SECTION BIOLOGICAL TREATMENT SYSTEM FUNCTIONAL DESCRIPTIONS

Size: px
Start display at page:

Download "SECTION BIOLOGICAL TREATMENT SYSTEM FUNCTIONAL DESCRIPTIONS"

Transcription

1 SECTION BIOLOGICAL TREATMENT SYSTEM FUNCTIONAL DESCRIPTIONS PART 1 GENERAL 1.1 DESCRIPTION A. Definition: 1. This Section describes the control philosophy and control system approach for the new Upper Hocking Water Pollution Control Facility, in regards to the biological treatment system (BTS) and its interaction with other processes at the plant. Included in this Section are monitoring requirements, scenario-based control capabilities, expected hardware capabilities, Operator Interface Terminal (OIT) display functions, and data logging requirements. 2. Control System Configuration: The Upper Hocking Water Pollution Control Facility programmable logic controllers (PLCs), human-machine interface (HMI), and OIT components shall be as shown on the Control System Configuration Diagram, with input and output signals as listed in the schedule at the end of Specification Schedule B. Related Sections: 1. Section 11010, Biological Treatment System General Provisions. 2. Section 11011, Membrane Bioreactor System. 3 Section 11012, Process Aeration Equipment. 4. Section 11013, Residuals Reduction System. 5. Section 11014, Sodium Hypochlorite and Citric Acid Feed Equipment. 6. Section 11015, Compressed Air System. 7. Section 11016, Filtrate Pumps. 8. Section 11017, Biological Treatment System Valves. 9. Section 11018, Biological Treatment System Instrumentation. 10. Section 11019, Biological Treatment System Controls, Interface, and Hardware. 11. Division 13, Applicable Sections on Instrumentation and Controls. C. This Section describes the minimum anticipated control programming that shall be provided by the biological treatment system Supplier in order to provide a fully functional system. Additional functionality may be required to provide a completely operable system and to meet the specific requirements of this installation and shall be provided by the biological system Supplier at no additional cost. The specific procedures, modes, setpoints, durations, etc. may be amended to optimize and customize the system operation upon approval of the Engineer /15/2008 4:36:52 PM

2 1.2 SUBMITTALS: A. PLC and OIT Application Software Documentation: Prepare and submit one electronic and five (5) hard copies of preliminary software documentation two (2) weeks prior to expected initiation of factory testing as specified herein and at each application programming review meeting. Electronic copy shall be in CD-R format. Submittal shall be for review and comment only and not be subject to formal approval action. Software documentation shall include the following as a minimum: 1. Complete electronic and hard copy printouts of OIT screen displays. Provide documentation for each display identifying configuration parameters, dynamic symbols with controlling elements, and operator adjustable values. 2. Complete electronic and hard copies of PLC listing of external and internal I/O address assignments, register assignments, and preset constant values. Also list all unused/undefined I/O and data table registers available. B. Operations and Maintenance Manuals: 1. Provide one electronic and three (3) hard copies of O&M manuals for the PLC and OIT application program in accordance with the requirements below. The O&M manuals shall include the following: a. Name, address, and telephone number of the BTS Supplier and each software manufacturer s local service representative. b. Copy of all approved submittal information as specified herein with corrections made to reflect all review comments and the actual system as tested and delivered to the site for installation. c. Standard technical documentation covering the procedures for programming, start-up, and shutdown of the PLC equipment including instruction set descriptions and programming procedures. d. The O&M Manuals shall conform to the requirements of Section 01781, Operation and Maintenance Data. e. The O&M Manuals shall include electronic and hard copy of the final software documentation. 2. Final versions of OIT screens, in the file formate readable by the OIT software language shall be made available on CD to the Owner, so that the Owner s designated programmer can incorporate the BTS graphics into the main HMI display. C. Application Programming Review Meetings: 1. Application programming review meetings shall be scheduled by the Engineer. Contractor and of representative of the BTS Supplier shall be required to attend a minimum of 2 meetings at the Owner s site. 2. The BTS Supplier shall provide five (5) color printouts/copies of the OIT graphics and other relevant deliverables to be discussed. The BTS Supplier shall provide the color printouts/copies to the Engineer and /15/2008 4:36:52 PM

3 Owner five (5) business days prior to the review meeting in which the material is discussed. 3. The purpose of the meetings shall be to insure that the PLC and OIT programs are in compliance with the intent of the specifications, and to allow the Owner to modify proposed screen graphics to match Owner s preferences. 4. Representatives at the meeting shall have the competence and authority to make any and all necessary decisions. Decisions and statements made at the meetings shall commit the Contractor and BTS Supplier to agreed procedures and schedules. 1.3 REQUIREMENTS A. The following points are necessary for successful integration of the control system with the plant. 1. Provide PLC programming and network configuration necessary to communicate to and from the various process equipment PLCs, drives, and other networked equipment. 2. Setpoints, alarm limits, timer ranges, and other values specified herein shall be for initial setting and use. These values shall be adjusted during field start-up to coordinate with actual equipment operating conditions. 3. All digital and analog inputs as listed in the Input/Output Schedule in Section (equipment on Network A ) shall be displayed on one or more process graphic displays. Other signals referred to in this document or necessary in the program but retrieved from the Network B PLC shall also be displayed the graphic displays. 4. All operator entered setpoints shall be tested for appropriate range both at the HMI entry field and in the PLC. The HMI shall flag any setpoint that is out of range and prompt the operator to enter a valid number. The PLC shall not accept any setpoint that is out of range. 5. The PLC shall generate a Fail to Run alarm if the PLC calls for any motor to run and running feedback is not received within 10 seconds. The alarm shall be annunciated at the HMI and the OIT. 6. The PLC shall generate a Fail to Open or a Fail to Close alarm if the PLC calls for any non-modulating valve or gate to operate and position feedback is not received within 125% of the full travel time. The alarm shall be annunciated at the HMI and the OIT. 7. The PLC shall generate a Position Deviation alarm for modulating valves and gates if the position feedback differs from the position control output by more than 5% for more than 60 seconds. The alarm shall be annunciated at the HMI and the OIT. 8. The PLC shall not generate a command output to any process equipment that is not controllable from the PLC (equipment not in Remote mode or in alarm). 1.4 GENERAL CONTROL PHILOSOPHY /15/2008 4:36:52 PM

4 A. Control System Description: 1. The Biological Treatment System Control System shall consist of the following components: a. A main control panel (Biological Treatment System Control Panel) which houses PLCs, additional I/O racks, and an OIT. This control panel shall be located in the Secondary Control Building Control Room. b. An additional control panel (Biological Treatment System Remote I/O Panel) which houses I/O racks, an OIT, and some relay logic functions for the RAS Screen and Compactor. This control panel shall be located in the Screening and Dewatering Building Electrical Room. c. A control panel located in the Residuals Reduction Tunnel, although provided under Division 13, contains remote I/O racks dedicated to the Biological Treatment System and is a node on the BTS network. 2. The control panels provided under Section also house an additional PLC, as well as additional remote I/O racks. This is depicted on the Drawings as Network B. The additional equipment shall not be programmed by the Biological Treatment System Supplier; rather, the Owner s designated programmer is responsible for programming this equipment. It is on a separate network from the BTS PLC. 3. The PLC shall be configured to operate all equipment manually or automatically based on monitored data, commands, and setpoints entered by operators at the OIT or SCADA system. All equipment shall also be controlled locally from the corresponding Variable Frequency Drive (VFD), actuator, or local control station. 4. The OITs shall provide detailed, user-friendly information on all equipment, and shall allow the operator to initiate process changes, alter setpoints, and respond to alarm conditions. 5. The PLC system shall be programmed to be standalone. The PLC shall control the attached equipment even in the event that communications with the OIT are severed. In such a case, the PLC shall control the BTS based on the most recently entered setpoints. B. Local Control Mode: 1. All equipment shall have local manual control capability at or near the equipment. This shall allow operators to use the equipment for testing, maintenance, and other such purposes. 2. Equipment relevant to the primary process (i.e. Filtrate Pumps, RAS Screen, etc.) shall be installed with Local-Off-Remote selector switches (provided under Division 16) to denote control location. If the switch is in the Local position, local manual control is enabled and PLC control is disabled. If the switch is in the Off position, the equipment shall not operate /15/2008 4:36:52 PM

5 C. Remote Control Mode: 1. Equipment with selector switches in the Remote position shall have an additional layer of control if the equipment is VFD driven. a. A VFD/PLC selector switch on the VFD determines whether control shall be from the VFD machine interface, or remotely from the PLC. b. Stop functionality shall be available at the VFD in any mode. 2. Equipment powered from the MCC for the BTS process shall be controlled by the PLC when the selector switch is in the Remote position. 3. Equipment under the control of the PLC can either operate in a completely automatic manner, PLC-Auto, or manually via operator input to an OIT or OIT screen, OIT-Manual. a. OIT-Manual Control: This mode of operation requires operator action at the OIT to change the operating status of pieces of equipment. Buttons located on the graphic displays shall allow for starting, stopping, changing speed, and other such functionality. Equipment safety interlocks shall be provided when in manual mode. For example, the PLC shall not allow pumping into a closed valve for an extended period of time, or to draw from an empty wet well. b. PLC-Auto Control: This mode of operation allows the PLC to control equipment based upon measured process variables, operator adjustable and fixed internal setpoints, and the selected control schemes. PART 2 PROCESS CONTROL DESCRIPTIONS 2.1 VERTICAL LOOP REACTORS A. Influent Feed to VLRs: 1. The influent flow to the VLR is controlled by the VLR Influent Control Valve. This valve is automatically controlled by the Network B PLC, and is used to limit the flow to the VLRs to below 6 MGD. A PID control algorithm maintains the flow setpoint and will be programmed by the Owner s designated programmer. a. The operator is permitted to assign a flow setpoint below 6 MGD. b. Interlocks will be performed between the valve and downstream equipment to stop flow upon alarm conditions. This data shall be coordinated between BTS programmer and Owner s designated programmer. 2. The flow rate is monitored by the Network B PLC, and this data will be made available to the BTS PLC through a network PLC. B. VLR Blowers: /15/2008 4:36:52 PM

