Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations

Size: px
Start display at page:

Download "Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations"

Transcription

1 Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations Grzegorz Kubicki, Ph.D. Department of Environmental Engineering, Warsaw University of Technology Izabela Tekielak Skałka, M.Sc. Eng. Research and CFD Simulations Department, SMAY LLC KEYWORDS Pressure differential systems, evacuation, high-rise buildings, fire safety INTRODUCTION The interior staircases are the only available escape routes for all occupants of the high-rise buildings in the case of fire. Protection of this area carried out by means of pressure differential systems must be as efficient as possible. THE ORIGIN OF THE RESEARCH PROGRAM The origin of the research program were numerous information and internal measurements of pressure distribution in staircases of high-rise buildings in different countries of European Union. These measurements indicated the unsuccessful operation of various types of smoke prevention systems. The obtained results were fully confirmed during the later tests carried out also with the participation of authors. As already observed, the stack effect may occur in the internal staircases before the start of fire ventilation system. Level of pressure distribution is strongly correlated with the difference between inside and outside temperature. The pressure difference is particularly evident in winter when the outdoor temperature falls well below 0 C, but also occurs with varying intensity in other conditions of temperature. The observations also showed that air supply raises the initial difference of pressure to a higher pressure level. Pressure relief damper allows to reduce the problem of distribution of pressure, but does not solve it. GOAL AND STAGES OF RESEARCH The observations were the reason to start an program of research. The goal of the research was to design the pressure differential system. This system was intended for buildings higher than 50 m. The new system was intended to operate with greater efficiency than the systems consisting of a multi-point air injection system and the pressure relief damper. It should also provide effective solution to counteract the stack effects within a building in the temperate climatic zone (with significant fluctuations of the outside temperature during the year).

2 Tests were carried out in the following stages: Stage I: Research on the test rig in The test rig was built in the staircase of reinforced-concrete frame building in Krakow (highest 92 m). Stage II: Research based on numerical analysis (CFD). Analysis were carried out in parallel with the Stage I. Stage III: Research carried out in the real building in the years Studies have been conducted to verify the results of research and to verify the effectiveness of the technical solutions developed during the Stage I. THE TEST RIG The test rig was built to the long-term observation of physical phenomena. Research required continuous measurement of different systems. For this reason, the building operated every day were excluded as a location for research. Studies conducted in unfinished building at Lubomirska street in Cracow. One staircase was in the building of reinforced concrete. The staircase included 23-floor with a total height of 92 m. Two independent systems has been investigated on the test rig: 1. pressure differential system constructed in accordance with the recommendations of the European standard [5] (vertical duct, supply air every 3 storeys) 2. system consisting of two reversible fans located at the top and bottom of the building. Figure 1. Real scale test stand 1 - control panel description multipoint air-supply system

3 Figure 2. Real scale test stand 2 - control panel description forced airflow system The test rig was equipped with a comprehensive system of monitoring physical parameters and registration data (Figure 1., Figure 2., Figure 3). The remote control panel allowed for supply of the air with varying intensity and various ways (concentrated air supply, multi-point air injection). Figure 3. Schematic diagram of measurement and data acquisition system

4 The staircase was equipped with the necessary elements of the carpentry and joinery and adjusted to the level of the tightness corresponding to tight class in accordance to Annex A of European standard [5]. RESEARCH During two years research program performed hundreds of tests to check the operation of the system of pressurization in various configurations air supply and air flow. Research carried out at different periods of the year at different air temperatures. The research was conducted in three steps. Step I: Goals of the first step was defined as follows: Define the factors influencing the initial pressure distribution in an unheated staircase, and the correlation between weather conditions and internal temperature. Long-term observation of pressure in staircase confirmed that the phenomenon of the stack effect is closely related to temperature conditions. Significant changes in the vertical distribution of pressure appear in both in the daily cycle and or during a temporary worsening of the weather. Figure 4 show the change in the pressure caused by change of daily temperature observed on the test stand. Figure 5 show the change in the pressure caused by rapid decrease in air temperature during the storm. Figure 4. Measurement data analysis temperature difference -> stack effect

5 Figure 5. Measurement data analysis temperature difference -> stack effect The measurements confirmed the influence of temperature on the pressure distribution in the staircase. The size of the pressure difference between the highest and lowest floors is proportional to the difference of external and internal air temperature. However, also in the space of a building is some of pressure, so the value of stack effect measured between usable space and the staircase is less than would appear from a typical formula describing the stack effect. Distribution of pressure in the building shown in Figure 6. Figure 6. Distribution of pressure in the building in winter. Above relationship was taken into account in the equation describing the stack effect by adding a new coefficient c. Additional coefficient allows to determine the pressure difference between the staircase and the usable area.

6 ϵ Where: pp ssssssssss_eeeeeeeeeeee = (ρρ ee ρρ ii ) gg h cc [PPPP] ρρ ee - the density of the outside air [kg/m 3 ], ρρ ii - the density of the indoor air [kg/m 3 ], gg - gravitational acceleration [m/s 2 ], h - height of staircase [m], cc - additional coefficient (cc0t 0,5 0,9) [-]. Coefficient depends on the ratio tightness of the staircase to tightness of the building - building on the tight staircase compared to full of holes elevation will have a high rate of c-factor. Coefficient depends also on the height of the building. The value of c-factor is higher for high-rise buildings and lower for low-rise buildings. Step II: Goals of the second step was defined as follows: Determination of the practical effectiveness of various forms of air supply and active control of supply air. During the tests were examined the effectiveness of different methods of pressurization: concentrated on the lowest and highest levels (single point air supply, double point air supply) and air flow distributed over the entire height of the staircase. In all cases achieved a similar result: the pressure increases but line of pressure kept their initial deviation. This means that the air supply into the staircase does not change the initial pressure difference between the lower and the high part of this space. Figure 7. Pressure distribution in the staircase for different method of supply air. Step III

