HEATEC TEC-NOTE. Setting Siemens Pressure Transmitter. Used on Heatec Vertical Asphalt Tanks. Publication No , Revised
|
|
- Arron O’Connor’
- 5 years ago
- Views:
Transcription
1 HEATEC TEC-NOTE, Revised Setting Siemens Pressure Transmitter Used on Heatec Vertical Asphalt Tanks This document provides information on setting Siemens pressure transmitters used on Heatec vertical asphalt tanks TAV-10, TAV-15, TAV-20, TAV-25, TAV-30 and TAV-35 (Figure 1). These tanks are used to store liquid asphalt. The transmitter indicates the level of liquid material in the tank. This document covers Siemens pressure transmitter SITRANS P, 7MF4133-1CA70-1NC6-Z B21+M43+Y01 (Figure 2). It is the transmitter model used by Heatec starting in September This document also covers Siemens pressure transmitter SITRANS P, 7MF4033-1CY10-1NC6-Z+B21+Y01 (Figure 3) (fitted with remote seal (sensor) 7MF4810-2QA02). It is the transmitter model Heatec provided prior to September liquid level display and control. A controller (Figures 12 and 13) is normally used in combination with the pressure transmitter. The controller also indicates the liquid levels and provides important safety controls. Remote displays can also use output signals from the transmitter to indicate liquid levels. Settings for controllers and remote displays are covered in other Heatec Tec-Notes. ISOLATION VALVE MOUNTING FLANGE WITH DIAPHRAGM PRESSURE TRANSMITTER Instructions in this document are the same for both transmitters unless noted otherwise. The information herein should enable operators to enter settings into the transmitters after the tanks are delivered to locations where they will be used. This document also provides information for converting levels to gallons. The transmitters have a sensor diaphragm in their mounting flange (Figure 2). Liquid pressure against the diaphragm is converted into a 4 to 20 ma (milliampere) output signal for ENGRAVED PLACARD Figure 2. Siemens pressure transmitter used September 2013 and later. DO NOT TILT TRANSMITTER Figure 1. Heatec vertical asphalt tanks. Figure 3. Siemens pressure transmitter used prior to September 2013.
2 QUICK CHECK When we install pressure transmitters on new asphalt tanks at our factory we program them for asphalt cements that have a specific gravity of 60 degrees F adjusted to for a storage temperature of 300 degrees F. These settings should enable the transmitter and its related controller to provide level indications very close to actual levels in the tank. When you first put the new tank into service, you should verify that our factory settings provide level indications with the accuracy you need. Verify the accuracy as follows: 1. Before putting asphalt into the tank, open the isolation valve (Figure 2) to vent the diaphragm to atmosphere and release trapped air. 2. Partially fill the tank (about 36 inches below the top) with asphalt and allow the transmitter to heat up from contact with the asphalt. 3. Note the level shown on the transmitter display. (Levels are displayed in inches as shown in Figure 4.) 4. Using a measuring tape for inches, determine the actual level of asphalt above the bottom of the tank. For instructions on how to measure actual levels refer to the information under the heading VERIFYING ACCURACY OF LEVELS. 5. Compare the level shown on the display with that found with the measuring tape. If the level shown on the transmitter display is within an inch or two of the level found with the measuring tape, your transmitter is ready for use as is. If the levels differ more than about two inches, you may want to reset the transmitter according to instructions herein for better accuracy. SETTINGS YOU CAN CHANGE Certain settings of the transmitter can be changed in the field using the magnetic push buttons shown in Figure 5. Settings in Mode 6 allow for adjustment of specific gravity, transmitter mounting height, and maximum tank height. In the past we recommended changing settings in Mode 7 to correct for differences between indications shown on the transmitter and actual level measurements made with a measuring tape. However, we no longer recommend using Mode 7 to correct for such variations. Please refer to the information under the heading Trial and Error for new recommendations. We set the transmitter to display the level of the liquid asphalt in the tank in inches (Figure 4). This is our standard unit of measure for level indications and cannot be changed in the field by operators. A number of other settings are based on inches and would require re-programing for other units of