6 1. If the DO and ORP setpoints in the VLR tanks can be maintained by the disc aerators alone, then the PLC shall shut off the VLR Blowers. If oxygen supplied by the disc aerators alone is not adequate to achieve the desired DO and ORP setpoints in the VLR tanks, then the VLR Blowers shall be switched on as required. 2. When the VLR Blowers are operating, the number of blowers in service and the speed of the blowers shall be automatically controlled via a PID algorithm to maintain the pressure in the common blower manifold within a pre-selected deadband. 3. The VLR Blowers Operating Procedure: a. The first blower in operation adjusts its speed to maintain a pressure setpoint within the common header. As the pressure drops, the blower shall increase in speed. Should the pressure demand push the blower to 100% speed for a short time, a second blower shall start. b. The first blower shall maintain 100% speed until the second blower reaches a point at which the pressure meets the setpoint. At this stage, both running blowers shall match speed as they attempt to maintain the pressure. c. The same process as described in parts a and b shall be used to start a third blower. d. If the pressure builds too high, the blowers shall slow down. Once they have reached a predetermined speed, the first one that was started shall stop. The remaining running blowers shall then ramp back up to maintain the pressure. This shall continue until the pressure has been met. e. Every time no blowers are running, and one is required to start, the one that was started the longest time ago shall start first. Provisions shall be created on the OIT screens to make changes to this system for customization purposes. C. Aeration Discs: 1. The PLC shall automatically vary the speed of the Aeration Discs to maintain the desired DO and ORP setpoints in each VLR tank. 2. The PID loop governing the Aeration Discs shall be dampened so that it does not interfere with the VLR Blower controls. D. VLR Air Flow Control Valves: 1. When the VLR Blowers are running, the position of the VLR Air Flow Control Valves shall be varied to control DO and ORP. The valves shall be limited to opening at pre-defined settings, rather than infinitely variable. 2. The PID loops for VLR Air Flow Control Valves and Aeration discs are cascaded. 2.2 MEMBRANE BIOREACTORS /15/2008 4:36:52 PM

7 A. General: 1. Modes of Operation: a. Online: The Membrane Tank can begin the filtration process. b. Offline: The Membrane Tank has been shutdown or a Clean-in- Place (CIP) is in operation. 2. Tank Rotation Membrane Tanks shall automatically be placed in service based on the flow conditions described in one of the following sections. When flow drops down in the system, all available Membrane Tanks will not be required for filtration and Membrane Tanks shall be rotated. Methods are: a. Last On, Last Off: If a Membrane Tank enters a maintenance clean, clean in place, or standby, or if the system enters Shutdown, the tank that has been in standby for the longest shall come online when a tank is required by the system for filtration. b. Caterpillar: When a Membrane Tank goes into relaxation another Membrane Tank shall start filtration if there is a tank in standby. 3. Tank Prioritization The prioritization of different operating states in the membrane operating system is required due to the use of the filtrate pipe work for multiple purposes. a. Relaxation: If a Membrane Tank is requesting relaxation it shall enter this before any other operations. b. CIP Fill / Filtrate Clean Water: If a Membrane Tank is empty and requesting to fill from other tanks then it will start after relaxation has completed. c. Recirculation Turbidity: If a Membrane Tank is requiring to go into recirculation due to a turbidity spike this shall occur after a CIP Fill request is completed. Relaxation on other tanks has no effect on this request. d. Maintenance Clean: The Maintenance Clean shall be delayed until CIP Fill, Recirculation Turbidity, and Recirculation CIP are completed. If Relaxation occurs on another tank then the timer shall continue after Relaxation is completed. e. Recirculation Storage in Place (SIP): If the Membrane Tank is requesting to perform the weekly recirculation or initial recirculation for SIP, it shall be queued behind all other tasks. Relaxation on the other tanks has no effect on this request. 4. Manual Entry The Membrane Operating System shall have nine manual push buttons (on OIT screen) per Membrane Tank that can be initiated by the operator. The operator can press buttons whether the membrane is in the online or offline state. The PLC shall automatically check that the necessary resources are available before the required sequence is initiated: a. Offline: This shall shutdown everything associated with the Membrane Tank including the Membrane Feed Pump and the Membrane Blower /15/2008 4:36:52 PM

8 b. Filtration / Start-up: If the Membrane Tank is standing by or shut down, this shall make the tank available for service. c. Clean in Place: Places the Membrane Tank into CIP by the operator. The CIP sequence shall then proceed automatically after resources are available. d. Maintenance Clean (MC): Maintenance Clean is an automatic operation but the operator can perform a manual MC by using this pushbutton. e. Extended Relaxation / Standby: The operator can be manually place the Membrane Tank in this mode, which shall take the tank offline. f. Draindown Rinse: The operator can manually drain down the Membrane Tank for maintenance. g. Storage in Place: Used to protect and prepare the Membrane Tank for extended periods of low flow. The SIP sequence shall then proceed automatically when resources become available. h. Clean Water Fill: Used for bubble tests, maintenance, and removal of the membrane modules. It shall run through a Draindown Rinse and Filtrate Fill, which is described in the next section. i. Recirculation: Used for manually putting a Membrane Tank into a recirculation loop, drawing water through the membranes and being discharged from the Filtrate Pump back into the tank. 5. Online Operating States: a. Standby / Extended Relaxation: Standby is an active state that a Membrane Tank enters from Filtration when: 1) The plant incoming flow is low and the Filtrate Pump cannot run below the minimum speed required for continuous operation. 2) The mixed liquor level in the tank is below a minimum set level. 3) A low mixed liquor feed flow alarm has been activated. A warning alarm shall be an operator entered setpoint. 4) If the Membrane Tank is filtering and the transmembrane pressure exceeds the preset value for a preset time. A shutdown alarm shall be set. 5) A low air flow / pressure alarm is activated. A warning alarm shall be set for this. 6) Placed in Standby manually. The Membrane Tank shall then remain in Standby Manual until it is manually restarted or is shut down. If restarted, the tank shall enter Fixed Filtration then Filtration. a) The Membrane Feed Pump and Membrane Blower run continuously when in Standby less than 24 hours. b) The Membrane Feed Pump and Membrane Blower run 10 minutes every hour when in Standby between 24 and 36 hours /15/2008 4:36:52 PM

9 c) The Membrane Feed Pump does not run, and the Membrane Blower runs 10 minutes every hour when in Standby over 36 hours. 6) When the demand increases due to incoming water, the Membrane Tank shall change from Standby and enter Startup if the system did not enter Standby because of alarm. If a tank has been put into Standby because of alarm, it must be cleared and manually put back into Startup by the operator. b. Startup: When the membrane system is started, the PLC shall control the start-up sequence. In Startup, the Membrane Feed Pump is called to run and the Membrane Tank is filled until the level in the membrane weir overflows. The vacuum system then primes the modules and filtrate piping in preparation for filtration. Once the Filtrate Pump is primed, it will start and the tank enters Fixed Filtration. c. Filtration: Filtrate is drawn from the Membrane Tank through the membrane by suction pressure. Particles that do not enter the membrane fibers overflow the tank and re-enter the Vertical Loop Reactors. The measured suction pressure required to draw the necessary flow through the membranes is the trans-membrane pressure (TMP). The TMP gauges the fouling on the membrane surface. The membrane system flow control is as follows: 1) The Filtrate Pump flow rate for each tank is based upon the number of tanks online and the level in the VLR wet well. Tanks are unavailable for filtration if they are: a) In Standby Manual mode. b) In Offline mode. c) In Shutdown Alarm mode. d) In Maintenance Clean mode. 2) On completion of the Startup sequence, the membrane system enters Fixed Filtration. In this mode, the Filtrate Pump ramps to a predetermined position based on the previous cycle VFD setting and maintains this speed for a preset duration. This allows filtrate flow to stabilize close to the flow set point before starting proportional control. 3) The membrane system enters Filtration Initialize ones the Fixed Filtration period ends. During this mode, the Filtrate Pump maintains the level in the VLR wet well. The PLC shall monitor filtrate flow, TMP, and VLR wet well level for a set period to provide an initial filtration reference point for these variables. The reference point determines when another Relaxation or CIP is required. 4) Normal Filtration mode consists of controlling the Filtrate Pump to maintain the VLR wet well level. d. Relaxation: Relaxation of the membrane fiber is used to remove caked solids accumulated during Filtration. The Filtrate pump shall /15/2008 4:36:52 PM

10 stop while the Membrane Blower and Membrane Feed Pump continue to run. Relaxation cycles on for 60 seconds for every 12 minutes of Filtration when flow conditions are at or below the maximum sustained flow. For flows above the maximum sustained flow, the Relaxation duration is 30 seconds every 6 minutes of Filtration. These parameters are default but shall be field adjustable. 1) Only one Membrane Tank should be in Relaxation at one time. This control is implemented to remove false variations in VLR wet well level due to multiple Membrane Tanks relaxing at the same time. 2) Membrane tanks are queued for Relaxation. The membrane requests a Relaxation period through the PLC program, and it is required that no other tanks are in Relaxation, and no Shutdown Alarm is present. Membranes shall continue in Filtration until the option to enter Relaxation is available. e. Maintenance Clean (MC): 1) Maintenance Clean provides interim disinfection of the membrane modules and filtrate piping, useful to control biological growth and membrane fouling. The MC is a fully automated backwash and aeration cycle. When a MC is performed the tank is in Standby with the Membrane Feed Pump and Membrane Blower still flowing into the tank. For initiation of MC, the required number of tanks for the flow shall be available for service. This allows maintaining throughput while performing an MC. Steps of a cycle are as follows: a) The Filtrate Pump is called to run while dosing Sodium Hypochlorite for 5 minutes. b) A 15 minute Relaxation. c) The Filtrate Pump is called to run while dosing Sodium Hypochlorite for 5 minutes. d) A 15 minute Relaxation. e) Recirculation. f) Filtration begins again. 2) Maintenance Clean Request and Resources: An automatic MC request is set by the PLC as part of the program. This is an adjustable parameter with a default of 7 days of Filtration. An MC can be started manually by the operator. An automatic MC shall also occur following a peak event, when the flow drops below the maximum sustained flow. The following is required before initiating an MC: a) No high flow warning is present. b) No Shutdown Alarm present. c) The VLR is above the Start MC or CIP fill level (also an adjustable parameter) /15/2008 4:36:52 PM

