Cable Pressurization Buffering

Size: px
Start display at page:

Download "Cable Pressurization Buffering"

Transcription

1 Cable Pressurization Buffering What This Practice Is About Introduction This practice describes the various buffering practices that are used to protect the integrity of the pressurized cable network during scheduled splice and sheath openings. In most cases, the buffering procedures presented here will provide adequate protection both to the individual cable and to the entire system. Determinations on which method to use should be based upon the degree of protection required for the specific cable environment. It should be noted, however, that certain extreme situations may require modifications of the procedures presented in this practice. If situations that have not been described in the following paragraphs arise, contact the supervisor for assistance. As each buffering method is presented, suggestions are made regarding the relative effectiveness and merits of the procedure. Wherever applicable, both the pros and cons of a particular buffering application are discussed to assess the effectiveness of the method. Definition By definition, buffering is a method of protecting both the cable and the system during splicing activity by providing a supplemental source (or sources) of air. When a pressurized cable sheath is opened during splicing activity, a 0 Pounds per Square Inch (PSI) leak is created. Pressurized air escapes from the opening and cable protection is reduced. Prescribed buffering procedures maximize cable protection by reducing the size of the pneumatic section in which the splice is located (Figure 1). This is accomplished by adding a source of air to an existing pneumatic section. If a splice opening occurs close to a source of air (or on a cable with very low pneumatic resistance), the increased demand on the air system could cause a dryer failure. Proper placement of a supplemental air source can prevent this from happening. Specifically, the purpose of buffering a sheath opening is fourfold: Purpose of Buffering To provide immediate protection to the cable being spliced by maintaining pressure in those portions that are vulnerable when the sheath is opened. System Studies Incorporated (28102.DES) 1

2 Figure 1 Buffering to Reduce Pneumatic Section 2

3 To maintain pressure protection throughout the entire system by keeping delivery pressures at or above the minimum air pressure standards. To offset the increased air pressure demands of central office compressors during splicing activities by providing a supplemental source of pressurized air. To minimize alarms to the Cable Pressure Monitoring System (CPMS). Methods of buffering vary depending upon the type of pressurization system in use and specific buffering objectives. It is critical to understand that there are certain tradeoffs with each buffering application. For example, it is advisable to weigh the preparation time with what is being accomplished in the way of overall cable protection. Although this practice does not address these tradeoffs specifically, it does suggest which buffering methods provide the most cable protection and which provide the least. Buffering Applications Buffering is a method of minimizing pneumatic sections and providing dual feed protection to a sheath opening. If pressurized air converges on a sheath opening from opposite directions, the sections of cable on both sides of the opening will be protected. In each of the buffering applications described in this part, cable pressures are maintained and the system's principal air source is protected against increased demand. There are one or more buffering procedures for each of the following applications. (a) Buffering in single feed systems (b) Buffering in air pipe systems (c) Buffering with buffer pipe Single Feed Systems In a single feed system, the technician must reduce the pneumatic section in which the splice is located and establish dual feed protection to the cable. Depending upon the location of the original air source, adequate buffering is performed with either one supplemental air source or two. Buffering Near the Central Office If the splice location is 1,000 feet or less from the office meter panel, buffering can be performed with one nitrogen tank. In this application, the tank should be placed on the field side of the sheath opening opposite the original source (Figure 2). The tank should be placed close enough to the opening to reduce the pneumatic section as much as possible, but not so close that the tank will empty before splicing has been completed. The recommended tank placement distance is 1,000 feet from the splice opening. Placing a tank closer than 1,000 feet decreases the pneumatic resistance between the tank and the splice location and causes a significant increase in the tank's flow rate. System Studies Incorporated (28102.DES) 3

4 Figure 2 Buffering Near Meter Panel Note: The buffering technique in Figure 2 provides adequate protection to the cable in most situations. If the access hole were wet, however, it would also be advisable to pump the closest access holes on each side of the splice opening. Buffering Farther Out in the Field If a splice location is farther than 1,000 feet from the office meter panel, two nitrogen tanks are required to effectively reduce the pneumatic section and provide adequate protection to the cable. In this situation, one nitrogen tank is placed on the office side of the splice; the other is placed on the field side. Each air source should be placed approximately 1,000 feet from the splice location (Figure 3). Figure 3 Buffering in the Field Note: It should be understood that the 1,000 foot tank placement distance referred to throughout this practice is only an approximation. In practice, distances may vary by as much as 200 to 300 feet with acceptable results. Buffering Near a Remote Dryer The buffering applications described for locations near the central office also apply to a single feed system with a remote dryer as the principal air source. In a situation where a remote dryer is within 1,000 feet of the proposed sheath opening, it is recommended that the remote dryer be turned off and two nitrogen tanks be used to buffer the splice. In this situation, place two nitrogen tanks on the cable one on each side of the splice location. Each tank should be placed approximately 1,000 feet from the sheath 4

5 opening (Figure 4). Once the tanks have been positioned and turned on, shut off the remote dryer by closing the bypass valve on the 3/8" tubing at the back of the dryer. If there is a manifold at the dryer, turn off the air only to the cable being spliced. In the example in Figure 4, opening the sheath without shutting off the remote dryer could cause excessive loss of air and overload the dryer. Proper buffering, as described above, eliminates this danger and provides maximum protection to the cable. It is critical to reopen the bypass valve at the dryer (or turn on the air supply at the manifold) after splicing has been completed. Figure 4 Buffering Close to Source Air Pipe Systems There are several buffering procedures that may be used in an air pipe pressurization system. The distinction is generally based on the location of the existing air sources and where the buffering will take place. The explanations which follow address buffering in air pipe systems at the following locations: On single feed laterals On dual feed cable sections between air pipe manifolds On dual feed sections in the manifold access hole Single Feed Laterals In a single feed section, such as a lateral or toward the endpoint of the cable past the manifold location, a supplemental source of air is required on the field side of the proposed sheath opening to establish dual feed cable protection. A tank (or tanks) regulated to a maximum of 10 PSI should be placed approximately 1,000 feet from the splice opening. Figure 5 illustrates a situation where the last air pipe manifold on the pipe is located approximately 1,000 feet from the splice location. In this situation, only one supplemental air source is required on the field side of the splice (1,000 feet away) to buffer the cable. The air pipe manifold provides the air supply to the cable on the central office side of the splice. System Studies Incorporated (28102.DES) 5