7 Goals of the third step was defined as follows: Study of the effectiveness of the system utilizing the airflow within the staircase to forming the pressure distribution. The system consists of two reversible fans located on the lowest and the highest floor of the staircase. One of the fan supply air into the staircase in the direction of the natural flow of air. The second fan operates in the extract function with less air flow. The air flow direction is calculated based on the initial pressure distribution, determined by measuring the inside and outside temperature. The fans are equipped with frequency inverters. Suitably selected airflow allows to stabilize the pressure on the entire height of the staircase. An integral part of the system are sensors of pressure, which signal is the basis for determining the quantity of air supply and exhaust air. Change the scenario (opening doors) changes the amount of supply air in a very short time. Supply of the air is increases. The airflow on the exhaust fan is restricted. The system returns to the previously air flows after closing the door. The solution provides the effectiveness of the system, reducing the time necessary to stabilize the pressure and automatically adapts to the changes in the work environment such as e.g. change in the level of tightness of the staircase. Figure 8. Pressure distribution stabilization inside staircase during summer (a) and winter (b) periods. Verification of assumptions and full confirmation of the effectiveness of the system was carried out on the test rig. Flow system can be used for forming any pressure in the staircase. For example, below were shown the results of measurements for a test create a pressure difference between the extreme floors of the building. The purpose of test was to obtain the pressure difference between the highest and the lowest floors equal to - 60 Pa. The initial distribution of the pressure was 10 Pa. During the test were set appropriate settings of the pressure controllers (100 Pa at the 1 floor and 40 Pa at the 23 floor). The system obtained set values without any problem. The results demonstrated high efficiency flow system to control the pressure in the staircase.

8 Figure 9. Example of possibility of pressure changes in the staircase using system based on flow. The test showed that it is possible achieve the desired pressure by the generation an air flow within the staircase. The analysis of the test results allowed to develop an advanced system using air flow resistance through the staircase. The method allows for the active prevention of the stack effect. USE OF CFD TOOLS TO VERIFY THE TEST RESULTS Research were supplemented by a program of computer simulations performed using the ANSYS FLUENT. Simulations were conducted in parallel with the measurements on the test rig, so that it was possible to validate the developed numerical model. Simulation results were compared to real all time. In order to carry CFD simulations developed a three-dimensional computational model. Numerical model takes into consideration all important architectural details as well as air supply, evacuation doors dimensions and exact location of air supply and air exhaust points. Air leakages were simulated as slots with located at the bottom of the door frame. In the model applied tetrahedral computational mesh composed of elements. the maximum dimension of the mesh at the boundaries is limited to 0.20 m. the size of model elements have been reduced in places characterized by small dimensions. In the model were used the following settings: CFD simulations were carried out in Double Precision Solver, parallel computing; two-equation k-epsilon turbulence model (RNG with full buoyancy effect); force of gravity has been taken into consideration; heat transfer inside the stairs was taken into consideration; Convergence criterions were taken into consideration; CFD simulations were conducted for the theoretical winter conditions (outside temperature -20 C, internal temperature +20 C). Criteria for the correct functioning of the pressure differential system was determined based on the European standard EN : minimum pressure was 50 Pa +/- 10% (45 Pa), maximum pressure was 60 Pa.

9 The examples of results of the simulation are shown below. Figure 10. Pressure distribution in the staircase for different pressure differentiation systems. In all analyzed cases the system based on flow have the highest efficiency to stabilize the pressure in the staircase. Compare the effectiveness of the presented solution with other types of installations a clear indication of the objective of the research project - creating a system based on flow capable of producing of a stable pressure even in the stack effect. VERIFICATION OF THE RESULTS OF RESEARCH IN PRACTICE The results of experiments and numerical analyzes have been confirmed many times in tests and measurements on real objects. In the years studies carried out in several buildings with a height exceeding 50 m in Poland. These buildings were equipped with different solutions of pressure differential systems. Below presents selected results of the two examples. Sky Tower in Wroclaw (the tallest building in Poland equipped with a system that uses air flow to stabilize the pressure) At the time of construction it was the tallest building in Poland, with a height exceeding 200 m. Inside the building there were two staircases. Stairways were equipped with a system composed of two main reversible fans located at the extreme floors of staircase and three additional fans. The distance between the points of air supply was between 10 and 23 storeys (37 and 87 m). Measurements during the winter (outside temperature +3 C, internal temperature +18 C). The examples of results of the measurements are shown below.

10 storey p staircase - corridor (volume flow) +59 Pa (out m 3 /h) (supply m 3 /h) +48 Pa (supply m 3 /h) Pa (supply m 3 /h) the main fan additional fan Table 1. The results of the measurements of pressure in the staircase Pa (supply m 3 /h) Measurements carried out in the building confirmed the ability of the system to stabilize the pressure of the flow in a stairwell, regardless of external conditions. Student House Riviera in Warsaw The staircase consisted of 21 floors above ground and one underground, with a total height of 66 m. Installation went was submitted with the fan connected to a vertical duct. The points of air supply arranged every 3 storeys. In the wall under the ceiling of the staircase was placed pressure relief damper, which, however, was closed during testing. Tests carried out during the winter (outside temperature ranged from -14 to -20 C). For such conditions in the staircase initial dissection of pressure was characterized by the value of 80-90Pa. The effect persisted after the start of the pressure differential system (Figure 11. Test 1 and Test 2). The normative value of the pressure (50 Pa) obtained only at the height of the middle of the staircase. Pressure in the bottom of the staircase achieved value -10 Pa and on the top floor achieved value + 60Pa.

11 Figure 11. The test results of pressure and temperature changes in the stairwell SUMMARY The conducted measurements show that the effectiveness of the pressure differential system is heavily dependent on external conditions, which is especially visible in the high-rise buildings. Systems composed of multipoint air-supply and pressure relief damper does not guarantee the correct distribution of pressure. The high-rise buildings require an individual approach. Studies have shown that an alternative way to protect vertical evacuation routes is a forced airflow system, which uses flow resistance inside the staircase to form the suitable pressure difference..

12 LITERATURE: 1. Tamura G.T., Assessment of stair pressurization systems for smoke control, ASHRE Transactions Vol. 98 part 1, 1992, 2. Tamura G.T. and Shaw C.Y., Experimental studies of mechanical venting for smoke control in tall office buildings, ASHRE Transactions Vol. 84 part 1, 1978, 3. Konrath B. Pressure differentia systems - The German experience with the standard EN considerations about the influence of the static pressure differential in the high-rise buildings, Horst A. Ermer Smoke Control by Pressurization in High-Rise Buildings - Empirical findings EuroFire EN Smoke and heat control systems - Part 6: Specification for pressure differential systems Kits, pren Smoke and heat control systems Part 13: Pressure differential systems (PDS) design and calculation methods, acceptance testing, maintenance and routine testing of installation

Experimental Fire Tower Studies on Mechanical Pressurization to Control Smoke Movement Caused by Fire Pressures

