The Key Variables Needed for PFDavg Calculation

Size: px
Start display at page:

Download "The Key Variables Needed for PFDavg Calculation"

Transcription

1 Iwan van Beurden, CFSE Dr. William M. Goble, CFSE exida Sellersville, PA 18960, USA July 2015 Update 1.2 September 2016 Abstract In performance based functional safety standards, safety function designs are verified using specified metrics. A key metric for process industry designs is called average Probability of Failure on Demand (PFDavg). After several studies of many field failure and proof test reports, several variables have been identified as key to a realistic PFDavg calculation. Most simplified equations including the informative section in IEC 61508, Part 6 do not include several key variables. It is shown that exclusion of these parameters may result in an optimistic metric calculation which may result in an unsafe design. This paper identifies the key variables that need to be included in a PFDavg calculation and provides some simplified equations showing the impact of most variables. An example showing two sets of variables reveals an entire SIL level difference in PFDavg calculation results. Introduction IEC 61511, the functional safety standard for the process industries, is performance based. Rather than having specific designs and a long list of specific rules that become obsolete, the IEC standard allows any design to be implemented. The standard allows the design to use old products or new technology. The standard allows innovation and good engineering. However, any design must be verified with documented performance metrics which must match risk reduction requirements in the form of safety integrity levels (SIL). In order to verify that a design meets the needed risk reduction, the designer must check three performance criteria [1]. exida calls these the three barriers.

2 The achieved SIL level is the minimum of: Barrier 1 SIL level based on Systematic Capability (SC) of each device used in a safety instrumented function (SIF). SC is a measure of design quality that shows sufficient protection against systematic design faults within a device. SC is achieved by either choosing a certified device with systematic capability to the given SIL level or by completing a prior use justification of a device to the given SIL level. Barrier 2 SIL level based on a PFH (high demand), or a PFDavg (low demand) for all equipment in a SIF. Barrier 3 SIL level based on minimum architecture constraints (SILac) for each element (sub system) in a SIF. There are many different tables that can be used to establish architecture constraints; some are in IEC 61511, and two alternatives are in IEC (Route 1H or Route 2H). All three of these design barriers must achieve the target SIL level or greater. If a SIF design only meets two of the barriers the worst case (lowest) SIL level wins. Barrier Two: PFDavg Calculation PFDavg calculation is an extremely important part of safety engineering in low demand applications as it is probably the hardest of the three barriers to meet if realistic assumptions are made and if realistic failure rates are used ( Target levels for PFDavg are defined in IEC for each of 4 Safety Integrity Levels (SIL). The highest safety level is achieved in SIL level 4 and the lowest is SIL level 1. Table 1 shows that PFDavg for a given set of safety function equipment will correspond to an equivalent SIL level within an order of magnitude range. Safety Integrity Level Low Demand Mode of Operation (Average Probability of Failure on Demand, PFDavg) to < to < to < to < 10 1 Table 1: SIL Level related to PFDavg How do we calculate a realistic number for PFDavg? What variables need to be taken into account when calculating PFDavg? 2

3 PFDavg Key Variables The Key Variables Needed for PFDavg Calculation As a result of research into hundreds of sets of field failure data and proof test results, a number of things have been observed which may significantly impact a PFDavg. exida has compiled a list comprised of nine variables that must be considered in order to calculate a realistic and safe PFDavg. 1. Failure rates of each device including failure modes and any diagnostic coverage from automatic diagnostics, λ DD, λ DU (attributes of the equipment chosen). 2. Mission Time, MT the time period a set of equipment will be operated before overhaul or replacement (assignable by end user practices). 3. Proof Test Intervals, TI (assignable by end user practices). 4. Proof Test Effectiveness, C pt (an attribute of proof test method). 5. Proof Test Duration, PTD (an attribute of end user practices). 6. Mean Time To Restore, MTTR (an attribute of end user practices). 7. Probability of Initial Failure, PIF (an attribute of end user practices). 8. Site Safety Index, SSI (an attribute of end user practices). 9. Redundancy of devices including common cause failures (an attribute of SIF design). Many of these variables are not commonly recognized and therefore not included, yet they may impact the result by a SIL level or more. Failure Rates, λ DD, λ DU Failure rates, in particular the dangerous failure rates, come from a variety of sources [2, 3, 4]. Most manufacturers provide an FMEDA prediction that has been verified by fault injection testing and field failure analysis [5, 6]. When automatic diagnostics are designed into a device or subsystem, FMEDA analysis can distinguish between those failures detected and those undetected by the automatic diagnostics. The total dangerous failure rate, is partitioned into two subcategories:, Dangerous Detected and, Dangerous Undetected. 3

4 Mission Time, MT The Key Variables Needed for PFDavg Calculation Mission Time is a period of time during which a set of equipment operates. This is an old reliability engineering term that is used to define the probability calculation period. Most end users choose a Mission Time of 5, 10, 20, or 30 years which corresponds to the end of life for the process equipment or a period of time between each major shutdown and overhaul/replacement of all equipment. Any SIF device that reaches the end of its useful life during the MT is replaced or completely overhauled and tested before the MT ends. Given a dangerous failure rate and a mission time, an approximation for probability of failure for a simplex (non redundant) system can be shown to be: PFD = λ DU * MT. The average Probability of Failure on Demand is then: PFDavg = λ DU * MT/2. Impact of an Ideal Proof Test Proof Test Intervals In most industrial applications where a Safety Instrumented System (SIS) is present, it is possible to design the SIF so that it can be manually proof tested to see if it is working or not. If an assumption is made that the proof test is 100% effective and requires no bypass time, this is called a perfect proof test. Now this assumption is quite unrealistic but is useful in showing the development of simplified equations to calculate PFDavg. At the end of a perfect proof test we may conclude there is no failure. This means that the probability of failure at that moment in time is ideally zero. The PFD as a function of time with perfect proof test looks like a repeating saw tooth as shown in Figure 1. PFD (t) Perfect Proof Test Impact Mission Time Interval Figure 1: Probability of Failure on Demand (PFD) as a function of time showing multiple cycles with a perfect proof test. 4

5 The book Control Systems Safety Evaluation and Reliability [7], Chapter 8 explains the derivation of this chart in great detail and provides the equation for PFDavg as:. The MT is no longer a variable in this situation because the PFDavg of each of the proof test cycles is the same as the PFDavg of the first cycle. This equation for PFDavg is of course very idealistic and unrealistic, but it is a great place to start the development of more realistic models and equations. Proof Test Effectiveness What happens in a real proof test? It can clearly be shown via detailed analysis of devices and examples that no real proof test is perfect. There are many examples of failures in products that cannot be detected by proof testing. An obvious example is a proof test done by putting a blocking device on an actuator and checking to see if the actuator / valve assembly attempts to move. This does show that a portion of the subsystem is working but the test gives no indication of the health of many parts including the valve seat. Did the valve actually seal? This test cannot tell and is clearly not perfect. What happens to PFD when you have an imperfect proof test? At the end of the proof test it is known that the probability of failure is reduced but it is not zero because not all failures are detected. Probability of failure is reduced to some value above zero. The probability of failure will increase after each proof test. This continues for the entire mission time of the system. Figure 2 shows the probability of failure on demand (PFD) as a function of time for an imperfect proof test. PFD (t) C PT Proof Test Interval Mission Time Interval Figure 2: Probability of Failure on Demand as a function of time with imperfect proof testing. 5

