1020 Industrial Drive, Orlinda, TN fax

Size: px
Start display at page:

Download "1020 Industrial Drive, Orlinda, TN fax"

Transcription

1 Operation Manual Ultrafiltration for High Purity Distribution K-A-HPTUF Series fax

2 TABLE OF CONTENTS Section 1 GENERAL 1.1 Warnings and Cautions Theory of Operation System Illustration System Components... 4 Section 2 SPECIFICATIONS 2.1 General Requirements Dimensions & Weight... 7 Section 3 INSTALLATION 3.1 Installation... 8 Section 4 OPERATION 4.1 Initial Start-Up Daily Start-Up Monitoring Procedures Adjusting Procedures Daily Shutdown Section 5 ROUTINE MAINTENANCE 5.1 Troubleshooting Routine Maintenance Membrane Replacement Disinfection Procedure Appendix A Sample Quality Assurance Checklist sales@specialtyh2o.com fax

3 Section 1.1 WARNINGS AND CAUTIONS WARNINGS Read this manual in its entirety before operating the Ultrafiltration for High Purity Distribution. Misuse, improper operation, and/or improper monitoring of this equipment could result in serious injury, death, or other serious reactions to the end users of the equipment. A regular disinfection schedule for the water treatment components including the Ultrafiltration for High Purity Distribution System should be outlined by the Governing Body of the facility. If the system is opened, a complete disinfection must be completed before dialysis treatments can be initiated. The Ultrafiltration for High Purity Distribution system must never be used as a primary filtration device. The system is designed for final filtration only. All hemodialysis treatments must be discontinued prior to initiating disinfection of the Ultrafiltration for High Purity Distribution System. The Ultrafiltration for High Purity Distribution System contains items which contact the final product water to the end user. Do not modify or adjust any part of this system. All replacement parts must be obtained from Specialty Water Technologies. CAUTIONS When used as a medical device, Federal law restricts this device to sale by or on the authority of a physician. Per CFR (b)(1). It is the responsibility of the governing body of the facility to ensure that all applicable regulations regarding the installation and operation of this system are observed. Only authorized personnel can install, perform service, or perform maintenance to the Ultrafiltration for High Purity Distribution System. Ultrafilters are to be used only for post-treatment of reverse osmosis (RO) treated water and are not intended to provide primary purification sales@specialtyh2o.com fax 1

4 Section 1.2 THEORY OF OPERATION The SWT Ultrafiltration Rack for High Purity Distribution is designed for high purity water loop distribution primarily in the medical (dialysis) setting. It is constructed of fiberglass membrane vessels with Teflon fittings and connections. The system is placed on the permeate water distribution loop. The Ultrafilter membranes remove particle and microbial contamination from the permeate water and are just one component in a complex system of water purification equipment for dialysis processes. The Membranes contained in the Ultrafiltration Rack will reject microbiological contamination as opposed to a dead end cartridge filter that traps particles. By setting a reject flow, the contaminants are flushed from the membranes. The reject flow rate can be turned off during non-operational hours of the facility. The Ultrafiltration Membranes are tolerant to bleach and renalin / peraciden at a 1:100 dilution ratio. They are not compatible with high level disinfection with bleach or renalin / peraciden. The membranes will not tolerate heat or ozone disinfection. The SWT Ultrafiltration Rack features zero dead leg plumbing, high purity sample ports, 316 S.S. pressure gauges, output flow meter, sampling cups, drains, and an adjustable reject with shut off valve sales@specialtyh2o.com fax 2

5 Section 1.3 SYSTEM ILLUSTRATION Permeate Tubes (Green) Configuration will vary depending on direction of loop flow Membrane Product Valve Inlet Pressure Gauge Inlet Sample Port Drain Cup UF Reject Shut Off Valve Outlet Flowmeter Outlet Pressure Gauge UF Permeate Sample Port Bypass Valve Drain Cup UF Reject Flow Membrane Vessels Drain Drain Reject Tubes (Black) fax 3

6 Section 1.4 SYSTEM COMPONENTS UF Reject Shut Off: Allows user to shut off UF reject flow. UF Reject Adjustment: Allows user to adjust UF reject flow according to facility policy fax 4

7 Operation Manual Specialty Water Technologies, Inc. Ultrafiltration for High Purity Distribution Section 1.4 SYSTEM COMPONENTS Inlet Sample Port: Sample Port and convenient drain cup for inlet of membranes. Gauge to monitor inlet flow pressure. UF Permeate Sample Port and Flowmeter: Sample Port and convenient drain cup for outlet of membranes. Gauge and flowmeter to monitor outlet flow pressure. UF Permeate Sampling Procedure: 1. Open and close port x Obtain a steady stream of water through port. Allow water to flow for specified time (facility policy). 3. Place sample cup under stream of water and collect sample sales@specialtyh2o.com fax 5

8 Section 1.4 SYSTEM COMPONENTS Membrane Product Valve: Valve to shut off permeate. Valve # 41 Membrane Bypass Valve: Valve used to bypass membranes during high level disinfection or during membrane change. Valve # sales@specialtyh2o.com fax 6

9 Section 2.1 SPECIFICATIONS ELECTRICAL AND WATER REQUIREMENTS: Water Requirements: Electrical Requirements: Drain Requirements: A properly pretreated water supply consisting of RO product water. Inlet pressure of psi None Must facilitate 3 5 gpm. SPECIFICATIONS: Models K-A-HPTUF-2 K-A-HPTUF-3 K-A-HPTUF-4 K-A-HPTUF-5 Max. Capacity GPM # of Filters Weight 95 lbs 140 lbs 185 lbs 230 lbs Overall Dimensions Mounting 32 W X 96 L 36 W X 96 L 40 W X 96 L Wall Mounted Ultra Filters 4 x 40 % Recovery 90% - 95% MWCO Incoming Water Requirements Pressure Gauges 10,000 daltons RO or DI water Stainless Steel accurate ±2% Flow Meters Reject accurate ±4 and Product accurate ±5% Disinfecting Sample Ports Compatible with 1% Peracetic Acid or Bleach 2 (1 Inlet and 1 Outlet) sales@specialtyh2o.com fax 7