measure. Moreover, we provide tables of information so operators can easily convert level indications into gallons. These tables are based on inches of height and the inside diameter of our tanks. Therefore, we do not set the transmitter for other units of measure or tank sizes except on special orders, which may incur extra programing and costs. ACCURACY If you need to obtain better accuracy than achieved with our factory settings, please consider the following factors: Accuracy is affected by specific gravity of the asphalt, which is also affected by its storage temperature. So, if the specific gravity and/or storage temperature for your asphalt is significantly different from our factory settings, it may be necessary to change Mode 6 settings on the transmitter to obtain more accurate level indications. Accuracy is also affected by the height of the transmitter above the inside bottom of the tank. Mounting flanges of transmitters installed on vertical asphalt tanks at Heatec are centered at a height of 11 inches above the inside bottom of the tank. Mounting flanges of transmitters retrofitted in the field are usually installed at the drain outlet, which is only 2.5 inches above the bottom of the tank. Different flange heights require different Mode 6 settings. We attach an engraved plastic plate on the front of the transmitter (Figure 2) with information that denotes the mounting height and tank height for which the transmitter was programed. Figure 4. Display on transmitter. Page 2 Figure 5. Magnetic push buttons.
3 CONCERN FOR TRAPPED AIR Trapped air between the isolation valve and the diaphragm in the transmitter flange may prevent the liquid asphalt from making proper contact with the diaphragm. This may cause erratic level indications. To avoid trapping air on a new tank, be sure to open the isolation valve for the transmitter before filling the tank with asphalt. When retrofitting a transmitter onto an asphalt tank, always mount it on a shutoff valve. The valve serves to isolate the transmitter if it needs to be removed for any reason. If the transmitter is being retrofitted onto the drain valve of a tank that is already filled with asphalt, trapped air should escape if you slowly open the valve to allow asphalt to make contact with the diaphragm. However, if air remains trapped between the valve and the diaphragm, you will likely see erratic level indications. In that case you will need to do the following: 1. Completely empty the tank. 2. If the drain valve is clogged with asphalt, flush it with a solvent to clear the asphalt. 3. Make sure transmitter is securely mounted on the valve. 4. Open the valve. 5. Refill the tank with asphalt while the valve is open.!warning Do not attempt to purge trapped air by loosening transmitter mounting bolts and opening the isolation valve. This would allow hot asphalt to escape along with the trapped air, endangering anyone it might contact. SETTINGS FOR MODE 6 The following information is intended for checking the existing setting in Mode 6 and changing it for a new specific gravity and/or new storage temperature. Settings in this mode are known as full scale blind settings. These settings can be made at virtually any time no matter how much asphalt is in the tank. A single full scale blind setting combines specific gravity, transmitter mounting height, and maximum tank height. Therefore, the number that appears in the transmitter display does not directly indicate specific gravity. Instead you must use the information in Figures 6 or 7 to see what specific gravity setting was included in this setting. The blind scale settings shown in these figures apply to transmitters used on Heatec tanks and incorporate a wide range of specific gravities. 1. Before changing the setting in Mode 6, determine the specific gravity of your asphalt corrected for storage temperature. Use the information discussed under the heading SPECIFIC GRAVITY to do that. 2. Loosen the cover on the magnetic push buttons of the transmitter (Figure 5) and open it for access to the three push buttons (mode, up arrow, and down arrow). 3. Push the mode button several times until the number 6 appears in the lower left corner of the display. This indicates the transmitter is in Mode 6. The value that appears on the main display is the full scale blind setting. 4. Read the numerical value shown on the main display. Now find the nearest blind scale value in Figure 6 or 7 as applicable, and note the specific gravity for that value. For example, suppose the blind scale number that appears on the display is The closest match in Figure 6 is A specific gravity of is shown for that blind scale value. Figure 6. Specific Gravity Vs Full Scale Blind Setting. (11-inch sensor height) Specific storage temp Full Scale Blind Setting Specific storage temp Full Scale Blind Setting The full scale blind setting is equal to a tank height of 600 inches minus the sensor height of 11 inches multiplied by the specific gravity of the asphalt. Page 3
