Gas Cabinets and Valve Manifold Boxes: Applying CGA G13- Rev 2015 to Gas Delivery Equipment

Size: px
Start display at page:

Download "Gas Cabinets and Valve Manifold Boxes: Applying CGA G13- Rev 2015 to Gas Delivery Equipment"

Transcription

1 Gas Cabinets and Valve Manifold Boxes: Applying CGA G13- Rev 2015 to Gas Delivery Equipment

2 The Standard Governing the Storage & Use of Silane: Compressed Gas Association s Publication CGA G : Storage and Handling of Silane and Silane Mixtures 1. Outdoor Storage & Use Section 6 2. Indoor Storage & Use Section 7 3. System Configuration for Cylinder Sources Section 8 4. System Configuration for Bulk Sources Section 9 5. Piping & Components Section Gas & Flame Detection Section Fire Protection System Section Ventilation System Section Venting & Treatment Section Purge Gas System Section Electrical Requirements Section Fundamental Supervisory Control Requirements Section 17

3 The Standard Governing the Storage & Use of Silane: Compressed Gas Association s Publication CGA G :

4 Why You Must Follow the Standard with this Gas 2005 Silane Explosion - Taiwan

5 Result of the Explosion:

6 Gas Cabinet Explosions: Silane released into a Gas Cabinet followed by an Explosion: Germany, fatality Japan, fatality & 1 injury Japan, Dec fatalities & 2 injuries US, Jan injury US, 1996 No injuries Japan, fatality US, 2003 No injuries US, injuries Taiwan, fatality India, fatality China, injury China, Injury * Data from 2012 Silane Safety Seminar

7 Why is Critical Systems Presenting on this Topic? CSI s History 17 years Supplying Gas Delivery & Abatement Equipment CSI s Background High Production Semiconductor Fabs What we Hear when we talk with Potential Customers What we See when we go to Customer s Sites Dangers of Silane & Desire to Promote Safety

8 Focus of the Presentation: 1. Tubing & Components 2. Gas Cabinets for Cylinder Use 3. Gas Rack Units 4. Valve Manifold Boxes / Enclosures

9 Tubing & Components Required per CGA G-13: 1. Tubing Connections Section a. Welded Fittings & VCR Acceptable No Compression! b. Metal Gaskets Only No Teflon or PCTFE

10 Tubing & Components Required per CGA G-13: 1. Tubing Connections Section a. Welded Fittings & VCR Acceptable No Compression! b. Metal Gaskets Only No Teflon or PCTFE

11 Tubing & Components Required per CGA G-13: 1. Tubing Connections Section a. Welded Fittings & VCR Acceptable No Compression! b. Metal Gaskets Only No Teflon or PCTFE 2. COAX Not Required Unless Silane is Mixed with a Toxic Section Process Valves Diaphragm or Bellows Only - Section Check Valves Cannot be Sole Means of Backflow Prevention - Section Regulators Section a. Metal Diaphragms Required b. Bonnet Relief Vents Required 6. Restricted Flow Orifice is Required Max Size Section

12 Tubing & Components Required per CGA G-13: 6. Restricted Flow Orifice is Required Max Size Section

13 Tubing & Components Required per CGA G-13: 6. Restricted Flow Orifice is Required Max Size Section

14 Tubing & Components Required per CGA G-13: 1. Tubing Connections Section a. Welded Fittings & VCR Acceptable No Compression! b. Metal Gaskets Only No Teflon or PCTFE 2. COAX Not Required Unless Silane is Mixed with a Toxic Section Isolation Valves No Packed Valves - Section Check Valves Spring Opposed, Positive Shutoff - Section a. Cannot be sole means of preventing backflow 5. Regulators Section a. Metal Diaphragms b. Bonnet Relief Vents Required 6. Restricted Flow Orifice is Required Max Size Section Excess Flow Control Required Section a. Valves, Control Devices, Flow Control Systems are Allowed b. Capable of Manual Reset AFTER Corrective Action

15 Gas Cylinder Cabinets:

16 Gas Cylinder Cabinet CGA G-13 Requirements: 1. G-13 Definition of Gas Cabinet Section Cabinet/Enclosure, Controller, Gas Panel 2. Connected to Scrubbed Exhaust 3. Lockable Windows to View & Operate Gas Panels 4. Control System Outside the Cabinet 5. Controller enables Auto-Purge Procedures 2. 2 Cylinders in a Gas Cabinet Separation Plates / Single Cabinets- Section Gas Monitoring All Connections Must be Monitored for Leaks - Section a. Indoor Storage Gas Monitoring or Optical Flame Detection System b. Sampling Points in Ducts from Enclosures Containing Breakable Connections a. Not Less than 5 Duct Diameters Downstream of Enclosure Connection c. 50 ppm Shutdown V0, Local Alarm, Transmit to Constantly Attended Location Sections ; &

17 Gas Cylinder Cabinet CGA G-13 Requirements: 1. G-13 Definition of Gas Cabinet Section Cabinet/Enclosure, Controller, Gas Panel 2. Connected to Scrubbed Exhaust 3. Lockable Windows to View & Operate Gas Panels 4. Control System Outside the Cabinet 5. Controller enables Auto-Purge Procedures 2. Less than 30 psi Cylinder Pressure Don t need a Gas Cabinet Section V0 Valve Shuts the Gas Supply at the Source - Section a. On the Cylinder or Close Coupled to the Cylinder Connection b. Remote Shutdown - ESO Button (Sec 6.4.1) - Gas Monitor - UVIR (Sec ) 4. 2 Cylinders in a Gas Cabinet Separation Plates / Single Cabinets- Section Gas Monitoring All Connections Must be Monitored for Leaks - Section a. Indoor Storage Gas Monitoring or Optical Flame Detection System b. Sampling Points in Ducts from Enclosures Containing Breakable Connections a. Not Less than 5 Duct Diameters Downstream of Enclosure Connection c. 50 ppm Shutdown V0, Local Alarm, Transmit to Constantly Attended Location Sections ; &

18 Gas Cylinder Cabinet CGA G-13 Requirements: 1. G-13 Definition of Gas Cabinet Section Cabinet/Enclosure, Controller, Gas Panel 2. Connected to Scrubbed Exhaust 3. Lockable Windows to View & Operate Gas Panels 4. Control System Outside the Cabinet 5. Controller enables Auto-Purge Procedures 2. Less than 30 psi Cylinder Pressure Don t need a Gas Cabinet Section V0 Valve Shuts the Gas Supply at the Source - Section a. On the Cylinder or Close Coupled to the Cylinder Connection b. Remote Shutdown - ESO Button (Sec 6.1.4) - Gas Monitor - UVIR (Sec )