Experimental Fire Tower Studies on Mechanical Pressurization to Control Smoke Movement Caused by Fire Pressures Experimental Fire Tower Studies on Mechanical Pressurization to Control Smoke Movement Caused by Fire Pressures G. T. TAMURA Institute for Research in Construction National Research Council of Canada Ottawa,

More information

Wind pressure coefficient determination for greenhouses built in a reclaimed land using CFD technique

Wind pressure coefficient determination for greenhouses built in a reclaimed land using CFD technique Ref: 1064 Wind pressure coefficient determination for greenhouses built in a reclaimed land using CFD technique Hyun-seob Hwang and In-bok Lee, Department of Rural Systems Engineering, Research Institute

More information

AIRFLOW AND TEMPERATURE FIELD CALCULATIONS FOR WINTER SPORTS FACILITIES

AIRFLOW AND TEMPERATURE FIELD CALCULATIONS FOR WINTER SPORTS FACILITIES AIRFLOW AND TEMPERATURE FIELD CALCULATIONS FOR WINTER SPORTS FACILITIES Andrea Frisque* Stantec Consulting, Vancouver BC V6B6A3, Canada Rowan, Williams, Davies & Irwin (RWDI), Vancouver, BC, V5Z 1K5, Canada**

More information

Pressure Differential Systems

Pressure Differential Systems Pressure Differential Systems German point of view to EN 12101-6 Considaration of the influence of aerostatic pressure differential in high rise buildings Dipl.-Ing. B. Konrath I.F.I. Institut for Industriel

More information

SUMMARY OF THE EXPERIMENTAL STUDIES OF COLD HELIUM PROPAGATION ALONG A SCALE MODEL OF THE LHC TUNNEL

SUMMARY OF THE EXPERIMENTAL STUDIES OF COLD HELIUM PROPAGATION ALONG A SCALE MODEL OF THE LHC TUNNEL EUROPEAN ORGANIZATION FOR NUCLEAR RESEARCH European Laboratory for Particle Physics Large Hadron Collider Project LHC Project Report 684 SUMMARY OF THE EXPERIMENTAL STUDIES OF COLD HELIUM PROPAGATION ALONG

More information

Outside Air Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program

Outside Air Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program 1 Outside Air Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program Jim Meacham, CTG Energetics Agenda 2 In Situ Testing Results Reduced Ventilation after

More information

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT - 277 - NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT Iseler J., Heiser W. EAS GmbH, Karlsruhe, Germany ABSTRACT A numerical study of the flow behaviour

More information

INTERACTION BETWEEN WIND-DRIVEN AND BUOYANCY-DRIVEN NATURAL VENTILATION Bo Wang, Foster and Partners, London, UK

INTERACTION BETWEEN WIND-DRIVEN AND BUOYANCY-DRIVEN NATURAL VENTILATION Bo Wang, Foster and Partners, London, UK INTERACTION BETWEEN WIND-DRIVEN AND BUOYANCY-DRIVEN NATURAL VENTILATION Bo Wang, Foster and Partners, London, UK ABSTRACT Ventilation stacks are becoming increasingly common in the design of naturally

More information

CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS

CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS T. Gélain, C. Prévost Institut de Radioprotection et de Sûreté Nucléaire (IRSN), Saclay, France Abstract In order to better understand the risks due

More information

Guidance on room integrity testing and its interpretation

Guidance on room integrity testing and its interpretation Guidance Note Guidance on room integrity testing and its interpretation Guidance on room integrity testing and its interpretation 1. SCOPE... 6 2. INTRODUCTION AND BACKGROUND... 6 2.1. DEVELOPMENT OF INTEGRITY

More information

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE - 247 - AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE J D Castro a, C W Pope a and R D Matthews b a Mott MacDonald Ltd, St Anne House,

More information

Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios

Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios Yunlong (Jason) Liu, PhD, PE HNTB Corporation Sean Cassady, FPE HNTB Corporation Abstract Extraction

More information

LONGITUDINAL AIR VELOCITY CONTROL IN A ROAD TUNNEL DURING A FIRE EVENT

LONGITUDINAL AIR VELOCITY CONTROL IN A ROAD TUNNEL DURING A FIRE EVENT - 27 - LONGITUDINAL AIR VELOCITY CONTROL IN A ROAD TUNNEL DURING A FIRE EVENT R. Borchiellini, V. Ferro, V. Giaretto Energy Department Politecnico di Torino Italy ABSTRACT Ventilation equipment is used

More information

CFD Simulation and Experimental Validation of a Diaphragm Pressure Wave Generator

CFD Simulation and Experimental Validation of a Diaphragm Pressure Wave Generator CFD Simulation and Experimental Validation of a Diaphragm Pressure Wave Generator T. Huang 1, A. Caughley 2, R. Young 2 and V. Chamritski 1 1 HTS-110 Ltd Lower Hutt, New Zealand 2 Industrial Research Ltd

More information

Effect of airflow direction on human perception of draught

Effect of airflow direction on human perception of draught Effect of airflow direction on human perception of draught J. Toftum, G. Zhou, A. Melikov Laboratory of Indoor Environment and Energy Department of Energy Engineering Technical University of Denmark Abstract

More information

CHARACTERISTICS OF LEAK DETECTION BASED ON DIFERENTIAL PRESSURE MEASUREMENT

CHARACTERISTICS OF LEAK DETECTION BASED ON DIFERENTIAL PRESSURE MEASUREMENT CHARACTERISTICS OF LEAK DETECTION BASED ON DIFERENTIAL PRESSURE MEASUREMENT Harus L.G..*, Maolin CAI**, Kenji KAWASHIMA** and Toshiharu KAGAWA** * Graduate student of Mechano-Micro Engineering Dept., Tokyo

More information

International Journal of Technical Research and Applications e-issn: , Volume 4, Issue 3 (May-June, 2016), PP.

