Mass Split of Two-Phase-Flow

Size: px
Start display at page:

Download "Mass Split of Two-Phase-Flow"

Transcription

1 Mass Split of Two-Phase-Flow The split of two-phase-flow at horizontal side-t-junctions in unbalanced pipe systems for clean extinguishing agents Speaker: Gudrun Fay Minimax

2 Content 1. Applications of clean extinguishing agents 2. Characteristics of two-phase flow 3. Experimental Setup and Data Collection 4. Comparison of results 5. Verification 6. Conclusions 2

3 Applications of clean agent systems Clean agents have many advantages Protection of sensitive electronic equipment Safe extinguishing concentrations below LOAL Very small agent storage volume 3

4 Applications of clean agent systems but they have some properties that cause challenges for designers: To extinguish a fire the fluid has to change from a liquid into a vapor. Boiling pressure at 70 F is near (HFC227ea) or even lower (FK ) ambient conditions (16 psi / 1 bar). The agent must leave the system with high velocity and obstructions near the nozzles have to be avoided. The system has to be pressurized with nitrogen. The mixture of agent and nitrogen creates two-phase flow with changing gas content in the pipe system. Modeling the hydraulic system is made complex by the two-phase flow. 4

5 Characteristics of two-phase flow Specific properties of two-phase flow Liquid-gas separation at low speed Differing flow pattern at horizontal and vertical pipes bubbles Increasing gas content with decreasing pressure Unequal split of liquid and gas at side-t-junctions flow direction bubble 5

6 Characteristics of two-phase flow Side-T 90 with water/air flow top view v 1 = kg/s Gas content x1: 0.21 % x3: 0.55 % p 1 = 14.8 bar D 1 =D 2 =D 3 =38 mm (Hwang, 1988) 6

7 Experimental Setup Test Arrangement for Side-T modeling Feeding 40 l container pipe and with straight 48 kg pipe: extinguishing 1 ½ agent (fill 90 density side = pipe: 1.2 kg/l) ½ Mass 610 psi split (42 from bar) 10% fill pressure to 35% into 70 F the (21 C) side container pipe temperature Mass flow feeding pipe 4.8 kg/s 64 F 75 F (18 C 24 C) ambient Straight pipe temperature flow divided equally by a bullhead-t ends in two identical nozzles 7

8 Experimental Setup Experimental setup Pressure transducer at the top of the container (in the nitrogen blanket) Pressure measurement at the start of the pipe system (behind valve) Pressure measurement at all nozzle 8

9 Experimental Setup Preparing the container Welded sockets at the top for pressure and temperature measurement Construction to shake filled container in a horizontal position Temperature is adjusted manually with a gas burner 9

10 Experimental Setup Data collection Socket for pressure transducer at the top of container (nitrogen blanket) Sockets for pressure transducer and thermocouple behind the hose and direction valve Sockets for pressure and temperature before each nozzle 10

11 Experimental Setup Agent collection at discharge Better First try 11

12 Experimental Setup Agent Collection at discharge 250 l bin, collected agent is weighed on a platform scale Plastic bag to collect drops and lead agent into the bin Metal can with 250 mm diameter around the nozzles to stop horizontal flying droplets 12

13 Comparison of Results Discharge at side nozzle Nozzle orifices: 10%: 4.1 mm 15%: 5.1 mm 20%: 6.1 mm 25%: 7.0 mm 30%: 7.8 mm 35%: 8.7 mm 13

14 Comparison of Results Discharge at side nozzle Nozzle orifices: 10%: 4.1 mm 15%: 5.1 mm 20%: 6.1 mm 25%: 7.0 mm 30%: 7.8 mm 35%: 8.7 mm 14

15 Comparison of Results Discharge at side nozzle Nozzle orifices: 10%: 4.1 mm 15%: 5.1 mm 20%: 6.1 mm 25%: 7.0 mm 30%: 7.8 mm 35%: 8.7 mm 15

16 Comparison of Results Discharge at side nozzle Nozzle orifices: 10%: 4.1 mm 15%: 5.1 mm 20%: 6.1 mm 25%: 7.0 mm 30%: 7.8 mm 35%: 8.7 mm 16

17 Verification Verification Tests Various container sizes: 40 l to 180 l Variable fill pressure: 360 psi, 610 psi, 725 psi Variable fill density: 0.4 to 1.2 Different pipe systems: pipe diameter ½ to 2 17

18 Verification - Test 1 Filling pressure 610 psi (42 bar) Container size Filling amount Fill density 100 l kg 1.2 kg/l 18

19 Verification - Test 1 Nozzle 5 Nozzles Exp kg kg Calc kg kg Dev. 3.1 % -0.2 % 19

20 Verification - Test 2 Filling pressure 610 psi (42 bar) Container size Filling amount Fill density 80 l 62,0 kg 0.78 kg/l 20

21 Verification - Test 2 Nozzle 5 Nozzles Exp. 6.5 kg 53.8 kg Calc. 6.1 kg 54.5 kg Dev % 1.3 % 21

22 Verification - Test 3 Filling pressure Container size 610 psi (42 bar) 80 l Filling amount 75,0 kg Fill density 0.94 kg/l 22