6 Figure 5 Buffering on Single Feed Section 1,000 Feet from Manifold A variation of the example in Figure 5 is when the last air pipe manifold on the pipe is located within 1,000 feet of the splice location. In this situation, a nitrogen tank is placed on the CO side of the manifold approximately 1,000 feet from the splice opening; a second tank is placed on the field side of the splice (Figure 6). Figure 6 Buffering on Single Feed Section Less Than 1,000 Feet from Manifold In this type of buffering application, a tank should always be placed at the end of the cable even if the distance from the endpoint to the splice is less than 1,000 feet. Establishing dual feed protection during buffering is more important than minimizing supplemental air source usage. Once the tanks have been placed, the manifold air source to the cable is turned off and the sheath opened. Once splicing has been completed, make sure to turn the air pipe manifold back on again. Note: Under no circumstances should an air pipe manifold be used for buffering when the distance from the manifold to the splice is less than 1,000 feet. This is especially true when splicing takes place in the manifold access hole. In these situations the increase in air flow at the manifold could severely jeopardize delivery pressure to the other cables in the pipe system. If the proposed splice location is farther than 1,000 feet from the last manifold on the pipe, a third buffering application exists. In this situation, two supplemental nitrogen 6

7 tanks must be placed on the cable on opposite sides of the splice opening (Figure 7). Once again, each tank should be placed approximately 1,000 feet from the splice. Figure 7 Buffering on Single Feed Section Farther Than 1,000 Feet from Manifold Buffering Midway Between Manifolds Dual feed cable sections provide a number of buffering options. For example, there are three approaches to buffering at access hole locations midway between air pipe manifolds. Four different buffering methods may be used when a sheath opening is scheduled at a manifold access hole. In each situation, the objectives are the same: to reduce the pneumatic sections of the cables being spliced and to assure delivery pressure to the other pneumatic sections. The decision on which method to use must be based on the amount of protection needed for each specific cable environment. The various methods of buffering at locations midway between manifolds are explained below. The least protective method is described first; the most protective method is described last. The procedures in each application are essentially the same as those described in the Mechanics of Buffering section of this practice. Variations in the procedures pertain to the actual placement of the supplemental air source(s). Midpoint buffering practices are as follows: (1) When the proposed splice location is in a dry access hole between air pipe manifolds, buffer the air pipe with an auxiliary air source (Figure 8). This sometimes supplements delivery pressure to the other cables in the system. For the most part, however, it serves only to reduce pipe alarms to the Figure 8 Buffering Air Pipe Between Two Manifold Access Holes System Studies Incorporated (28102.DES) 7

8 CPMS. It does not increase protection to the cables being opened because it does not reduce the length of the pneumatic section. This method is the least recommended method of buffering when access holes are wet. Note: The delivery pressure of the nitrogen tank must be regulated to 0.5 PSI above the air pipe pressure. If the nitrogen tank is substantially higher, it could drain during splicing activity. (2) Place nitrogen tanks on the cable 1,000 feet away from the sheath opening to assure adequate cable protection (Figure 9). This is a better approach to buffering when wet access hole conditions exist. The advantage of this application over the first midpoint buffering method is that placing nitrogen tanks decreases the size of the pneumatic section. A potential problem is that one or both tanks may run dry. Figure 9 Buffering Cable Midway Between Manifold Access Holes (Least Protection) (3) Place buffer hoses from the air pipe to the cable 1,000 feet away from the sheath opening in both directions, and place a nitrogen tank in the access hole with the splice (Figure 10). The buffer hoses provide protection to the cables, and the nitrogen tank on the air pipe prevents CPMS alarms and supplements pipe delivery pressure. Figure 10 Buffer Hoses from Air Pipe to Cable 8

9 Note: The pressure at the tank should be set at 0.5 PSI above the pipe pressure. The advantage of this type of buffering is that, unlike nitrogen tanks, buffer hoses provide an unlimited source of air from the air pipe. The disadvantage is that buffer hoses are not always removed after buffering. Each buffer hose left in place creates at least one unmonitored pneumatic section. Buffering in the Manifold Access Hole When splicing activity occurs in the manifold access hole or within 1,000 feet of it, both the cable and the manifold must be protected. In this situation, a new dual feed pneumatic section is created, and the manifold air flow to the cable is turned off. Follow the procedures for buffering as explained at the end of this practice. Also, be sure to turn off the manifold valve for the cable being opened after the new air source(s) has been attached. Do not turn off the entire manifold. If the cable being spliced is stubbed or interlaced with other cables, their respective manifold valves must also be turned off during splicing activity. This should be done before opening the closure. Make sure that the manifold is turned back on when splicing activity has been completed and that all supplemental air sources have been removed. There are four methods for buffering a splice opening that is located at or near an air pipe manifold: (a) Use buffer hoses to supply air feed from the air pipe to the cable section (Figure 11). Place each buffer hose 1,000 feet away from the sheath opening. (b) Use nitrogen tanks to buffer the sheath opening direction. Place the tanks at the same locations (1,000 feet from the sheath opening) as the buffer hoses in Figure 11. Figure 11 Buffering Near Manifold with Buffer Hoses (c) If the splice opening is near the last manifold on the air pipe, place a nitrogen tank on the cable 1,000 feet to the field side of the sheath opening (Figure 12). Use a buffer hose from the air pipe to the cable on the central office side of the opening. System Studies Incorporated (28102.DES) 9

