1 SIZING OF WATER PIPING SYSTEM (This appendix is informative and is not part of the code.) SECTION AP101 GENERAL AP101.1 Scope. AP This appendix outlines two procedures for sizing a water piping system (see Sections AP103.3 and AP201.1). The design procedures are based on the minimum static pressure available from the supply source, the head charges in the system caused by friction and elevation, and the rates of flow necessary for operation of various fixtures. AP Because of the variable conditions encountered in hydraulic design, it is impractical to specify definite and detailed rules for sizing of the water piping system. Accordingly, other sizing or design methods conforming to good engineering practice standards are acceptable alternatives to those presented herein. SECTION AP102 INFORMATION REQUIRED AP102.1 Preliminary. Obtain the necessary information regarding the minimum daily static service pressure in the area where the building is to be located. If the building supply is to be metered, obtain information regarding friction loss relative to the rate of flow for meters in the range of sizes likely to be used. Friction loss data can be obtained from most manufacturers of water meters. AP102.2 Demand load. AP Estimate the supply demand of the building main and the principal branches and risers of the system by totaling the corresponding demand from the applicable part of Table AP103.3(3). AP Estimate continuous supply demands in gallons per minute (L/m) for lawn sprinklers, air conditioners, etc., and add the sum to the total demand for fixtures. The result is the estimated supply demand for the building supply. SECTION AP103 SELECTION OF PIPE SIZE AP103.1 General. Decide from Table P what is the desirable minimum residual pressure that should be maintained at the highest fixture in the supply system. If the highest group of fixtures contains flush valves, the pressure for the group should not be less than 15 pounds per square inch (psi) (103.4 kpa) flowing. For flush tank supplies, the available pressure should not be less than 8 psi (55.2 kpa) flowing, except blowout action fixtures must not be less than 25 psi (172.4 kpa) flowing. AP103.2 Pipe sizing. AP Pipe sizes can be selected according to the following procedure or by other design methods conforming to acceptable engineering practice and approved by the administrative authority. The sizes selected must not be less than the minimum required by this code. AP Water pipe sizing procedures are based on a system of pressure requirements and losses, the sum of which must not exceed the minimum pressure available at the supply source. These pressures are as follows: 1. Pressure required at fixture to produce required flow. See Sections P of this code and Section of the International Plumbing Code. 2. Static pressure loss or gain (due to head) is computed at psi per foot (9.8 kpa/m) of elevation change. Example: Assume that the highest fixture supply outlet is 20 feet (6096 mm) above or below the supply source. This produces a static pressure differential of 8.66 psi (59.8 kpa) loss [20 feet by psi/foot (2096 mm by 9.8 kpa/m)]. 3. Loss through water meter. The friction or pressure loss can be obtained from meter manufacturers. 4. Loss through taps in water main. 5. Losses through special devices such as filters, softeners, backflow prevention devices and pressure regulators. These values must be obtained from the manufacturers. 6. Loss through valves and fittings. Losses for these items are calculated by converting to equivalent length of piping and adding to the total pipe length. 7. Loss caused by pipe friction can be calculated when the pipe size, the pipe length and the flow through the pipe are known. With these three items, the friction loss can be determined. For piping flow charts not included, use manufacturers tables and velocity recommendations. Note: For all examples, the following metric conversions are applicable: 1 cubic foot per minute = L/s 1 square foot = m 2 1 degree = rad 1 pound per square inch = kpa 1 inch = 25.4 mm 1 foot = mm 1 gallon per minute = L/m 2009 VIRGINIA RESIDENTIAL CODE P-1

2 AP103.3 Segmented loss method. The size of water service mains, branch mains and risers by the segmented loss method, must be determined according to water supply demand [gpm (L/m)], available water pressure [psi (kpa)] and friction loss caused by the water meter and developed length of pipe [feet (m)], including equivalent length of fittings. This design procedure is based on the following parameters: The calculated friction loss through each length of the pipe. A system of pressure losses, the sum of which must not exceed the minimum pressure available at the street main or other source of supply. Pipe sizing based on estimated peak demand, total pressure losses caused by difference in elevation, equipment, developed length and pressure required at the most remote fixture, loss through taps in water main, losses through fittings, filters, backflow prevention devices, valves and pipe friction. Because of the variable conditions encountered in hydraulic design, it is impractical to specify definite and detailed rules for sizing of the water piping system. Current sizing methods do not address the differences in the probability of use and flow characteristics of fixtures between types of occupancies. Creating an exact model of predicting the demand for a building is impossible and final studies assessing the impact of water conservation on demand are not yet complete. The following steps are necessary for the segmented loss method. 1. Preliminary. Obtain the necessary information regarding the minimum daily static service pressure in the area where the building is to be located. If the building supply is to be metered, obtain information regarding friction loss relative to the rate of flow for meters in the range of sizes to be used. Friction loss data can be obtained from manufacturers of water meters. Enough pressure must be available to overcome all system losses caused by friction and elevation so that plumbing fixtures operate properly. Section of the International Plumbing Code requires that the water distribution system be designed for the minimum pressure available taking into consideration pressure fluctuations. The lowest pressure must be selected to guarantee a continuous, adequate supply of water. The lowest pressure in the public main usually occurs in the summer because of lawn sprinkling and supplying water for air-conditioning cooling towers. Future demands placed on the public main as a result of large growth or expansion should also be considered. The available pressure will decrease as additional loads are placed on the public system. 2. Demand load. Estimate the supply demand of the building main and the principal branches and risers of the system by totaling the corresponding demand from the applicable part of Table AP103.3(3). When estimating peak demand, sizing methods typically use water supply fixture units (w.s.f.u.) [see Table AP103.3(2)]. This numerical factor measures the load-producing effect of a single plumbing fixture of a given kind. The use of fixture units can be applied to a single basic probability curve (or table), found in the various sizing methods [Table AP103.3(3)]. The fixture units are then converted into gallons per minute (L/m) flow rate for estimating demand Estimate continuous supply demand in gallons per minute (L/m) for lawn sprinklers, air conditioners, etc., and add the sum to the total demand for fixtures. The result is the estimated supply demand for the building supply. Fixture units cannot be applied to constant-use fixtures such as hose bibbs, lawn sprinklers and air conditioners. These types of fixtures must be assigned the gallon per minute (L/m) value. 3. Selection of pipe size. This water pipe sizing procedure is based on a system of pressure requirements and losses, the sum of which must not exceed the minimum pressure available at the supply source. These pressures are as follows: 3.1. Pressure required at the fixture to produce required flow. See Section P of this code and Section of the International Plumbing Code Static pressure loss or gain (because of head) is computed at psi per foot (9.8 kpa/m) of elevation change Loss through a water meter. The friction or pressure loss can be obtained from the manufacturer Loss through taps in water main [see Table AP103.3(4)] Losses through special devices such as filters, softeners, backflow prevention devices and pressure regulators. These values must be obtained from the manufacturers Loss through valves and fittings [see Tables AP103.3(5) and AP103.3(6)]. Losses for these items are calculated by converting to equivalent length of piping and adding to the total pipe length Loss caused by pipe friction can be calculated when the pipe size, the pipe length and the flow through the pipe are known. With these three items, the friction loss can be determined using Figures AP103.3(2) through AP103.3(7). When using charts, use pipe inside diameters. For piping flow charts not included, use manufacturers tables and velocity recommendations. Before attempting to size any water supply system, it is necessary to gather preliminary information which includes available pressure, piping material, select design velocity, elevation differences and developed length to most remote fixture. The water supply system is divided into sections at major changes in elevation or where branches lead to fixture groups. The peak demand must be determined in each part of the hot and cold water supply system which includes the corresponding water supply fixture unit and conversion to gallons per minute (L/m) flow rate to be expected P VIRGINIA RESIDENTIAL CODE