4 5. If the specific gravity shown for that blind scale reading is significantly different from the one you found in Step 1 above, you need to change this setting. 6. Thus, to obtain a full scale blind setting for another specific gravity, simply choose a specific gravity value shown in Figure 6 or 7 with a value closest to the specific gravity from Step 1 above. Then note the full scale blind setting shown alongside the specific gravity listed. 7. Use the up arrow and down arrow to change the full scale blind setting to the new value you found in the previous step. Secure the cover after making changes. Figure 7. Specific Gravity Vs Full Scale Blind Setting. (2.5 inch sensor height) Specific storage temp Full Scale Blind Setting Specific storage temp Full Scale Blind Setting The full scale blind setting is equal to a tank height of 600 inches minus the sensor height of 2.5 inches multiplied by the specific gravity of the asphalt. SPECIFIC GRAVITY To obtain maximum accuracy of level indications, the transmitter must be set for the specific gravity of the material that will actually be stored in the tank. This must be the specific gravity of the material at the temperature at which it will be stored in the tank. If its specific gravity is significantly higher or lower than that used to set the transmitter, the transmitter will not provide accurate level indications. This could allow operators to overfill the tank or cause coking of the heating coils. Specific gravities vary with the types of asphalt. And the specific gravity of a particular type of asphalt varies with its temperature. If you decide to store a different type of material, or if you change its storage temperature significantly, you need to reset the transmitter. If the specific gravity and/or storage temperature of the material varies only slightly from one tank load to another, you can use a setting that is average for most loads. In that case, the level indications will be slightly less accurate, but may be plenty accurate for your operations. Your supplier should be able to tell you the specific gravity of the asphalt you intend to store in your tanks. The BOL (Bill of Lading) for the truck that delivers your asphalt may show the specific gravity for each load. But be aware that the specific gravity shown on the BOL may be for standard temperature of 60 degrees F, which is not your storage temperature. Or it may only show API (American Petroleum Institute) gravity, which is not the same as specific gravity. Another way to learn the actual specific gravity of your material is to have it analyzed in your own laboratory, if you have one. In any case the known specific gravity at 60 degrees F will have to be corrected to your storage temperature. You can easily do that yourself using the information shown in Figure 8. Just multiply the known specific gravity for 60 degrees F by the multiplier shown next to the temperature that matches your tank storage temperature. For example if the known specific gravity is at 60 degrees F, and your storage temperature is 300 degrees F, use the multiplier of shown in the Figure 8. Thus: times equals 0.949, which is the specific gravity corrected for your storage temperature. If you have difficulty determining the corrected specific gravity for your material, try using one shown in Figure 9. It shows the specific gravities for several grades of asphalt cement at various storage temperatures. However, these are typical and may vary somewhat from actual specific gravities of your material. Page 4
5 Figure 8. Temperature Corrections For Specific Gravities Temperature Multiplier 60 Degrees F Degrees F Degrees F Degrees F Degrees F Degrees F Degrees F Multipliers shown here are from Matls. IM T102C, published by Iowa Department of Transportation Temperature Figure 9. Specific gravities for typical asphalt cements for a variety of storage temperatures. Unmodified Asphalt Binders PG PG PG PG PG PG Degrees F Degrees F Degrees F Degrees F Degrees F Degrees F Degrees F Specific gravities shown in green are for unmodified asphalt binders at 60 degrees F, offered by BP Products North America, published in TDS/US/ Specific gravities at other temperatures were calculated using the multipliers shown in Matls. IM T102C, published by Iowa Department of Transportation. This information is shown for reference purposes only. The specific gravity of your material may vary from those shown here. If your supplier doesn t know the specific gravity of your material you might want to use the specific gravity for PG 52-28, which is an approximate average of those shown. Page 5