10 (d) Use a nitrogen tank in place of the buffer hose in Figure 12. In this situation, there will be two nitrogen tanks supplying air to the cable section each 1,000 feet away in the opposite directions. Figure 12 Buffering Near the Last Air Pipe Manifold Systems with Buffer Pipe Another acceptable method of buffering is the use of a specially installed air pipe called a buffer pipe. In dual feed systems, the buffer pipe is engineered into the pressurization system along with the main feeder pipe. A buffer pipe is a standard air pipe that parallels the main route. In an air pipe system it is placed in the same conduit run as the feeder pipe. Buffering Equipment Buffer pipe originates at a pipe panel in the central office and generally includes the following equipment: Flow transducer (0 20 SCFH) Buffer pipe identification tags Pressure testing valves in each access hole A control flow valve at the end of the pipe. A buffer pipe provides easy access to an air source during buffering activity. Depending upon the location of the sheath opening, the buffer pipe can eliminate the use of nitrogen tanks during buffering activities. As a ready air source, it is pneumatically connected to a cable with buffer hoses placed at the recommended distances (Figure 13). Note: As in other buffering applications at or near an air pipe manifold, it is necessary to turn off air feed from the manifold to the cable being spliced. Make sure to turn the manifold air supply back on after splicing has been completed. The Proper Use of Buffer Pipe The same general buffering procedures presented throughout this part apply to buffer pipe. Special emphasis, however, must be placed on not misusing the pipe. Buffer pipe is not an engineering alternative to leak locating; it should not be used to keep 10

11 Figure 13 Buffer Pipe Application cable pressures up. It is a temporary and convenient air source for buffering. Among the concerns when using buffer pipe are the following: Caution should be taken not to open the sheath if cable pressure falls below the minimum acceptable pressure standards. Buffer hoses should not be placed closer than 1,000 feet from the splice opening. Doing so increases the output of the central office compressor without increasing cable protection. When splicing activities have been completed and the sheath closure has been tested, buffer hoses must be removed. Buffer pipe is not designed to be used as a permanent air source. If buffer hoses are not disconnected from the cable, a new unmonitored pneumatic section is created (Figure 14). Mechanics of Buffering The Manual Process of Buffering The manual process of buffering a sheath opening is essentially the same for each type of buffering application. This process includes placing a supplemental air source (or sources) on the cable or air pipe, checking pressures, opening the splice closure, maintaining air protection to the cable on each side of the opening, closing the sheath, and removing the supplemental air source(s). Variations of these procedures depend on each buffering application they are used in. For example, when splicing activity takes place near an existing air dryer, it may be necessary to turn off the air dryer to protect it from excessive output. In this case, an alternate source of air is required to replace the output of the dryer. System Studies Incorporated (28102.DES) 11

12 Figure 14 Unmonitored Pneumatic Section Buffering Procedure For the most part, however, buffering procedures are similar for each application. The recommended procedures are as follows: Step 1 Before opening the cable, measure the cable pressure with a C pressure gauge and record the reading. If the cable pressure does not meet or exceed minimum air pressure standards for the cable environment, contact the local supervisor for specific buffering procedures. Note: Minimum cable pressure standards are as listed below. Select the appropriate standard for your operating company. Underground Cable 5 or 6 PSI Buried Cable 3 or 4 PSI Step 2 Step 3 Step 4 Place a nitrogen tank or tanks on the cable at the prescribed locations. Connect a hose from the tank to an F pressure testing valve at each buffering location. Regulate delivery pressure from the nitrogen tank(s) to 10 PSI. Pressures higher than 10 PSI may result in damage to the C pressure gauge and cable. Open the splice closure. 12

13 Step 5 Step 6 Step 7 Step 8 Step 9 Periodically check the pressure level of the nitrogen tank(s), and replace with a new tank(s) if necessary. When work has been completed, use a torque wrench for proper sealing of all closures. Pressure test the sheath closure according to local practices. Continue buffering until the cable pressure at the sheath opening is within 0.5 PSI of the original pressure. Remove nitrogen tank(s) and/or buffer hose after the cable pressure at the opening has been restored. Note: Although safety regulations are not discussed in this practice, it is critical that routine and specialized safety precautions are taken when working with high pressure equipment and air sources. Always wear safety glasses and double check all fittings before and after making connections to the cable system. Fittings must be able to withstand the normal operating system pressure and the slightly higher buffering pressure. When using nitrogen tanks, be careful not to bleed excessive nitrogen into the access holes. Nitrogen can displace the available oxygen and seriously contaminate the work environment. System Studies Incorporated (28102.DES) 13

14 14

A Primer on Cable Pressurization

A Primer on Cable Pressurization A Primer on Cable Pressurization Maintenance Due to operating company downsizing, and the resulting re-distribution of personnel, there is a definite need these days for some basic information on cable

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

ACCU-PULSE Installation and Operation Instructions

ACCU-PULSE Installation and Operation Instructions ACCU-PULSE Installation and Operation Instructions Pump Discharge Installation: Chargeable Models Step 1: Mounting Position Mount ACCU-PULSE as close to the pump discharge as possible to absorb the pulse

More information

accidents which arise due to non-observance of these instructions and the safety information herein.

accidents which arise due to non-observance of these instructions and the safety information herein. 3 GALLON PANCAKE COMPRESSOR Model: 50959 CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or grind materials such as wood, paint, metal, concrete, cement, or other masonry.