3 through each section. Sizing methods require determination of the most hydraulically remote fixture to compute the pressure loss caused by pipe and fittings. The hydraulically remote fixture represents the most downstream fixture along the circuit of piping requiring the most available pressure to operate properly. Consideration must be given to all pressure demands and losses, such as friction caused by pipe, fittings and equipment; elevation; and the residual pressure required by Table P The two most common and frequent complaints about water supply system operation are lack of adequate pressure and noise. Problem: What size Type L copper water pipe, service and distribution will be required to serve a two-story factory building having on each floor, back-to-back, two toilet rooms each equipped with hot and cold water? The highest fixture is 21 feet (6401 mm) above the street main, which is tapped with a 2-inch (51 mm) corporation cock at which point the minimum pressure is 55 psi (379.2 kpa). In the building basement, a 2-inch (51 mm) meter with a maximum pressure drop of 11 psi (75.8 kpa) and 3-inch (76 mm) reduced pressure principle backflow preventer with a maximum pressure drop of 9 psi (62.1 kpa) are to be installed. The system is shown by Figure AP103.3(1). To be determined are the pipe sizes for the service main and the cold and hot water distribution pipes. Solution: A tabular arrangement such as shown in Table AP103.3(1) should first be constructed. The steps to be followed are indicated by the tabular arrangement itself as they are in sequence, columns 1 through 10 and lines A through L. Step 1 Columns 1 and 2: Divide the system into sections breaking at major changes in elevation or where branches lead to fixture groups. After point B [see Figure AP103.3(1)], separate consideration will be given to the hot and cold water piping. Enter the sections to be considered in the service and cold water piping in Column 1 of the tabular arrangement. Column 1 of Table AP103.3(1) provides a line-by-line recommended tabular arrangement for use in solving pipe sizing. The objective in designing the water supply system is to ensure an adequate water supply and pressure to all fixtures and equipment. Column 2 provides the pounds per square inch (psi) to be considered separately from the minimum pressure available at the main. Losses to take into consideration are the following: the differences in elevations between the water supply source and the highest water supply outlet, meter pressure losses, the tap in main loss, special fixture devices such as water softeners and backflow prevention devices and the pressure required at the most remote fixture outlet. The difference in elevation can result in an increase or decrease in available pressure at the main. Where the water supply outlet is located above the source, this results in a loss in the available pressure and is subtracted from the pressure at the water source. Where the highest water supply outlet is located below the water supply source, there will be an increase in pressure that is added to the available pressure of the water source. Column 3: According to Table AP103.3(3), determine the gpm (L/m) of flow to be expected in each section of the system. These flows range from 28.6 to 108 gpm. Load values for fixtures must be determined as water supply fixture units and then converted to a gallon-per-minute (gpm) rating to determine peak demand. When calculating peak demands, the water supply fixture units are added and then converted to the gallon-per-minute rating. For continuous flow fixtures such as hose bibbs and lawn sprinkler systems, add the gallon-per-minute demand to the intermittent demand of fixtures. For example, a total of 120 water supply fixture units is converted to a demand of 48 gallons per minute. Two hose bibbs 5 gpm demand = 10 gpm. Total gpm rating = 48.0 gpm + 10 gpm = 58.0 gpm demand. Step 2 Line A: Enter the minimum pressure available at the main source of supply in Column 2. This is 55 psi (379.2 kpa). The local water authorities generally keep records of pressures at different times of day and year. The available pressure can also be checked from nearby buildings or from fire department hydrant checks. Line B: Determine from Table P the highest pressure required for the fixtures on the system, which is 15 psi (103.4 kpa), to operate a flushometer valve. The most remote fixture outlet is necessary to compute the pressure loss caused by pipe and fittings, and represents the most downstream fixture along the circuit of piping requiring the available pressure to operate properly as indicated by Table P Line C: Determine the pressure loss for the meter size given or assumed. The total water flow from the main through the service as determined in Step 1 will serve to aid in the meter selected. There are three common types of water meters; the pressure losses are determined by the American Water Works Association Standards for displacement type, compound type and turbine type. The maximum pressure loss of such devices takes into consideration the meter size, safe operating capacity (gpm) and maximum rates for continuous operations (gpm). Typically, equipment imparts greater pressure losses than piping. Line D: Select from Table AP103.3(4) and enter the pressure loss for the tap size given or assumed. The loss of pressure through taps and tees in pounds per square inch (psi) is based on the total gallon-per-minute flow rate and size of the tap. Line E: Determine the difference in elevation between the main and source of supply and the highest fixture on the system. Multiply this figure, expressed in feet, by 0.43 psi (2.9 kpa). Enter the resulting psi loss on Line E. The difference in elevation between the water supply source and the highest water supply outlet has a significant impact on the sizing of the water supply system. The difference in elevation usually results in a loss in the available pressure because the water supply outlet is generally located above the water supply source. The loss is caused by the pressure required to lift the 2009 VIRGINIA RESIDENTIAL CODE P-3

4 water to the outlet. The pressure loss is subtracted from the pressure at the water source. Where the highest water supply outlet is located below the water source, there will be an increase in pressure which is added to the available pressure of the water source. Lines F, G and H: The pressure losses through filters, backflow prevention devices or other special fixtures must be obtained from the manufacturer or estimated and entered on these lines. Equipment such as backflow prevention devices, check valves, water softeners, instantaneous or tankless water heaters, filters and strainers can impart a much greater pressure loss than the piping. The pressure losses can range from 8 psi to 30 psi. Step 3 Line I: The sum of the pressure requirements and losses that affect the overall system (Lines B through H) is entered on this line. Summarizing the steps, all of the system losses are subtracted from the minimum water pressure. The remainder is the pressure available for friction, defined as the energy available to push the water through the pipes to each fixture. This force can be used as an average pressure loss, as long as the pressure available for friction is not exceeded. Saving a certain amount for available water supply pressures as an area incurs growth, or because of aging of the pipe or equipment added to the system is recommended. Step 4 Line J: Subtract Line I from Line A. This gives the pressure that remains available from overcoming friction losses in the system. This figure is a guide to the pipe size that is chosen for each section, incorporating the total friction losses to the most remote outlet (measured length is called developed length). Exception: When the main is above the highest fixture, the resulting psi must be considered a pressure gain (static head gain) and omitted from the sums of Lines B through H and added to Line J. The maximum friction head loss that can be tolerated in the system during peak demand is the difference between the static pressure at the highest and most remote outlet at no-flow conditions and the minimum flow pressure required at that outlet. If the losses are within the required limits, every run of pipe will also be within the required friction head loss. Static pressure loss is at the most remote outlet in feet = loss in psi caused by elevation differences. Step 5 Column 4: Enter the length of each section from the main to the most remote outlet (at Point E). Divide the water supply system into sections breaking at major changes in elevation or where branches lead to fixture groups. Step 6 Column 5: When selecting a trial pipe size, the length from the water service or meter to the most remote fixture outlet must be measured to determine the developed length.however, in systems having a flush valve or temperature controlled shower at the topmost floors the developed length would be from the water meter to the most remote flush valve on the system. A rule of thumb is that size will become progressively smaller as the system extends farther from the main source of supply. Trial pipe size may be arrived at by the following formula: Line J: (Pressure available to overcome pipe friction) 100/equivalent length of run total developed length to most remote fixture percentage factor of 1.5 (note: a percentage factor is used only as an estimate for friction losses imposed for fittings for initial trial pipe size) = psi (average pressure drop per 100 feet of pipe). For trial pipe size see Figure AP103.3(3) (Type L copper) based on 2.77 psi and 108 gpm = 2 1 / 2 inches. To determine the equivalent length of run to the most remote outlet, the developed length is determined and added to the friction losses for fittings and valves. The developed lengths of the designated pipe sections are as follows: A - B 54 ft B - C 8 ft C - D 13 ft D - E 150 ft Total developed length = 225 ft The equivalent length of the friction loss in fittings and valves must be added to the developed length (most remote outlet). Where the size of fittings and valves is not known, the added friction loss should be approximated. A general rule that has been used is to add 50 percent of the developed length to allow for fittings and valves. For example, the equivalent length of run equals the developed length of run (225 ft 1.5 = 338 ft). The total equivalent length of run for determining a trial pipe size is 338 feet. Example: 9.36 (pressure available to overcome pipe friction) 100/ 338 (equivalent length of run = ) = 2.77 psi (average pressure drop per 100 feet of pipe). Step 7 Column 6: Select from Table AP103.3(6) the equivalent lengths for the trial pipe size of fittings and valves on each pipe section. Enter the sum for each section in Column 6. (The number of fittings to be used in this example must be an estimate.) The equivalent length of piping is the developed length plus the equivalent lengths of pipe corresponding to friction head losses for fittings and valves. Where the size of fittings and valves is not known, the added friction head losses must be approximated. An estimate for this example is found in Table AP.1. P VIRGINIA RESIDENTIAL CODE

