Tirpur Area Water Supply Project A Report on Transient Modeling Study

Size: px
Start display at page:

Download "Tirpur Area Water Supply Project A Report on Transient Modeling Study"

Transcription

1 y February of 81

2 y INTRODUCTION: The report presents results from a transient modeling study conducted on the clear water transmission main of Tirpur Areas Water Supply Project, Tamilnadu, India. The main objectives of the study were: 1. To evaluate adequacy of the existing protection measures against extreme transient pressures that are likely to occur during normal shutdown, power failure and pump startup scenarios and 2. To reinforce protection measures that can withstand transient pressures resulting from occasional abnormal operating procedures i.e., less than adequate compliance to recommended pump and valve operation. BACKGROUND: There are two pumping stations (Clear Well Pump House or CWPH and Booster Station) on the clear water transmission main modeled in this study. Each station has three pumps two duty pumps and one for standby operation. The original design included protection measures for the pipeline against severe transient pressures resulting from power failure scenario in which all four pumps (two at CWPH and two at Booster Station) operating at their rated conditions get tripped. The protection included 4 one-way surge tanks, two of which are located between CPWH and Booster station (Figure 3). In addition, the original design included 91 air release valves (120 mm orifice diameter) on the pipeline to facilitate air release during pump startup operation. Although the primary purpose for these air valves is to let air out of the system during pipe filling operation, they 2 of 81

3 y can become active during normal operation if there is air entrainment in the pipeline for some unforeseen reasons. The air valves can also let the air into the pipeline when pressures in the pipeline at air valve drop below atmospheric conditions. Proper selection and sizing of these air valves becomes essential when there is a potential for air entrainment during normal operation of the pipeline (Funk et,al.,1992 and Lingireddy et.al, 2004). Improper selection and sizing could potentially lead to unwanted secondary pressure spikes which in turn could damage the pipeline either at the location where they were generated or elsewhere as the pressure waves travel through the pipeline system. Damages to the pipeline systems have been reported after the pipeline was commissioned. Some of those damages were attributed to transient generated pressures during abnormal pump operation. Much of the damage appears to be between Clearwater Pump House and Booster Station. The sluice valve that was ruptured on June 25 th, 2006 was located around a chainage of 4400m from CWPH and was between CWPH and Booster station. There were two similar incidents of sluice valve ruptures prior to June 25 th, 2006 and both locations were close to CWPH and were between CWPH and Booster station. A pressure relief valve that opens at 40m of head has been recently added at a location close to suction side of the Booster station to prevent excessive pressure rise in that area. The flow is predominantly by gravity towards the discharge end of the pipeline (last 6.3 km) and there is a standpipe arrangement at the beginning of the gravity portion of the treated water main. 3 of 81

4 y DATA SUMMARY: Data for the clear water transmission main of was obtained from HCC. Data obtained from HCC included as-built pipeline profile drawings in electronic format, intake structure and pump station details, pump control and check valves, tank and connecting pipe sizes for all four oneway surge tanks (OSTs). Figure 1 shows the schematic of the pipeline profile for the clear water transmission main. Other physical and hydraulic characteristics of the pipeline system are listed in the following. o Low water level(intake sump) o Water level at Discharge o Number of working pumps (CWPH) o Number of working pumps (BPS) : 175m : 327m : 2 (+1 standby) : 2 (+1 standby) o Pump rated speed for Both CWPH & BPS): 990 rpm o Rated discharge per pump (CWPH) : m 3 /s o Rated discharge per pump (BPS) : m 3 /s o Rated pump head (CWPH) : 108.2m o Rated pump head (BPS) : 120 o o Pump and Motor Inertia (GD 2 ) Pump and Motor Inertia (GD 2 ) o Pump efficiency (CWPH) : 89% o Pump efficiency (BPS) : 90% o Pump file : 1 o NRV closure time o Cavitation head : 360kgf-m 2 (CWPH) : 560kgf-m 2 (Booster) : 0.5 s (linear closure) : -9.5m 4 of 81

5 y 5 of 81

6 y TRANSIENT MODEL RUNS: In tune with stated objectives of the study, initial model runs were geared towards verifying adequacy of the existing protection measures. A Surge2000 model was built for the clear water transmission main based on the information obtained from HCC. Steady state analysis was carried out to ensure that the flows and pressures match the design values. Figure 2 shows steady state hydraulic gradeline (HGL) for the clear water transmission main while all 4 pumps (two at each station) are operating at their rated speed. The existing protection for the pipeline system comprises four one-way surge tanks (OSTs). These tanks were sized to protect the system against most severe transient pressures resulting from simultaneous failure of all four operating pumps. Although there are 91 air valves on the pipeline, the original design did not explicitly consider these air valves as part of baseline protection. A transient analysis was run on this model to simulate simultaneous failure of all four operating pumps. This transient model run included existing OSTs but not the air valves. Likewise, the pressure relief valve that has been recently placed on the suction side of Booster station was not included in the model. The model, however, did include the vacuum breaking arrangement located towards the discharge end of pipeline. Figure 3 shows a pressure envelope following pump trip during a 200 second transient simulation. The corresponding pressure profile from the original design report is shown in Figure 4. As evident from Figures 3 and 4, the pressure profiles from the current model run and the original design agree fairly well. Model runs pertaining to the original design allowed the pressures to drop below cavitation limit (Figure 4). To be consistent with the results reported earlier, the current model run allowed the pressures to drop below the cavitation limit as well. This is why the low pressures at certain locations shown in Figure 3 have dropped below the cavitation limit of - 9.5m. 6 of 81

7 y Figures 5 and 6 show pressure head variation at discharge headers of CWPH and Booster Station respectively, for the current model run. Figures 7 and 8 show the pump speed variation curves. Figure 9 shows pressure head variation at two representative nodes where the low pressures dropped below cavitation head. Figure 10 shows pressure head variations at OSTs. The highest pressure head over the entire system was about 130m and occurred right around the Booster Station. Based on the diameter (1400 mm) and thickness (12 mm) of the pipeline and assuming manufactured/fabricated grade C steel for pipe material, the highest allowable transient pressure for this pipeline is 180m (AWWA M11). The 12 mm thickness for the pipeline also allows it to withstand significantly large negative pressures (theoretical limit of -20m). The lowest pressures in the system were around -20m. The low pressures in the system are within the theoretical allowable pressure limits even without considering the air valves for surge protection. There are air valves at all places along the pipeline where pressures drop below zero and are expected to provide relief against low pressure conditions provided they are of good quality and are maintained in good condition. The model was updated to simulate the effect of existing two-stage air valves on the negative pressures. In addition, the cavitation head was limited to -9.5m (i.e., pressures were not allowed to drop below vapor pressure). Figure 11 shows the pressure envelope corresponding to this model run. As evident from this figure, the negative pressure condition improves without a significant impact on the positive pressures when the effect of air valves was taken into account. Based on the results presented in Figures 3 through 11, it is clearly evident that the existing OST based protection is adequate to protect the system against adverse transient pressures resulting from simultaneous failure of all four operating pumps. Since, the pressure relief valve (PRV) on the suction side of 7 of 81

8 y Booster Station is currently part of the existing pipeline system, the model was updated to incorporate the PRV and was analyzed for the worst case scenario. Figure 12 shows the pressure envelope corresponding to this model run. No undue positive pressures were noticed for this run either. Maximum pressure between CWPH and Booster Station has dropped by a few meters indicating the benefits of adding the PRV. The flowrate through the pressure relief valve is shown in Figure 13. For most pipeline systems, simultaneous failure of all operating pumps results in most severe transient pressures. Occasionally, however, other operating scenarios and events can trigger more sever pressure transients. Therefore, it is important to verify if the existing OSTs can adequately protect the pipeline system from such operating scenarios. One such scenario is a pump startup operation when the OSTs and pipeline are filled with water (e.g. after a normal pump shutdown condition and after charging the OSTs). Figure 14 shows the pressure envelope corresponding to this model run. This modeling scenario did not consider the effect of air valves on transient response. The highest pressure in the system was slightly less than 160m and it occurs on the discharge side of the Booster Station confirming the adequacy of the existing protection for pump startup condition following a normal pump shutdown operation. Next, a single pump startup operation within a few minutes of power failure condition has been simulated. Figure 15 shows the pressure envelope corresponding to this model run. This model run did not consider the influence of air valves on the transient pressures. As evident from this figure, the highest pressure is no more than 160m and occurs between the CWPH and Booster Station. Therefore, the pipeline appears to be safe for normal pump startup operation a few minutes after a pump trip event when presence of air valves is ignored. However, presence of air valves that are not equipped with surge suppressing mechanism may pose additional problems during a pump startup 8 of 81