19 Gas Cylinder Cabinet CGA G-13 Requirements: 1. G-13 Definition of Gas Cabinet Section Cabinet/Enclosure, Controller, Gas Panel 2. Connected to Scrubbed Exhaust 3. Lockable Windows to View & Operate Gas Panels 4. Control System Outside the Cabinet 5. Controller enables Auto-Purge Procedures 2. Less than 30 psi Cylinder Pressure Don t need a Gas Cabinet Section V0 Valve Shuts the Gas Supply at the Source - Section a. On the Cylinder or Close Coupled to the Cylinder Connection b. Remote Shutdown - ESO Button (Sec 6.1.4) - Gas Monitor - UVIR (Sec ) 4. 2 Cylinders in a Gas Cabinet Separation Plates / Single Cabinets- Section

20 Gas Cylinder Cabinet CGA G-13 Requirements: 1. G-13 Definition of Gas Cabinet Section Cabinet/Enclosure, Controller, Gas Panel 2. Connected to Scrubbed Exhaust 3. Lockable Windows to View & Operate Gas Panels 4. Control System Outside the Cabinet 5. Controller enables Auto-Purge Procedures 2. Less than 30 psi Cylinder Pressure Don t need a Gas Cabinet Section V0 Valve Shuts the Gas Supply at the Source - Section a. On the Cylinder or Close Coupled to the Cylinder Connection b. Remote Shutdown - ESO Button (Sec 6.1.4) - Gas Monitor - UVIR (Sec ) 4. 2 Cylinders in a Gas Cabinet Separation Plates / Single Cabinets- Section Gas Monitoring All Connections Must be Monitored for Leaks - Section a. Indoor Storage Gas Monitoring or Optical Flame Detection System b. Sampling Points in Ducts from Enclosures Containing Breakable Connections a. Not Less than 5 Duct Diameters Downstream of Enclosure Connection c. 50 ppm Shutdown V0, Local Alarm, Transmit to Constantly Attended Location Sections ; &

21 Gas Cylinder Cabinet CGA G-13 Requirements: 6. Flame Monitoring Shuts the Gas Supply at the Source - Section a. Outside the Cabinet at Potential Leak Points - Sec b. Inside the Gas Cabinet or Enclosure Required - Sec Fire Protection System Quick Response Sprinkler Head - Water Only Section a. Desire is to Keep the Cylinder Cool and Not put out the Fire 8. Emergency Power Delivery Systems Must Fail Safe Section Supervisory Control Requirements Section 17.1 a. Exhaust & Gas Monitoring, Flame Detection, Emergency Shut Off b. Piping with Breakable Connections Gas Monitor & Flame Detection

22 Gas Cylinder Cabinet CGA G-13 Requirements: 6. Flame Monitoring Shuts the Gas Supply at the Source - Section a. Outside the Cabinet at Potential Leak Points - Sec b. Inside the Gas Cabinet or Enclosure Required - Sec Fire Protection System Quick Response Sprinkler Head - Water Only Section a. Desire is to Keep the Cylinder Cool and Not put out the Fire 8. Emergency Power Delivery Systems Must Fail Safe Section Supervisory Control Requirements Section 17.1 a. Exhaust & Gas Monitoring, Flame Detection, Emergency Shut Off b. Piping with Breakable Connections Gas Monitor & Flame Detection

23 Gas Cylinder Cabinet CGA G-13 Requirements: 6. Flame Monitoring Shuts the Gas Supply at the Source - Section a. Outside the Cabinet at Potential Leak Points - Sec b. Inside the Gas Cabinet or Enclosure Required - Sec Fire Protection System Quick Response Sprinkler Head - Water Only Section a. Desire is to Keep the Cylinder Cool and Not put out the Fire 8. Emergency Power Delivery Systems Must Fail Safe Section Supervisory Control Requirements Section 17.1 a. Exhaust & Gas Monitoring, Flame Detection, Emergency Shut Off b. Piping with Breakable Connections Gas Monitor & Flame Detection 10. Ventilation System Section 13.2 a. Continuous Exhaust - Required b. Non-combustible Ductwork - Required c. Required Airflow 250:1 Volume Ratio Section d. Failure in Ventilation System Local Alarm & Transmission to Constantly Attended Location e. Enclosures Designed to Prevent Pocketing Section f. Unattended Operations Table 6

24 Gas Cylinder Cabinet CGA G-13 Requirements: 11. Silane Venting & Treatment - Section 14 a. If No Toxics - Gas from Cycle Purging dilute with Inert Gas, Open Air Disposal - Sec 14.2 b. Mixed with Toxics Abate with Appropriate Scrubber c. Treatment System Must be designed for Silane - Section 14.3 d. Vent into Ducts - < 25% of the LFL or 0.34% if Ignition is Only Concern Section 14.4 e. Must have a Dedicated Process Vent Section 14.5 f. Vent Stack Designed to Prevent Thermal Radiation from Causing Harm - Section 14.5 g. Purge through Venturi on Gas Panel must be Continuous Section

25 Gas Cylinder Cabinet CGA G-13 Requirements: 12. Purge Gas System - Section 15 a. Must use Vacuum in Combination with Purge Gas Section 15.1 b. Must use a Dedicated Purge Bottle Section 15.2

26 Gas Cylinder Cabinet CGA G-13 Requirements: 12. Purge Gas System - Section 15 a. Must use Vacuum in Combination with Purge Gas Section 15.1 b. Must use a Dedicated Purge Bottle Section 15.2

27 Gas Cylinder Cabinet CGA G-13 Requirements: 12. Purge Gas System - Section 15 a. Must use Vacuum in Combination with Purge Gas Section 15.1 b. Must use a Dedicated Purge Bottle Section 15.2

28 Gas Cylinder Cabinet CGA G-13 Requirements: 12. Purge Gas System - Section 15 a. Must use Vacuum in Combination with Purge Gas Section 15.1 b. Must use a Dedicated Purge Bottle Section 15.2 c. Cannot use House Gas for Purging Section d. Can use House Gas for Venturi Vents Section 14.5 e. Must have a Check Valve before the Venturi Section f. Panel Consists of Dedicated Supply, Regulator, Relief Valve, Check Valve & Low Purge Gas Alarm Section 15.3

29 Purge Gas Panel:

30 CGA G-13 Requirements for Gas Cabinets Containers > 14 liters & Concentrations > 1.36% Automatic Shutdown (Cabinet & 1 Remote) Z-Purge in Controller Vacuum Venturi for Purge/Vent Exhaust Monitor Sprinkler Quick Response Head UVIR Flame Monitor / Gas Monitor Dedicated Purge System Excess Flow Switch or Valve Regulator Bonnet Vent Line Low Purge Gas Pressure Alarm Check Valve on Purge Panel AOP on Cylinder or Close Coupled Shutoff Valve Cylinder Isolation - Separate Cabinet or Steel Plate High Flow Gas Cabinet Vents Enclosure Designed to Eliminate Pocketing