5 Step 8 Column 7: Add the figures from Column 4 and Column 6, and enter in Column 7. Express the sum in hundreds of feet. Step 9 Column 8: Select from Figure AP103.3(3) the friction loss per 100 feet ( mm) of pipe for the gallon-per-minute flow in a section (Column 3) and trial pipe size (Column 5). Maximum friction head loss per 100 feet is determined on the basis of total pressure available for friction head loss and the longest equivalent length of run. The selection is based on the gallon-per-minute demand, the uniform friction head loss, and the maximum design velocity. Where the size indicated by the hydraulic table indicates a velocity in excess of the selected velocity, a size must be selected which produces the required velocity. Step 10 Column 9: Multiply the figures in Columns 7 and 8 for each section and enter in Column 9. Total friction loss is determined by multiplying the friction loss per 100 feet ( mm) for each pipe section in the total developed length by the pressure loss in fittings expressed as equivalent length in feet. Note: Section C-F should be considered in the total pipe friction losses only if greater loss occurs in Section C-F than in pipe Section D-E. Section C-F is not considered in the total developed length. Total friction loss in equivalent length is determined in Table AP.2. Step 11 Line K: Enter the sum of the values in Column 9. The value is the total friction loss in equivalent length for each designated pipe section. Step 12 Line L: Subtract Line J from Line K and enter in Column 10. The result should always be a positive or plus figure. If it is not, repeat the operation using Columns 5, 6, 8 and 9 until a balance or near balance is obtained. If the difference between Lines J and K is a high positive number, it is an indication that the pipe sizes are too large and should be reduced, thus saving materials. In such a case, the operations using Columns 5, 6, 8 and 9 should be repeated. The total friction losses are determined and subtracted from the pressure available to overcome pipe friction for trial pipe size. This number is critical because it provides a guide to whether the pipe size selected is too large and the process should be repeated to obtain an economically designed system. Answer: The final figures entered in Column 5 become the design pipe size for the respective sections. Repeating this operation a second time using the same sketch but considering the demand for hot water, it is possible to size the hot water distribution piping. This has been worked up as a part of the overall problem in the tabular arrangement used for sizing the service and water distribution piping. Note that consideration must be given to the pressure losses from the street main to the water heater (Section A-B) in determining the hot water pipe sizes. COLD WATER PIPE SECTION A-B FITTINGS/VALVES PRESSURE LOSS EXPRESSED AS EQUIVALENT LENGTH OF TUBE (feet) TABLE AP.1 HOT WATER PIPE SECTION FITTINGS/VALVES PRESSURE LOSS EXPRESSED AS EQUIVALENT OF TUBE (feet) / 2 Gate valves 3 A-B / 2 Gate valves / 2 Side branch tee / 2 Side branch tee 12 B-C / 2 Straight run tee 0.5 B-C 1-2 Straight run tee degree ell 0.5 C-F / 2 Side branch tee 12 C-F / 2 Side branch tee 7 C-D / 2 90-degree ell 7 C-D 1-1 / 2 90-degree ell 4 D-E / 2 Side branch tee 12 D-E / 2 Side branch tee 7 PIPE SECTIONS TABLE AP.2 FRICTION LOSS EQUIVALENT LENGTH (feet) Cold Water Hot Water A-B = = 2.21 B-C = = 0.22 C-D = = 0.54 D-E = = 5.02 Total pipe friction losses (Line K) VIRGINIA RESIDENTIAL CODE P-5

6 For SI: 1 foot = mm, 1 gpm = L/m. FIGURE AP103.3(1) EXAMPLE-SIZING P VIRGINIA RESIDENTIAL CODE

7 TABLE AP103.3(1) RECOMMENDED TABULAR ARRANGEMENT FOR USE IN SOLVING PIPE SIZING PROBLEMS COLUMN Line Description Lb per square inch (psi) Gal. per min through section Length of section (feet) Trial pipe size (inches) Equivalent length of fittings and valves (feet) Total equivalent length col. 4 and col. 6 (100 feet) Friction loss per 100 feet of trial size pipe (psi) Friction loss in equivalent length col. 8 x col. 7 (psi) Excess pressure over friction losses (psi) A B C D E F G H I J Service and cold water distribution piping a Minimum pressure available at main Highest pressure required at a fixture (Table P2903.1) Meter loss 2 meter Tapinmainloss2 tap [Table AP103.3(4)] Static head loss 21 ft 0.43 psi/ft Special fixture loss backflow preventer Special fixture lossfilter Special fixture lossother Total overall losses and requirements (Sum of Lines B through H) Pressure available to overcome pipe friction (Line A minus Line I) DESIGNATION Pipe section (from diagram) Cold water Distribution piping FU AB BC CD CF b DE b / / / / / K L Total pipe friction losses (cold) Difference (Line J minus Line K) Pipe section (from diagram) Diagram Hot water Distribution Piping A B B C C D C F b D E b / / / / K L Total pipe friction losses (hot) Difference (Line J minus Line K) For SI: 1 inch = 25.4 mm, 1 foot = mm, 1 psi = kpa, 1 gpm = L/m. a. To be considered as pressure gain for fixtures below main (to consider separately, omit from I and add to J ). b. To consider separately, in K use C-F only if greater loss than above VIRGINIA RESIDENTIAL CODE P-7

8 TABLE AP103.3(2) LOAD VALUES ASSIGNED TO FIXTURES a FIXTURE OCCUPANCY TYPE OF SUPPLY CONTROL LOAD VALUES, IN WATER SUPPLY FIXTURE UNITS (wsfu) Cold Hot Total Bathroom group Private Flush tank Bathroom group Private Flush valve Bathtub Private Faucet Bathtub Public Faucet Bidet Private Faucet Combination fixture Private Faucet Dishwashing machine Private Automatic Drinking fountain Offices, etc. 3 / 8 valve Kitchen sink Private Faucet Kitchen sink Hotel, restaurant Faucet Laundry trays (1 to 3) Private Faucet Lavatory Private Faucet Lavatory Public Faucet Service sink Offices, etc. Faucet Shower head Public Mixing valve Shower head Private Mixing valve Urinal Public 1 flush valve Urinal Public 3 / 4 flush valve Urinal Public Flush tank Washing machine (8 lb) Private Automatic Washing machine (8 lb) Public Automatic Washing machine (15 lb) Public Automatic Water closet Private Flush valve Water closet Private Flush tank Water closet Public Flush valve Water closet Public Flush tank Water closet Public or private Flushometer tank For SI: 1 inch = 25.4 mm, 1 pound = kg. a. For fixtures not listed, loads should be assumed by comparing the fixture to one listed using water in similar quantities and at similar rates. The assigned loads for fixtures with both hot and cold water supplies are given for separate hot and cold water loads and for total load. The separate hot and cold water loads being three-fourths of the total load for the fixture in each case. P VIRGINIA RESIDENTIAL CODE

9 TABLE AP103.3(3) TABLE FOR ESTIMATING DEMAND SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKS SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH VALVES Load Demand Load Demand (Water supply fixture units) (Gallons per minute) (Cubic feet per minute) (Water supply fixture units) (Gallons per minute) (Cubic feet per minute) (continued) 2009 VIRGINIA RESIDENTIAL CODE P-9

10 TABLE AP103.3(3)continued TABLE FOR ESTIMATING DEMAND SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKS SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH VALVES Load Demand Load Demand (Water supply fixture units) (Gallons per minute) (Cubic feet per minute) (Water supply fixture units) (Gallons per minute) (Cubic feet per minute) , , , , , , , , , , , , , , , , , , For SI: TABLE AP103.3(4) LOSS OF PRESSURE THROUGH TAPS AND TEES IN POUNDS PER SQUARE INCH (psi) SIZE OF TAP OR TEE (inches) GALLONS PER MINUTE 5 / 8 3 / / / inch = 25.4 mm, 1 pound per square inch = kpa, 1 gallon per minute = L/m. P VIRGINIA RESIDENTIAL CODE

11 TABLE AP103.3(5) ALLOWANCE IN EQUIVALENT LENGTHS OF PIPE FOR FRICTION LOSS IN VALVES AND THREADED FITTINGS (feet) PIPE SIZE (inches) FITTING OR VALVE 1 / 2 3 / / / / degree elbow degree elbow Tee, run Tee, branch Gate valve Balancing valve Plug-type cock Check valve, swing Globe valve Angle valve For SI: 1 inch = 25.4 mm, 1 foot = mm, 1 degree = rad. NOMINAL OR STANDARD SIZE (inches) TABLE AP103.3(6) PRESSURE LOSS IN FITTINGS AND VALVES EXPRESSED AS EQUIVALENT LENGTH OF TUBE a (feet) Standard EII FITTINGS 90-Degree Tee 90 Degree 45 Degree Side Branch Straight Run Coupling VALVES Ball Gate Butterfly Check 3 / / / / / / / / For SI: 1 inch = 25.4 mm, 1 foot = mm, 1 degree = rad. a. Allowances are for streamlined soldered fittings and recessed threaded fittings. For threaded fittings, double the allowances shown in the table. The equivalent lengths presented above are based on a C factor of 150 in the Hazen-Williams friction loss formula. The lengths shown are rounded to the nearest half-foot VIRGINIA RESIDENTIAL CODE P-11