More information

Inert Air (N2) Systems Manual

Inert Air (N2) Systems Manual INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing

More information

Spring Loaded Regulators Constant Loaded Regulators Twin Parallel Flow Regulators Field Service Regulators

Spring Loaded Regulators Constant Loaded Regulators Twin Parallel Flow Regulators Field Service Regulators Product Line Brochure J0B Effective Date 2/01 Spring Loaded Regulators Constant Loaded Regulators Twin Parallel Flow Regulators Field Service Regulators P R O D U C T L I N E O V E R V I E W Regulator

More information

LNG Regulator Test Kit

LNG Regulator Test Kit OVERVIEW Chart provides a LNG Economizer/Regulator Test Kit to help save money and time by allowing a technician to more accurately and easily diagnose the operability of the pressure control regulator/economizer

More information

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock or Electrocution: MODEL NUMBER: 20008 200 PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank IMPORTANT: It is

More information

200 PSI FAST-FILL AIR SOURCE KIT

200 PSI FAST-FILL AIR SOURCE KIT 200 PSI FAST-FILL AIR SOURCE KIT 55% Duty Compressor on 2.0 Gallon Air Tank PART NO. 20007 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of

More information

200 PSI HIGH-FLOW AIR SOURCE KIT

200 PSI HIGH-FLOW AIR SOURCE KIT 200 PSI HIGH-FLOW AIR SOURCE KIT 50% Duty Compressor on 2.0 Gallon Air Tank PART NO. 20008 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of

More information

Aquavar SOLO 2 Frequently Asked Questions

Aquavar SOLO 2 Frequently Asked Questions Aquavar SOLO 2 Frequently Asked Questions How do I size the Aquavar SOLO 2 for the appropriate pump/motor combination? Can I use a 208 Volt motor? Can I run the Aquavar SOLO 2 up to 80HZ? What are the

More information

Operation Manual - PN A MENSOR MODEL 73 SHOP AIR BOOSTER

Operation Manual - PN A MENSOR MODEL 73 SHOP AIR BOOSTER Operation Manual - PN 0017946001 A MENSOR MODEL 73 SHOP AIR BOOSTER Mensor Model 73 Shop Air Booster System (750 psi Version) April 23, 2012 Trademarks / Copyright Mensor is a registered trademark of Mensor

More information

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For Your Safety... 2 Description.... 2 Setup Mode.... 2 Lights/Alarms.... 3 Operation.... 4 Calibration....

More information

RAM 4021-PR. Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

RAM 4021-PR. Operation Manual. Worldwide Manufacturer of Gas Detection Solutions RAM 4021-PR Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021-PR For Your Safety... 2 Description.... 2 Setup Mode.... 2 Lights/Alarms.... 3 Operation.... 4

More information

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 9 ACCUMULATORS The material needed for outcome 2 is very extensive so there are

More information

RAM 4021-DPX Operation Manual

RAM 4021-DPX Operation Manual RAM 4021-DPX Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS ABL 4021-DPX / RAM 4021-DPX For Your Safety... 3 Description... 3 Setup Mode... 4 Lights/Alarms... 4 Operation...

More information

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE MODEL NUMBER: M20005 AIR SOURCE KIT 30% Duty Compressor on 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE USER MANUAL IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock

More information

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289 3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for

More information

RAM 4021 Operation Manual

RAM 4021 Operation Manual RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For your safety...3 Description...3 Set-up mode...4 Annunciator lights/alarms...4 Operation...5 Calibration...6

More information

OPERATION MANUAL NTF-15

OPERATION MANUAL NTF-15 OPERATION MANUAL NTF-15 Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81235-00 (Rev B) TABLE

More information

RAM Operation Manual

RAM Operation Manual RAM 4021-1 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021-1 For Your Safety... 2 Description... 2 Setup Mode... 3 Lights/Alarms... 3 Operation... 4 Calibration...

More information

/ /

/ / GN 4- kw/5.5-0 hp Dual Output Compressors (Air/Nitrogen) Driving Nitrogen Forward GN: the dual output solution From cargo blanketing in LNG vessels to the inflation of Formula tires, nitrogen is used in

More information

OPERATION MANUAL NTF-60 Plus

OPERATION MANUAL NTF-60 Plus OPERATION MANUAL NTF-60 Plus Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81264-00 (Rev A)

More information

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For Your Safety... 2 Description.... 2 Setup Mode.... 2 Lights/Alarms.... 3 Operation.... 4 Calibration....

More information

Piped Air SCBA Refilling System Standard

Piped Air SCBA Refilling System Standard WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Piped Air SCBA Refilling System Standard SCOPE: This specification

More information

Best Practices Pneumatics Machine & Design. Written by Richard F. Bullers, CFPPS as published in Fluid Power Journal, July/August 2016

Best Practices Pneumatics Machine & Design. Written by Richard F. Bullers, CFPPS as published in Fluid Power Journal, July/August 2016 Pneumatics Machine & Design Written by Richard F. Bullers, CFPPS as published in Fluid Power Journal, July/August 2016 Contents at Atmospheric Air The air at a compressor s intake contains about 78% nitrogen,

More information

with O 2 Controller Instruction Manual

with O 2 Controller Instruction Manual 14500 Coy Drive, Grass Lake, Michigan 49240 734-475-2200 E-mail: sales@coylab.com www.coylab.com Hypoxic Cabinets (In-Vivo / In-Vitro) with O 2 Controller Instruction Manual Index Page Warranty 2 Warnings

More information

Wilo Triple Duty Valve / Triple Service Valve Installation and operating instructions