6 Figure 3 shows the PFDavg for the entire MT consisting of six proof test intervals. Comparing the PFDavg of the first test interval with the overall PFDavg clearly shows a larger PFDavg for the entire MT. This difference is due to proof test effectiveness. PFD (t) PFDavg PFDavg First TI C PT Proof Test Interval Mission Time Interval Figure 3: Probability of Failure on Demand with imperfect proof testing showing PFDavg. Proof test effectiveness can be expressed in a simplified approximate equation. The proof test effectiveness,, is a number between 0 100% which indicates the portion of the λ DU detected by the manual proof test. The first term of the new equation uses the ideal formula for PFDavg multiplied by C PT as those failures are detected by the proof test. The second term of the new equation shows failures not detected by the proof test (1 C PT ) with a longer time interval, MT. Mean Time To Restore (MTTR) When a safety function has automatic diagnostics, the PFDavg is impacted by the MTTR unless the SIF is programmed to automatically shut down on a detected failure. Assuming this is not done, when a failure is detected by an automatic diagnostic, annunciated to operations personnel, and a repair person is dispatched quickly so that the average repair time is maintained, then the failure only contributes to the PFD for a small duration of time called Mean Time To Restore (MTTR). This amount of time is the average time it takes to find, diagnose, and repair a failure in a system. The PFDavg equation for this situation is: When this is added to the previous equation, the result is: 6

7 Every time a system fails we repair it. As long as the average repair time is maintained, the portion of that equation is valid. Proof Test Duration (PTD) When proof testing is done with the process active and hazards present then proof test designers must decide if the safety function must be bypassed during the proof test. A safety function bypass is done when the testing will (or might) cause a false trip of the process unit. What happens to PFD during that bypass time? When a safety function is put on bypass that means it will not respond to a demand. The PFD during the duration of the proof test period equals 1. This will cause the PFD(t) function to look like Figure 4, where PFD goes to 1 for the duration of the proof test and then down to the expected level. 1 Proof Test starts. Safety function put into bypass. Proof Test complete, bypass is removed. PFD Dangerous Failure occurs Proof Test Duration (PTD) Mission Time Figure 4: Probability of Failure on Demand during a proof test bypass with no failure found. How do we account for this time, known as Proof Test Duration (PTD)? The time spent in bypass (PTD) occurs once every proof test interval (TI). Therefore the PFDavg due to PTD is a new term in the equation. If no problem is found during the proof test then:. 7

8 However, when there is a problem found during the proof test, the average time needed to repair the problem and restore safety function operation (MTTR) must be accounted for. The equation then looks like this:. By separating the two terms in the numerator, we can multiply the second term by the probability of dangerous failure. This accounts for the probability of finding a problem during the proof test interval. The equation then looks like: which simplifies to:, The equation above can now be added to our existing PFDavg equation to create an equation that accounts for all variables so far considered: which simplifies to:. Probability of Initial Failure (PIF) Probability of initial failure means that a device does not work when a SIF is first brought into operation. In effect, the PFD is 1 at least until the first proof test. An extensive study of detailed proof test data [8, 9] showed that there was clearly a probability of initial failure in some types of devices used in SIF applications. Three independent data sets of pressure relief valves predicted an initial failure probability of approximately 1% 1.6%. This initial failure probability was extremely significant as it accounted for the majority of failures observed in proof test. This appears to happen when there is not careful installation and thorough commissioning procedures. When commissioning testing cannot be done after installation, there is a higher PIF. This can be modeled in the approximation equation by adding the PIF contribution. 8

9 Site Safety Index (SSI) During a detailed study of field returns [10] at Moore Products Co. in the late 1990s, it was discovered that the return rate for identical modules was 4 times different from one site to another. Some failures were due to systematic problems where untrained people were damaging equipment during their proof test process. However when those failures were removed from the data, there was still roughly a 2X difference in failure rate for the same device from site to site. Since the 1998 study, several other field failure studies from a number of different sources, primarily end users in the process industries, have indicated there is also a difference in failure rates for the same product from site to site. Typically the ratio is averaging between 1.2 and 3 times difference depending on product type. Therefore we conclude that random failures can be divided into two categories. There are random failures attributed to a product and random failures that are site specific. These seem to be related to procedures, training, and other variables that some have called the safety culture. exida defines this variable as the Site Safety Index (SSI) [11]. Several factors have been identified thus far which impact the SSI. These include the quality of: 1. Commissioning Test 2. Safety Validation Test 3. Proof Test Procedures 4. Proof Test Documentation 5. Failure Diagnostic and Repair Procedures 6. Device Useful Life Tracking and Replacement Process 7. SIS Modification Procedures 8. SIS Decommissioning Procedures 9. And others SSI can be evaluated using a set of questions and a scoring system [12, 13, 14]. The SSI model has five levels as shown in Table 1. 9

10 Table 1: Five levels of Site Safety Index from exsilentia Level Effectiveness Description SMI 4 100% Perfect Repairs are always correctly performed, Testing is always done correctly and on schedule, equipment is always replaced before end of useful life, etc. SMI 3 99% Almost perfect Repairs are correctly performed, Testing is done correctly and on schedule, equipment is replaced before end of useful life, etc. SMI 2 90% Good Repairs are correctly performed, Testing is done correctly and mostly on schedule, most equipment is replaced before end of useful life, etc. SMI 1 60% Medium Repairs are often correctly performed, Testing is done and mostly on schedule, some equipment is replaced before end of useful life, etc. SMI 0 0% None Repairs are not performed, Testing is not done, equipment is not replaced until failure, etc. PIF, failure rates, probability of successful repair, probability of successful proof test, and probability of doing a proof test on schedule are all impacted by SSI because of the stochastic nature of those probabilities. Redundancy What about redundancy? To account for redundancy, time dependent probabilities can be used in fault trees; where an OR gate is involved we add up the probabilities (provided that the events are mutually exclusive), and if an AND gate is involved we multiply the probabilities (providing the events are independent). These fault trees would be quite complicated but the resulting equations would be somewhat realistic. Alternatively Markov models can be used as a simpler method to calculate probabilities as a function of time. The detailed equations are beyond the scope of this paper. All nine of the variables listed need to be considered when calculating a PFDavg. 10

11 Variable Number Description Source Applicability 1 Failure Rates, DD and DU Manufacturer Always 2 Mission Time, MT End User Always 3 Proof Test Intervals, TI End User Always 4 Proof Test Effectiveness, C PT End User Always 5 Proof Test Duration, PTD End User If proof test done with process operating 6 Mean Time To Restore, MTTR End User If no automatic shutdown after detected fault 7 Probability of Initial Failure, PIF End User If equipment is not 100% tested after installation 8 Safety Maturity Index End User Always 9 Redundancy System Designer If HFT=1 or more The impact of not using realistic variables To evaluate the impact on PFDavg of not using all important variables, consider the example of a high level protection SIF. The proposed design has a SIL level 2 target. The design is using a single SIL level 2 capability level transmitter, a SIL level 3 capability certified safety logic solver, and a single remote actuated valve. The actuated valve consists of a certified solenoid valve, a certified scotch yoke actuator and a certified ball valve with all components having a SIL level 3 capability. Using certified parts eliminates any need to perform prior use analysis for safety integrity purposes. The exsilentia tool accounts for all critical variables. Using exsilentia, idealistic/optimistic variables are entered. A mission time (MT) of 5 years is entered, and the proof test interval is 1 year for the sensor and field elements, and 5 years for the logic solver. A proof test coverage of 100% is entered which is the equivalent of not considering proof test coverage as a variable. It is also assumed that the proof test is done with the process offline which removes PTD from the calculation. 11