12 Note: Fluid velocities in excess of 5 to 8 feet/second are not usually recommended. FIGURE AP103.3(2) FRICTION LOSS IN SMOOTH PIPE a (TYPE K, ASTM B 88 COPPER TUBING) For SI: 1 inch = 25.4 mm, 1 foot = mm, 1 gpm = L/m, 1 psi = kpa, 1 foot per second = m/s. a. This chart applies to smooth new copper tubing with recessed (streamline) soldered joints and to the actual sizes of types indicated on the diagram. P VIRGINIA RESIDENTIAL CODE

13 Note: Fluid velocities in excess of 5 to 8 feet/second are not usually recommended. FIGURE AP103.3(3) FRICTION LOSS IN SMOOTH PIPE a (TYPE L, ASTM B 88 COPPER TUBING) For SI: 1 inch = 25.4 mm, 1 foot = mm, 1 gpm = L/m, 1 psi = kpa, 1 foot per second = m/s. a. This chart applies to smooth new copper tubing with recessed (streamline) soldered joints and to the actual sizes of types indicated on the diagram VIRGINIA RESIDENTIAL CODE P-13

14 Note: Fluid velocities in excess of 5 to 8 feet/second are not usually recommended. FIGURE AP103.3(4) FRICTION LOSS IN SMOOTH PIPE a (TYPE M, ASTM B 88 COPPER TUBING) For SI: 1 inch = 25.4 mm, 1 foot = mm, 1 gpm = L/m, 1 psi = kpa, 1 foot per second = m/s. a. This chart applies to smooth new copper tubing with recessed (streamline) soldered joints and to the actual sizes of types indicated on the diagram. P VIRGINIA RESIDENTIAL CODE

15 FIGURE AP103.3(5) FRICTION LOSS IN FAIRLY SMOOTH PIPE a For SI: 1 inch = 25.4 mm, 1 foot = mm, 1 gpm = L/m, 1 psi = kpa, 1 foot per second = m/s. a. This chart applies to smooth new steel (fairly smooth) pipe and to actual diameters of standard-weight pipe VIRGINIA RESIDENTIAL CODE P-15

16 FIGURE AP103.3(6) FRICTION LOSS IN FAIRLY ROUGH PIPE a For SI: 1 inch = 25.4 mm, 1 foot = mm, 1 gpm = L/m, 1 psi = kpa, 1 foot per second = m/s. a. This chart applies to fairly rough pipe and to actual diameters which in general will be less than the actual diameters of the new pipe of the same kind. P VIRGINIA RESIDENTIAL CODE

17 FIGURE AP103.3(7) FRICTION LOSS IN FAIRLY ROUGH PIPE a For SI: 1 inch = 25.4 mm, 1 foot = mm, 1 gpm = L/m, 1 psi = kpa, 1 foot per second = m/s. a. This chart applies to very rough pipe and existing pipe and to their actual diameters VIRGINIA RESIDENTIAL CODE P-17

18 SECTION AP201 SELECTION OF PIPE SIZE AP201.1 Size of water-service mains, branch mains and risers. The minimum size water service pipe shall be 3 / 4 inch (19.1 mm). The size of water service mains, branch mains and risers shall be determined according to water supply demand [gpm (L/m)], available water pressure [psi (kpa)] and friction loss caused by the water meter and developed length of pipe [feet (m)], including equivalent length of fittings. The size of each water distribution system shall be determined according to the procedure outlined in this section or by other design methods conforming to acceptable engineering practice and approved by the code official: 1. Supply load in the building water-distribution system shall be determined by total load on the pipe being sized, in terms of water-supply fixture units (w.s.f.u.), as shown in Table AP103.3(2). For fixtures not listed, choose a w.s.f.u. value of a fixture with similar flow characteristics. 2. Obtain the minimum daily static service pressure [psi (kpa)] available (as determined by the local water authority) at the water meter or other source of supply at the installation location. Adjust this minimum daily static pressure [psi (kpa)] for the following conditions: 2.1. Determine the difference in elevation between the source of supply and the highest water supply outlet. Where the highest water supply outlet is located above the source of supply, deduct 0.5 psi (3.4 kpa) for each foot (0.3 m) of difference in elevation. Where the highest water supply outlet is located below the source of supply, add 0.5 psi (3.4 kpa) for each foot (0.3 m) of difference in elevation Where a water pressure reducing valve is installed in the water distribution system, the minimum daily static water pressure available is 80 percent of the minimum daily static water pressure at the source of supply or the set pressure downstream of the pressure reducing valve, whichever is smaller Deduct all pressure losses caused by special equipment such as a backflow preventer, water filter and water softener. Pressure loss data for each piece of equipment shall be obtained through the manufacturer of the device Deduct the pressure in excess of 8 psi (55 kpa) resulting from installation of the special plumbing fixture, such as temperature-controlled shower and flushometer tank water closet. Using the resulting minimum available pressure, find the corresponding pressure range in Table AP The maximum developed length for water piping is the actual length of pipe between the source of supply and the most remote fixture, including either hot (through the water heater) or cold water branches multiplied by a factor of 1.2 to compensate for pressure loss through fittings. Select the appropriate column in Table AP201.1 equal to or greater than the calculated maximum developed length. 4. To determine the size of water service pipe, meter and main distribution pipe to the building using the appropriate table, follow down the selected maximum developed length column to a fixture unit equal to or greater than the total installation demand calculated by using the combined water supply fixture unit column of Table AP Read the water service pipe and meter sizes in the first left-hand column and the main distribution pipe to the building in the second left-hand column on the same row. 5. To determine the size of each water distribution pipe, start at the most remote outlet on each branch (either hot or cold branch) and, working back toward the main distribution pipe to the building, add up the water supply fixture unit demand passing through each segment of the distribution system using the related hot or cold column of Table AP Knowing demand, the size of each segment shall be read from the second left-hand column of the same table and maximum developed length column selected in Steps 1 and 2, under the same or next smaller size meter row. In no case does the size of any branch or main need to be larger that the size of the main distribution pipe to the building established in Step 4. P VIRGINIA RESIDENTIAL CODE

19 METER AND SERVICE PIPE (inches) TABLE AP201.1 MINIMUM SIZE OF WATER METERS, MAINS AND DISTRIBUTION PIPING BASED ON WATER SUPPLY FIXTURE UNIT VALUES (w.s.f.u.) DISTRIBUTION PIPE (inches) MAXIMUM DEVELOPMENT LENGTH (feet) Pressure Range 30 to 39 psi / 4 1 / 2 a / 4 3 / / / / / / / / / / / / / METER AND SERVICE PIPE (inches) DISTRIBUTION PIPE (inches) MAXIMUM DEVELOPMENT LENGTH (feet) Pressure Range 40 to 49 psi / 4 1 / 2 a / 4 3 / / / / / / / / / / / / / (continued) 2009 VIRGINIA RESIDENTIAL CODE P-19

20 METER AND SERVICE PIPE (inches) TABLE AP201.1continued MINIMUM SIZE OF WATER METERS, MAINS AND DISTRIBUTION PIPING BASED ON WATER SUPPLY FIXTURE UNIT VALUES (w.s.f.u.) DISTRIBUTION PIPE (inches) MAXIMUM DEVELOPMENT LENGTH (feet) Pressure Range 50 to 60 psi / 4 1 / 2 a / 4 3 / / / / / / / / / / / / / METER AND SERVICE PIPE (inches) DISTRIBUTION PIPE (inches) MAXIMUM DEVELOPMENT LENGTH (feet) Pressure Range Over / 4 1 / 2 a / 4 3 / / / / / / / / / / / / / For SI: 1 inch = 25.4, 1 foot = mm. a. Minimum size for building supply is 3 / 4 -inch pipe. P VIRGINIA RESIDENTIAL CODE

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEMS CHART A-1 FRICTION LOSSES FOR DISK-TYPE WATER METERS 1-1/2"

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEMS CHART A-1 FRICTION LOSSES FOR DISK-TYPE WATER METERS 1-1/2 RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEMS Because of the variable conditions encountered, it is impractical to lay down definite detailed rules of procedure for determining the sizes of water

More information

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM CHART A 1.2 FRICTION LOSSES FOR DISK-TYPE WATER METERS 1-1/2"

