Dynamic Behaviour of Fault Gases and Online Gas Sensors. Germany

Size: px
Start display at page:

Download "Dynamic Behaviour of Fault Gases and Online Gas Sensors. Germany"

Transcription

1 21, rue d Artois, F PARIS A2-116 CIGRE 2016 http : // Dynamic Behaviour of Fault Gases and Online Gas Sensors S. TENBOHLEN 1, I. HÖHLEIN 2, M. LUKAS 3, A. MÜLLER 4, K. SCHRÖDER 5, U. SUNDERMANN 6 1 University of Stuttgart, 2 Siemens AG, 3 Vattenfall Europe Generation AG, 4 TÜV SÜD ET, 5 EMH GmbH, 6 Amprion Germany SUMMARY To ensure safe and secure operation of transformers a number of diagnosis techniques are known. Especially, the established dissolved gas analysis (DGA) can provide relevant information about internal transformer faults. Natural aging, thermal and electrical failures generate typical fault gases, which dissolve in the insulating oil. By analysing these fault gas profiles evidence about kind and severity of the fault can be estimated. A feasible gas based diagnosis requires the consideration of both, gas generation and gas losses. Gases escaping through the conservator tank may lead to misleading concentration levels and underrated gas generation rates. Therefore, the influence of gas losses on DGA based diagnoses should be considered. In this contribution a model of transformers gas losses dependent on oil temperature and the boundary surface area in the conservator is presented. A system of two differential equations is used for modelling the gas transport. At a higher oil exchange rate, the losses rise. The calculation shows that for free breathing transformers the fault gas loss is mainly influenced by the exchange of oil between main tank and conservator. Online instruments for gas-in-oil analysis may be based on other than gas chromatographic techniques, nevertheless bringing high accuracy and precision. A laboratory comparison between classical DGA and online DGA-monitors based on infrared technology or membrane extraction with consequent conductivity measurement of hydrogen and carbon monoxide has been performed and evaluated. The real time swift response to concentration changes, as well as the good correlation between laboratory and monitoring values make commercial instruments monitoring based on IR technology very promising for field applications. Several use cases show the possibilities but also limits of online condition monitoring with gas sensors. With the example of a large generator step-up transformer it is shown how the careful analysis of the dynamic the fault gas development offers the possibility to keep a faulty transformer longer in service. This enabled the utility to keep the power station as long in operation as needed for providing a backup transformer. KEYWORDS Power Transformer, Gas in Oil Analysis, Online Monitoring, IR spectroscopy, Gas Diffusion, Oil Flow Rate, Gas Loss Factor stefan.tenbohlen@ieh.uni-stuttgart.de

2 1 INTRODUCTION Regarding the availability of electrical energy networks power transformers play a dominant role for asset managers. To ensure safe and secure operation of transformers a number of diagnosis techniques are known. Especially, the established dissolved gas analysis (DGA) can provide relevant information about internal transformer faults. Natural aging, thermal and electrical failures generate typical fault gases, which dissolve in the insulating oil. By analysing these fault gas profiles evaluation on kind and severity of the fault can be estimated. Online Monitoring is a powerful tool, enabling the control of fault gas development continuously and thus guaranteeing an optimal energy transmission. The existing DGA standards are based on relatively complicated procedures, which can be well controlled under laboratory conditions. The field application, however, requires robustness and high long time precision for reliable trend development, which is the main focus of online monitoring. For an accurate diagnosis not only gas generation but also gas losses should be taken into account especially for free breathing transformers. Gases escaping through the conservator tank may lead to misleading concentration levels and underrated gas generation rates. Therefore, the influence of gas losses on DGA based diagnoses should be considered. Furthermore the dynamic behaviour and accuracy of online gas sensors hast to be taken into account. Several use cases show the possibilities but also limits of online condition monitoring using gas sensors. 2 DYNAMICS BETWEEN OIL AND GAS PHASE 2.1 Oil Flow Rate between Tank and Conservator A feasible gas based diagnosis requires the consideration of both, gas generation and gas losses. Gases escaping through the conservator tank may lead to misleading concentration levels and underrated gas generation rates especially for free breathing transformers [1, 2]. But also the other way round is possible: gases from the ambient air, mainly nitrogen and oxygen, are slowly dissolving in the conservator tank oil and are afterwards mixed with the main tank oil, too. An adequate model can help to assume the actual fault gas generation rate of a transformer. Thus, the severity of an upcoming fault could be determined more accurately for free breathing transformers. The loss of dissolved fault gases mainly depends on the conservator tank design. The oil is in direct contact to ambient air at free breathing conservator tanks. Fault gases can evaporate into the atmosphere and air gases can dissolve in the transformer oil. Free breathing conservator tanks for power transformers are common in several European and other countries [3]. Gas exchange does not occur at hermetically sealed transformers, transformers with a gas blanket or transformers with a membrane installed in the conservator tank. The exchange of dissolved gases through the conservator tank is called breathing. The oil transports dissolved fault gases from the main into the conservator tank. There, the different fault gas concentrations between oil and air are equalized by diffusion, which results in a loss of fault gases and an increase of ambient air gases. Breathing depends on the exchange rate between main tank and conservator [2]. The exchange rate depends on several factors: the entire oil volume of the transformer, the loading behaviour of the transformer, the ambient temperature, the design of the conservator tank and its connection to the main tank. The oil flow is driven by two effects. The temperature dependent oil density forces a volume change of the oil and hence a flow from the main tank into the conservator tank at rising temperatures because oil expands with app % K -1. Additionally, a convection effect occurs (natural circulation), which is caused by the temperature gradient between main tank top oil temperature and the oil temperature in the conservator tank which approximately equals ambient temperature. The flow rate for 26 different power transformers is calculated from thermal monitoring data in order to evaluate the effects of breathing [4]. The calculation only considers the oil flow due to volume change. The transformers nominal power varies between 31.5 and 850 MVA including generator step-up units, grid couplers and wind park transformers. Therefore, the loading and the cooling types are diverse. The resulting flow rates cover a wide range from 4 to 36 l/day per 1000 l oil volume for grid coupling and wind park transformers, both with volatile load factors. Generation step-up units 2

3 provide a flow rate of l/day per 1000 l oil volume, with stable load factors. ODWF units provide even lower flow rates because of a temperature controlled cooling system. 2.2 Laboratory Experiments for Evaporation via the Conservator The exchange of gases at the boundary surface between oil and ambient air in the conservator tank is simulated in a laboratory setup. Barrels are used as substitutes for a conservator tank. These barrels have a total volume of about 217 l. To vary the surface area between oil and ambient air inside, one experiment is carried out with an upright standing barrel with a boundary surface of about 0.26 m² and one with a horizontal barrel and a boundary surface of about 0.48 m². The oil volume is kept constant at 100(± 5) l. Thus, there is a gas volume with about 117 l over the oil, which is open to the atmosphere. All experiments use mineral oil. Before each experiment, the oil is degassed, dried, and filtered at 60 C with a vacuum oil treatment system. After degassing a fault gas mix is dissolved in the oil using a porous PTFE plastic. A. Influence of surface area The influence of the boundary surface between oil and ambient air on the loss of fault gases is examined by the two surface areas 0.26 m² and 0.48 m². The experiments are performed at room temperature. Throughout the experiment the oil is not moved. Fig. 1 (left) shows the concentration profile of hydrogen for the two different boundary surfaces. The curves are exponential partial regressions to the corresponding measured values, with C(t) = C 0 exp(-l t). The gas loss factor l has the unit 1/h and depends on the boundary surface area. The decrease of hydrogen concentration is faster for the larger surface area. Besides hydrogen, also other fault gases are analysed with the same experimental setup. Fig. 1 (right) shows the gas loss factors l of all gases for both surface areas. With a linear increasing surface area the gas loss factor also increases linearly. Thus, more gases evaporate. Hydrogen evaporates at the fastest rate, followed by CO and CH 4. H 6 evaporates the slowest. concentration (ppm) surface area 0.48 m² surface area 0.26 m² loss factor l (1/h) 8 x CO CH 4 H 4 H time (hours) surface area (m²) Figure 1: left: Concentration trend of hydrogen for different boundary surface areas right: Gas loss factor over surface area for different fault gases B. Temperature dependency In this series of experiments, the influence of temperature is investigated. Four temperatures are considered: room temperature (about 22 C), 35 C, 50 C and 65 C. All tests are performed using the same oil volume (100 l) and with a constant surface area between oil and ambient air (0.26 m²). Fig. 2 (left) shows the fitted gas loss factors l for all gases at different temperatures. The gas loss factors over temperature show an exponential increase. An exemplary exponential gradient over temperature is plotted for CO. Again, has a higher gas loss factor and is more volatile than the other presented gases. 3