31 Gas Rack Units:

32 Gas Rack Unit G-13 Requirements: 1. V0 Valve Shuts the Gas Supply at the Source - Section a. On the Cylinder or Close Coupled to the Cylinder Connection b. Remote Shutdown or ESO Button (Sec 6.1.4) or Gas Monitor, UVIR (Sec ) 2. Separation Plates between Cylinders - Section a. 1/4 Thick Steel Plates Minimum 18 Below & 6 Above Centerline of Valve or Other Means of Providing Equivalent Protection 3. Purge Panel Requirements Same as Gas Cabinets Section Gas Monitoring Not Required - Section Flame Detection Section a. Required in Potential Leak Zones b. Approved for Outdoor Silane use with no False Trips from Artificial Sources 6. Ventilation Systems Section a. Natural ventilation acceptable, Mechanical ventilation for Obstructed Spaces 7. Supervisory Control Requirements Section 17.1 a. Exhaust Monitoring w/ Alarm if Mechanical Ventilation Used b. Flame Detection with Source Shutdown c. Emergency Shut off at Exits

33 Gas Rack Unit G-13 Requirements: 1. V0 Valve Shuts the Gas Supply at the Source - Section a. On the Cylinder or Close Coupled to the Cylinder Connection b. Remote Shutdown or ESO Button (Sec 6.1.4) or Gas Monitor, UVIR (Sec ) 2. Separation Plates between Cylinders - Section a. 1/4 Thick Steel Plates Minimum 18 Below & 6 Above Centerline of Valve or Other Means of Providing Equivalent Protection 3. Purge Panel Requirements Same as Gas Cabinets Section Gas Monitoring Not Required - Section Flame Detection Section a. Required in Potential Leak Zones b. Approved for Outdoor Silane use with no False Trips from Artificial Sources 6. Ventilation Systems Section a. Natural ventilation acceptable, Mechanical ventilation for Obstructed Spaces 7. Supervisory Control Requirements Section 17.1 a. Exhaust Monitoring w/ Alarm if Mechanical Ventilation Used b. Flame Detection with Source Shutdown c. Emergency Shut off at Exits

34 Typical Outdoor Cylinder Layout: Setback Distances and Openness Requirements Section 6 a. Distances to Exposure for Outdoor Cylinders Section 6, Table 3

35 CGA G-13 Requirements for Rack Units Containers > 14 liters & Concentrations > 1.36% Automatic Shutdown (Cabinet Sensors & Remote) Z-Purge in Controller Emergency Shutoff Sprinkler Vacuum Venturi for Purge/Vent UVIR Flame Monitor Excess Flow Switch Low Pressure Purge Gas Alarm AOP Cylinder Shutoff Valve (Close Coupled is OK) Check Valve on Purge Gas 1/4 Steel Plate (6 Above/18 Below Centerline of Cylinder Valve

36 Valve Manifold Boxes / Enclosures:

37 Valve Manifold Box CGA G-13 Requirements: 1. Description Nothing in Code says you can t use a Manual VMB - Section a. CAN BE Controlled Automatically b. Emergency Gas Shutoff & Purging MAY BE Accomplished with Automated VMB 2. Branch Purging from Non Dedicated Source if Backflow Prevention - Section Gas Monitoring Section a. Same as Gas Cabinet per - Section b. Activation of Gas Monitoring Shuts Source of Gas (at VMB or Cabinet) 4. Flame Detection Section a. Same as Gas Cabinet per - Section b. Activation of Flame Monitoring Shuts Source of Gas (at Cabinet) 5. Fire Protection VMBs not Mentioned Section Ventilation Systems Section 13.2 a. Same as Gas Cabinet Requirements See Table 6 for Exhaust Flow Rates 7. Supervisory Control Requirements Section 17.1 a. Exhaust & Gas Monitoring, Flame Detection

38 CGA G-13 Requirements for Valve Manifold Boxes Individual Stick Shutdown Z-Purge in Controller Tool Gas Monitoring Shuts Down Stick - VMB Gas Monitoring Shuts Down the Cabinet Emergency Shutdown Exhaust Monitoring Enclosure Design to Eliminate Pocketing UVIR Flame Monitor High Flow Enclosure

39 Silane Gas Installation Supplement: Supplement from UNIDOCS based on California Fire Code helps when applying for Silane permit. Covers Key Code Aspects of Silane Systems and points to where in your submittals they reside.

40

41 Summary of Air Products Internal Safety Requirements for Silane (note: Any exceptions to these requirements require a Hazop / Safety Review to ensure equivalent protection is in place) U.S. Requirements All Silane Systems Additional Requirements for Enclosed Systems UVIR Detector Gas Monitor Exhausted Enclosure for Indoor Equipment Dedicated Purge System High Pressure not liquid bulk (Purge Source) Overpressure Protection Process Vent Dedicated to Silane Continuous Purge on Vent Line Electrical Hazardous Area Protection Secondary Containment (recommended) Access / View Port for Distribution Systems Access Port for Source Systems Exhaust Monitor Automatic Door and Window Closures Ventilation > 250 times potential Leak Rate Trickle Purged Vent Header Welded Fittings / Breakable Connections Process Vent Vacuum System Backflow Prevention Cylinder Isolation Valves Pressure Indication Compatible Materials Equipment and Hazard Labels Separation Plates or Individual Cabinets 150 ft/min Min Open Window Velocity 200 ft/min Ave Open Window Velocity No Pocketing in Enclosure Additional Requirements for Source Systems RFO in Source Container Valve RFO Max for Cylinders Sprinkler Captured Bonnet Relief Vents Emergency Shutoff System Excess Flow Protection Metal Separation Plates Remote Emergency Stop 12 gauge Sheet Metal for Enclosures Pressure Regulation Controller Cylinder Restraints Provisions for Seismic Anchoring All-Welded Pigtail Automated Purging High Pressure Leak Test