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM CHART A 1.2 FRICTION LOSSES FOR DISK-TYPE WATER METERS 1-1/2 RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Because of the variable conditions encountered, it is impractical to lay down definite detailed rules of procedure for determining the sizes of water

More information

Read Only Document Not For Distribution

Read Only Document Not For Distribution Appendix B Sizing the Building Water Supply System B.1 General...229 B.2 Preliminary Information...229 B.2.1 General...229 B.2.2 Materials For System...229 B.2.3 Characteristics Of The Water Supply...229

More information

SIZING AND CAPACITIES OF GAS PIPING

SIZING AND CAPACITIES OF GAS PIPING SIZING AND CAPACITIES OF GAS PIPING A.1 General piping considerations. The first goal of determining the pipe sizing for a fuel gas piping system is to make sure that there is sufficient gas pressure at

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 14 Hydraulics Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 14 Hydraulics Revised DRIVER OPERATOR Page 1 of 14 HYDRAULICS Hydraulics applied in the dynamic fire ground environment is an art that comes with study and experience. The following describes the factors that must be mastered

More information

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS SEC Project No. 1803007-000 November 20, 2006 TABLE OF CONTENTS I. ABSTRACT...1 II. INTRODUCTION...1 III. HISTORY...2 IV. VARIABLE SPEED

More information

Tous fluid flow systems. Further details on specific piping systems

Tous fluid flow systems. Further details on specific piping systems CHAPTER 33 PIPE SIZING Pressure Drop Equations... 33.1 WATER PIPING... 33.3 Flow Rate Limitations... 33.3 Hydronic System Piping... 33.4 Service Water Piping... 33.6 STEAM PIPING... 33.9 Low-Pressure Steam

More information

Water Hammer Arrestors

Water Hammer Arrestors Water Hammer rrestors watts.com What is Water Hammer? T he noise from banging pipes is caused by shocks of high speed water flowing in the piping system when a fixture is suddenly closed. Sudden stoppage

More information

Water Hammer Arresters Standard PDI-WH 201 Revised 2006

Water Hammer Arresters Standard PDI-WH 201 Revised 2006 Water Hammer Arresters Standard PDI-WH 201 Revised 2006 Certification Sizing Placement Reference Data THE PLUMBING AND DRAINAGE INSTITUTE 800 Turnpike Street, Suite 300 North Andover, MA 01845 Phone: (800)

More information

RELIABLE PROTECTION FOR A WIDE RANGE OF RESIDENTIAL, COMMERCIAL AND INDUSTRIAL APPLICATIONS. water pressure reducing valves

RELIABLE PROTECTION FOR A WIDE RANGE OF RESIDENTIAL, COMMERCIAL AND INDUSTRIAL APPLICATIONS. water pressure reducing valves RELIABLE PROTECTION FOR A WIDE RANGE OF RESIDENTIAL, COMMERCIAL AND INDUSTRIAL APPLICATIONS water pressure reducing valves Table of Contents Product...Page How Pressure Reducing Valves Work...3 36 Series...

More information

then the work done is, if the force and the displacement are in opposite directions, then the work done is.

then the work done is, if the force and the displacement are in opposite directions, then the work done is. 1. What is the formula for work? W= x 2. What are the 8 forms of energy? 3. Write the formula for the following: Kinetic Energy Potential Energy 4. If the force and the displacement are in the same direction,

More information

Irrigation System Winterization and Pressurization Procedures

Irrigation System Winterization and Pressurization Procedures Irrigation System Winterization and Pressurization Procedures Introduction Any time that an irrigation system is filled and pressurized, or when the system is drained and water flushed from the system,

More information

pumping gases JET PUMP TECHNICAL DATA

pumping gases JET PUMP TECHNICAL DATA Section 1000 Bulletin 100 Issued 9/87 Replaces 7/84 JET PUMP TECHNICAL DATA pumping gases This technical bulletin includes general information about Penberthy Jet Pumps plus specific details for selecting

More information

Master Control Systems, Inc. Variable Speed Fire Pump Controllers

Master Control Systems, Inc. Variable Speed Fire Pump Controllers Master Control Systems, Inc. Variable Speed Fire Pump Controllers Meets NFPA 20-2013 UL/FM Listed and Approved for fire protections 1 Why Variable Speed? Huge Sprinkler System and Standpipe Cost Savings

More information

Quick Reference Technical Data

Quick Reference Technical Data Bulletin 127C 2 Quick Reference Technical Data For over 100 years, The Spencer Turbine Company has specialized in innovative solutions to air and gas handling problems. Spencer's product line includes

More information

Pre-adjustable pressure reducing valves with self-contained cartridge

Pre-adjustable pressure reducing valves with self-contained cartridge Pre-adjustable pressure reducing valves with self-contained cartridge 535..H series ACCREDITED ISO 91 FM 15 15/17 GB replaces 15/1GB Function Pressure reducing valves are devices which, when installed

More information

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13 Page 1 of 13 1. Description The Viking 2 Model G-2000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

22. Specialty Valves.

22. Specialty Valves. 22. Specialty Valves. a. Types of Specialty Valves. 1) Use of the following specialty valves is covered in this section: Altitude Valve, Pressure Reducing Valve, Pressure Relief Valve, Swing Check Valve,

More information

V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants

V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants Product Code No. LIT-12011515 Issued June 19, 2009 The V248 Series 3-Way Pressure-Actuated Water-Regulating Valves

More information

Principles of Pressure Regulation. Zurn Wilkins Pressure Reducing Valves

Principles of Pressure Regulation. Zurn Wilkins Pressure Reducing Valves Principles of Pressure Regulation Zurn Wilkins Pressure Reducing Valves Benefits of Pressure Reduction Water Conservation The average household can reduce water consumption around 33% by adjusting the

More information

The most common terms rating air flow capacity are ICFM, FAD, ANR, SCFM or nl/min

The most common terms rating air flow capacity are ICFM, FAD, ANR, SCFM or nl/min Rating of Air Compressors and Air Equipment The most common terms rating air flow capacity are ICFM, FAD, ANR, SCFM or nl/min There is no universal standard for rating air compressors, air equipment and

More information

Wet pipe low flow foam/water system

Wet pipe low flow foam/water system December 6, 2010 Foam 14a 1. The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with Viking supplied foam concentrates. This system consists of a standard

More information

PumpAgents.com - Click here for Pricing/Ordering Nominal psi (bar) Cut-In Cut-Out

PumpAgents.com - Click here for Pricing/Ordering Nominal psi (bar) Cut-In Cut-Out PumpAgents.com - Click here for Pricing/Ordering Model 31670-Series Dual Max 7.5 GPM (28 LPM) AUTOMATIC TWO STAGE WATER SYSTEM WITH ACCUMULATOR TANK AND PUMPGARD STRAINER IDEAL FOR PLEASURE AND COMMERCIAL

More information

TECHNICAL DATA Q= C. Table 1 - Specifications

TECHNICAL DATA Q= C. Table 1 - Specifications September 25, 2013 Pressure Regulation 537a 1. Description The Model B-3 Pilot Operated Pressure Control Valve is a factory assembled unit. The unit consists of a Model J-2 Halar coated Flow Control Valve,

More information

Model 420-HY Pressure Regulating Hydrant Valve

Model 420-HY Pressure Regulating Hydrant Valve Model 420-HY Pressure Regulating Hydrant Valve INSTALLATION OPERATION MAINTENANCE 1. Safety First BERMAD believes that the safety of personnel working with and around our equipment is the most important

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 3-2 Orifice Plates EXERCISE OBJECTIVE In this exercise, you will study how differential pressure flowmeters operate. You will describe the relationship between the flow rate and the pressure drop

More information

Baker maric flow control valves

Baker maric flow control valves Gate Valves 1 Baker maric flow control valves A - W - E - 2 Baker Maric Flow Control Valves Ever since water has been piped there has been a definite need for a practical, accurate, self cleaning and inexpensive

More information

Air Amplifiers & SYSTEMS

Air Amplifiers & SYSTEMS Air Amplifiers & SYSTEMS We Accept VISA, MasterCard and American Express Air Amplifiers Point-of-Use Air Solutions Maximator air amplifiers are designed to boost plant air pressure or increase the supply

More information

Smart Water Application Technologies (SWAT)

Smart Water Application Technologies (SWAT) Smart Water Application Technologies (SWAT) Turf and Landscape Irrigation Equipment PRESSURE REGULATING SPRAY HEAD SPRINKLERS Equipment Functionality Test Testing Protocol Version 3.0 (May 2012) Developed