11 d) Total filtrate flow from the plant is greater than required for MC with one tank out of service. If not, the filtrate flow on the on-line Membrane Tanks shall be forced to the flow required. e) Sufficient Membrane Tanks are in service so that the peak flow rate for an individual tank is not exceeded. f) No other Membrane Tank is in MC, CIP Fill, or Drawdown Rinse. 3) Maintenance Clean Sodium Hypochlorite Transfer Pump: The dosing pump shall start automatically. The pump shall be available to run when: a) The PLC is functional. b) The chemical storage tank is above the low level setpoint. c) The tank about to MC is not in Shutdown Alarm mode. f. Recirculation High Turbidity: If high turbidity is alarmed, the Membrane Tank with the high turbidity shall automatically go into recirculation per priority level. The Recirculation mode shall pull filtrate through the membranes and back to the Membrane Tank instead of the discharge line. The PLC continues to monitor turbidity. When the turbidity is within allowable limits for a preset amount of time, the system transfers back into Filtration mode. If the filtrate stays above limits for a preset amount of time, the Membrane Tank shall shutdown. If another tank is available, the PLC shall bring it online. g. Recirculation Tank Startup: At the end of an MC or CIP the system shall step through a Recirculation mode to remove any residual chemicals in the membranes and filtrate lines. The Recirculation mode pills filtrate through the membranes and back into the Membrane Tank instead of the discharge line. The PLC shall close a valve isolating the turbidimeter during this procedure to protect the instrument from corrosion. At the end of this step the program continues with MC, CIP, or enters Filtration. 6. Offline Operating States: a. Shutdown Alarm: If this mode is achieved, the Membrane Tank stops the process. The tank cannot be started until the alarm condition is rectified and the Shutdown Alarm has been reset. b. Draindown and Rinse: Draindown and Rinse needs to be performed for inspection and maintenance of membrane and associated pipework, as part of CIP sequences or as part of Bubble Test. 1) Primary Operation: a) The tank drain valve opens allowing liquid to drain to the Plant Drain Wet Well. b) The tank is filled with filtrate from the common discharge header using the Filtrate Pump. c) The Membrane Blower runs for a preset period of time /15/2008 4:36:52 PM

12 d) The tank drain valve opens again allowing liquid to drain to the plant drain wet well. 2) Manual Draindown Rinse (DDR): The DDR can also be initiated manually by the operator if the Membrane Tank is Offline. In this case, the DDR sequence is normally used prior to removing module racks from the tank, placing the tank into SIP mode, or for inspection or maintenance of other tank components. 3) Draindown Rinse Completion: At the end of the DDR, a screen shall appear on the OIT, prompting the operator if another DDR is required. If Yes is selected, then another DDR shall be performed. If No is selected, then the PLC shall carry out the next step in the sequence. After 5 minutes of inactivity, the PLC will consider the selection to be No. 4) Draindown Rinse Resources, CIP: Before a DDR takes place as part of CIP, the PLC shall ensure that all resources are available. See the following sections. 5) Draindown Rinse Resources, Single: For DDR as a single sequence, the following conditions shall be present: a) No High Flow Warning Alarm. b) No Shutdown Alarm c) VLR wet well is above the Start DDR level (field adjustable) d) Total filtrate flow from the plant is greater than required for Membrane Tank fill. If not, the filtrate flow on the online tanks should be forced to the flow required. e) Sufficient Membrane tanks are in service so that the peak flow rate for an individual tank is not exceeded. f) No other Membrane tanks are in CIP Fill, MC, or DDR. 6) Draindown Rinse Scheduling: If the DDR Resource is not immediately available when the request is initiated, the Membrane Tank continues in normal operation cycles. Once the DDR commences, Draindown and Rinse shall appear in the OIT display. If the DDR is halted and unable to fill with filtrate so that the membrane modules are exposed to air for a set period of time, the tank shall be filled with mixed liquor automatically. c. Filtrate Fill: The Filtrate Fill sequence follows directly after the Draindown Rinse when a clean water fill is initiated. 1) Primary Operation: a) The Membrane Tank shall fill from the common discharge header using the Filtrate Pump until the level is at the top of the membrane header. b) The Membrane Blowers are turned off. 2) Filtrate Fill Required Resources: /15/2008 4:36:52 PM

13 a) Total filtrate flow from the plant shall be greater than required for Membrane Tank fill. If not, the filtrate flow for the online tanks shall be forced to the required flow. b) Sufficient Membrane Tanks are in service so that the peak flow rate for an individual tank is not exceeded. c) No other Membrane Tank is in CIP Fill. d. Bubble Test: The Bubble Test is used to assist in the detection of leaks within a Membrane Tank. This procedure is a manual operation, and the operator first places the tank in Offline mode. 1) The operator then presses the Clean Water Fill push button. 2) A Draindown Rinse is automatically initiated. 3) A Filtrate Fill follows the Draindown Rinse. 4) Low pressure air is used to drain the membrane fibers of liquid. The test air remains on for the duration of the test period. 5) If the TMP exceeds 9 psig, the Membrane Integrity Test Solenoid Valve shall close. e. Clean in Place: Cleaning is necessary to remove the contaminants that cannot be removed by Relaxation. 1) General: a) The OIT prompts the operator for the type of cleaning that shall be performed Sodium Hypochlorite, Citric Acid, or both. When both are selected, Citric Acid is used first. b) The OIT prompts the operator what action the membrane should take once the CIP has finished either Storage in Place or Online. c) If the influent flow is high enough, the PLC shall put another tank online if one is available for service. 2) Clean in Place Request: OIT displays a warning alarm when a CIP is required. This may happen if any of the following conditions occur: a) A preset maximum filtration time has been reached. b) The permeability of the membranes has decreased to a preset minimum value. 3) Clean in Place Required Resources: The CIP Request shall be set when the operator manually initiates a CIP after ensuring that there is the appropriate amount of downtime available for the CIP. Before the CIP, the PLC determines if the following is available: a) The filtrate discharge flow rate is greater than the flow rate required for a CIP fill. The filtrate flow rate is greater than 980 gpm. b) The influent flow is at a rate that can be managed by the other tanks. c) There is sufficient chemical available to perform the CIP. d) The VLR wet well is above the Start CIP Fill Level. e) No shutdown alarms are in action /15/2008 4:36:52 PM

14 3) Clean in Place Cycle: The CIP cycle runs through the steps automatically. During a CIP, all of the steps and time to completion shall be displayed on the OIT. Steps are as follows: a) A Draindown Rinse is performed. b) Once able to proceed, the tank is filled with filtrate from the tanks online using the Filtrate Pump. At the same time, chemical is dosed directly in the CIP fill line, mixing with the filtrate to produce the desired concentration. c) The CIP solution is recirculated through the membranes via the Filtrate Pump and back into the Membrane Tank in CIP mode. d) The membranes are soaked in cleaning solution, which is timed and can be extended to improve cleaning efficiency. e) The soak is divided into blocks of time typically 20 minutes with aeration and soak cycles. For the acid clean, the system aerates the membranes to mix chemical for 5 minutes (adjustable) with 15 minutes of soak. This process is repeated until the end of the soak time. For Sodium Hypochlorite cleaning, the system does not require aeration, but it shall be an option selectable from the OIT. f) Soak time is calculated based upon the water temperature, input from the discharge temperature transmitter. The minimum soak time is three (3) hours. The soak time can be extended if desired by updating a parameter on the OIT display for the particular Membrane Tank. g) At the conclusion of the soak, the Membrane Tank drain valve opens and the wasted CIP solution is discharged to the Plant Drain Wet Well. An alarm is highlighted on the OIT that waste is currently being discharged. h) If the Membrane Tank is entering storage next, the program automatically changes to a Storage in Place. i) If the membrane is coming back online, a rinse sequence is performed. The Membrane Tank is filled and continuously fed with mixed liquor feed and the Membrane Blower is used to remove any remaining chemical residuals. j) Upon restarting the system, the Membrane Tank is placed into Filtration Recirculation. The Filtrate is returned to the tank and not discharged. k) If both chemicals are used to clean, then a Draindown Rinse is completed with includes 10 minutes of recirculation to remove acid residual /15/2008 4:36:52 PM

15 l) On completion of the CIP cycle, the Membrane Tank shall enter Standby and enter Filtration when required. 3) Clean in Place Halt: If a CIP cycle is stopped before completion, the Membrane Tank enters CIP Halt mode. The PLC retains all current timing information and program step numbers. Halts occur if any of the following occur: a) A valve failure for the Membrane Tank being cleaned. b) A chemical transfer pump fails. c) If CIP flow is not available to fill Membrane Tank during the fill procedure. d) A shutdown alarm occurs. e) The operator manually initiates CIP Halt. f) Power Failure. g) Emergency Stop activated. 3) Clean in Place Resume: When a shutdown alarm is present, the tank shall be placed in Shutdown Alarm mode. To resume a CIP cycle from CIP Halt mode, the following is required: a) The membrane should be in CIP Halt mode with alarms reset. b) There are no CIP system alarms. 4) Clean in Place Waste Disposal: a) The CIP chemical solution shall be drained to the Plant Drain Wet Well and shall be metered back to the VLR by the Membrane Tank Drain Pump. Prior to the chemical drain the wet well will be pumped to the low level using the Plant Drain Pumps, controlled by the Network B PLC. The Membrane Tank Drain Pump shall start upon indication that the Membrane Tank Drain Pump Influent Valve is open. b) The Membrane Tank Drain Pump shall be initiated by the chemical drain procedure. Other drains around the plant, as well as the DDR drain procedure, shall be pumped by the Plant Drain Pumps. No other CIP should be initiated until the Plant Drain Wet Well reached the low level. 5) Chemical Transfer Pumps: The pumps associated with the chemical transfer to the Membrane Tank are piped into the CIP Fill line for in-line dosing. The dosing pump starts automatically, for a preset period of around 20 minutes. Chemical transfer pumps are as follows: a) NaOCl Metering Pump 1. b) NaOCl Metering Pump 2. c) Citric Acid Metering Pump 1. 6) Sodium Hypochlorite Metering Pump Operation: The transfer pump is permitted to operate at any time that: a) The PLC is running. b) The Membrane Tank is not in Shutdown Alarm mode /15/2008 4:36:52 PM

