analog output Calibrated and temperature compensated Ratiometric voltage output, 0.5 4.5 V Digital signal conditioning, 12 bit output resolution Differential,

More information

INSTRUCTION MANUAL Pressure Relief Device LPT

INSTRUCTION MANUAL Pressure Relief Device LPT INSTRUCTION MANUAL Pressure Relief Device LPT 5COV475800 LPT REV00 CONTENT: 1 SAFETY 1.1 Safety instructions 2 1.2 Specified applications 2 1.3 Safety notes on the equipment operation 2 2 PRESSURE RELIEF

More information

Float Operated Level Controllers

Float Operated Level Controllers CONTENTS Float Operated Level Controllers IM0015 Nov. 2014 PAGE Introduction 1 Scope 1 Description 1 Specification 1 Control Installation 2 INTRODUCTION Side Mount Back Mount Prior to installing, the instructions

More information

High-performance submersible pressure transmitter For level measurement Model LH-10

High-performance submersible pressure transmitter For level measurement Model LH-10 Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-10 WIKA data sheet PE 81.09 Applications Level measurement in rivers and lakes Deep well

More information

BGA244 Binary Gas Analyzer

BGA244 Binary Gas Analyzer Quick Start Guide Revision 1.0 Certification Warranty Service certifies that this product met its published specification at the time of shipment. This product is warranted against defects in materials

More information

Installation, operating and maintenance Instructions for Seemag bypass level indicator

Installation, operating and maintenance Instructions for Seemag bypass level indicator Issue: S Date: 05-09-14 Type G35 General information The Seetru bypass magnetic level indicator, abbreviate SEEMAG, serves to show the filling level of fluids in tanks, basins, tubes etc. The Seemag operates

More information

Magnetic level switch type MR783 Instruction Manual

Magnetic level switch type MR783 Instruction Manual Magnetic level switch Magnetic level switch type MR783 1. DESCRIPTION page 3 1.1 Operation page 3 1.2 Application page 3 1.3 Description page 3 2. SPECIFICATIONS page 3 2.1 Service Conditions page 4 2.2

More information

Manual Actuated Boiler Blowdown Valves

Manual Actuated Boiler Blowdown Valves Manual Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Operation 5. Maintenance 6. Spare parts p.1 1. Safety

More information

Coiling Tube with Twist-Proof Fitting

Coiling Tube with Twist-Proof Fitting http://www.pisco.co.jp FITTING CONTROLLER VALVE TUBE MAKE-TO-ORDER PRODUCTS Push-In Fitting Type Anti-Twisting Coiling Tube for Air Tool Coiling Tube with Twist-Proof Fitting 306 Avoid Twisted Tube Problem

More information

Mounting instructions. Strain transducer SLB-700A. B 26.SLB700A.10 e

Mounting instructions. Strain transducer SLB-700A. B 26.SLB700A.10 e Mounting instructions Strain transducer SLB-700A B 26.SLB700A.10 e SLB700A 3 Contents Page Safety instructions.............................................. 4 1 Applications..................................................

More information

Pressure transmitter PASCAL Ci4

Pressure transmitter PASCAL Ci4 Pressure transmitter PASCAL Ci4 for general application,type Series CI4100 Features Pressure transmitter for the measuring of relative and absolute pressures of gases, vapors and liquids High-resolution

More information

Types and approvals. Page 1/6. Data Sheet

Types and approvals. Page 1/6. Data Sheet Page 1/6 Panel-mounting Thermostats EM Series as: Protection temperature monitor STW (STB) Protection temperature limiter STB tested to DIN 3440 and Pressure Equipment Directive 97/23/EC Brief description

More information

GI Series Diaphragm Pressure Gauge Guard

GI Series Diaphragm Pressure Gauge Guard Diaphragm Pressure Gauge Guard INSTRUCTION MANUAL Please read this Instruction Manual Carefully and Thoroughly for the Correct and Optimum use of this Product. Kindly keep this manual in a convenient place

More information

Torque Tube TB300 Digital Transmitters

Torque Tube TB300 Digital Transmitters Page 1 of 7 7E.300-E Issue 4-2009 Description Series TB300 torque tube liquid level instruments utilize the buoyancy exerted on a displacer when immersed in a liquid. The buoyancy on the displacer is proportional

More information

Installation and Operation Manual

Installation and Operation Manual Installation and Operation Manual WIKA FLR-SBDF / BLR-SBDF Magnetic Level Transmitter (Please retain for future usage) Contact: Gayesco-WIKA USA, L.P. 229 Beltway Green Boulevard Pasadena, TX 77503 www.wika.com

More information

DMK 458. Pressure Transmitter for Marine and Offshore. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.25 % FSO option: 0.