6 VERIFYING ACCURACY OF LEVELS You should verify that the asphalt level indications produced by the pressure transmitter are acceptably accurate. You need to use a measuring tape marked in inches to determine the actual level of asphalt above the inside bottom of the tank. To minimize error make the measurement while the asphalt level in the tank is about 36 inches below the top. To find the exact level, measure the empty space at the top of the tank using the measuring tape. (See Figure 10). Then subtract the empty space measurement from the inside height of the tank shown in Figure 11. Note: When making your measurement it is difficult to measure directly from the inside top surface of the tank to the asphalt surface. It is much easier to measure from the bottom edge of the manway to the surface of the asphalt. If you do that you will need to make a separate measurement to determine the distance from the edge of the manway to the topmost surface inside the tank. Then you should add the two measurements together as indicated in Figure 10. Your final answer should match the number of inches displayed on the transmitter and controller, within an inch or two. If the indicated level differs much more than that try and find the cause. Start by checking the full scale blind setting of the transmitter as detailed under the heading SETTINGS FOR MODE 6 to confirm correct settings. Make sure it is properly set for the asphalt actually stored in the tank based on the specific gravity of the asphalt at its storage temperature. Be aware that debris or anything blocking the port where the transmitter connects to the tank will cause erroneous operation of the transmitter. TRIAL AND ERROR In the event that measured levels differ significantly from levels indicated by the transmitter it may be possible to use a trial and error method to bring the two into agreement. You might want to try this method especially when you are not sure about the specific gravity of the asphalt stored in the tank. Please remember that temperature variations can significantly change its specific gravity. So make sure the temperature used for specific gravity is the same as the actual storage temperature. But before proceeding with the trial and error method, carefully recheck your taped measurements and your arithmetic for errors. And then check the full scale blind scale setting on the transmitter to make sure it is correct. ASPHALT SURFACE EMPTY SPACE (A PLUS B) MANWAY A B If the two levels still do not agree, proceed with the trial and error method. It involves nothing more than changing the existing values of the full scale blind setting on the transmitter in Mode 6 (see Figures 6 or 7, as applicable). Either increase or decrease those values in small increments until the displayed level indications agree with the level found with the measuring tape. For example, if the existing value is 559.6, increase it to Or decrease it to Continue this process until you get a suitable match. LEVEL SHOWN ON DISPLAY TANK INSIDE HEIGHT Each time you enter a new value and store it, check the transmitter to see how close it agrees with the level found using the measuring tape. Keep doing this until you get an acceptable match. PRESSURE TRANSMITTER EITHER 11 INCHES OR 2.5 INCHES DEAD ZONE Figure 10. Key distances related to level display. After using this method to attain agreement between the transmitter and measuring tape we recommend that you recheck one against the other several times over a period of a several days. TANK OVERFLOW PROTECTION The pressure transmitter works in combination with the level controller (Figures 12 and 13) to provide overflow protection. Accordingly, the controller automatically shuts off the unloading pump when the material in the tank reaches a level approximately 24 inches from the inside top of the tank. Figure 11. Inside height (inches) of vertical asphalt tanks. TAV-10 TAV-15 TAV-20 TAV-25 TAV-30 TAV Page 6 The tank is also equipped with a high level float switch. It functions as a backup system for the shutoff provided by the controller. The float switch will shut off the unloading pump