4 loss factor l (1/h) CO CH 4 H 4 H 6 concentration (ppm) main tank, 20 l/h conservator, 20 l/h main tank, 40 l/h conservator, 40 l/h temperature ( C) time (days) Figure 2: left: Gas loss factors of different fault gases over temperature. Dashed line: exemplary exponential gradient for CO. right: Concentration trend for in main tank (straight line) and conservator (dashed line) at different oil exchange rates The large deviation between the gas loss factor at 22 C and 35 C may be explained by the experimental procedure. No heating of the test barrel is necessary at room temperature (22 C). At higher temperatures (35-65 C) a ring-shaped barrel heater is used. Due to the radial heat input a convection effect occurs in the oil. This leads to an increased mixing of the oil and thus to a higher gas loss factor. 2.3 Calculation of Fault Gas Losses The conducted experiments show the possibility to calculate the gas losses of a free breathing conservator tank by taking the oil temperature and the boundary surface area into account. Changes of the gas concentration in the main tank influence the concentration in the conservator tank and vice versa. Therefore, the derivative of each concentration is affected by the concentrations of both, main and conservator tank. A system of two differential equations is used for modelling the gas transport (1). (1) K(t) and A(t) are the time-dependent gas concentrations of the main tank oil K and of the conservator tank oil A; m, n, p and q are constants which depend on the volume, the gas loss factor and the oil exchange rate. The exemplary transformer has an oil volume of l for the simulation. The free breathing conservator tank of this transformer has an oil filled volume of 1700 l. The main tank contains a concentration of 200 ppm dissolved hydrogen as starting condition. At the beginning, there is no dissolved hydrogen in the conservator tank. The exchange between the main and conservator tank is assumed constant at 20 l/h (40 l/h) corresponding to the results shown in chapter 2.1. Every hour, 20 l oil flow into the conservator and back into the main tank. Temperatures are also considered constant. The gas loss factor in the conservator tank is set to l H2 = 0.1, which corresponds to a surface area of 1.5 m² and an average temperature of 15 C. The l H2 value is extrapolated from the values measured in the experiment presented above. Fig. 2 (right) shows the concentration trend for hydrogen with the previously made assumptions. The oil concentration of hydrogen in the main tank decreases exponentially. The concentration in the 4

5 conservator first increases and then decreases exponentially. At a starting concentration for of 200 ppm the loss corresponds to ppm/h or 2.06 ppm/d for an oil exchange of 20 l/h. At higher oil exchange rates also the losses rise. The comparison between the calculations for 20 l/h and 40 l/h shows, that the fault gas loss is strongly influenced by the exchange of oil between main and conservator tank. For an improved model further laboratory tests as well as the evaluation of existing measurements from real transformers have to be performed. 3 INVESTIGATION OF ACCURACY AND DYNAMIC RESPONSE OF ONLINE GAS SENSORS The requirements on gas-in-oil monitoring on-site are not less demanding compared to these in the laboratory. The DGA under laboratory conditions has been described in numerous standards and is based on gas chromatography, allowing a very low detection limit. Laboratory methods, however, require intensive maintenance, e.g. change of parts as well as gas supply and trained personnel. On-site gas monitors have higher challenges in the sense of robustness and long term stability [5]. To meet these requirements other techniques than gas chromatography are becoming more competitive. In the case of the single gas (or warn type) monitors the conductivity sensor technology for detecting gases like hydrogen or carbon monoxide has found wide application. Single gas sensors with membrane gas extraction technology can be robust but they have typically limited accuracy. In addition their oil transport system based on alternating temperature inlet change requires averaging and filtering of raw values due to the variation of those values from conductivity sensors with the temperature inlet change. Figure 3 shows the reaction of raw values ( sensor output in µs) and filtered/averaged values ( display value in ppm) on a stepwise increase of gas in oil content for a hydrogen and carbon monoxide (warn type) sensor. It is based on a conductivity sensor with membrane extraction and a transport system based on alternating temperature inlet change (sensor oil temperature in C). Due to the alternating sensor oil temperature the displayed value has to be filtered which results in an output delay of app. one hour. Figure 3: Dependency of raw values ( sensor output in µs) and filtered/averaged values ( display value in ppm) on alternating temperature inlet change (Sensor oil temp.) For the determination of hydrocarbon gases as well as carbon oxides one or multi fold type channel IR based on-site monitors are already state of art. Infrared technology is robust. In combination with hydrogen detection by means of e.g. conductivity detectors, it allows a simultaneous high resolution and fast response determination of the fault gases responsible for major faults. An important part of the system is the gas extraction out of the oil. Wide spread systems are membrane or head space extraction. The reliability of the sensor is depending on its ability to sample and analyse representative oil out of the bulk. Important is the transport of the oil out of the tank to the analysing system this could be pump enabled or by alternating temperature inlet change. Manufacturers of on-line monitors indicate accuracy and stability of measurement which, however, are always connected to certain testing setups and very difficult to be validated by users. The calculation 5

6 of detection limit, repeatability and reproducibility according statistic procedures e.g. DIN are applicable for laboratory methods, but not for on-line measuring equipment. Of importance for the user is the comparability of the values to laboratory methods, as well as the quick response to changing gas concentrations. In this study a comparison of the absolute values of a commercial IRbased on-line monitor with laboratory gas-in-oil values has been performed. The examined gas-in-oil monitor is able to determine simultaneously carbon monoxide, acetylene and ethylene by means of IR spectroscopy and hydrogen by means of a microelectronic sensor. The concentration in the oil has been reached by the introducing of a gas mixture of hydrocarbons, carbon monoxide, carbon dioxide, atmospheric gases and hydrogen in the system and circulating the oil at ambient temperature and 40 C. The concentration has been continuously monitored by taking samples and analysing these with laboratory DGA for comparison. Since the starting concentration of the hydrocarbons was relatively high, a partial degassing during circulation has been performed in order to follow the rate of concentration change. The test has been done on a testing device, consisting of degassing unit used simultaneously as a conservator, tank with possibility of heating, circulating unit, connected with the tank and conservator where the monitoring devices are attached, and vacuum and circulating pumps. The comparison between the monitor readings and laboratory gas-in-oil analysis of the corresponding fault gases is presented on Figure 4 to Figure 6. Figure 4: Comparison of low range monitored hydrogen values with laboratory gas-in-oil values Figure 5: Comparison of low range monitored carbon monoxide values with laboratory gas-in-oil values Figure 6: Comparison of monitored ethylene values with laboratory gas-in-oil values Figure 7: Development of hydrogen and acetylen after an electrical failure 6