Wilo Triple Duty Valve / Triple Service Valve Installation and operating instructions Wilo Triple Duty Valve / Triple Service Valve Installation and operating instructions WIL-IO-SD-001-10 1 Description The Triple Duty Valve (TDV) / Triple Service Valve (TSV) is a quiet operating heavy-duty

More information

Storage Systems and Accessories

Storage Systems and Accessories Storage Systems and Accessories High Pressure Air and Inert Gases 4500-6000 PSIG DOT and ASME Cylinders High Pressure Storage Systems If an application requires storage, either in the form of a single

More information

Winter Shut Down Procedure

Winter Shut Down Procedure Winter Shut Down Procedure Although we live in Beautiful BC, we still experience freezing temperatures. To minimize the risk of freeze damage to your irrigation system, you ll need to winterize it. Our

More information

Portable Oil Lube Air Compressors

Portable Oil Lube Air Compressors Portable Oil Lube Air Compressors 8003631 8003632 0410149 8018968 8018940 Owner s Manual Read and understand operating instructions before use Safety definitions The information listed below should be

More information

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO 97C COMPRESSOR KIT 12V PART NO. 00097 97C COMPRESSOR KIT 24V PART NO. 02497 98C COMPRESSOR KIT PART NO. 00098 97C 98C IMPORTANT: It is essential that you and any other operator of this product read and

More information

Section GAS CHLORINATION SYSTEM

Section GAS CHLORINATION SYSTEM PART 1 GENERAL 1.01 SUMMARY Section 11260 This Section includes the furnishing and subsequent installation, complete and in place, of a functioning gas chlorination disinfection system for water as shown

More information

Medical Gas Control Panel

Medical Gas Control Panel Medical Gas Control Panel INSTALLATION & MAINTENANCE MANUAL 255105 (Rev. 6) 2018-04 2 255105 (Rev. 6) 2018-04 1.0 User Responsibilities The information contained in this installation and operation maintenance

More information

444C DUAL PERFORMANCE VALUE PACK

444C DUAL PERFORMANCE VALUE PACK (Chrome) PART NO. 44432 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using this product. SAVE THIS MANUAL

More information

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which January 27, 2012 307a 1. (Refer to Figures 1-3.) A Viking Non-Interlocked Preaction system utilizes a Viking Deluge Valve to control water flow into system piping equipped with closed sprinklers. Under

More information

INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT

INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT P.O. Box 1058 1058 West Industrial Avenue Guthrie, OK 73044-1058 405-282-5200 FAX: 405-282-8105 www.autoquip.com Item # 830ABS Version 1.0 07/2001

More information

PRESSURIZED EQUIPMENT AND SYSTEMS

PRESSURIZED EQUIPMENT AND SYSTEMS SECTION 20 PRESSURIZED EQUIPMENT AND SYSTEMS 20.A GENERAL 20.A.01 Inspections and tests - general. a. Pressurized equipment and systems shall be inspected and performance tested before being placed in

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

OPERATING AND MAINTENANCE MANUAL

OPERATING AND MAINTENANCE MANUAL Series 4300 Engineered Performance TABLE OF CONTENTS 0 INTRODUCTION 1 1 Scope 1 2 Description 1 3 Specifications 1 0 INSTALLATION 1 1 Mounting 1 2 Piping 1 1 Connecting Process Pressure 2 2 Vent Connections

More information

400C & 450C DUAL PERFORMANCE VALUE PACKS

400C & 450C DUAL PERFORMANCE VALUE PACKS (Chrome) PART NO. 40013 (Silver) PART NO. 45012 (Chrome) PART NO. 45013 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before

More information

LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual

LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual 002694 IntroductIon 8-1-11 Page 1 ForEWord This manual is intended for use with

More information

Data Sheet Issue A

Data Sheet Issue A Features 1. Differential latching clappertype, lighweight, dependable construction. 2. Low Air Pressurized System, 8 psi -to- 26 psi (0,6 bar to- 1,8 bar) 3. Reset externally. Cover removal is not required.

More information

Exercise 2-3. Flow Rate and Velocity EXERCISE OBJECTIVE C C C

Exercise 2-3. Flow Rate and Velocity EXERCISE OBJECTIVE C C C Exercise 2-3 EXERCISE OBJECTIVE C C C To describe the operation of a flow control valve; To establish the relationship between flow rate and velocity; To operate meter-in, meter-out, and bypass flow control

More information

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions L 100 Bubble-Tube Level System Installation, Operation and Maintenance Instructions Figure 1 Contents Section Description Page 1.0 Introduction 2 2.0 Specifications 3 3.0 Installation 3 4.0 Warranty 6

More information

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS)

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS) South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System Designed for: Dry or Preaction Fire Protection Systems (FPS) 1.0 Description of Work 1.1 The Fire Sprinkler Contractor shall provide

More information

Model 7989T Steel Pipe Squeezer Sch. 40 & Sch. 80. Operations Manual

Model 7989T Steel Pipe Squeezer Sch. 40 & Sch. 80. Operations Manual 10-12 Steel Pipe Squeezer Sch. 40 & Sch. 80 Operations Manual 1.0 Introduction This manual is issued as a basic operation manual covering the Regent Model 7989T, Pipe Squeezer and Pump as manufactured

More information

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS READ ALL INSTRUCTIONS PRIOR TO INSTALLATION AND OPERATION TO AVOID POSSIBLE INJURY Warning: Always consider any accumulator to contain pressure until proven

More information

Freedom8 ShoeBox Compressor Manual

Freedom8 ShoeBox Compressor Manual Freedom8 ShoeBox Compressor Manual Warning!! This product is not a toy! Use or misuse can cause severe injury or death! Use only with adult supervision. This unit is only to be used with tanks, hoses and