7 Figure 12. Controller currently used with pressure transmitter. at a level of approximately 7 inches from the inside top if the controller fails to shutoff the unloading pump. TANK COIL PROTECTION The pressure transmitter works in combination with the level controller (Figures 12 and 13) to prevent coking of the heating coil. Accordingly, the controller automatically shuts off the heat when the material in the tank reaches a level slightly above the tops of the heating coils. DISPLAY LEVELS VS. GALLONS As already noted the transmitter displays levels in inches. You may need to know how many gallons of material that various levels represent. Some error is unavoidable when measuring levels and converting them to gallons of asphalt stored in the tank. Such determinations are not reliable substitutes for metering and calibration equipment. It is important to note that pressure transmitters on Heatec tanks are now set up to display the height of the asphalt above the inside bottom of the tank. Several years ago we set the transmitters to display the height of the asphalt above the location of the transmitter sensor. You should not change the position of the transmitter or the location of its sensor. Doing that would cause all indications to be wrong. The standard height for sensors of transmitters installed at Heatec is 11 inches above the bottom of the tank. (This distance may vary plus or minus 1/4-inch.) Consequently, the transmitter displays inches when the asphalt level is at the same height as the sensor. And when the asphalt level is 11 inches there are approximately 647 gallons of material in the tank. Figure 13. Controller previously used with pressure transmitter. When transmitters are retrofitted in the field they are usually installed in the drain outlet. The height of the drain outlet is 2.5 inches. Consequently the transmitter displays 2.50 inches when the asphalt level is at the same height as the sensor. And when the asphalt level is 2.5 inches there are approximately 147 gallons of material in the tank. But note that the transmitter does not actually indicate asphalt levels lower than the height of its sensor. This is known as the DEAD ZONE (Figure 10). So when the display of a transmitter installed at a height of 11 inches shows 11.00, the amount of asphalt in the dead zone is somewhere between 0 and 647 gallons. And when the display of a transmitter installed at a height of 2.5 inches shows 2.50, the amount of asphalt in the dead zone is somewhere between 0 and 147 gallons. The table shown in Figure 14 enables you to convert levels to gallons. The column labeled inches refers to the numbers that are displayed on the transmitter (Figure 4) and on the liquid level controller (Figure 12). (The number of decimal points that appear on the displays vary, but do not affect accuracy.) It is useful to remember that each inch of liquid level equals about 59 gallons. INSTALLING A NEW TRANSMITTER New transmitters must be programmed at the Heatec factory using special Siemens software configured for Heatec tanks. An engraved placard (Figure 2) on the transmitter indicates that we programed the transmitter at our factory. Transmitters that have not been programmed using the special software cannot be re-programmed by plant operators to work properly. After the transmitter is programmed by Heatec, certain settings can be changed in the field by operators as explained earlier. Page 7
8 LIMITATIONS The level indicating system is ideal for determining the amount of asphalt stored in asphalt tanks. But its level indications cannot be used for liquid metering or for custody transfer. The system has limitations due mainly to variations in the specific gravity of liquids stored in the tank and due to dimensional variations in tank components. Temperature variations are a major concern. As previously stated, the transmitter must be set for asphalt at its storage temperature in order to get accurate level indications. Please be aware that the level indications produced by the pressure transmitter are not measured directly. The transmitter only senses pressure (pounds per square inch). The pressure is produced by weight of the liquid asphalt pressing against a small diaphragm in the transmitter. Pressure on the diaphragm varies a 4 to 20 ma signal that is converted into an indication of level. Only the liquid asphalt above the transmitter affects pressure on the diaphragm. The pressure is proportional to the height of the liquid above the bottom of the tank. Liquid asphalt in the tank below the transmitter has no effect