23 Verification - Test 3 Nozzle 5 Nozzles Exp kg 50.2 kg Calc kg 48.5 kg Dev. 8.0 % -3.5 % 23

24 Verification - Test 4 Filling pressure Container size 360 psi (25 bar) 40 l Filling amount 45,6 kg Fill density 1.14 kg/l 24

25 Verification - Test 4 Nozzle 5 Nozzles Exp kg kg Calc kg kg Dev % 1.5 % 25

26 Verification Summary of Results Summary of verification tests Deviation of side-flow at verification tests Test No. Mass split Deviation 10% 1 10 % -6.6 % 2 14 % 3.1 % 3 34 % 8.0 % Deviation of the side flow 5% 0% -5% 4 35 % -3.4 % -10% 0% 10% 20% 30% 40% mass split 26

27 Conclusions Result of tests: Deviation in discharge is below 10 % at all test cases Conclusions: The model is valid for mass splits from 10% to 35% to the side. The model does not depend from the parameters of the feeding container. It is suitable for typical pipe dimensions of clean agent systems. It gives opportunities in the individual design of unbalanced pipe system. 27

The Split of Two-Phase-Flow at Horizontal Side-T-junctions in Unbalanced Pipe Systems for Clean Extinguishing Agents

The Split of Two-Phase-Flow at Horizontal Side-T-junctions in Unbalanced Pipe Systems for Clean Extinguishing Agents The Split of Two-Phase-Flow at Horizontal Side-T-junctions in Unbalanced Pipe Systems for Clean Extinguishing Agents Abstract by Gudrun Fay Minimax GmbH & CO. KG Industriestraße 10-12, 23840 Bad Oldesloe,

More information

CLEAN AGENT FIRE EXTINGUISHING SYSTEM MX 1230 Extinguishing Agent Cylinders

CLEAN AGENT FIRE EXTINGUISHING SYSTEM MX 1230 Extinguishing Agent Cylinders The technical data described herein is for components of the Minimax Fire Products MX 30 Clean Agent System. For design, installation, and operation instructions, refer to the latest edition of the original

More information

Joint industry project on foam

Joint industry project on foam Joint industry project on foam, E.D. Nennie (TNO Fluid dynamics) W. Schiferli (Shell Projects & Technology) 2 Introduction Foamers are used for gas well deliquification. Lab tests are being used to evaluate

More information

Chapter 9. Forces and Fluids

Chapter 9. Forces and Fluids Chapter 9 Forces and Fluids Key Terms hydraulic systems incompressible mass neutral buoyancy pascal pneumatic systems pressure unbalanced forces weight Archimedes principle average density balanced forces

More information

Design Review Agenda

Design Review Agenda Design Review Agenda 1) Introduction, Motivation, and Previous Work a. Previous Work and Accomplishments i. Platform Launches ii. Successful Test Firings 2) More In-Depth Design Overview of the Existing

More information

Paper 2.2. Operation of Ultrasonic Flow Meters at Conditions Different Than Their Calibration

Paper 2.2. Operation of Ultrasonic Flow Meters at Conditions Different Than Their Calibration Paper 2.2 Operation of Ultrasonic Flow Meters at Conditions Different Than Their Calibration Mr William Freund, Daniel Measurement and Control Mr Klaus Zanker, Daniel Measurement and Control Mr Dale Goodson,

More information

Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events

Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events K. Takase 1), H. Akimoto 1) 1) Japan Atomic Energy Research Institute (JAERI),

More information

Safety instructions and operating manual

Safety instructions and operating manual 5-Master Safety instructions and operating manual TBF-PyroTec GmbH Lichterfelder Str. 5 A 21502 Geesthacht Tel.: + 49 (0)4152 157 9950 Fax: + 49 (0)4152 157 9951 Flame projector 5-Master Safety instructions

More information

TWO PHASE FLOW METER UTILIZING A SLOTTED PLATE. Acadiana Flow Measurement Society

TWO PHASE FLOW METER UTILIZING A SLOTTED PLATE. Acadiana Flow Measurement Society TWO PHASE FLOW METER UTILIZING A SLOTTED PLATE Acadiana Flow Measurement Society Gerald L. Morrison Presented by: Mechanical Engineering Department Daniel J. Rudroff 323 Texas A&M University Flowline Meters

More information

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65 Data Sheet 819346-02 Issue Date: 05/17 Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300, 50, 65 UNA 45hl MAX, UNA 46hl MAX, UNA 46Ahl MAX UNA 45v MAX with cover for mounting electrode

More information

Process Dynamics, Operations, and Control Lecture Notes - 20

Process Dynamics, Operations, and Control Lecture Notes - 20 Lesson 0. Control valves 0.0 Context Controller output is a signal that varies between 0 and 100%. Putting this signal to use requires a final control element, a device that responds to the controller

More information

Grade 8 Science: Unit 2-Fluids Chapter 9: Force, Pressure Area

Grade 8 Science: Unit 2-Fluids Chapter 9: Force, Pressure Area Grade 8 Science: Unit 2-Fluids Chapter 9: Force, Pressure Area Key Terms: hydraulic systems, incompressible, mass, neutral buoyancy, pascal, pneumatic systems, pressure, unbalanced forces, weight, Archimedes