9 y condition immediately after a pump trip event. Air entered the pipeline during a pump trip event exits through the same orifice during a pump startup event and can result in a secondary transient air slam pressure (Lingireddy et.al., 2004). Though the secondary transient may not be strong enough to damage the air valve where air slam pressure occurs, propagation of secondary pressure wave to low elevation regions may increase the pressures in those regions sufficient enough to damage the air valves and/or other devices. Transient analysis was repeated considering the existing 2-stage air valves. Figure 16 shows the pressure envelope corresponding to this model run during a 500 second transient simulation. As evident from Figure 16, pressure heads in the initial portions of the pipeline went up by nearly 50m from the previous runs. Highest pressure in the system was about 20 bars and occurs near CWPH. Note that this run included the newly installed pressure relief valve upstream of the Booster Station. Figure 17 shows pressure head variation at the first air valve location (Air-1) immediately downstream from CWPH. Figure 18 shows pressure head variation at Air-26 (chainage 13885) which is located at the highest elevation point between CWPH and Booster Station. Being at the peak location, this air valve tends to ingress most air into the pipeline during low pressure conditions. Figure 19 shows the air volume curve at this location. About 3m 3 of air enters the pipeline at this location during the pump trip event. Complete expulsion of this air occurs at 236 seconds from the start of simulation (Figure 20). Figure 21 shows the variation in flowrate at the time of complete expulsion of air which results in a fairly significant air slam pressure as seen in Figure 18 (at 236 seconds). This modeling run did not take into account any mal-functioning valves (leaking NRVs, flow bypass valves, discharge BFVs etc) at pump station that will allow continuous draining of the pipeline after the pump trip event and before starting up the pump. If such continuous draining conditions exist, the volume of air entering the pipeline would be much higher than 3m 3 and consequently much higher magnitude of flow change at the time of complete expulsion of air. Higher flow change at the time of complete expulsion results in higher air slam pressure. 9 of 81

10 y It is in this context, the use of surge suppressing air valves help reduce the air slam pressures and therefore reduce the overall positive pressures associated with rapid expulsion of unintended and unwanted air. The model from the previous run was modified replacing the existing 2-stage air valves with 200 mm 3-stage surge suppressing air valves. Figure 22 shows the pressure envelope for this simulation. Comparing pressures from this figure with those presented in Figure 16, it is evident that the use of three stage air valves of uniform size (200 mm) did not provide much relief for maximum positive pressures although they appeared to have reduced the occurrences of low pressures and cavitation conditions. Figures 23 and 24 show the pressure head and air volume curves respectively, at air valve located at highest elevation point between CWPH and Booster Station. Although the air slam pressure is slightly lower compared to 2- stage air valve case (Figure 18), it is still very significant indicating that the size of air valve at this location being too large to alleviate the air slam pressure. Other air valves, being same size, could be causing additional air slam pressures as well. Therefore, the approach of one size fits all appears to not help reduce the air slam pressures for this pipeline system. Attempts were made to optimize the air valve sizes such that the air slam pressures would be minimized and consequently minimizing the overall maximum pressures in the entire system. After several attempts, an optimal set of two and three stage air valves were arrived. Data used for these air valves came from A.R.I. Flow Control Accessories, Israel. Figure 25 shows the pressure envelope corresponding to this model run. Figure 26 shows the pressure head variation at Air-26 (air valve at peak location between CWPH and Booster Station). Air slam pressure at this location is about 25m less than the case with existing 2-stage air valves (Figure 18). Figure 27 shows the air volume curve at Air-26 and Figure 28 shows the close up view of the air volume curve at the time of complete expulsion of air. Comparing the air volume curve shown in 10 of 81

11 y Figure 28 with that in Figure 20, it is evident that the use of an optimal threestage air valve slows down the expulsion of air towards the end thereby reducing the secondary transient due to air slam. Figure 29 shows the variation in flowrate at the time of complete expulsion of air. Figure 30 shows pressure head variation at the first air valve location (Air-1) immediately downstream from CWPH. Maximum pressure at this location was brought down to 150m from about 200m corresponding to non surge-suppressing air valves. Now that the efficiency of optimal combination of 3-stage surge suppressing air valves of ARI has been established, it is important to verify if that combination (along with the existing OSTs) can also provide adequate protection against transient pressures arising from other critical operating scenarios. The following critical operating scenarios were identified and transient modeling runs were conducted to verify the sufficiency of the proposed air valve combination along with existing OSTs and Pressure Relief Valve. A. Two pumps at each station (full capacity) are working under steady state conditions and a power failure occurs tripping all 4 operating pumps simultaneously. B. Two pumps at each station (full capacity) are working under steady state conditions and a power failure occurs at CWPH tripping both of the CWPH pumps simultaneously. This calls for turning the Booster Station pumps off before the down surge generated at CWPH reaches Booster Station. Booster pumps are turned off 14 seconds (travel time between CWPH and Booster Station) after power failure at CWPH. C. Two pumps at each station (full capacity) are working under steady state conditions and a power failure occurs at Booster Station tripping both of the operating pumps simultaneously. CWPH pumps are turned off 14 seconds (travel time between CWPH and Booster Station) after power failure at Booster Station. 11 of 81

12 y D. One pump at each station is working under steady state conditions and both get tripped simultaneously. Within a few minutes both pumps are restarted one after the other. Operating Scenario A Figure 31 shows the steady state hydraulic grade line (HGL) for this pipeline system while all 4 pumps are operating at their rated speed. Figure 32 shows pressure envelope for this transient scenario (all 4 operating pumps trip simultaneously) during a 500 second simulation. Highest transient pressure in the system was about 130m (Figure 33) and the lowest pressure was about -7m. Figure 34 shows pressure head variation at a few representative nodes where the pressure drops below atmospheric pressure. Figure 35 shows pressure head variations at OSTs. As evident from these figures, the optimal combination of 3- stage air valves (along with existing OSTs and pressure relief valve) provides adequate protection for this operating scenario. Operating Scenario B Figure 36 shows the steady state hydraulic grade line (HGL) for this pipeline system while all 4 pumps are operating at their rated speed. Figure 37 shows pressure envelope for this transient scenario (Booster Pumps trip 14 seconds after CWPH pumps get tripped) during a 500 second simulation. Highest transient pressure in the system was about 130m (Figure 38) and the lowest pressure was about -7m. Figure 39 shows pressure head variation at a few representative nodes where the pressure drops below atmospheric pressure. Figure 40 shows pressure head variations at OSTs. As evident from these figures, the optimal combination of 3-stage air valves (along with existing OSTs and pressure relief valve) provides adequate protection for this operating scenario. 12 of 81

13 y Operating Scenario C Figure 41 shows the steady state hydraulic grade line (HGL) for this pipeline system while all 4 pumps are operating at their rated speed. Figure 42 shows pressure envelope for this transient scenario (CWPH trips 14 seconds after Booster Pumps get tripped) during a 500 second simulation. Highest transient pressure in the system was about 140m (Figure 43) and the lowest pressure was about -8.5m. Figure 44 shows pressure head variation at a few representative nodes where the pressure drops below atmospheric pressure. Figure 45 shows pressure head variations at OSTs. As evident from these figures, the optimal combination of 3-stage air valves (along with existing OSTs and pressure relief valve) provides adequate protection for this operating scenario. Operating Scenario D Figure 46 shows the steady state hydraulic grade line (HGL) for this pipeline system when one pump at each station is operating at its rated speed. Figure 47 shows pressure envelope for this transient scenario during a 500 second simulation. Highest transient pressure in the system was about 150m (Figure 48) and the lowest pressure was about -4m. Figure 49 shows pressure head variation at a few representative nodes where the pressure drops below atmospheric pressure. Figure 50 shows pressure head variations at OSTs. As evident from these figures, the optimal combination of 3-stage air valves (along with existing OSTs and pressure relief valve) provides adequate protection for this operating scenario. Model Runs with Air Valve Sizes Recommended by Black and Veatch: The contractor has requested to evaluate the adequacy of air valve sizes recommended by Black and Veatch International Ltd., for this pipeline project. 13 of 81