12 Figure 7: exsilentia Screen shot showing results of idealistic assumptions In this example, the PFDavg was computed as 6.82x10 3. This value meets SIL level 2 with a Risk Reduction Factor (RRF) of 147. It can be seen that the architecture constraints meet SIL level 2 and systematic capabilities met SIL level 2. Therefore, the entire design meets SIL level 2 (all indicated by red circles). The pie chart on the left side of Figure 7 (indicated by an arrow) shows how much each subsystem contributed to the PFDavg. The figure shows that final elements were the main contributor. The exsilentia tool also calculates the Mean Time to Fail Spuriously (MTTFS), which is boxed in blue. This number indicates how often a false trip will occur, so high numbers are the goal in order to avoid costly false trips. But what if more realistic variables were entered for the same SIF? A mission time of 25 years will now be used. A proof test interval of 1 year for the sensor and final element, as well as 5 years for the logic solver will be used. Proof test coverage is now 90% for the sensor and 70% for final element. A proof test duration of 2 hours is included and an MTTR value of 48 hours is more realistic. Site Safety Index is medium for the sensor and final elements, and good for the logic solver. This calculation considers all nine variables. 12

13 Figure 8: exsilentia screen shot with more realistic variables considered What happened to the PFDavg? For the set of idealistic values the PFDavg was 6.82x10 3 and the RRF was 147. The same design was analyzed again, but this time all nine variables are being realistically included. The calculated PFDavg for this Safety Instrumented Function now drops to a value of 5.76x10 2! The RRF, which was at a value of 147, now drops to 17! This barely meets SIL level 1. Why are these values so different? Sensitivity analysis indicates that proof test coverage (%) is a significant variable. SSI is significant. The impact of PTD is not that significant in this case, but it sometimes can be. Failure rates, redundancy, proof test intervals, and Mean Time to Restore are all well known variables covered in IEC 61508, Part 6 equations. Proof test effectiveness and mission time are even mentioned in the new version of IEC However, these variables are only mentioned and are not part of any of the presented equations. Other variables, especially Site Safety Index, are largely overlooked. All of the variables need to be taken into account to ensure a safe design. 13

14 References 1. Three Steps in SIF Design Verification, White Paper, exida. Sellersville, PA June SINTEF, OREDA Offshore and Onshore Reliability Data Handbook, Vol 1. Topside Equipment and Vol. 2 Subsea Equipment, 6th Ed, OREDA Participants, Safety Equipment Reliability Handbook 4 th Edition, exida. Sellersville, PA Bukowski, J. V. and Stewart, L. L., Explaining the Differences in Mechanical Failure Rates: exida FMEDA Predictions and OREDA Estimations, White Paper, exida. Sellersville, PA July Goble, W. M., and Brombacher, A. C., "Using a Failure Modes, Effects and Diagnostic Analysis (FMEDA) to Measure Diagnostic Coverage in Programmable Electronic Systems," Reliability Engineering and System Safety, Vol. 66, No. 2, November Grebe, J.C., and Goble, W. M., FMEDA Accurate Product Failure Metrics, White Paper, exida. Sellersville, PA V1.2, October Goble, W. M., Control Systems Safety Evaluation and Reliability, Third Edition, ISA, Research Triangle Park, NC, Bukowski, J. V. (2007), "Results of Statistical Analysis of Pressure Relief Valve Proof Test Data Designed to Validate a Mechanical Parts Failure Database," Technical Report, September, exida, Sellersville, PA. 9. Bukowski, J. V., and Goble, W. M. (2009), "Analysis of Pressure Relief Valve Proof Test Data," AIChE Journal Process Safety Progress, March van Beurden, I.J.W.R.J., Reliability Analysis of Quadlog, Field failure research and study of the reliability information flow, Moore Products Co., Spring House, PA, USA, February Bukowski, J. V. and Goble, W. M., "A Proposed Framework for Incorporating the Effects of End User Practices in the Computation of PFDavg," exida white paper, January Bukowski, J. V., Gross, R., and van Beurden, I., "Product Failure Rates vs Total Failure Rates at Specific Sites: Implications for Safety," Proceedings AIChE 11th Annual Global Conference on Process Safety Process Plant Safety Symposium, Austin, TX, April Bukowski, J. V. and Chastain Knight, D., Assessing Safety Culture via the Site Safety Index TM, Proceedings AIChE 12th Annual Global Congress on Process Safety Process Plant Safety Symposium, Houston, TX, April Bukowski, J. V. and Stewart, L.L., Quantifying the Impacts of Human Factors on Functional Safety, Proceedings AIChE 12th Annual Global Congress on Process Safety Process Plant Safety Symposium, Houston, TX, April

15 Revision History The Key Variables Needed for PFDavg Calculation Revision 0.1 Initial Draft July, 2015 Micah Stutzman, W. Goble Revision 1 First Release July, 2015 Revision 1.1 Updated SSI terminology October 7, 2015 TES and WMG Revision 1.2 Updated references, conditions September 2016 WMG 15

Pneumatic QEV. SIL Safety Manual SIL SM Compiled By : G. Elliott, Date: 8/19/2015. Innovative and Reliable Valve & Pump Solutions

Pneumatic QEV. SIL Safety Manual SIL SM Compiled By : G. Elliott, Date: 8/19/2015. Innovative and Reliable Valve & Pump Solutions SIL SM.0010 1 Pneumatic QEV Compiled By : G. Elliott, Date: 8/19/2015 Contents Terminology Definitions......3 Acronyms & Abbreviations..4 1. Introduction 5 1.1 Scope 5 1.2 Relevant Standards 5 1.3 Other

More information

Solenoid Valves used in Safety Instrumented Systems

Solenoid Valves used in Safety Instrumented Systems I&M V9629R1 Solenoid Valves used in Safety Instrumented Systems Operating Manual in accordance with IEC 61508 ASCO Valves Page 1 of 7 Table of Contents 1 Introduction...3 1.1 Terms and Abbreviations...3

More information

FP15 Interface Valve. SIL Safety Manual. SIL SM.018 Rev 1. Compiled By : G. Elliott, Date: 30/10/2017. Innovative and Reliable Valve & Pump Solutions

FP15 Interface Valve. SIL Safety Manual. SIL SM.018 Rev 1. Compiled By : G. Elliott, Date: 30/10/2017. Innovative and Reliable Valve & Pump Solutions SIL SM.018 Rev 1 FP15 Interface Valve Compiled By : G. Elliott, Date: 30/10/2017 FP15/L1 FP15/H1 Contents Terminology Definitions......3 Acronyms & Abbreviations...4 1. Introduction...5 1.1 Scope.. 5 1.2