More information

Smart Water Application Technologies (SWAT)

Smart Water Application Technologies (SWAT) Smart Water Application Technologies (SWAT) Turf and Landscape Irrigation Equipment PRESSURE REGULATING SPRAY HEAD SPRINKLERS Equipment Functionality Test Testing Protocol Version 3.0 (May 2012) Developed

More information

WaterSense Specification for Spray Sprinkler Bodies. Version 1.0

WaterSense Specification for Spray Sprinkler Bodies. Version 1.0 Version 1.0 September 21, 2017 WaterSense Specification for Spray Sprinkler Bodies 1.0 Scope and Objective This specification establishes the criteria for labeling bodies of spray sprinklers 1 under the

More information

FIREX200 CLEAN AGENT FIRE SUPPRESSION SYSTEM

FIREX200 CLEAN AGENT FIRE SUPPRESSION SYSTEM CYLINDERS Agent Tank The agent storage tank consists of a high pressure steel tank fitted with a valve and internal siphon tube, factory filled with FIREX200 gas (HFC-227 ea), and super-pressurized with

More information

Procedure of Xenon Transfer

Procedure of Xenon Transfer Procedure of Xenon Transfer Feng Zhou,MIT CC: Martina Green February 28, 2005 In this write up, we discuss the procedure on how to transfer xenon to a designed gas storage vessel that supplies xenon to

More information

Old-Exam.Questions-Ch-14 T072 T071

Old-Exam.Questions-Ch-14 T072 T071 Old-Exam.Questions-Ch-14 T072 Q23. Water is pumped out of a swimming pool at a speed of 5.0 m/s through a uniform hose of radius 1.0 cm. Find the mass of water pumped out of the pool in one minute. (Density

More information

CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO Walnut Lake Rd th Street Houston TX Garner, IA 50438

CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO Walnut Lake Rd th Street Houston TX Garner, IA 50438 CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO. 10 Jerry Paul Smith Joel Clancy JPS Measurement Consultants, Inc Colorado Engineering Experiment Station, Inc (CEESI) 13002 Walnut Lake

More information

TRAINING ON ANTAM STANDARD CODE For TESTING OF KNAPSACK MISTERS CUM DUSTERS

TRAINING ON ANTAM STANDARD CODE For TESTING OF KNAPSACK MISTERS CUM DUSTERS TRAINING ON ANTAM STANDARD CODE For TESTING OF KNAPSACK MISTERS CUM DUSTERS PART - 8: TESTS & CHECKS FOR PERFORMANCE 2 16-28 October2016, Nanjing China 2nd Training of Trainers on ANTAM Codes Organized

More information

Ball Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6"

Ball Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3, 4, 6 Data Sheet 819584-00 Issue Date: 01/17 Ball Float Steam Trap UNA 43 PN 16/C 125/JIS 10K UNA 46 PN 40/C 150/C 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6" UNA 43 hl, UNA 46 hl UNA 43 v, UNA 46 v with

More information

Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765

Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765 Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765 Application Single-acting positioner for attachment to pneumatic control valves. Supplied with either an electric input signal from

More information

A review of best practices for Selection, Installation, Operation and Maintenance of Gas meters for Flare Applications used for Managing facility

A review of best practices for Selection, Installation, Operation and Maintenance of Gas meters for Flare Applications used for Managing facility A review of best practices for Selection, Installation, Operation and Maintenance of Gas meters for Flare Applications used for Managing facility mass balance and compliance 1. What, When and Why? 2. Flare

More information

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles International Journal of Engineering Research and Development e-issn: 7-067X, p-issn: 7-00X, www.ijerd.com Volume 3, Issue 4 (August ), PP. 33-39 Experimental Analysis on Vortex Tube Refrigerator Using

More information

COMMITTEE DRAFT. API 520 Part I 10 th Edition Ballot Item 2.1. This ballot covers the following item:

COMMITTEE DRAFT. API 520 Part I 10 th Edition Ballot Item 2.1. This ballot covers the following item: This ballot covers the following item: API 520 Part I 10 th Edition Ballot Item 2.1 2008 12 Modify guidance to PRV datasheets (Line 17) to assist user s with determining the temperature to use for selecting

More information

PROCESS MONITORING AND CONTROL

PROCESS MONITORING AND CONTROL Chemical Engineering Process Design PROCESS MONITORING AND CONTROL Keith Marchildon David Mody Monitoring means Measurement 1. There is no Control without Monitoring 2. Monitoring should not be done without

More information

Experimental Analysis and CFD Simulation of Pressure Drop of Carbon Dioxide in Horizontal Micro Tube Heat Exchangers

Experimental Analysis and CFD Simulation of Pressure Drop of Carbon Dioxide in Horizontal Micro Tube Heat Exchangers Internatıonal Journal of Natural and Engineering Sciences 8 (2): 15-20, 2014 ISSN: 1307-1149, E-ISSN: 2146-0086, www.nobel.gen.tr Experimental Analysis and CFD Simulation of Pressure Drop of Carbon Dioxide