14 y Models created for different critical operating scenarios were updated with the air valve location, type and size information provided by the contractor per Black and Veatch Recommendations. Air valve characteristics provided by ARI Flow Control Systems (Israel) were employed for modeling both three-stage (air valves with anti-slam device) and two-stage valves. Nominal size for all air valves (with and without anti-slam device) was specified as 200mm. Figure 51 shows pressure envelope from the transient run corresponding to scenario B, described in the previous sections. Comparison of this pressure envelope with that from an earlier run with optimal air valve sizes (Figure 37) indicates potential cavitation conditions at several locations in the system when uniform size air valves are used. Although, the thickness of pipeline allows it to withstand higher negative pressures (well below the vapor pressure of water), limiting the high negative pressures allows much smoother operation and minimizes unwanted secondary transients due to collapse of vapor cavities. After several attempts, occurrences of extremely low pressures conditions were minimized by replacing five of the 200mm anti-slam air valves (AV-13, AV-25, AV-35, AV-50, AV-79) with 150mm anti-slam air valves. Figures 52 through 55 show the corresponding pressure envelopes for scenarios A-D. DYNAMIC CHARACTERISTIC OF CHECK VALVES: Although it is difficult to model the exact closure characteristics of a check valve for lack of reliable closure characteristics data, one could verify the validity of check valve modeling assumptions with the help of manufacturer suggested deceleration vs. reverse velocity data. The proposed check valves for this project are VAG SKR slanted seat valves. The manufacturer suggested deceleration vs. reverse velocity data for these check valves is shown in Figure 56. Reverse velocity at the time of complete closure of check valve can be assessed based 14 of 81

15 y on the deceleration at the time of flow reversal. Deceleration at the time of flow reversal can be determined by analyzing Surge2000 model of the pipeline system with NO check valves at pumps thereby allowing flow reversal. Pumps at CWPH: Figure 57 shows the flowrate at pump discharge (with NO check valves) following pump trip, along with the corresponding deceleration of flow. From Figure 57, the deceleration at the time of flow reversal is roughly 0.2 m/s 2. This deceleration may be used to determine the potential reverse flow velocity at the time of complete closure of check valve from manufacturer suggested data. For a deceleration of 0.2 m/s 2 at the time of flow reversal, SKR valve gives a reverse velocity of about 0.02 m/s at check valve closure (Figure 58). Knowing the celerity of MS pipe (1200m/s) and the velocity change of 0.02 m/s, the change in pressure head (pressure spike) at the time of complete closure of check valve may be determined using Joukowsky s equation as H = (c/g) V H = (1200/9.81) 0.02 H = 2.45m This change in pressure head at the time of complete closure may be compared with change in pressure computed by the Surge2000 model to determine if the assumed check valve closure characteristics are reasonable. Figure 59 shows the flow and head variation at pump discharge for the first few seconds of Surge2000 simulation. It may be noted that all Surge2000 models for the pipe 15 of 81

16 y system under consideration used a 0.5 second linear closure time for the check valves. From Figure 59, the change in pressure head at the time of complete check valve closure (zero flowrate though the pump) is around 5m. Since the change in pressure head computed by the Surge2000 model is significantly higher than the value computed from the deceleration characteristics (2.45m), the assumed check valve closure characteristics provide conservative (worse than what s possible in reality) estimates for the transient pressures. So the assumed linear closure characteristics for the check valves will results in conservative estimates for the transient pressures as the actual closure characteristics reduce the flow area very rapidly in the first half of the closure time. Pumps at Booster Station: Figure 60 shows the flowrate at pump discharge (with NO check valves) following pump trip, along with the corresponding deceleration of flow. From Figure 60, the deceleration at the time of flow reversal is roughly 0.2 m/s 2. This deceleration may be used to determine the potential reverse flow velocity at the time of complete closure of check valve from manufacturer suggested data. For a deceleration of 0.2 m/s 2 at the time of flow reversal, SKR valve gives a reverse velocity of about 0.02 m/s at check valve closure (Figure 61). Knowing the celerity of MS pipe (1200m/s) and the velocity change of 0.02 m/s, the change in pressure head (pressure spike) at the time of complete closure of check valve may be determined using Joukowsky s equation as H = (c/g) V 16 of 81

17 y H = (1200/9.81) 0.02 H = 2.45m This change in pressure head at the time of complete closure may be compared with change in pressure computed by the Surge2000 model to determine if the assumed check valve closure characteristics are reasonable. Figure 62 shows the flow and head variation at pump discharge for the first few seconds of Surge2000 simulation. It may be noted that all Surge2000 models for the pipe system under consideration used a 0.5 second linear closure time for the check valves. From Figure 62, the change in pressure head at the time of complete check valve closure (zero flowrate though the pump) is around 12m. Since the change in pressure head computed by the Surge2000 model is significantly higher than the value computed from the deceleration characteristics (2.45m), the assumed check valve closure characteristics provide conservative (worse than what s possible in reality) estimates for the transient pressures. So the assumed linear closure characteristics for the check valves will results in conservative estimates for the transient pressures as the actual closure characteristics reduce the flow area very rapidly in the first half of the closure time. SUMMARY: The existing protection based on the one-way surge tanks appears to be more than adequate for protecting the pipeline system from adverse transient pressure generated during a pump trip event. Abnormal operation and inadequate maintenance conditions that may results in excessive accumulation of air at peak points may result in secondary pressure transients from air slam pressures during a pump startup event immediately after a pump trip event. Pressures in excess of 17 of 81

18 y 20 bars were noted close to the clear water pump station as a result of air slam pressures at peak air valve locations. Use of one size 3-stage surge suppressing air valve did not appear to help reduce the air slam pressures. An optimal combination of sizes for 3-stage surge suppressing air valve provided adequate relief for different operating scenarios. Use of 200mm two-stage and three-stage (anti-slam) air valves at all locations as recommended by Black and Veatch provide adequate protection to the pipeline against high pressure transients. However, they appear to cause cavitation and other low pressure conditions at several locations. Although the pipeline is capable of withstanding very high negative pressures (based on its thickness), it is advisable to avoid cavitation and the associated secondary transient pressure problems. Replacing five of the anti-slam 200mm air valves (AV-13, AV-25, AV-35, AV-50, AV-79) with 150mm anti-slam air valves appear to minimize the extreme low pressure conditions thereby allowing much smother operation. The VAG SKR Slanted disk check valves provide satisfactory operation against flow reversal through pumps. RECOMMENDATIONS: Based on an extensive transient modeling runs, the study recommends the use 200mm two-stage and three-stage (anti-slam) air valves as recommended by Black and Veatch except for the air valves at AV-13, AV-25, AV-35, AV-50, AV- 79. At these locations, 150mm anti-slam valves are recommended in place of 200mm anti-slam valves to minimize the occurrence of extensive low pressure conditions. The recommended protection is in addition to the OST protection per original design and a newly installed pressure relief valve. The recommended protection can only work if the OSTs are maintained properly and are ensured to 18 of 81

19 y have water to their design capacity prior to running all the pumps at their rated speed. REFERENCES: Funk, J.E., Wood, D.J., Lingireddy, S. and D.C. Denger, Pressure Surges due to Rapid Expulsion of Air, International Conference on Unsteady Flow and Fluid Transients, Sept-Oct 1992, Durham, England. Lingireddy, S., Wood, D.J., and Zloczower, N. (2004) Pressure Surges in Pipeline Systems Due to Air Release. Jl. American Water Works Association, 96 (7), of 81

20 Elevation (m) System Profile 0 1.0E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Figure 1. Schematic of clear water transmission main profile 20 of 81

21 HGL (m) System Profile 0 1.0E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Figure 2. Pipeline schematic between CWPH and Booster Station. 21 of 81

22 HGL (m) 380 Baseline Model E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Figure 3. Max/Min Pressure Envelope with Existing OST Protection (Pressures allowed to drop below vapor pressure) 22 of 81

23 Figure 4. Max/Min Pressure Profile Original Design (obtained from HCC) 23 of 81

24 Head (m) Time (s) Figure 5. Pressure Head Variation on Discharge Side of CWPH (Existing OST Protection) 24 of 81

25 Head (m) Time (s) Figure 6. Pressure Head Variation on Discharge Side of Booster Station (Existing OST Protection) 25 of 81

26 Speed (rpm) Time (s) Figure 7. Pump Speed Variation at CWPH (Existing OST Protection) 26 of 81

27 Speed (rpm) Time (s) Figure 8. Pump Speed Variation at Booster Station (Existing OST Protection) 27 of 81

28 Head (m) Time (s) J-110 J-91 Figure 9. Pressure Head Variation at Representative Nodes where Pressures Dropped Below Cavitation Head 28 of 81

29 Head (m) Time (s) OST-1 OST-4 OST-3 OST-2 Figure 10. Water Level Drawdown Curves for Different OSTs 29 of 81

30 HGL (m) 380 Baseline Model (OSTs + Air Valves) E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 11. Max/Min Pressure Envelope with Existing OST Protection + Air Valves (Low Pressures were Limited to Vapor Pressure) 30 of 81