16 7) Citric Acid Metering Pump Operation: The transfer pump is permitted to operate at any time that: a) The PLC is running. b) The Membrane Tank is not in Shutdown Alarm mode. c) The Citric Acid Storage Tank is above the low level setpoint. e. Storage in Place: Storage in Place (SIP) function is used to protect a Membrane Tank during periods of low flow. The SIP can be a standalone function or performed at the end of a CIP. 1) General Operation: The sequence drains the tank using the Draindown Rinse function. The following then takes place: a) The tank is filled with discharge filtrate using the Filtrate Pump. b) The dosing pump shall run for 5 minutes to give a low concentration of chlorine as the water flows into the Membrane Tank. c) The filtrate shall be recirculated through the membranes back into the Membrane Tank for 20 minutes. d) The valves to the Membrane Tank are closed. e) The PLC runs a recirculation loop once per week for 20 minutes. 2) Storage in Place Request: An SIP Request is set when the operator selects Storage in Place on the OIT or selects Storage Following CIP. 3) Storage in Place Resources: The resources required to start an SIP cycle include the following: a) The filtrate discharge flow rate is greater than the flow rate required for a CIP fill. b) The influent flow rate is at a rate that can be managed by other Membrane Tanks that are Online. c) No shutdown alarms are active. 4) Storage in Place Auto Restart Requirements: As the influent flow is subject to both seasonal and diurnal flow there may be a time when one or two Membrane Tanks are in SIP at the start of a peak event. In order to manage flow, tanks in SIP may be automatically brought back online if required. The requirements to bring online a membrane in SIP include the following: a) The filtrate flow rate of Membrane Tank(s) in service is at peak hourly flow rate; and b) The VLR wet well level transmitter is at the HI-HI level setpoint. 5) Storage in Place Auto Restart Sequence: The Membrane Tank returning to service shall run through the following procedure: a) The Membrane Tank is filled and continuously fed mixed liquor, to dilute the chemical solution /15/2008 4:36:52 PM

17 b) The Membrane Blower is started. c) The Membrane Tank is placed into Filtration Recirculation, the filtrate is returned to the tank and not discharged. d) After 10 minutes of recirculation the discharge valve is opened and normal Filtration commences. B. Flow Control: 1. The Membrane Operating System is started automatically by a start signal from the PLC. Once started, is shall operated automatically under the control of the PLC. No operator input is required for control of Filtration and Relaxation cycles and the Biological System PLC shall automatically adjust its operation to suit the incoming flow and the level in the VLR wet well. 2. Membrane Start Sequence: The MOS is only available for starting when: a. The main power is ON. b. PLC communications are OK. c. Liquid levels in the VLR are OK. d. Membrane Blowers are available. e. Membrane Feed Pumps are available. f. No shutdown alarms are present. 3. A Membrane Tank is placed in Auto Mode after Standby Mode will automatically enter Startup and go directly to Online Mode when required by the PLC. The operations of Membrane Tanks are as follows: a. The Membrane Tanks shall be called to service as required by the level in the VLR wet well. When a Membrane Tank is requested, the tank that has been offline for the longest period shall be called to run in a Last On / Last Off configuration. The Membrane Tanks shall operates as generally shown in the Table below. # of Cells in service Min. Flow Filtrate Pump Flow (gpm) Max. Sustained Flow Max 3 day sustained Flow Min. Flow Influent Flow (MGD) Max. Sustained Flow , ,512 1,690 3, ,268 2,667 4, b. If the flow drops below a minimum flow the system shall attempt to take a tank out of service after a 2 hour delay. c. Maximum sustained flow is the flow at which the MOS can operate on a continuous basis with no time constraint. d. Maximum 3 day sustained flow is the maximum flow rate that the MOS can be maintained at for 3 days before it should be returned to the maximum sustained flow. e. If the flow rate is at or above 1512 gpm per Membrane Tank at any time, the system shall bring an additional tank online. If no Max 3 day sustained Flow /15/2008 4:36:52 PM

18 additional tanks are available, a warning alarm shall be displayed on the OIT. 4. Peak Daily Flow Control: If the filtrate flow to a given Membrane Tank is above the maximum sustained flow and at or below the 3 day sustained flow, then a timer shall start. If the flow stays above the maximum sustained flow for 24 hours, and there is a tank in Standby, then it shall be called to service. When a tank is put back into Standby, it should be the tank that ran for 24 hours at the elevated flow. When the filtrate flow has been above the maximum sustained flow for 70 hours continuously or 140 hours over a 30 day rolling period, then a warning alarm shall be displayed on the OIT. 5. Minimum Flow Filtrate Setpoint: If the filtrate flow from the plant is less than 756 gpm, the Filtrate Pump is set up for a batch mode of operation. The low flow rate on the pump is fixed and switches on and off based on the VLR wet well level. In this configuration the MOS shall go in and out of Filtrate Standby based on the levels in the VLR wet well. When multiple tanks are in service, the minimum flow filtrate setpoint shall be used to take a tank offline after a 2 hour delay. 6. Level in the VLR Wet Well: The Filtrate Pumps for the MOS are controlled by monitoring the level in the VLR Wet Well. The range of level in the wet well is between 12 ft and 18 ft. Outside of this range an alarm shall activate. a. The Filtrate Pump shall have preset limits on what maximum flow rates the membranes can see. b. If the high level alarm activates, the Filtrate Pump shall be run at maximum flow of 1506 gpm until the level drops to 13.5 ft, then it shall maintain the level at 15 ft with PID control algorithms. c. If level drops below 12 ft, the Filtrate Pumps shall stop. The pumps shall not be called to run until the level is at 17.5 ft. Upon restart after a low level pump stoppage, the pump shall begin operating at the previous flow until the level is seen to increase further, then is shall control around the level with PID control algorithms. d. The Filtrate Pump VFD shall adjust proportionally to the level in the VLR wet well. Between the Start and Stop setpoints, the Filtrate Pump shall modulate using proportional control to maintain the level in the VLR wet well. As the level increases in the tank, the Filtrate Pump shall ramp up and as the level decreases in the tank, the Filtrate Pump shall ramp down. 7. Membrane Blowers: The Membrane Blowers provide low pressure air to scour the membrane surface. The supply of air is continuous in Filtration and Relaxation modes. During Maintenance Clean, CIP, or Standby modes, the need for air is intermittent. a. The blowers are VFD driven and the BTS PLC monitors and controls the speed to maintain flow setpoints. b. There are 3 duty Membrane Blowers. The air discharged enters a common header leading to a Thermal Mass Flowmeter for each /15/2008 4:36:52 PM

19 Tanks in service Membrane Tank. The PLC calculates the difference between the actual reading and a setpoint to adjust a modulating valve to provide the flow as required. c. Required air flow is based upon filtrate flow rates: Average Flow Peak Flow Flow per tank (scfm) Total system flow (scfm) # of blowers operating Flow per tank (scfm) Total system flow (scfm) 1 1,470 1, ,308 2, ,470 2, ,308 4, ,470 4, ,308 6,924 3 d. The blower speed is controlled by a PID algorithm to maintain a set flow range in the header; the set flow range is + 10% the set valve in the table. e. The air flow is based on the number of membrane modules installed. 7. Membrane Feed Pumps: The mixed liquor flow is variable based on the allowed mixed liquor concentration in the tank for a given filtrate flow. This can be transferred to a basic equation: y = mx + b, where y = mixed liquor flow and x = net filtrate flow. Using the table below: # of blowers operating Filtrate Flow ML Flow gradient for equation y-intercept Range (gpm) (gpm) (m) equation (b) 756 to 844 2,290 N/A N/A 845 to ,800 m = b = for a. During non-peak conditions (up to 845 gpm) the mixed liquor feed flow rate shall utilize the Mixed Liquor Suspended Solids (MLSS) concentration in VLR 1C and the filtrate flow rate to determine the most efficient set point. This set point shall be base on maintaining a mixed liquor concentration of 12,500 mg/l in the MOS overflow channel. b. The PLC calculates the mixed liquor feed flow rate based on the filtrate flow rate reading of the filtrate flowmeter and the reading of the MLSS sensor. The mixed liquor concentration in the MOS overflow is set to 12,500 mg/l which is the allowable concentration for sustainable operation. c. In the event of low MLSS concentrations in the VLR tank and/or low filtrate flows, there is a minimum mixed liquor feed flow rate which is based on maintaining a minimum velocity in the mixed liquor distribution laterals in the Membrane Tank. This minimum flow rate is 2,290 gpm /15/2008 4:36:52 PM