More information

Application Note 13: Electron Microscope Decontamination

Application Note 13: Electron Microscope Decontamination The Chlorine Dioxide People Providing you with gaseous chlorine dioxide solutions for your decontamination needs Application Note 13: Electron Microscope Decontamination M Uses: An electron microscope

More information

New power in production logging

New power in production logging New power in production logging Locating the zones where fluids enter the wellbore in a producing or injecting well is an important aspect of production logging. It is relatively straightforward to establish

More information

Air Bubble Departure on a Superhydrophobic Surface

Air Bubble Departure on a Superhydrophobic Surface Air Bubble Departure on a Superhydrophobic Surface A. Kibar 1, R. Ozbay 2, C.H. Choi 2 1 Department of Mechanical and Material Technologies, Kocaeli University, 41285, Kocaeli, Turkey 2 Department of Mechanical

More information

Numerical Investigation of Air Bubbles Evolution and Coalescence from Submerged Orifices Based on OpenFOAM

Numerical Investigation of Air Bubbles Evolution and Coalescence from Submerged Orifices Based on OpenFOAM Numerical Investigation of Air Bubbles Evolution and Coalescence from Submerged Orifices Based on OpenFOAM Pan Feng, He Ying, Li-zhong Mu 2018-7-6 Dalian University of Technology, China Outline Background

More information

RESIDENTIAL WATER DISTRIBUTION

RESIDENTIAL WATER DISTRIBUTION RESIDENTIAL WATER DISTRIBUTION This case study demonstrates the steady-state simulation of the fresh water (drinking water) reticulation system in a small village. WATER RETICULATION Page1 WATER RETICULATION

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 3-2 Orifice Plates EXERCISE OBJECTIVE In this exercise, you will study how differential pressure flowmeters operate. You will describe the relationship between the flow rate and the pressure drop

More information

Chapter 16 Test. Directions: Write the correct letter on the blank before each question.

Chapter 16 Test. Directions: Write the correct letter on the blank before each question. Chapter 16 Test Name: Date: Directions: Write the correct letter on the blank before each question. Objective 1: Explain the way vaporization and steam relate to the extinguishing properties of water.

More information

Key Terms Chapter 7. boiling boiling point change of state concentration condensation deposition evaporation flow rate fluid freezing point

Key Terms Chapter 7. boiling boiling point change of state concentration condensation deposition evaporation flow rate fluid freezing point Foldable Activity Using the instructions on page 267 in your textbook on how to make foldables, write a key term on each front tab, and the definition on the inside (see example that I made up). You will

More information

WP2 Fire test for toxicity of fire effluents

WP2 Fire test for toxicity of fire effluents Pagina 3 di 89 TRA SFEU VTT 22.6.2009 v.2 WP2 Fire test for toxicity of fire effluents Task 2.1.2 Development of small-scale test method for fire effluents Step 1: Use of modeling Plans according to DoW:

More information

SINGLE VALVE WITH LOW-FLOW BYPASS

SINGLE VALVE WITH LOW-FLOW BYPASS CONTROL VALVES Pressure Reducing Valve Sizing Guide Sizing pilot operated reducing valves is not a complicated process. It starts with determining requirements and following these guidelines in valve size

More information

This portion of the piping tutorial covers control valve sizing, control valves, and the use of nodes.

This portion of the piping tutorial covers control valve sizing, control valves, and the use of nodes. Piping Tutorial A piping network represents the flow of fluids through several pieces of equipment. If sufficient variables (flow rate and pressure) are specified on the piping network, CHEMCAD calculates

More information

VERTICAL BLADDER TANK

VERTICAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Tight Spaces UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

Chapter 14 Fluids Mass Density Pressure Pressure in a Static Fluid Pascal's Principle Archimedes' Principle

Chapter 14 Fluids Mass Density Pressure Pressure in a Static Fluid Pascal's Principle Archimedes' Principle Chapter 14 Fluids Mass Density Pressure Pressure in a Static Fluid Pascal's Principle Archimedes' Principle Fluids in Motion The Equation of Continuity DEFINITION OF MASS DENSITY The mass density ρ is

More information

HORIZONTAL BLADDER TANK

HORIZONTAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Low Ceilings UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

ME 333 Fluid Mechanics. Lab Session VISCOUS LOSSES IN PIPES

ME 333 Fluid Mechanics. Lab Session VISCOUS LOSSES IN PIPES ME 333 Fluid Mechanics Lab Session VISCOUS LOSSES IN PIPES Introduction Flow in pipes, laminar or turbulent, is subject to pressure losses that result from the viscous stresses on the wall of the pipe.

More information

The water supply for a hydroelectric plant is a reservoir with a large surface area. An outlet pipe takes the water to a turbine.