International Journal of Technical Research and Applications e-issn: ,  Volume 4, Issue 3 (May-June, 2016), PP. DESIGN AND ANALYSIS OF FEED CHECK VALVE AS CONTROL VALVE USING CFD SOFTWARE R.Nikhil M.Tech Student Industrial & Production Engineering National Institute of Engineering Mysuru, Karnataka, India -570008

More information

CROSS CONTAMINATION OF IN-SUITE MURB VENTILATION SYSTEMS

CROSS CONTAMINATION OF IN-SUITE MURB VENTILATION SYSTEMS CROSS CONTAMINATION OF IN-SUITE MURB VENTILATION SYSTEMS Presented By: Sandra Dedesko University of Toronto Contributing Authors: Caleb Parker Kim Pressnail Marianne Touchie Dave DeRose Multi-Unit Residential

More information

The Usage of Propeller Tunnels For Higher Efficiency and Lower Vibration. M. Burak Şamşul

The Usage of Propeller Tunnels For Higher Efficiency and Lower Vibration. M. Burak Şamşul The Usage of Propeller Tunnels For Higher Efficiency and Lower Vibration M. Burak Şamşul ITU AYOC 2014 - Milper Pervane Teknolojileri Company Profile MILPER is established in 2011 as a Research and Development

More information

FIRE MODELLING OF ENERGY-EFFICIENT APARTMENT BUILDINGS Consideration of air-tightness and mechanical ventilation

FIRE MODELLING OF ENERGY-EFFICIENT APARTMENT BUILDINGS Consideration of air-tightness and mechanical ventilation FIRE MODELLING OF ENERGY-EFFICIENT APARTMENT BUILDINGS Consideration of air-tightness and mechanical ventilation Simo Hostikka, Rahul Kallada Janardhan, Umar Riaz, and Topi Sikanen 1 Aalto University simo.hostikka@aalto.fi

More information

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage William M. Pitts, Jiann C. Yang, Kuldeep Prasad, and Marco Fernandez National Institute of Standards

More information

Smoke Control through Ventilation Systems on the Fire-Induced Conditions in a Stairwell

Smoke Control through Ventilation Systems on the Fire-Induced Conditions in a Stairwell International Journal of Information and Electronics Engineering, Vol. 6, No. 2, March 2016 Smoke Control through Ventilation Systems on the Fire-Induced Conditions in a Stairwell Aristides Lopes da Silva,

More information

Numerical and Experimental Investigation of the Possibility of Forming the Wake Flow of Large Ships by Using the Vortex Generators

Numerical and Experimental Investigation of the Possibility of Forming the Wake Flow of Large Ships by Using the Vortex Generators Second International Symposium on Marine Propulsors smp 11, Hamburg, Germany, June 2011 Numerical and Experimental Investigation of the Possibility of Forming the Wake Flow of Large Ships by Using the

More information

CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS

CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS - 56 - CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS Gloth O., Rudolf A. ILF Consulting Engineers Zürich, Switzerland ABSTRACT This article investigates the

More information

OPTIMIZING THE LENGTH OF AIR SUPPLY DUCT IN CROSS CONNECTIONS OF GOTTHARD BASE TUNNEL. Rehan Yousaf 1, Oliver Scherer 1

OPTIMIZING THE LENGTH OF AIR SUPPLY DUCT IN CROSS CONNECTIONS OF GOTTHARD BASE TUNNEL. Rehan Yousaf 1, Oliver Scherer 1 OPTIMIZING THE LENGTH OF AIR SUPPLY DUCT IN CROSS CONNECTIONS OF GOTTHARD BASE TUNNEL Rehan Yousaf 1, Oliver Scherer 1 1 Pöyry Infra Ltd, Zürich, Switzerland ABSTRACT Gotthard Base Tunnel with its 57 km

More information

REVIEW Effects of Side Vents and Span Numbers on Wind-Induced Natural Ventilation of a Gothic Multi-Span Greenhouse

REVIEW Effects of Side Vents and Span Numbers on Wind-Induced Natural Ventilation of a Gothic Multi-Span Greenhouse JARQ 38 (4), 7 33 (004) http://www.jircas.affrc.go.jp REVIEW Effects of Side Vents and Span Numbers on Wind-Induced Natural Ventilation of a Gothic Multi-Span Greenhouse Murat KACIRA 1,, Sadanori SASE

More information

AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR

AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR - 9 - AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR O Gorman S., Nuttall R., Purchase A. Parsons Brinckerhoff, Australia ABSTRACT Recent fire tests for tunnels

More information

I.CHEM.E. SYMPOSIUM SERIES NO. 97 BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES

I.CHEM.E. SYMPOSIUM SERIES NO. 97 BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES M. R. Marshall* and P. L. Stewart-Darling* A simple mathematical model for the buoyancy driven ventilation of an enclosed space, using a two-pipe

More information

CFD Analysis ofwind Turbine Airfoil at Various Angles of Attack

CFD Analysis ofwind Turbine Airfoil at Various Angles of Attack IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 13, Issue 4 Ver. II (Jul. - Aug. 2016), PP 18-24 www.iosrjournals.org CFD Analysis ofwind Turbine

More information

Pressure coefficient on flat roofs of rectangular buildings

Pressure coefficient on flat roofs of rectangular buildings Pressure coefficient on flat roofs of rectangular buildings T. Lipecki 1 1 Faculty of Civil Engineering and Architecture, Lublin University of Technology, Poland. t.lipecki@pollub.pl Abstract The paper

More information

Air Leakage Detailing & Awareness Services

Air Leakage Detailing & Awareness Services Tel: 08456 808048 Mob: 07866 948200 www.aldas.co.uk Info@aldas.co.uk Report on the Repeat Air Permeability Testing of the Passivhaus Refurbishment of: 57 Portfield Street, Hereford 16 th July 2010 Address:

More information

HYDROGEN RISK ANALYSIS FOR A GENERIC NUCLEAR CONTAINMENT VENTILATION SYSTEM

HYDROGEN RISK ANALYSIS FOR A GENERIC NUCLEAR CONTAINMENT VENTILATION SYSTEM HYDROGEN RISK ANALYSIS FOR A GENERIC NUCLEAR CONTAINMENT VENTILATION SYSTEM u, Z. 1 and Jordan, T. 2 Karlsruhe Institute of Technology, P.O. Box 3640, 76021 Karlsruhe, Germany 1 zhanjie.xu@kit.edu, 2 thomas.jordan@kit.edu

More information

SAFE ESCAPE FROM LONGWALL DEVELOPMENT SECTION IN CASE OF A BELT FIRE

SAFE ESCAPE FROM LONGWALL DEVELOPMENT SECTION IN CASE OF A BELT FIRE Abstract When a fire occurs outby a working area, the immediate safe evacuation of miners from the mine should always be the first action during the rescue operation. However, many times, the dedicated

More information

METRO System Design. Witt&Sohn AG Aug-11

METRO System Design. Witt&Sohn AG Aug-11 METRO System Design Content Purpose Comparison Metro Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary Purpose Presentation: Degree of Complexity of Metro Systems No

More information

Keywords: contra-rotating fan, air pressure, deformation of blades.