42 Summary of Air Products Internal Safety Requirements for Silane (note: Any exceptions to these requirements require a Hazop / Safety Review to ensure equivalent protection is in place) U.S. Requirements All Silane Systems Additional Requirements for Enclosed Systems UVIR Detector Sec Gas Monitor Sec Exhausted Enclosure for Indoor Equipment Sec 7.11 Dedicated Purge System Sect 15.2 High Pressure not liquid bulk (Purge Source) Sec 15 Overpressure Protection Sec Process Vent Dedicated to Silane - Sec Continuous Purge on Vent Line Sec Electrical Hazardous Area Protection Sec 16 & 17.1 Secondary Containment (recommended) - Sec Trickle Purged Vent Header Welded Fittings / Breakable Connections Sec Process Vent Sec & Sec 14 Vacuum System Sec 13.2 Backflow Prevention Sec & Sec Cylinder Isolation Valves Sec & Sec Pressure Indication Sec Compatible Materials Sec 7.10 & Sec Equipment and Hazard Labels Sec & Check Valves on Purge Gas - Sec Access / View Port for Distribution Systems Separation Plates or Individual Cabinets - Sec Access Port for Source Systems Sec ft/min Min Open Window Velocity Table 6 Exhaust Monitor Sec ft/min Ave Open Window Velocity Table 6 Automatic Door and Window Closures No Pocketing in Enclosure Sec Ventilation > 250 times potential Leak Rate Sec Additional Requirements for Source Systems RFO in Source Container Valve Sec RFO Max for Cylinders Sec Sprinkler Sec Captured Bonnet Relief Vents Sec Emergency Shutoff System Sec Excess Flow Protection Sec Metal Separation Plates Sec Remote Emergency Stop Sec gauge Sheet Metal for Enclosures Pressure Regulation Sec Controller Sec & Sec Cylinder Restraints Provisions for Seismic Anchoring All-Welded Pigtail -Sec Automated Purging Sec 15.1 High Pressure Leak Test - Sec

43 In Closing: 1. Silane can be Deadly 2. Your local AHJ Authority Having Jurisdiction needs to be involved in the process before you bring this gas in Provide Silane Gas Installation Supplement for headache relief 3. Always enlist a qualified Engineering Firm knowledgeable about Silane - to help design and assure compliance with all Applicable Standards & Codes ANSI/CGA G-13 - NFPA 318 & 55 IFC Chapters 18, 27, 30 & 41 FM Global EMI S18 4. In conjunction with your Engineering Firm, develop a Silane Procedures Manual and Train your Technicians how to operate/maintain the systems properly 5. Don t sidestep a Quality Gas System because it s more expensive than you budgeted. a. Find companies like ours that manufacture high quality systems and are familiar with Code and Safety requirements b. Make sure that their systems are CGA Code G13 Compliant 6. Purchase a copy of the Standard and read it.

44

45

46

TYPICAL TOXIC GAS SYSTEM INSPECTION VIOLATIONS

TYPICAL TOXIC GAS SYSTEM INSPECTION VIOLATIONS TYPICAL TOXIC GAS SYSTEM INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility,

More information

Section 1.3: PRESSURE VESSEL COMPONENTS AND SYSTEMS AND COMPRESSED GAS CYLINDERS

Section 1.3: PRESSURE VESSEL COMPONENTS AND SYSTEMS AND COMPRESSED GAS CYLINDERS Section 1.3: PRESSURE VESSEL COMPONENTS AND SYSTEMS AND COMPRESSED GAS CYLINDERS TABLE OF CONTENTS Page A. Regulations, Standards and References 1.3-2 B. Scope 1.3-2 C. Design Features for the Storage

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

The Standard of Excellence in Safety, Quality, and Performance

The Standard of Excellence in Safety, Quality, and Performance A Division of APPLIED ENERGY SYSTEMS, INC. The Standard of Excellence in Safety, Quality, and Performance CENTURION SOURCE SYSTEMS CENTURION CONTROLS Centurion source systems are the latest offering from

More information

Description Advanced Features Typical Applications

Description Advanced Features Typical Applications Series single stage, brass barstock line regulator Description Advanced Features Typical Applications The Series regulators are intended for secondary pressure control of noncorrosive, high purity or liquefied

More information

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT Reference: IFC, Denver Amendments, NFPA Approved: Joseph L. Gonzales, Division Chief, Fire Prevention and Investigation Division Number: IFC- 3001-1 Effective Date: February 1, 2012 Page 1 of 5 This policy

More information

National Fire Protection Association Report http://submittals.nfpa.org/terraviewweb/contentfetcher?commentparams=%28comment... Page 1 of 2 1/16/2014 Committee Input No. 104-NFPA 55-2013 [ Global Input

More information

SPECIFICATIONS. Approximate Weight: 10 oz. Surface Finish: Ra micro inch or less MATERIALS OF CONSTRUCTION

SPECIFICATIONS. Approximate Weight: 10 oz. Surface Finish: Ra micro inch or less MATERIALS OF CONSTRUCTION DIFFUSION-RESISTANT, DIAPHRAGM SEAL, EXCESS FLOW SHUT-OFF VALVES (FS SERIES) FS Series Excess Flow Shut-Off Valves are designed to automatically shut-off the delivery of gas in a line if the flow exceeds

More information

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES THIS BOOKLET CONTAINS PROPRIETARY INFORMATION OF ADVANCED SPECIALTY GAS EQUIPMENT CORP. AND IS PROVIDED TO THE PURCHASER SOLELY FOR USE

More information

RESOLUTION A.567(14) adopted on 20 November 1985 REGULATION FOR INERT GAS SYSTEMS ON CHEMICAL TANKERS

RESOLUTION A.567(14) adopted on 20 November 1985 REGULATION FOR INERT GAS SYSTEMS ON CHEMICAL TANKERS INTERNATIONAL MARITIME ORGANIZATION A 14/Res.567 16 January 1986 Original: ENGLISH ASSEMBLY - 14th session Agenda item lo(b) IMO RESOLUTION A.567(14) adopted on 20 November 1985 THE ASSEMBLY, RECALLING

More information

OCCUPATIONAL SAFETY AND ENVIRONMENTAL HEALTH GUIDELINE

OCCUPATIONAL SAFETY AND ENVIRONMENTAL HEALTH GUIDELINE OCCUPATIONAL SAFETY AND ENVIRONMENTAL HEALTH GUIDELINE Subject: Installation, Use and Maintenance of Gas Source Semiconductor Tools Date: 5/28/03 Revision: 00 SUMMARY: Individuals working with gas source

More information

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor)

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1. According to NFPA 99, SCFM is an acronym for. a) Surface Conditions at Fahrenheit Mercury b) Standard Conditions

More information

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS CHAPTER 35 FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS SECTION 3501 GENERAL 3501.1 Scope. The storage and use of flammable gases shall be in accordance with this chapter. Compressed gases shall also

More information

MEDICAL EQUIPMENT CATALOG

MEDICAL EQUIPMENT CATALOG THE MOST TRUSTED MEDICAL EQUIPMENT IN NORTH AMERICA MEDICAL EQUIPMENT CATALOG Total Components Including Bulk Oxygen Supply, Back up and Delivery Equipment Designs for High Pressure, Liquid or Bulk Applications