More information

Solenoid Valves For Gas Service FP02G & FP05G

Solenoid Valves For Gas Service FP02G & FP05G SIL Safety Manual SM.0002 Rev 02 Solenoid Valves For Gas Service FP02G & FP05G Compiled By : G. Elliott, Date: 31/10/2017 Reviewed By : Peter Kyrycz Date: 31/10/2017 Contents Terminology Definitions......3

More information

Explaining the Differences in Mechanical Failure Rates: exida FMEDA Predictions and OREDA Estimations

Explaining the Differences in Mechanical Failure Rates: exida FMEDA Predictions and OREDA Estimations Explaining the Differences in Mechanical Failure Rates: exida FMEDA Predictions and OREDA Estimations Julia V. Bukowski, PhD Department of Electrical & Computer Engineering Villanova University Loren Stewart,

More information

Bespoke Hydraulic Manifold Assembly

Bespoke Hydraulic Manifold Assembly SIL SM.0003 1 Bespoke Hydraulic Manifold Assembly Compiled By : G. Elliott, Date: 12/17/2015 Contents Terminology Definitions......3 Acronyms & Abbreviations..4 1. Introduction 5 1.1 Scope 5 1.2 Relevant

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Contact elements Type 8082 and Type 8208 with or without 8602 actuator Customer: R. STAHL Schaltgeräte GmbH Waldenburg Germany Contract No.: Stahl

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Emerson s Rosemount 2051 Pressure Transmitter with 4-20mA HART Device Label SW 1.0.0-1.4.x Company: Rosemount Inc. Shakopee, MN USA Contract No.:

More information

Hydraulic (Subsea) Shuttle Valves

Hydraulic (Subsea) Shuttle Valves SIL SM.009 0 Hydraulic (Subsea) Shuttle Valves Compiled By : G. Elliott, Date: 11/3/2014 Contents Terminology Definitions......3 Acronyms & Abbreviations..4 1. Introduction 5 1.1 Scope 5 1.2 Relevant Standards

More information

SPR - Pneumatic Spool Valve

SPR - Pneumatic Spool Valve SIL SM.008 Rev 7 SPR - Pneumatic Spool Valve Compiled By : G. Elliott, Date: 31/08/17 Contents Terminology Definitions:... 3 Acronyms & Abbreviations:... 4 1.0 Introduction... 5 1.1 Purpose & Scope...

More information

Eutectic Plug Valve. SIL Safety Manual. SIL SM.015 Rev 0. Compiled By : G. Elliott, Date: 19/10/2016. Innovative and Reliable Valve & Pump Solutions

Eutectic Plug Valve. SIL Safety Manual. SIL SM.015 Rev 0. Compiled By : G. Elliott, Date: 19/10/2016. Innovative and Reliable Valve & Pump Solutions SIL SM.015 Rev 0 Eutectic Plug Valve Compiled By : G. Elliott, Date: 19/10/2016 Contents Terminology Definitions......3 Acronyms & Abbreviations...4 1. Introduction..5 1.1 Scope 5 1.2 Relevant Standards

More information

DeZURIK. KGC Cast Knife Gate Valve. Safety Manual

DeZURIK. KGC Cast Knife Gate Valve. Safety Manual KGC Cast Knife Gate Valve Safety Manual Manual D11036 August 29, 2014 Table of Contents 1 Introduction... 3 1.1 Terms... 3 1.2 Abbreviations... 4 1.3 Product Support... 4 1.4 Related Literature... 4 1.5

More information

DeZURIK. KSV Knife Gate Valve. Safety Manual

DeZURIK. KSV Knife Gate Valve. Safety Manual KSV Knife Gate Valve Safety Manual Manual D11035 August 29, 2014 Table of Contents 1 Introduction... 3 1.1 Terms... 3 1.2 Abbreviations... 4 1.3 Product Support... 4 1.4 Related Literature... 4 1.5 Reference

More information

RESILIENT SEATED BUTTERFLY VALVES FUNCTIONAL SAFETY MANUAL

RESILIENT SEATED BUTTERFLY VALVES FUNCTIONAL SAFETY MANUAL Per IEC 61508 and IEC 61511 Standards BRAY.COM Table of Contents 1.0 Introduction.................................................... 1 1.1 Terms and Abbreviations...........................................

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Abc. X Series Ball Valve Company: Abc. Inc. Sellersville, PA USA Contract Number: Q11/12-345 Report No.: Abc 11/12-345 R001 Version V1, Revision

More information

DeZURIK Double Block & Bleed (DBB) Knife Gate Valve Safety Manual

DeZURIK Double Block & Bleed (DBB) Knife Gate Valve Safety Manual Double Block & Bleed (DBB) Knife Gate Valve Safety Manual Manual D11044 September, 2015 Table of Contents 1 Introduction... 3 1.1 Terms... 3 1.2 Abbreviations... 4 1.3 Product Support... 4 1.4 Related

More information

TRI LOK SAFETY MANUAL TRI LOK TRIPLE OFFSET BUTTERFLY VALVE. The High Performance Company

TRI LOK SAFETY MANUAL TRI LOK TRIPLE OFFSET BUTTERFLY VALVE. The High Performance Company TRI LOK TRI LOK TRIPLE OFFSET BUTTERFLY VALVE SAFETY MANUAL The High Performance Company Table of Contents 1.0 Introduction...1 1.1 Terms and Abbreviations... 1 1.2 Acronyms... 1 1.3 Product Support...

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Primary Elements Company: Rosemount Inc. (an Emerson Process Management company) Chanhassen, MN USA Contract Number: Q13/04-008 Report No.: ROS 13/04-008

More information

Reliability of Safety-Critical Systems Chapter 3. Failures and Failure Analysis

Reliability of Safety-Critical Systems Chapter 3. Failures and Failure Analysis Reliability of Safety-Critical Systems Chapter 3. Failures and Failure Analysis Mary Ann Lundteigen and Marvin Rausand mary.a.lundteigen@ntnu.no RAMS Group Department of Production and Quality Engineering

More information

Safety Manual VEGAVIB series 60

Safety Manual VEGAVIB series 60 Safety Manual VEGAVIB series 60 NAMUR Document ID: 32005 Contents Contents 1 Functional safety... 3 1.1 General information... 3 1.2 Planning... 4 1.3 Adjustment instructions... 6 1.4 Setup... 6 1.5 Reaction

More information

SIL explained. Understanding the use of valve actuators in SIL rated safety instrumented systems ACTUATION

SIL explained. Understanding the use of valve actuators in SIL rated safety instrumented systems ACTUATION SIL explained Understanding the use of valve actuators in SIL rated safety instrumented systems The requirement for Safety Integrity Level (SIL) equipment can be complicated and confusing. In this document,

More information

Understanding the How, Why, and What of a Safety Integrity Level (SIL)

Understanding the How, Why, and What of a Safety Integrity Level (SIL) Understanding the How, Why, and What of a Safety Integrity Level (SIL) Audio is provided via internet. Please enable your speaker (in all places) and mute your microphone. Understanding the How, Why, and

More information

Safety Manual VEGAVIB series 60

Safety Manual VEGAVIB series 60 Safety Manual VEGAVIB series 60 Contactless electronic switch Document ID: 32002 Contents Contents 1 Functional safety... 3 1.1 General information... 3 1.2 Planning... 4 1.3 Adjustment instructions...