More information

4-7 kw/ hp. Dual Output Compressors (Air/Nitrogen) Driving Nitrogen Forward

4-7 kw/ hp. Dual Output Compressors (Air/Nitrogen) Driving Nitrogen Forward GN 4-7 kw/5.5-10 hp Dual Output Compressors (Air/Nitrogen) Driving Nitrogen Forward Total capability, total responsibility Right at the heart of your business, Atlas Copco delivers quality compressed air

More information

HYDROSTATIC LEAK TEST PROCEDURE

HYDROSTATIC LEAK TEST PROCEDURE This information is proprietary and shall not be disclosed outside your organization, nor shall it be duplicated, used or disclosed for purposes other than as permitted under the agreement with Kinetics

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS Tempe Pressure Cell June 1995 Fig. 1a 1400 Tempe Pressure Cells with 3cm cylinders and 6cm cylinders) mounted on the Tempe Cell Stand Fig. 1b Disassembled 1400 Tempe Pressure Cell

More information

Operating Manual. Model BAC-30RT30/BAC-30DC

Operating Manual. Model BAC-30RT30/BAC-30DC Model BAC-30RT30/BAC-30DC Manual No. BAC012 (Rev 1 October 2002) Operating Manual AIR SYSTEMS INTERNATIONAL, INC. 829 Juniper Crescent, Chesapeake, Va., 23320 Telephone (757) 424-3967 Toll Free 1-800-866-8100

More information

450P- RV AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES

450P- RV AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES 450P- RV AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES PART NO. 45053 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing

More information

MODEL NUMBER: P PORTABLE COMPRESSOR

MODEL NUMBER: P PORTABLE COMPRESSOR MODEL NUMBER: 30033-300P PORTABLE COMPRESSOR IMPORTANT: It is essential that you and any other operator of the product read and understand the contents of this manual before installing and using this product.

More information

U.S. CONCRETE, INC. SAFETY POLICY and PROCEDURE MANUAL

U.S. CONCRETE, INC. SAFETY POLICY and PROCEDURE MANUAL SAFE -14 Page 1 of 8 U.S. CONCRETE, INC. SAFETY POLICY and PROCEDURE MANUAL FUNCTION Safety TOPIC Hotwork Permit Program OBJECTIVE(S): GENERAL POLICY: To provide a work atmosphere that is conducive to

More information

COMPRESSOR REPLACEMENT PROCEDURE (R-134A)

COMPRESSOR REPLACEMENT PROCEDURE (R-134A) 372 ROUTE 4 BARRINGTON, NH 03825 USA TEL (603) 868-5720 FAX (603) 868-1040 1-800-435-6708 COMPRESSOR REPLACEMENT PROCEDURE (R-134A) [ ] If possible operate the compressor with proper charge for 5 minutes

More information

TECHNICAL MANUAL CALIBRATION PROCEDURE FOR PRESSURE GAUGE. This publication replaces T.O. 33K dated 30 January 2012.

TECHNICAL MANUAL CALIBRATION PROCEDURE FOR PRESSURE GAUGE. This publication replaces T.O. 33K dated 30 January 2012. TECHNICAL MANUAL CALIBRATION PROCEDURE FOR GAUGE This publication replaces T.O. 33K6-4-427-1 dated 30 January 2012. Distribution Statement C - Distribution authorized to U. S. Government agencies and their

More information

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor)

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1. According to NFPA 99, SCFM is an acronym for. a) Surface Conditions at Fahrenheit Mercury b) Standard Conditions

More information

LAKOS Waterworks. PWC Series Sand Separators. Installation & Operation Manual LS-829 (10/12)

LAKOS Waterworks. PWC Series Sand Separators. Installation & Operation Manual LS-829 (10/12) LAKOS Waterworks PWC Series Sand Separators Installation & Operation Manual LS-829 (10/12) Table of Contents Separator Operation... 3 Individual Model Details.... 4 Flow vs. Pressure Loss Chart 4 Installation

More information

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO 400H HARDMOUNT AIR COMPRESSOR KIT PART NO. 40042 450H HARDMOUNT AIR COMPRESSOR KIT PART NO. 45042 400H 450H IMPORTANT: It is essential that you and any other operator of this product read and understand

More information

256 Pneumatic Pressure Indicator

256 Pneumatic Pressure Indicator 256 Pneumatic Pressure Indicator 51425699 Copyright 2002 Slope Indicator Company. All Rights Reserved. This equipment should be installed, maintained, and operated by technically qualified personnel. Any

More information

Crystal Spring Feeder Protocols

Crystal Spring Feeder Protocols Crystal Spring Feeder Protocols Installation Instructions Starting Weaned Pigs Management Instructions Gro Master 402.493.4550 3838 North 108th Omaha, NE 68164 Crystal Spring Feeder Protocols Installation

More information

CVI Valve Line. Exceeds the industry s highest standards for reliability and performance

CVI Valve Line. Exceeds the industry s highest standards for reliability and performance CVI Valve Line Exceeds the industry s highest standards for reliability and performance Available in the most standard models with the shortest lead times in the industry Exceptional quality every CVI

More information

Complying with NFPA 58 Transfer Area and Bulk Plant Liquid Opening Requirements

Complying with NFPA 58 Transfer Area and Bulk Plant Liquid Opening Requirements May 2005 Complying with NFPA 58 Transfer Area and Bulk Plant Liquid Opening Requirements D450143T012 R www.fisherregulators.com/lp Table of Contents Table of Contents............................................................

More information

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve. Foam 302 a 1. DESCRIPTION (Refer to Figure 1 on page 302 e.) The Viking Low-Flow Foam/Water Proportioning System is a UL Listed and FM Approved system, for use with 3M and Viking brand foam concentrate.