31 HGL (m) 380 Baseline Model (OSTs + Air Valves + PRV) E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 12. Max/Min Pressure Envelope with Existing OST Protection + Air Valves + Pressure Relief Valve 31 of 81

32 Flow (m^3/s) 1.2 Flow Through PRV Time (s) Figure 13. Flow through Pressure Relief Valve 32 of 81

33 HGL (m) 400 Pump Startup E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 14. Pressure Envelope for Pump Startup Operation (OSTs and Pipeline are filled with water) 33 of 81

34 HGL (m) _ E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 15. Pressure envelope ignoring existing Air Valves single pump startup following pump trip 34 of 81

35 Pressure (kpa) _ E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 16. Pressure envelope WITH existing Air Valves pump startup following pump trip 35 of 81

36 Head (m) 200 Air Time (s) Figure 17. Pressure head variation at Air-1 (chainage 361) 36 of 81

37 Head (m) 90 Air Time (s) Figure 18. Pressure head variation at Air-26 (chainage 13885) 37 of 81

38 Volume (m^3) 3.5 Air Time (s) Figure 19. Air volume curve for Air-26 (chainage 13885) 38 of 81

39 Volume (m^3) Air Time (s) Figure 20. Close up view of air volume curve at the time of complete expulsion of air 39 of 81

40 Flow (CMS) 1.0 Air Time (s) Figure 21. Variation in flowrate in the pipeline at Air-26 at the time of complete expulsion of air 40 of 81

41 HGL (m) _ E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 22. Pressure envelope with all 200 mm 3-stage air valves 41 of 81

42 Head (m) 90 Air Time (s) Figure 23. Pressure head variation at Air-26 (200 mm 3-stage air valves) 42 of 81

43 Volume (m^3) 3.5 Air Time (s) Figure 24. Air volume curve for Air-26 (200 mm 3-stage air valves) 43 of 81

44 HGL (m) Optimal Sizes for 3-Stage Surge Suppressing Air Valves E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Time Lower Limit Cavitation Figure 25. Pressure envelope with optimal combination of 3-stage air valves 44 of 81

45 Head (m) 70 Air Time (s) Figure 26. Pressure head variation at Air-26 (optimal combination of 3-stage air valves) 45 of 81

46 Volume (m^3) 3.0 Air Time (s) Figure 27. Air volume curve for Air-26 (optimal combination of 3-stage air valves) 46 of 81

47 Volume (m^3) 2.0 Air Time (s) Figure 28. Close up view of air volume curve at the time of complete expulsion of air 47 of 81

48 Flow (m^3/s) 1.0 Air Time (s) Figure 29. Variation in flowrate in pipeline at Air-26 at the time of complete expulsion of air 48 of 81

49 Head (m) 160 Air Time (s) Figure 30. Pressure head variation at Air-1(optimal combination of 3-stage air valves) 49 of 81

50 HGL (m) 450 Steady State E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Figure 31. Steady State HGL for Operating Scenario A 50 of 81

51 HGL (m) 450 _ E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 32. Pressure envelope for operating scenario A 51 of 81

52 Head (m) 140 Booster Pump Discharge Time (s) Figure 33. Pressure head variation at Booster Pump discharge (highest pressure in the system occurs at this node) 52 of 81

53 Head (m) Time (s) J-170 J-177 J-178 Figure 34. Pressure head variation at a few representative nodes where the lowest pressure dropped below atmospheric pressure. 53 of 81

54 Head (m) 26 OST Water Levels Time (s) OST-1 OST-2 OST-3 OST-4 Figure 35. Water Level Drawdown Curves for OSTs 54 of 81

55 HGL (m) 450 _ E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Time Lower Limit Cavitation Figure 36. Steady State HGL for Operating Scenario B 55 of 81

56 HGL (m) 450 _ E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 37. Pressure envelope for operating scenario B 56 of 81

57 Head (m) 160 Booster Pump Discharge Time (s) Figure 38. Pressure head variation at Booster Pump discharge (highest pressure in the system occurs at this node) 57 of 81

58 Head (m) Time (s) J-223 J-292 Figure 39. Pressure head variation at a few representative nodes where the lowest pressure dropped below atmospheric pressure. 58 of 81

59 Head (m) 26 OST Water Levels Time (s) OST-1 OST-2 OST-3 OST-4 Figure 40. Water Level Drawdown Curves for OSTs 59 of 81

60 HGL (m) 450 Steady State E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Figure 41. Steady State HGL for Operating Scenario C 60 of 81

61 HGL (m) 450 Min and Max E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 42. Pressure envelope for operating scenario C 61 of 81

62 Head (m) 160 Chainage = 1000m Time (s) Figure 43. Pressure head variation at Booster Pump discharge (highest pressure in the system occurs at this node) 62 of 81

63 Head (m) Time (s) J-118 J-309 J-626 J-66 Figure 44. Pressure head variation at a few representative nodes where the lowest pressure dropped below atmospheric pressure. 63 of 81

64 Head (m) Time (s) OST-1 OST-2 OST-3 OST-4 Figure 45. Water Level Drawdown Curves for OSTs 64 of 81

65 HGL (m) 400 Steady State E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Figure 46. Steady State HGL for Operating Scenario D 65 of 81

66 HGL (m) E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 47. Pressure envelope for operating scenario D 66 of 81

67 Head (m) Time (s) Figure 48. Pressure head variation at Booster Pump discharge (highest pressure in the system occurs at this node) 67 of 81

68 Head (m) Time (s) J-178 J-223 J-66 Figure 49. Pressure head variation at a few representative nodes where the lowest pressure dropped below atmospheric pressure. 68 of 81

69 Head (m) Time (s) OST-1 OST-4 OST-3 OST-2 Figure 50. Water Level Drawdown Curves for OSTs 69 of 81

70 HGL (m) 400 Pressure Envelope Cavitation conditions E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 51. Pressure envelope for operating scenario B with 200mm size two and three stage air valves recommended by Black and Veatch 70 of 81

71 HGL (m) 400 _ E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 52. Pressure envelope for operating scenario A 71 of 81

72 HGL (m) 400 Pressure Envelope E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 53. Pressure envelope for operating scenario B 72 of 81

73 HGL (m) 400 Pressure Envelope E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 54. Pressure envelope for operating scenario C 73 of 81

74 HGL (m) 450 Max/Min Pressure Head Envelope E+4 2.0E+4 3.0E+4 4.0E+4 5.0E+4 Distance (m) Pipeline Envelope Min Max Lower Limit Cavitation Figure 55. Pressure envelope for operating scenario D 74 of 81

75 Figure 56. Dynamic characteristics of VAG non-return valves (courtesy: VAG) 75 of 81

76 Decceleration (m/s^2) Flowrate (m^3/s) Decceleration Calculations Decceleration(m/s^2) Flowrate(m^3/s) Flow Reversal Point (No CV at Pump) Decceleration = 0.25m/s^ Time (s) -0.2 Figure 57. Flow deceleration at pump discharge following pump trip pumps were modeled with NO check valves(cwps) 76 of 81

77 Reverse Velocity = 0.02m/s Deceleration = 0.25m/s 2 Figure 58. Reverse velocity based on calculated deceleration(cwps) 77 of 81

78 Head (m) Flowrate (m^3/s) Head Increase due to CV Closure Head(m) Flowrate(m^3/s) Check Valve Closure Head Increase = 5m Time (s) -0.2 Figure 59. Pressure head variation from Surge2000 model pumps modeled with check valves (CWPH) 78 of 81

79 Decceleration (m/s^2) Flowrate (m^3/s) Decceleration Calculations Flow Reversal Point (No CV at Pump) Decceleration(m/s^2) Flowrate(m^3/s) Decceleration = 0.2m/s^2 0-4 Time (s) -0.2 Figure 60. Flow deceleration at pump discharge following pump trip pumps were modeled with NO check valves(booster) 79 of 81

80 Reverse Velocity = 0.02m/s Deceleration = 0.2m/s 2 Figure 61. Reverse velocity based on calculated deceleration(booster Station) 80 of 81

81 Head (m) Flowrate (m^3/s) Head Increase due to CV Closure Head(m) 0.8 Flowrate(m^3/s) Head Increase = 12m Check Valve Closure Time (s) Figure 62. Pressure head variation from Surge2000 model pumps modeled with check valves (Booster) 81 of 81

Journal of Applied Fluid Transients, Vol 1-1, April 2014 (3-1)

Journal of Applied Fluid Transients, Vol 1-1, April 2014 (3-1) Modeling and Field Verification Study of Air Slam Conditions on kalanit Pipeline System By Yiftach Brunner & Sathish Kumar ir valves are integral part of long water transmission mains and are essential

