Dual Fuel Gas / Light Oil Burners

Size: px
Start display at page:

Download "Dual Fuel Gas / Light Oil Burners"

Transcription

1 Installation, use and maintenance instructions Dual Fuel Gas / Light Oil Burners RLS Low - High Operation C

2 CONTENTS FUEL OIL / GAS Technical data page 3 Burner models Accessories Burner description Packaging - Weight Max. dimensions Standard equipment Firing rates Minimum furnace dimensions Installation Boiler plate Blast tube length Securing the burner to the boiler FUEL OIL Choice of nozzles for 1st and 2nd stage Nozzle assembly Adjustments before first firing FUEL OIL / GAS Servomotor WARNING If you smell gas: Do not touch any electrical items. Open all windows. Close all gas supply valves. Contact your local gas authority immediately. Do not store flammable or hazardous materials in the vicinity of fuel burning appliances. Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or death. Refer to this manual for instructional or additional information. Consult a certified installer, service representative or the gas supplier for further assistance. Burner shall be installed in accordance with manufacturers requirements as outlined in this manual, local codes and authorities having juristiction. FUEL OIL Pump Fuel supply Hydraulic connections Pump priming Burner calibration GAS Gas pressure Gas piping Adjustments before first firing Burner starting Burner firing Burner calibration FUEL OIL / GAS Maintenance Hydraulic system layout ELECTRICAL Factory wiring diagram - RLS with burner mounted LFL. 18 Factory wiring diagram - RLS 50 with burner mounted LFL Field wiring diagram - RLS with burner mounted LFL 20 Factory wiring diagram - RLS with remote panel Appendix - Burner firing rates according to air density Flame signal measurement Siemens LFL control sequence of operations Siemens LFL control troubleshooting guide Burner start up report

3 TECHNICAL DATA MODEL RLS 28 RLS 38 RLS 50 Output (1) 2nd stage MBtu/hr (4) Delivery (1) kw GPH min. 1st MBtu/hr (4) stage kw GPH Fuel #2 Fuel oil Natural gas / Propane gas Gas pressure at maximum delivery (2), Gas: Natural gas WC Operation low-high Nozzles number 2 Ambient temperature F (0-40 C) Combustion air temperature F max 140 (60 C) Main power supply (+/- 10%) V/Ph/Hz 120/1/ /460/575/3/60 Electric motors rpm 3400 Fan motor V / 460 / 575 W - HP A µf n/a Fan motor capacitor Pump motor V W - HP A Pump motor capacitor µf Ignition transformer Oil V1 - V2 I1 - I2 Gas V1 - V2 I1 - I2 Pump (1) Reference conditions: Ambient temperature 68 F (20 C) - Barometric pressure 394 WC - Altitude 329 ft. (2) Pressure at test point 7)(A)p.4 with zero pressure in the combustion chamber and maximum burner output. (3) Sound pressure measured in manufacturer s combustion laboratory, with burner operating on test boiler and at maximum rated output. (4) Equivalent Btu values based on 1 USGPH = 140,000 Btu/hr. Burner models designation: Delivery (at 174 PSI) Pressure range Fuel temperature GPH PSI F max ,8 12,5 120 V - 2 x 5 kv 3.7 A - 35 ma 120 V - 1 x 7 kv 1.6 A - 23 ma (60 C) Electrical power consumption W max Electrical protection NEMA 1 Noise Levels (3) dba Model Code Voltage Flame safeguard RLS 28 RLS 38 RLS 50 C ( ) C ( ) C ( ) C ( ) C ( ) C ( ) C ( ) C ( ) 120/1/60 120/1/60 120/1/60 120/1/ /460/3/60 575/3/ /460/3/60 575/3/60 Burner mounted Remote panel Burner mounted Remote panel Burner mounted Burner mounted Remote panel Remote panel Accessories (optional): Kit for lengthening the combustion head L =Standard length L1 =Length obtainable with the kit COD L = 7 1/2 L1 = 12 27/32 RLS 28 COD L = 7 29 /32 L1 = 13 7/32 RLS 38 COD L = 8 1/2 L1 = 13 13/16 RLS 50 Kit for LPG operation - Code : The kit allows the RLS burners to operate on LPG. Gas train according to UL Standards: see page 12. Important: The installer is responsible for the supply and installation of any required safety device(s) not indicated in this manual. 3

4 (A) D2534 D2536 inch A B C lbs RLS / / /16 95 RLS / / /16 99 RLS / / / D88 D1118 BURNER DESCRIPTION (A) 1 Combustion head 2 Ignition electrodes 3 Screw for combustion head adjustment 4 Sleeve 5 Low air pressure switch (differential operating type) 6 Air pressure test point 7 Gas pressure test point and head fixing screw 8 Screw securing fan to sleeve 9 Slide bars for opening the burner and inspecting the combustion head 10 Pump 11 Safety solenoid valve 12 Low and high fire oil valves 13 Servomotor 14 UV scanner 15 Plate with four hole knock-outs for flexible hoses and electrical cable routing. 16 Air inlet to fan 17 Gas input connection 18 Boiler mounting flange 19 Flame stability disk 20 Flame inspection window 21 Oil / gas selector switch 22 Fan motor contactor and thermal overload with reset button (RLS 50 three-phase) 23 Flame safeguard with lock-out pilot light and lock-out reset button 24 Power switch for different operations: automatic - manual - off Button for: power increase - power reduction 25 Burner terminal strip 26 Low oil pressure switch 27 Pump motor Two types of burner failure may occur: Flame safeguard lock-out: if the flame relay 23)(A) pushbutton lights up, it indicates that the burner is in lock-out. To reset, press the pushbutton. Motor trip (RLS 50 three-phase): Release by pressing the pushbutton on the thermal overload 22)(A). PACKAGING - WEIGHT - Approximate measurements The burners are shipped in cardboard boxes with the maximum dimensions shown in table. The weight of the burner complete with packaging is indicated in Table. MAX. DIMENSIONS (C) - Approximate measurements The maximum dimensions of the burners are given in (C). Note that if you need to examine the combustion head, the burner must be pulled backward on the slide bars and turned upward. The maximum dimension of the burner, without the cover, when open is given by measurement H. D495 RLS A B C D E F G H I L M / / / /2 5 1 / / / /8 4 1 /4 6 5 /8 1 1 / / / / / / / / /8 4 1 /4 6 5 /8 1 1 / / / / / / / / /8 4 1 /4 6 5 /8 1 1 /2 STANDARD EQUIPMENT 1 - Gas train flange 1 - Flange gasket 4 - Flange fixing screws 4 - Screws to secure the burner flange to the boiler: 3/8 W x Adaptor G 1 /8 / 1 /8 NPT 1 - Instruction booklet 1 - Spare parts list (C) 4

5 Combustion chamber pressure WC Combustion chamber pressure WC RLS 28 RLS 38 FIRING RATES (A) The RLS Model burners can work in two ways: low and high fire. MAXIMUM OUTPUT must be selected in area A. MINIMUM OUTPUT must not be lower than the minimum limit shown in the diagram: RLS 28 = 378 MBtu/hr = 2.7 GPH RLS 38 = 434 MBtu/hr = 3.1 GPH RLS 50 = 546 MBtu/hr = 3.9 GPH Important: The firing rate area values have been obtained considering an ambient temperature of 68 F (20 C), and an atmospheric pressure of 394 WC and with the combustion head adjusted as shown on page 7. Note: The FIRING RATE areas given in figure (A) have been reduced by 10% with respect to the maximum range that can be reached. Consult Appendix on page 22 for operation at different ambient temperatures and/or altitudes. MINIMUM FURNACE DIMENSIONS The firing rates were set in relation to certified test boilers. Figure indicates the diameter and length of the test combustion chamber. Example: output 1388 MBtu/hr: diameter 20 inch - length 4.9 ft. RLS 50 Combustion chamber pressure WC (A) D2537 Diameter (inches) Furnace dimensions Length (ft) D2918 5