DMK 458. Pressure Transmitter for Marine and Offshore. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.25 % FSO option: 0. Pressure Transmitter for Marine and Offshore Ceramic Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0. % FSO Nominal pressure from 0... 40 mbar up to 0... 0 bar Output signals -wire:

More information

High-performance submersible pressure transmitter For level measurement Model LH-20

High-performance submersible pressure transmitter For level measurement Model LH-20 Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-20 WIKA data sheet PE 81.56 Applications Deep well and borehole measurements Groundwater

More information

Instruction Manual Differential Pressure Transmitter

Instruction Manual Differential Pressure Transmitter DE61 Instruction Manual Differential Pressure Transmitter Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance

More information

Declaration of Conformity as per Directive 97/23/EC

Declaration of Conformity as per Directive 97/23/EC Declaration of Conformity as per Directive 97/23/EC The manufacturer declares that:, 47906 Kempen, Germany Multi-way diverting valves Series 29a and Series 29b, with packing with lever 1. The valves are

More information

Type 3709 Pneumatic Lock-up Valve. Translation of original instructions. Mounting and Operating Instructions EB 8391 EN

Type 3709 Pneumatic Lock-up Valve. Translation of original instructions. Mounting and Operating Instructions EB 8391 EN Type 3709 Pneumatic Lock-up Valve Translation of original instructions Mounting and Operating Instructions EB 8391 EN Edition July 2017 Note on these mounting and operating instructions These mounting

More information

Technical Data. General specifications Switching element function Rated operating distance s n 2 mm

Technical Data. General specifications Switching element function Rated operating distance s n 2 mm 0102 Model Number Features 2 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories EXG-12 Quick mounting bracket with dead stop BF 12 Mounting flange, 12 mm Technical Data specifications Switching

More information

AMS 2710 PCB pressure sensor module with V output

AMS 2710 PCB pressure sensor module with V output FEATURES Universal pressure sensor module with 0.. 10 V voltage output Fully calibrated and temperature compensated sensor module Variants for (bidirectional) differential, gage, absolute and barometric

More information

KTM OM-2 SPLIT BODY FLOATING BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

KTM OM-2 SPLIT BODY FLOATING BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installation these instructions must be fully read and understood SECTION 1 - STORAGE 1.1 Preparation and preservation for storage All valves should be properly packed in order to protect the parts

More information

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Manual Brass Shut-Off Valve DN10 through DN22

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Manual Brass Shut-Off Valve DN10 through DN22 Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU FAS Manual Brass Shut-Off Valve DN10 through DN22 Please read these operating instructions carefully to ensure a safe operation

More information

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors 0862050/1 IM-P086-18 MI Issue 1 Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors Installation and Maintenance Instructions 1. Safety Information 2. General product information 3. Installation 4.

More information

High-performance submersible pressure transmitter For level measurement Model LH-20

High-performance submersible pressure transmitter For level measurement Model LH-20 Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-20 WIKA data sheet PE 81.56 Applications Deep well and borehole measurements Groundwater

More information

Instruction Manual Differential Pressure Transmitter

Instruction Manual Differential Pressure Transmitter DE13 Instruction Manual Differential Pressure Transmitter Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance

More information

VS18/26 with PROFINET and EtherNet/IP Interface. ATEX Installation Instructions

VS18/26 with PROFINET and EtherNet/IP Interface. ATEX Installation Instructions VS18/26 with PROFINET and EtherNet/IP Interface ATEX Installation Instructions INDEX 1. INTENDED USAGE 3 2. OPERATING MANUAL ATEX 4 2.1 General conditions 4 2.2 Installation 5 2.3 Operating 5 2.4 Failures

More information

Air Purge Unit. Series: LSP-compact Type: EJG 2-2. (Controlled with DigiFlow 515) Installation & Operation Manual 11/2014

Air Purge Unit. Series: LSP-compact Type: EJG 2-2. (Controlled with DigiFlow 515) Installation & Operation Manual 11/2014 Air Purge Unit Series: LSP-compact Type: EJG 2-2 (Controlled with DigiFlow 515) Installation & Operation Manual 11/2014 Headquarters Sales Office BENELUX Intra-Automation GmbH B. V. Intra-Automation HTP