10 Section 3.1 INSTALLATION Mounting the UF Rack on the wall: Please use illustration in section 1.3 for reference 1. Due to the weight of the UF Rack, it must be mounted onto plywood. 2. Wall space for mounting must be a minimum of 3 feet in width and 8 feet high. 3. Remove the 1 1/2 drain cup up rights out of the assembly at the 90 degree pipe. They are not glued. 4. Using the (4) 5/16 x 1 1/2 lag screws with the 1/2 flat washers provided in the hardware kit, secure the strut to the plywood on the wall. Secure at the ends of both strut pieces. When leveling, place the level on the strut, not the membrane housings. 5. Attach the top valve assembly by connecting and tightening the valve connection. 6. Use the (5) 1 1/2 Nylon spacers with 3 sheetrock screws and white caps to secure plastic frame to plywood in pre-drilled holes. 7. Connect blue permeate tubes to top of membrane housings. 8. Make inflow and outflow connections as needed for existing loop. 9. Re-attach drain cup up rights. These are not glued. 10. Plumb the drain to the nearest source as desired. May be plumbed to the right or left. **Loop and UF Rack must be disinfected before initiation of hemodialysis treatments** sales@specialtyh2o.com fax 8

11 Section 4.1 OPERATION INITIAL START-UP 1. On initial start-up or membrane replacement, divert the product water flow to drain (not to reservoir or distribution loop) for a minimum of 2 hours to rinse preservative from the membranes. DAILY START-UP 1. Ensure the R.O. has been placed into the OPERATE mode. 2. Ensure storage tank is at least half full (not applicable to direct feed systems). 3. The inlet and outlet valves open, and the by-pass valve is in the closed position. 4. Open the reject shut-off valve. 5. Verify that the reject flow is 5% to 10% of product flow. MONITORING PROCEDURES 1. The Ultrafilter system must be monitored on a daily schedule by a qualified technician using a checklist. An example checklist is provided in Appendix A of this manual and may be reproduced for use. 2. The filter gauges should be checked with water flowing when there is NO demand for purified water. 3. Monitoring Requirements: Filter System Inlet Pressure Filter System Outlet Pressure By-pass Valve Normally Closed Product Flow Reject Flow Bacteria/Endotoxins (check at least monthly; more often if necessary) must meet established standards sales@specialtyh2o.com fax 9

12 Section 4.2 OPERATION ADJUSTING PROCEDURES 1. The only adjustment to a 4x40 Ultrafilter System is the reject flow. Locate the reject flow rate adjustment knob on the filter system. Slowly turn the adjustment knob clockwise or counterclockwise as required to increase or decrease the reject flow rate to 5-10% of product flow. 2. Any other adjustments are to the loop delivery pump and/or the pressure by-pass on the loop return at the storage tank. DAILY SHUTDOWN 1. Ensure there are no requirements for purified water. 2. Close the reject shut-off valve until the flow ceases and the reject flow meter indicates zero flow rate sales@specialtyh2o.com fax 10

13 Section 5.1 ROUTINE MAINTENANCE TROUBLESHOOTING GUIDE Problem Possible Causes Possible Solutions The recovery rate is less than 90% The product flow has decreased by 10% or greater If the Delta P is lower than the initial qualification Reject adjustment valve needs adjusted Membranes are fouled Membranes exceed recommended change out time Loop return pressure regulator could be out of adjustment. Adjust the reject valve to establish a recovery rate of 90-95% Check the inlet pressure to the filter system. If the inlet pressure has decreased below the design specification, then adjust the pressure settings at the loop/delivery system. Perform a disinfect Adjust the pressure valve at the loop return at the storage tank. The product water is contaminated with microbiological contaminates The pressure drop is greater than 15 psi Delta P at the initial qualification with zero demand Membrane ruptured Missing or damaged O- rings Oxidized membranes Membranes are fouled Improper disinfection Membranes exceed recommended change out time Loop return pressure regulator could be out of adjustment Membranes are fouled Membranes exceed recommended change out time If the above step down not correct the problem, replace the membranes and/or O-rings Perform a disinfect If disinfect does not correct the problem, the membranes must be replaced. Adjust the pressure regulator at the loop return at the storage tank. Perform a disinfect Replace Membranes sales@specialtyh2o.com fax 11

14 Section 5.1 ROUTINE MAINTENANCE 1. Keep component clean by periodically wiping with a soft cloth. 2. Do not use harsh chemicals to clean the outside components of the system. 3. Inspect regularly for leaks and tighten fittings gently if needed. 4. Replace membranes and seals every 3 years, unless directed by clinical management sooner. 5. Only install manufacturer recommended ultra-filtration membranes sales@specialtyh2o.com fax 12

15 Section 4.2 MEMBRANE REPLACEMENT ** Ensure there are no hemodialysis treatments in session ** 1. Turn loop pump off. 2. Open Reject Valve to drain membranes Disconnect the permeate and inflow from the top of each membrane vessel Disconnect the service manifold from the top of the vessels. 5. Disconnect the inlet and outlet loop from the UF Rack. 6. It may be necessary to remove the top bracket from the wall to access the membranes. 7. Remove the retaining clip from the top of each vessel. Pull the end caps out Remove adapter and membrane from each vessel. 9. Remove reject tubing, retaining clips, end caps and adapters from bottom of vessels. 10. Clean membrane vessels and adaptors according to facility policy. 11. Replace all O-rings with new ones. 12. Re-insert cleaned adapters, retaining clamps, end caps and reject tubing on bottom of vessels. 13. Place new membranes in vessels. (Record Serial Numbers) 14. Place adaptors, end caps and retaining clips back in place Reattach the bracket, manifold and permeate lines. 16. Reattach the inlet and outlet connections Turn the loop pump on and check for leaks. WARNING: System MUST be rinsed of packing preservative and disinfected immediately after membrane change sales@specialtyh2o.com fax 13