20 C. Effluent Flow Control Calculation: 1. Clean water required for the MC, CIP, or SIP, which comes from the common effluent line, passes through the filtrate flow meter for each respective tank being cleaned prior to entering the tank. This rate is subtracted from the totalized flow. 2. During a recirculation mode, the flow rate measured by the filtrate flowmeter is not added or subtracted from the totalized effluent flow. 2.3 RESIDUALS REDUCTION SYSTEM A. General: 1. Modes of Operation: a. The two Interchange Tanks alternate daily on the process carried out. 1) During Day 1, Tank 1 shall withdraw and fill and Tank 2 shall react. 2) During Day 2, Tank 1 shall react and Tank 2 shall withdraw and fill. b. This cycle repeats until the process is taken offline. 2. Interchange Tank Return Cycle: a. A timer triggered in the BTS PLC begins the return cycle for Interchange Tank 1. b. The PLC calculates the required fill amount based on a sludge reduction time (SRT) calculation or a predetermined level, which is operator adjustable. c. If SRT mode is selected, then the PLC calculates the decant amount. d. The Interchange Tank 1 Decant Valve opens and a preset quantity of clear liquid is transferred to the VLR tanks. The operator can adjust the quantity of clear liquid withdrawn to modify the total suspended solids (TSS) concentration in the Interchange Tanks. e. Interchange Mixer 1 starts when the first set point level is reached. f. Interchange Tank 1 indicates the final set point level has been reached. This is determined either by preset levels, or a decant amount entered in the OIT. g. Interchange Tank 1 Decant Valve is closed. h. This step is also carried out by Tank 2 on days that Tank 1 is reacting. 3. Solids Flow to Interchange Tank: a. The Interchange Mixer 1 continues to run during flow to the Interchange Tank. b. The BTS PLC begins the wasting phase of operation based on maintaining a SRT calculation or a predetermined level. 1) PLC calculates plant inventory using the MLSS probe in the VLR tank. The MLSS concentration multiplied by the volume of the VLR tanks equals the sludge inventory. The totalizer /15/2008 4:36:52 PM

21 goal for interchange flow is then a setpoint fraction of the VLR tank inventory. 2) Interchange Mass, in pounds = MLSS (in mg/l) x VLR volume (in millions of gallons) x 8.34 x setpoint fraction. 3) If the SRT for the system is 10 days, then the set point fraction would be 1/10 th. 4) The SRT set point is adjustable by the operator at the OIT. The Interchange Mass cannot exceed the design loading. 5) High level indication in the Interchange Tank prevents the sequence and an alarm is triggered on the OIT. c. The Interchange Tank 1 Feed Valve is opened directing flow to Interchange Tank 1. If the SRT mode is selected by the operator, the PLC begins totalizing mass flow using signals from the VLR MLSS probe and Interchange Tank level transmitter. d. The Interchange Reactor reaches the set point. e. The Interchange Tank 1 Feed Valve closes. f. The Interchange Mixer 1 stops. g. This step is also carried out by Tank 2 on days that Tank 1 is reacting. 4. Interchange Tank Environment Control: Periodically, when the Return Cycle and Solid flow are not in progress, other functions are carried out in the Interchange Tanks: a. Interchange Tank Mixer starts. b. The BTS PLC starts a timer, and after 15 minutes (or entered setpoint) the PLC accepts the signal from the tank s ORP probe. c. If the ORP signal is below the setpoint, a Residuals Blower starts, and the PLC starts a timer. d. At the end of this timer, the Interchange Tank Mixer and Residuals Blower stops. e. If the ph drops below a setpoint prior to the Residuals Blower timer expiring, this shall also cause the Interchange Tank Mixer and Residuals Blower to stop. f. Blowers are controlled by PLC timers which shall signal the start of the Interchange Tank Mixer and Residuals Blower for a predetermined period of time. B. Solids Separation Module Operation: 1. RAS Screen and RAS Screenings Compactor: a. During normal operation, the RAS Pumps continuously direct flow to the RAS Screen. b. If the RAS Pumps are off, then the PLC shuts down the RAS Screen process train. c. If the float switch mounted in the RAS Screen discharge chute closes, then the PLC shall stop the RAS Pumps and shut down the RAS Screen process train. 2. Spray Water: /15/2008 4:36:52 PM

22 a. If the RAS Screen is running, then the internal and external spray water solenoid valves shall open. b. If the RAS Screenings Compactor is running, then the spray water solenoid valves shall open periodically as determined by a timer. c. If the RAS Screen and RAS Screenings Compactor are ready to be back on service after a maintenance stop, then the spray system shall start before running the equipment for a preset period of time. d. If the pressure switch on the spray water line detects low pressure, then the PLC shall shut off the RAS Pumps immediately and sounds an alarm. The RAS Screen and RAS Screenings Compactor shall also shut off after preset delay intervals. e. The spray water system shall have the ability to be controlled from the BTS OIT screens for manual operations. Manual shutdown shall close the spray water solenoid valves. 3. Grit Cyclones: a. A PLC timer signals the start of the RAS Grit Pump, and opening of the RAS Grit Pump Dilution Water Solenoid Valve. A second PLC timer begins counting. When the second timer has finished, the pump is stopped and the solenoid valve is closed. b. The inerts removal can be adjusted at the OIT by set point. The frequency of the inerts removal operation is adjustable. c. The Grit Cyclone can only operate if the RAS Screen is in operation. PART 3 OPERATOR INTERFACE 3.1 GENERAL A. Operator Interface Terminals: 1. The OIT stations shall provide detailed information on the operation of plant equipment. From the OIT stations, plant operators shall receive a complete picture of the plant processes. B. Process Graphic Displays: 1. The graphic displays that reside on the OIT stations shall be the operator s primary window into the process. All monitored and calculated data points in the BTS PLC shall be available for display via graphic symbol color changes, text messages, animation, or other display action. 2. The graphic displays shall allow the operator to enter control set points and initiate manual commands (i.e., PLC auto/manual selection, manual start/stop control). All set points and operator inputs shall be tested for validity at both the PLC and OIT level. Out of range inputs shall be rejected and the system shall prompt the operator for a valid input /15/2008 4:36:52 PM

NOTICE. Issued: February 12, 2010 AO# Dundas Street West, Oakville, ON CANADA Phone: (905) Fax: (905)

NOTICE. Issued: February 12, 2010 AO# Dundas Street West, Oakville, ON CANADA Phone: (905) Fax: (905) NOTICE The enclosed materials are considered proprietary property of GE Water & Process Technologies. No assignments, either implied or expressed, of intellectual property rights, data, know how, trade

More information

Technical Service Bulletin March 2015 TSB142.01

Technical Service Bulletin March 2015 TSB142.01 Technical Service Bulletin March 2015 TSB142.01 Commissioning Procedure for HYDRAcap This Technical Service Bulletin provides information for commissioning of a HYDRAcap membrane system in a water treatment

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

Technical Service Bulletin October 2013 TSB135.03

Technical Service Bulletin October 2013 TSB135.03 Technical Service Bulletin October 2013 TSB135.03 Backwash Optimization for HYDRAcap Analysis Systems by Qualitative This Technical Service Bulletin provides optimization information for the backwash process

More information

Toronto Water Ashbridges Bay Treatment Plant Aeration Tank 2 - Process Control Narrative

Toronto Water Ashbridges Bay Treatment Plant Aeration Tank 2 - Process Control Narrative Toronto Water Ashbridges Bay Treatment Plant Aeration Tank 2 - Process Control Narrative 3 14.02.11 Issued For Construction Rev 3 2 14.09.09 Issued For Construction 1 13.04.26 100% Submission For Programmers

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The LDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

COMPRESSOR PACK SUCTION CONTROLLER TYPE: LP41x

COMPRESSOR PACK SUCTION CONTROLLER TYPE: LP41x Electrical Installation Requirements Care should be taken to separate the power and signal cables to prevent electrical interference and possible damage due to inadvertent connection. SUPPLY E L N LN2

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

Design Envelope Booster. Sequence of operation

Design Envelope Booster. Sequence of operation Design Envelope Booster Sequence of operation File No: 62.835 Date: february 11, 2015 Supersedes: 62.835 Date: july 11, 2014 sequence of operation Design Envelope Booster 2 general The packaged domestic

More information

SENSAPHONE APPLICATION NOTE. Functions: C Programming, Pump Control, Data Logging

SENSAPHONE APPLICATION NOTE. Functions: C Programming, Pump Control, Data Logging SENSAPHONE APPLICATION NOTE Application: Pump Station Volumetric Flow Calculation Functions: C Programming, Pump Control, Data Logging Sensaphone Model: SCADA 3000 Who needs to perform Volumetric Flow

More information

ACV-10 Automatic Control Valve

ACV-10 Automatic Control Valve ACV-10 Automatic Control Valve Installation, Operation & Maintenance General: The Archer Instruments ACV-10 is a precision automatic feed rate control valve for use in vacuum systems feeding Chlorine,

More information

The Next Generation for Level Control. By Ryan Spooner, Singer Valve

The Next Generation for Level Control. By Ryan Spooner, Singer Valve The Next Generation for Level Control By Ryan Spooner, Singer Valve The Next Generation for Level Control Water is an essential resource to everyday life and therefore having a way to store and distribute

More information

Important considerations for use of Cembrane

Important considerations for use of Cembrane Important considerations for use of Cembrane Content Civil Works Handling Measuring Instruments Hydraulic System Installation & Start-up Others Civil works Accuracy of tank Fixation of position holder

More information

DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Point and Nonpoint Source Management. Design Standards for Sequencing Batch Reactors

DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Point and Nonpoint Source Management. Design Standards for Sequencing Batch Reactors DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Point and Nonpoint Source Management DOCUMENT NUMBER: 385-2188-003 TITLE: EFFECTIVE DATE: AUTHORITY: POLICY: PURPOSE: APPLICABILITY: DISCLAIMER: Design

More information

These variables can be accessed by holding the UP button for 5 seconds.