More information

OPERATING MANUAL CHEMTRAC 840M MANUAL RETRACTABLE PROCESS HOLDER

OPERATING MANUAL CHEMTRAC 840M MANUAL RETRACTABLE PROCESS HOLDER OPERATING MANUAL CHEMTRAC 840M MANUAL RETRACTABLE PROCESS HOLDER Table of contents 1 Security and safety measures... 5 1.1 General safety instructions... 5 1.2 Intended use... 5 1.3 Danger zones and residual

More information

Operating Instructions for Intrinsically Safe Pressure Transmitters Series DMG/******** for Hazardous Application in Coal Mining Industry

Operating Instructions for Intrinsically Safe Pressure Transmitters Series DMG/******** for Hazardous Application in Coal Mining Industry Operating Instructions for Intrinsically Safe ressure Transmitters Series DMG/******** for Hazardous Application in Coal Mining Industry Contents 1. Introduction 2. Abbreviations, symbols 3. Important

More information

Change Valve. Push-In Fitting Type Three-way Changeover Valve. Changeover Air Direction by 90. Lightweight and Compact Design.

Change Valve. Push-In Fitting Type Three-way Changeover Valve. Changeover Air Direction by 90. Lightweight and Compact Design. http://www.pisco.co.jp VALVE TUBE MAKE-TO-ORDER PRODUCTS Push-In Fitting Type Three-way Changeover Valve Change Valve Changeover Air Direction by 90 Lightweight and Compact Design. Fine Operability and

More information

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25 Self-operated Pressure Regulators Differential Pressure Regulators (opening) Type 42-20 Type 42-25 Type 42-20 Differential Pressure Regulator Type 42-25 Differential Pressure Regulator Mounting and Operating

More information

L3 Pressure and Level transmitter

L3 Pressure and Level transmitter SENSORS FOR AND BIOPHARMA. Product Information L3 L3 Pressure and Level transmitter Range of applications Hydrostatic Level measurement in dynamic temperature environments Pressure measurement in pipes

More information

High-performance submersible pressure transmitter For level measurement Model LH-10

High-performance submersible pressure transmitter For level measurement Model LH-10 Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-10 WIKA data sheet PE 81.09 Applications Level measurement in rivers and lakes Deep well

More information

Dual Solenoid Gas Valve Installation

Dual Solenoid Gas Valve Installation Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing or servicing FLYNN Gas Products. Carefully follow all instructions in this bulletin and all instructions

More information

Operating Instructions Temperature Measuring System MF420-5T-100

Operating Instructions Temperature Measuring System MF420-5T-100 Operating Instructions Temperature Measuring System Dnhqdhnjah MF420-5T-100 Dmsklakla Read before use! Observe all safety instructions! Keep for future reference! Fon +49/7221/64103 Fax +49/7221/17103

More information

Instruction Manual EMA 84 Digital Pressure Gauge

Instruction Manual EMA 84 Digital Pressure Gauge Instruction Manual EMA 84 Digital Pressure Gauge halstrup-walcher GmbH Stegener Straße 10 D-79199 Kirchzarten Phone: +49 (0) 76 61/39 63 0 Fax: +49 (0) 76 61/39 63 99 E-Mail: info@halstrup-walcher.com

More information

Technical Data Sheet MF010-O-LC

Technical Data Sheet MF010-O-LC Technical Data Sheet MF010-O-LC - 1 - 1. Properties The oxygen measuring system MF010-O-LC determines the oxygen content in gas mixtures up to a temperature of 250 C. It is particularly suitable for the

More information

Insert Ring. Protection Ring from Tube Deformation. Protect tubes from deformation. Ultra soft tube is connectable to Fitting.

Insert Ring. Protection Ring from Tube Deformation. Protect tubes from deformation. Ultra soft tube is connectable to Fitting. http://www.pisco.co.jp TUBE MAKE-TO-ORDER PRODUCTS Protection Ring from Deformation Insert Ring 668 Protect tubes from deformation. Ultra soft tube is connectable to Fitting. Necessary for the connection

More information

DTG - LCD Digital Temperature Gauge USER MANUAL

DTG - LCD Digital Temperature Gauge USER MANUAL DTG - LCD USER MANUAL Page 1 of 7 USERS GUIDE page 1. Description 3 2. Function 3 3. Safety Instruction 3 3.1. Safety Conventions 3 3.2. Proper Use 3 4. Installation 4 4.1. Unpacking 4 4.2. Storage 4 4.3.