16 Section 4.3 DISINFECTION PROCEDURE ** See System Illustration for Clarification of Components ** This is a general guide for disinfection of the Specialty Water Technologies Ultrafiltration Rack. The user must follow all facility policies and guidelines regarding this component of the water treatment system. *** Ensure there are no hemodialysis treatments in session *** Do not expose UF membranes to bleach concentrations greater than 1:100 dilution of % Sodium Hypochlorite. *** Do not use: splash-less or gel bleach (creates foam), or scented bleach. 1:100 Disinfection: Membranes are not bypassed. 1. Turn Loop Pump off. 2. Fill storage tank to 90 gallons of RO water. 3. Add appropriate amount of disinfectant to tank to make a 1:100 concentration solution. 4. Turn the loop pump on to circulate the disinfectant through the loop 5. Verify presence of disinfectant at loop return point 6. Circulate disinfectant through loop for amount of time stated in facility policies and procedures. 7. Recommended dwell time of no greater than 30 minutes. Prolonged exposure to bleach will shorten the life of the membranes. 8. During the circulation of disinfectant, open and close both sample ports, the reject shut off and reject flow adjustment valves to flush with disinfectant. Very quickly, rotate the UF Bypass Valve (Red Handle) to the bypass position. 9. Then close the Membrane Product Valve (Blue Handle). Do not close the Membrane Product Valve with the loop pump running unless the UF Bypass valve is on Bypass 10. Open the Membrane Product Valve (Blue Valve). 11. Place the UF Bypass (Red Handle) valve to the Service position. Rinsing Procedure: 1. Rinse the storage tank of disinfectant and ensure disinfectant tests negative at the loop return. 2. With the loop pump running, repeat steps 8-11 above. Rinse loop for the time frame designated in facility policies and procedures. 3. Check for absence of disinfectant at all points of use. 4. Thirty minutes later, check for absence of disinfectant at all points of use. ** Disinfectant must be thoroughly rinsed and tested negative ** ** Due to possible rebound of disinfectant, it is recommended that another test for disinfectant is done prior to initiation of hemodialysis treatments ** sales@specialtyh2o.com fax 14

17 APPENDIX A SAMPLE QUALITY ASSURANCE CHECKLIST Post Treatment Checklist M T W T F S S DATE STORAGE TANK.2 Vent Filter Installed (Y/N) REPRESSURIZATION PUMPS Correct Rotation (Y/N) Flow Switch Operates Properly (Y/N) Pump Discharge Pressure (PSI) U.V. LIGHT (if used) Post U.V. Light Pressure (PSI) U.V. Light Pressure PSI (<15 PSI) U.V. Light On (Y/N) 0.03 / 0.05 MICRON FILTER (if used) Post 0.03 / 0.05 Micron Filter Pressure (PSI) 0.03 / 0.05 Micron Filter Pressure PSI (<15 PSI) ULTRAFILTERS IN WATER ROOM (if used) Post UF Pressure (PSI) *UF PSI (<15 PSI per element) UF Product Flow (GPM) UF Reject Flow (GPM) ULTRAFILTERS IN REUSE ROOM (if used) Pre UF Pressure (PSI) Post UF Pressure (PSI) UF Product Flow (GPM) UF Reject Flow (GPM) LOOP RETURN Loop Return Flow (if used) (GPM) Loop Return Pressure (PSI) TECHNICIAN S INITIALS sales@specialtyh2o.com fax 15

18 Ultrafiltration Operation Manual Rev. 8_2017 Manual P/N: OM-K-A-HPTUF fax

1020 Industrial Drive, Orlinda, TN fax

1020 Industrial Drive, Orlinda, TN fax Operation Manual Tank Distribution System A-UPT Series 615-654-4441 sales@specialtyh2o.com 615-654-4449 fax TABLE OF CONTENTS Section 1 GENERAL 1.2 Warnings and Cautions... 1 1.2 Theory of Operation...

More information

4 x 40 Spiral Wound Ultra Filter System

4 x 40 Spiral Wound Ultra Filter System Better Water LLC 4 x 40 Spiral Wound Ultra Filter System Operator Manual rev. Apr 2015 Better Water LLC. All rights reserved. The content of this manual is the intellectual property of Better Water LLC.

More information

Operation Manual. Carbon Filtration Industrial Drive, Orlinda, TN fax

Operation Manual. Carbon Filtration Industrial Drive, Orlinda, TN fax Operation Manual Carbon Filtration 615-654-4441 sales@specialtyh2o.com 615-654-4449 fax TABLE OF CONTENTS Section 1 GENERAL 1.1 Warnings and Cautions... 1 1.2 Theory of Operation... 2 1.3 System Illustration...

More information

Concentrate Distribution System (Stand Mounted) A-CDS-70-X & A-CDS-TANK-X-ST Industrial Drive, Orlinda, TN 37141

Concentrate Distribution System (Stand Mounted) A-CDS-70-X & A-CDS-TANK-X-ST Industrial Drive, Orlinda, TN 37141 0 Operation Manual Concentrate Distribution System (Stand Mounted) A-CDS-70-X & A-CDS-TANK-X-ST 615-654-4441 sales@specialtyh2o.com 615-654-4449 fax TABLE OF CONTENTS Section 1 GENERAL 1.1 Warnings and

More information

CART FOR CENTURION 1500+

CART FOR CENTURION 1500+ CART FOR CENTURION 1500+ Operation & Maintenance Manual www.ameriwater.com 800-535-5585 AmeriWater 3345 Stop 8 Rd. Dayton, OH 45414 98-0161 Rev A Contents 1. GENERAL INFORMATION... 1 1.1. Features...

More information

REVERSE OSMOSIS WATER FILTRATION SYSTEM MODEL EWR 4075 INSTRUCTION MANUAL

REVERSE OSMOSIS WATER FILTRATION SYSTEM MODEL EWR 4075 INSTRUCTION MANUAL REVERSE OSMOSIS WATER FILTRATION SYSTEM MODEL EWR 4075 INSTRUCTION MANUAL Excalibur Water Systems 142 Commerce Park Drive, Unit M & N Barrie, Ontario L4N 8W8 CANADA www.excaliburwater.com 2013.05.7446

More information

Light Commercial Reverse Osmosis System. EE-1000 Manual

Light Commercial Reverse Osmosis System. EE-1000 Manual Light Commercial Reverse Osmosis System EE-1000 Manual Nimbus Water Systems 41840 McAlby Court, Suite A Murrieta, CA 92562 800-451-9343 Fax 951-894-2801 www.nimbuswater.com Nimbus Water Systems 1 EE-1000

More information

FlashGARD HP Reverse Osmosis Filtration System Model Number FSTMO75 Part Number

FlashGARD HP Reverse Osmosis Filtration System Model Number FSTMO75 Part Number 3M Water Filtration Products FlashGARD HP Reverse Osmosis Filtration System Model Number FSTMO75 Part Number 56123-06 Installer: Please leave this manual with owner/operator. End User: Please retain for