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Isolating repeater 9164 Customer: R. STAHL Schaltgeräte GmbH Waldenburg Germany Contract No.: STAHL 16/08-032 Report No.: STAHL 16/08-032 R032 Version

More information

Achieving Compliance in Hardware Fault Tolerance

Achieving Compliance in Hardware Fault Tolerance Mirek Generowicz FS Senior Expert (TÜV Rheinland #183/12) Engineering Manager, I&E Systems Pty Ltd Abstract The functional safety standards ISA S84/IEC 61511 (1 st Edition, 2003) and IEC 61508 both set

More information

L&T Valves Limited SAFETY INTEGRITY LEVEL (SIL) VERIFICATION FOR HIGH INTEGRITY PRESSURE PROTECTION SYSTEM (HIPPS) Report No.

L&T Valves Limited SAFETY INTEGRITY LEVEL (SIL) VERIFICATION FOR HIGH INTEGRITY PRESSURE PROTECTION SYSTEM (HIPPS) Report No. L&T Valves Limited TAMIL NADU SAFETY INTEGRITY LEVEL (SIL) VERIFICATION FOR HIGH INTEGRITY PRESSURE PROTECTION SYSTEM (HIPPS) MAY 2016 Report No. 8113245702-100-01 Submitted to L&T Valves Ltd. Report by

More information

This manual provides necessary requirements for meeting the IEC or IEC functional safety standards.

This manual provides necessary requirements for meeting the IEC or IEC functional safety standards. Instruction Manual Supplement Safety manual for Fisher Vee-Ball Series Purpose This safety manual provides information necessary to design, install, verify and maintain a Safety Instrumented Function (SIF)

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Solenoid Valves SNMF 532 024 ** ** and SMF 52 024 ** ** Customer: ACG Automation Center Germany GmbH & Co. KG Tettnang Germany Contract No.: ACG

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Surge Protective Devices D9324S Customer: G.M. International s.r.l Villasanta Italy Contract No.: GM 16/02-055 Report No.: GM 16/02-055 R005 Version

More information

Safety Manual. Process pressure transmitter IPT-1* 4 20 ma/hart. Process pressure transmitter IPT-1*

Safety Manual. Process pressure transmitter IPT-1* 4 20 ma/hart. Process pressure transmitter IPT-1* Safety Manual Process pressure transmitter IPT-1* 4 20 ma/hart Process pressure transmitter IPT-1* Contents Contents 1 Functional safety 1.1 General information... 3 1.2 Planning... 4 1.3 Instrument parameter

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Solenoid Drivers KFD2-SL2-(Ex)1.LK.vvcc KFD2-SL2-(Ex)*(.B).vvcc Customer: Pepperl+Fuchs GmbH Mannheim Germany Contract No.: P+F 06/09-23 Report No.:

More information

Reliability of Safety-Critical Systems Chapter 4. Testing and Maintenance

Reliability of Safety-Critical Systems Chapter 4. Testing and Maintenance Reliability of Safety-Critical Systems Chapter 4. Testing and Maintenance Mary Ann Lundteigen and Marvin Rausand mary.a.lundteigen@ntnu.no RAMS Group Department of Production and Quality Engineering NTNU

More information

Safety Manual OPTISWITCH series relay (DPDT)

Safety Manual OPTISWITCH series relay (DPDT) Safety Manual OPTISWITCH series 5000 - relay (DPDT) 1 Content Content 1 Functional safety 1.1 In general................................ 3 1.2 Planning................................. 5 1.3 Adjustment

More information

Section 1: Multiple Choice

Section 1: Multiple Choice CFSP Process Applications Section 1: Multiple Choice EXAMPLE Candidate Exam Number (No Name): Please write down your name in the above provided space. Only one answer is correct. Please circle only the

More information

Safety manual for Fisher GX Control Valve and Actuator

Safety manual for Fisher GX Control Valve and Actuator Instruction Manual Supplement GX Valve and Actuator Safety manual for Fisher GX Control Valve and Actuator Purpose This safety manual provides information necessary to design, install, verify and maintain

More information

Valve Communication Solutions. Safety instrumented systems

Valve Communication Solutions. Safety instrumented systems Safety instrumented systems Safety Instrumented System (SIS) is implemented as part of a risk reduction strategy. The primary focus is to prevent catastrophic accidents resulting from abnormal operation.

More information

Neles trunnion mounted ball valve Series D Rev. 2. Safety Manual

Neles trunnion mounted ball valve Series D Rev. 2. Safety Manual Neles trunnion mounted ball valve Series D Rev. 2 Safety Manual 10SM D en 1/2017 2 Neles trunnion mounted ball valve, Series D Table of Contents 1 Introduction...3 2 Structure of the D series trunnion

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Digital Output Module Valve DOMV 9478/22-08-51 Company: R. STAHL Schaltgeräte GmbH Waldenburg Germany Contract No.: STAHL 11/01-104 Report No.: STAHL

More information

Implementing IEC Standards for Safety Instrumented Systems

Implementing IEC Standards for Safety Instrumented Systems Implementing IEC Standards for Safety Instrumented Systems ABHAY THODGE TUV Certificate: PFSE-06-607 INVENSYS OPERATIONS MANAGEMENT What is a Safety Instrumented System (SIS)? An SIS is designed to: respond

More information

Rosemount 2130 Level Switch

Rosemount 2130 Level Switch Rosemount 2130 Level Switch Functional Safety Manual Manual Supplement Reference Manual Contents Contents 1Section 1: Introduction 1.1 Scope and purpose of the safety manual.............................................

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Temperature transmitter PR5337 / PR6337 / PR7501 with 4..20 ma output Customer: PR electronics A/S Rønde Denmark Contract No.: PR electronics A/S

More information

Section 1: Multiple Choice Explained EXAMPLE

Section 1: Multiple Choice Explained EXAMPLE CFSP Process Applications Section 1: Multiple Choice Explained EXAMPLE Candidate Exam Number (No Name): Please write down your name in the above provided space. Only one answer is correct. Please circle

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: 3051S SIS Pressure Transmitter, with Safety Feature Board, Software Revision 3.0 Customer: Rosemount Inc. Chanhassen, MN USA Contract No.: Ros 02/11-07

More information

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, MN USA

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, MN USA Failure Modes, Effects and Diagnostic Analysis Project: 3095MV Mass Flow Transmitter Customer: Rosemount Inc. Chanhassen, MN USA Contract No.: Q04/04-09 Report No.: Ros 04/04-09 R001 Version V1, Revision

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Ground Monitoring Device 71**/5, 81**/5, 82**/5 Company: R. STAHL Schaltgeräte GmbH Waldenburg Germany Contract No.: STAHL 11/07-089 Report No.:

More information

Every things under control High-Integrity Pressure Protection System (HIPPS)

Every things under control High-Integrity Pressure Protection System (HIPPS) Every things under control www.adico.co info@adico.co Table Of Contents 1. Introduction... 2 2. Standards... 3 3. HIPPS vs Emergency Shut Down... 4 4. Safety Requirement Specification... 4 5. Device Integrity