7 Generally the monitoring values of hydrogen, carbon monoxide and hydrocarbons even in a low level are in a good agreement with the laboratory values and within the 20 % uncertainty (Figure 4, Figure 5). The values of ethylene seem to be consequently higher in comparison to these measured by means of GC (Figure 6). Since the gas mixture contained propylene, it seems probable that the ethylene monitoring value is a sum value of the unsaturated hydrocarbons, which however does not interfere with common evaluation criteria. The tested monitoring device is vacuum proof. The applied vacuum caused a decrease in the gas-in-oil values as expected. This decrease was well seen as trend not only in the laboratory gas-in-oil values, but also in the monitoring level. Figure 7 shows a significant and fast increase of both hydrogen and acetylene values from a multigas sensor for hydrogen, carbon monoxide, acetylene and ethylene mounted on a 100 MVA 220/23,8 kv transformer after an electrical failure. The high values for both hydrogen and acetylene have been confirmed by both portable offline DGA as well as laboratory DGA analysis. The transformer has been taken off service and it has been inspected by the manufacturer. After switching off the transformer the gas production stopped. This real time swift response to concentration changes, as well as the good correlation between laboratory and monitoring values make commercial instruments monitoring based on IR technology very promising for field applications. However multigas sensors based on other extraction principles then membrane extraction (e.g. head space or vacuum extraction) present other challenges due to the need of moving parts to realize the oil transport and gas extraction (pump, compressor, flow meter, oil and gas vales and oil level sensors). Potential solutions and future research work could therefore be the combination of new membrane extraction technologies in combination with IR gas sensing principle. 4 USE CASES FROM ONSITE MEASUREMENTS 4.1 Gassing Behaviour due to Broken Potential Connection Figure 8 shows, as an example for early fault recognition, a developing hydrogen content measured by single gas monitor mounted at a 400 kv single phase GSU transformer (267 MVA). After detection of the increased hydrogen level a conventional DGA was performed that validated the hydrogen level and showed an additional amount of acetylene. With respect to the DGA a PD measurement was performed that showed a PD-level of several nano coulombs, the PD location pointed to a failure location at the connection of the HV bushing. The final inspection of the bushing and the lead connection showed a broken potential connection of the HV screening electrode. As a conclusion gas monitors are useful to detect faults like PD or hot spots, where the fault development is coupled with gas generation. Figure 8: Hydrogen level of a 400 kv single phase GSU transformer with broken potential connection 7

8 4.2 Gassing Behaviour after Inter Turn Failure On the other hand gas sensors can t detect faults where no gas is produced or where the fault development is spontaneous. Figure 9 shows the reading of a single gas monitor mounted at a 400 kv three phase GSU transformer (750MVA) before and after a serious fault. Before the fault the measured gas concentration was constant and in good correlation to the conventional DGA. After the tripping of the Buchholz relay a steep increase of the gas content appeared. The inspection of the active part of the transformer showed an inter turn failure within the HV winding of one phase. It is typical for inter turn failures that the gas generation starts not till the discharge occurs. Gas monitors are also helpful to ensure the integrity of a transformer when operating out of normal service conditions. Figure 9: Gas concentration of a 400 kv GSU transformer before and after an inter turn failure 4.3 Gassing Behaviour under Overload Condition Figure 10 shows the reading of a single gas monitor mounted at a 750 MVA GSU transformer with overload capability of 1000 MVA. Due to a failure of a transformer in parallel the unit had to operate at a load of 1000 MVA during a period of some months. When starting the overload operation a steep increase of the measured gas concentration was detected. Conventional DGA showed that the increase was caused by the increase of CO concentration with respect to the higher temperatures. After a few days the gas concentration stayed constant and remained stable until the overload operation was finished. After some months of normal operation the gas concentration decreased to the level the transformer had before the overload operation started. Figure 10: Gas concentration of a 750 MVA GSU transformer with overload capability of 1000 MVA before and after overload operation 8

9 4.4 Extension of Operating Time by DGA Monitoring A 600 MVA / 380 kv generator step-up unit monitored by an IR-based multi gas analyser showed in the beginning of July a strong and continuous increase of dissolved combustible gases (Figure 11). Because of the high TDCG rate (total dissolved combustible gases) of more than 100 ppm/day, in parallel to the DGA monitoring system oil samples were analysed in the laboratory daily. This offered the possibility to check the deviation between monitoring and laboratory results. The dissolved gas was extracted by headspace and vacuum technology. Hydrocarbons showed very good agreement between monitoring and laboratory values (Figure 11a). The highest deviations occurred with hydrogen, which could be attributed to its high diffusivity. But although the oil samples analysed in the laboratory revealed slightly different absolute gas values, the failure cause and trend corresponded fairly well with the monitoring results. Most notably hydrogen, methane, ethane and ethylene were generated in high amounts. The Duval triangle indicated a thermal fault with temperatures above 700 C. The concentration of CO and CO 2 stayed almost constant, which indicated no involvement of paper in the fault. Because the amount of acetylene increased during the first 50 days quiet slowly just by app. 15 ppm melting of the core laminations was also excluded as failure cause. a) b) Figure 11: Gas concentration of a 600 MVA / 380 kv GSU transformer In the beginning of August the total amount of dissolved combustible gases (app ppm) and respective generation rate exceeded the values given as Condition 4 according to IEEE Std C57.104, which suggests to remove the transformer from service under these circumstances [6]. Despite of the high dissolved combustible gas amounts (see Figure 11b) no undissolved gases could be detected in the Buchholz relay. Additionally the very low level of acetylene led to the decision to keep the transformer in service until a spare transformer would be in place. If the rise of acetylene had exceeded 5ppm/day in an interval of two days or an abrupt rise of 5 ppm/h occurred, the transformer would have been switched off immediately. Due to the continuous monitoring of the different fault gases this strategy of supervised extension of operation was possible in order to prevent switching off the power station with its high financial impact. The reduction of load factor showed a stagnation of the gas generation. Based on the DGA results as potential failure causes problems with current leads (e.g. increased resistance of selector contacts or crimped connections) or circulating currents were taken into account. Unfortunately the repetitive changing of tap positions didn t change the gassing behaviour. After a further increase of the gassing rate the loading of the transformer was reduced by 50 %. Due to this load reduction the gas production stopped immediately, which at least could be interpreted as a temporary intermission of the failure. Also the following load increase showed no resumption of the failure. 9