More information

Pure Water Power Purification System 4-Stage RODI Operations Manual

Pure Water Power Purification System 4-Stage RODI Operations Manual Pure Water Power Purification System 4-Stage RODI Operations Manual Flush Valve Lever Quick Disconnect for RO Water Testing Water Supply In Drain Hose Pure Water Out to Waterfed Pole New Machine Setup

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Product Preservers Anti-Scale System Chemical-Free, Salt-Free Scale Prevention Introduction The Product Preservers Anti-Scale System will condition the tap

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual Model H2F H2Flow Anti-Scale System Chemical-Free, Salt-Free Scale Prevention Introduction The H2Flow Anti-Scale System will condition the tap water providing

More information

REVERSE OSMOSIS WATER FILTRATION SYSTEM MODEL EWR 3035 INSTRUCTION MANUAL

REVERSE OSMOSIS WATER FILTRATION SYSTEM MODEL EWR 3035 INSTRUCTION MANUAL REVERSE OSMOSIS WATER FILTRATION SYSTEM MODEL EWR 3035 INSTRUCTION MANUAL Excalibur Water Systems 142 Commerce Park Drive, Unit M & N Barrie, Ontario L4N 8W8 CANADA www.excaliburwater.com 3-Stage RO System

More information

Operating Instructions Model and Hydrostatic Test Pump

Operating Instructions Model and Hydrostatic Test Pump Operating Instructions Model 29200 and 2920 Hydrostatic Test Pump Dimension Weight Pump Pressure for 29200 Pump Pressure for 2920 Gauge for 29200 Gauge for 2920 Inlet Connection Outlet Connection Hose

More information

Installation, Operation, and Maintenance Manual Parker Balston Model N2-04 Nitrogen Generator

Installation, Operation, and Maintenance Manual Parker Balston Model N2-04 Nitrogen Generator Installation, Operation, and Maintenance Manual Parker Balston Figure 1 - N2-04 Nitrogen Generator These instructions must be thoroughly read and understood before installing and operating this product.

More information

ULTRA PURE SYSTEMS 625 GPD RODI INSTALLATION AND OPERATION MANUAL

ULTRA PURE SYSTEMS 625 GPD RODI INSTALLATION AND OPERATION MANUAL ULTRA PURE SYSTEMS 625 GPD RODI INSTALLATION AND OPERATION MANUAL Thank you for choosing UPS (Ultra-Pure Systems) for your RO/DI solution. We are confident you have made the right decision. This system

More information

IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS Warrior D.E. Filter Operating Procedures IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS Table of Contents SECTION I. FILTER INSTALLATION... 1 SECTION II. FILTER

More information

Operation Manual - PN A MENSOR MODEL 73 SHOP AIR BOOSTER

Operation Manual - PN A MENSOR MODEL 73 SHOP AIR BOOSTER Operation Manual - PN 0017946001 A MENSOR MODEL 73 SHOP AIR BOOSTER Mensor Model 73 Shop Air Booster System (750 psi Version) April 23, 2012 Trademarks / Copyright Mensor is a registered trademark of Mensor

More information

CS Controlled Dissolved Gas assembly with optional CS Air Aspirator assembly. Installation and Operation information

CS Controlled Dissolved Gas assembly with optional CS Air Aspirator assembly. Installation and Operation information CS-425-01 Controlled Dissolved Gas assembly with optional CS-603-01 Air Aspirator assembly Installation and Operation information Serial # CS-XXX Date of shipment:, 2005 Shipped to: Purchase order #: xxxxxxx

More information

UltRo Dual Flow Reverse Osmosis Water System

UltRo Dual Flow Reverse Osmosis Water System UltRo Dual Flow Reverse Osmosis Water System Congratulations on this great investment to your health. **IMPORTANT NOTE BEFORE YOU BEGIN** We recommend you call your local friendly plumber to ensure proper

More information

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SUPPLIMENT TO eom IMPORTANT READ THIS MANUAL BEFORE PRODUCT INSTALLATION, OPERATION, INSPECTION & MAINTENANCE Tougher and more rigid guidelines are being established

More information

3M Water Filtration Products

3M Water Filtration Products 3M Water Filtration Products Installation and Operation Instructions for ScaleGard TM HP Reverse Osmosis System Installer: Please leave this manual with owner/operator. Owner/Operator: Please retain for

More information

SpectraPure PUMPED RO SYSTEMS (PSP) User s Manual for PSP-1500 Systems

SpectraPure PUMPED RO SYSTEMS (PSP) User s Manual for PSP-1500 Systems SpectraPure PUMPED RO SYSTEMS (PSP) User s Manual for PSP-1500 Systems 2 3 PSP-1500 SYSTEM DESCRIPTION Reverse Osmosis RO Reverse Osmosis utilizes the unique properties of a semi-permeable membrane to

More information

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION INSTALLATION INSTRUCTIONS CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION The CVS Controls 67CFR Filter regulator is a pressure reducing supply regulator typically used for pneumatic

More information

PRS-11 Particle Reduction System OPERATIONS MANUAL REV A 3SEP08

PRS-11 Particle Reduction System OPERATIONS MANUAL REV A 3SEP08 PRS-11 OPERATIONS MANUAL 3024546 REV A 3SEP08 PRS-11 Operations Manual TABLE OF CONTENTS Page CHAPTER ONE: GENERAL INFORMATION 1 Section 1.1 General 1 1.2 Warranty Information 1 1.3 Service/Technical

More information

Yoke Block Instruction Manual

Yoke Block Instruction Manual Yoke Block Instruction Manual ! WARNING IMPORTANT: READ MANUAL COMPLETELY BEFORE OPERATING THIS DEVICE This manual contains instructions on periodically required checks to be performed by the user. These

More information

Easy Nest Kits. Installation Suggestions

Easy Nest Kits. Installation Suggestions Easy Nest Kits Installation Suggestions 2 General Recommendations Hydraulics Vacuum breakers should be installed to prevent siphoning. Flexible connectors should follow FRP tank manufacturers recommendations.

More information

Multi-Probe Sampling System User Guide & Manual

Multi-Probe Sampling System User Guide & Manual Multi-Probe Sampling System User Guide & Manual Rev. 06/05/12 Part #22200012 Table of Contents CHAPTER 1: SYSTEM DESCRIPTION... 2 FUNCTION AND THEORY... 3 SYSTEM COMPONENTS... 4 CHAPTER 2: SYSTEM INSTALLATION...