on the transmitter and is considered to be in a dead zone. The volume of the liquid in the tank changes in proportion to changes in its temperature. An increase in the temperature of the liquid causes it to expand and increase its level in the tank. A decrease in temperature causes it to contract and decrease its level in the tank. But level changes caused solely by changes in temperature do not change the weight of the liquid in the tank. Therefore, pressure on the diaphragm in the transmitter remains the same despite changes in temperature. Accordingly, the transmitter cannot sense a change in level due to expansion or contraction and the level displayed on the transmitter will no longer match the actual level. This is why the transmitter must be calibrated for liquid at a certain temperature and will not produce accurate level indications at other temperatures. USING 4 TO 20 ma OUTPUT The pressure transmitter can be used to generate a 4 to 20 ma signal for checking a controller used in combination with the transmitter. The signal can also be used to check a remote display such as a Datel display. The procedure is as follows: 1. Push the mode button several times until Mode 8 Cur appears on the transmitter display. 2. Push the up and down arrow buttons simultaneously until the display on the transmitter shows 4.0 ma. 3. Check the value that appears on the controller and/or remote display. If the transmitter is mounted at a height of eleven inches, 11 should appear on controller and/or display. If the transmitter is mounted at a height of two and one half inches, the whole number 3 should appear on the controller and/or display. 4. Push the up arrow two times. The display on the transmitter should show 20.0 ma. 5. Check the value that appears on the controller and/or remote display. They should show Push the mode button until the display on the transmitter returns to display mode. HELP In the event that you cannot get your Heatec level indicating system working properly, please call Heatec at and ask to speak to a service technician. We recommend that you become familiar with the information in this Tec-Note before calling Heatec. This information will make it easier to discuss your concerns by phone. Heatec, Inc Wilson Road Chattanooga, Tennessee (423) (800) Fax (423) Heatec, Inc. Page 8
9 Figure 14. Asphalt volumes at various levels (Page 1 of 3 pages) INCHES GALLONS INCHES GALLONS INCHES GALLONS INCHES GALLONS INCHES GALLONS , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,576 Page 9
10 Figure 14. Asphalt volumes at various levels (Page 2 of 3 pages) INCHES GALLONS INCHES GALLONS INCHES GALLONS INCHES GALLONS INCHES GALLONS , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,817 Page 10
11 Figure 14. Asphalt volumes at various levels (Page 3 of 3 pages) INCHES GALLONS INCHES GALLONS INCHES GALLONS INCHES GALLONS INCHES GALLONS , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , Page 11
12 HEATEC,INC. an Astec Industries Company 5200 WILSON RD CHATTANOOGA, TN USA FAX heatec.com
HEATEC TEC-NOTE Publication No Revised
HEATEC TEC-NOTE Revised 6-17-10 Setting up Vega radar sensors for Heatec vertical asphalt tanks This document provides information for setting up Vega radar sensors installed on Heatec tanks that store
More informationLiquid level measurement using hydrostatic pressure and buoyancy
iquid level measurement using hydrostatic pressure and buoyancy This worksheet and all related files are licensed under the Creative Commons Attribution icense, version 1.0. To view a copy of this license,
More information#LZ400 LEAKALYZER. Water Loss Sensor INSTRUCTION MANUAL Country Dr. #190 St. Paul, MN
#LZ400 LEAKALYZER Water Loss Sensor INSTRUCTION MANUAL 2885 Country Dr. #190 St. Paul, MN 55117 800-348-1316 www.leaktools.com Your Partner in Swimming Pool Water Conservation Product Purpose: 2 The Leakalyzer
More informationproduct manual HM-4140, HM-4150, HM-4160 HM-4160A HM-4150 Humboldt FlexPanels
12.09 product manual HM-4140, HM-4150, HM-4160 HM-4160A HM-4150 Humboldt FlexPanels Introduction: This manual covers the installation and operation of Humboldt FlexPanels for Triaxial and Permeability
More informationExercise 2-2. Second-Order Interacting Processes EXERCISE OBJECTIVE DISCUSSION OUTLINE. The actual setup DISCUSSION
Exercise 2-2 Second-Order Interacting Processes EXERCISE OBJECTIVE Familiarize yourself with second-order interacting processes and experiment with the finer points of controller tuning to gain a deeper
More informationExercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.