Keywords: contra-rotating fan, air pressure, deformation of blades. 2nd International Conference on Machinery, Materials Engineering, Chemical Engineering and Biotechnology (MMECEB 2015) Study on Deformation of the Two Rotors of Contra-Rotating Fan under Variable Speeds

More information

Research on natural gas pipeline leakage and ventilation scheme in tunnel

Research on natural gas pipeline leakage and ventilation scheme in tunnel Research on natural gas pipeline leakage and ventilation scheme in tunnel Hongfang Lu 1,, Kun Huang 1, Lingdi Fu 1, Zhihao Zhang 1, Shijuan Wu 3, You Lyu 4 1 School of Petroleum Engineering, Southwest

More information

Table of contents. I Drawings 33. A1 Design criteria 1 A1.1 Local thermal discomfort indices... 1

Table of contents. I Drawings 33. A1 Design criteria 1 A1.1 Local thermal discomfort indices... 1 Table of contents A1 Design criteria 1 A1.1 Local thermal discomfort indices........................... 1 A2 Experiment set-up 3 A2.1 Equipment....................................... 3 A2.2 Test cases.......................................

More information

Smoke and heat Ventilator Testing

Smoke and heat Ventilator Testing Instituut vir Termodinamika en Meganika Institute for Thermodynamics and Mechanics Smoke and heat Ventilator Testing by CJ Zietsman and GR Smith November 2005 Departement Meganiese Ingenieurswese Privaat

More information

OPTIMIZATION OF SINGLE STAGE AXIAL FLOW COMPRESSOR FOR DIFFERENT ROTATIONAL SPEED USING CFD

OPTIMIZATION OF SINGLE STAGE AXIAL FLOW COMPRESSOR FOR DIFFERENT ROTATIONAL SPEED USING CFD http:// OPTIMIZATION OF SINGLE STAGE AXIAL FLOW COMPRESSOR FOR DIFFERENT ROTATIONAL SPEED USING CFD Anand Kumar S malipatil 1, Anantharaja M.H 2 1,2 Department of Thermal Power Engineering, VTU-RO Gulbarga,

More information

Fire and Safety for Offshore drilling and production Ajey Walavalkar ANSYS Inc.

Fire and Safety for Offshore drilling and production Ajey Walavalkar ANSYS Inc. Fire and Safety for Offshore drilling and production Ajey Walavalkar ANSYS Inc. 1 ANSYS, Inc. September 12, Fire and safety related applications Gas Dispersion and Ventilation Formation of combustible

More information

Vibration Analysis and Test of Backup Roll in Temper Mill

Vibration Analysis and Test of Backup Roll in Temper Mill Sensors & Transducers 2013 by IFSA http://www.sensorsportal.com Vibration Analysis and Test of Backup Roll in Temper Mill Yuanmin Xie College of Machinery and Automation, Wuhan University of Science and

More information

FLOW CONSIDERATIONS IN INDUSTRIAL SILENCER DESIGN

FLOW CONSIDERATIONS IN INDUSTRIAL SILENCER DESIGN FLOW CONSIDERATIONS IN INDUSTRIAL SILENCER DESIGN George Feng, Kinetics Noise Control, Inc., 3570 Nashua Drive, Mississauga, Ontario Vadim Akishin, Kinetics Noise Control, Inc., 3570 Nashua Drive, Mississauga,

More information

The Mechanism Study of Vortex Tools Drainage Gas Recovery of Gas Well

The Mechanism Study of Vortex Tools Drainage Gas Recovery of Gas Well Advances in Petroleum Exploration and Development Vol. 7, No. 1, 214, pp. 62-66 DOI:1.3968/j.aped.1925543821471.1931 ISSN 1925-542X [Print] ISSN 1925-5438 [Online] www.cscanada.net www.cscanada.org The

More information

Keywords: pressurization; smokeproof enclosure; leakage; CFD (computational fluid dynamics); experimental test

Keywords: pressurization; smokeproof enclosure; leakage; CFD (computational fluid dynamics); experimental test Article Design of a Pressurized Smokeproof Enclosure: CFD Analysis and Experimental Tests Giordana Gai 1 and Piergiacomo Cancelliere 2, * 1 Department of Structural and Geotechnical Engineering, University

More information

Analysis of Pressure Rise During Internal Arc Faults in Switchgear

Analysis of Pressure Rise During Internal Arc Faults in Switchgear Analysis of Pressure Rise During Internal Arc Faults in Switchgear ASANUMA, Gaku ONCHI, Toshiyuki TOYAMA, Kentaro ABSTRACT Switchgear include devices that play an important role in operations such as electric

More information

EXPERIMENTAL STUDY ON SNOW BEHAVIOR AROUND FENCES INSTALLED ALONG ELEVATED HIGHWAY

EXPERIMENTAL STUDY ON SNOW BEHAVIOR AROUND FENCES INSTALLED ALONG ELEVATED HIGHWAY ISTP-16, 25, PRAGUE 16 TH INTERNATIONAL SYMPOSIUM ON TRANSPORT PHENOMENA EXPERIMENTAL STUDY ON SNOW BEHAVIOR AROUND FENCES INSTALLED ALONG ELEVATED HIGHWAY Akinori Nakata*, Haruo Soeda*, Junji Onishi*,

More information

CFD Study of Solid Wind Tunnel Wall Effects on Wing Characteristics

CFD Study of Solid Wind Tunnel Wall Effects on Wing Characteristics Indian Journal of Science and Technology, Vol 9(45), DOI :10.17485/ijst/2016/v9i45/104585, December 2016 ISSN (Print) : 0974-6846 ISSN (Online) : 0974-5645 CFD Study of Solid Wind Tunnel Wall Effects on

More information

Smoke and heat control systems

Smoke and heat control systems BRITISH STANDARD BS EN 12101-6:2005 Smoke and heat control systems Part 6: Specification for pressure differential systems Kits The European Standard EN 12101-6:2005 has the status of a British Standard

More information

HEAT LOAD ELIMINATION BY USING DISPLACEMENT VENTILATION IN A CLASSROOM

HEAT LOAD ELIMINATION BY USING DISPLACEMENT VENTILATION IN A CLASSROOM TECHNICAL TRANSACTIONS CIVIL ENGINEERING CZASOPISMO TECHNICZNE BUDOWNICTWO 3-B/2014 MARTIN KOVAC*, KATARINA KNIZOVA*, ANNA SEDLAKOVA* HEAT LOAD ELIMINATION BY USING DISPLACEMENT VENTILATION IN A CLASSROOM