6 inch A B C RLS / /16 3/8 W RLS / /16 3/8 W RLS / /16 3/8 W (A) D455 INSTALLATION BOILER PLATE (A) Drill the combustion chamber mounting plate as shown in (A). The position of the threaded holes can be marked using the head gasket supplied with the burner. BLAST TUBE LENGTH The length of the blast tube must be selected according to the indications provided by the manufacturer of the boiler, and it must be greater than the thickness of the boiler door complete with its insulation. The range of lengths available, L (inch), is as follows Blast tube 10): RLS 28 RLS 38 RLS 50 short 71/2 729/32 81/2 long 1227/32 137/ /16 For boilers with front flue passes 13) or flame inversion chambers, protective insulation 11) must be inserted between the boiler refractory 12) and the blast tube 10). This protective insulation must not compromise the extraction of the blast tube. For boilers having a water-cooled front the insulation 11)-12) is not required unless it is required by the boiler manufacturer. (C) 60 RLS 28 RLS 38 RLS 50 NOZZLE GPH GPH MBTU/h 145 PSI 174 PSI 203 PSI 174 PSI D2538 D339 SECURING THE BURNER TO THE BOILER Detach the combustion head from the burner, fig. : - disconnect the oil pipes by unscrewing the two connectors 4). - remove screw 14) and withdraw the cover 15). - remove the screws 2) from the slide bars 3). - remove screw 1) and pull the burner back on slide bars 3) by about 4. Disconnect the electrode wires and then pull the burner completely off the slide bars, after removing the split pin from the slide bar 3). Secure the flange 9) to the boiler plate, inserting the gasket 6). Use the 4 screws, also supplied with the unit, after first protecting the thread with an anti-locking product. The seal between burner and boiler must be airtight. CHOICE OF NOZZLES FOR 1ST AND 2ND STAGE Both nozzles must be chosen from among those listed in table (C). The first nozzle determines the delivery of the burner at low fire. The second nozzle works together with the 1st nozzle to determine the delivery of the burner at high fire. The deliveries at low and high fire must be contained within the value range indicated on page 3. Use nozzles with a 60 spray angle at the recommended pressure of 174 PSI.The two nozzles usually have equal deliveries. Example with the RLS 28 Model Boiler output = 921 efficiency 80 % Output required by the burner = 921 / 0.8 = 1151 MBtu/hr 1151 / 2 = 576 MBtu/hr (4.0 USGPH) per nozzle therefore, two equal, 60, 174 PSI nozzles are required: 1 = 4.00 GPH with 2 = 4.00 GPH, or the following two different nozzles: 1 = 4.50 GPH with 2 = 3.50 GPH, or: 1 = 3.50 GPH with 2 = 4.50 GPH. (D) D1122 6

7 D1146 D1147 NOZZLE ASSEMBLY Remove screw 1)(D)p.6 and extract the internal part 2)(D)p.6 Install two nozzles with the box wrench 1)(A), after having removed the plastic plugs 2)(A), fitting the wrench through the central hole in the flame stability disk or loosen screws 1), remove disk 2) and replace the nozzles using the wrench 3). Do not use any sealing products such as gaskets, sealing compound, or tape. Be careful to avoid damaging the nozzle sealing seat. The nozzles must be screwed into place tightly but carefully. The nozzle for low fire operation is the one underneath the firing electrodes fig. (C). (A) Make sure that the electrodes are positioned as shown in figure (C). Refit the burner 4)(F) to the slide bars 3) at approximately 4 from the sleeve 5) - burner positioned as shown in fig. p. 6 - insert the ignition electrode cables and then slide the burner up to the sleeve so that it is positioned as shown in fig. (F). Refit screws 2)(F) on slide bars 3). Secure the burner to the sleeve by tightening screw 1) and then refit the split pin into one of two slide bars 3). Connect the oil pipes again by screwing on the two connectors 4)p.6. Important When fitting the burner on the two slide bars, it is advisable to gently draw out the high tension cables until they are slightly stretched. D2539 (C) SETTING THE COMBUSTION HEAD ADJUSTMENTS BEFORE FIRST FIRING (light-oil operation) Combustion head setting The setting of the combustion head depends exclusively on the delivery of the burner at high fire. Turn screw 5)(D) until the notch shown in diagram (E) is level with the front surface of flange 6)(D). Example burner RLS 38: High fire burner delivery = 9.6 GPH. If diagram (E) is consulted it is clear that for this delivery, the combustion head must be adjusted using notch 4, as shown in fig. (D). Pump adjustment No settings are required for the pump, which is set to 174 PSI by the manufacturer. This pressure must be checked and adjusted (if required) after the burner has been ignited. The only operation required in this phase is the application of a pressure gauge on the appropriate pump connection. Fan damper adjustment The first time the burner is fired leave the factory setting unchanged for both low and high fire operation. (D) D2540 D1149 N Notches Burner output in 2nd stage operation (E) D2541 (F) 7

8 (A) PUMP SUNTEC AL 65 ORANGE CAM BLUE CAM RED CAM RESET D2522 SERVOMOTOR (A) The servomotor adjusts the air damper. The servomotor rotates through 90 in 25 seconds. Do not alter (for the time-being) the factory setting. Blue cam Sets the position of the air damper during low fire operation. Red cam Sets the position of the air damper during high fire operation. Orange cam Establishes when the high fire gas or fuel oil valve opens. It must always operate (just) before the red cam and after the blue cam. PUMP 1 - Suction 1/4 NPT 2 - Return 1/4 NPT 3 - Pressure gauge attachment G 1/8 4 - Vacuum gauge attachment G 1/8 5 - Pressure regulator A - Min. delivery rate at 174 PSI pressure B - Delivery pressure range C - Max. suction pressure D - Viscosity range E - Max fuel oil temperature F - Max. suction and return pressure G - Pressure calibration in the factory H - Filter mesh width D2542 A B C D E F G H GPH PSI PSI cst F - C PSI PSI inch AL

9 (A) 6 6 D cm H + H V P 7 5 A B 3 + H - H ft L ft Ø inch 5/16 3/8 1/ FUEL SUPPLY (A) The burner is equipped with a self-priming pump which is capable of feeding itself within the limits listed in the table at the side. The tank higher than the burner A The distance P must not exceed 33 ft in order to avoid subjecting the pump's seal to excessive strain; the distance "V" must not exceed 13 ft in order to permit pump self-priming even when the tank is almost completely empty. The tank lower than the burner B Pump suction values higher than 6.5 PSI must not be exceeded because at higher levels gas is released from the fuel, the pump starts making noise and its working lifespan decreases. It is good practice to ensure that the return and suction lines enter the burner from the same height; in this way it will be more improbable that the suction line fails to prime or stops priming. Key H = Pump/Foot valve height difference L = Piping length Ø = Inside pipe diameter 1 = Burner 2 = Pump 3 = Filter 4 = Manual on/off valve 5 = Suction line 6 = Foot valve 7 = Return line HYDRAULIC CONNECTIONS The pumps are equipped with a by-pass that connects return line and suction line. The pumps are installed on the burner with the by-pass closed by screw 6), see diagram page 17. It is therefore necessary to connect both hoses to the pump. The pump seal will be damaged immediately if it is run with the return line closed and the by-pass screw inserted. Remove the plugs from the suction and return connections of the pump. Insert the hose connectors into the connections and screw them down. Take care that the hoses are not stretched or twisted during installation. Route the hoses through the holes in the plate, preferably using those on the right side, fig.: unscrew the screws 1), now divide the insert piece into its two parts 2) and 3) and remove the thin plug blocking the two passages 4). Install the hoses where they cannot be stepped on or come into contact with hot surfaces of the boiler and where they do not hamper the opening of the burner. Now connect the other end of the hoses to the suction and return lines. PUMP PRIMING - Before starting the burner, make sure that the tank return line is not clogged. Obstructions in the line could cause the pump seal located on the pump shaft to break. (The pump leaves the factory with the by-pass closed). - Also check to make sure that the valves located on the suction line are open and that there is sufficient fuel in the tank. - For self-priming to take place, one of the screws 3) of the pump, see fig. page 8, must be loosened in order to bleed off the air contained in the suction line D2544 9