More information

SECTION 25 TESTING AND DISINFECTING WATER MAINS General

SECTION 25 TESTING AND DISINFECTING WATER MAINS General SECTION 25 TESTING AND DISINFECTING WATER MAINS 25-1.01 Scope 25-1 General This section describes the requirements for pressure and leak testing, and disinfecting of water mains and appurtenances, including

More information

The Hoffman Specialty Series 2000 consists of main

The Hoffman Specialty Series 2000 consists of main Pressure and/or Temperature Pilot Operated Steam Series 2000 The Hoffman Specialty Series 2000 consists of main valves, pilot valves, wells and hardware kits. They are designed to meet a wide range of

More information

Liquid Level Measurement

Liquid Level Measurement Technical Article Liquid Level Measurement A pressure transmitter can be used to determine the liquid level in a tank, well, river or other body of liquid. The pressure at the bottom of a liquid filled

More information

Joint Expo 2012 February 7-8, 2012 BASIC HYDRAULICS

Joint Expo 2012 February 7-8, 2012 BASIC HYDRAULICS Tim Sullivan, P.E. Hubbell, Roth & Clark, Inc. Outline Pressure Hydraulic Energy and Head Losses System-Pump Curves Concepts of hydraulics as they relate to Operators and Mechanics Outline Good News Bad

More information

V146 Series 2-Way Pressure-Actuated Water-Regulating Valves

V146 Series 2-Way Pressure-Actuated Water-Regulating Valves roduct/technical Bulletin V146 Issue Date November 20, 2002 V146 Series 2-Way ressure-actuated Water-Regulating s The V146 Series 2-Way ressure-actuated Water-Regulating s regulate water flow and control

More information

DS05C,D,G Dial Set Pressure Regulating Valves

DS05C,D,G Dial Set Pressure Regulating Valves DS05C,D,G Dial Set Pressure Regulating Valves APPLICATION The Honeywell DS05C,D,G Dial Set Pressure Regulating Valve is a high quality pressure regulating valve that maintains a constant outlet pressure

More information

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE ractical Guide The following article was published in ASHRAE Journal, March 2003. Copyright 2003 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational

More information

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50) Page 1 of 8 1. DESCRIPTION The Viking Model F-1 Deluge Valve is a quick opening, differential diaphragm, flood valve with one moving mechanism. The Deluge Valve is used to control water flow in Deluge

More information

Autotrol Performa ProSoft

Autotrol Performa ProSoft Autotrol Performa ProSoft With 960 Series Control 5-Cycle Conditioner 5-Cycle FA Filter Water Conditioning Control System Installation, Operation and Maintenance Manual Table of Contents Installation.....................................

More information

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data Technical Services: Tel: (800) 381-312 / Fax: (800) 71-5500 Customer Service/Sales: Tel: (215) 362-0700 / (800) 523-6512 Fax: (215) 362-5385 Model B-1 Pipe Line Strainer 3,, 6 & 8 Inch (DN80, DN100, DN150

More information

Full Range Pressure Compensating Variable Flow Control

Full Range Pressure Compensating Variable Flow Control Engineering & Manufacturing Solutions Specifications: See flow chart for capacity. Rated for 3000 psi (207 bar). Weighs 7- ¾ lbs. (3.52 kg). 30-Micron Filtration Recommended. Torque to turn side lever

More information

Experiment 8: Minor Losses

Experiment 8: Minor Losses Experiment 8: Minor Losses Purpose: To determine the loss factors for flow through a range of pipe fittings including bends, a contraction, an enlargement and a gate-valve. Introduction: Energy losses

More information

The Discussion of this exercise covers the following points: Range with an elevated or suppressed zero Suppressed-zero range Elevated-zero range

The Discussion of this exercise covers the following points: Range with an elevated or suppressed zero Suppressed-zero range Elevated-zero range Exercise 4-3 Zero Suppression and Zero Elevation EXERCISE OBJECTIVE In this exercise, you will learn the effect that mounting a pressure transmitter above or below the reference level has on the hydrostatic

More information

CONTINENTAL NH3 PRODUCTS PRODUCT CATALOG

CONTINENTAL NH3 PRODUCTS PRODUCT CATALOG PRODUCT CATALOG October 2012 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Continental NH3 Products A-360 MANIFOLD ORDERING INFORMATION Thank you for ordering our new A-360 manifold system. To assist in

More information

Air Operated Hydraulic Pumping Systems to 50,000 psi

Air Operated Hydraulic Pumping Systems to 50,000 psi High Pressure Equipment Air Operated Hydraulic Pumping Systems to 50,000 psi PS-10: 10,000 psi PS-20: 20,000 psi PS-30: 30,000 psi PS-40: 40,000 psi PS-50: 50,000 psi PS-90: 90,000 psi High Pressure air

More information

International Journal of Technical Research and Applications e-issn: , Volume 4, Issue 3 (May-June, 2016), PP.

International Journal of Technical Research and Applications e-issn: ,  Volume 4, Issue 3 (May-June, 2016), PP. DESIGN AND ANALYSIS OF FEED CHECK VALVE AS CONTROL VALVE USING CFD SOFTWARE R.Nikhil M.Tech Student Industrial & Production Engineering National Institute of Engineering Mysuru, Karnataka, India -570008

More information

PENBERTHY SERIES LM, ELL, FL, GL, GH, U, L AND 2NC FOR PUMPING GASES

PENBERTHY SERIES LM, ELL, FL, GL, GH, U, L AND 2NC FOR PUMPING GASES Practical, simple and cost-effective alternatives for process industries to purge gases from chambers, exhaust, evacuate or prime using liquid, steam or air operating media FEATURES Simple design with

More information

Firestop Products and Systems Estimating Guide

Firestop Products and Systems Estimating Guide F i rr eessttooppppi ni ng g http://flamesafe.rectorseal.com PRODUCT DATA UPDATES TECH LETTERS DETAILS MSDS CONTACTS FAQS Firestop Products and Systems Estimating Guide Through-penetrations Estimating

More information

Inflatable Packer Single & Double. Single & Double Packer Dimension. Wireline Packer. Water Testing Packer (WTP) Packer

Inflatable Packer Single & Double. Single & Double Packer Dimension. Wireline Packer. Water Testing Packer (WTP) Packer Inflatable Packer Single & Double Single & Double Packer Dimension Wireline Packer Water Testing Packer (WTP) Packer Packer Working Pressure & Depth Chart Packer Water Hand Pump Packer Air Driven Pump

More information

V248 Series 3-Way Pressure-Actuated. Water-Regulating Valves for High-Pressure

V248 Series 3-Way Pressure-Actuated. Water-Regulating Valves for High-Pressure V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants The V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants regulate water

More information

H16 Losses in Piping Systems

H16 Losses in Piping Systems H16 Losses in Piping Systems The equipment described in this manual is manufactured and distributed by TECQUIPMENT LIMITED Suppliers of technological laboratory equipment designed for teaching. BONSALL

More information

Pressure and/or Temperature Pilot Operated Steam Regulators Series 2000

Pressure and/or Temperature Pilot Operated Steam Regulators Series 2000 Hoffman Specialty Regulators Regulators Pressure and/or Temperature Operated Regulators Series 2000 The Hoffman Specialty Series 2000 consists of main valves, pilot valves, wells and hardware kits. They

More information

PRESSURE DROP CHARTS

PRESSURE DROP CHARTS PRESSURE DROP FOR SMALL PEX TUBING AT 100 F Take the total heat load (BTUH) for the area that the loop is covering and divide it by 501. Divide the result with the Delta-T to find GPM for the loop. Find

More information

HOW TO PLAN AN UNDERGROUND IRRIGATION SYSTEM

HOW TO PLAN AN UNDERGROUND IRRIGATION SYSTEM HOW TO PLAN AN UNDERGROUND IRRIGATION SYSTEM CHECK THE AVAILABILITY OF WATER MEASURE THE WATER PRESSURE Close all household taps. Fit a pressure gauge to an outdoor tap, then open it completely (STATIC

More information

BUTTERFLY VALVES. Toll Free (877) - ICFLUID -2-

BUTTERFLY VALVES. Toll Free (877) - ICFLUID  -2- BUTTERFLY VALVES 1. General HyrdoWer is a globally recognized manufacturer of power unit accessories. They have become specialists in the design of Butterfly Valves and Hydraulic Compensators. The shut

More information

Chapter 10 SWIMMING POOLS

Chapter 10 SWIMMING POOLS 4-10-1: COMPLIANCE REQUIRED: Chapter 10 SWIMMING POOLS It shall be unlawful to construct, maintain, install or enlarge any swimming pool in the City except in compliance with the provisions of this Chapter.