More information

Transient Analysis and Design Considerations for Hydraulic Pipelines. Jonathan Funk, EIT

Transient Analysis and Design Considerations for Hydraulic Pipelines. Jonathan Funk, EIT Transient Analysis and Design Considerations for Hydraulic Pipelines Jonathan Funk, EIT Transient Analysis 2 Objectives Develop an intuitive understanding of water hammer and transient response Present

More information

UNIT 15 WATER HAMMER AND SURGE TANKS

UNIT 15 WATER HAMMER AND SURGE TANKS UNT 15 WATER HAMMER AND SURGE TANKS Structure 15.1 ntroduction Objectives 15.2 Water Hammer 15.2.1 Expression for Rise in Pressure 15.3 Rapid Acceleration of Flow 15.4 Surge Tanks 15.5 Summary 15.6 Keywords

More information

Appendix M. Hydraulic Transient Analysis

Appendix M. Hydraulic Transient Analysis Water Storage and Distribution Master Plan City of Barrie October 2013 Final Appendix M Hydraulic Transient Analysis Project Number: TP110135 Appendices 131-20095-00 Wednesday October 9th, 2013 Paul Smeltzer

More information

Suppress Your Surges: Surge Suppression Fundamentals. April 13, 2017

Suppress Your Surges: Surge Suppression Fundamentals. April 13, 2017 Suppress Your Surges: Surge Suppression Fundamentals April 13, 2017 How Bad Can Waterhammer Really Be? 2 Workshop Agenda What is waterhammer? Causes of waterhammer Instantaneous surge pressures Surges

More information

PRESSURE SURGES IN PIPELINES

PRESSURE SURGES IN PIPELINES CHAPTER 4 PRESSURE SURGES IN PIPELINES 4.1 FEATURES OF PRESSURE SURGE In the past, water engineers were facing problems with repeated pipe bursts, failing seals etc. They termed the cause of failure as

More information

Susceptibility of Distribution Systems to Negative Pressure Transients. Presenters: Kala Fleming and Mark Le Chevallier Moderator: Jian Zhang

Susceptibility of Distribution Systems to Negative Pressure Transients. Presenters: Kala Fleming and Mark Le Chevallier Moderator: Jian Zhang Susceptibility of Distribution Systems to Negative Pressure Transients Presenters: Kala Fleming and Mark Le Chevallier Moderator: Jian Zhang Housekeeping Please mute your phone lines Type in questions

More information

CASE STUDY. Elvington To Brayton Barff Air valve replacement Program

CASE STUDY. Elvington To Brayton Barff Air valve replacement Program CASE STUDY Elvington To Brayton Barff Air valve replacement Program Vent-O-Mat Anti-Shock Air valves have helped Yorkshire Water reduce maintenance costs, reduces surge and improve flows in their trunk

More information

Injector Dynamics Assumptions and their Impact on Predicting Cavitation and Performance

Injector Dynamics Assumptions and their Impact on Predicting Cavitation and Performance Injector Dynamics Assumptions and their Impact on Predicting Cavitation and Performance Frank Husmeier, Cummins Fuel Systems Presented by Laz Foley, ANSYS Outline Overview Computational Domain and Boundary

More information

MITIGATING PIPE AND RISER HYDRAULIC PIPELINE ISSUES WITH THE I-RISER PLUS

MITIGATING PIPE AND RISER HYDRAULIC PIPELINE ISSUES WITH THE I-RISER PLUS 24 TH July 2013 MITIGATING PIPE AND RISER HYDRAULIC PIPELINE ISSUES WITH THE I-RISER PLUS Vern Costelow Business Development Consultant AWMA Water Control Solutions INTRODUCTION Surface irrigation is still

More information

Tutorial. BOSfluids. Relief valve

Tutorial. BOSfluids. Relief valve Tutorial Relief valve The Relief valve tutorial describes the theory and modeling process of a pressure relief valve or safety valve. It covers the algorithm BOSfluids uses to model the valve and a worked

More information

DAV - P. Product Catalogue DAV - P. Air release & Vacuum Break Valves. (Plastic Air Valves) DAV - P. Edition 2012

DAV - P. Product Catalogue DAV - P. Air release & Vacuum Break Valves. (Plastic Air Valves) DAV - P. Edition 2012 Product Catalogue DAV - P DAV - P Air release & Vacuum Break Valves Edition 1 DAV - P (Plastic Air Valves) DAV Series Overview General The presence of trapped air in a pressurized pipeline can have serious

More information

PROVING THAT BLADDER SURGE TANKS CURED EXCESSIVE SURGE CONDITIONS IN A 30 FORCE MAIN

PROVING THAT BLADDER SURGE TANKS CURED EXCESSIVE SURGE CONDITIONS IN A 30 FORCE MAIN Background PROVING THAT BLADDER SURGE TANKS CURED EXCESSIVE SURGE CONDITIONS IN A 30 FORCE MAIN Bo, P.E., Hazen and Sawyer, P.C. Sean FitzGerald, P.E., Hazen and Sawyer, P.C. The Sanitation District No.

More information

Laboratory studies of water column separation

Laboratory studies of water column separation IOP Conference Series: Materials Science and Engineering OPEN ACCESS Laboratory studies of water column separation To cite this article: R Autrique and E Rodal 2013 IOP Conf. Ser.: Mater. Sci. Eng. 52

More information

PIPELINE DESIGN, OPERATION AND MAINTENANCE COURSE CONTINUING PROFESSIONAL DEVELOPMENT RESULTS SHEET

PIPELINE DESIGN, OPERATION AND MAINTENANCE COURSE CONTINUING PROFESSIONAL DEVELOPMENT RESULTS SHEET E1 BASIC PIPELINE DESIGN Question Description Solution E1Q1 Calculated pipe diameter = Commercial diameter = Pipe material = 283 mm 315 mm mpvc E1Q2 E1Q3 Maximum pressure downstream of pump based on calculated

More information

Courses of Instruction: Controlling and Monitoring of Pipelines

Courses of Instruction: Controlling and Monitoring of Pipelines Courses of Instruction: Controlling and Monitoring of Pipelines Date December 2010 Dr. Peter Eschenbacher Partner Angergraben 4 85250 Altomünster Germany Tel. +49-(0)8254 / 99 69 57 Fax +49-(0)8254 / 99

More information

Selecting Controls for Water Distribution Systems

Selecting Controls for Water Distribution Systems Utah State University DigitalCommons@USU Reports Utah Water Research Laboratory January 1994 Selecting Controls for Water Distribution Systems J. Paul Tullis Follow this and additional works at: https://digitalcommons.usu.edu/water_rep

More information

S0ME CONSIDERATIONS IN SELECTION OF SURGE PROTECTION EQUIPMENT.

S0ME CONSIDERATIONS IN SELECTION OF SURGE PROTECTION EQUIPMENT. 1 S0ME CONSIDERATIONS IN SELECTION OF SURGE PROTECTION EQUIPMENT. PAL TELLE Bsc (Mech) Eng, MBL Ultra Control Valves cc SYNOPSIS Most potential problems experienced on pipelines can be overcome by careful

More information

Transient Analyses In Relief Systems

Transient Analyses In Relief Systems Transient Analyses In Relief Systems Dirk Deboer, Brady Haneman and Quoc-Khanh Tran Kaiser Engineers Pty Ltd ABSTRACT Analyses of pressure relief systems are concerned with transient process disturbances

More information

Hydraulic transients, also known as pressure

Hydraulic transients, also known as pressure FWRJ Surge Protections: Modeling vs. Design vs. Construction Jinsheng Huo Hydraulic transients, also known as pressure surge or water hammer, are the timevarying phenomena that occur when the equilibrium

More information

Product Catalogue DAV - P DAV - P. Air release & Vacuum Break Valves. (Plastic Air Valves) DAV - P

Product Catalogue DAV - P DAV - P. Air release & Vacuum Break Valves. (Plastic Air Valves) DAV - P Product Catalogue DAV - P DAV - P Air release & Vacuum Break Valves DAV - P (Plastic Air Valves) DAV Series??? Overview General The presence of trapped air in a pressurized pipeline can have serious effects

More information

Theory, Application, and Sizing of Air Valves

Theory, Application, and Sizing of Air Valves VM AV/WP White Paper Theory, Application, and Sizing of Air Valves Table of Contents Introduction...................... 2 Three Basic Types of Air Valves....... 2 Air Release Valves................. 3

More information

2016 Webinar Sponsors

2016 Webinar Sponsors Copyright 2016 American Water Works Association 2016 Webinar Sponsors 2 Please consider the environment before printing. 1 Webinar Moderator Alex Gerling ReuseEngineer American Water Works Association