10 On 10 th of September the transformer was switched off as scheduled and exchanged by a spare unit provided at that moment. A visual inspection of the tank revealed that due to mechanical problems the tank got in contact with the magnetic core sheets, which resulted in circulating currents via the normal core grounding system. This circulating current is induced by the load dependent stray flux and can reach levels of some hundred amperes. At the contact point of tank and core a hot spot with oil carbon was visible indicating the decomposition of the oil. Additionally the copper cable for the normal grounding of the core outside on top of the tank was melted which led to the intermission of the failure. 5 CONCLUSION A feasible gas based diagnosis requires the consideration of both, gas generation and gas losses. A model for free breathing transformers gas losses dependent on oil temperature and the boundary surface area in the conservator is presented. A system of two differential equations is used for modelling the gas transport. At a higher oil exchange rate between tank and conservator the losses rise. The calculation shows that for free breathing transformers the fault gas loss is mainly influenced by the exchange of oil between main tank and conservator. A laboratory comparison between classical DGA and online DGA-monitors based on infrared technology or membrane extraction with successive conductivity measurement of hydrogen and carbon monoxide has been performed and evaluated. The real time swift response to concentration changes, as well as the good correlation between laboratory and monitoring values make commercial instruments monitoring based on IR technology very promising for field applications. Several use cases show the possibilities but also limits of online condition monitoring with gas sensors for the identification of developing faults. With the example of a large generator step-up transformer it is shown how the careful attention of the dynamic fault gas development offers the possibility to keep a faulty transformer longer in service. This enables the utility to keep the power station longer in operation in order to provide a spare transformer. 6 BIBLIOGRAPHY [1] R. Anderson, U-R. Roderick, V. Jaakkola, N. Östman, The transfer of fault gases in transformers and its effect upon the interpretation of gas analysis data, Cigré Report 12-02, 1976 [2] E. Bräsel, O. Bräsel, U. Sasum, Gashaushalt bei Transformatoren der offenen Bauart Neue Erkenntnisse, ew, Jg. 109, Heft 14-15, pp , 2010 [3] Cigré Brochure 296, Recent Developments in DGA Interpretation, June 2006 [4] A. Müller, S. Tenbohlen, Analysis of Fault Gas Losses through the Conservator Tank of Free- Breathing Power Transformers, 18 th Int. Symp. on High Voltage Engineering, Seoul, South Korea, 2013 [5] Cigré Brochure 409, Report on Gas Monitors for Oil-Filled Electrical Equipment, February 2010 [6] IEEE Std. C57.104, IEEE Guide for the Interpretation of Gases Generated in Oil-Immersed Transformers,

Online DGA-monitoring of power transformers

Online DGA-monitoring of power transformers Online DGA-monitoring of power transformers Senior Industry Expert, Vaisala Finland Member of CIGRE A2/D1.47 and D1.52 WGs April 2018 Vaisala Webinar content 1. Dissolved gases why and which gases 2. Fault

More information

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS M. Jovalekic 1*, D. Vukovic 1 and S. Tenbohlen 1 1 Institute of Power Transmission and High Voltage Technology (IEH) University

More information

A Revised Framework for the Transformer DGA Guide

A Revised Framework for the Transformer DGA Guide A Revised Framework for the Transformer DGA Guide Jim Dukarm for WG C57.104 Spring 2007 Presentation Topics Purpose and scope of the Guide Main departures from earlier versions Definition of transformer

More information

Improved Monitoring of Dissolved Transformer Gases on the Basis of a Natural Internal Standard (NIS)

Improved Monitoring of Dissolved Transformer Gases on the Basis of a Natural Internal Standard (NIS) CIGRÈ 23 BRUGGE 2007 Improved Monitoring of Dissolved Transformer Gases on the Basis of a Natural Internal Standard (NIS) E. Bräsel, U. Sasum Gatron Germany Eckhard.Braesel@gatron.de J. Aragon-Patil, S.

More information

Mathieu Guertin. Morgan Schaffer Inc. Canada. Director Europe, Russia and Africa. A cost effective strategy for smart grid technology adoption

Mathieu Guertin. Morgan Schaffer Inc. Canada. Director Europe, Russia and Africa. A cost effective strategy for smart grid technology adoption Mathieu Guertin Director Europe, Russia and Africa Morgan Schaffer Inc. Canada A cost effective strategy for smart grid technology adoption Why protecting assets? Cost of fault: $52 MILLIONS!!! Easy ROI

More information

Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers

Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers Maintenance Practices & Procedures for Substation Class Distribution Power Transformers Why should special maintenance practices be applied to power transformers? Power transformers utilize active cooling

More information

MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS

MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS Zohra Khan 1, Avinash Paranjpe 2 1 ME Student, Electrical Power System, PES COE/ Dr. B.A.M. University, (India)

More information

Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers

Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers P. Werle, C. Radigk ABB Transformatoren GmbH Halle, Gemany peter.werle@de.abb.com W. Sorgatz

More information

Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI

Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI A THESIS SUBMITTED IN PARTIAL FULFILLMENT OF THE REQUIREMENTS FOR THE DEGREE OF Master of Technology

More information

Categorizing Faults via DGA. GE Grid Solutions M&D

Categorizing Faults via DGA. GE Grid Solutions M&D ategorizing Faults via DGA GE Grid Solutions M&D First, What Is Transformer Dissolved Gas Analysis? Sample Test Doc Diagnosis Doctors extract information about our health from our blood. Technicians extract

More information

Understanding Dissolved Gas Analysis (DGA) Techniques and Interpretations

Understanding Dissolved Gas Analysis (DGA) Techniques and Interpretations By Jeff Golarz ABSTRACT The use of Dissolved Gas Analysis (DGA) as a method for determining the types of pending or occurring faults within power transformers has been in practice for many years. It has

More information

Dissolved Gas Analysis - Past, Present and Future

Dissolved Gas Analysis - Past, Present and Future I. INTRODUCTION Dissolved Gas Analysis - Past, Present and Future Fredi Jakob Weidmann-ACTI Inc. It has been well over thirty years since dissolved gas analysis, DGA, was introduced as a diagnostic tool

More information

TRANSFORMER SERVICE. Dissolved gas analysis and oil condition testing

TRANSFORMER SERVICE. Dissolved gas analysis and oil condition testing TRANSFORMER SERVICE Dissolved gas analysis and oil condition testing D I S S O LV E D G A S A N A LY S I S A N D O I L C O N D I T I O N T E S T I N G Transformer diagnostic services at ABB perform dissolved

More information

EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS

EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS The 9 th International Symposium on High Voltage Engineering, Pilsen, Czech Republic, August, 23 28, 25 EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS

More information

* Analysis of TCG ( Total Combustible Gas ) and 6 kinds of Gases * High Sensitivity for C 2

* Analysis of TCG ( Total Combustible Gas ) and 6 kinds of Gases * High Sensitivity for C 2 Portable DGA Dissolved Gas Analyzer MITSUBISHI Portable Dissolved Gas Analyzer (PGA-300) is used to analyze 6 kinds of dissolved gases in transformer oil, thereby improving prompt action

More information

Since the beginning of production of oil for transformers

Since the beginning of production of oil for transformers EVENTS DIAGNOSTICS Photo courtesy of Končar D&ST, Zagreb, Croatia Chromatographic analysis of gases from the transformer The process of creating and detecting gases in the transformers ABSTRACT Given the

More information

DGA Tools: Duval Triangles and Pentagons

DGA Tools: Duval Triangles and Pentagons DGA Tools: Duval Triangles and Pentagons C. Beauchemin, TJH2b Analytical Services Inc. Initially presented at the TechCon SE Asia, Kuala Lumpur, April 10, 2017 This presentation use some material from

More information

DSC 204 HP Phoenix. High-Pressure Differential Scanning Calorimetry up to 15 MPa Method, Technique and Applications

DSC 204 HP Phoenix. High-Pressure Differential Scanning Calorimetry up to 15 MPa Method, Technique and Applications DSC 204 HP Phoenix High-Pressure Differential Scanning Calorimetry up to 15 MPa Method, Technique and Applications DSC 204 HP Phoenix The ability to apply pressure improves the capabilities of Differential

More information

Technical Data Sheet MF010-O-LC

Technical Data Sheet MF010-O-LC Technical Data Sheet MF010-O-LC - 1 - 1. Properties The oxygen measuring system MF010-O-LC determines the oxygen content in gas mixtures up to a temperature of 250 C. It is particularly suitable for the

More information

TRANSFORMER RELIABILITY AND DISSOLVED-GAS ANALYSIS. Delta-X Research Inc, Victoria BC, and 2 IREQ, Varennes QC CANADA