10 (A) 1 2 D791 - Start the burner by closing the control circuit, with switch 1)(A) in the "MAN" position and with switch 21)(A)p.4 in the "OIL" position. - The pump is primed when the fuel oil starts coming out of the screw 3)p.8. Stop the burner: switch 1)(A) set to "OFF" and tighten the screw 3). The time required for this operation depends upon the diameter and length of the suction tubing. If the pump fails to prime at the first starting of the burner and the burner locks out, reset the burner, and then repeat the starting operation. Do not illuminate the UV scanner cell or the burner will lock out. BURNER CALIBRATION (light-oil operation) Note It is advisable to first set the burner for operation on oil and then for gas. WARNING Turn burner off prior to switching fuels FIRING Set switch 1)(A) to "MAN". During the first firing, and the change from low to high fire, there is a momentary lowering of the fuel pressure caused by the filling of the high fire nozzle tubing. This lowering of the fuel pressure can cause the burner to lock-out. OPERATION The optimum calibration of the burner requires an analysis of the flue gases at the boiler outlet and adjustments at the following points: Low and high fire nozzles See the information listed on page 6. Combustion head The adjustment of the combustion head already carried out (page 7) need not be altered unless the high fire input of the burner is changed. Pump pressure 174 PSI: this is the pressure calibrated in the factory which is usually sufficient for most purposes. Sometimes, this pressure must be adjusted to: 145 PSI in order to reduce fuel delivery. This adjustment is possible only if the surrounding temperature remains above 0 C; 203 PSI in order to increase fuel delivery or to ensure firings even at temperatures of less than 0 C. In order to adjust pump pressure, use the screw 5)p.8. Low fire fan air damper Keep the burner operating at low fire. The fan air damper is adjusted by moving the blue cam of the servomotor, see page 8. High fire fan air damper Press switch 2)(A) increase output and keep it pressed until the high fire position. The fan air damper is adjusted by moving the red cam of the servomotor, see page 8. 10

11 RLS 28 (A) MBtu/hr RLS 38 MBtu/hr RLS 50 MBtu/hr p ( WC) Natural gas p ( WC) Natural gas p ( WC) Natural gas GAS PRESSURE The adjacent tables show minimum pressure losses at combustion head depending on the burner output at high fire. Gas pressure measured at test point 1), with: Combustion chamber at 0 WC Burner operating at high fire Natural gas Calculate the approximate high fire output of the burner as follows: - subtract the combustion chamber pressure from the gas pressure measured at test point 1). - Find the nearest pressure value to your result in the table for the burner in question. - Read off the corresponding output on the left. Example - RLS 28 High fire operation Natural gas Gas pressure at test point 1) = 3.66 WC Pressure in combustion chamber = 0.79 WC = 2.87 WC A high fire ouput of 796 MBtu/hr shown in table RLS 28 corresponds to 2.87 WC pressure, natural gas. This value serves as a rough guide, the effective delivery must be measured at the gas meter. To calculate the required gas pressure at test point 1), set the output required from the burner in high fire operation: - find the nearest output value in the table for the burner in question. - Read off the pressure at test point 1). - Add this value to the estimated pressure in the combustion chamber. Example - RLS 28 Required burner output in high fire operation: 796 MBtu/hr Natural gas Gas pressure at burner output of 796 MBtu/hr, taken from table RLS 28, natural gas = 2.87 WC Pressure in combustion chamber = 0.79 WC = 3.66 WC pressure required at test point 1). D

12 (A) TYPICAL SCHEMATIC GAS PIPING D1137 GAS PIPING The gas train must be connected to the gas attachment 1)(A), using flange 2), gasket 3) and screws 4) supplied with the burner. The gas train can enter the burner from the right or left side, depending on which is the most convenient, see fig. (A). Gas solenoid 6) must be as close as possible to the burner to ensure gas reaches the combustion head within the safety time period. Make sure that the pressure governor calibration range (colour of the spring) comprises the pressure required by the burner. GAS TRAIN It must be type-approved according to UL Standards and is supplied separately from the burner. Note See the accompanying instructions for the adjustment of the gas train. KEY TO LAYOUT 1 - Gas input pipe 2 - Manual valve 3 - Pressure regulator 4 - Low gas pressure switch 5 - Safety solenoid VS 6-2nd safety shutt-off valve 7 - Standard issue burner gasket with flange 8 - Burner D

13 (A) LOW GAS PRESSURE SWITCH D2547 AIR PRESSURE SWITCH D2548 ADJUSTMENTS BEFORE FIRST FIRING (gas operation) Adjustment of the combustion head has been illustrated on page 7. In addition, the following adjustments must also be made: - open manual valves down stream and up stream from the gas train. - Adjust the minimum gas pressure switch to the start of the scale (A). - Adjust the air pressure switch to the zero position of the scale. - Purge the air from the gas line. Fit a U-type manometer (C) to the gas pressure test point on the sleeve. The manometer readings are used to calculate the high fire burner firing rate using the tables on page 11. Before starting up the burner it is good practice to adjust the gas train so that ignition takes place in conditions of maximum safety, i.e. with gas delivery at the minimum. BURNER STARTING (gas operation) NOTE: it is advisable to first set the burner to operate on oil and then on gas. D2549 WARNING Turn burner off prior to switching fuels Close the control circuit and set switch 1)(C) to "MAN" position. (C) 1 2 D791 BURNER FIRING (gas operation) Having completed the checks indicated in the previous heading, the burner should fire. If the motor starts but the flame does not appear and the flame relay goes into lock-out, reset and wait for a new firing attempt. If firing is still not achieved, it may be that gas is not reaching the combustion head within the safety time period. In this case increase gas firing delivery. The arrival of gas at the sleeve is indicated by the U-type manometer (C). Once the burner has fired, proceed with calibration. 13

14 1 2 BURNER CALIBRATION (gas operation) The optimum calibration of the burner requires an analysis of the flue gases at the boiler outlet. Adjust successively: 1 - High fire burner output 2 - Low fire burner output 3 - Air pressure switch 4 - Minimum gas pressure switch (A) D HIGH FIRE OUTPUT High fire output of the burner must be set within the firing rate range shown on page 5. Press switch 2)(A) output increase : the servomotor will open the air damper at the previously set value for oil and will control the opening of the high fire gas valve. Gas calibration Adjust gas delivery to the amount of air at this position. - If delivery needs to be reduced, diminish outlet gas pressure and, if it is already very low, slightly close high fire adjustment valve.( if installed) - If delivery needs to be increased, increase outlet gas pressure. 2 - LOW FIRE OUTPUT Burner power at low fire operation must be selected within the firing rate range shown on page 5. Press switch 2)(A) output decrease and keep it pressed until the low fire position is reached: the servomotor will close the air damper at the previously set value for oil and will control the opening of the low fire gas valve. Adjusting gas delivery Adjust gas delivery to the amount of air by adjusting the low fire gas valve VR1. 14

15 AIR PRESSURE SWITCH 3 - AIR PRESSURE SWITCH (A) - CO CHECK Adjust the air pressure switch after having performed all other burner adjustments with the air pressure switch set to the start of the scale (A). With the burner operating in low fire, increase adjustment pressure by slowly turning the relative dial clockwise until the burner locks out. Then turn the dial anti-clockwise by about 20% of the set point and repeat burner starting to ensure it is correct. If the burner locks out again, turn the dial anti-clockwise a little bit more. D2548 Attention: As a rule, the air pressure switch must block the formation of CO. To check this, insert a combustion analyser into the chimney, slowly close the fan suction inlet (for example with cardboard) and check that the burner locks out, before the CO in the fumes exceeds 400 ppm. (A) LOW GAS PRESSURE SWITCH The air pressure switch may operate in "differential" operation in two pipe system. If a negative pressure in the combustion chamber during pre-purging prevents the air pressure switch from switching, switching may be obtained by fitting a second pipe between the air pressure switch and the suction inlet of the fan. In this way the air pressure switch operates as adifferential pressure switch. D LOW GAS PRESSURE SWITCH Adjust the low gas pressure switch after having performed all the other burner adjustments with the pressure switch set at the start of the scale. With the burner operating at high fire, increase adjustment pressure by slowly turning the relative dial clockwise until the burner locks out. Then turn the dial anti-clockwise by 0.8 WC and repeat burner starting to ensure it is uniform. If the burner locks out again, turn the dial anti-clockwise again by 0.4 WC. 15