More information

User Manual for the Mars Calibration Bench

User Manual for the Mars Calibration Bench User Manual for the Mars Calibration Bench Fall 2013 Table of Contents Table of Contents Table of Contents... iii Introduction... v Chapter 1: The Mars Calibration Bench... 1 What Is the Mars Calibration

More information

Water Hammer In Irrigation Systems 1

Water Hammer In Irrigation Systems 1 CIR828 1 G. A. Clark and D. Z. Haman 2 Irrigation system design includes pump sizing and selection, valve sizing and selection, and pipe sizing as well as the proper selection and placement of many other

More information

COMPRESSED AIR DISTRIBUTION SYSTEMS

COMPRESSED AIR DISTRIBUTION SYSTEMS Series COMPRESSED AIR DISTRIBUTION SYSTEMS 18 DESIGNING AN EFFICIENT COMPRESSED AIR DISTRIBUTION The main source of inefficiencies and problems affecting compressed air distribution systems is often the

More information

SERVICE MANUAL MODEL BA050BMST BREATHING AIR PANEL

SERVICE MANUAL MODEL BA050BMST BREATHING AIR PANEL www.modsafe.com SERVICE MANUAL MODEL BA050BMST BREATHING AIR PANEL WARNING: Do not attempt to operate this equipment without first reading and understanding the service manual enclosed with this device.

More information

Positive displacement proportioning of two-component epoxy intumescent coatings for passive fire protection

Positive displacement proportioning of two-component epoxy intumescent coatings for passive fire protection Positive displacement proportioning of two-component epoxy intumescent coatings for passive fire protection WHITE PAPER In today s protective coating industry, there is a growing demand to proportion and

More information

Manual. FRESH AERO OneOP Model PC (Portable Compressors) Tire Inflator. Where Imagination Meets Innovation

Manual. FRESH AERO OneOP Model PC (Portable Compressors) Tire Inflator. Where Imagination Meets Innovation FRESH AERO OneOP Model PC (Portable Compressors) Tire Inflator For inflating aircraft tires and all types of other vehicle tires and air operated devices Manual The Fresh Aero Group Where Imagination Meets

More information

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only) 42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) 42047 Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only) 45052 Constant Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor

More information

MANUAL BE SERIES Test Benches

MANUAL BE SERIES Test Benches The CustomCrimp Manual BE Series Test Benches are designed with features that make proof and burst testing of hydraulic hose assemblies a quick and easy procedure. CUSTOMIZED AND SPECIAL DESIGN BENCHES

More information

100C Air Compressor Kit

100C Air Compressor Kit 10010 100C Air Compressor (standard mounting bracket, CE Spec) 10014 100C Air Compressor (no leader hose or check valve, CE Spec) 10016 100C Air Compressor (with Omega Bracket, CE Spec) IMPORTANT: It is

More information

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE February 9, 1998 Foam 101a A BLADDER TANK WITH 1. DESCRIPTION A Wet Pipe Bladder Tank Foam/Water System is a standard wet pipe automatic sprinkler system capable of discharging a foam/water solution automatically

More information

1020 Industrial Drive, Orlinda, TN fax

1020 Industrial Drive, Orlinda, TN fax Operation Manual Ultrafiltration for High Purity Distribution K-A-HPTUF Series 615-654-4441 sales@specialtyh2o.com 615-654-4449 fax TABLE OF CONTENTS Section 1 GENERAL 1.1 Warnings and Cautions... 1 1.2

More information

THE DELIVERY OF GAS SUPPLY

THE DELIVERY OF GAS SUPPLY GAS ASSIST INJECTION MOLDING THE DELIVERY OF GAS SUPPLY April 2010 www.bauerptg.com THE DELIVERY OF GAS SUPPLY Gas assist requires a source of high-pressure nitrogen gas that can be controlled and delivered

More information

200 PSI COMPRESSORS - MODEL NUMBERS

200 PSI COMPRESSORS - MODEL NUMBERS 200 PSI COMPRESSORS - MODEL NUMBERS 380C AIR COMPRESSOR KIT PART NO. 38033 480C AIR COMPRESSOR KIT PART NO. 48043 380C 480C IMPORTANT: It is essential that you and any other operator of this product read

More information

Flow meter. bellow vaporizer. APL valve. Scavenging system

Flow meter. bellow vaporizer. APL valve. Scavenging system Introductory Lecture Series: The Anesthesia Machine PORNSIRI WANNADILOK Objectives Anesthesia Machine Ventilators Scavenging Systems System Checkout 1 Flow meter ventilator bellow vaporizer Corrugated

More information

Nitrogen Tyre Inflator Owner s Manual

Nitrogen Tyre Inflator Owner s Manual Nitrogen Tyre Inflator Owner s Manual Model:PN-8890 Please read this manual carefully before attempting assembly or use. 1 Suit for: Motorcycle, Car, Light Truck, Bus Manual Model Nitrogen Tyre Inflation

More information

Purge Star & Ring Purge Systems

Purge Star & Ring Purge Systems March 2013 Operator s Manual Purge Star & Ring Purge Systems Additional instruction for Purge Star Single Hose, Purge Star Double (bypass) Hose and Ring Purge with bypass hose and gas dump valve feature.

More information

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y INSTALLATION and INSTRUCTION MANUAL for QUALITY AIR BREATHING SYSTEMS Model 50 Systems Outfitted with ABM-725 Monitor M A R T E C H S E R V I C E S C O M P A N Y OFFICE: (507) 843-4700 P.O. BOX 7079 Toll

More information

Types 749B and R130 Changeover Manifolds

Types 749B and R130 Changeover Manifolds Instruction Manual MCK-1179 Types 749B and R130 June 2012 Types 749B and R130 Changeover Manifolds TYPE HSRL-749B TYPE 64SR/122 TYPE R130/21 TYPE 749B/21 Figure 1. Changeover Manifolds and Regulator Assemblies

More information

MODEL NUMBER: P PORTABLE COMPRESSOR

MODEL NUMBER: P PORTABLE COMPRESSOR MODEL NUMBER: 44043-440P PORTABLE COMPRESSOR IMPORTANT: It is essential that you and any other operator of the product read and understand the contents of this manual before installing and using this product.