TRANSFORMER RELIABILITY AND DISSOLVED-GAS ANALYSIS. Delta-X Research Inc, Victoria BC, and 2 IREQ, Varennes QC CANADA 21, rue d Artois, F-75008 PARIS CIGRÉ-807 2016 CIGRÉ Canada Conference http : //www.cigre.org Vancouver, BC Canada, October 17-19, 2016 TRANSFORMER RELIABILITY AND DISSOLVED-GAS ANALYSIS J. J. DUKARM 1

More information

Real-time Analysis of Industrial Gases with Online Near- Infrared Spectroscopy

Real-time Analysis of Industrial Gases with Online Near- Infrared Spectroscopy Real-time Analysis of Industrial Gases with Online Near- Infrared Branch 5 Petrochemical, Biofuels Keywords Process, NIR, Gases, Gas Cell, Ethylene, Carbon Dioxide, Propane, Butane, Acetylene Summary Near-infrared

More information

A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION

A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION Athira K Anil 1, Archana R 2 1 PG Student, Electrical and Electronics Engineering, FISAT, Kerala, India 2 Associate Professor, Electrical

More information

Managing on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution power transformers

Managing on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution power transformers 24th International Conference & Exhibition on Electricity Distribution (CIRED) 12-15 June 2017 Session 1: Network components Managing on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution

More information

Measurement of Representative Landfill Gas Migration Samples at Landfill Perimeters: A Case Study

Measurement of Representative Landfill Gas Migration Samples at Landfill Perimeters: A Case Study Measurement of Representative Landfill Migration Samples at Landfill Perimeters: A Case Study Breda M. Kiernan, PhD. National Centre for Sensor Research, Dublin City University Glasnevin Dublin 9 Ireland

More information

LINEAR TRANSFORMATION APPLIED TO THE CALIBRATION OF ANALYTES IN VARIOUS MATRICES USING A TOTAL HYDROCARBON (THC) ANALYZER

LINEAR TRANSFORMATION APPLIED TO THE CALIBRATION OF ANALYTES IN VARIOUS MATRICES USING A TOTAL HYDROCARBON (THC) ANALYZER LINEAR TRANSFORMATION APPLIED TO THE CALIBRATION OF ANALYTES IN VARIOUS MATRICES USING A TOTAL HYDROCARBON (THC) ANALYZER Michael T Tang, Ph.D. Grace Feng Greg Merideth Rui Huang Matheson Gas Applied Lab

More information

Impact of Vacuum treatment on DGA Dipl.-Ing. J. Altmann

Impact of Vacuum treatment on DGA Dipl.-Ing. J. Altmann 1 1. Introduction Impact of Vacuum treatment on DGA Dipl.-Ing. J. Altmann State of the art for the diagnosis of undesired changes in the Insulating Systems of oilimmersed transformers is DGA - Dissolved

More information

Nandkumar Wagh, D.M. Deshpande

Nandkumar Wagh, D.M. Deshpande International Journal of Scientific & Engineering Research, Volume 4, Issue 9, September-2013 2503 Fuzzy Decision on Transformer Fault Diagnosis using Dissolved Gas Analysis and IEC Ratio Codes Nandkumar

More information

Research Article. Fault diagnosis of power transformer based on chemical properties of insulation oil

Research Article. Fault diagnosis of power transformer based on chemical properties of insulation oil Available online www.jocpr.com Journal of Chemical and Pharmaceutical Research, 015, 7(3):83-88 Research Article ISSN : 0975-7384 CODEN(USA) : JCPRC5 Fault diagnosis of power transformer based on chemical

More information

ENVIRONMENTAL AND POLLUTANTS GAS ANALYZERS

ENVIRONMENTAL AND POLLUTANTS GAS ANALYZERS XIX IMEKO World Congress Fundamental and Applied Metrology September 6, 9, Lisbon, Portugal ENVIRONMENTAL AND POLLUTANTS GAS ANALYZERS Ana Madeira, Florbela A. Dias and Eduarda Filipe 3 Instituto Português

More information

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT - 277 - NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT Iseler J., Heiser W. EAS GmbH, Karlsruhe, Germany ABSTRACT A numerical study of the flow behaviour

More information

The Role of Gas Monitoring in the Prevention and Treatment of Mine Fires

The Role of Gas Monitoring in the Prevention and Treatment of Mine Fires University of Wollongong Research Online Coal Operators' Conference Faculty of Engineering and Information Sciences 28 The Role of Gas Monitoring in the Prevention and Treatment of Mine Fires D. Brady

More information

Impact of imperfect sealing on the flow measurement of natural gas by orifice plates

Impact of imperfect sealing on the flow measurement of natural gas by orifice plates Impact of imperfect sealing on the flow measurement of natural gas by orifice plates Rubens Silva Telles 1, Kazuto Kawakita 2 1 IPT Instituto de Pesquisas Tecnológicas, São Paulo, Brazil, rtelles@ipt.br

More information

Nitrogen subtraction on reported CO 2 emission using ultrasonic flare gas meter

Nitrogen subtraction on reported CO 2 emission using ultrasonic flare gas meter Nitrogen subtraction on reported CO 2 emission using ultrasonic flare gas meter Kjell-Eivind Frøysa, Christian Michelsen Research AS, Bergen, Norway Henning Ekerhovd, StatoilHydro ASA, Kollsnes, Norway

More information

Draft Guide for the Interpretation of Gases in Oil Immersed Transformers

Draft Guide for the Interpretation of Gases in Oil Immersed Transformers Draft Guide for the Interpretation of Gases in Oil Immersed Transformers Sponsored by the Transformers Committee of the IEEE Power Engineering Society Copyright 2004 by the Institute of Electrical and

More information

MIL-STD-883G METHOD

MIL-STD-883G METHOD STEADY-STATE LIFE 1. PURPOSE. The steady-state life test is performed for the purpose of demonstrating the quality or reliability of devices subjected to the specified conditions over an extended time

More information

Performance Overview calibration Laboratory EP Instruments Messtechnik und Kalibrierung GmbH

Performance Overview calibration Laboratory EP Instruments Messtechnik und Kalibrierung GmbH Performance Overview calibration Laboratory EP Instruments Messtechnik und Kalibrierung GmbH 1 D-K-15143-01-00 Services around the measurement technology in Germanys most accurate DAkkS laboratory*. Whether

More information

Courses of Instruction: Controlling and Monitoring of Pipelines

Courses of Instruction: Controlling and Monitoring of Pipelines Courses of Instruction: Controlling and Monitoring of Pipelines Date December 2010 Dr. Peter Eschenbacher Partner Angergraben 4 85250 Altomünster Germany Tel. +49-(0)8254 / 99 69 57 Fax +49-(0)8254 / 99

More information

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV 16-1 INTRODUCTION 16-1.1 Purpose. The purpose of this chapter is to familiarize divers with the techniques used to mix divers breathing gas. 16-1.2 Scope. This chapter

More information

Intelligent SUNTEX DC-5310(RS) Dissolved Oxygen Transmitter

Intelligent SUNTEX DC-5310(RS) Dissolved Oxygen Transmitter Intelligent SUNTEX DC-5310(RS) Dissolved Oxygen Transmitter Overview C % ppm 4~20mA Analog Output ppb Power Supply 100~240 VAC mg/l Dimensions 96 x 96 x 132mm RS-485 Digital Output (for DC-5310-RS only)

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

Columbus Instruments

Columbus Instruments 0215-003M Portable O 2 /CO 2 /CH 4 Meter User s Manual Columbus Instruments 950 NORTH HAGUE AVENUE TEL:(614) 276-0861 COLUMBUS, OHIO 43204, USA FAX:(614) 276-0529 1 www.colinst.com TOLL FREE 1-800-669-5011