Exercise 5-2 Bubblers EXERCISE OBJECTIVE Learn to measure the level in a vessel using a bubbler. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Bubblers How to measure
More informationTANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel
TANK MANAGER FOR TWO TANKS OPERATING MANUAL 10/31/11 C-More T6C L color touch panel 1 TABLE OF CONTENTS GENERAL...3 INSTALLATION...4 STONE TEST PROCEDURE...7 OPERATIONAL SUMMARY...7 AUTO CARBONATION...10
More informationACCURACY, PERFORMANCE, AND HANDLING OF OIL-FILLED DIGIQUARTZ PRESSURE INSTRUMENTATION
Application Note Doc. G8108-001 Rev. A - 23-Jul-02 ACCURACY, PERFORMANCE, AND HANDLING OF OIL-FILLED DIGIQUARTZ PRESSURE INSTRUMENTATION For more information regarding Digiquartz products contact: Paroscientific,
More informationCover Page for Lab Report Group Portion. Head Losses in Pipes
Cover Page for Lab Report Group Portion Head Losses in Pipes Prepared by Professor J. M. Cimbala, Penn State University Latest revision: 02 February 2012 Name 1: Name 2: Name 3: [Name 4: ] Date: Section
More informationGE Oil & Gas. Mooney * Flowgrid * Slam Shut Regulator. Delivering accuracy, performance and protection
GE Oil & Gas Mooney * Flowgrid * Slam Shut Regulator Delivering accuracy, performance and protection Industries Gas transmission Gas distribution Midstream gas Gas processing Applications Gas pipelines
More informationInjection Systems INSTALLATION AND OPERATING GUIDE HI FLO VERTICAL TANK SYSTEMS
TM INSTALLATION AND OPERATING GUIDE HI FLO VERTICAL TANK SYSTEMS When the HI-FLO Metering Head is attached to a tank, the tank will be pressurized to the same pressure as the irrigation system. Before
More informationDesign DSA Steam-Atomized Desuperheater
Instruction Manual DSA Desuperheater Design DSA Steam-Atomized Desuperheater Contents Introduction............................... 1 Scope of Manual......................... 1 Description..............................
More informationAcornVac Vacuum Plumbing Systems - Trouble Shooting Guide
AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide 1. Accumulators Problem Accumulator is overflowing If Accumulator continues to overflow Correction 1. Push and hold the manual activation button
More informationCover Page for Lab Report Group Portion. Pump Performance
Cover Page for Lab Report Group Portion Pump Performance Prepared by Professor J. M. Cimbala, Penn State University Latest revision: 02 March 2012 Name 1: Name 2: Name 3: [Name 4: ] Date: Section number:
More informationFisher DSA Steam-Atomized Desuperheater
Instruction Manual DSA Desuperheater Fisher DSA Steam-Atomized Desuperheater Contents Introduction... 1 Scope of Manual... 1 Description... 1 Principle of Operation... 2 Installation... 2 Operating Instructions...
More informationACV-10 Automatic Control Valve
ACV-10 Automatic Control Valve Installation, Operation & Maintenance General: The Archer Instruments ACV-10 is a precision automatic feed rate control valve for use in vacuum systems feeding Chlorine,
More informationThe Discussion of this exercise covers the following points:
Exercise 5-3 Wet Reference Leg EXERCISE OBJECTIVE Learn to measure the level in a vessel using a wet reference leg. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Measuring
More informationThe Discussion of this exercise covers the following points: Range with an elevated or suppressed zero Suppressed-zero range Elevated-zero range
Exercise 4-3 Zero Suppression and Zero Elevation EXERCISE OBJECTIVE In this exercise, you will learn the effect that mounting a pressure transmitter above or below the reference level has on the hydrostatic
More informationSINGLE VALVE WITH LOW-FLOW BYPASS
CONTROL VALVES Pressure Reducing Valve Sizing Guide Sizing pilot operated reducing valves is not a complicated process. It starts with determining requirements and following these guidelines in valve size
More informationL 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions
L 100 Bubble-Tube Level System Installation, Operation and Maintenance Instructions Figure 1 Contents Section Description Page 1.0 Introduction 2 2.0 Specifications 3 3.0 Installation 3 4.0 Warranty 6
More informationGerald D. Anderson. Education Technical Specialist
Gerald D. Anderson Education Technical Specialist The factors which influence selection of equipment for a liquid level control loop interact significantly. Analyses of these factors and their interactions
More informationFisher DVI Desuperheater Venturi Inline
Instruction Manual DVI Desuperheater Fisher DVI Desuperheater Venturi Inline Contents Introduction... 1 Scope of Manual... 1 Description... 1 Principle of Operation... 2 Installation... 3 Operating Instructions...