More information

Theory, Applications and Sizing of Air Valves

Theory, Applications and Sizing of Air Valves Practice + Operations Theory, Applications and Sizing of Air Valves Val-Matic Valve & Mfg. Corp. When air is allowed to accumulate in pressurized pipelines, efficiency is sacrificed and serious damage

More information

RESIDENTIAL WATER DISTRIBUTION

RESIDENTIAL WATER DISTRIBUTION RESIDENTIAL WATER DISTRIBUTION This case study demonstrates the steady-state simulation of the fresh water (drinking water) reticulation system in a small village. WATER RETICULATION Page1 WATER RETICULATION

More information

EN M '

EN M ' THE AMERICAN SOCIETY OF MECHANICAL ENGINEERS 345 E. 47th St New York, N.Y. 10017 The Society shall not be responsible for statements or opinions advancedin papers or &Scission at meetings of the Society

More information

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply 4.1.1 General The primary function of a system for handling fuel oil is to transfer oil from the storage tank to the oil burner at specified conditions

More information

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE ractical Guide The following article was published in ASHRAE Journal, March 2003. Copyright 2003 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational

More information

Water Hammer In Irrigation Systems 1

Water Hammer In Irrigation Systems 1 CIR828 1 G. A. Clark and D. Z. Haman 2 Irrigation system design includes pump sizing and selection, valve sizing and selection, and pipe sizing as well as the proper selection and placement of many other

More information

ANTI SHOCK RELIEF VALVE

ANTI SHOCK RELIEF VALVE ANTI SHOCK RELIEF VALVE Wheeler Road Coventry CV3 4LA England Brüsseler Allee 2 D-41812 Erkelenz Tel. +44(0)2476-217-400 Fax +44(0)2476-217-488 Tel. +49(0)24 31-80 91-0 Fax +49(0)24 31-80 91-19 www.sunhydraulics.com

More information

Steam generator tube rupture analysis using dynamic simulation

Steam generator tube rupture analysis using dynamic simulation Steam generator tube rupture analysis using dynamic simulation Heat Exchangers are used to transfer heat from a hot fluid to a cold fluid. Most of the times these fluids are available at different pressures

More information

my SYSTEM A guide to common applications in water distribution systems

my SYSTEM A guide to common applications in water distribution systems my SYSTEM A guide to common applications in water distribution systems WWW.SINGERVALVE.COM INDEX This short guide is intended to offer guidance on some of the common problems, applications and questions

More information

Experimental investigation of the check valve behaviour when the flow is reversing

Experimental investigation of the check valve behaviour when the flow is reversing EPJ Web of Conferences, (7) DOI:./ epjconf/7 EFM Experimental investigation of the valve behaviour when the flow is reversing D. Himr a,v.habán, M. Hudec, and V. Pavlík Brno University of Technology, Faculty

More information

CFD Analysis of the Anti-Surge Effects by Water Hammering

CFD Analysis of the Anti-Surge Effects by Water Hammering IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS CFD Analysis of the Anti-Surge Effects by Water Hammering To cite this article: Tae-oh Kim et al 2015 IOP Conf. Ser.: Mater. Sci.

More information

SINGER MODEL 106/206-RPS-L&H

SINGER MODEL 106/206-RPS-L&H DESCRIPTION: Model 106/206-RPS-L&H dissipates surges caused by power failure to pumps. The valve anticipates the surge by opening on low line pressure associated with sudden stopping of pumps. This assures

More information

Sizing Pulsation Dampeners Is Critical to Effectiveness

Sizing Pulsation Dampeners Is Critical to Effectiveness Sizing Pulsation Dampeners Is Critical to Effectiveness Pressure variation is an important consideration when determining the appropriate size pulsation dampener needed for an application. by David McComb,

More information

A centrifugal pump consists of an impeller attached to and rotating with the shaft and a casing that encloses the impeller.

A centrifugal pump consists of an impeller attached to and rotating with the shaft and a casing that encloses the impeller. Centrifugal pump How centrifugal pumps work A centrifugal pump consists of an impeller attached to and rotating with the shaft and a casing that encloses the impeller. In centrifugal pump, liquid is forced

More information

Safety. April 2018 Supersedes all previous publications 2018 Chevron Phillips Chemical Company LP

Safety. April 2018 Supersedes all previous publications 2018 Chevron Phillips Chemical Company LP Technical Note 802 Leak Testing of Polyethylene Pipe For Municipal and Industrial Applications Part 1 Pre-Test Considerations Leak testing may be used to find leaks in a newly constructed or newly modified

More information

IFS NUVENT SERIES IWF FOR POTABLE WATER ANTI SLAM AIR RELEASE AND VACUUM BREAK AIR VALVES

IFS NUVENT SERIES IWF FOR POTABLE WATER ANTI SLAM AIR RELEASE AND VACUUM BREAK AIR VALVES IFS NUVENT SERIES IWF FOR POTABLE WATER ANTI SLAM AIR RELEASE AND VACUUM BREAK AIR VALVES CONTENTS About IFS High volume air discharge Curves and operation Anti slam air discharge Curves and operation

More information

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS SEC Project No. 1803007-000 November 20, 2006 TABLE OF CONTENTS I. ABSTRACT...1 II. INTRODUCTION...1 III. HISTORY...2 IV. VARIABLE SPEED

More information

Application Worksheet

Application Worksheet Application Worksheet All dimensions are nominal. Dimensions in [ ] are in millimeters. Service Conditions Medium Through Valve: Required C v : Temperature Maximum: Minimum: Normal: Flow Maximum: Minimum:

More information

CONTROL VALVE WHAT YOU NEED TO LEARN?

CONTROL VALVE WHAT YOU NEED TO LEARN? CONTROL VALVE WHAT YOU NEED TO LEARN? i) The control valve characteristics refers to the relationship between the volumetric flowrate F (Y-axis) through the valve AND the valve travel or opening position

More information

Wastewater combination air valve in stainless steel AISI 316 Mod. SCS

Wastewater combination air valve in stainless steel AISI 316 Mod. SCS Wastewater combination air valve in Mod. SCS The air valve guarantees the proper operation of sewage/industrial lines allowing the entrance of large quantity of air in case of pipe bursting or draining,

More information

TROUBLESHOOTING GUIDELINES

TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES PROBLEM: Performance 1. The most common problem in this area comes from inadequate flow to the LAKOS Separator(s). All LAKOS Separators operate within a prescribed flow range

More information

BACK PRESSURE / SUSTAINING

BACK PRESSURE / SUSTAINING In many liquid piping systems, it is vital that line pressure is maintained within relatively narrow limits. This is the function of the 108 Pressure Relief / Back Pressure Series of the OCV control valves.

More information

DAV - MP DAV - MP. Metallic-Shield Air Valves. Product Catalogue. (Metallic-Shield Air Valves) DAV - MP

DAV - MP DAV - MP. Metallic-Shield Air Valves. Product Catalogue. (Metallic-Shield Air Valves) DAV - MP DAV - MP Metallic-Shield Air Valves Product Catalogue DAV - MP DAV - MP (Metallic-Shield Air Valves) Edition 9/ DAV Series DAV-MP Overview General The presence of trapped air in a pressurized pipeline

More information

This portion of the piping tutorial covers control valve sizing, control valves, and the use of nodes.

This portion of the piping tutorial covers control valve sizing, control valves, and the use of nodes. Piping Tutorial A piping network represents the flow of fluids through several pieces of equipment. If sufficient variables (flow rate and pressure) are specified on the piping network, CHEMCAD calculates

More information

1.2 Example 1: A simple hydraulic system

1.2 Example 1: A simple hydraulic system Note: It is possible to use more than one fluid in the Hydraulic library. This is important because you can model combined cooling and lubrication systems of a library. The hydraulic library assumes a

More information

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER P: REFERENCE OPERATING CONDITION STUDIES (PCC)

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER P: REFERENCE OPERATING CONDITION STUDIES (PCC) PAGE : 1 / 11 1. PASSIVE SINGLE FAILURE ANALYSIS The aim of the accident analysis in Chapter P is to demonstrate that the safety objectives have been fully achieved, despite the most adverse single failure.