More information

Avenger Model 33M Installation & Operation Instructions

Avenger Model 33M Installation & Operation Instructions Avenger Model 33M Installation & Operation Instructions Manufacturing Contact Information A+ Corporation, LLC Call for expert product application assistance: 41041 Black Bayou Rd. Gonzales, LA 70737 Phone:

More information

PremAire INSTRUCTIONS FOR VORTEX TUBE MODE OF OPERATION

PremAire INSTRUCTIONS FOR VORTEX TUBE MODE OF OPERATION DUAL SUPPLY REGULATOR ESCAPE CYLINDER VORTEX MAIN INLET PremAire INSTRUCTIONS FOR VORTEX TUBE MODE OF OPERATION WARNING THIS MANUAL MUST BE READ CAREFULLY BY ALL PERSONS WHO HAVE OR WILL HAVE THE RESPONSIBILITY

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS HIGH PRESSURE PUMP To minimize vibration, it is best to build brackets on the motor itself, similar to alternator brackets. Use cardboard to construct a pattern first before making

More information

Manual. Bypass Feeder. Installation Maintenance Repair Manual. Chemical Addition and Filtering

Manual. Bypass Feeder. Installation Maintenance Repair Manual. Chemical Addition and Filtering Manual Bypass Feeder Chemical Addition and Filtering Installation Maintenance Repair Manual Advantage Controls P.O. Box 1472 Muskogee, OK 74402 Phone: 918-686-6211 Fax: 918-686-6212 www.advantagecontrols.com

More information

Softeners Clack Model V125DTH Medical / Industrial Series Operation and Service Manual

Softeners Clack Model V125DTH Medical / Industrial Series Operation and Service Manual Softeners Clack Model V125DTH Medical / Industrial Series Operation and Service Manual www.ameriwater.com 800-535-5585 AmeriWater LLC 3345 Stop 8 Rd. Dayton, OH 45414 Clack Softener Manual, 98-0180 Rev.

More information

Operating Instructions Models 36200, , 46200, Hydrostatic Test Pumps

Operating Instructions Models 36200, , 46200, Hydrostatic Test Pumps Operating Instructions Models 36200, 362000, 46200, 462000 Hydrostatic Test Pumps 46200 DIMENSIONS: 28 (70cm) L x 24 (60cm) W x 38 (87.5cm) H WEIGHT: PUMP: ENGINE: CONTROL: GAUGE: DISCHARGE HOSE: INTAKE

More information

INSTRUCTION MANUAL GAS TRAK

INSTRUCTION MANUAL GAS TRAK INSTRUCTION MANUAL GAS TRAK 166 Keystone Drive Montgomeryville, PA 18936 Telephone: 215-641-2700 Fax: 215-641-2714 INT-0234 rev A1 TABLE OF CONTENTS SERVICE 3 LIMITED WARRANTY 3-4 USER RESPONSIBILITY 4-5

More information

Installation and commissioning instructions 255 series and 256 series

Installation and commissioning instructions 255 series and 256 series Installation and commissioning instructions 255 series and 256 series Table of contents 1 General information... 3 1.1 About these instructions... 3 1.2 About this product... 3 1.3 Appropriate usage...

More information

Operating Instructions Models and Hydrostatic Test Pumps

Operating Instructions Models and Hydrostatic Test Pumps Operating Instructions Models 46501 and 465010 Hydrostatic Test Pumps 46501 DIMENSIONS: WEIGHT: PUMP: ENGINE: CONTROL: GAUGE: DISCHARGE HOSE: INLET HOSE: 28 (70cm) L x 24 (60cm) W x 35 (87.5cm) H 136 lbs.

More information

Installation and Use Manual

Installation and Use Manual Installation and Use Manual EMASMB & LMASMB Surface Mount Bottle Filling Stations Model EMASMB IMPORTANT THIS IS AN INDOOR APPLICATION ONLY! ALL SERVICE TO BE PERFORMED BY AN AUTHORIZED SERVICE PERSONNEL.

More information

User Guide. Pall Laboratory Manifold. For laboratory use. Not for use in a manner other than indicated. Introduction. Regulatory References

User Guide. Pall Laboratory Manifold. For laboratory use. Not for use in a manner other than indicated. Introduction. Regulatory References User Guide Pall Laboratory Manifold For laboratory use. Not for use in a manner other than indicated. Introduction Application and Intended Use The membrane filtration (MF) technique is a method of analyzing

More information

Medical Gas Control Panel

Medical Gas Control Panel Medical Gas Control Panel INSTALLATION & MAINTENANCE MANUAL 255105 (Rev. 6) 2018-04 2 255105 (Rev. 6) 2018-04 1.0 User Responsibilities The information contained in this installation and operation maintenance

More information

REVERSE OSMOSIS INSTALLATION Watermark 4 Stage

REVERSE OSMOSIS INSTALLATION Watermark 4 Stage REVERSE OSMOSIS INSTALLATION Watermark 4 Stage BRIEF TECHNICAL ASPECT OF THE WATER TREATMENT SYSTEM The Filter Systems Australia Water Treatment System utilizes a process called reverse osmosis (RO). As

More information

PRO SINK -R 1 and 2. Dilution system CONTENTS

PRO SINK -R 1 and 2. Dilution system CONTENTS PRO SINK -R 1 and 2 Dilution system CONTENTS 1.0 Product description 2 2.0 Warnings.. 3 3.0 Installation procedure 4 4.0 Plumbing connections 4 5.0 Technical features.. 5 6.0 Maintenance... 6 7.0 Troubleshooting......6

More information

Operation and Maintenance Manual for GENTEC Model 881VR Continuous/Intermittent Digital Suction Regulators

Operation and Maintenance Manual for GENTEC Model 881VR Continuous/Intermittent Digital Suction Regulators Operation and Maintenance Manual for GENTEC Model 881VR Continuous/Intermittent Digital Suction Regulators Genstar Technologies Co., Inc. 4525 Edison Avenue Chino, CA 91710 USA TEL 909-0-272 FAX 909-0-485

More information

WALL MOUNTED EMERGENCY EYE & EYE/FACE WASH HAND OPERATED

WALL MOUNTED EMERGENCY EYE & EYE/FACE WASH HAND OPERATED WALL MOUNTED EMERGENCY EYE & EYE/FACE WASH HAND OPERATED Installation, Operating & Maintenance Instructions EEE120 EFE300 I00097_Oct 17 NOTE: THIS DOCUMENT IS TO BE LEFT ONSITE WITH FACILITY MANAGER AFTER