More information

API Standard Venting Atmospheric and Low-Pressure Storage Tanks: Nonrefrigerated and Refrigerated

API Standard Venting Atmospheric and Low-Pressure Storage Tanks: Nonrefrigerated and Refrigerated General API Standard 2000 - Venting Atmospheric and Low-Pressure Storage Tanks: Is there any limit for the maximum allowable linear velocity or any other parameter for the roof of a floating roof tank

More information

User's Manual. MixRite TF 10. Edition 05.08

User's Manual. MixRite TF 10. Edition 05.08 User's Manual MixRite TF 10 Edition 05.08 1 Tefen MixRite TF 10 fertilizer and chemicals Injector Congratulations on your purchase of one of Tefen s high quality products. To get the best results from

More information

INSTALLATION & START-UP INSTRUCTIONS FLECK 9100SXT METER TWIN ALTERNATING WATER SOFTENER SYSTEMS

INSTALLATION & START-UP INSTRUCTIONS FLECK 9100SXT METER TWIN ALTERNATING WATER SOFTENER SYSTEMS INSTALLATION & START-UP INSTRUCTIONS FLECK 9100SXT METER TWIN ALTERNATING WATER SOFTENER SYSTEMS 1999-2007 QualityWaterForLess.com - 1 - info@qualitywaterforless.com Preface: Thank you for your purchase

More information

ASYBCO 90 O ELBOW LONG RADIUS O.D. I.D.

ASYBCO 90 O ELBOW LONG RADIUS O.D. I.D. 90 O ELBOW LONG RADIUS Standard weight Extra strong Schedule 160 Double extra strong ASTM A-234 ASME / ANSI B16.9 Carbon and ferritic alloy steel Produced from X-rayed, stress-relieve welded pipe. Welds

More information

Water Hammer In Irrigation Systems 1

Water Hammer In Irrigation Systems 1 CIR828 1 G. A. Clark and D. Z. Haman 2 Irrigation system design includes pump sizing and selection, valve sizing and selection, and pipe sizing as well as the proper selection and placement of many other

More information

Chapter 13 Fluids. Copyright 2009 Pearson Education, Inc.

Chapter 13 Fluids. Copyright 2009 Pearson Education, Inc. Chapter 13 Fluids Phases of Matter Density and Specific Gravity Pressure in Fluids Atmospheric Pressure and Gauge Pressure Pascal s Principle Units of Chapter 13 Measurement of Pressure; Gauges and the

More information

AIR GAP (AG) Low Hazard High Hazard

AIR GAP (AG) Low Hazard High Hazard AIR GAP (AG) On Low Hazard and High Hazard applications, Air Gap (AG) is used for the physical separation (vertical distance) between the lowest opening point from any pipe or outlet supplying water and

More information

Moyno ERT Power Sections. Operational Guidelines

Moyno ERT Power Sections. Operational Guidelines Moyno ERT Power Sections Operational Guidelines Moyno ERT Power Section Operational Guidelines Index 1. Introduction... 3 2. ERT Performance Graph Interpretation... 3 3. Elastomer Compression (Fit) Recommendations...

More information

STANDARD FOR CONTROL VALVE SEAT LEAKAGE

STANDARD FOR CONTROL VALVE SEAT LEAKAGE 11-3 STANDARD FOR CONTROL VALVE SEAT LEAKAGE 1. PURPOSE 1.1 This standard establishes a series of seat leakage classes for control valves and defines the test procedures. 2. SCOPE & LIMITATIONS 2.1 Selection

More information

Lab #4 Pipe Flow, Minor and Major Losses, and Walking in Osborne Reynolds Shoes CEE 331 Fall 2006

Lab #4 Pipe Flow, Minor and Major Losses, and Walking in Osborne Reynolds Shoes CEE 331 Fall 2006 CEE 331 Lab 4 Page 1 of 5 Lab #4 Pipe Flow, Minor and Major Losses, and Walking in Osborne Reynolds Shoes CEE 331 Fall 2006 Safety The major safety hazard in this laboratory is a shock hazard. Given that

More information

Owners Manual Models: 075-AQF-CX. Aquatrol Backwashing Catalytic Carbon Filter. Visit us online at.

Owners Manual Models: 075-AQF-CX. Aquatrol Backwashing Catalytic Carbon Filter.  Visit us online at. Visit us online at www.uswatersystems.com Aquatrol Backwashing Catalytic Carbon Filter Owners Manual Models: 075-AQF-CX REVISION # 1.0 REVISION DATE October 11, 2017 US Water Systems, Inc. 1209 Country

More information

Assistant Lecturer Anees Kadhum AL Saadi

Assistant Lecturer Anees Kadhum AL Saadi Pressure Variation with Depth Pressure in a static fluid does not change in the horizontal direction as the horizontal forces balance each other out. However, pressure in a static fluid does change with

More information

INSTALLATION & START-UP INSTRUCTIONS. Clack WS1 & WS1.25 METER WATER SOFTENER SYSTEMS

INSTALLATION & START-UP INSTRUCTIONS. Clack WS1 & WS1.25 METER WATER SOFTENER SYSTEMS INSTALLATION & START-UP INSTRUCTIONS Clack WS1 & WS1.25 METER WATER SOFTENER SYSTEMS 1999-2009 QualityWaterForLess.com - 1 - info@qualitywaterforless.com Preface: Thank you for your purchase of a new Water

More information

INSTRUCTOR GUIDE REFERENCES: PUMPING APPARATUS DRIVER/OPERATOR HANDBOOK, FIRST EDITION, IFSTA

INSTRUCTOR GUIDE REFERENCES: PUMPING APPARATUS DRIVER/OPERATOR HANDBOOK, FIRST EDITION, IFSTA TOPIC: RELAY PUMPING OPERATIONS LEVEL OF INSTRUCTION: TIME REQUIRED: ONE HOUR INSTRUCTOR GUIDE MATERIALS: APPROPRIATE AUDIO VISUAL SUPPORT REFERENCES: PUMPING APPARATUS DRIVER/OPERATOR HANDBOOK, FIRST

More information

my SYSTEM A guide to common applications in water distribution systems

my SYSTEM A guide to common applications in water distribution systems my SYSTEM A guide to common applications in water distribution systems WWW.SINGERVALVE.COM INDEX This short guide is intended to offer guidance on some of the common problems, applications and questions

More information

CLEANING, INSPECTION, AND TESTING OF SEWERS

CLEANING, INSPECTION, AND TESTING OF SEWERS CLEANING, INSPECTION, AND TESTING OF SEWERS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Cleaning, Inspecting, and Testing Sanitary Sewers B. Cleaning, Inspecting, and Testing Storm Sewers C. Cleaning and

More information

APPENDIX B HYDRAULIC DESIGN DATA FOR CULVERTS

APPENDIX B HYDRAULIC DESIGN DATA FOR CULVERTS TM 5-820-4/AFM 88-5, Chap 4 APPENDIX B HYDRAULIC DESIGN DATA FOR CULVERTS B-1. General. a. This appendix presents diagrams, charts, coefficients and related information useful in design of culverts. The

More information

36H SERIES Combination Gas Valve

36H SERIES Combination Gas Valve FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION The 36H series combination gas valve is

More information

BERMAD Irrigation. Automatic Metering Valve (AMV) 900-D Series. Basic Valve ??????? IR-900-D.

BERMAD Irrigation. Automatic Metering Valve (AMV) 900-D Series. Basic Valve ??????? IR-900-D. asic Valve??????? I-9-D Automatic Metering Valve (AMV) The EMAD Model I-9-D is a unique product integrating both a vertical turbine oltman-type water meter and a pilot operated, diaphragm actuated control

More information

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25 Self-operated Pressure Regulators Differential Pressure Regulators (opening) Type 42-20 Type 42-25 Type 42-20 Differential Pressure Regulator Type 42-25 Differential Pressure Regulator Mounting and Operating

More information

Proper Pump Installation Practices

Proper Pump Installation Practices Proper Pump Installation Practices 80-779, Rev. 10/08 There is a Reason Every Unit Comes With This Bright Orange Tag! Proper Alignment and Coupling Installation Do Not Drive Coupling Onto Shaft Pump Alignment

More information

VACUUM TESTING PRECAST CONCRETE MANHOLES

VACUUM TESTING PRECAST CONCRETE MANHOLES 1 OF 5 testing is a quick, safe and practical way to validate manhole system integrity. Manhole sections can be tested at the precast concrete plant prior to delivery or on site prior to backfilling. Here

More information

WAT305 Math Part 1 ABC Math

WAT305 Math Part 1 ABC Math WAT305 Math Part 1 ABC Math Good to know for certification: You have used 35 150lb cylinders of Chlorine in 2011 how many pounds total did you use? How many pounds per month did you use? If demand is expected

More information

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL Capital Controls Series 71V3000 The Series 71V3000 electrically-heated vaporizer automatically vaporizes and superheats liquid chlorine, sulfur dioxide or ammonia at a rate controlled by the gas feed system.