More information

Automatic Valve Proving Control

Automatic Valve Proving Control ISO 9001 Automatic Valve Proving Control 7 696 LDU11 UL recognized FM approved Features Performs leak test of the gas shut-off valves before start-up and/or immediately after burner shut-down No inlet

More information

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT. Number: 2015 IFC Effective Date: February 1, 2017 Page 1 of 5

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT. Number: 2015 IFC Effective Date: February 1, 2017 Page 1 of 5 Subject: COMPRESSED GAS Reference: IFC, Denver Amendments, NFPA Approved: Manuel Almaguer Division Chief, Fire Prevention Division Number: 2015 IFC- 5301-1 Effective Date: February 1, 2017 Page 1 of 5

More information

Dangerous Gas Standard

Dangerous Gas Standard Dangerous Gas Standard Purpose The purpose of this standard is to establish the minimum standards required for researchers at Clemson University that utilize dangerous gases (i.e., toxic, highly toxic,

More information

Change all references to Material Safety Data Sheets (MSDS) to Safety Data Sheets (SDS).

Change all references to Material Safety Data Sheets (MSDS) to Safety Data Sheets (SDS). National Fire Protection Association Report of 75 http://submittals.nfpa.org/terraviewweb/contentfetcher?commentpara... 12/9/2014 11:04 AM Second Revision No. 23-NFPA 55-2014 [ Global Comment ] Change

More information

Piped Air SCBA Refilling System Standard

Piped Air SCBA Refilling System Standard WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Piped Air SCBA Refilling System Standard SCOPE: This specification

More information

INSTRUCTIONS FOR HIGH PURITY, CHANGEOVER REGULATOR SYSTEMS (PCS, CRS SERIES)

INSTRUCTIONS FOR HIGH PURITY, CHANGEOVER REGULATOR SYSTEMS (PCS, CRS SERIES) INSTRUCTIONS FOR HIGH PURITY, CHANGEOVER REGULATOR SYSTEMS (PCS, CRS SERIES) THIS BOOKLET CONTAINS PROPRIETARY INFORMATION OF ADVANCED SPECIALTY GAS EQUIPMENT CORP. AND IS PROVIDED TO THE PURCHASER SOLELY

More information

TABLE OF CONTENTS PART 2 - CONFINED SPACES

TABLE OF CONTENTS PART 2 - CONFINED SPACES May 11, 2006 TABLE OF CONTENTS PART 2 - CONFINED SPACES Page DEFINITIONS... 2-1 GENERAL... 2-2 RESPONSIBILITIES... 2-2 HAZARD ASSESSMENT AND WORK PROCEDURES... 2-3 IDENTIFICATION AND ENTRY PERMITS... 2-3

More information

IH Report: SUFMO 08/09-CC21 1/27/2009 Stanford University Gas Cabinet Installation and Performance Criteria

IH Report: SUFMO 08/09-CC21 1/27/2009 Stanford University Gas Cabinet Installation and Performance Criteria Stanford University Gas Cabinet Installation and Performance Criteria I. Application Gas cabinets are ventilated enclosures that are used to isolate hazardous gas cylinders from the surrounding work place.

More information

The Air Liquide Gas System Equipment Brochure

The Air Liquide Gas System Equipment Brochure The Air Liquide Gas System Equipment Brochure The Equipment Manufacturing Center (EMC) was in dire need of marketing materials... A group of us teamed up to determine which systems needed highlighting,

More information

Cal/OSHA T8 CCR 1536 Cal/OSHA T8 CCR 4799 Cal/OSHA T8 CCR 4845 Cal/OSHA T8 CCR 4848

Cal/OSHA T8 CCR 1536 Cal/OSHA T8 CCR 4799 Cal/OSHA T8 CCR 4845 Cal/OSHA T8 CCR 4848 Cal/OSHA Gas Systems for Welding GAS WELDING Cal/OSHA T8 CCR 1536 Cal/OSHA T8 CCR 4799 Cal/OSHA T8 CCR 4845 Cal/OSHA T8 CCR 4848 When performing gas welding, the following precautions, work procedures,

More information

First Revision No. 16-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement

First Revision No. 16-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement of 152 2/9/2016 10:48 AM First Revision No. 16-NFPA 87-2015 [ Global Input ] Change document title to: Standard for Fluid Heaters See Word file for changes related to converting the document from a recommended

More information

Inert Air (N2) Systems Manual

Inert Air (N2) Systems Manual INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing

More information

Safetygram #26 Silane

Safetygram #26 Silane Safetygram #26 Silane Warning: Improper storage, handling or use of silane or its mixtures can result in serious injury and/or property damage. Handle this product in accordance with the Air Products and

More information

Safetygram #26 Silane

Safetygram #26 Silane Safetygram #26 Silane Warning: Improper storage, handling or use of silane or its mixtures can result in serious injury and/or property damage. Handle this product in accordance with the Air Products and

More information

STORAGE AND USE OF HIGH HAZARD GAS

STORAGE AND USE OF HIGH HAZARD GAS Page 1 of 9 STORAGE AND USE OF 1. Definition of High Hazard (HH) Gases For these guidelines, any gas meeting one or more of the following definitions based on International Fire Code (IFC) and National

More information

GAS COMPRESSION SYSTEM

GAS COMPRESSION SYSTEM GAS COMPRESSION SYSTEM The gas compression system at HI 376 A consists of two natural gas turbine-driven Compressors (CBA-4020/4070). Both Compressors are needed for the volume of gas being compressed.

More information

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series Introduction Powerex manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists of a regulator

More information

623 Series Dome Load Regulators

623 Series Dome Load Regulators ADI 3202C Certified ISO 9001 623 Series Dome Load Regulators INSTALLATION AND OPERATION INSTRUCTIONS This Equipment is intended to be installed and operated by trained personnel. Before Installing or Operating,

More information

Central Gas System Inquiry. Check List - Detailed Form

Central Gas System Inquiry. Check List - Detailed Form Central Gas System Inquiry Check List - Detailed Form Checklist for Installation When considering a centralized gas supply system there are a variety of areas to be consider. This checklist will assist

More information

MANUAL DIRECT PURGE OPTION. UNION Instruments GmbH CWD2005 PLUS. General information, safety standards and regulations for direct purge option

MANUAL DIRECT PURGE OPTION. UNION Instruments GmbH CWD2005 PLUS. General information, safety standards and regulations for direct purge option MANUAL DIRECT PURGE OPTION UNION Instruments GmbH CWD2005 PLUS General information, safety standards and regulations for direct purge option Version: V1.00 Stand: 24.03.2010 Union Instruments GmbH Zeppelinstr.