16 FLAME INSPECTION WINDOW MAINTENANCE (A) UV SCANNER OPENING THE BURNER D484 D1140 Combustion The optimum calibration of the burner requires an analysis of the flue gases. Significant differences with respect to the previous measurements indicate the points where more care should be exercised during maintenance. Gas leaks Make sure that there are no gas leaks on the pipework between the gas meter and the burner. Flame inspection window Clean the flame inspection window (A). Combustion head Open the burner and make sure that all components of the combustion head are in good condition, not deformed by the high temperatures, free of impurities from the surroundings and correctly positioned. If in doubt, disassemble the elbow fitting 7)(C). Nozzles (fuel oil) Do not clean the nozzle orifices. The nozzle filters however may be cleaned or replaced as required. Replace the nozzles every 2-3 years or whenever necessary. Combustion must be checked after the nozzles have been changed. UV scanner Clean the glass cover from any dust that may have accumulated. The UV scanner 1) is held in position by a pressure fit and can therefore be removed by pulling it outward. Flexible hoses (fuel oil) Check to make sure that the flexible hoses are still in good condition and that they are not crushed or otherwise deformed. Burner Check for excess wear or loose screws. Also make sure that the screws securing the electrical leads in the burner connections are fully tightened. Clean the outside of the burner. Combustion Adjust the burner if the combustion values found at the beginning of the operation do not comply with the regulations in force, or do not correspond to good combustion. Record the new combustion values; they will be useful for subsequent comparison. TO OPEN THE BURNER (C): - switch off the electrical power. - Remove screws 1) and withdraw cover 2). - Disconnect the light-oil pipes 7). - Remove screw 5), the split pin 9) and pull the burner back by about 4 on the slide bars 6). Disconnect the electrode leads and then pull the burner fully back. - Tilt the burner as shown in the figure and fit the split pin 9) into one of the slide bar holes so that the burner remains in position Now extract the internal part 7) after having removed the screw 8). TO CLOSE THE BURNER (C): remove the split pin 9) and push the burner until it is about 4 from the sleeve. Re-connect the leads and slide the burner in until it comes to a stop. Refit screw 5), the split pin 9) and pull the leads gently out until they are slightly stretched. Reconnect the light-oil pipes. (C) D

17 HYDRAULIC SYSTEM LAYOUT (A) 1 Pump suction 2 Filter 3 Pump 4 Pressure regulator 5 Return pipe 6 By-pass screw 7 Pump return 8 Safety solenoid 9 Low fire valve 10 High fire valve 11 Filter M Pressure gauge P Low oil pressure switch V Vacuum gauge P OIL PRESSURE SWITCH The oil pressure switch 26)(A) page 4 is factory set to 145 PSI (10 bar). If the oil pressure goes below this value, the pressure switch stops the burner. COMBUSTION CHECKS CO 2 It is better to set the burner with CO 2 not higer than 10% (with natural gas). In this way avoiding a loss of calibration setting (for example draft variation) that could cause combustion with little air and the production of CO. CO It must be not higher than 400 PPM. D2596 (A) 17

18 Factory Wiring Diagram RLS With burner mounted Siemens LFL control D2295 Continuous fan operation Change the wire connection from terminal 6 to terminal 1, move the jumper from terminals to terminals 4-12 and change the K1-9 wire connection from terminal A2 of of the motor contactor to terminal 6 of the control box, as indicated below. (A) Burners RLS Key to layout (A) C1 - Fan motor capacitor C2 - Pump motor capacitor CMV - Motor contactor K1 - Relay DA - LFL Control box S1 - Switch for following operations: MAN = manual AUT = automatic OFF S2 - Button for: - = power reduction + = power increaser S3 MA MB MV MP PA PO RT SM TA TB UV V1 V2 VS - OIL/GAS selector - Auxiliary terminal strip - Burner terminal strip - Fan motor - Pump motor - Air pressure switch - Oil pressure switch - Thermal overload - Servomotor - Ignition transformer - Burner ground - UV scanner - Low fire oil valve - High fire oil valve - Safety oil valve D

19 Factory Wiring Diagram RLS 50 With burner mounted Siemens LFL control D2296 Continuous fan operation Change the wire connection from terminal 6 to terminal 1, move the jumper from terminals to terminals 4-12 and change the K1-9 wire connection from terminal A2 of of the motor contactor to terminal 6 of the control box, as indicated below. (A) Burners RLS 50 Key to layout (A) C1 - Fan motor capacitor C2 - Pump motor capacitor CMV - Motor contactor K1 - Relay DA - LFL Control box S1 - Switch for following operations: MAN = manual AUT = automatic OFF S2 - Button for: - = power reduction + = power increaser S3 MA MB MV MP PA PO RT SM TA TB UV V1 V2 VS - OIL/GAS selector - Auxiliary terminal strip - Burner terminal strip - Fan motor - Pump motor - Air pressure switch - Oil pressure switch - Thermal overload - Servomotor - Ignition transformer - Burner ground - UV scanner - Low fire oil valve - High fire oil valve - Safety oil valve D

20 Field Wiring Diagram RLS with burner mounted Siemens LFL control D2297 (A) Field Wiring Diagram RLS 50 with burner mounted Siemens LFL control D2298 (C) RLS RLS V V 460 V 575 V F A T10 T6 T6 T4 S AWG ELECTRICAL CONNECTIONS Use flexible cables according to local Regulations. LAYOUT (A) - The RLS 28 - RLS 38 Models LAYOUT - The RLS 50 Model Fuses and wire size layout (A) -, see table (C). Wire size when not indicated: AWG18 Key to layouts (A) - H1 - Remote lock-out signal H2 - Low fire signal H3 - High signal H4 - Power on signal H5 - Permission ok IN - Burner manual stop switch PG - Low gas pressure switch PS - Remote lock-out reset MB - Burner terminal strip OCR - High-low control. If the burner is to be set up for single stage operation install jumper between terminals T6 and T8. OC HL Y11 Y12 Y10 - Operating control. - High limit - Low fire gas valve - High fire gas valve - Safety gas valve NOTES The setting of thermal overload must correspond to the motor amperage on of the burner. Model RLS 50 three-phase, leaves the factory preset for 460 V power supply. If V power supply is uùsed, change the fan motor connection from star to delta and change the setting of the thermal overload as well. The RLS burners have been type- approved for intermittent operation. This means they should compulsorily be stopped at least once every 24 hours to enable the flame safeguard to check its own efficiency at start-up. Burner halts are normally provided for automatically by the boiler load control system. If this is not the case, a time switch should be fitted in series to IN to provide for burner shut-down at least once every 24 hours. 20

21 Factory Wiring Diagram RLS with remote control panel D2416 (A) Factory Wiring Diagram RLS 50 with remote control panel D2419 LAYOUT (A) Burners RLS The flame safeguard is in remote panel. See the internal electrical systems of the remote panel in order to have the complete wiring diagram. LAYOUT Burners RLS 50 The flame safeguard is in remote panel. See the internal electrical systems of the remote panel in order to have the complete wiring diagram. Key to layout (A) - C1 - Fan motor capacitor C2 - Pump motor capacitor CMV - Motor contactor K1 - Relay DA - LFL Control box S1 - Switch for following operations: MAN = manual AUT = automatic OFF S2 - Button for: - = power reduction + = power increaser S3 - OIL/GAS selector MA - Auxiliary terminal strip MB MV MP PA PO RT SM TA TB UV V1 V2 VS - Burner terminal strip - Fan motor - Pump motor - Air pressure switch - Oil pressure switch - Thermal overload - Servomotor - Ignition transformer - Burner ground - UV scanner - Low fire oil valve - High fire oil valve - Safety oil valve 21