The water supply for a hydroelectric plant is a reservoir with a large surface area. An outlet pipe takes the water to a turbine. Fluids 1a. [1 mark] The water supply for a hydroelectric plant is a reservoir with a large surface area. An outlet pipe takes the water to a turbine. State the difference in terms of the velocity of the

More information

EDUCTOR. principle of operation

EDUCTOR. principle of operation EDUCTOR principle of operation condensate and mixing eductor s are designed to mix two liquids intimately in various proportions in operations where the pressure liquid is the greater proportion of the

More information

Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124

Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124 Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124 13.7 Pressure Equipment Directive (PED) 97/23/EC 1 The Pressure Equipment Directive (PED) 97/23/EC applies to the design, manufacturing and conformity

More information

Impact of imperfect sealing on the flow measurement of natural gas by orifice plates

Impact of imperfect sealing on the flow measurement of natural gas by orifice plates Impact of imperfect sealing on the flow measurement of natural gas by orifice plates Rubens Silva Telles 1, Kazuto Kawakita 2 1 IPT Instituto de Pesquisas Tecnológicas, São Paulo, Brazil, rtelles@ipt.br

More information

CFD Flow Analysis of a Refrigerant inside Adiabatic Capillary Tube

CFD Flow Analysis of a Refrigerant inside Adiabatic Capillary Tube CFD Flow Analysis of a Refrigerant inside Adiabatic Capillary Tube Y Raja Kumar ¹, Dr.P Usha sri ² PG Student¹, Associate professor² Department of Mechanical Engineering, University College of Engineering

More information

STUDY OF SLUG CONTROL TECHNIQUES IN PIPELINE SYSTEMS

STUDY OF SLUG CONTROL TECHNIQUES IN PIPELINE SYSTEMS STUDY OF SLUG CONTROL TECHNIQUES IN PIPELINE SYSTEMS JOSÉ L. A,VIDAL Petrobrás Research Center - CENPES/PDEP/TOOL Av.Horácio de Macedo 95- Cidade Universitária 191-915 -Rio de Janeiro-RJ E-mail:josearias@petrobras.com.br

More information

Cavitation in Valves

Cavitation in Valves VM CAV/WP White Paper Cavitation in Valves Table of Contents Introduction............................... 2 Cavitation Analysis.......................... 2 Cavitation Data............................. 3

More information

Natural Gas Conversion Kit

Natural Gas Conversion Kit SERIAL #: Attention: Centro recommends that a qualified gas technician perform the gas supply conversion and orifice replacement for this BBQ model. Natural Gas Conversion Kit F O R U S E W I T H M O D

More information

Correction of Pressure Drop in Steam and Water System in Performance Test of Boiler

Correction of Pressure Drop in Steam and Water System in Performance Test of Boiler IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Correction of Pressure Drop in Steam and Water System in Performance Test of Boiler To cite this article: Jinglong Liu et al 2018

More information

Restriction Orifice. Single or Multi Stage Orifice to. Reduce Pressure or. Limit the Flow Rate

Restriction Orifice. Single or Multi Stage Orifice to. Reduce Pressure or. Limit the Flow Rate Restriction Orifice Single or Multi Stage Orifice to Reduce Pressure or Limit the Flow Rate Restriction Orifice Plates Series ROPS Principle Restriction Orifice Plates and Critical Flow Devices and their

More information

SPECIFYING MOTIONLESS MIXERS

SPECIFYING MOTIONLESS MIXERS SPECIFYING MOTIONLESS MIXERS The operating cost for the energy necessary to mix fluids with a motionless mixer is usually far lower than for any competitive mixing technique. An extruder which melts, mixes

More information

Slide 1 / What is the density of an aluminum block with a mass of 4050 kg and volume of 1.5 m 3?

Slide 1 / What is the density of an aluminum block with a mass of 4050 kg and volume of 1.5 m 3? Slide 1 / 68 1 What is the density of an aluminum block with a mass of 4050 kg and volume of 1.5 m 3? Slide 2 / 68 2 What is the mass of a rectangular shaped ice block with dimensions of 0.04m x 0.05m

More information

Chapter 3 EXPERIMENTAL: EQUIPMENT, SET-UP, AND PROCEDURE

Chapter 3 EXPERIMENTAL: EQUIPMENT, SET-UP, AND PROCEDURE Chapter 3 EXPERIMENTAL: EQUIPMENT, SET-UP, AND PROCEDURE 72 3.0 Introduction The experimental work was carried out in three stages. First stage: a laboratory scale single nozzle horizontal jet ejector

More information

SENSITIVITY ANALYSIS OF THE FIRST CIRCUIT OF COLD CHANNEL PIPELINE RUPTURE SIZE FOR WWER 440/270 REACTOR

SENSITIVITY ANALYSIS OF THE FIRST CIRCUIT OF COLD CHANNEL PIPELINE RUPTURE SIZE FOR WWER 440/270 REACTOR PROCEEDINGS OF THE YEREVAN STATE UNIVERSITY Physical and Mathematical Sciences 216, 2, p. 57 62 P h y s i c s SENSITIVITY ANALYSIS OF THE FIRST CIRCUIT OF COLD CHANNEL PIPELINE RUPTURE SIZE FOR WWER 44/27

More information

Characterizing Flow Losses Occurring in Air Vents and Ejector Pins in High Pressure Die Castings

Characterizing Flow Losses Occurring in Air Vents and Ejector Pins in High Pressure Die Castings This paper is subject to revision. Statements and opinions advanced in this paper or during presentation are the author s and are his/her responsibility, not the Association s. The paper has been edited