More information

Understanding safety life cycles

Understanding safety life cycles Understanding safety life cycles IEC/EN 61508 is the basis for the specification, design, and operation of safety instrumented systems (SIS) Fast Forward: IEC/EN 61508 standards need to be implemented

More information

Ultima. X Series Gas Monitor

Ultima. X Series Gas Monitor Ultima X Series Gas Monitor Safety Manual SIL 2 Certified " The Ultima X Series Gas Monitor is qualified as an SIL 2 device under IEC 61508 and must be installed, used, and maintained in accordance with

More information

High performance disc valves Series Type BA, BK, BW, BM, BN, BO, BE, BH Rev Safety Manual

High performance disc valves Series Type BA, BK, BW, BM, BN, BO, BE, BH Rev Safety Manual High performance disc valves Series Type BA, BK, BW, BM, BN, BO, BE, BH Rev. 2.0 Safety Manual 10SM B Disc en 4/2018 2 High performance disc valves Series, Type BA, BK, BW, BM, BN, BO, BE, BH, Rev. 2.0

More information

High Integrity Pressure Protection Systems HIPPS

High Integrity Pressure Protection Systems HIPPS High Integrity Pressure Protection Systems HIPPS HIPPS > High Integrity Pressure Protection Systems WHAT IS A HIPPS The High Integrity Pressure Protection Systems (HIPPS) is a mechanical and electrical

More information

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA Failure Modes, Effects and Diagnostic Analysis Project: 3051C Pressure Transmitter Customer: Rosemount Inc. Chanhassen, Minnesota USA Contract No.: Ros 03/10-11 Report No.: Ros 03/10-11 R001 Version V1,

More information

SIL Safety Manual. ULTRAMAT 6 Gas Analyzer for the Determination of IR-Absorbing Gases. Supplement to instruction manual ULTRAMAT 6 and OXYMAT 6

SIL Safety Manual. ULTRAMAT 6 Gas Analyzer for the Determination of IR-Absorbing Gases. Supplement to instruction manual ULTRAMAT 6 and OXYMAT 6 ULTRAMAT 6 Gas Analyzer for the Determination of IR-Absorbing Gases SIL Safety Manual Supplement to instruction manual ULTRAMAT 6 and OXYMAT 6 ULTRAMAT 6F 7MB2111, 7MB2117, 7MB2112, 7MB2118 ULTRAMAT 6E

More information

Jamesbury Pneumatic Rack and Pinion Actuator

Jamesbury Pneumatic Rack and Pinion Actuator Jamesbury Pneumatic Rack and Pinion Actuator Valv-Powr Series VPVL Rev. 3.0 Safety Manual 10SM VPVL en 5/2017 2 Jamesbury Pneumatic Rack and Pinion Actuator, Valv-Powr Series VPVL, Rev 3.0, Safety Manual

More information

Rosemount 2120 Level Switch

Rosemount 2120 Level Switch Rosemount 2120 Level Switch Functional Safety Manual Manual Supplement Manual Supplement Contents Contents 1Section 1: Introduction 1.1 Scope and purpose of the safety manual.............................................

More information

SIL Safety Manual for Fisherr ED, ES, ET, EZ, HP, or HPA Valves with 657 / 667 Actuator

SIL Safety Manual for Fisherr ED, ES, ET, EZ, HP, or HPA Valves with 657 / 667 Actuator SIL Safety Manual ED, ES, ET, EZ, HP, HPA Valves w/ 657/667 Actuator SIL Safety Manual for Fisherr ED, ES, ET, EZ, HP, or HPA Valves with 657 / 667 Actuator Purpose This safety manual provides information

More information

REASSESSING FAILURE RATES

REASSESSING FAILURE RATES REASSESSING FAILURE RATES M. Generowicz, MIET, MIEAust, TÜV Rheinland FS Senior Expert A. Hertel, AMIChemE I&E Systems Pty Ltd SUMMARY In the context of process industries, automated safety functions are

More information

Safety Manual VEGASWING 61, 63. NAMUR With SIL qualification. Document ID: 52084

Safety Manual VEGASWING 61, 63. NAMUR With SIL qualification. Document ID: 52084 Safety Manual VEGASWING 61, 63 NAMUR With SIL qualification Document ID: 52084 Contents Contents 1 Document language 2 Scope 2.1 Instrument version... 4 2.2 Area of application... 4 2.3 SIL conformity...

More information

Reliability Analysis Including External Failures for Low Demand Marine Systems

Reliability Analysis Including External Failures for Low Demand Marine Systems Reliability Analysis Including External Failures for Low Demand Marine Systems KIM HyungJu a*, HAUGEN Stein a, and UTNE Ingrid Bouwer b a Department of Production and Quality Engineering NTNU, Trondheim,

More information

Vibrating Switches SITRANS LVL 200S, LVL 200E. Safety Manual. NAMUR With SIL qualification

Vibrating Switches SITRANS LVL 200S, LVL 200E. Safety Manual. NAMUR With SIL qualification Vibrating Switches SITRANS LVL 200S, LVL 200E NAMUR With SIL qualification Safety Manual Contents 1 Document language 2 Scope 2.1 Instrument version... 4 2.2 Area of application... 4 2.3 SIL conformity...

More information

Neles ValvGuard VG9000H Rev 2.0. Safety Manual

Neles ValvGuard VG9000H Rev 2.0. Safety Manual Neles ValvGuard VG9000H Rev 2.0 Safety Manual 10SM VG9000H en 11/2016 2 Neles ValvGuard VG9000H Rev 2.0 Safety Manual Table of Contents 1 General information...3 1.1 Purpose of the document... 3 1.2 Description

More information

THE IMPROVEMENT OF SIL CALCULATION METHODOLOGY. Jinhyung Park 1 II. THE SIL CALCULATION METHODOLOGY ON IEC61508 AND SOME ARGUMENT

THE IMPROVEMENT OF SIL CALCULATION METHODOLOGY. Jinhyung Park 1 II. THE SIL CALCULATION METHODOLOGY ON IEC61508 AND SOME ARGUMENT THE IMPROVEMENT OF SIL CALCULATION METHODOLOGY Jinhyung Park 1 1 Yokogawa Electric Korea: 21, Seonyu-ro45-gil Yeongdeungpo-gu, Seoul, 07209, Jinhyung.park@kr.yokogawa.com Safety Integrity Level (SIL) is

More information

EL-O-Matic E and P Series Pneumatic Actuator SIL Safety Manual

EL-O-Matic E and P Series Pneumatic Actuator SIL Safety Manual SIL Safety Manual DOC.SILM.EEP.EN Rev. 0 April 2017 EL-O-Matic E and P Series Pneumatic Actuator SIL Safety Manual schaal 1:1 EL Matic TM EL-O-Matic E and P Series DOC.SILM.EEP.EN Rev. 0 Table of Contents

More information

Standards. Certification. Education & Training. Publishing. Conferences & Exhibits. Table of Contents. View Excerpt. Buy the Book

Standards. Certification. Education & Training. Publishing. Conferences & Exhibits. Table of Contents. View Excerpt. Buy the Book Standards Certification Education & Training Publishing Conferences & Exhibits Table of Contents View Excerpt Buy the Book Safety Instrumented System Design By Iwan van Beurden, CFSE William M. Goble,