22 APPENDIX - Burner firing rates according to air density above sea level average barom. pressure CORRECTION FACTOR F Air temperature F ( C) ft m W.C. mbar 0 (0 C) 41 (5 C) 50 (10 C) 59 (15 C) 68 (20 C) 77 (25 C) 86 (30 C) 104 (40 F) ,087 1,073 1,061 1,050 1,037 1,025 1,013 1,000 0,988 0,977 0,964 0,942 0,919 0,897 0,875 0,852 1,068 1,054 1,042 1,031 1,018 1,007 0,995 0,982 0,971 0,959 0,946 0,925 0,902 0,881 0,859 0,837 1,049 1,035 1,024 1,013 1,000 0,989 0,977 0,965 0,954 0,942 0,930 0,909 0,886 0,866 0,844 0,822 1,031 1,017 1,006 0,995 0,983 0,972 0,960 0,948 0,937 0,926 0,914 0,893 0,871 0,851 0,829 0,808 1,013 1,000 0,989 0,978 0,966 0,955 0,944 0,932 0,921 0,910 0,898 0,878 0,856 0,836 0,815 0,794 0,996 0,983 0,972 0,962 0,950 0,939 0,928 0,916 0,906 0,895 0,883 0,863 0,842 0,822 0,801 0,781 0,980 0,967 0,956 0,946 0,934 0,923 0,913 0,901 0,891 0,880 0,868 0,849 0,828 0,808 0,788 0,768 0,948 0,936 0,926 0,916 0,904 0,894 0,884 0,872 0,862 0,852 0,841 0,822 0,801 0,783 0,763 0,743 (A) The FIRING RATE area values have been obtained considering a surrounding temperature of 68 F (20 C), and an atmospheric pressure of 398 W.C. and with the combustion head adjusted as shown on page 7. The burner may be required to operate with combustion air at a higher temperature and/or at higher altitudes. Heating of air and increase in altitude produce the same effect: the expansion of the air volume, i.e. the reduction of air density. The burner fan's delivery remains substantially the same, but the oxygen content per cubic meter and the fan's head are reduced. It is therefore important to know if the maximum output required of the burner at a given combustion chamber pressure remains within the burner's firing rate range even at different temperature and altitude conditions. Proceed as follows to check the above: W.C. 1 -Find the correction factor F in the Table (A) for the plant's air temperature and altitude. 2 -Divide the burner's delivery Q by F in order to obtain the equivalent delivery Qe: H2 H3 H1 D2617 Qe A MBTU/h Qe = Q : F (MBTU/h) 3 -In the firing rate range of the burner, Fig., indicate the work point defined by: Qe = equivalent delivery H1 = combustion chamber pressure The resulting point A must remain within the firing rate range. 4 -Plot a vertical line from Point A as shown in Figure and find the maximum pressure H2 of the firing rate. 5 -Multiply H2 by F to obtain the maximum reduced pressure H3 of the firing rate. H3 = H2 x F ( W.C.) If H3 is greater than H1, as shown in Fig., the burner delivers the output required. If H3 is lower than H1, the burner's delivery must be reduced. A reduction in delivery is accompanied by a reduction of the pressure in the combustion chamber: Qr = reduced delivery H1r = reduced pressure H1r = H1 x ( Qr ) 2 Q Example, a 5% delivery reduction: Qr = Q x 0.95 H1r = H1 x (0.95) 2 Steps 2-5 must now be repeated using the new Qr and H1r values. Important: the combustion head must be adjusted in respect to the equivalent delivery Qe. 22

23 (A) High - Low D1143 FLAME SIGNAL Min value for a good signal: 70 µa. If the value is lower, it can be due to: Worn scanner; Low current; Bad set up of the burner. In order to measure the current, use a microammeter of 100 µa c.c., connected to the scanner, with a capacitor of 100 µf - 1V c.c. at the same level of the instrument. See fig. (A). SEQUENCE OF OPERATION See fig. - (C). LFL Series 01 t1 t2 t3 t4 t optional t6 t7 t8 optional 12 4 D2921 Legend for the times t1 Pre-purge time with air damper open t2 Safety time t3 Pre-ignition time, short (ignition transformer on terminal 16) t4 Interval between start of t2 and release of valve at terminal 19 t5 Interval between end of t4 and release of load controller or valve at terminal 20 t5 Running time of air damper into OPEN position t6 Running time of air damper into low-flame position (MIN) t7 Permissible after-burn time t8 Interval until OPEN command for the air damper is given FIRING FAILURE If the burner does not fire, it locks out within 2.5 seconds from opening the pilot valve and then within 5 seconds from opening the main valves. BURNER FLAME GOES OUT DURING OPERA- TION If the flame should accidentally go out during operation, the burner will lock out within 1s. 23

24 Control program under fault conditions and lock-out indication In case of any disturbance, the sequence mechanism stops and with it the lock-out indicator. The symbol above the reading mark of the indicator gives the type of disturbance: No start, e.g. because one contact is not closed. Lock-out during or after control program sequence due to extraneous light (e.g. non-extinguished flames, leaking fuel valves, defects in the flame supervision circuit, etc.). Interruption of startup sequence, because the OPEN signal has not been delivered to terminal 8 by cam 1 (gas) or cam 4 (oil). Terminals 6, 7 and 14 remain under voltage until the fault has been corrected! P Lockout, because there is no air pressure indication at the beginning of air pressure control. Every air pressure failure after this moment in time leads to lock-out, too! Lock-out due to a fault in the flame supervision circuit. Interruption of startup sequence, because the position signal for the low-flame position has not been delivered to terminal 8 by cam 3 (gas) or cam 5 (oil). Terminals 6, 7 and 14 remain under voltage until the fault has been corrected! 1 Lock-out, because no flame signal is present after completion of the (1st) safety time. 2 Lock-out, because no flame signal has been received on completion of the 2nd safety time (flame signal of the main flame with interrupted pilot burners). Lock-out, because the flame signal has been lost during burner operation. If lock-out occurs at any other moment in time between the start and the pre-ignition wich is not marked by a symbol, this is usually caused by a premature, i.e. faulty flame signal, e.g. caused by a self-igniting UV tube. 24

25 BURNER START UP REPORT Model number: Project name: Installing contractor: Serial number: Start-up date: Phone number: GAS OPERATION Gas Supply Pressure: Main Power Supply: Control Power Supply: Burner Firing Rate: Manifold Pressure: Pilot Flame Signal: Low Fire Flame Signal: High Fire Flame Signal: CO 2 : Low Fire O 2 : Low Fire CO: Low Fire NO X : Low Fire Net Stack Temp - Low Fire: Comb. Efficiency - Low Fire: Overfire Draft: High Fire High Fire High Fire High Fire High Fire: High Fire: OIL OPERATION Oil supply pressure: Oil suction pressure: Control Power Supply: Burner Firing Rate: Low Fire Flame Signal: High Fire Flame Signal: Low Fire Nozzle Size: High Fire Nozzle Size: CO 2 : Low Fire O 2 : Low Fire CO: Low Fire NO X : Low Fire Net Stack Temp - Low Fire: Comb. Efficiency - Low Fire: Overfire Draft: Smoke number: High Fire High Fire High Fire High Fire High Fire: High Fire: CONTROL SETTINGS Operating Setpoint: High Limit Setpoint: Low Gas Pressure: High Gas Pressure: Low Oil Pressure: High Oil Pressure: Flame Safeguard Model Number: Modulating Signal Type: NOTES 25

26

27

28 35 Pond Park Road Hingham, Massachusetts, U.S.A RIELLO Meadowpine Blvd. Mississauga, Ontario, Canada L5N 6H6

RS 28/1-38/1 On - Off Operation

RS 28/1-38/1 On - Off Operation Installation, use and maintenance instructions Gas Burners RS 28/1-38/1 On - Off Operation C6505054 CONTENTS TECHNICAL DATA.............................. page 3 Burner models.......................................

More information

RS 70/M - 100/M - 130/M Low-High-Low or Modulating Operation

RS 70/M - 100/M - 130/M Low-High-Low or Modulating Operation Installation, use and maintenance instructions Gas Burners RS 70/M - 100/M - 130/M Low-High-Low or Modulating Operation C6505056-2915766 (0) CONTENTS TECHNICAL DATA.............................. page 3

More information

RS 45/M LN Low-High-Low or Modulating Operation

RS 45/M LN Low-High-Low or Modulating Operation Installation, use and maintenance instructions Gas Burners RS 45/M LN Low-High-Low or Modulating Operation C6505071-2915847 (2) CONTENTS TECHNICAL DATA...............................page 3 Burner models.......................................