More information

FIRE LOGISTICS AND MATH EDUCATION A Rumpke Public Outreach Program

FIRE LOGISTICS AND MATH EDUCATION A Rumpke Public Outreach Program FIRE LOGISTICS AND MATH EDUCATION A Rumpke Public Outreach Program Welcome & Introductions Identify emergency exits to all participants. Identify location of restroom facilities. Cover any other related

More information

NGN Series nitrogen generator

NGN Series nitrogen generator NGN Series 8-64 nitrogen generator Applications how it works RK series 5-40 F Blanketing of Chemicals and Pharmaceuticals Gas Assisted Injection Moulding (GAIM) Laser Cutting Food Heat Treament of Ferrous

More information

Test Report # Rev 0. Adiabatic Compression With Constant Bleed Valve

Test Report # Rev 0. Adiabatic Compression With Constant Bleed Valve Test Report # 30016558 Rev 0 Adiabatic Compression With Constant Bleed Valve Scope: This test report contains test data on the effects of adiabatic compression in nitrogen service on AP3600 diaphragm valves,

More information

Micro Channel Recuperator for a Reverse Brayton Cycle Cryocooler

Micro Channel Recuperator for a Reverse Brayton Cycle Cryocooler Micro Channel Recuperator for a Reverse Brayton Cycle Cryocooler C. Becnel, J. Lagrone, and K. Kelly Mezzo Technologies Baton Rouge, LA USA 70806 ABSTRACT The Missile Defense Agency has supported a research

More information

M A B MAB INFLATABLE GASKET SLIDE VALVES SERIES TSV FOR POWDERED AND GRANULAR SOLID MATERIALS

M A B MAB INFLATABLE GASKET SLIDE VALVES SERIES TSV FOR POWDERED AND GRANULAR SOLID MATERIALS Automatic slide valves type TSV-150 with inflatable sealing system. The range of TSV slide valves supplied by MAB can always close against a head of flowing solids. The TSV series of inflatable gasket

More information

Fluid Flow. Link. Flow» P 1 P 2 Figure 1. Flow Model

Fluid Flow. Link. Flow» P 1 P 2 Figure 1. Flow Model Fluid Flow Equipment: Water reservoir, output tubes of various dimensions (length, diameter), beaker, electronic scale for each table. Computer and Logger Pro software. Lots of ice.temperature probe on

More information

Mass Flow Controller (MFC) for Gases

Mass Flow Controller (MFC) for Gases Mass Flow Controller (MFC) for Gases Type 8713 can be combined with... Direct flow measurement by MEMS- Technology for nominal flow rates from 1 ml N /min to 8 l N /min (N 2 ) High accuracy and repeatability

More information

Mass Flow Controller (MFC) for Gases

Mass Flow Controller (MFC) for Gases Mass Flow Controller (MFC) for Gases Bypass MFC with capillary technology for nominal flow rates from 5 ml N /min to 15 l N /min Applicable for aggressive gases Compact design and digital communication

More information

Gas Vapor Injection on Refrigerant Cycle Using Piston Technology

Gas Vapor Injection on Refrigerant Cycle Using Piston Technology Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Gas Vapor Injection on Refrigerant Cycle Using Piston Technology Sophie

More information

Profile LFR-45 LIFUS5 ITALY. Italian National Agency for New Technologies, Energy and Sustainable Economic Development, C.R. ENEA Brasimone, Italy

Profile LFR-45 LIFUS5 ITALY. Italian National Agency for New Technologies, Energy and Sustainable Economic Development, C.R. ENEA Brasimone, Italy Profile LFR-45 LIFUS5 ITALY GENERAL INFORMATION NAME OF THE FACILITY ACRONYM COOLANT(S) OF THE FACILITY LOCATION (address): OPERATOR CONTACT PERSON (name, address, institute, function, telephone, email):

More information

Level MEASUREMENT 1/2016

Level MEASUREMENT 1/2016 Level MEASUREMENT 1/2016 AGENDA 2 A. Introduction B. Float method C. Displacer method D. Hydrostatic pressure method E. Capacitance method G. Ultrasonic method H. Radar method I. Laser method J. Level

More information

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS Electropneumatic Positioner and Pneumatic Positioner Type 3760 Application Single-acting positioners for direct attachment to pneumatic control valves. Supplied with an electric input signal of 4 to 20

More information

Sizing Pulsation Dampeners Is Critical to Effectiveness

Sizing Pulsation Dampeners Is Critical to Effectiveness Sizing Pulsation Dampeners Is Critical to Effectiveness Pressure variation is an important consideration when determining the appropriate size pulsation dampener needed for an application. by David McComb,

More information

with FE -13 TM Most DuPont FE-13 systems are designed with a concentration of 15.9% whereas the NOAEL level of this extinguishing agent is 30%.

with FE -13 TM Most DuPont FE-13 systems are designed with a concentration of 15.9% whereas the NOAEL level of this extinguishing agent is 30%. LPG Systems with FE -13 TM Most DuPont FE-13 systems are designed with a concentration of 15.9% whereas the NOAEL level of this extinguishing agent is 30%. The agent is stored in seamless drawn steel high

More information

OIL AND GAS INDUSTRY

OIL AND GAS INDUSTRY This case study discusses the sizing of a coalescer filter and demonstrates its fouling life cycle analysis using a Flownex model which implements two new pressure loss components: - A rated pressure loss