More information

22. Specialty Valves.

22. Specialty Valves. 22. Specialty Valves. a. Types of Specialty Valves. 1) Use of the following specialty valves is covered in this section: Altitude Valve, Pressure Reducing Valve, Pressure Relief Valve, Swing Check Valve,

More information

BACK PRESSURE / SUSTAINING

BACK PRESSURE / SUSTAINING SPECIFICATIONS DIMENSIONS In many liquid piping systems, it is vital that line pressure is maintained within relatively narrow limits. This is the function of the 108 Pressure Relief / Back Pressure Series

More information

Improve Reliability of Turbomachinery Lubrication and Sealing Systems

Improve Reliability of Turbomachinery Lubrication and Sealing Systems Improve Reliability of Turbomachinery Lubrication and Sealing Systems Fisher Pressure Control Solutions For Turbomachinery Applications Protect the integrity of your Turbomachinery support system Turbomachinery

More information

TUTORIAL. NPSHA for those who hate that stuffy word. by Jacques Chaurette p. eng. copyright 2006

TUTORIAL. NPSHA for those who hate that stuffy word. by Jacques Chaurette p. eng.  copyright 2006 TUTORIAL NPSHA for those who hate that stuffy word by Jacques Chaurette p. eng. www.lightmypump.com copyright 2006 page.2 NPSHA for those who hate that stuffy word This article follows the same approach

More information

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump.

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump. Exercise 2-3 Centrifugal Pumps EXERCISE OBJECTIVE In this exercise, you will become familiar with the operation of a centrifugal pump and read its performance chart. You will also observe the effect that

More information

Asheville s Fairview Water System Improvements: from Modeling to Contract Documents. April 19, 2016 Meg Roberts, PE

Asheville s Fairview Water System Improvements: from Modeling to Contract Documents. April 19, 2016 Meg Roberts, PE Asheville s Fairview Water System Improvements: from Modeling to Contract Documents April 19, 2016 Meg Roberts, PE City of Asheville Water Distribution System Customer elevations range 1,950 feet to 3,650

More information

Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events

Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events K. Takase 1), H. Akimoto 1) 1) Japan Atomic Energy Research Institute (JAERI),

More information

Evaluating Surge Potential in CSO Tunnels

Evaluating Surge Potential in CSO Tunnels 14 Evaluating Surge Potential in CSO Tunnels Karen E. Ridgway Tunnels are being proposed to control combined sewer overflow (CSO) in numerous cities in the United States and Canada. The tunnels are intended

More information

NORMAL OPERATING PROCEDURES Operating Parameter Information

NORMAL OPERATING PROCEDURES Operating Parameter Information Operating Parameter Information Each operator performing the normal operating procedures (routine checks) of the facility should be familiar with the current normal operating parameters of all systems

More information

Pigging as a Flow Assurance Solution Avoiding Slug Catcher Overflow

Pigging as a Flow Assurance Solution Avoiding Slug Catcher Overflow Pigging as a Flow Assurance Solution Avoiding Slug Catcher Overflow Aidan O'Donoghue, Pipeline Research Limited, Glasgow, UK This paper sets out to provide an initial method of assessing the bypass requirements

More information

Numerical simulation of the ALBA s synchrotron cooling system response to pump start-up and shut-down Page 1

Numerical simulation of the ALBA s synchrotron cooling system response to pump start-up and shut-down Page 1 Numerical simulation of the ALBA s synchrotron cooling system response to pump start-up and shut-down Page 1 Abstract This project consists of the development and validation of a numerical model to simulate

More information

Exercise 4-2. Centrifugal Pumps EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Pumps

Exercise 4-2. Centrifugal Pumps EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Pumps Exercise 4-2 Centrifugal Pumps EXERCISE OBJECTIVE Familiarize yourself with the basics of liquid pumps, specifically with the basics of centrifugal pumps. DISCUSSION OUTLINE The Discussion of this exercise

More information

THE INFLOW OF UNWANTED AIR

THE INFLOW OF UNWANTED AIR IN PRESSURIZED PIPES The main reason for the inflow of air in public water distribution systems is excessive water velocity. Air traveling with water in pressurized pipes can result in high turbulence

More information

VACUVENT VE SERIES CATALOGUE

VACUVENT VE SERIES CATALOGUE VACUVENT VE SERIES CATALOGUE October 2018 " ba f wa e " The Triple Function Air Valve Vacuvent offers a tri function air valve that not only breaks vacuum, but also reduces surge on pipeline filling and

More information

Modeling a Pressure Safety Valve

Modeling a Pressure Safety Valve Modeling a Pressure Safety Valve Pressure Safety Valves (PSV), Pressure Relief Valves (PRV), and other pressure relieving devices offer protection against overpressure in many types of hydraulic systems.

More information

Control of air related problems for PVC and aluminum irrigation pipelines by Jeffery Kishel

Control of air related problems for PVC and aluminum irrigation pipelines by Jeffery Kishel Control of air related problems for PVC and aluminum irrigation pipelines by Jeffery Kishel A thesis submitted in partial fulfillment of the requirements for the degree of Master of Science in Civil Engineering

More information

Design Enhancements on Dry Gas Seals for Screw Compressor Applications

Design Enhancements on Dry Gas Seals for Screw Compressor Applications VDI-Berichte Nr. 1932, 2006 B 8 331 Design Enhancements on Dry Gas Seals for Screw Compressor Applications Dipl.-Ing C. Kirchner, Flowserve Dortmund GmbH & Co KG, Dortmund Introduction The development

More information

The Protection of Silos From Over. Pressurisation During Filling

The Protection of Silos From Over. Pressurisation During Filling SHAPA Technical Bulletin No.11 The Protection of Silos From Over Pressurisation During Filling Page 1 of 8 August 2005 The Protection of Silos From Over Pressurisation During Filling By James Duggleby,

More information

A Study of Pressure Safety Valve Response Times under Transient Overpressures

A Study of Pressure Safety Valve Response Times under Transient Overpressures A Study of Pressure Safety Valve Response Times under Transient Overpressures B C R Ewan, Chemical & Biological Engineering Department, University of Sheffield, Mappin St, Sheffield, S1 3JD. C Weil, 7

More information

Installation Operation Maintenance

Installation Operation Maintenance 682 Seal Cooler New generation seal cooler to meet and exceed the seal cooler requirements stated in the 4th Edition of API Standard 682 Installation Operation Maintenance Experience In Motion Description

More information

OLGA. The Dynamic Three Phase Flow Simulator. Input. Output. Mass transfer Momentum transfer Energy transfer. 9 Conservation equations

OLGA. The Dynamic Three Phase Flow Simulator. Input. Output. Mass transfer Momentum transfer Energy transfer. 9 Conservation equations 서유택 Flow Assurance The Dynamic Three Phase Flow Simulator 9 Conservation equations Mass (5) Momentum (3) Energy (1) Mass transfer Momentum transfer Energy transfer Input Boundary and initial conditions

More information

The Fernhill Rising Main Bursts What Went Wrong and What Was Done About It?

The Fernhill Rising Main Bursts What Went Wrong and What Was Done About It? The Fernhill Rising Main Bursts What Went Wrong and What Was Done About It? Uwe Kaeding 1, Steven Whichelo 1, Martin Ellis 2, Stuart Pile 1, Gerry Essenberg 2, Derek Falvey 1, John Mills-Ramage 1 1. United

More information

Fluid-Structure Interaction Analysis of a Flow Control Device

Fluid-Structure Interaction Analysis of a Flow Control Device Abaqus Technology Brief Fluid-Structure Interaction Analysis of a Control Device TB-06-FSI-2 Revised: April 2007. Summary The Vernay VernaFlo flow controls are custom-designed fluid flow management devices

More information

Copyright, 2005 GPM Hydraulic Consulting, Inc.

Copyright, 2005 GPM Hydraulic Consulting, Inc. Troubleshooting and Preventive Maintenance of Hydraulic Systems Learning to Read the Signs of Future System Failures Instructed by: Al Smiley & Alan Dellinger Copyright, 2005 GPM Hydraulic Consulting,

More information

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE - 247 - AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE J D Castro a, C W Pope a and R D Matthews b a Mott MacDonald Ltd, St Anne House,

More information

Effect of Pump Inertia & Valve Closure time on the Transient Flow Condition of a Water Supply Network: A Case Study

Effect of Pump Inertia & Valve Closure time on the Transient Flow Condition of a Water Supply Network: A Case Study Effect of Pump Inertia & Valve Closure time on the Transient Flow Condition of a Water Supply Network: A Case Study Sachin Kumar 1, Dr. Ruchi Khare 2 1Student of MTech (WRE), 2Faculty of Civil Engineering,

More information

SB AXIAL FLOW VALVES

SB AXIAL FLOW VALVES SB9509.3 AXIAL FLOW VALVES The improved technology for pressure regulation The American Axial Flow Valve provides pressure and flow control in high capacity pipelines. It can be used for pressure regulation,

More information

The API states the following about tube rupture for a shell-and-tube heat exchangers:

The API states the following about tube rupture for a shell-and-tube heat exchangers: Tutorial This tutorial describes the theory and modeling process of a tube rupture event using the special element type Rupture element in BOSfluids. It covers the algorithm BOSfluids uses to model the