More information

GEA FOR ADVANCED STRUCTURAL DYNAMIC ANALYSIS

GEA FOR ADVANCED STRUCTURAL DYNAMIC ANALYSIS SMART SOLUTIONS FOR VIBRATION MONITORING GEA FOR ADVANCED STRUCTURAL DYNAMIC ANALYSIS ANALYSIS OF CIVIL STRUCTURES - EXPO MERLATA PEDESTRIAN BRIDGE ABSTRACT Civil structures and in particular bridges and

More information

Numerical Analysis of Wind loads on Tapered Shape Tall Buildings

Numerical Analysis of Wind loads on Tapered Shape Tall Buildings IJSTE - International Journal of Science Technology & Engineering Volume 1 Issue 11 May 2015 ISSN (online): 2349-784X Numerical Analysis of Wind loads on Tapered Shape Tall Buildings Ashwin G Hansora Assistant

More information

Workshop 1: Bubbly Flow in a Rectangular Bubble Column. Multiphase Flow Modeling In ANSYS CFX Release ANSYS, Inc. WS1-1 Release 14.

Workshop 1: Bubbly Flow in a Rectangular Bubble Column. Multiphase Flow Modeling In ANSYS CFX Release ANSYS, Inc. WS1-1 Release 14. Workshop 1: Bubbly Flow in a Rectangular Bubble Column 14. 5 Release Multiphase Flow Modeling In ANSYS CFX 2013 ANSYS, Inc. WS1-1 Release 14.5 Introduction This workshop models the dispersion of air bubbles

More information

Development of virtual 3D human manikin with integrated breathing functionality

Development of virtual 3D human manikin with integrated breathing functionality SAT-9.2-2-HT-06 Development of virtual 3D human manikin with integrated breathing functionality Martin Ivanov Development of virtual 3D human manikin with integrated breathing functionality: The presented

More information

Observed Roughness Lengths for Momentum and Temperature on a Melting Glacier Surface

Observed Roughness Lengths for Momentum and Temperature on a Melting Glacier Surface 5 Observed Roughness Lengths for Momentum and Temperature on a Melting Glacier Surface The roughness lengths for momentum and temperature are calculated on a melting glacier surface. Data from a five level

More information

Akasison Flow phenomena of a siphonic roof outlet

Akasison Flow phenomena of a siphonic roof outlet Akasison Flow phenomena of a siphonic roof outlet Ir. Marc Buitenhuis MTD Hydraulic research engineer Akatherm BV, Panningen, The Netherlands 06-01-2011 Abstract So far the investigations on siphonic roof

More information

Airtightness Testing in Large Buildings: NESEA 2016

Airtightness Testing in Large Buildings: NESEA 2016 Airtightness Testing in Large Buildings: NESEA 2016 Dr John Straube, P.Eng. Associate Professor, University of Waterloo Principal, RDH Building Science This session: why would one invest in airtightness

More information

Wind Flow Model of Area Surrounding the Case Western Reserve University Wind Turbine

Wind Flow Model of Area Surrounding the Case Western Reserve University Wind Turbine Wind Flow Model of Area Surrounding the Case Western Reserve University Wind Turbine Matheus C. Fernandes 1, David H. Matthiesen PhD *2 1 Case Western Reserve University Dept. of Mechanical Engineering,

More information

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A 2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A PROJECT ADDRESS TESTING AUTHORITY TELEPHONE Checked by/date Enforcement Agency Use GENERAL INFORMATION OF BLDG. PERMIT PERMIT # BLDG. CONDITIONED FLOOR

More information

Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events

Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events K. Takase 1), H. Akimoto 1) 1) Japan Atomic Energy Research Institute (JAERI),

More information

Single-sided Natural Ventilation Driven by a Combination of Wind Pressure and Temperature Difference Larsen, Tine Steen; Heiselberg, Per Kvols

Single-sided Natural Ventilation Driven by a Combination of Wind Pressure and Temperature Difference Larsen, Tine Steen; Heiselberg, Per Kvols Aalborg Universitet Single-sided Natural Ventilation Driven by a Combination of Wind Pressure and Temperature Difference Larsen, Tine Steen; Heiselberg, Per Kvols Published in: Proceedings III The th international

More information

Determination of the Design Load for Structural Safety Assessment against Gas Explosion in Offshore Topside

Determination of the Design Load for Structural Safety Assessment against Gas Explosion in Offshore Topside Determination of the Design Load for Structural Safety Assessment against Gas Explosion in Offshore Topside Migyeong Kim a, Gyusung Kim a, *, Jongjin Jung a and Wooseung Sim a a Advanced Technology Institute,

More information

MODELING AND SIMULATION OF VALVE COEFFICIENTS AND CAVITATION CHARACTERISTICS IN A BALL VALVE

MODELING AND SIMULATION OF VALVE COEFFICIENTS AND CAVITATION CHARACTERISTICS IN A BALL VALVE Proceedings of the 37 th International & 4 th National Conference on Fluid Mechanics and Fluid Power FMFP2010 December 16-18, 2010, IIT Madras, Chennai, India FMFP2010 341 MODELING AND SIMULATION OF VALVE

More information

Copyright by Turbomachinery Laboratory, Texas A&M University

Copyright by Turbomachinery Laboratory, Texas A&M University Proceedings of the 2 nd Middle East Turbomachinery Symposium 17 20 March, 2013, Doha, Qatar Effectiveness of Windage Features on High Speed Couplings Steven Pennington Global Engineering Manager John Crane

More information

Chapter 2 Ventilation Network Analysis

Chapter 2 Ventilation Network Analysis Chapter 2 Ventilation Network Analysis Abstract Ventilation network analysis deals with complex working procedures to calculate the air currents flowing in the various meshes or branches of a mine network.