These variables can be accessed by holding the UP button for 5 seconds. PureSilk Chromatalyzer QUICK SETUP GUIDE Read Owners Manual before operating this unit Only electrically qualified and authorized persons are permitted to service this unit Warranty is void if non-genuine

More information

Touch Screen Guide. OG-1500 and OG Part # T011

Touch Screen Guide. OG-1500 and OG Part # T011 Touch Screen Guide OG-1500 and OG-2000 Part # 9000000.T011 Effective 11/2010 External View Internal View 1. Transducer Banks 2. Oxygen Sensor 3. PLC These are the two manifolds with three (3) transducers

More information

UNIVERSITY OF WATERLOO

UNIVERSITY OF WATERLOO UNIVERSITY OF WATERLOO Department of Chemical Engineering ChE 524 Process Control Laboratory Instruction Manual January, 2001 Revised: May, 2009 1 Experiment # 2 - Double Pipe Heat Exchanger Experimental

More information

PART 1 GENERAL..2 Components of the gas chlorination system include, but are not limited to the following:

PART 1 GENERAL..2 Components of the gas chlorination system include, but are not limited to the following: PART 1 GENERAL 1.1 DESCRIPTION.1 This section includes the supply, delivery and installation, testing and placement into operation of a gas chlorination system, and appurtenances as specified herein and

More information

Nothing's as cool, as a freshwater pool. easychem 770 ORP and ph Controller for Pools and Spas with Timer Output for Pool Pump

Nothing's as cool, as a freshwater pool. easychem 770 ORP and ph Controller for Pools and Spas with Timer Output for Pool Pump Page 1 of 6 TPS Australia - Quality hand-made instruments since 1968. Nothing's as cool, as a freshwater pool easychem 770 ORP and ph Controller for Pools and Spas with Timer Output for Pool Pump Automatic

More information

Accu-Tab Systems 1000 Series by Axiall Corporation

Accu-Tab Systems 1000 Series by Axiall Corporation Accu-Tab Systems 1000 Series by Axiall Corporation Installation and Operating Instructions Model 1050 DANGER: DO NOT MIX CHEMICALS! The Accu-Tab chlorinator is designed for use with Axiall approved tablets

More information

Accu-Tab Systems 2000 P Series by Axiall Corporation

Accu-Tab Systems 2000 P Series by Axiall Corporation Accu-Tab Systems 2000 P Series by Axiall Corporation Installation and Operating Instructions Models 2075 P 2150 P For NSF/ANSI-Standard 61 NSF STANDARD 61 applications use NSF/ANSI Standard 60 listed Axiall

More information

V10K GAS FEED SYSTEM WALLACE & TIERNAN PRODUCTS

V10K GAS FEED SYSTEM WALLACE & TIERNAN PRODUCTS V10K GAS FEED SYSTEM WALLACE & TIERNAN PRODUCTS V10K SYSTEM: PROVEN TECHNOLOGY WORLDWIDE IN USE Since Charles F. Wallace and Martin F. Tiernan discovered the first chlorine gas feed system in 1913 the

More information

CCT-7320/ROC-2313 Reverse Osmosis Controller

CCT-7320/ROC-2313 Reverse Osmosis Controller CCT-7320/ROC-2313 Reverse Osmosis Controller 1 General The instrument is a combined control instrument of a reverse osmosis controller and an on-line conductivity instrument. It can perform the operation

More information

GAS FUEL VALVE FORM AGV5 OM 8-03

GAS FUEL VALVE FORM AGV5 OM 8-03 ALTRONIC AGV5 OPERATING MANUAL GAS FUEL VALVE FORM AGV5 OM 8-03 WARNING: DEVIATION FROM THESE INSTALLATION INSTRUCTIONS MAY LEAD TO IMPROPER ENGINE OPERATION WHICH COULD CAUSE PERSONAL INJURY TO OPERATORS

More information

Digester Processes. 1. Raw Sludge Pumping System

Digester Processes. 1. Raw Sludge Pumping System Digester Processes 1. Raw Sludge Pumping System Removes accumulated sludge from the primary clarifiers, pumped through 1 of 2 pipes either 150 or 200mm in diameter (Fig. 1.1). Fig 1.1 Pipes feeding Digesters

More information

2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications

2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications Application Description AG/266PILD-EN Rev. C 2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic Pressure Measurement Engineered solutions for all applications Increase plant productivity

More information

UNITY 2 TM. Air Server Series 2 Operators Manual. Version 1.0. February 2008

UNITY 2 TM. Air Server Series 2 Operators Manual. Version 1.0. February 2008 UNITY 2 TM Air Server Series 2 Operators Manual Version 1.0 February 2008 1. Introduction to the Air Server Accessory for UNITY 2...2 1.1. Summary of Operation...2 2. Developing a UNITY 2-Air Server method

More information

Controlling the prefeeder

Controlling the prefeeder Controlling the prefeeder A prefeeder is a modulating device of some kind, controlling the material flow into the belt feeder infeed. You need it for three reasons: 1. The material can not be sheared at

More information

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A 2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A PROJECT ADDRESS TESTING AUTHORITY TELEPHONE Checked by/date Enforcement Agency Use GENERAL INFORMATION OF BLDG. PERMIT PERMIT # BLDG. CONDITIONED FLOOR

More information

Ingersoll Rand. X-Series System Automation

Ingersoll Rand. X-Series System Automation Ingersoll Rand -Series System Automation Energy Savings on Demand! Ingersoll Rand As much as 20% to 60% of the energy used to operate compressed air systems is wasted. This is primarily due to operating

More information

Operating instructions Electrical switching facility pco

Operating instructions Electrical switching facility pco Operating instructions Electrical switching facility pco from software version V1.33 on TABLE OF CONTENTS 1. Before you start... 4 1.1 Brief description... 4 1.2 Using this manual... 4 2. pco integrated

More information

( ) ( ) *( A ) APPLICATION DATA. Procidia Control Solutions Coarse/Fine Control. Split-Range Control. AD Rev 2 April 2012

( ) ( ) *( A ) APPLICATION DATA. Procidia Control Solutions Coarse/Fine Control. Split-Range Control. AD Rev 2 April 2012 APPLICATION DATA Procidia Control Solutions / Control AD353-118 Rev 2 April 2012 This application data sheet describes implementing a coarse/fine control strategy in a Siemens Procidia 353 controller.

More information

UsER manual for Watersens ph -REDOX

UsER manual for Watersens ph -REDOX UsER manual for Watersens -REDOX Cl 8 1 2 6 3 3 7 7 4 4 4 4 Parts List 1 Redox Probe 1 x 2 PH Probe 1 x 5 Tube Weight 2 x 6 Connection Valve 1 x chlorine 3 Chlorine and Pumps 2 x 7 Dosing Valve 2 x 5 5

More information

Blue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION

Blue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION Blue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION Install your Blue River Technologies Port-A-Poly mixing system in a clean dry area.

More information

SCOTTISH WATER. Waste Water Treatment Works. Typical WWTW Ellipse Equipment No: XXXX Ellipse Plant No: STW00XXXX

SCOTTISH WATER. Waste Water Treatment Works. Typical WWTW Ellipse Equipment No: XXXX Ellipse Plant No: STW00XXXX SCOTTISH WATER Waste Water Treatment Works Typical WWTW Ellipse Equipment No: 500000XXXX Ellipse Plant No: STW00XXXX Works Manual Volume 1/3 Operating Manual (OMA) Non-Routine Operations Manual Ref No:

More information

The Use of a Process Simulator to Model Aeration Control Valve Position and System Pressure

The Use of a Process Simulator to Model Aeration Control Valve Position and System Pressure The Use of a Process Simulator to Model Aeration Control Valve Position and System Pressure Matthew Gray 1 * and Steve Kestel 1 1 BioChem Technology, King of Prussia, PA *Email: mgray@biochemtech.com ABSTRACT

More information

Commandant United States Coast Guard

Commandant United States Coast Guard Commandant United States Coast Guard 2703 Martin Luther King Jr. Ave. SE Washington, DC 20593-7509 Staff Symbol: CG-OES Phone: 202-372-1431 Fax: 202-372-8382 Email: John.A.Meehan@uscg.mil 5760 Evoqua Water

More information

1020 Industrial Drive, Orlinda, TN fax

1020 Industrial Drive, Orlinda, TN fax Operation Manual Tank Distribution System A-UPT Series 615-654-4441 sales@specialtyh2o.com 615-654-4449 fax TABLE OF CONTENTS Section 1 GENERAL 1.2 Warnings and Cautions... 1 1.2 Theory of Operation...

More information

Armfield Distillation Column Operation Guidelines

Armfield Distillation Column Operation Guidelines Armfield Distillation Column Operation Guidelines 11-2016 R.Cox Safety SAFETY GLASSES ARE REQUIRED WHEN OPERATING THE DISTILLATION COLUMN Wear gloves when mixing alcohol feedstock The column will become

More information

Built-in Purge Control Functions

Built-in Purge Control Functions Built-in Purge Control Functions Why clean a sensor? As the velocity sensor was calibrated clean, operating it clean also preserves the best calibration. Any build up of material on a thermal sensor tends

More information

Reverse Osmosis System Installation Guide and Operation Manual.