More information

Operational Settings:

Operational Settings: instrucalc features more than 70 routines associated with control valves, ISO flow elements, relief valves and rupture disks, and calculates process data at flow conditions for a comprehensive range of

More information

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists 3,350 108,000 1.7 M Open access books available International authors and editors Downloads Our

More information

LECTURE 20 FLOW CONTROL VAVLES SELF EVALUATION QUESTIONS AND ANSWERS

LECTURE 20 FLOW CONTROL VAVLES SELF EVALUATION QUESTIONS AND ANSWERS LECTURE 20 FLOW CONTROL VAVLES SELF EVALUATION QUESTIONS AND ANSWERS 1: A cylinder has to exert a forward thrust of 150 kn and a reverse thrust of 15 kn. The effects of using various methods of regulating

More information

Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios

Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios Yunlong (Jason) Liu, PhD, PE HNTB Corporation Sean Cassady, FPE HNTB Corporation Abstract Extraction

More information

CVEN 311 Fluid Dynamics Fall Semester 2011 Dr. Kelly Brumbelow, Texas A&M University. Final Exam

CVEN 311 Fluid Dynamics Fall Semester 2011 Dr. Kelly Brumbelow, Texas A&M University. Final Exam CVEN 311 Fluid Dynamics Fall Semester 2011 Dr. Kelly Brumbelow, Texas A&M University Final Exam 8 pages, front & back, not including reference sheets; 21 questions An excerpt from the NCEES Fundamentals

More information

International Journal of Technical Research and Applications e-issn: , Volume 4, Issue 3 (May-June, 2016), PP.

International Journal of Technical Research and Applications e-issn: ,  Volume 4, Issue 3 (May-June, 2016), PP. DESIGN AND ANALYSIS OF FEED CHECK VALVE AS CONTROL VALVE USING CFD SOFTWARE R.Nikhil M.Tech Student Industrial & Production Engineering National Institute of Engineering Mysuru, Karnataka, India -570008

More information

FIRE PROTECTION. In fact, hydraulic modeling allows for infinite what if scenarios including:

FIRE PROTECTION. In fact, hydraulic modeling allows for infinite what if scenarios including: By Phil Smith, Project Manager and Chen-Hsiang Su, PE, Senior Consultant, Lincolnshire, IL, JENSEN HUGHES A hydraulic model is a computer program configured to simulate flows for a hydraulic system. The

More information

JUST WHEN YOU HAD SEEN IT ALL: THE VALUE OF HIGH FREQUENCY PRESSURE DATA. James Dunning, CEO tel:

JUST WHEN YOU HAD SEEN IT ALL: THE VALUE OF HIGH FREQUENCY PRESSURE DATA. James Dunning, CEO tel: JUST WHEN YOU HAD SEEN IT ALL: THE VALUE OF HIGH FREQUENCY PRESSURE DATA James Dunning, CEO james.dunning@syrinix.com tel: 415-992-8040 PEOPLE DON T UNDERSTAND THE PRESSURE ON ME AGENDA Why worry about

More information

2007 International Association of Hydraulic Engineering and Research

2007 International Association of Hydraulic Engineering and Research ACCEPTED VERSION Bryan W. Karney and Angus R. Simpson In-line check valves for water hammer control Journal of Hydraulic Research, 2007; 45(4):547-554 2007 International Association of Hydraulic Engineering

More information

Free Surface Flow Simulation with ACUSIM in the Water Industry

Free Surface Flow Simulation with ACUSIM in the Water Industry Free Surface Flow Simulation with ACUSIM in the Water Industry Tuan Ta Research Scientist, Innovation, Thames Water Kempton Water Treatment Works, Innovation, Feltham Hill Road, Hanworth, TW13 6XH, UK.

More information

Modelling of Pressurised Pipes within InfoWorks ICM and CS

Modelling of Pressurised Pipes within InfoWorks ICM and CS Modelling of Pressurised Pipes within InfoWorks ICM and CS 1. Introduction Correctly modelling pressurised pipes, variously described as forcemains or rising mains, can be one of the more difficult aspects

More information

Fail Operational Controls for an Independent Metering Valve

Fail Operational Controls for an Independent Metering Valve Group 14 - System Intergration and Safety Paper 14-3 465 Fail Operational Controls for an Independent Metering Valve Michael Rannow Eaton Corporation, 7945 Wallace Rd., Eden Prairie, MN, 55347, email:

More information

BERMAD Waterworks. Combination Air Valve. Air Valves Series. Typical Applications. Features & Benefits. Additional Features.

BERMAD Waterworks. Combination Air Valve. Air Valves Series. Typical Applications. Features & Benefits. Additional Features. BERMA Waterworks Combination Air Valve Model C7 BERMA C7 is a high quality combination air valve for a variety of water networks and operating conditions. It evacuates air during pipeline filling, allows

More information

Experimental Study of Water Hammer Pressure in a Commercial Pipe

Experimental Study of Water Hammer Pressure in a Commercial Pipe IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) Experimental Study of Water Hammer Pressure in a Commercial Pipe Ashish Kumar Patel 1 1 (School of Mechanical Engineering, Lovely Professional

More information

Digester Processes. 1. Raw Sludge Pumping System

Digester Processes. 1. Raw Sludge Pumping System Digester Processes 1. Raw Sludge Pumping System Removes accumulated sludge from the primary clarifiers, pumped through 1 of 2 pipes either 150 or 200mm in diameter (Fig. 1.1). Fig 1.1 Pipes feeding Digesters

More information

Analysis of Pressure Rise During Internal Arc Faults in Switchgear

Analysis of Pressure Rise During Internal Arc Faults in Switchgear Analysis of Pressure Rise During Internal Arc Faults in Switchgear ASANUMA, Gaku ONCHI, Toshiyuki TOYAMA, Kentaro ABSTRACT Switchgear include devices that play an important role in operations such as electric

More information

Dynamic Analysis of a Multi-Stage Compressor Train. Augusto Garcia-Hernandez, Jeffrey A. Bennett, and Dr. Klaus Brun

Dynamic Analysis of a Multi-Stage Compressor Train. Augusto Garcia-Hernandez, Jeffrey A. Bennett, and Dr. Klaus Brun Dynamic Analysis of a Multi-Stage Compressor Train Augusto Garcia-Hernandez, Jeffrey A. Bennett, and Dr. Klaus Brun Slide 2: Presenter/Author Bios Augusto Garcia-Hernandez Group Leader, Pipeline Simulation,

More information

Float Valve Function and Design Considerations

Float Valve Function and Design Considerations Float Operated Inlet Control Valves Their Ins and Outs Ian McCrone Chairman, Association of Tank and Cistern Manufacturers How often are you confronted with problems associated with Float Operated Level

More information

S-CO 2 Brayton Recompression Loop Design and Control

S-CO 2 Brayton Recompression Loop Design and Control S-CO 2 Brayton Recompression Loop Design and Control 1) Background 2) Recommended Design Features 3) Modeling Strategy IST Model Changes Transient Results Prepared by: Mike Hexemer Advanced Concepts Knolls

More information

LNG Loading Lines Surge Analysis for ESD System Application

LNG Loading Lines Surge Analysis for ESD System Application LNG Loading Lines urge nalysis for ED ystem pplication Nasrul yahruddin bstract PT BDK has recently implemented an Emergency hutdown ystem (ED) for the ship LNG Loading rms. When the ED ystem activates,

More information

DANFLO Control Valves 400 Series Model 20

DANFLO Control Valves 400 Series Model 20 DANFLO Control Valves 400 Series Model 20 Back Pressure/Pressure Relief The DANFLO Model 20 is a pilot operated valve suitable for use in gas or liquid facilities and requires no outside power for operation.

More information

A SEMI-PRESSURE-DRIVEN APPROACH TO RELIABILITY ASSESSMENT OF WATER DISTRIBUTION NETWORKS

A SEMI-PRESSURE-DRIVEN APPROACH TO RELIABILITY ASSESSMENT OF WATER DISTRIBUTION NETWORKS A SEMI-PRESSURE-DRIVEN APPROACH TO RELIABILITY ASSESSMENT OF WATER DISTRIBUTION NETWORKS S. S. OZGER PhD Student, Dept. of Civil and Envir. Engrg., Arizona State Univ., 85287, Tempe, AZ, US Phone: +1-480-965-3589

More information

Operators of petroleum plants

Operators of petroleum plants Validating anti-surge control systems At a gas processing plant, real time simulation was used to analyse the design of a surge protection scheme for a natural gas compressor, after questions arose over

More information