More information

New England Municipal Building Officials Preventing Drowning and Suction Entrapment through Code Compliance

New England Municipal Building Officials Preventing Drowning and Suction Entrapment through Code Compliance New England Municipal Building Officials Preventing Drowning and Suction Entrapment through Code Compliance 2009 International Family of Codes Swimming Pools and Spas 2009 International Building Code 2009

More information

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS)

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS) South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System Designed for: Dry or Preaction Fire Protection Systems (FPS) 1.0 Description of Work 1.1 The Fire Sprinkler Contractor shall provide

More information

VPPL VARIABLE DISPLACEMENT AXIAL-PISTON PUMPS FOR INTERMEDIATE PRESSURE SERIES 10

VPPL VARIABLE DISPLACEMENT AXIAL-PISTON PUMPS FOR INTERMEDIATE PRESSURE SERIES 10 / ED VPPL VARIABLE DISPLACEMENT AXIAL-PISTON PUMPS FOR INTERMEDIATE PRESSURE SERIES OPERATING PRINCIPLE The VPPL are variable displacement axial-piston pumps with variable swash plate, suitable for applications

More information

Cross- Connection Control CEU 203. Continuing Education from the American Society of Plumbing Engineers. September ASPE.

Cross- Connection Control CEU 203. Continuing Education from the American Society of Plumbing Engineers. September ASPE. Cross- Connection Control Continuing Education from the American Society of Plumbing Engineers September 2013 ASPE.ORG/ReadLearnEarn CEU 203 READ, LEARN, EARN Note: In determining your answers to the CE

More information

NORDCALC Introduction... 2 Registration... 2 Flow Calculations tab Torque Calculation & Actuator Mounting Data tab... 21

NORDCALC Introduction... 2 Registration... 2 Flow Calculations tab Torque Calculation & Actuator Mounting Data tab... 21 NORDCALC User Guide Table of Contents NORDCALC Introduction... 2 Registration... 2 Flow Calculations tab... 5 Calculating the gas flow rate for gaseous medium... 6 Calculating the pressure drop for gaseous

More information

Fisher DSA Steam-Atomized Desuperheater

Fisher DSA Steam-Atomized Desuperheater Instruction Manual DSA Desuperheater Fisher DSA Steam-Atomized Desuperheater Contents Introduction... 1 Scope of Manual... 1 Description... 1 Principle of Operation... 2 Installation... 2 Operating Instructions...

More information

Type 3 - PSA Nitrogen Generation System

Type 3 - PSA Nitrogen Generation System Type 3 - PSA Nitrogen Generation System Designed for: Dry or Pre-Action Fire Protection Systems (FPS) with a total capacity from 6,000 to 18,000 gallons 1.0 Nitrogen Generation Corrosion Inhibiting System

More information

ENERGY BLADE 3K4. Energy Blade Installation Instructions

ENERGY BLADE 3K4. Energy Blade Installation Instructions ENERGY BLADE 3K4 Energy Blade Installation Instructions 1 Contents General information 2 Scope of these instructions 2 Product information 2 Designated use 3 Warranty 3 Safety instructions 4 Assembly and

More information

Serving. Petrochemicals Power Semiconductor Waste Treatment Oil & Gas Transmission Lines Bulk Gas Plants

Serving. Petrochemicals Power Semiconductor Waste Treatment Oil & Gas Transmission Lines Bulk Gas Plants Serving Petrochemicals Power Semiconductor Waste Treatment Oil & Gas Transmission Lines ulk Gas Plants Mining & Metals Pharmaceuticals Pulp & Paper Mills Sugar Mills Nuclear Desalinization Plants NOTES:

More information

TUTORIAL. NPSHA for those who hate that stuffy word. by Jacques Chaurette p. eng. copyright 2006

TUTORIAL. NPSHA for those who hate that stuffy word. by Jacques Chaurette p. eng.  copyright 2006 TUTORIAL NPSHA for those who hate that stuffy word by Jacques Chaurette p. eng. www.lightmypump.com copyright 2006 page.2 NPSHA for those who hate that stuffy word This article follows the same approach

More information

MANUAL FLOW CONTROL 2-1/2" - 18" QUICKSET FLOW CHART

MANUAL FLOW CONTROL 2-1/2 - 18 QUICKSET FLOW CHART This chart performs two functions: It allows you to calculate the permanent pressure drop for any size Quickset or. This figure is useful mostly in the design process, for system calculations. It allows

More information

Performa Cv Twin Alternating and High Flow Systems. Manual Supplement

Performa Cv Twin Alternating and High Flow Systems. Manual Supplement Performa Cv Twin Alternating and High Flow Systems Manual Supplement Table of Contents 1.0 Installation and Start-Up.............. 3 Water Line Connection Brine Tank Turbine Connection Connecting Manifold

More information

SPH 4C Unit 4 Hydraulics and Pneumatic Systems

SPH 4C Unit 4 Hydraulics and Pneumatic Systems SPH 4C Unit 4 Hydraulics and Pneumatic Systems Properties of Fluids and Pressure Learning Goal: I can explain the properties of fluids and identify associated units. Definitions: Fluid: A substance that

More information

Optimizing Gas Supply for Industrial Lasers

Optimizing Gas Supply for Industrial Lasers Optimizing Gas Supply for Industrial Lasers Laser cutting of metals and other materials has grown rapidly due to developments in laser power, advancements in CNC automation, and decreasing costs. The industrial

More information

Types S100K and S102K Pressure Regulators

Types S100K and S102K Pressure Regulators Instruction Manual Form 5624 Types S0K and S2K 01/01 Types S0K and S2K Pressure Regulators W7478-1 Figure 1. Types S0K and S2K Pressure Regulator Introduction Scope of Manual This manual provides instructions

More information

Technical Data Sheet TI-F50 Locking Units series KFH

Technical Data Sheet TI-F50 Locking Units series KFH English translation of German original Locking Units series KF Further important practical advice is given in Operating Manual BA-F50., Rod diameter 18 mm 50 mm øz 8 L 2 6 x 6 0 min. 4x30 KF 18 to KF 32,

More information

FLUID DYNAMICS Ch.E-204 Umair Aslam Lecturer Department of Chemical Engineering

FLUID DYNAMICS Ch.E-204 Umair Aslam Lecturer Department of Chemical Engineering FLUID DYNAMICS Ch.E-204 Umair Aslam Lecturer Department of Chemical Engineering Fluid Mechanics is the branch of physics that studies fluids (liquids, gases, and plasmas) and the forces on them. Fluid

More information

TESTING APPLICATION STANDARD (TAS)

TESTING APPLICATION STANDARD (TAS) TESTING APPLICATION STANDARD (TAS) No. 00(A)-9 TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE AND/OR INCREASED WINDSPEED RESISTANCE OF SOFFIT VENTILATION STRIP AND CONTINUOUS OR INTERMITTENT VENTILATION

More information

Pre-adjustable pressure reducing valves

Pre-adjustable pressure reducing valves Pre-adjustable pressure reducing valves H series CCREDITED ISO 9 FM / N Replaces / N Function Pressure reducing valves are devices which, when installed on water systems, reduce and stabilize the pressure

More information

MEASUREMENT BEST PRACTICES FORIMPROVEDREFINERY SAFETY, AVAILABILITY & EFFICIENCY

MEASUREMENT BEST PRACTICES FORIMPROVEDREFINERY SAFETY, AVAILABILITY & EFFICIENCY MEASUREMENT BEST PRACTICES FORIMPROVEDREFINERY SAFETY, AVAILABILITY & EFFICIENCY Mark Menezes, PlantWeb Marketing Manager Rosemount Inc. Eric Wickberg, Pressure Applications Marketing Manager Rosemount

More information

Pneumatic Reservoir Analysis Work Sheet

Pneumatic Reservoir Analysis Work Sheet Pneumatic Reservoir Analysis Work Sheet Getting Started Use a pair of dial calipers to measure the length and diameter dimensions of the: 1. End Cap 2. Threaded Boss 3. Stainless Steel Tube Record these

More information