Reverse Osmosis System Installation Guide and Operation Manual. Reverse Osmosis System Installation Guide and Operation Manual. Table of Contents 1 Introduction...2 2 Installation...3 2.1 Feed water connection...3 2.2 Permeate and concentrate plumbing...3 2.3 Electrical

More information

EXPERIMENT 2 LEVEL CONTROL SYSTEM

EXPERIMENT 2 LEVEL CONTROL SYSTEM EXPERIMENT 2 LEVEL CONTROL SYSTEM 1.0 OBJECTIVE To study the response of level control process in open tank using the PID controller. 2.0 INTRODUCTION TO THE APPARATUS (MODEL WLF922). a) The process consists

More information

Every things under control High-Integrity Pressure Protection System (HIPPS)

Every things under control High-Integrity Pressure Protection System (HIPPS) Every things under control www.adico.co info@adico.co Table Of Contents 1. Introduction... 2 2. Standards... 3 3. HIPPS vs Emergency Shut Down... 4 4. Safety Requirement Specification... 4 5. Device Integrity

More information

Sequence of Operations

Sequence of Operations MAGNUM Condensing Unit Software 5580 Enterprise Pkwy. Fort Myers, FL 33905 Office: 239-694-0089 Fax: 239-694-0031 Sequence of Operations MAGNUM Chiller V8 software www.mcscontrols.com MCS Total Solution

More information

Highest Quality. Gas Chlorination Systems

Highest Quality. Gas Chlorination Systems Highest Quality Gas Chlorination Systems Application: Gas chlorination systems are used for water disinfection and other purposes in a variety of applications. Compared to other disinfection methods, chlorine

More information

Operating Guidelines for PermSelect Modules Liquid Contacting

Operating Guidelines for PermSelect Modules Liquid Contacting Operating Guidelines for PermSelect Modules Liquid Contacting PermSelect PDMSXA-2500 (0.25m 2 ) PermSelect PDMSXA-7500 (0.75m 2 ) PermSelect PDMSXA-1.0 (1m 2 ) PermSelect PDMSXA-2.1 (2.1m 2 ) PermSelect

More information

Application Notes. SLP85xD Load Cells

Application Notes. SLP85xD Load Cells Application Notes Load Cells Table of Contents 1 Introduction 3 2 Description of the Filling Cycle 4 3 Filling Optimization 7 4 Filling Monitor 8 4.1 Weight-Based Filling Monitor... 8 4.2 Time-Based Filling

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Models: EPS Single Pump EPT Twin Pump EPS-HP EPT-HP Single Pump High Pressure Twin Pump High Pressure

More information

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply 4.1.1 General The primary function of a system for handling fuel oil is to transfer oil from the storage tank to the oil burner at specified conditions

More information

Standard Chiller 1/4 compressors Manual version: /10/96

Standard Chiller 1/4 compressors Manual version: /10/96 Application program for Macroplus II Standard Chiller 1/4 compressors Manual version: 1.4-18/10/96 Program code: EP000ECH02 Rif.: 68EM Contents 0$,1)($785(6 HARDWARE...2 FUNCTIONS OF THE SYSTEM...3 PROTECTIONS...3

More information

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions Document Number: XE-ATA5PM-R1A UBEC 1AT AUTO TANK Fill System 08899155 Installation, Operation, & Setup Instructions Rev170906-EB-FRC PHYSICAL: 1302 WEST BEARDSLEY AVE ELKHART, IN 46514 WWW.ELKHARTBRASS.COM

More information

Process Simulator Evaluates Blower and Valve Control Strategies for WWTP Aeration

Process Simulator Evaluates Blower and Valve Control Strategies for WWTP Aeration Process Simulator Evaluates Blower and Valve Control Strategies for WWTP Aeration inshare By Steve Kestel and Tilo Stahl (BioChem Technology) and Matthew Gray (Keystone Engineering Group) Introduction

More information

A TECHNICAL REFERENCE

A TECHNICAL REFERENCE A TECHNICAL REFERENCE FOR CAREL DCM CONTROLLERS DIGITAL COMPRESSOR MODULE CANADIAN HEAD OFFICE AND FACTORY USA HEAD OFFICE AND FACTORY CANADIAN EASTERN FACTORY 1401 HASTINGS CRES. SE CALGARY, ALBERTA T2G

More information

Using Modbus Protocol with the ALTUS Net Oil Computer. Instruction Manual

Using Modbus Protocol with the ALTUS Net Oil Computer. Instruction Manual Using Modbus Protocol with the ALTUS Net Oil Computer Instruction Manual November 2000 Using Modbus Protocol with the ALTUS Net Oil Computer Instruction Manual November 2000 For technical assistance,

More information

AX5000 Operational Manual

AX5000 Operational Manual MIYACHI AMERICA CORPORATION The World Leader in Hermetic Sealing Systems AX5000 Operational Manual 0 Document #107-00092-001 Dec, 2013 AX5000 Operational Manual Miyachi America Corporation 1820 S. Myrtle

More information

Pool and Spa. Water Testing

Pool and Spa. Water Testing Pool and Spa Water Testing Pocket Digital Testers for Pools HI-701 Checker: Free Chlorine Hand-held Colorimeter The HI-701 is a simple, accurate and cost effective way to measure free chlorine. Free Chlorine:

More information

OPERATING MANUAL LO-CROSS-FLOW CF M

OPERATING MANUAL LO-CROSS-FLOW CF M VA FILTRATION USA 110 Dodd Court American Canyon, CA 94503 Tel : (707) 552 2616 Fax :(707) 552 3871 Web : www.vafiltration.com OPERATING MANUAL LO-CROSS-FLOW CF8-2-200M January, 2017 TECHNICAL SPECIFICATIONS

More information

MONSOON 6V Pump Control System

MONSOON 6V Pump Control System MONSOON 6V Pump Control System Installation and Operating Instructions Please pass these instructions on to the operator of this equipment. INTRODUCTION MONSOON 6V Pump Controller The MONSOON 6V pump control

More information

OPERATION MANUAL NTF-15

OPERATION MANUAL NTF-15 OPERATION MANUAL NTF-15 Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81235-00 (Rev B) TABLE

More information

High Pressure Chem-SCAN Operating Manual

High Pressure Chem-SCAN Operating Manual GAS INLET VALVES REACTIVE GAS PRESSURE RELIEF VALVE INERT GAS VENT VENT VALVE REACTOR INLET VALVES PRESSURE TRANSDUCERS REACTORS STIRRER & THERMOWELL HEATING JACKET STIRRER MOTORS High Pressure Chem-SCAN

More information

After filling the pool with clean water in the summer, two basic factors can take place due to the exposure of water to the sun and the air.

After filling the pool with clean water in the summer, two basic factors can take place due to the exposure of water to the sun and the air. ENGLISH WHAT HAPPENS TO THE WATER IN YOUR POOL? This should be a question of prime consideration for all pool owners. In the past some pools did not use filtering systems, the owner was faced with the

More information

OPERATION MANUAL NTF-60 Plus

OPERATION MANUAL NTF-60 Plus OPERATION MANUAL NTF-60 Plus Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81264-00 (Rev A)

More information

CASE STUDY. Compressed Air Control System. Industry. Application. Background. Challenge. Results. Automotive Assembly

CASE STUDY. Compressed Air Control System. Industry. Application. Background. Challenge. Results. Automotive Assembly Compressed Air Control System Industry Automotive Assembly Application Savigent Platform and Industrial Compressed Air Systems Background This automotive assembly plant was using over 40,000 kilowatt hours

More information

ES 2070 SV. Electronic controller for water softening units. Instruction Manual. Software version 1.00

ES 2070 SV. Electronic controller for water softening units. Instruction Manual. Software version 1.00 ES 2070 SV Electronic controller for water softening units Instruction Manual Software version 1.00 CONTENTS System Description... 1 Illustration... 2 Status and Regeneration.... 3 Messages... 3 LED -

More information

LP Separator Level Control by Variable Speed and Multi Stage Brine Reinjection Pumps at Kawerau and Nga Awa Purua Geothermal Projects, New Zealand

LP Separator Level Control by Variable Speed and Multi Stage Brine Reinjection Pumps at Kawerau and Nga Awa Purua Geothermal Projects, New Zealand Proceedings World Geothermal Congress 2010 Bali, Indonesia, 25-29 April 2010 LP Separator Level Control by Variable Speed and Multi Stage Brine Reinjection Pumps at Kawerau and Nga Awa Purua Geothermal

More information

SINGLE VALVE WITH LOW-FLOW BYPASS

SINGLE VALVE WITH LOW-FLOW BYPASS CONTROL VALVES Pressure Reducing Valve Sizing Guide Sizing pilot operated reducing valves is not a complicated process. It starts with determining requirements and following these guidelines in valve size

More information

Inerting System Design for Medium Speed Vertical Spindle Coal Pulverizers TABLE OF CONTENTS

Inerting System Design for Medium Speed Vertical Spindle Coal Pulverizers TABLE OF CONTENTS Inerting System Design for Medium Speed Vertical Spindle Coal Pulverizers The PRB Coal Users Group plans to develop a Design Guide for Mill Inerting as an aid to users when designing a mill inerting system.

More information

Modelling Today for the Future. Advanced Modelling Control Techniques

Modelling Today for the Future. Advanced Modelling Control Techniques CwMAG 1 st Autumn Conference 2012 Modelling Today for the Future Advanced Modelling Control Techniques What are advanced modelling controls? Why do we have them? How can we use them? What are the differences

More information

KELCO F60 DIGITAL PUMP CONTROLLER

KELCO F60 DIGITAL PUMP CONTROLLER KELCO F60 DIGITAL PUMP CONTROLLER PROGRAMMING INSTRUCTIONS KELCO Engineering Pty Ltd Sydney Australia www.kelco.com.au Table Of Contents Introduction 1 Programming the Controller 2 F60 Modes and Functions,

More information

1 STARTUP Overview Buttons Basics of Control Resetting Faults and Alarms OPERATION...

1 STARTUP Overview Buttons Basics of Control Resetting Faults and Alarms OPERATION... Operation & Service Manual 940126-0002 pco 3 Programmable Logic Controller Contents 1 STARTUP...1 1.1 Overview... 1 1.1.1 Buttons... 1 1.1.2 Basics of Control... 1 1.2 Resetting Faults and Alarms... 2

More information

AN INNOVATIVE APPROACH TO OPTIMIZE REVERSE OSMOSIS MEMBRANE PERFORMANCE

AN INNOVATIVE APPROACH TO OPTIMIZE REVERSE OSMOSIS MEMBRANE PERFORMANCE AN INNOVATIVE APPROACH TO OPTIMIZE REVERSE OSMOSIS MEMBRANE PERFORMANCE Lance R. Littrell, P.E. 1 Glenn W. Dunkelberger, P.E. 1 1 Reiss Environmental, Inc. 12001 Research Parkway Suite 228 Orlando, FL

More information

Topline Peristaltic Dosing Pump for PAC Installation, Commissioning and O&M Manual

Topline Peristaltic Dosing Pump for PAC Installation, Commissioning and O&M Manual Topline Peristaltic Dosing Pump for PAC Installation, Commissioning and O&M Manual Topline Electronics Limited 2105 This publication may not be copied, in full or in part, without prior written consent