More information

SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company

SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company CIF A Tyco International Company 1 Foam Concentrate CIF 3% AFFF -UL Listed -UL Canada Listed 6% AFFF 6 parts AFFF concentrate to 94 parts water -UL Listed- Foam Liquid -UL Canada Listed 3% FLUOROPROTEIN

More information

Application of Flex-Z release agent with a pneumatic gun

Application of Flex-Z release agent with a pneumatic gun Application of Flex-Z release agent with a pneumatic gun Manual for spray-gun Granudan ApS Knud Bro Alle 4 DK-3650 Stenloese Denmark www.granudan.com www.granudan.cn Application of Release agent (Flex-Z)

More information

Constant Pressure Inlet (CCN) Operator Manual

Constant Pressure Inlet (CCN) Operator Manual Constant Pressure Inlet (CCN) Operator Manual DOC-0125 Revision J 2545 Central Avenue Boulder, CO 80301-5727 USA C O P Y R I G H T 2 0 1 1 D R O P L E T M E A S U R E M E N T T E C H N O L O G I E S, I

More information

International Journal of Technical Research and Applications e-issn: , Volume 4, Issue 3 (May-June, 2016), PP.

International Journal of Technical Research and Applications e-issn: ,  Volume 4, Issue 3 (May-June, 2016), PP. DESIGN AND ANALYSIS OF FEED CHECK VALVE AS CONTROL VALVE USING CFD SOFTWARE R.Nikhil M.Tech Student Industrial & Production Engineering National Institute of Engineering Mysuru, Karnataka, India -570008

More information

Available online at ScienceDirect

Available online at   ScienceDirect Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 71 ( 2014 ) 44 56 Experimental Research of Integrated Compressed Air Foam System of Fixed (ICAF) for Liquid Fuel Jing-yuan Cheng

More information

Test pumps. Pressure sources. Good reasons for proper and reliable calibration

Test pumps. Pressure sources. Good reasons for proper and reliable calibration Test pumps Pressure is one of the most commonly measured quantities in engineering, which is why exact and reliable pressure measurement is especially important. However, the characteristics of the even

More information

Section 2 Multiphase Flow, Flowing Well Performance

Section 2 Multiphase Flow, Flowing Well Performance Section 2 Multiphase Flow, Flowing Well Performance Multiphase Vertical Flow When producing an oil or gas well, the flow of the fluids up the tubing will be in most cases be 2 phase, liquid and gas. The

More information

Irrigation &Hydraulics Department lb / ft to kg/lit.

Irrigation &Hydraulics Department lb / ft to kg/lit. CAIRO UNIVERSITY FLUID MECHANICS Faculty of Engineering nd Year CIVIL ENG. Irrigation &Hydraulics Department 010-011 1. FLUID PROPERTIES 1. Identify the dimensions and units for the following engineering

More information

Injector Dynamics Assumptions and their Impact on Predicting Cavitation and Performance

Injector Dynamics Assumptions and their Impact on Predicting Cavitation and Performance Injector Dynamics Assumptions and their Impact on Predicting Cavitation and Performance Frank Husmeier, Cummins Fuel Systems Presented by Laz Foley, ANSYS Outline Overview Computational Domain and Boundary

More information

English. New Energy-efficient Snowgun System

English. New Energy-efficient Snowgun System English New Energy-efficient Snowgun System Field testing at the SLF facilities in Davos About NESSy This innovative new snowgun is the result of 3 years intense research and development and joint collaboration

More information

A New Way to Handle Changing Fluid Viscosity and the Full-to-empty Effect

A New Way to Handle Changing Fluid Viscosity and the Full-to-empty Effect A New Way to Handle Changing Fluid Viscosity and the Full-to-empty Effect Nordson EFD, 40 Catamore Blvd., East Providence RI 02914 www.nordsonefd.com A New Way to Handle Changing Fluid Viscosity And the

More information

1.2 Example 1: A simple hydraulic system

1.2 Example 1: A simple hydraulic system Note: It is possible to use more than one fluid in the Hydraulic library. This is important because you can model combined cooling and lubrication systems of a library. The hydraulic library assumes a

More information

SUMMARY PROBLEMS CAUSED BY BACKFLOW IN PIPE SYSTEMS.

SUMMARY PROBLEMS CAUSED BY BACKFLOW IN PIPE SYSTEMS. Page 1 of 11 SUMMARY There are many problems derived from a reverse flow in a piping system. A solution presented in this paper is the WaStop inline check valve. The paper aims to explain some of the important

More information

TUTORIAL. NPSHA for those who hate that stuffy word. by Jacques Chaurette p. eng. copyright 2006

TUTORIAL. NPSHA for those who hate that stuffy word. by Jacques Chaurette p. eng.  copyright 2006 TUTORIAL NPSHA for those who hate that stuffy word by Jacques Chaurette p. eng. www.lightmypump.com copyright 2006 page.2 NPSHA for those who hate that stuffy word This article follows the same approach