More information

Petro-Chemical & Analyzer Sampling Systems

Petro-Chemical & Analyzer Sampling Systems Petro-Chemical & Analyzer Sampling Systems Pressure control solutions for your industry. The Tescom brand offers a comprehensive range of regulators, valves and changeover systems that are ideal for analyzer

More information

Gas delivery systems. How to ensure uninterrupted high quality gas delivery from the source to the apparatus? Dr. Gastons Vereskuns Trakai,Lithuania

Gas delivery systems. How to ensure uninterrupted high quality gas delivery from the source to the apparatus? Dr. Gastons Vereskuns Trakai,Lithuania Gas delivery systems. How to ensure uninterrupted high quality gas delivery from the source to the apparatus? Dr. Gastons Vereskuns Trakai,Lithuania May 7, 2014 What it is gas delivery system? It is a

More information

TotalPac X Single interlock Preaction system Electric release

TotalPac X Single interlock Preaction system Electric release DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical and mechanical

More information

NGP-250/500 Nitrogen Generator Quick Start Guide

NGP-250/500 Nitrogen Generator Quick Start Guide NGP-250/500 Nitrogen Generator Quick Start Guide Version: A July 2013 Potter Electric Signal Company, LLC 5757 Phantom Dr., Suite 125 P. O. Box 42037 Hazelwood, MO 63042 Phone: (314) 595-6900 Document

More information

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions L 100 Bubble-Tube Level System Installation, Operation and Maintenance Instructions Figure 1 Contents Section Description Page 1.0 Introduction 2 2.0 Specifications 3 3.0 Installation 3 4.0 Warranty 6

More information

Installation of Ballast Water Management Systems

Installation of Ballast Water Management Systems (Sept 2015) (Rev.1 May 2016) Installation of Ballast Water Management Systems 1. Application In addition to the requirements contained in BWM Convention (2004), the following requirements are applied to

More information

Instruction Manual VCG-6

Instruction Manual VCG-6 Specifications Amps / Volts requirements 400 ma @ 24 VDC Propane pressure (VCG-6LP) 11 WC / 2.8 kpa Natural Gas pressure (VCG-6NG) 4.5 WC / 1.15 kpa Cu ft per hour / CO2 3-6 SCFH BTU Rating (Variable)

More information

PGM PREPIPED GAS MANIFOLD

PGM PREPIPED GAS MANIFOLD INSTRUCTIONS PGM PREPIPED GAS MANIFOLD WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components by unqualified

More information

Burner Management System DEMO Operating instructions

Burner Management System DEMO Operating instructions Burner Management System DEMO Operating instructions Burner Management System DEMO Operating Instructions Startup Summary - Normal startup is accomplished in four basic steps: 1. Leak Test a. Safety Valve

More information

INSTRUCTIONS FOR MODELS UPH & UPHS HIGH FLOW, HIGH PURITY GAS REGULATORS

INSTRUCTIONS FOR MODELS UPH & UPHS HIGH FLOW, HIGH PURITY GAS REGULATORS INSTRUCTIONS FOR MODELS UPH & UPHS HIGH FLOW, HIGH PURITY GAS REGULATORS THIS BOOKLET CONTAINS PROPRIETARY INFORMATION OF ADVANCED SPECIALTY GAS EQUIPMENT CORP. AND IS PROVIDED TO THE PURCHASER SOLELY

More information

MEGR-1912 Instruction Manual

MEGR-1912 Instruction Manual MEGR-1912 PRESSURE REGULATOR Instruction Manual- Look Inside For: Description Installation Start-Up Maintenance Parts Ordering Parts List Marshall Excelsior Company Marshall, MI 49068 269-789-6700 FAX

More information

ASHE Monograph. Medical Gas Cylinder and Bulk Tank Storage

ASHE Monograph. Medical Gas Cylinder and Bulk Tank Storage ASHE Monograph Medical Gas Cylinder and Bulk Tank Storage ASHE Monograph Medical Gas Cylinder and Bulk Tank Storage Susan B. McLaughlin, MBA, FASHE, CHFM, CHSP David A. Dagenais, CHSP, CHFM, SASHE JUNE

More information

ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E)

ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E) ECS Protector PGEN-30 (PGEN-30E) Specifications For use under U.S. Patents 8,720,591, 9,144,700 and 9,186,533 Dimensions (cabinet): 24.5 (W) x 52.5 (H) x 8.5 (D) (622mm(W) x 1,334mm(H) x 216mm(D)) Dimensions

More information

Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage.

Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage. Operating instructions GB VD Burners Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage. To the Equipment Owner: Please read

More information

CITY AND COUNTY OF DENVER CR&CF RISK UNIT Compressed Gas Safety Standard

CITY AND COUNTY OF DENVER CR&CF RISK UNIT Compressed Gas Safety Standard CITY AND COUNTY OF DENVER CR&CF RISK UNIT 65.5.11 Compressed Gas Safety Standard 1.0 Introduction 2.0 Scope This standard has been developed to protect all City and County of Denver employees and contractors

More information

COMPRESSED GASES CHAPTER 53

COMPRESSED GASES CHAPTER 53 CHAPTER 53 COMPRESSED GASES SECTION 5301 GENERAL 5301.1 Scope. Storage, use and handling of compressed gases in compressed gas containers, cylinders, tanks and systems shall comply with this chapter, including

More information

SNS BL-13B NPDGamma Experiment

SNS BL-13B NPDGamma Experiment SNS BL-13B NPDGamma Experiment Hydrogen Supply to Cryogenic Target, Relief and Vent System Design Review April 7, 2010 C-156 9:00 10:30 PM Hydrogen System Block Diagram Diagram of Major System Components

More information

DF-550E PROCESS ANALYSERS APPLICATIONS FEATURES

DF-550E PROCESS ANALYSERS APPLICATIONS FEATURES PROCESS ANALYSERS DF-550E The DF-550E Nano Trace oxygen analyser is a Coulometric sensor based analyser designed to measure oxygen as a contaminant at ultra trace levels in ultra high purity electronic

More information

Public Comment No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment

Public Comment No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Public Comment No. 4-NFPA 318-2013 [ Section No. 2.3.4 ] 2.3.4 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D5, Standard Test Method

More information

Propane Conversion Kit Instruction

Propane Conversion Kit Instruction Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates GB142-24 84,800 btu/hr GB142-30 106,000 btu/hr GB142-45 160,900 btu/hr GB142-60 214,800 btu/hr This kit and instructions are

More information

Chemical Feed Equipment Floor-Mounted Gas Dispenser - Series CH4200

Chemical Feed Equipment Floor-Mounted Gas Dispenser - Series CH4200 Specification Bulletin (rev.01) Series CH4200 Chemical Feed Equipment Floor-Mounted Gas Dispenser - Series CH4200 Easy, fast& accurate digital with 11 points calibration Laser sensor offering actual feed