More information

Dual fuel Gas-Oil/Gas burner

Dual fuel Gas-Oil/Gas burner Installation, use and maintenance instructions Dual fuel Gas-Oil/Gas burner MODEL GI/EMME 400 TYPE 496 T80 291 (6) TECHNICAL FEATURES Thermal power 116/232 465 kw - 100.000/200.000 400.000 kcal/h Fuels

More information

Installation, use and maintenance instructions. Gas burner (5)

Installation, use and maintenance instructions. Gas burner (5) Installation, use and maintenance instructions Gas burner MODEL GAS 4 TYPE 516 T80 291 (5) TECHNICAL FEATURES Thermal output 180-470 kw 154.800-404.200 kcal/h Fuel Natural gas Pci 8-10 kwh/m 3 = 7000-8600

More information

Propane Conversion Kit Instruction

Propane Conversion Kit Instruction Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates Logamax plus GB62-80 kw 270,000 btu/hr Logamax plus GB62-00 kw 35,000 btu/hr This kit and instructions are for converting the

More information

Forced draught gas burner

Forced draught gas burner Installation, use and maintenance instructions GB Forced draught gas burner Two stage operation CODE MODEL TYPE 3752282 GAS 4/2 522 T80 291 (4) - 07/2015 Declaration of conformity in accordance with ISO

More information

Forced draught gas burner

Forced draught gas burner Installation, use and maintenance instructions Forced draught gas burner Code Model Type 3752182 GAS 3/2 521T80 291 (4) - 05/2012 DECLARATION Declaration of conformity in accordance with ISO / IEC 17050-1

More information

Propane Conversion Kit Instructions

Propane Conversion Kit Instructions 604 8 0/ US/CA For heating engineers Propane Conversion Kit Instructions Logano G4 X gas-fired boiler This conversion kit and the accompanying instructions are for conversion of G4 X gas-fired boilers

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS 1NP0680 - PROPANE CONVERSION FOR USE WITH MODELS: PM8, PC8, PM9, PC9, FL9M, FL9C, FC9M, FC9C This conversion kit is to be installed by a qualified service agency

More information

Instructions for High Altitude Conversion

Instructions for High Altitude Conversion 6304 38 0/ US/CA For heating engineers Instructions for High Altitude Conversion Logano G334 X gas-fired boiler This conversion kit and the accompanying instructions are for conversion of G334 X gas-fired

More information

SPECIFICATIONS ATTENTION

SPECIFICATIONS ATTENTION VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane

More information

Propane Conversion Kit Instruction

Propane Conversion Kit Instruction Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates GB142-24 84,800 btu/hr GB142-30 106,000 btu/hr GB142-45 160,900 btu/hr GB142-60 214,800 btu/hr This kit and instructions are

More information

INSTALLATION GUIDE Gas Rangetops

INSTALLATION GUIDE Gas Rangetops INSTALLATION GUIDE Gas Rangetops Contents Wolf Gas Rangetops........................... 3 Safety Instructions............................ 4 Gas Rangetop Specifications.................... 5 Gas Rangetop

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! INLET PRESS TAP WHITE-RODGERS 36E93-304 Delay-Opening Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY

More information

Gas Burners RS 190/M Low-High-Low or Modulating Operation

Gas Burners RS 190/M Low-High-Low or Modulating Operation Installation, use and maintenance instructions Gas Burners RS 190/M Low-High-Low or Modulating Operation C6505057-2915994 (6) - 05/2009 CONTENTS TECHNICAL DATA.............................. page 3 Burner

More information

Forced draught natural gas/propane burner

Forced draught natural gas/propane burner Installation, use and maintenance instructions GB Forced draught natural gas/propane burner Single stage operation CODE MODEL TYPE 3757425 G750 579T (6) - 10/2013 TABLE OF CONTENTS Installation instructions

More information

Installation, use and maintenance instructions. Gas Burners. RS 68/M LN - RS 120/M LN Low-High-Low or Modulating Operation

Installation, use and maintenance instructions. Gas Burners. RS 68/M LN - RS 120/M LN Low-High-Low or Modulating Operation Installation, use and maintenance instructions Gas Burners RS 68/M LN - RS 120/M LN Low-High-Low or Modulating Operation C6505072-2915848 (5) - 06/2011 CONTENTS TECHNICAL DATA..............................

More information

Automatic Valve Proving Control

Automatic Valve Proving Control ISO 9001 Automatic Valve Proving Control 7 696 LDU11 UL recognized FM approved Features Performs leak test of the gas shut-off valves before start-up and/or immediately after burner shut-down No inlet

More information

GM Series Dual-Block Multi-Function Gas Control Valves

GM Series Dual-Block Multi-Function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series

More information

Propane Conversion Kit Instruction

Propane Conversion Kit Instruction Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates GB42-24 84,800 btu/hr Tab. GB42-30 06,000 btu/hr GB42-45 49,000 btu/hr GB42-60 24,800 btu/hr This kit and instructions are

More information

ACCESSORY KIT INSTALLATION MANUAL

ACCESSORY KIT INSTALLATION MANUAL ACCESSORY KIT INSTALLATION MANUAL LP (PROPANE) CONVERSION KIT 1NP0366 FOR USE WITH MODELS: G8C & GF8 This conversion kit shall be installed by a qualified service agency in accordance with these instructions

More information

36H SERIES Combination Gas Valve

36H SERIES Combination Gas Valve FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION The 36H series combination gas valve is

More information

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WTE-RODGERS 36E96-314 DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL

More information

200 PSI COMPRESSORS - MODEL NUMBERS

200 PSI COMPRESSORS - MODEL NUMBERS 200 PSI COMPRESSORS - MODEL NUMBERS 380C AIR COMPRESSOR KIT PART NO. 38033 480C AIR COMPRESSOR KIT PART NO. 48043 380C 480C IMPORTANT: It is essential that you and any other operator of this product read

More information

WARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only

WARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only Natural Gas High Altitude Conversion Kit United States Installations Only Installation Instructions Light Commercial Packaged Gas Electric Units R7TQ Series 6, - 7 1/2, & 10 Ton (2,001 FT - 10,000 FT)

More information

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet) Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet) INSTALLATION INSTRUCTIONS For R7 Series Light Commercial Packaged Gas Electric Units IIMPORTANT: Please

More information

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION DUAL FUEL EXCESS AIR BURNER MODEL: 3610, 3651 Revision: 0 FEATURES Burns all fuel gases or light oils Nozzle mix design for on ratio control or excess air 350% excess air all sizes on gas or oil Turndown

More information

100C Air Compressor Kit

100C Air Compressor Kit 10010 100C Air Compressor (standard mounting bracket, CE Spec) 10014 100C Air Compressor (no leader hose or check valve, CE Spec) 10016 100C Air Compressor (with Omega Bracket, CE Spec) IMPORTANT: It is

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT ALPKT57- INSTALLATION INSTRUCTIONS PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements... Table of Contents INSTALLATION

More information

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WTE-RODGERS 36E54-214 DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

Conversion instructions from natural gas to propane

Conversion instructions from natural gas to propane 6 720 804 895 202/0 EN-US For heating engineers Conversion instructions from natural gas to propane Room air-independent special gas-fired boiler Logano GA24 This conversion kit and the instructions are

More information

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO 420C AIR COMPRESSOR KIT PART NO. 42042 460C AIR COMPRESSOR KIT PART NO. 46043 420C 460C IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this

More information

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION

More information

INSTALLATION & MAINTENANCE MANUAL FOR RIVERSIDE HYDRONICS BG400 GAS BURNER 140,000 thru 1,400,000 Btu/h

INSTALLATION & MAINTENANCE MANUAL FOR RIVERSIDE HYDRONICS BG400 GAS BURNER 140,000 thru 1,400,000 Btu/h INSTALLATION & MAINTENANCE MANUAL FOR RIVERSIDE HYDRONICS BG400 GAS BURNER 140,000 thru 1,400,000 Btu/h CARBON MONOXIDE WARNING: CAUTION: IMPROPER COMBUSTION MAY CAUSE SERIOUS INJURY. RIVERSIDE HYDRONICS

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS PROPANE CONVERSION - INDUCED COMBUSTION FURNACES 1NP0501 FOR USE WITH 95% MODELS: TG9S, GG9S (130,000 BTU ONLY) FOR USE WITH 80% MODELS: TG(8,L)S, GG(8,L)S (130,000

More information

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WHITE-RODGERS 36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

Instruction Manual VCG-6

Instruction Manual VCG-6 Specifications Amps / Volts requirements 400 ma @ 24 VDC Propane pressure (VCG-6LP) 11 WC / 2.8 kpa Natural Gas pressure (VCG-6NG) 4.5 WC / 1.15 kpa Cu ft per hour / CO2 3-6 SCFH BTU Rating (Variable)

More information

IMPORTANT SAFETY INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock: - Do not disassemble. Do not attempt repairs or modifications. Refer to qualified service agencies for all service and repairs.