More information

LEAP CO 2 Laboratory CO 2 mixtures test facility

LEAP CO 2 Laboratory CO 2 mixtures test facility LEAP CO 2 Laboratory CO 2 mixtures test facility THE PROJECT AIM CO 2 flows made available by several capture techniques are contaminated with impurities and this affects the design and operations of the

More information

Basic concepts of phase behavior

Basic concepts of phase behavior Basic concepts of phase behavior 1) Single component system. Ethane is taken as an example for single component system. Ethane exists as gas phase at ordinary conditions. At other than ordinary conditions,

More information

Profile LFR-43 HELENA ITALY. Italian National Agency for New Technologies, Energy and Sustainable Economic Development, C.R. ENEA Brasimone, Italy

Profile LFR-43 HELENA ITALY. Italian National Agency for New Technologies, Energy and Sustainable Economic Development, C.R. ENEA Brasimone, Italy Profile LFR-43 HELENA ITALY GENERAL INFORMATION NAME OF THE FACILITY ACRONYM COOLANT(S) OF THE FACILITY LOCATION (address): OPERATOR CONTACT PERSON (name, address, institute, function, telephone, email):

More information

Modeling a Pressure Safety Valve

Modeling a Pressure Safety Valve Modeling a Pressure Safety Valve Pressure Safety Valves (PSV), Pressure Relief Valves (PRV), and other pressure relieving devices offer protection against overpressure in many types of hydraulic systems.

More information

1. The principle of fluid pressure that is used in hydraulic brakes or lifts is that:

1. The principle of fluid pressure that is used in hydraulic brakes or lifts is that: University Physics (Prof. David Flory) Chapt_15 Thursday, November 15, 2007 Page 1 Name: Date: 1. The principle of fluid pressure that is used in hydraulic brakes or lifts is that: A) pressure is the same

More information

Computer Simulation Helps Improve Vertical Column Induced Gas Flotation (IGF) System

Computer Simulation Helps Improve Vertical Column Induced Gas Flotation (IGF) System JOURNAL ARTICLES BY FLUENT SOFTWARE USERS JA187 Computer Simulation Helps Improve Vertical Column Induced Gas Flotation (IGF) System Computer simulation has helped NATCO engineers make dramatic improvements

More information

SINORIX Valve Reconditioning

SINORIX Valve Reconditioning Document No. 129-097 SINORIX Valve Reconditioning Product Description These instructions explain how to recondition and fill 1-inch through 4-inch SINORIX valves. Product Numbers Verify that the appropriate

More information

HYDRAULICS. H89.8D - Hydraulic Bench

HYDRAULICS. H89.8D - Hydraulic Bench HYDRAULICS H89.8D - Hydraulic Bench 1. General The H89.8D and ancillary equipment have been developed to provide a comprehensive range of experiments in fluid mechanics. The bench is of robust construction

More information

QUESTION 1. Sketch graphs (on the axes below) to show: (1) the horizontal speed v x of the ball versus time, for the duration of its flight;

QUESTION 1. Sketch graphs (on the axes below) to show: (1) the horizontal speed v x of the ball versus time, for the duration of its flight; QUESTION 1 A ball is thrown horizontally from a cliff with a speed of 10 ms -1 shown in the diagram at right. Neglecting the effect of air resistance and taking gravitational acceleration to be g +9.8ms

More information

Chapter 4, Problem 30.

Chapter 4, Problem 30. Chapter 4, Problem 30. A well-insulated rigid tank contains 5 kg of a saturated liquid vapor mixture of water at l00 kpa. Initially, three-quarters of the mass is in the liquid phase. An electric resistor

More information

Pneumatic Conveying Systems Theory and Principles Session 100

Pneumatic Conveying Systems Theory and Principles Session 100 Pneumatic Conveying Systems Theory and Principles Session 100 1 Controls & Instrumentation P = Actual Pressure V = Actual Volume T is Typically Ignored Key Relationship PV/T Terminal Point Any Point Pick

More information

QUESTION 1. Sketch graphs (on the axes below) to show: (1) the horizontal speed v x of the ball versus time, for the duration of its flight;

QUESTION 1. Sketch graphs (on the axes below) to show: (1) the horizontal speed v x of the ball versus time, for the duration of its flight; QUESTION 1 A ball is thrown horizontally from a cliff with a speed of 10 ms -1 shown in the diagram at right. Neglecting the effect of air resistance and taking gravitational acceleration to be g = +9.8ms

More information

Sapag Control valve MONOVAR

Sapag Control valve MONOVAR MONOVAR MONOVAR is the energy dissipating valve Features MONOVAR DN 2000 (80 ) Extremely simple design (patented) Excellent cavitation characteristics Very accurate flow or pressure control Manual or automatic

More information

MODELLING OF FUME EXTRACTORS C. R.

MODELLING OF FUME EXTRACTORS C. R. LD8 19th International Symposium of Ballistics, 7 11 May 21, Interlaken, Switzerland MODELLING OF FUME EXTRACTORS C. R. Woodley WS4 Guns and Warheads Department, Defence Evaluation and Research Agency,

More information

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS READ ALL INSTRUCTIONS PRIOR TO INSTALLATION AND OPERATION TO AVOID POSSIBLE INJURY Warning: Always consider any accumulator to contain pressure until proven

More information