More information

Proof Testing A key performance indicator for designers and end users of Safety Instrumented Systems

Proof Testing A key performance indicator for designers and end users of Safety Instrumented Systems Proof Testing A key performance indicator for designers and end users of Safety Instrumented Systems EUR ING David Green BEng(hons) CEng MIET MInstMC RFSE Ron Bell OBE BSc CEng FIET Engineering Safety

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Variable area flow meter RAMC Customer: Rota Yokogawa GmbH & Co. KG Wehr Germany Contract No.: Rota Yokogawa 05/04-20 Report No.: Rota Yokogawa 05/04-20

More information

Functional safety. Functional safety of Programmable systems, devices & components: Requirements from global & national standards

Functional safety. Functional safety of Programmable systems, devices & components: Requirements from global & national standards Functional safety Functional safety of Programmable systems, devices & components: Requirements from global & national standards Matthias R. Heinze Vice President Engineering TUV Rheinland of N.A. Email

More information

FULL STAINLESS STEEL EXPLOSION-PROOF SOLUTIONS OIL & GAS I OFFSHORE AND ONSHORE

FULL STAINLESS STEEL EXPLOSION-PROOF SOLUTIONS OIL & GAS I OFFSHORE AND ONSHORE FULL STAINLESS STEEL EXPLOSION-PROOF SOLUTIONS OIL & GAS I OFFSHORE AND ONSHORE ASCO Numatics ASCO Numatics is the world leader in design, manufacturer of solenoid valves and accessories for both offshore

More information

YT-3300 / 3301 / 3302 / 3303 / 3350 / 3400 /

YT-3300 / 3301 / 3302 / 3303 / 3350 / 3400 / Smart positioner YT-3300 / 3301 / 3302 / 3303 / 3350 / 3400 / 3410 / 3450 Series SIL Safety Instruction. Supplement to product manual July. 2015 YTC Ver 1.06 1 Table of contents 1 Introduction... 3 1.1

More information

PROCESS AUTOMATION SIL. Manual Safety Integrity Level. Edition 2005 IEC 61508/61511

PROCESS AUTOMATION SIL. Manual Safety Integrity Level. Edition 2005 IEC 61508/61511 PROCESS AUTOMATION Manual Safety Integrity Level SIL Edition 2005 IEC 61508/61511 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of

More information

Continuous Gas Analysis. ULTRAMAT 6, OXYMAT 6 Safety Manual. Introduction 1. General description of functional safety 2

Continuous Gas Analysis. ULTRAMAT 6, OXYMAT 6 Safety Manual. Introduction 1. General description of functional safety 2 Introduction 1 General description of functional safety 2 Continuous Gas Analysis ULTRAMAT 6, OXYMAT 6 Device-specific safety instructions 3 List of abbreviations A Operating Instructions Supplement to

More information

Commissioning and safety manual

Commissioning and safety manual Commissioning and safety manual CNL35L DNL35L SIL2 LOREME 12, rue des Potiers d'etain Actipole BORNY - B.P. 35014-57071 METZ CEDEX 3 Phone 03.87.76.32.51 - Telefax 03.87.76.32.52 Contact: Commercial@Loreme.fr

More information

Accelerometer mod. TA18-S. SIL Safety Report

Accelerometer mod. TA18-S. SIL Safety Report Accelerometer mod. TA18-S SIL Safety Report SIL005/11 rev.1 of 03.02.2011 Page 1 of 7 1. Field of use The transducers are made to monitoring vibrations in systems that must meet particular technical safety

More information

A quantitative software testing method for hardware and software integrated systems in safety critical applications

A quantitative software testing method for hardware and software integrated systems in safety critical applications A quantitative software testing method for hardware and software integrated systems in safety critical applications Hai ang a, Lixuan Lu* a a University of Ontario Institute of echnology, Oshawa, ON, Canada

More information

Analysis of Instrumentation Failure Data

Analysis of Instrumentation Failure Data Analysis of Instrumentation Failure Data A structured approach Standards Certification Education & Training Publishing Conferences & Exhibits Matthew F. (Matt) Murphy Senior Consultant, DuPont Engineering

More information

DETERMINATION OF SAFETY REQUIREMENTS FOR SAFETY- RELATED PROTECTION AND CONTROL SYSTEMS - IEC 61508

DETERMINATION OF SAFETY REQUIREMENTS FOR SAFETY- RELATED PROTECTION AND CONTROL SYSTEMS - IEC 61508 DETERMINATION OF SAFETY REQUIREMENTS FOR SAFETY- RELATED PROTECTION AND CONTROL SYSTEMS - IEC 61508 Simon J Brown Technology Division, Health & Safety Executive, Bootle, Merseyside L20 3QZ, UK Crown Copyright

More information

New Thinking in Control Reliability

New Thinking in Control Reliability Doug Nix, A.Sc.T. Compliance InSight Consulting Inc. New Thinking in Control Reliability Or Your Next Big Headache www.machinerysafety101.com (519) 729-5704 Control Reliability Burning Questions from the

More information

Session: 14 SIL or PL? What is the difference?

Session: 14 SIL or PL? What is the difference? Session: 14 SIL or PL? What is the difference? Stewart Robinson MIET MInstMC Consultant Engineer, Pilz Automation Technology UK Ltd. EN ISO 13849-1 and EN 6061 Having two different standards for safety

More information

Safety Integrity Verification and Validation of a High Integrity Pressure Protection System (HIPPS) to IEC 61511

Safety Integrity Verification and Validation of a High Integrity Pressure Protection System (HIPPS) to IEC 61511 Safety Integrity Verification and Validation of a High Integrity Pressure Protection System (HIPPS) to IEC 61511 Abstract Author: Colin Easton ProSalus Limited ~ Independent Safety Consultants A key requirement

More information

AUTHOR(S) CLIENT(S) Multiclient - PDS Forum CLASS. THIS PAGE ISBN PROJECT NO. NO. OF PAGES/APPENDICES

AUTHOR(S) CLIENT(S) Multiclient - PDS Forum CLASS. THIS PAGE ISBN PROJECT NO. NO. OF PAGES/APPENDICES TITLE SINTEF REPORT SINTEF Technology and Society Safety Research Address: NO-7465 Trondheim, NORWAY Location: S P Andersens veg 5 NO-7031 Trondheim Telephone: +47 73 59 27 56 Fax: +47 73 59 28 96 Enterprise

More information

H250 M9 Supplementary instructions

H250 M9 Supplementary instructions H250 M9 Supplementary instructions Variable area flowmeter Safety manual acc. to IEC 61508:2010 KROHNE CONTENTS H250 M9 1 Introduction 3 1.1 Fields of application... 3 1.2 User benefits... 3 1.3 Relevant

More information

YT-300 / 305 / 310 / 315 / 320 / 325 Series

YT-300 / 305 / 310 / 315 / 320 / 325 Series Volume Booster YT-300 / 305 / 310 / 315 / 320 / 325 Series SIL Safety Instruction. Supplement to product manual Apr. 2016 YTC Ver. 2.01 1 Table of contents 1 Introduction... 3 1.1 Purpose of this document...