More information

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM IMI CORNELIUS INC One Cornelius Place Anoka, MN 55303-623 Telephone (800) 238-3600 Facsimile (612) 22-326 INSTALLATION INSTRUCTIONS FOR INSTALLING CO 2 BLENDER KIT (P/N 111612000 IN BEER SYSTEM SECONDARY

More information

PEDESTAL MOUNTED EMERGENCY EYE & EYE/FACE WASH

PEDESTAL MOUNTED EMERGENCY EYE & EYE/FACE WASH PEDESTAL MOUNTED EMERGENCY EYE & EYE/FACE WASH Installation, Operating & Maintenance Instructions EEE180 EEE210 EFE360 EFE390 ENBE180 ENBE210 ENBE360 ENBE390 I00011_Apr 18 NOTE: THIS DOCUMENT IS TO BE

More information

Hydraulic Punch Drivers

Hydraulic Punch Drivers SERVICE MANUAL 7804SB / 7806SB Quick Draw 7704SB / 7706SB Quick Draw Flex Quick Draw Hydraulic Punch Drivers Serial Codes AHJ and YZ Read and understand all of the instructions and safety information in

More information

INSTALLATION INSTRUCTION & OWNER S MANUAL

INSTALLATION INSTRUCTION & OWNER S MANUAL INSTALLATION INSTRUCTION & OWNER S MANUAL System Tested and Certified by NSF International against NSF/ANSI 42 for the reduction of Chlorine, Taste and Odor and 58 for the reduction of Total Dissolved

More information

DS06D,G Dial Set Pressure Regulating Valve

DS06D,G Dial Set Pressure Regulating Valve DS06D,G Dial Set Pressure Regulating Valve PRODUCT DATA FEATURES APPLICATION Built-in, factory-calibrated outlet pressure adjustment dial. Noncorroding unitized cartridge contains all working parts and

More information

This Page Intentionally Left Blank 2

This Page Intentionally Left Blank 2 Reverse Osmosis User s Manual Model M2-4240, M2-6240, M2-8240, M2-10240, M2-12240 M2-12240 Pictured This Page Intentionally Left Blank 2 TABLE OF CONTENTS INTRODUCTION... 4 SAFETY... 4 FEED WATER AND OPERATION

More information

OPERATION MANUAL NTF-15

OPERATION MANUAL NTF-15 OPERATION MANUAL NTF-15 Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81235-00 (Rev B) TABLE

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION Installation, Operation, and Maintenance Balston Model 75-77 Nitrogen Generator Figure 1-75-77 Overall Dimensions These instructions must be thoroughly read and understood before

More information

Table of Contents. Operating Instructions. Resource v.2 Conserving Regulator

Table of Contents. Operating Instructions. Resource v.2 Conserving Regulator Operating Instructions Table of Contents Resource v.2 Conserving Regulator Safety Information Device Precautions Introduction Product Features Product Specifications Feature Illustrations Set Up Usage

More information

Technical Information

Technical Information Technical Information Installation, Operation, Installation, Operation and Maintenance and Maintenance Manual Manual Balston Model 75700-K728 Nitrogen Generator Figure 1-75700-K728 Overall Dimensions These

More information

Operating Instructions Models and Hydrostatic Test Pumps

Operating Instructions Models and Hydrostatic Test Pumps Operating Instructions Models 33100 and 33101 Hydrostatic Test Pumps 33100 DIMENSIONS: WEIGHT: PUMP: MOTOR: CONTROL: GAUGE: DISCHARGE HOSE: 16 (40cm) L x 22 (55cm) W x 18 (45cm) H 87 lbs., 39.5 kg Triplex

More information

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE INSTALLATION, OPERATION & MAINTENANCE MANUAL INTERFACE DEVICES, INC. 230 Depot Road, Milford, CT 06460 Ph: (203) 878-4648, Fx: (203) 882-0885, E-mail: info@interfacedevices.com

More information

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series Introduction Powerex manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists of a regulator

More information

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL 00, 0, 000 00, 000, 00 A. TECHNICAL INFORMATION Model 00 Inlet/Outlet " Air Inlet /" 0 / 000 /" /" 00 /" /" 000 /" /" 00 /" /" Flow Rate GPM/ 0LPM GPM/ 0LPM GPM/ LPM GPM/ LPM GPM/ 0LPM GPM/ 0LPM Maximum

More information

OPERATION MANUAL NTF-60 Plus

OPERATION MANUAL NTF-60 Plus OPERATION MANUAL NTF-60 Plus Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81264-00 (Rev A)

More information

HPB25 Hydraulic Paving Breaker

HPB25 Hydraulic Paving Breaker INSTRUCTION MANUAL HPB25 Hydraulic Paving Breaker Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. Register this product at www.greenlee.com

More information

Installation Guide & Owner s Manual. Model V4700. Water Filtration for Dental & Medical Instrument Washing Equipment

Installation Guide & Owner s Manual. Model V4700. Water Filtration for Dental & Medical Instrument Washing Equipment Installation Guide & Owner s Manual Model V4700 Water Filtration for Dental & Medical Instrument Washing Equipment Safety Guides & General Information Please read this manual completely before attempting

More information

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289 3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for

More information

MN-800-TF REVERSE OSMOSIS TREATMENT SYSTEM OWNERS MANUAL

MN-800-TF REVERSE OSMOSIS TREATMENT SYSTEM OWNERS MANUAL MN-800-TF REVERSE OSMOSIS TREATMENT SYSTEM OWNERS MANUAL Nimbus Water Systems 41840 McAlby Court, Suite A Murrieta, CA 92562-7036 800-451-9343 THE NIMBUS MN-800 TF REVERSE OSMOSIS TREATMENT SYSTEM TABLE

More information

Instruction & Parts Manual

Instruction & Parts Manual Large Capacity Spring Rewind Hose Reel Instruction & Parts Manual Model 88402 3/4 Hose Capacity Model 88402DEF 3/4 Hose Capacity Model 88403 1/2 Hose Capacity Model 88405 1 Hose Capacity P/N 88403-75L