More information

3D CDF MODELING OF SHIP S HEELING MOMENT DUE TO LIQUID SLOSHING IN TANKS A CASE STUDY

3D CDF MODELING OF SHIP S HEELING MOMENT DUE TO LIQUID SLOSHING IN TANKS A CASE STUDY Journal of KONES Powertrain and Transport, Vol. 17, No. 4 21 3D CDF ODELING OF SHIP S HEELING OENT DUE TO LIQUID SLOSHING IN TANKS A CASE STUDY Przemysaw Krata, Jacek Jachowski Gdynia aritime University,

More information

A COMPARATIVE STUDY OF MIX FLOW PUMP IMPELLER CFD ANALYSIS AND EXPERIMENTAL DATA OF SUBMERSIBLE PUMP

A COMPARATIVE STUDY OF MIX FLOW PUMP IMPELLER CFD ANALYSIS AND EXPERIMENTAL DATA OF SUBMERSIBLE PUMP IMPACT: International Journal of Research in Engineering & Technology (IMPACT: IJRET) ISSN 2321-8843 Vol. 1, Issue 3, Aug 2013, 57-64 Impact Journals A COMPARATIVE STUDY OF MIX FLOW PUMP IMPELLER CFD ANALYSIS

More information

ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN

ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN (This page intentionally blank) ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN TABLE OF CONTENTS O- Definitions... O- Objective... O- Design

More information

AVEMS & UNICLIMA joint Position paper on Regulation (EU) No.1253/2014 Paris, June 8 th

AVEMS & UNICLIMA joint Position paper on Regulation (EU) No.1253/2014 Paris, June 8 th AVEMS & UNICLIMA joint Position paper on Regulation (EU) No.1253/2014 Paris, June 8 th Considerations about hybrid and low pressure ventilation fans in the regulation 1253/2014 1) Definition of hybrid

More information

Overview ASTATT3. Carry out air tightness testing for single dwellings and other small buildings

Overview ASTATT3. Carry out air tightness testing for single dwellings and other small buildings Overview This standard is for those who carry out air tightness and/or change rate testing of single dwellings and small up to a gross internal volume of 4000m³ inside the thermal line as defined by EN13829

More information

Measuring range Δp (span = 100%) Pa

Measuring range Δp (span = 100%) Pa 4.4/ RLE 5: Volume-flow controller, continuous How energy efficiency is improved Enables demand-led volume flow control for the optimisation of energy consumption in ventilation systems. Areas of application

More information

Determination of the wind pressure distribution on the facade of the triangularly shaped high-rise building structure

Determination of the wind pressure distribution on the facade of the triangularly shaped high-rise building structure Determination of the wind pressure distribution on the facade of the triangularly shaped high-rise building structure Norbert Jendzelovsky 1,*, Roland Antal 1 and Lenka Konecna 1 1 STU in Bratislava, Faculty

More information

An Overview of Arup Computational Fluid Dynamics Projects

An Overview of Arup Computational Fluid Dynamics Projects An Overview of Arup Computational Fluid Dynamics Projects Jennifer Keenahan 1, Cristina Paduano 1, Réamonn Mac Réamoinn 1 1 Arup, 50 Ringsend Road, Dublin 4, Ireland email: jennifer.keenahan@arup.com,

More information

Liquid Level Measurement

Liquid Level Measurement Technical Article Liquid Level Measurement A pressure transmitter can be used to determine the liquid level in a tank, well, river or other body of liquid. The pressure at the bottom of a liquid filled

More information

ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS

ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS 3 rd International Conference on Energy Systems and Technologies 16 19 Feb. 2015, Cairo, Egypt ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS

More information

CORESTA RECOMMENDED METHOD N 6

CORESTA RECOMMENDED METHOD N 6 CORESTA RECOMMENDED METHOD N 6 DETERMINATION OF VENTILATION DEFINITIONS AND MEASUREMENT PRINCIPLES (2015 Revision September 2016) 1. SCOPE This CORESTA Recommended Method specifies a method for the determination

More information

Verification and Validation Pathfinder

Verification and Validation Pathfinder 403 Poyntz Avenue, Suite B Manhattan, KS 66502 USA +1.785.770.8511 www.thunderheadeng.com Verification and Validation Pathfinder 2015.1 Release 0504 x64 Disclaimer Thunderhead Engineering makes no warranty,

More information

Validation of a Neutral Pressure Isolation Room

Validation of a Neutral Pressure Isolation Room Validation of a Neutral Pressure Isolation Room Andrew Fletcher, William Booth and Blanca Beato Arribas BSRIA Ltd., UK Corresponding email: Andrew.Fletcher@bsria.co.uk SUMMARY The principles behind a new

More information

Tutorial. BOSfluids. Relief valve

Tutorial. BOSfluids. Relief valve Tutorial Relief valve The Relief valve tutorial describes the theory and modeling process of a pressure relief valve or safety valve. It covers the algorithm BOSfluids uses to model the valve and a worked

More information

AN IMPROVED CROSS VENTILATION MODEL IN WINDY REGIONS

AN IMPROVED CROSS VENTILATION MODEL IN WINDY REGIONS AN IMPROVED CROSS VENTILATION MODEL IN WINDY REGIONS Ahmed A.Rizk, Professor Architectural Engineering Department, Tanta University, Egypt Yasser. A.Al- Samadony, Assistant Professor Mechanical Power Engineering

More information

Study on the Influencing Factors of Gas Mixing Length in Nitrogen Displacement of Gas Pipeline Kun Huang 1,a Yan Xian 2,b Kunrong Shen 3,c

Study on the Influencing Factors of Gas Mixing Length in Nitrogen Displacement of Gas Pipeline Kun Huang 1,a Yan Xian 2,b Kunrong Shen 3,c Applied Mechanics and Materials Online: 2013-06-13 ISSN: 1662-7482, Vols. 321-324, pp 299-304 doi:10.4028/www.scientific.net/amm.321-324.299 2013 Trans Tech Publications, Switzerland Study on the Influencing

More information

Quantification of the Effects of Turbulence in Wind on the Flutter Stability of Suspension Bridges

Quantification of the Effects of Turbulence in Wind on the Flutter Stability of Suspension Bridges Quantification of the Effects of Turbulence in Wind on the Flutter Stability of Suspension Bridges T. Abbas 1 and G. Morgenthal 2 1 PhD candidate, Graduate College 1462, Department of Civil Engineering,

More information

PRODUCT CONFIGURATOR AT mcr Monsun. smoke extraction and air supply axial-flow fans

PRODUCT CONFIGURATOR AT   mcr Monsun. smoke extraction and air supply axial-flow fans PRODUCT CONFIGURATOR AT WWW.MERCOR.COM.P mcr Monsun smoke extraction and air supply axial-flow fans APPICATION mcr Monsun fans are designed to extract hot air, smoke and exhaust gases from fire-exposed

More information

REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION

REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION Mads Mysen* 1, Axel Cablé 1, Peter G. Schild 1, and Kari Thunshelle 1 1 SINTEF Building and Infrastructure Forskningsveien

More information

Results of Field Measurements and CONTAM Simulation. Building Science

Results of Field Measurements and CONTAM Simulation. Building Science 28 Building Science Corporation Tracer Gas Testing January 26 Results of Field Measurements and CONTAM Simulation Aaron Townsend Building Science Tracer gas test of a production Building America house