More information

Impact of Common Cause Failure on Reliability Performance of Redundant Safety Related Systems Subject to Process Demand

Impact of Common Cause Failure on Reliability Performance of Redundant Safety Related Systems Subject to Process Demand Impact of Common Cause Failure on Reliability Performance of Redundant Safety Related Systems Subject to Process Demand Siamak Alizadeh a, Srinivas Sriramula b School of Engineering, University of Aberdeen,

More information

PL estimation acc. to EN ISO

PL estimation acc. to EN ISO PL estimation acc. to EN ISO 3849- Example calculation for an application MAC Safety / Armin Wenigenrath, January 2007 Select the suitable standard for your application Reminder: The standards and the

More information

What is Good Practice for the Proof Testing of Safety Instrumented Systems of Low Safety Integrity?

What is Good Practice for the Proof Testing of Safety Instrumented Systems of Low Safety Integrity? SYMPOSIUM SRIS NO 59 HAZARDS IChem What is Good Practice for the Proof Testing of Safety Instrumented Systems of ow Safety Integrity? Jeff Wood BSc, Cng, FIMC, MIT, Ineos ChlorVinyls Runcorn Site, PO Box

More information

innova-ve entrepreneurial global 1

innova-ve entrepreneurial global 1 www.utm.my innova-ve entrepreneurial global Safety Integrity Level (SIL) is defined as: Relative level of risk-reduction provided by a safety function to specify a target level of risk reduction. SIL is

More information

What safety level can be reached when combining a contactor with a circuitbreaker for fail-safe switching?

What safety level can be reached when combining a contactor with a circuitbreaker for fail-safe switching? FAQ 01/2015 What safety level can be reached when combining a contactor with a circuitbreaker for fail-safe switching? SIRIUS Safety Integrated http://support.automation.siemens.com/ww/view/en/40349715

More information

C. Mokkapati 1 A PRACTICAL RISK AND SAFETY ASSESSMENT METHODOLOGY FOR SAFETY- CRITICAL SYSTEMS

C. Mokkapati 1 A PRACTICAL RISK AND SAFETY ASSESSMENT METHODOLOGY FOR SAFETY- CRITICAL SYSTEMS C. Mokkapati 1 A PRACTICAL RISK AND SAFETY ASSESSMENT METHODOLOGY FOR SAFETY- CRITICAL SYSTEMS Chinnarao Mokkapati Ansaldo Signal Union Switch & Signal Inc. 1000 Technology Drive Pittsburgh, PA 15219 Abstract

More information

Proposed Abstract for the 2011 Texas A&M Instrumentation Symposium for the Process Industries

Proposed Abstract for the 2011 Texas A&M Instrumentation Symposium for the Process Industries Proposed Abstract for the 2011 Texas A&M Instrumentation Symposium for the Process Industries Focus Area: Automation HMI Title: Author: Shared Field Instruments in SIS: Incidents Caused by Poor Design

More information

Double whammy: the benefits of valve signatures and partial stroke testing

Double whammy: the benefits of valve signatures and partial stroke testing Double whammy: the benefits of valve signatures and partial stroke testing By Paul Gruhn, P.E., C.F.S.E., L&M Engineering and Derek Essam, Drallim Abstract Many papers have been written over the past five

More information

Session One: A Practical Approach to Managing Safety Critical Equipment and Systems in Process Plants

Session One: A Practical Approach to Managing Safety Critical Equipment and Systems in Process Plants Session One: A Practical Approach to Managing Safety Critical Equipment and Systems in Process Plants Tahir Rafique Lead Electrical and Instruments Engineer: Qenos Botany Site Douglas Lloyd Senior Electrical

More information

Functional Safety SIL Safety Instrumented Systems in the Process Industry

Functional Safety SIL Safety Instrumented Systems in the Process Industry Products Solutions Services Functional Safety SIL Safety Instrumented Systems in the Process Industry BASF - Press Photo 2 section Foreword rubric 3 Foreword has come into focus since the publication of

More information

Improving Reliability & Safety Performance of Solenoid Valves by Stroke Testing

Improving Reliability & Safety Performance of Solenoid Valves by Stroke Testing Improving Reliability & Safety Performance of Solenoid Valves by Stroke Testing Loren L. Stewart, BSME, CFSE exida 80 N. Main St., Sellersville, Pa 18960 lstewart@exida.com Julia V. Bukowski, Ph.D. Dept.

More information

COMPLIANCE with IEC EN and IEC EN 61511

COMPLIANCE with IEC EN and IEC EN 61511 COMPLIANCE with IEC EN 61508 and IEC EN 61511 Certificate No.: C- IS-260811 01 CERTIFICATE OWNER: ORION S.p.A. VIA CABOTO, 8 I-34148 TRIESTE (Italy) WE HEREWITH CONFIRM THAT THE ANALYSIS DEVELOPED BY ORION;

More information

model for functional safety of

model for functional safety of Application of Weibull reliability model for functional safety of electro-hydraulic system 1 When the safety of the machinery users relies on a reliable function of the control system, than a safety function

More information

PREDICTING HEALTH OF FINAL CONTROL ELEMENT OF SAFETY INSTRUMENTED SYSTEM BY DIGITAL VALVE CONTROLLER

PREDICTING HEALTH OF FINAL CONTROL ELEMENT OF SAFETY INSTRUMENTED SYSTEM BY DIGITAL VALVE CONTROLLER PREDICTING HEALTH OF FINAL CONTROL ELEMENT OF SAFETY INSTRUMENTED SYSTEM BY DIGITAL VALVE CONTROLLER Riyaz Ali FIELDVUE Business Development Manager Fisher Controls Int'l., LLC. Marshalltown, IA 50158

More information

The Risk of LOPA and SIL Classification in the process industry

The Risk of LOPA and SIL Classification in the process industry The Risk of LOPA and SIL Classification in the process industry Mary Kay O Connor Process Safety Center International Symposium Beyond Regulatory Compliance, Making Safety Second Nature October 28-29,

More information

CHANGE HISTORY DISTRIBUTION LIST

CHANGE HISTORY DISTRIBUTION LIST Issue Date of Issue CR/DR Numbers CHANGE HISTORY No. of Pages Draft A Aug 2011 N/A 28 Draft Issue Pages Changed and Reasons for Change Sept 2011 N/A 28 Formal issue with client comments from draft issue

More information

Service & Support. Questions and Answers about the Proof Test Interval. Proof Test According to IEC FAQ August Answers for industry.

Service & Support. Questions and Answers about the Proof Test Interval. Proof Test According to IEC FAQ August Answers for industry. Cover sheet Questions and Answers about the Proof Test Interval Proof Test According to IEC 62061 FAQ August 2012 Service & Support Answers for industry. Contents This entry originates from the Siemens

More information

Transmitter mod. TR-A/V. SIL Safety Report

Transmitter mod. TR-A/V. SIL Safety Report Transmitter mod. TR-A/V SIL Safety Report SIL003/09 rev.1 del 09.03.2009 Pagina 1 di 7 1. Employ field The transmitters are dedicated to the vibration monitoring in plants where particular safety requirements

More information

Advanced LOPA Topics

Advanced LOPA Topics 11 Advanced LOPA Topics 11.1. Purpose The purpose of this chapter is to discuss more complex methods for using the LOPA technique. It is intended for analysts who are competent with applying the basic

More information