More information

AUK Environmental Sensor. Determining the refractive index of the air. AUK Environmental Sensor

AUK Environmental Sensor. Determining the refractive index of the air. AUK Environmental Sensor AUK Environmental Sensor Environmental influences can be compensated in two ways: 1. "Manual" input of the current data for air temperature, humidity and pressure and the material temperature of the testpiece

More information

Axpo Power Ltd. 2) GE Grid Solutions

Axpo Power Ltd. 2) GE Grid Solutions PS 3 SF6-free 123 kv Substation Solution to meet Axpo s sustainability strategy C. LINDNDER 1), D. GAUTSCHI 2) 1) Axpo Power Ltd. 2) GE Grid Solutions SUMMARY As it is the strategic goal of Axpo Power

More information

Title: Standard Operating Procedure for Measurement of Ethylene (C 2 H 4 ) in Ambient Air by Reduced Gas Detection (RGD)

Title: Standard Operating Procedure for Measurement of Ethylene (C 2 H 4 ) in Ambient Air by Reduced Gas Detection (RGD) Procedure No: SOP-026 Revision No: 1.0 January 24, 2011 Page No.: 1 of 10 1. INTRODUCTION AND SCOPE To obtain timely data for the purpose of air quality assessment, air quality trend reporting and to meet

More information

Working in Gas Hazard Areas

Working in Gas Hazard Areas / Health & Safety OPERATIONS STANDARDS Ref.: Aperam Safety ST 012 Working in Gas Hazard Areas Issue: 15.05.2012 Vers.: v0 Rev.: AM Safety ST 012 v1.2 08.05.2012 Working in Gas Hazard Areas Controlled Updated

More information

Elektromotoren und Gerätebau Barleben GmbH. Kooperationspartner Transformatorgase. Universal Breathing Buffer Box (G3B)

Elektromotoren und Gerätebau Barleben GmbH. Kooperationspartner Transformatorgase. Universal Breathing Buffer Box (G3B) Elektromotoren und Gerätebau Barleben GmbH Kooperationspartner Transformatorgase Universal Breathing Buffer Box (G3B) Elektromotoren und Gerätebau Barleben GmbH Table of contents page 1. Extension of the

More information

Gas density monitor With integrated transmitter Model GDM-100-TI

Gas density monitor With integrated transmitter Model GDM-100-TI SF 6 gas solutions Gas density monitor With integrated transmitter Model GDM-100-TI grid Products WIKA data sheet SP 60.05 for further approvals see page 5 Applications Gas density monitoring of closed

More information

Commercial Practice Test Method Internal Vapor Analysis of Hermetic Devices

Commercial Practice Test Method Internal Vapor Analysis of Hermetic Devices Commercial Practice Test Method Internal Vapor Analysis of Hermetic Devices Oneida Research Services, Inc. 8282 Halsey Road Whitesboro, NY 13492 Phone: (315) 736-5480 FAX: (315) 736-9321 1.0 Purpose The

More information

Title: Standard Operating Procedure for Dasibi Model 5008 Gas Dilution Calibrator

Title: Standard Operating Procedure for Dasibi Model 5008 Gas Dilution Calibrator Procedure No: SOP-034 Revision No: 1.0 Revised Dec. 29, 2010 Page No.: 1 of 10 1. INTRODUCTION AND SCOPE This procedure is intended to describe the operations of the Dasibi model 5008 calibrator. The Dasibi

More information

WP2 Fire test for toxicity of fire effluents

WP2 Fire test for toxicity of fire effluents Pagina 3 di 89 TRA SFEU VTT 22.6.2009 v.2 WP2 Fire test for toxicity of fire effluents Task 2.1.2 Development of small-scale test method for fire effluents Step 1: Use of modeling Plans according to DoW:

More information

Diagnostics of HV bushings through oil sampling and analysis. Experience with GSU transformers

Diagnostics of HV bushings through oil sampling and analysis. Experience with GSU transformers DIAGNOSTICS Bushings are a critical part of the transformer, and their failures often have destructive consequences for the transformer, with a high risk of fire ABSTRACT Bushings are highly stressed parts

More information

The FLUX-METER: implementation of a portable integrated instrumentation for the measurement of CO 2 and CH 4 diffuse flux from landfill soil cover.

The FLUX-METER: implementation of a portable integrated instrumentation for the measurement of CO 2 and CH 4 diffuse flux from landfill soil cover. : implementation of a portable integrated instrumentation for the measurement of CO 2 and CH 4 diffuse flux from landfill soil cover. I. Minardi*, E. Giovenali*, L. Coppo*, G. Virgili*, D. Continanza*,

More information

O3 3E 1 F Gas Sensor Module

O3 3E 1 F Gas Sensor Module Product Information Pack O3 3E 1 F Gas Sensor Module (Ozone) CONTENTS Product Data Sheet Product Specification 2 Poisoning and Cross Sensitivities 3 Operating Instructions Introduction 4 Electrostatic

More information

OXY Integral. INTERCON ENTERPRISES INC Tel: Fax: Internet:

OXY Integral. INTERCON ENTERPRISES INC Tel: Fax: Internet: OXY Integral INTERCON ENTERPRISES INC Tel: 800 665 6655 Fax: 604 946 5340 E-Mail: sales@intercononline.com Internet: www.intercononline.com Manual Integral 2006 1 INDEX 2-3 PREFACE 4 INTRODUCTION 5 Principle

More information

Review of oxygen deficiency requirements for graham s ratio

Review of oxygen deficiency requirements for graham s ratio University of Wollongong Research Online Coal Operators' Conference Faculty of Engineering and Information Sciences 2017 Review of oxygen deficiency requirements for graham s ratio Sean Muller Simtars,

More information

Discovery HP-TGA 75/750. Site Preparation Guide

Discovery HP-TGA 75/750. Site Preparation Guide Discovery HP-TGA 75/750 Site Preparation Guide Revision A Issued August 2018 Table of Contents Table of Contents... 2 Ideal Setup... 3 System Components... 4 Instrument Measurements... 5 Utility Requirements...

More information

Fig. 2. M.I. Yaroslavtsev, 2002

Fig. 2. M.I. Yaroslavtsev, 2002 SPECIAL FEATURES OF USING N O FOR HEATING OF THE TEST GAS IN A HOT-SHOT WIND TUNNEL M.I. Yaroslavtsev Institute of Theoretical and Applied Mechanics SB RAS, 630090 Novosibirsk Russia 1. The study of heat

More information

Certification of AMS acc. EN 15267, Part 3 - Overview and First Experience -

Certification of AMS acc. EN 15267, Part 3 - Overview and First Experience - Certification of AMS acc. EN 15267, Part 3 - Overview and First Experience - Dr. Wolfgang Jockel, Martin Schneider, TÜV Rheinland Group, D-51105 Cologne / Germany 1. Introduction A new basis for the certification

More information

E. Agu, M. Kasperski Ruhr-University Bochum Department of Civil and Environmental Engineering Sciences

E. Agu, M. Kasperski Ruhr-University Bochum Department of Civil and Environmental Engineering Sciences EACWE 5 Florence, Italy 19 th 23 rd July 29 Flying Sphere image Museo Ideale L. Da Vinci Chasing gust fronts - wind measurements at the airport Munich, Germany E. Agu, M. Kasperski Ruhr-University Bochum

More information

Manual of SF6 Comprehensive Tester

Manual of SF6 Comprehensive Tester Manual of SF6 Comprehensive Tester Important Description All the staff taking in charge of the usage or maintenance of this product should carefully read this manual. The same as any other complicated