More information

Dosing & Granudos. Controllers. Chemical Storage. Chemical. Dosing &

Dosing & Granudos. Controllers. Chemical Storage. Chemical. Dosing & C hemical Dosing & Controllers Granudos Chemical Dosing & Controllers Controllers Chemical Storage Granudos Granudos 10-CPR Touch Granudos 10-CPR Touch swimming pool disinfection system using IQ Granu-Chlor

More information

Accu-Tab PowerBase 3012AT by Axiall Corporation

Accu-Tab PowerBase 3012AT by Axiall Corporation Accu-Tab PowerBase 3012AT by Axiall Corporation Installation and Operating Instructions DANGER: DO NOT MIX CHEMICALS! The PowerBase 3012AT chlorinator system is designed for use with Axiall Corp. approved

More information

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION OCT2010 STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 020 87833050

More information

CT433 - Machine Safety

CT433 - Machine Safety Rockwell Automation On The Move May 16-17 2018 Milwaukee, WI CT433 - Machine Safety Performance Level Selection and Design Realization Jon Riemer Solution Architect Safety & Security Functional Safety

More information

INSTRUCTION MANUAL. Automatic Water Softener System. Model: PSE-08. Xsential Water Filtration Systems

INSTRUCTION MANUAL. Automatic Water Softener System. Model: PSE-08. Xsential Water Filtration Systems INSTRUCTION MANUAL Automatic Water Softener System Model: PSE-08 Xsential Water Filtration Systems 78 Daly Street Ascot Western Australia 6104 Ph: 1300 366 295 Fax: (08) 9277 2266 www.xsential.com.au Welcome

More information

WF STEUERUNGSTECHNIK GMBH. INFORMATION and TECNICAL DESCRIPTION

WF STEUERUNGSTECHNIK GMBH. INFORMATION and TECNICAL DESCRIPTION 1 INFORMATION and TECNICAL DESCRIPTION 14 2 AIRLEADER Professional Compressor Management + Compressed Air Visualisation + Alarm Service Management + AIRLEADER - has been the effective answer for compressed

More information

Safety Manual VEGAVIB series 60

Safety Manual VEGAVIB series 60 Safety Manual VEGAVIB series 60 NAMUR Document ID: 32005 Contents Contents 1 Functional safety... 3 1.1 General information... 3 1.2 Planning... 4 1.3 Adjustment instructions... 6 1.4 Setup... 6 1.5 Reaction

More information

EXPERIMENT 1 AIR PRESSURE CONTROL SYSTEM

EXPERIMENT 1 AIR PRESSURE CONTROL SYSTEM EXPERIMENT 1 AIR PRESSURE CONTROL SYSTEM 1.0 OBJECTIVE To study the response of gas pressure control using PID controller. 2.0 INTRODUCTION TO THE APPARATUS a) The process plant consists of two air vessels

More information

Hydro-Control V User Guide

Hydro-Control V User Guide Hydro-Control V User Guide Hydronix Part no: HD0193 Version 2.3.0 Revision date: July 2006 1 COPYRIGHT Neither the whole or any part of the information contained in nor the product described in this documentation

More information

USER MANUAL. Intelligent Diagnostic Controller IDC24-A IDC24-AF IDC24-AFL IDC24-F IDP24-A * IDP24-AF * IDP24-AFL * IDP24-F * 1/73

USER MANUAL. Intelligent Diagnostic Controller IDC24-A IDC24-AF IDC24-AFL IDC24-F IDP24-A * IDP24-AF * IDP24-AFL * IDP24-F * 1/73 USER MANUAL Intelligent Diagnostic Controller IDC24-A IDC24-AF IDC24-AFL IDC24-F IDP24-A * IDP24-AF * IDP24-AFL * IDP24-F * *) Require software ID: DID-SW-001 1/73 Table of contents 1 General... 3 1.1

More information

Burner Management System DEMO Operating instructions

Burner Management System DEMO Operating instructions Burner Management System DEMO Operating instructions Burner Management System DEMO Operating Instructions Startup Summary - Normal startup is accomplished in four basic steps: 1. Leak Test a. Safety Valve

More information

A TYPICAL AERATION UPGRADE CONSIDERATIONS AND OUTCOMES. Michael Young. Michael Young, Director, Faraga Pty Ltd and Aer-Force Pty Ltd

A TYPICAL AERATION UPGRADE CONSIDERATIONS AND OUTCOMES. Michael Young. Michael Young, Director, Faraga Pty Ltd and Aer-Force Pty Ltd A TYPICAL AERATION UPGRADE CONSIDERATIONS AND OUTCOMES Paper Presented by: Michael Young Author: Michael Young, Director, Faraga Pty Ltd and Aer-Force Pty Ltd 6 th Annual WIOA NSW Water Industry Engineers

More information

WATER CONTROL SYSTEM QUICK START

WATER CONTROL SYSTEM QUICK START SETTINGS MENU SYSTEM OPTIONS WATER LEVEL BAR GRAPH 3 DS SPRAY ON/OFF CS SPRAY ON/OFF BEACON WATER CONTROL SYSTEM QUICK START WWW.GFWORLDWIDE.COM +1 (208) 664-9291 SERVICE@GFWORLDWIDE.COM DISPLAY SCREEN

More information

The Future of Hydraulic Control in Water-Systems

The Future of Hydraulic Control in Water-Systems The Future of Hydraulic Control in Water-Systems A. Heimann Manager of R&D and of Technical Support & Applications Engineering departments at Dorot Automatic Control Valves Dorot Control Valves, Kibbutz

More information

CPF 270, CPF 340. Instruction book

CPF 270, CPF 340. Instruction book CPF 270, CPF 340 Instruction book Chicago Pneumatic CPF 270, CPF 340 Instruction book Original instructions Copyright Notice Any unauthorized use or copying of the contents or any part thereof is prohibited.

More information

ENS-200 Energy saving trainer

ENS-200 Energy saving trainer ENS-200 Energy saving trainer Find out about the essential aspects of energy efficiency in compressed air installations Save money Put it into practice Take care of the environment Get training www.smctraining.com

More information

The Air Liquide Gas System Equipment Brochure

The Air Liquide Gas System Equipment Brochure The Air Liquide Gas System Equipment Brochure The Equipment Manufacturing Center (EMC) was in dire need of marketing materials... A group of us teamed up to determine which systems needed highlighting,

More information

DOMESTIC HOT WATER TEMPERATURE CONTROL with SAFEGUARD

DOMESTIC HOT WATER TEMPERATURE CONTROL with SAFEGUARD ETV Platinum Plus R C O R P O R A T I O N Electronic Tempering Valve DOMESTIC HOT WATER TEMPERATURE CONTROL with SAFEGUARD Conforms to the following: ASSE 1017 California Lead Free Plumbing Law CSA B 125.3

More information

Commandant United States Coast Guard

Commandant United States Coast Guard Commandant United States Coast Guard 2703 Martin Luther King Jr. Ave. SE Washington, DC 20593-7509 Staff Symbol: CG-OES Phone: 202-372-1431 Fax: 202-372-8382 Email: Regina.R.Bergner@uscg.mil 5760 September

More information

Associated Hazard (outcome) Control Measures. Reduction of water supply

Associated Hazard (outcome) Control Measures. Reduction of water supply Raw water Intake Low lift pumphouse Structural failure of intake Source water Inability to pump-all 4 pumps (loss of power, etc.), structural failure, fire Loss of the 2 larger capacity pumps Structural

More information

TANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel

TANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel TANK MANAGER FOR TWO TANKS OPERATING MANUAL 10/31/11 C-More T6C L color touch panel 1 TABLE OF CONTENTS GENERAL...3 INSTALLATION...4 STONE TEST PROCEDURE...7 OPERATIONAL SUMMARY...7 AUTO CARBONATION...10

More information

Digital Level Control One and Two Loops Proportional and Integral Control Single-Loop and Cascade Control

Digital Level Control One and Two Loops Proportional and Integral Control Single-Loop and Cascade Control Digital Level Control One and Two Loops Proportional and Integral Control Single-Loop and Cascade Control Introduction This experiment offers a look into the broad field of process control. This area of

More information

M-06 Nitrogen Generator (Nitrogen Making Machine)

M-06 Nitrogen Generator (Nitrogen Making Machine) Guideline No.M-06 (201510) M-06 Nitrogen Generator (Nitrogen Making Machine) Issued date: 20 th October, 2015 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains

More information

Safety Manual. Process pressure transmitter IPT-1* 4 20 ma/hart. Process pressure transmitter IPT-1*

Safety Manual. Process pressure transmitter IPT-1* 4 20 ma/hart. Process pressure transmitter IPT-1* Safety Manual Process pressure transmitter IPT-1* 4 20 ma/hart Process pressure transmitter IPT-1* Contents Contents 1 Functional safety 1.1 General information... 3 1.2 Planning... 4 1.3 Instrument parameter

More information

Safe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant

Safe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant Health and Safety Executive Safe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant Background Accidents involving

More information

CCS240 and CCS241. Technical Information. Sensors for chlorine dioxide Amperometric, membrane-covered sensors for installation in the CCA250 assembly

CCS240 and CCS241. Technical Information. Sensors for chlorine dioxide Amperometric, membrane-covered sensors for installation in the CCA250 assembly Technical Information CCS240 and CCS241 Sensors for chlorine dioxide Amperometric, membrane-covered sensors for installation in the CCA250 assembly Application Chlorine dioxide is used for disinfection

More information

MP15 Jockey Pump Controller

MP15 Jockey Pump Controller Setup and Operating Instructions MP15 Jockey Pump Controller This manual provides general information, installation, operation, maintenance, and system setup information for Metron Model MP15 Jockey Pump

More information

ATL R/V Atlantis AUXILIARY PLANT OPERATION APPENDIX OPERATING PROCEDURES

ATL R/V Atlantis AUXILIARY PLANT OPERATION APPENDIX OPERATING PROCEDURES 110 AIR CONDITIONING CHILLED WATER PLANT 1. Ensure power to water chiller controller and all fan coil unit controllers is on 2. Ensure chilled water expansion tank level is at its proper level 3. Ensure

More information