More information

444C DUAL PERFORMANCE VALUE PACK

444C DUAL PERFORMANCE VALUE PACK (Chrome) PART NO. 44432 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using this product. SAVE THIS MANUAL

More information

Two stage operation forced draught natural gas/propane burner

Two stage operation forced draught natural gas/propane burner Installation & Operating Manual Two stage operation forced draught natural gas/propane burner The following pages contain information, descriptions and diagrams for the proper installation and wiring of

More information

IPG IGNITION GAS PILOTS BACK-LOADED GAS

IPG IGNITION GAS PILOTS BACK-LOADED GAS INSTRUCTIONS IPG IGNITION GAS PILOTS BACK-LOADED GAS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components

More information

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO 97C COMPRESSOR KIT 12V PART NO. 00097 97C COMPRESSOR KIT 24V PART NO. 02497 98C COMPRESSOR KIT PART NO. 00098 97C 98C IMPORTANT: It is essential that you and any other operator of this product read and

More information

Installation Instructions

Installation Instructions LP and High Altitude LP Gas Conversion Kit For United States Installations Installation Instructions For Model Series *G6/PGF1 Furnaces, *L1/PGC1 Furnaces, and *R4/PPG1 Gas/Electric Appliances using Honeywell

More information

Model 130M Pneumatic Controller

Model 130M Pneumatic Controller Instruction MI 017-450 May 1978 Model 130M Pneumatic Controller Installation and Operation Manual Control Unit Controller Model 130M Controller is a pneumatic, shelf-mounted instrument with a separate

More information

INSTALLATION & MAINTENANCE MANUAL FOR PVI FIREPOWER BG600 GAS BURNER 1,200,000 thru 2,400,000 Btu/h

INSTALLATION & MAINTENANCE MANUAL FOR PVI FIREPOWER BG600 GAS BURNER 1,200,000 thru 2,400,000 Btu/h INSTALLATION & MAINTENANCE MANUAL FOR PVI FIREPOWER BG600 GAS BURNER 1,200,000 thru 2,400,000 Btu/h CARBON MONOXIDE WARNING: CAUTION: IMPROPER COMBUSTION MAY CAUSE SERIOUS INJURY. PVI recommends a seasonal

More information

Installation Instructions

Installation Instructions 48011HW NATURAL GAS TO PROPANE CONVERSION KIT 58HDX, 359AAV, PG9YAB, PG9YAA Installation Instructions SAFETY REQUIREMENTS Installing and servicing heating equipment can be hazardous due to gas and electrical

More information

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO 250C-IG COMPRESSOR KIT 12V PART NO. 25050 250C-IG COMPRESSOR KIT 24V PART NO. 25058 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual

More information

Single stage operation forced draught natural gas/propane burner

Single stage operation forced draught natural gas/propane burner Installation & Operating Manual Single stage operation forced draught natural gas/propane burner The following pages contain information, descriptions and diagrams for the proper installation and wiring

More information

C645A-E Pressure Switches

C645A-E Pressure Switches C645A-E Switches FEATURES PRODUCT DATA C645A,B,D,E GENERAL C645A,B with Window C645C The C645 pressure switches are safety devices used in positive-pressure or differential-pressure systems to sense gas

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 6C8-5 Combination Gas Control INSTALLATI INSTRUCTIS Operator: Save these instructions for future use FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS

More information

WARNING: Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings FOR YOUR SAFETY

WARNING: Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings FOR YOUR SAFETY Form CP-UD-GC Obsoletes I-UD-GC (Version E) Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters General and Warnings All gas conversion must be done by a qualified

More information

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS 36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS Type 36C04, 36C14 Step-Opening Combination Gas Control (24 Volt, 120 Volt & 750 mv Models) INSTALLATI INSTRUCTIS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW

More information

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Installation Instructions Issue Date August 19, 2008 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied

More information

INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1*

INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1* INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1* THIS KIT CONTAINS: AOPS7741 (NATURAL TO PROPANE CONVERSION PARTS FOR MODEL SIZE, 50) AOPS7742(NATURAL

More information

400C & 450C DUAL PERFORMANCE VALUE PACKS

400C & 450C DUAL PERFORMANCE VALUE PACKS (Chrome) PART NO. 40013 (Silver) PART NO. 45012 (Chrome) PART NO. 45013 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before

More information

Installation Instructions For Natural Gas Conversion

Installation Instructions For Natural Gas Conversion Installation Instructions For Natural Gas Conversion (Kit Part No. 1175405) This kit is designed to convert PGX4 and PX4 Two -Stage Gas units for use with Natural Gas. Table 1 Heating Value at Altitude

More information

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Installation Instructions Issue Date March 13, 2013 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied

More information

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO 400H HARDMOUNT AIR COMPRESSOR KIT PART NO. 40042 450H HARDMOUNT AIR COMPRESSOR KIT PART NO. 45042 400H 450H IMPORTANT: It is essential that you and any other operator of this product read and understand

More information

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM-20/25 GM-40/45 Issue Date 1298 UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function

More information

RC 195 Receiver-Controller

RC 195 Receiver-Controller Document No. 129-082 RC 195 Receiver-Controller Product Description The POWERS RC 195 Receiver-Controller is a pneumatic instrument that receives one, two or three pneumatic inputs. It produces a pneumatic

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS HIGH ALTITUDE APPLICATION CONVERSION INSTRUCTION HIGH EFFICIENCY GAS FURNACES 1PS0306 / 1PS0307 / 1PS0308 / 1PS0309 / 1PS0901 / 1PS0902 / 1PS0903 FOR USE WITH MODELS:

More information

INSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles

INSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles INSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles MODELS MLS TYG48C ML-769368-Z1 TYG60C ML-766505-Z www.wolfrange.com TYG48C ITW Food Equipment Group, LLC An Illinois Tool Works Company 3600 North

More information

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1. 2 GALLON TWIN STACK AIR COMPRESSOR Model: 9526 DO NOT RETURN TO STORE. Please CALL 800-348-5004 for parts and service. CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or

More information

Valve Proving System VDK 200 A S06*

Valve Proving System VDK 200 A S06* Valve Proving System VDK 200 A S06* Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter

More information

Gas Check. Short testing time, with automatic start-up if no leakage was detected from previous operation.

Gas Check. Short testing time, with automatic start-up if no leakage was detected from previous operation. Quality Products at Competitive Prices Gas Check Automatic testing of the down-stream installation to check that all valves are closed and that pipework and fittings are gas tight before each system start-up.

More information

The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction.

The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction. ACCESSORY KIT INSTALLATION INSTRUCTIONS HIGH ALTITUDE APPLICATION CONVERSION MID-EFFICIENCY SINGLE-STAGE INDUCED COMBUSTION FURNACES MODELS: P*HU/G8T-UH/L8T-UH/FL8 UPFLOW / HORIZONTAL P*DN/G8T-DN/L8T-DN

More information

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS Installation Instructions For Model Series *G7/*GC2 Furnaces and Appliances Using Honeywell Gas Valves. BEFORE THE CONVERSION

More information

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GS-20/25 GS-40/45 Issue Date 1298 GS-20/25 and GS-40/45 Series Single-block Multi-function Gas

More information

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO 250C-IG COMPRESSOR KIT 12V PART NO. 25050 250C-IG COMPRESSOR KIT 24V PART NO. 25058 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual

More information

O.K. Safety first CDN USA. Table of Contents. Approvals. Attention IFGC CSA UL ANSI NFPA

O.K. Safety first CDN USA. Table of Contents. Approvals. Attention IFGC CSA UL ANSI NFPA S06 & S02 Valve Proving System Installation Instructions USA CDN Table of Contents Table of Contents... Page 1 Approvals... Page 1 Attention... Page 1 Specification... Page 2 Mounting.... Page 3 Wiring...