More information

Using Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems. J.C.M. VAN ROSSUM * Prysmian Group NL The Netherlands

Using Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems. J.C.M. VAN ROSSUM * Prysmian Group NL The Netherlands 21, rue d Artois, F-75008 PARIS CIGRE US National Committee 2012 Grid of the Future Symposium http : //www.cigre.org Using Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems

More information

Analysis of Pressure Rise During Internal Arc Faults in Switchgear

Analysis of Pressure Rise During Internal Arc Faults in Switchgear Analysis of Pressure Rise During Internal Arc Faults in Switchgear ASANUMA, Gaku ONCHI, Toshiyuki TOYAMA, Kentaro ABSTRACT Switchgear include devices that play an important role in operations such as electric

More information

Advanced Test Equipment Rentals ATEC (2832) OMS 600

Advanced Test Equipment Rentals ATEC (2832) OMS 600 Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) OMS 600 Continuous partial discharge monitoring system for power generators and electrical motors Condition monitoring

More information

Flow in a shock tube

Flow in a shock tube Flow in a shock tube April 30, 05 Summary In the lab the shock Mach number as well as the Mach number downstream the moving shock are determined for different pressure ratios between the high and low pressure

More information

Manual. Online Degasser DDG-75. Manual Degasser DDG-75 April DURATEC Analysentechnik GmbH Rheinauer Strasse 4 DE Hockenheim Germany

Manual. Online Degasser DDG-75. Manual Degasser DDG-75 April DURATEC Analysentechnik GmbH Rheinauer Strasse 4 DE Hockenheim Germany Manual Degasser DDG-75 April 2007 1 Manual Online Degasser DDG-75 DURATEC Analysentechnik GmbH Rheinauer Strasse 4 DE-68766 Hockenheim Germany Tel. +49-6205-9450-0 Fax. +49-6205-9450-33 email info@duratec.com

More information

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the 1151 METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS 1.0 Scope and Application. 1.1 Analytes. Analyte Volatile Organic Compounds (VOC) CAS No. No CAS number assigned 1.2 Scope. This method

More information

For many applications, there is no technical reason anymore to keep the oil volumes of a transformer with vacuum type OLTC separated

For many applications, there is no technical reason anymore to keep the oil volumes of a transformer with vacuum type OLTC separated COLUMN For many applications, there is no technical reason anymore to keep the oil volumes of a transformer with vacuum type OLTC separated 20 TRANSFORMERS MAGAZINE Volume 4, Issue 2 Rainer FROTSCHER Common

More information

Introductory Lab: Vacuum Methods

Introductory Lab: Vacuum Methods Introductory Lab: Vacuum Methods Experiments in Modern Physics (P451) In this lab you will become familiar with the various components of the lab vacuum system. There are many books on this topic one of

More information

29th Monitoring Research Review: Ground-Based Nuclear Explosion Monitoring Technologies

29th Monitoring Research Review: Ground-Based Nuclear Explosion Monitoring Technologies IMPROVED CALIBRATION AND OPERATION OF A STABLE-GAS QUANTIFICATION MANIFOLD AS PART OF A RADIOXENON COLLECTION SYSTEM ABSTRACT Richard M. Williams, James C. Hayes, and Randy R. Kirkham Pacific Northwest

More information

Comparative temperature measurements in an experimental borehole heat exchanger. Vincent Badoux 1, Rita Kobler 2

Comparative temperature measurements in an experimental borehole heat exchanger. Vincent Badoux 1, Rita Kobler 2 European Geothermal Congress 2016 Strasbourg, France, 19-24 Sept 2016 Comparative temperature measurements in an experimental borehole heat exchanger Vincent Badoux 1, Rita Kobler 2 1 GEOTEST AG, Bernstrasse

More information

Visual Observation of Nucleate Boiling and Sliding Phenomena of Boiling Bubbles on a Horizontal Tube Heater

Visual Observation of Nucleate Boiling and Sliding Phenomena of Boiling Bubbles on a Horizontal Tube Heater Proceedings of the 2 nd World Congress on Mechanical, Chemical, and Material Engineering (MCM'16) Budapest, Hungary August 22 23, 216 Paper No. HTFF 146 DOI:.11159/htff16.146 Visual Observation of Nucleate

More information

CTB3365x Introduction to Water Treatment

CTB3365x Introduction to Water Treatment CTB3365x Introduction to Water Treatment D4b Aeration Doris van Halem Did you know that there are not just gasses in your glass of sparkling coke, but also in the tap water you drink? Welcome to the water

More information

Fail Operational Controls for an Independent Metering Valve

Fail Operational Controls for an Independent Metering Valve Group 14 - System Intergration and Safety Paper 14-3 465 Fail Operational Controls for an Independent Metering Valve Michael Rannow Eaton Corporation, 7945 Wallace Rd., Eden Prairie, MN, 55347, email:

More information

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12 LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/ This experiment will introduce you to the kinetic properties of low-pressure gases. You will make observations on the rates with which selected

More information

Hot extractive multi-channel gas analyser for continuous process and emissions monitoring.

Hot extractive multi-channel gas analyser for continuous process and emissions monitoring. Product Data Sheet CODEL Continuous Emission Monitoring GCEM4100 Extractive Gas Analyser CO, CO2, NO, NO2, SO2, HCL, CH4 & H2O Hot extractive multi-channel gas analyser for continuous process and emissions

More information

deltaflowc deltaflowc Venturi or Probe

deltaflowc deltaflowc Venturi or Probe deltaflowc Mass Flowmeter for Gases - Multivariable with ultra fast dp, p and T-sensors - Compact, accurate and user-friendly - Ideal for OEMs deltaflowc Venturi or Probe Precise mass flow metering deltaflowc

More information

Hot extractive multi-channel gas analyser for continuous process and emissions monitoring.

Hot extractive multi-channel gas analyser for continuous process and emissions monitoring. Product Data Sheet CODEL Continuous Emission Monitoring GCEM4100 Extractive Gas Analyser CO, CO2, NO, NO2, SO2, HCL, CH4 & H2O Hot extractive multi-channel gas analyser for continuous process and emissions

More information

Monitoring transformers with infrared cameras

Monitoring transformers with infrared cameras APPLICATION NOTE Monitoring transformers with infrared cameras Most transformers are cooled by either oil or air while operating at temperatures much higher than ambient. In fact, operating temperatures

More information

Laboratory Hardware. Custom Gas Chromatography Solutions WASSON - ECE INSTRUMENTATION. Engineered Solutions, Guaranteed Results.

Laboratory Hardware. Custom Gas Chromatography Solutions WASSON - ECE INSTRUMENTATION. Engineered Solutions, Guaranteed Results. Laboratory Hardware Custom Gas Chromatography Solutions Engineered Solutions, Guaranteed Results. WASSON - ECE INSTRUMENTATION Laboratory Hardware Wasson-ECE Instrumentation offers hardware-only solutions

More information

Applications of a Magnetic Sector Process Mass Spectrometer to the Analysis of Variable Vacuum Samples

Applications of a Magnetic Sector Process Mass Spectrometer to the Analysis of Variable Vacuum Samples Applications of a Magnetic Sector Process Mass Spectrometer to the Analysis of Variable Vacuum Samples Outline of Presentation Introduction Process Gas Analysis Magnetic Sector Mass Spectrometer Standard

More information

Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks

Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks Proceedings of the 4th International Conference on Systems and Control, Sousse, Tunisia, April 28-30, 2015 TuCA.2 Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks

More information

DISSOLVED GAS ANALYSIS OF POWER TRANSFORMERS

DISSOLVED GAS ANALYSIS OF POWER TRANSFORMERS International Journal of Electrical and Electronics Engineering Research (IJEEER) ISSN(P): 2250-155X; ISSN(O): 2278-943X Vol. 3, Issue 5, Dec 2013, 1-10 TJPRC Pvt. Ltd. DISSOLVED GAS ANALYSIS OF POWER

More information

This test shall be carried out on all vehicles equipped with open type traction batteries.