More information

Supplementary Installation and Operating Instructions. Variable Area Flow Meters SGK-1 Ex SGK-2 Ex SGK-3 Ex. Category: II 2G Ex IIC II 3G Ex IIC

Supplementary Installation and Operating Instructions. Variable Area Flow Meters SGK-1 Ex SGK-2 Ex SGK-3 Ex. Category: II 2G Ex IIC II 3G Ex IIC Supplementary Installation and Operating Instructions Variable Area Flow Meters SGK-1 Ex SGK-2 Ex SGK-3 Ex Category: II 2G Ex IIC II 3G Ex IIC Contents 1 General safety directions...3 2 Main safety features...4

More information

Installation and Operation Manual

Installation and Operation Manual Manual Static pressure transducer with controller Differential static pressure transducer with analog output and optional PI control mode Large diaphragm element with differential transformer Transducer

More information

Hand Valve Series. Push-In Fitting Type Shut-off Valve (Residual Pressure Release Valve) Control Open/Close for Air Supply.

Hand Valve Series. Push-In Fitting Type Shut-off Valve (Residual Pressure Release Valve) Control Open/Close for Air Supply. http://www.pisco.co.jp VALVE TUBE MAKE-TO-ORDER PRODUCTS Push-In Fitting Type Shut-off Valve (Residual Pressure Release Valve) Hand Valve Series 556 Control Open/Close for Air Supply. Release Residual

More information

Operating Manual. Diaphragm Seals Models , 107, , 207,

Operating Manual. Diaphragm Seals Models , 107, , 207, Operating Manual Diaphragm Seals Models 100-105, 107, 200-205, 207, 300-304 (non-electrical device) in an ####=ATEX finish For explosion risk areas in accordance with Directive 94/9/EC (ATEX) Zone 1 and

More information

Instruction Manual 742 5/1/2009. Eclipse Ratio Regulators ES Series Version 1

Instruction Manual 742 5/1/2009. Eclipse Ratio Regulators ES Series Version 1 Instruction Manual 742 5/1/2009 Eclipse Ratio Regulators ES Series Version 1 Copyright Copyright 1997 by Eclipse, Inc. All rights reserved worldwide. This publication is protected by federal regulation

More information

High-performance submersible pressure transmitter For level measurement in hazardous areas Model LH-20

High-performance submersible pressure transmitter For level measurement in hazardous areas Model LH-20 Electronic pressure measurement High-performance submersible pressure transmitter For level measurement in hazardous areas Model LH-20 WIKA data sheet PE 81.56 Applications Deep well and borehole measurements

More information

P9000 DESCRIPTION. For parts requiring RoHS compliance, please contact factory. P February /6

P9000 DESCRIPTION. For parts requiring RoHS compliance, please contact factory. P February /6 P9000 High accuracy through digital compensation High thermal stability Rugged stainless steel construction Ideal for test stands High burst pressure limit DESCRIPTION The P9000 Series is a range of advanced,

More information

VG5 Supplementary instructions

VG5 Supplementary instructions VG5 Supplementary instructions 2-wire / 10 GHz Radar (FMCW) Level Meter Supplementary Instructions for ATEX applications HYCONTROL CONTENTS VG5 1 General safety information 4 1.1 Scope of the document...

More information

BGA158 Series CE Approved Class A Shutoff Gas Valve

BGA158 Series CE Approved Class A Shutoff Gas Valve Installation Instructions BGA158 Issue Date August 24, 2011 BGA158 Series CE Approved Class A Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated gas valve that

More information

Differential pressure

Differential pressure Differential pressure 9 Overview Page 200 VEGADIF 65 Page 202 Chemical seal Page 204 Accessory Page 208 199 VEGADIF For differential pressure, level and flow measurements Measuring principle The sensor

More information

Cautions : 1. Clogging of the element raises resistance to exhaust, thus lowering the

Cautions : 1. Clogging of the element raises resistance to exhaust, thus lowering the The Silencer, connected to the exhaust port of a device, suppresses the exhaust noise. The Silencer displays an excellent noise suppression effect. Three types are available for your selection. The element

More information