More information

Valve Proving System VDK 200 A S02

Valve Proving System VDK 200 A S02 Valve Proving System VDK 200 A S02 Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter

More information

V8200A,C,H,M and VR8200A,C,H,M Continuous Pilot Combination Gas Controls

V8200A,C,H,M and VR8200A,C,H,M Continuous Pilot Combination Gas Controls V800A,C,H,M and VR800A,C,H,M Continuous Pilot Combination Gas Controls APPLICATION These continuous pilot combination gas controls are used in gas-fired appliances up to 00 cfh capacity of natural gas.

More information

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302 SL 40-399 G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302 If converting from Propane to Natural Gas, order the Natural Gas Conversion Parts Kit (IBC Part # P-303) from your authorized IBC Distributor.

More information

LNVx Gas Conversion Kit Instructions

LNVx Gas Conversion Kit Instructions TB134 Issue 1.0 Nov 2018 Applies to models: LNVx LNVx Gas Conversion Kit Instructions +44 (0) 1460 53535 info@powrmatic.co.uk www.powrmatic.co.uk General Information Heater conversion between gases will

More information

/2004 US/CA

/2004 US/CA 630 9765 0/004 US/CA For the contractor Propane Conversion Kit Instructions Sealed Combustion Gas Boiler Logano GA44 This kit and instructions are for converting the GA44 model boilers from Natural Gas

More information

INSTALLATION MANUAL TDR 8 P GAS FIRED ROTISSERIE OVEN

INSTALLATION MANUAL TDR 8 P GAS FIRED ROTISSERIE OVEN INSTALLATION MANUAL MODELS TDR 8 P GAS FIRED ROTISSERIE OVEN Programmable controls TDR 8 P Gas types: Natural Gas G20/25 Propane G31 (Butane G30) Model TDR 8 P Gas - NOTICE - This manual is prepared for

More information

VR8205S,T Direct Ignition Combination Gas Controls

VR8205S,T Direct Ignition Combination Gas Controls VR805S,T Direct Ignition Combination Gas Controls INSTALLATION INSTRUCTIONS APPLICATION TheVR805S,T Direct Ignition Combination Gas Controls are used in gas-fired appliances with up to 70 ft 3 /hr capacity

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS Type 36C67 Combination (24 Volt Models) INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING

More information

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289 3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for

More information

Dual Solenoid Gas Valve Installation

Dual Solenoid Gas Valve Installation Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing or servicing FLYNN Gas Products. Carefully follow all instructions in this bulletin and all instructions

More information

200 PSI FAST-FILL AIR SOURCE KIT

200 PSI FAST-FILL AIR SOURCE KIT 200 PSI FAST-FILL AIR SOURCE KIT 55% Duty Compressor on 2.0 Gallon Air Tank PART NO. 20007 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of

More information

Forced draught gas burners Quemadores de gas Queimadores a gás

Forced draught gas burners Quemadores de gas Queimadores a gás Installation, use and maintenance instructions Instrucciones de Instalación, Funcionamiento y Mantenimiento Instruções de Instalação, Funcionamento e Manutenção GB E P Forced draught gas burners Quemadores

More information

Pressure Dump Valve Service Kit for Series 2300 Units

Pressure Dump Valve Service Kit for Series 2300 Units Instruction Sheet Pressure Dump Valve Service Kit for Series 00 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00 applicator tanks when the unit

More information

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock or Electrocution: MODEL NUMBER: 20008 200 PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank IMPORTANT: It is

More information

TANDEM MODULATOR FOR OUTLET GAS FLOW: STEPPED (836 TANDEM) - CONTINUOUS (837 TANDEM) SERVO-CONTROLLED PRESSURE REGULATOR

TANDEM MODULATOR FOR OUTLET GAS FLOW: STEPPED (836 TANDEM) - CONTINUOUS (837 TANDEM) SERVO-CONTROLLED PRESSURE REGULATOR SIT Group 836-837 TANDEM MULTIFUNCTIONAL GAS CONTROL MODULATOR FOR OUTLET GAS FLOW: STEPPED (836 TANDEM) - CONTINUOUS (837 TANDEM) SERVO-CONTROLLED PRESSURE REGULATOR ALL ADJUSTMENTS ACCESSIBLE FROM ABOVE

More information

Natural Gas to L.P. Gas Conversion Kit

Natural Gas to L.P. Gas Conversion Kit Natural Gas to L.P. Gas Conversion Kit For Bosch 80% AFUE Gas Furnace, BGS80 Model Installation Instructions 3124627 2 Natural Gas to L.P. Gas Conversion Kit Installation Instructions Data subject to change

More information

Budget Range Operators Handbook

Budget Range Operators Handbook Budget Range Operators Handbook BAMBI AIR COMPRESSORS LTD 152 Thimble Mill Lane Heartlands Birmingham B7 5HT United Kingdom Tel: 0121 322 2299 Fax: 0121 322 2297 Email: sales@bambi-air.co.uk www.bambi-air.co.uk

More information

G96 Series BASOTROL Dual Operator Valve

G96 Series BASOTROL Dual Operator Valve Installation Instructions 9. Issue Date February 22, 2013 G96 Series BASOTROL Dual Operator Valve Applications The G96 valves are combination, dual operator, automatic valves available with or without

More information

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE MODEL NUMBER: M20005 AIR SOURCE KIT 30% Duty Compressor on 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE USER MANUAL IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock

More information

WARNING: FOR OUTDOOR USE ONLY

WARNING: FOR OUTDOOR USE ONLY Certified to CSA International 4.96 US For Outdoor Gas Fireplaces A HIGHER STANDARD IN QUALITY AND APPEARANCE SAFE AND BEAUTIFUL OUTDOOR LARGO FIRE PIT FOR PROPANE AND *NATURAL GAS OWNER S MANUAL WARNING:

More information

SL G3. Warning

SL G3. Warning Important: If converting from Propane to Natural Gas - order the Natural Gas Conversion Parts Kit (IBC Part # P-307) from your authorized IBC Distributor. Use the Propane Gas conversion parts kit if the

More information

installation instructions

installation instructions installation instructions GAS CONVERSION KIT PROPANE-TO-NATURAL P/N 315572-71201 4GAD 6GAD Cancels: IIK 4G-50-4 IIK 4G-50-5 7/15/91 NOTE: Read the entire instructions before starting the installation.

More information

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235) P/N 126905-01 Rev. B 11/2016 INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235) For All Single, Dual and Triple Burner Natural and Propane/LP Gas Logs P126905-01 For

More information

200 PSI HIGH-FLOW AIR SOURCE KIT

200 PSI HIGH-FLOW AIR SOURCE KIT 200 PSI HIGH-FLOW AIR SOURCE KIT 50% Duty Compressor on 2.0 Gallon Air Tank PART NO. 20008 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CTROL COULD CAUSE PERSAL INJURY AND/OR PROPERTY DAMAGE.

More information

VERTICAL AIR COMPRESSORS

VERTICAL AIR COMPRESSORS VERTICAL AIR COMPRESSORS MODEL NO: VE15C150, VE18C150, VE25C150 PART NO: 2226010, 2226020, 2226025 OPERATION & MAINTENANCE INSTRUCTIONS LS0715 INTRODUCTION Thank you for purchasing this CLARKE Vertical

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW, DOWNFLOW, UPFLOW/HORIZONTAL & HORIZONTAL ONLY INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this

More information

Natural Gas to L.P. Gas Conversion Kit

Natural Gas to L.P. Gas Conversion Kit Natural Gas to L.P. Gas Conversion Kit For Bosch 96% AFUE Gas Furnace, BGH96 Model Installation Instructions 3124627 2 Natural Gas to L.P. Gas Conversion Kit Installation Instructions Data subject to change

More information