This test shall be carried out on all vehicles equipped with open type traction batteries. 5.4. Determination of hydrogen emissions page 1 RESS-6-15 5.4.1. This test shall be carried out on all vehicles equipped with open type traction batteries. 5.4.2. The test shall be conducted following

More information

Gas Sampling Fitting with MK2.1 and L-Probe

Gas Sampling Fitting with MK2.1 and L-Probe measuring controlling automation measuring controlling automation measuring controlling automation Page i von 8 Operation Manual Gas Sampling Fitting with MK2.1 and L-Probe Page ii von 8 Manufacturer MESA

More information

Applied Technology and Best Practices in CEE. Conference

Applied Technology and Best Practices in CEE. Conference Geoinform Applied Technology and Best Practices in CEE Conference THE DEVELOPMENT OF MUD GAS LOGGING SYSTEMS AND THEIR ROLE IN HYDROCARBON EXPLORATION Sándor Pugner GEOINFORM Ltd. Budapest, 17 November

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 6974-4 First edition 2000-04-01 Natural gas Determination of composition with defined uncertainty by gas chromatography Part 4: Determination of nitrogen, carbon dioxide and

More information

Your local gas generation partner. Precision series Modular gas generation solution for GC.

Your local gas generation partner. Precision series Modular gas generation solution for GC. Your local gas generation partner Precision series Modular gas generation solution for GC www.peakscientific.com Perform with Precision Specifically designed and engineered for GC laboratory applications,

More information

IRwin Methane Leak Detector. Innovation makes the difference

IRwin Methane Leak Detector. Innovation makes the difference IRwin Methane Leak Detector Innovation makes the difference Innovative methane detector system for easy survey of gas pipelines IRwin is a portable methane leak detector for fast and easy survey of gas

More information

Transient Analyses In Relief Systems

Transient Analyses In Relief Systems Transient Analyses In Relief Systems Dirk Deboer, Brady Haneman and Quoc-Khanh Tran Kaiser Engineers Pty Ltd ABSTRACT Analyses of pressure relief systems are concerned with transient process disturbances

More information

H 2. Sensor Series Take no risk! Install a Hydrogen Sensor in your Gaschromatograph

H 2. Sensor Series Take no risk! Install a Hydrogen Sensor in your Gaschromatograph Sensor Series 9000 Take no risk! Install a Hydrogen Sensor in your Gaschromatograph Carrier Gases for GC Probably more than 90% of the present GC instruments run with helium as carrier gas. Some people

More information

COAL MINES TECHNICAL SERVICES, GAS DETECTION RELATED SERVICES FOR MINES RESCUE

COAL MINES TECHNICAL SERVICES, GAS DETECTION RELATED SERVICES FOR MINES RESCUE COAL MINES TECHNICAL SERVICES, GAS DETECTION RELATED SERVICES FOR MINES RESCUE Peter Mason Manager, Coal Mines Technical Services, a division of Mines Rescue Pty Ltd, Australia ABSTRACT The NSW Mines Rescue

More information

Schedule of Requirements THERMODYNAMICS LABORATORY- CHEMICAL ENGINEERING DEPARTMENT

Schedule of Requirements THERMODYNAMICS LABORATORY- CHEMICAL ENGINEERING DEPARTMENT S. No 1 Description Calorimeter The Unit should be designed for the accurate determination of the calorific value of liquid and solid hydrocarbons and other fuels. Specifications: A temperature-controlled

More information

APPLICATION NOTE. Fast Analysis of Coal Mine Gas Using the INFICON 3000 Micro GC ABSTRACT

APPLICATION NOTE. Fast Analysis of Coal Mine Gas Using the INFICON 3000 Micro GC ABSTRACT APPLICATION NOTE Fast Analysis of Coal Mine Gas Using the INFICON 3000 Micro GC ABSTRACT The INFICON 3000 Micro GC provides two fast and accurate solutions for the analysis of coal mine gas components.

More information

Laboratory Hardware. Custom Gas Chromatography Solutions WASSON - ECE INSTRUMENTATION. Custom solutions for your analytical needs.

Laboratory Hardware. Custom Gas Chromatography Solutions WASSON - ECE INSTRUMENTATION. Custom solutions for your analytical needs. Laboratory Hardware Custom Gas Chromatography Solutions Custom solutions for your analytical needs. Laboratory Hardware Wasson-ECE Instrumentation offers hardware-only solutions for advanced chromatography

More information

MEGAS 2.0. Gas analysis with direct C-Level Calculation and Bus-Connection. Data sheet

MEGAS 2.0. Gas analysis with direct C-Level Calculation and Bus-Connection. Data sheet Data sheet MEGAS 2.0 Gas analysis with direct C-Level Calculation and Bus-Connection Mesa Industrie-Elektronik GmbH Neckarstraße 19, D-45768 Marl info@mesa-gmbh.de +49 (0) 2365-97 45 1-0 +49 (0) 2365-97

More information

PIG MOTION AND DYNAMICS IN COMPLEX GAS NETWORKS. Dr Aidan O Donoghue, Pipeline Research Limited, Glasgow

PIG MOTION AND DYNAMICS IN COMPLEX GAS NETWORKS. Dr Aidan O Donoghue, Pipeline Research Limited, Glasgow PIG MOTION AND DYNAMICS IN COMPLEX GAS NETWORKS Dr Aidan O Donoghue, Pipeline Research Limited, Glasgow A model to examine pigging and inspection of gas networks with multiple pipelines, connections and

More information

MEASURING WATER CONTENT IN COMPRESSED BREATHING AIR IN COMPLIANCE WITH EN 12021:2014 ULTRA-PRECISE AND ULTRA-RELIABLE WITH POLYMER TECHNOLOGY

MEASURING WATER CONTENT IN COMPRESSED BREATHING AIR IN COMPLIANCE WITH EN 12021:2014 ULTRA-PRECISE AND ULTRA-RELIABLE WITH POLYMER TECHNOLOGY MEASURING WATER CONTENT IN COMPRESSED BREATHING AIR IN COMPLIANCE WITH EN 12021:2014 ULTRA-PRECISE AND ULTRA-RELIABLE WITH POLYMER TECHNOLOGY SPORTS & SAFETY BAUER KOMPRESSOREN WHY PRECISE MEASUREMENT

More information

Online Publication Date: 19 January, 2012 Publisher: Asian Economic and Social Society

Online Publication Date: 19 January, 2012 Publisher: Asian Economic and Social Society Online Publication Date: 19 January, 2012 Publisher: Asian Economic and Social Society Prediction of Faults using Hydrocarbon Gases Data of Mineral Oil Immersed Power Transformers using Computer Intelligence

More information

Measurement Technology

Measurement Technology In the field of compressed air, measuring pressure provides the data basis for rating the correct pressure head of pressure differences in the distribution system as well as for controlling and regulating

More information

Vortex flowmeters. Product family introduction Principle of operation Product review Applications Key product features

Vortex flowmeters. Product family introduction Principle of operation Product review Applications Key product features Vortex flowmeters introduction Product review s Key product features This document should not be duplicated, used, distributed, or disclosed for any purpose unless authorized by Siemens. Page 1 Vortex

More information