More information

Propane Conversion Kit Instruction

Propane Conversion Kit Instruction Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates Logamax plus GB62-80 kw 270,000 btu/hr Logamax plus GB62-00 kw 35,000 btu/hr This kit and instructions are for converting the

More information

Manifolds & pressure reducing sets

Manifolds & pressure reducing sets Manifolds & pressure reducing sets Automatic Changeover Manifold (Electronic) Providing continuous supply of medical gases Pneumatech Medical Gas Solutions (PMGS) PureGAS Manifolds provide a duty or standby

More information

Propane Conversion Kit Instruction

Propane Conversion Kit Instruction Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates GB42-24 84,800 btu/hr Tab. GB42-30 06,000 btu/hr GB42-45 49,000 btu/hr GB42-60 24,800 btu/hr This kit and instructions are

More information

RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE

RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE March 22, 2013 RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE Regulators: Symptom: Pressure Drop Cause: External leaks detected at pigtail hose MPT fitting connection(s) to regulator body

More information

REGULATORS FOR SPECIFIC APPLICATIONS

REGULATORS FOR SPECIFIC APPLICATIONS SINGLE-STAGE REGULATORS FOR NITROUS OXIDE AND CARBON DIOXIDE (MODELS SG9011, SG9012, SG9014) Nitrous Oxide and Carbon Dioxide frequently cause ordinary regulators to freeze up. Models SG9011, SG9012 and

More information

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE February 9, 1998 Foam 101a A BLADDER TANK WITH 1. DESCRIPTION A Wet Pipe Bladder Tank Foam/Water System is a standard wet pipe automatic sprinkler system capable of discharging a foam/water solution automatically

More information

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection February 9, 1998 Foam 201a 1. DESCRIPTION A Deluge Bladder Tank Foam/Water System is a standard deluge system capable of discharging a foam/water solution automatically through open sprinklers, spray nozzles,

More information

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289 3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for

More information

Pressure Regulators. Operating Instructions. Instrumentation

Pressure Regulators. Operating Instructions. Instrumentation Pressure Regulators Operating Instructions FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THIS PRODUCT CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE. This document and other information from the

More information

Valve Proving System VDK 200 A S02

Valve Proving System VDK 200 A S02 Valve Proving System VDK 200 A S02 Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter

More information

Valve Proving System VDK 200 A S06*

Valve Proving System VDK 200 A S06* Valve Proving System VDK 200 A S06* Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter

More information

CENTRAL GAS SUPPLY SYSTEMS : CYLINDER BATTERIES AND HIGH PRESSURE HOSES

CENTRAL GAS SUPPLY SYSTEMS : CYLINDER BATTERIES AND HIGH PRESSURE HOSES P0170E-1.DOCX/08.16/MG CENTRAL GAS SUPPLY SYSTEMS : CYLINDER BATTERIES AND HIGH PRESSURE HOSES With a Central Gas Supply System, individual work places or gas take-off stations are supplied with gas through

More information

Oxford Instruments Plasma Technology. PlasmaPro NGP80. Installation Data Sheet. Original Instructions.

Oxford Instruments Plasma Technology. PlasmaPro NGP80. Installation Data Sheet. Original Instructions. Oxford Instruments Plasma Technology www.oxford-instruments.com About this data sheet This data sheet provides basic information about the installation of a tool. Floor and wall loadings Table 1 lists

More information

1 Exam Prep. Tabs and Highlights

1 Exam Prep. Tabs and Highlights 1 Exam Prep NFPA 14: Standard for the Installation of Standpipe and Hose Systems Tabs and s These 1 Exam Prep tabs are based on the NFPA 14: Standard for the Installation of Standpipe and Hose Systems,

More information

Thank You for Attending Today s Webinar. Today s Featured Speaker

Thank You for Attending Today s Webinar. Today s Featured Speaker Thank You for Attending Today s Webinar Your Host Mike DeLacluyse President Lesman Instrument Company miked@lesman.com Today s Featured Speaker A.J. Piskor Combustion & Controls Specialist Lesman Instrument

More information

INSTRUCTIONS FOR MODELS APC & APG HIGH PURITY, CORROSIVE GAS REGULATORS

INSTRUCTIONS FOR MODELS APC & APG HIGH PURITY, CORROSIVE GAS REGULATORS INSTRUCTIONS FOR MODELS APC & APG HIGH PURITY, CORROSIVE GAS REGULATORS THIS BOOKLET CONTAINS PROPRIETARY INFORMATION OF ADVANCED SPECIALTY GAS EQUIPMENT CORP. AND IS PROVIDED TO THE PURCHASER SOLELY FOR

More information

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures Operations & Service Manual TESCOM 50-4X Series Safety, Installation & Start-Up Procedures Do not attempt to select, install, use or maintain this product until you have read and fully understood this

More information

Petro-Chemical & Analyzer Sampling Systems

Petro-Chemical & Analyzer Sampling Systems Petro-Chemical & Analyzer Sampling Systems Pressure control solutions for your industry. The Tescom brand offers a comprehensive range of regulators, valves and changeover systems that are ideal for analyzer

More information

KC Series Gas Components and Supply Design Guide

KC Series Gas Components and Supply Design Guide Technical Bulletin KC Series Gas Components and Supply Design Guide GF-1030 General AERCO KC Series gas fired potable water heaters and boilers are modulating input devices that require an adequate volume

More information

Information Sheet. About this information sheet. Floor and wall loadings. Attachment of process module to floor. PlasmaPro Estrelas100

Information Sheet. About this information sheet. Floor and wall loadings. Attachment of process module to floor. PlasmaPro Estrelas100 Information Sheet PlasmaPro Estrelas100 About this information sheet This data sheet provides basic information about the installation of a PlasmaPro Estrelas100 tool. Some of the information in this sheet

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

Compressed Gases and Cryogens

Compressed Gases and Cryogens Compressed Gases and Cryogens University of Tennessee Safety Guide HM-011 Document Contact: EHS Date effective: January 1, 2009 Revision Date: October 1, 2015 Purpose This guideline adheres to the Occupational

More information

PERMA-CYL 230/450/1000/1500/2000. Installation Manual Manual # Revision B

PERMA-CYL 230/450/1000/1500/2000. Installation Manual Manual # Revision B PERMA-CYL 230/450/1000/1500/2000 Installation Manual Manual #11630833 - Revision B TABLE OF CONTENTS SAFETY 3 THE PERMA-CYL FAMILY 4 CONDUCTING A SITE EVALUATION 5 OUTDOOR INSTALLATION EXTERNALLY SITED/GAS

More information

INSTRUCTIONS FOR SINGLE STAGE LECTURE BOTTLE REGULATORS

INSTRUCTIONS FOR SINGLE STAGE LECTURE BOTTLE REGULATORS INSTRUCTIONS FOR SINGLE STAGE LECTURE BOTTLE REGULATORS THIS BOOKLET CONTAINS PROPRIETARY INFORMATION OF ADVANCED SPECIALTY GAS EQUIPMENT CORP. AND IS PROVIDED TO THE PURCHASER SOLELY FOR USE IN CONJUNCTION

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW, DOWNFLOW, UPFLOW/HORIZONTAL & HORIZONTAL ONLY INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this

More information

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302 SL 40-399 G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302 If converting from Propane to Natural Gas, order the Natural Gas Conversion Parts Kit (IBC Part # P-303) from your authorized IBC Distributor.