More information

Yoke Block Instruction Manual

Yoke Block Instruction Manual Yoke Block Instruction Manual ! WARNING IMPORTANT: READ MANUAL COMPLETELY BEFORE OPERATING THIS DEVICE This manual contains instructions on periodically required checks to be performed by the user. These

More information

BioAerosol Nebulizing Generator. Operation and Maintenance User Manual

BioAerosol Nebulizing Generator. Operation and Maintenance User Manual BioAerosol Nebulizing Generator Operation and Maintenance User Manual INTRODUCTION The BANG or BioAerosol Nebulizing Generator is a unique nebulizer for the generation of aqueous aerosols at a low air

More information

BLS 1900 Optimum REVERSE OSMOSIS SYSTEM

BLS 1900 Optimum REVERSE OSMOSIS SYSTEM Installation, Operation, and Maintenance Manual BLS 1900 Optimum REVERSE OSMOSIS SYSTEM JANUARY 2019 Table of Contents 3. BLS Reverse Osmosis System Introduction 3. How Reverse Osmosis Works 3. Definitions

More information

OPERATING MANUAL LO-CROSS-FLOW CF M

OPERATING MANUAL LO-CROSS-FLOW CF M VA FILTRATION USA 110 Dodd Court American Canyon, CA 94503 Tel : (707) 552 2616 Fax :(707) 552 3871 Web : www.vafiltration.com OPERATING MANUAL LO-CROSS-FLOW CF8-2-200M January, 2017 TECHNICAL SPECIFICATIONS

More information

Operating Instructions Models and Hydrostatic Test Pumps

Operating Instructions Models and Hydrostatic Test Pumps Operating Instructions Models 46453 and 464530 Hydrostatic Test Pumps 46453 DIMENSIONS: 27 (67.5cm) L x 22 (55cm) W x 34 (85cm) H WEIGHT: 160 lbs. 73 kg PUMP: Twin piston: Positive displacement type Inlet

More information

Hydraulic Punch Drivers

Hydraulic Punch Drivers INSTRUCTION MANUAL 7804SB / 7806SB Quick Draw 7704SB / 7706SB Quick Draw Flex 7904SB / 7906SB Quick Draw 90 Quick Draw Hydraulic Punch Drivers Serial Codes AHJ, YZ, and ZA Read and understand all of the

More information

This Page Intentionally Left Blank 2

This Page Intentionally Left Blank 2 Reverse Osmosis User s Manual Model M1-4240, M1-6240, M1-8240, M1-10240, M1-12240 M1-12240 Pictured This Page Intentionally Left Blank 2 TABLE OF CONTENTS INTRODUCTION... 4 SAFETY... 4 FEED WATER AND OPERATION

More information

CSA Sample Draw Aspirator Adapter Operator s Manual

CSA Sample Draw Aspirator Adapter Operator s Manual 30-0951-CSA Sample Draw Aspirator Adapter Operator s Manual Part Number: 71-0367 Revision: 0 Released: 4/30/15 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

Operating Instructions Models and Hydrostatic Test Pumps

Operating Instructions Models and Hydrostatic Test Pumps Operating Instructions Models 36454 and 364540 Hydrostatic Test Pumps 36454 DIMENSIONS: 24 (61cm) L x 19 (48cm) W x 19.5 (50cm) H WEIGHT: 135 lbs 61.5 kg PUMP: Twin piston: Positive displacement type Inlet

More information

Installation Instructions

Installation Instructions Installation Instructions COLONY SOFT 7.0 Single Control Lavatory Faucet with Speed Connect Drain Congratulations on purchasing your American Standard faucet with the Speed Connect drain, a feature found

More information

D05 Pressure Regulating Valves

D05 Pressure Regulating Valves D05 Pressure Regulating Valves FEATURES PRODUCT DATA Noncorroding unitized cartridge contains all working parts and is easily replaceable. Includes built-in strainer and thermal bypass. Balanced seat construction

More information

Operating Instructions Model and Hydrostatic Test Pump

Operating Instructions Model and Hydrostatic Test Pump Operating Instructions Model 39300 and 39301 Hydrostatic Test Pump Dimension Weight Pump Style Capacity Pressure Motor Lubrication Control Gauge Inlet Connection Outlet Connection Discharge Hose Hose Ends

More information

Commercial RO CRO Series 2020 & 2436

Commercial RO CRO Series 2020 & 2436 Better Water LLC Commercial RO CRO Series 2020 & 2436 rev. Apr 2016 Better Water LLC. All rights reserved. The content of this manual is the intellectual property of Better Water LLC. It is furnished for

More information

Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia

Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia - 1-122.6010.6 These instructions describe the installation, operation and maintenance of the subject equipment. Failure

More information

GETZ EQUIPMENT INNOVATORS PART NO.: 9G59554 MODEL: MS 36 SC-R HYDROSTATIC TEST PUMP

GETZ EQUIPMENT INNOVATORS PART NO.: 9G59554 MODEL: MS 36 SC-R HYDROSTATIC TEST PUMP GETZ EQUIPMENT INNOVATORS PART NO.: 9G59554 MODEL: MS 36 SC-R HYDROSTATIC TEST PUMP LIMITED WARRANTY Getz Equipment Innovators warrants its products, and component parts of any product manufactured by

More information

COMPACT TRIPLE WALL OUTLET STATION MODEL INSTALLATION AND OPERATING INSTRUCTIONS

COMPACT TRIPLE WALL OUTLET STATION MODEL INSTALLATION AND OPERATING INSTRUCTIONS COMPACT TRIPLE WALL OUTLET STATION MODEL 6255-1 INSTALLATION AND OPERATING INSTRUCTIONS To assure safe operation and conformation to local fire codes, all Porter Outlet Stations are designed to be used

More information

ULTRA PURE SYSTEMS 400 GPD RODI INSTALLATION AND OPERATION MANUAL

ULTRA PURE SYSTEMS 400 GPD RODI INSTALLATION AND OPERATION MANUAL ULTRA PURE SYSTEMS 400 GPD RODI INSTALLATION AND OPERATION MANUAL Thank you for choosing UPS (Ultra-Pure Systems) for your RO/DI solution. We are confident you have made the right decision. This system

More information

Technical Service Bulletin June 2015 TSB122.06

Technical Service Bulletin June 2015 TSB122.06 Technical Service Bulletin June 2015 TSB122.06 Element Loading Guidelines This bulletin provides general information and guidelines for installing Hydranautics elements in order to provide optimally reliable