More information

GAS VALVE RETROFIT KIT Pull Through Tube Heater Models

GAS VALVE RETROFIT KIT Pull Through Tube Heater Models GAS VALVE RETROFIT KIT Pull Through Tube Heater Models DESCRIPTION: This kit is designed to replace existing Honeywell gas valves #VR8205P and #VR8205Q with White-Rodgers gas valves #36J23 and #36J58 respectively

More information

RULES OF THE OIL AND GAS PROGRAM DIVISION OF WATER RESOURCES CHAPTER DRILLING WELLS TABLE OF CONTENTS

RULES OF THE OIL AND GAS PROGRAM DIVISION OF WATER RESOURCES CHAPTER DRILLING WELLS TABLE OF CONTENTS RULES OF THE OIL AND GAS PROGRAM DIVISION OF WATER RESOURCES CHAPTER 0400-52-06 DRILLING WELLS TABLE OF CONTENTS 0400-52-06-.01 Drilling Equipment 0400-52-06-.03 Casingheads 0400-52-06-.02 Blowout Prevention

More information

Data Sheet Issue A

Data Sheet Issue A Features 1. Differential-type valve, lightweight, dependable construction. 2. Low Air Pressurized System, 10 psi -to- 26 psi (0,7 bar -to- 1,8 bar). 3. Reset externally.cover removal is not required. 4.

More information

MODEL NUMBER: P-A AUTOMATIC PORTABLE COMPRESSOR

MODEL NUMBER: P-A AUTOMATIC PORTABLE COMPRESSOR MODEL NUMBER: 45043-450P-A AUTOMATIC PORTABLE COMPRESSOR IMPORTANT: It is essential that you and any other operator of the product read and understand the contents of this manual before installing and

More information

EMERGENCY WALL MOUNTED HAND OPERATED DELUGE SHOWER

EMERGENCY WALL MOUNTED HAND OPERATED DELUGE SHOWER EMERGENCY WALL MOUNTED HAND OPERATED DELUGE SHOWER Installation, Operating & Maintenance Instructions EW1050 I00232_Mar 2016 NOTE: THIS DOCUMENT IS TO BE LEFT ONSITE WITH FACILITY MANAGER AFTER INSTALLATION

More information

D Series Air and Water Kit Part# 02550

D Series Air and Water Kit Part# 02550 D Series Air and Water Kit Part# 02550 Unpacking Please open and inspect your package upon receipt. Your package was packed with great care and all the necessary packing materials to arrive to you undamaged.

More information

450P AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES

450P AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES EXTREME SERIES PART NO. 45043 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using this product. SAVE THIS

More information

Guidance on the maintenance and inspection of fixed CO 2 fire-extinguishing systems

Guidance on the maintenance and inspection of fixed CO 2 fire-extinguishing systems Translation. Only the Danish document has legal validity. Guidance no. 9514 of 9 July 2014 issued by the Danish Maritime Authority Guidance on the maintenance and inspection of fixed CO 2 fire-extinguishing

More information

6900 Maintenance Instruction System Flush

6900 Maintenance Instruction System Flush Equipment Required FA74005 Damper Drain Tube FA16005 Cover Removal Tool FA900005 Beaker 0.25 Litre FA900003 Solvent Cleaning Bottle FA940021 Syringe Polypropylene 50 ml as required FA999045 Gloves Latex

More information

Eliminating Medical Gas Shutdowns for 10 years

Eliminating Medical Gas Shutdowns for 10 years Eliminating Medical Gas Shutdowns for 10 years Smart Tap is a tool used by hospitals. It has been used OVER 5000 TIMES to accomplish: Relocation of Bulk Gas Systems Relocation of zone valves Tie-ins of

More information

API MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks

API MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks API MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks 1. Scope This document describes procedures for determining or confirming the fill condition of

More information

Model DDX-LP Dry Pipe Valve System 8 (200mm) Features. Differential latching clapper-type, lighweight, dependable construction.

Model DDX-LP Dry Pipe Valve System 8 (200mm) Features. Differential latching clapper-type, lighweight, dependable construction. Bulletin 335 Model DDX-LP Dry Pipe Valve System 8 (200mm) Bulletin 335 Features 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Differential latching clapper-type, lighweight, dependable construction. Low Air Pressurized

More information

TECHNICAL DATA. than the water inlet pressure to the concentrate

TECHNICAL DATA. than the water inlet pressure to the concentrate Foam102a 1. DESCRIPTION The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with 3M foam concentrates. This system consists of a standard wet pipe sprinkler

More information

Setup Guide for your HVO Naked Drone

Setup Guide for your HVO Naked Drone Setup Guide for your HVO 60 + 60 Naked Drone 1 The Big Picture 1. Choose The System Location 2. Get the Power Ready 3. Get an Approved Oxygen Regulator 4. Get the Tools You ll Need 5. Unpack the crate

More information

NGP-250/500 Nitrogen Generator Quick Start Guide

NGP-250/500 Nitrogen Generator Quick Start Guide NGP-250/500 Nitrogen Generator Quick Start Guide Version: A July 2013 Potter Electric Signal Company, LLC 5757 Phantom Dr., Suite 125 P. O. Box 42037 Hazelwood, MO 63042 Phone: (314) 595-6900 Document

More information