More information

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS Page 1 of 5 GUIDELINES FOR CONDUCTING 1. Definition of Hydrogenation and Hydrogenolysis Reactions Hydrogenation reactions are synthetic transformations involving hydrogen, metallic catalysts (such as nickel,

More information

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE 1 of 10 1. DESCRIPTION (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system

More information

NORMAL OPERATING PROCEDURES Operating Parameter Information

NORMAL OPERATING PROCEDURES Operating Parameter Information Operating Parameter Information Each operator performing the normal operating procedures (routine checks) of the facility should be familiar with the current normal operating parameters of all systems

More information

MANUAL GAS MANIFOLDS

MANUAL GAS MANIFOLDS MANUAL GAS MANIFOLDS Phoenix Pipeline Products Limited. Unit 8, McKenzie Industrial Park, Tel No.: 44 (0) 161 428 7200 Bird Hall Lane, Fax No.: 44 (0) 161 428 7010 Stockport, Email: info@p3-phoenix.com

More information

SERIES 30. Spring Operated Tank Blanketing Valve PROTECTOSEAL.

SERIES 30. Spring Operated Tank Blanketing Valve PROTECTOSEAL. SERIES 30 PROTECTOSEAL 1 2" NPT inlet and outlet standard Direct acting valve mechanism Optional flanged or threaded inlet and outlet connections available Inlet gas pressures from 10 PSIG to 200 PSIG

More information

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SUPPLIMENT TO eom IMPORTANT READ THIS MANUAL BEFORE PRODUCT INSTALLATION, OPERATION, INSPECTION & MAINTENANCE Tougher and more rigid guidelines are being established

More information

ACV-10 Automatic Control Valve

ACV-10 Automatic Control Valve ACV-10 Automatic Control Valve Installation, Operation & Maintenance General: The Archer Instruments ACV-10 is a precision automatic feed rate control valve for use in vacuum systems feeding Chlorine,

More information

I. Subject: Compressed gas cylinders, regulators, and portable liquid systems.

I. Subject: Compressed gas cylinders, regulators, and portable liquid systems. I. Subject: Compressed gas cylinders, regulators, and portable liquid systems. II. Objective: To provide safe and effective use, storage, and transport of therapeutic gases. II. Procedure: A. Compressed

More information

632 Series Gas Distribution System

632 Series Gas Distribution System ADI3223-B Certified ISO 9001:2000 632 Series Gas Distribution System INSTALLATION AND OPERATION INSTRUCTIONS Before Installing or Operating, Read and Comply with These Instructions Controls Corporation

More information

Highest Quality. Gas Chlorination Systems

Highest Quality. Gas Chlorination Systems Highest Quality Gas Chlorination Systems Application: Gas chlorination systems are used for water disinfection and other purposes in a variety of applications. Compared to other disinfection methods, chlorine

More information

Detector Carrier Gas Comments Detector anode purge or reference gas. Electron Capture Nitrogen Maximum sensitivity Nitrogen Argon/Methane

Detector Carrier Gas Comments Detector anode purge or reference gas. Electron Capture Nitrogen Maximum sensitivity Nitrogen Argon/Methane Gas requirements Gases for packed columns The carrier gas you use depends upon the type of detector and the performance requirements. Table 520-1 lists gas recommendations for packed column use. In general,

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Preaction 346a 1. Description The 6 Model G-6000P Electric Release Preaction System Riser Assembly can be used as a Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction

More information

FireLock NXT Dry Valve. System No. Submitted By Spec Sect Para Location Date Approved Date

FireLock NXT Dry Valve. System No. Submitted By Spec Sect Para Location Date Approved Date The patent-pending Victaulic Series 768 FireLock NXT is a low differential, latched clapper valve that uses a unique direct acting diaphragm to separate system water supplies from dry-pipe sprinkler systems.

More information

TECHNICAL DATA. than the water inlet pressure to the concentrate

TECHNICAL DATA. than the water inlet pressure to the concentrate Foam102a 1. DESCRIPTION The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with 3M foam concentrates. This system consists of a standard wet pipe sprinkler

More information

GAS SUPPLY DESIGN GUIDE

GAS SUPPLY DESIGN GUIDE GAS SUPPLY DESIGN GUIDE Natural Gas, Propane Gas, or Dual Fuel Fired Modulating, Condensing Boilers BENCHMARK Series Gas-Fired Boilers For models: BMK750 to BMK6000 Last Update: 06/20/2014 PR1 06/20/14

More information

Optimizing Gas Supply for Industrial Lasers

Optimizing Gas Supply for Industrial Lasers Optimizing Gas Supply for Industrial Lasers Laser cutting of metals and other materials has grown rapidly due to developments in laser power, advancements in CNC automation, and decreasing costs. The industrial

More information

ENVIRONMENTAL CONTROL SYSTEM (ECS)

ENVIRONMENTAL CONTROL SYSTEM (ECS) ENVIRONMENTAL CONTROL SYSTEM (ECS) DESCRIPTION AND OPERATION The ECS system comprises the following subsystems: bleed air management, environmental control unit (ECU) temperature control air distribution

More information

Installation and Operation Instructions

Installation and Operation Instructions Bentintoshape llc Installation and Operation Instructions Fire Pit - Hidden Tank Models www.bentintoshape.net INTRODUCTION Your bentintoshape Cor-Ten Steel Gas Fire Pit is designed for installation in

More information

IS YOUR FLAP VALVE IN COMPLIANCE WITH NFPA ?

IS YOUR FLAP VALVE IN COMPLIANCE WITH NFPA ? IEP Technologies 417-1 South Street, Marlborough, MA, 01752 ph 855.793.8407 fax 508.485.3115 www.ieptechnologies.com IS YOUR FLAP VALVE IN COMPLIANCE WITH NFPA 69-2014? Introduction Dust explosions can

More information