More information

Installation, Operation and Maintenance Manual for Back Pressure Regulator

Installation, Operation and Maintenance Manual for Back Pressure Regulator Installation, Operation and Maintenance Manual for Back Pressure Regulator Model 8860 2009 Groth Corporation IOM-8860 Rev. B 12541 Ref. ID: 95565 Page 2 of 13 Table of Contents I. INTRODUCTION 3 II. DESIGN

More information

Sterisil Ac+ Installation & Operating Manual

Sterisil Ac+ Installation & Operating Manual Sterisil Ac+ Installation & Operating Manual 719 622 7200 Sterisil.com Arbor Dental Associates 2 Table of Contents Introduction 4 Sterisil Ac + Features 5 Installation Instructions 6 Maintenance 10 Troubleshooting

More information

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED VULCAN 36RB 36IRB WOLF C36RB C36IRB This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not

More information

Installation of Your SprayMaster System

Installation of Your SprayMaster System Installation of Your SprayMaster System 1. At the installation site, remove all equipment from the corrugated box and the polyethylene drum and replace the drum lid. Check the picture to identify each

More information

Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h)

Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h) Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h) 100 PPD (2 kg/h) Maximum 250 PPD (5 kg/h) Maximum 500 PPD (10 kg/h) Maximum - 1-122.6006.9 These instructions describe the

More information

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1. 2 GALLON TWIN STACK AIR COMPRESSOR Model: 9526 DO NOT RETURN TO STORE. Please CALL 800-348-5004 for parts and service. CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or

More information

IMPORTANT PLEASE READ BEFORE COMMENCING INSTALLATION

IMPORTANT PLEASE READ BEFORE COMMENCING INSTALLATION IMPORTANT PLEASE READ BEFORE COMMENCING INSTALLATION This Fitting Guide is designed to assist in the Installation of your Reverse Osmosis System. Some of the parts that are supplied with each system may

More information

Accu-Tab PowerBase 3012AT by Axiall Corporation

Accu-Tab PowerBase 3012AT by Axiall Corporation Accu-Tab PowerBase 3012AT by Axiall Corporation Installation and Operating Instructions DANGER: DO NOT MIX CHEMICALS! The PowerBase 3012AT chlorinator system is designed for use with Axiall Corp. approved

More information

Installation Instructions

Installation Instructions Installation Instructions COLONY SOFT 7.0 Centerset Lavatory Faucet 7.0 with Speed Connect Drain Congratulations on purchasing your American Standard faucet with the Speed Connect drain, a features found

More information

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax:

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax: 2 Table Of Contents 1. Introduction 3 2. About this Manual 3 3. Contacting YZ Systems 3 4. Vessel Components 4 5. Specifications 5 6. Application 6 7. Theory of Operation 7 8. DuraSite Installation & Use

More information

Installation & Instruction Manual For Portable Series R.O. units:

Installation & Instruction Manual For Portable Series R.O. units: Installation & Instruction Manual For Portable Series R.O. units: Please read carefully before proceeding with installation *System components and appearance may vary from above image. REPLACEMENT AND

More information

INDUSTRIAL VALVES MODELS: C62-A; C62-D. INSTRUCTION MANUAL Installation Operation Parts Service DIAPHRAGM BYPASS PRESSURE REGULATING VALVES

INDUSTRIAL VALVES MODELS: C62-A; C62-D. INSTRUCTION MANUAL Installation Operation Parts Service DIAPHRAGM BYPASS PRESSURE REGULATING VALVES INSTRUCTION MANUAL Installation Operation Parts Service IMPORTANT Record your Regulator model number and serial number here for easy reference: Model No. Serial No. Date of Purchase When ordering parts

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION Installation, Operation, and Maintenance Balston 75-96 and 75-98 Nitrogen Generation System Tower Pressure Gauge 5'-1" 3'-6" 7'-4" 6'-10 1/2" PLAN VIEW Figure 1 - Balston 75-96 and

More information

Air Operated Hydraulic Pumping Systems to 50,000 psi

Air Operated Hydraulic Pumping Systems to 50,000 psi High Pressure Equipment Air Operated Hydraulic Pumping Systems to 50,000 psi PS-10: 10,000 psi PS-20: 20,000 psi PS-30: 30,000 psi PS-40: 40,000 psi PS-50: 50,000 psi PS-90: 90,000 psi High Pressure air

More information

LIBERTY and PATRIOT SAND FILTER SERIES INSTALLATION & OPERATION MANUAL. RX Clear Patriot Sand Filters

LIBERTY and PATRIOT SAND FILTER SERIES INSTALLATION & OPERATION MANUAL. RX Clear Patriot Sand Filters LIBERTY and PATRIOT SAND FILTER SERIES INSTALLATION & OPERATION MANUAL RX Clear Patriot Sand Filters 8 Tank 12 Tank 16 Tank 22 Tank 24 Tank MLA-F91-PS08 MLA-F91-PS12 MLA- F91-PS16 MLA-F91-PS22 MLA-F91-P24

More information

DRAFT Standard Operating Procedure Ultrafiltration and Reverse Osmosis

DRAFT Standard Operating Procedure Ultrafiltration and Reverse Osmosis DRAFT Standard Operating Procedure Ultrafiltration and Reverse Osmosis R.Cox 8-2016 Safety Equipment Description R.O Membrane Specifications UF Membrane Specifications Startup Checklist Reverse Osmosis

More information

PRODUCT SERIES: A-SF-3000BD

PRODUCT SERIES: A-SF-3000BD CONTINENTAL NH3 PRODUCTS INSTALLATION, OPERATION, REPAIR AND MANTINANCE INSTRUCTIONS PRODUCT SERIES: A-SF-3000BD ATTENTION: Please follow all of the instruction in this manual carefully and read the entire

More information

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS READ ALL INSTRUCTIONS PRIOR TO INSTALLATION AND OPERATION TO AVOID POSSIBLE INJURY Warning: Always consider any accumulator to contain pressure until proven

More information

SERVICE MANUAL MODEL BA600AMST-S1 BREATHING AIR PANEL

SERVICE MANUAL MODEL BA600AMST-S1 BREATHING AIR PANEL SERVICE MANUAL MODEL BA600AMST-S1 BREATHING AIR PANEL WARNING: Do not attempt to operate this equipment without first reading and understanding the service manual enclosed with this device. 2/05 GENERAL

More information