More information

ANALYSIS OF AERODYNAMIC CHARACTERISTICS OF A SUPERCRITICAL AIRFOIL FOR LOW SPEED AIRCRAFT

ANALYSIS OF AERODYNAMIC CHARACTERISTICS OF A SUPERCRITICAL AIRFOIL FOR LOW SPEED AIRCRAFT ANALYSIS OF AERODYNAMIC CHARACTERISTICS OF A SUPERCRITICAL AIRFOIL FOR LOW SPEED AIRCRAFT P.Sethunathan 1, M.Niventhran 2, V.Siva 2, R.Sadhan Kumar 2 1 Asst.Professor, Department of Aeronautical Engineering,

More information

A. M. Dalavi, Mahesh Jadhav, Yasin Shaikh, Avinash Patil (Department of Mechanical Engineering, Symbiosis Institute of Technology, India)

A. M. Dalavi, Mahesh Jadhav, Yasin Shaikh, Avinash Patil (Department of Mechanical Engineering, Symbiosis Institute of Technology, India) IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN(e) : 2278-1684, ISSN(p) : 2320 334X, PP : 45-49 www.iosrjournals.org Modeling, Optimization & Manufacturing of Vortex Tube and Application

More information

Gas Vapor Injection on Refrigerant Cycle Using Piston Technology

Gas Vapor Injection on Refrigerant Cycle Using Piston Technology Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Gas Vapor Injection on Refrigerant Cycle Using Piston Technology Sophie

More information

This test shall be carried out on all vehicles equipped with open type traction batteries.

This test shall be carried out on all vehicles equipped with open type traction batteries. 5.4. Determination of hydrogen emissions page 1 RESS-6-15 5.4.1. This test shall be carried out on all vehicles equipped with open type traction batteries. 5.4.2. The test shall be conducted following

More information

Smoke Ventilation of Common Access Areas of Flats and Maisonettes (BD2410) - Final Factual Report Appendix A (Review)

Smoke Ventilation of Common Access Areas of Flats and Maisonettes (BD2410) - Final Factual Report Appendix A (Review) Smoke Ventilation of Common Access Areas of Flats and Maisonettes (BD2410) - Final Factual Report Appendix A (Review) The authors of this report are employed by BRE. The work reported herein was carried

More information

This is an author produced version of Determining the optimum spacing and arrangement for commercial wind towers for ventilation performance.

This is an author produced version of Determining the optimum spacing and arrangement for commercial wind towers for ventilation performance. This is an author produced version of Determining the optimum spacing and arrangement for commercial wind towers for ventilation performance. White Rose Research Online URL for this paper: http://eprints.whiterose.ac.uk/81544/

More information

New Technologies applied to the design and optimization of tunnel ventilation systems

New Technologies applied to the design and optimization of tunnel ventilation systems New Technologies applied to the design and optimization of tunnel ventilation systems Ing. Justo Suárez Area Manager - ZITRON Dot. Ing. Massimiliano Bringiotti Managing Director - GEOTUNNEL Ing. Ana Belén

More information

Application Block Library Fan Control Optimization

Application Block Library Fan Control Optimization Application Block Library Fan Control Optimization About This Document This document gives general description and guidelines for wide range fan operation optimisation. Optimisation of the fan operation

More information

Wind Effect on Smoke Exhaust by Natural Vent

Wind Effect on Smoke Exhaust by Natural Vent The 2012 World Congress on Advances in Civil, Environmental, and Materials Research (ACEM 12) Seoul, Korea, August 26-30, 2012 Wind Effect on Smoke Exhaust by Natural Vent J. Li 1) and *W.K. Chow 2) 1)

More information

Experimental determination of deflagration explosion characteristics of methane air mixture and their verification by advanced numerical simulation

Experimental determination of deflagration explosion characteristics of methane air mixture and their verification by advanced numerical simulation Structures Under Shock and Impact XII 169 Experimental determination of deflagration explosion characteristics of methane air mixture and their verification by advanced numerical simulation M. Mynarz,

More information

STAIRCASE PRESSURIZATION SYSTEM

STAIRCASE PRESSURIZATION SYSTEM STAIRCASE PRESSURIZATION SYSTEM Staircase Pressurization System SMOKE AND HEAT CONTROL SYSTEMS: Specification for pressure differential systems NORM: BS EN 12101-6:2005 This norm specifies the pressure

More information

Evaluation of the optimum conditions for a local ventilation system in connection with the mine ventilation network

Evaluation of the optimum conditions for a local ventilation system in connection with the mine ventilation network Underground Mining Technology 2017 M Hudyma & Y Potvin (eds) 2017 Australian Centre for Geomechanics, Perth, ISBN 978-0-9924810-7-0 https://papers.acg.uwa.edu.au/p/1710_55_lee/ Evaluation of the optimum

More information

Study by numerical simulations on the breathing effect in a semi-underground highway with beams and a roof above it

Study by numerical simulations on the breathing effect in a semi-underground highway with beams and a roof above it Study by numerical simulations on the breathing effect in a semi-underground highway with beams and a roof above it M Hagiwara East Nippon Expressway Co., Ltd, Japan A Mizuno, T Tsutaki Kogakuin University,

More information

Critical Gust Pressures on Tall Building Frames-Review of Codal Provisions

Critical Gust Pressures on Tall Building Frames-Review of Codal Provisions Dr. B.Dean Kumar Dept. of Civil Engineering JNTUH College of Engineering Hyderabad, INDIA bdeankumar@gmail.com Dr. B.L.P Swami Dept. of Civil Engineering Vasavi College of Engineering Hyderabad, INDIA

More information

CFD Modeling of Thermal Manikin Heat Loss in a Comfort Evaluation Benchmark Test

CFD Modeling of Thermal Manikin Heat Loss in a Comfort Evaluation Benchmark Test CFD Modeling of Thermal Manikin Heat Loss in a Comfort Evaluation Benchmark Test Håkan O. Nilsson 1, Henrik Brohus 2 and Peter V. Nielsen 2 1 Department of Technology and Built Environment, University

More information

Influence of the external dynamic wind pressure on the ventilation of double facades

Influence of the external dynamic wind pressure on the ventilation of double facades Influence of the external dynamic wind pressure on the ventilation of double facades Claudia Ziller & Bernd Döring Institute of steel construction, Aachen, Germany ABSTRACT: The ventilation rate in the

More information