More informationCompiled by: B Beard. Approved by: SH Carstens. Description of requirements and procedures for compact provers to be used as verification standards.
1. Scope Description of requirements and procedures for compact provers to be used as verification standards. 2. Reference documents Trade Metrology Act SANS1698 3. Policy A. BASIC REQUIREMENTS Compact
More informationOPERATION AND MAINTENANCE MANUAL
OPERATION AND MAINTENANCE MANUAL Skum Bladder Tank Type Vertical. Table of Contents Page General Description 2 1. Installation 1.1 Safety 2 1.2 Transporting 2 1.3 Inspection 2 1.4 Filling Instruction 3-7
More informationREVISIONS. App Thom. App Sud. App PC IG 2014/09/19
/5 REVISIONS Rev Description Rev n by Sud PC Thom VB LH Clyd r Act Issue Date YYYY/MM/DD Gen. updates to content, format and spec number. Previously 564-00.0.0 FF 204/09/9 IG 204/09/9 N/A N/A N/A N/A N/A
More informationWATER CONTROL SYSTEM QUICK START
SETTINGS MENU SYSTEM OPTIONS WATER LEVEL BAR GRAPH 3 DS SPRAY ON/OFF CS SPRAY ON/OFF BEACON WATER CONTROL SYSTEM QUICK START WWW.GFWORLDWIDE.COM +1 (208) 664-9291 SERVICE@GFWORLDWIDE.COM DISPLAY SCREEN
More informationTECHNICAL DATA. than the water inlet pressure to the concentrate
Foam102a 1. DESCRIPTION The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with 3M foam concentrates. This system consists of a standard wet pipe sprinkler
More informationBubble Tube Installations
Instruction MI 020-328 September 2013 Bubble Tube Installations For Liquid Level, Density, and Interface Level Measurements 2 Contents Introduction... 5 Abbreviations... 5 Principle of Operation... 5 Alternative
More informationAir Eliminators and Combination Air Eliminators Strainers
Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.
More informationOVERVIEW pg 3. Major Points to Consider pg 3 Minor Points to Consider pg 3. INSTRUCTIONS pg 4
TABLE OF CONTENTS OVERVIEW pg 3 Major Points to Consider pg 3 Minor Points to Consider pg 3 INSTRUCTIONS pg 4 How Does Nordic Freeze Work pg 4 How Long Will the Ice Plug Take to Form pg 4 How Do I Know
More informationAMT-Ex Dewpoint Transmitter
AMT-Ex Dewpoint Transmitter Instruction Manual Alpha Moisture Systems Alpha House 96 City Road Bradford BD8 8ES England Tel: +44 1274 733100 Fax: +44 1274 733200 email: mail@amsytems.co.uk web: www.amsystems.co.uk
More informationUBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions
Document Number: XE-ATA5PM-R1A UBEC 1AT AUTO TANK Fill System 08899155 Installation, Operation, & Setup Instructions Rev170906-EB-FRC PHYSICAL: 1302 WEST BEARDSLEY AVE ELKHART, IN 46514 WWW.ELKHARTBRASS.COM
More information2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications
Application Description AG/266PILD-EN Rev. C 2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic Pressure Measurement Engineered solutions for all applications Increase plant productivity
More informationBlue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION
Blue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION Install your Blue River Technologies Port-A-Poly mixing system in a clean dry area.
More informationWedge Type Flow Meter Installation and Operation Manual
Wedge Type Flow Meter Installation and Operation Manual 358-EN Please read and save these instructions. Wedge Type Flow Meter PLEASE READ THIS FIRST! The purpose of this document is to provide guidance
More informationFloat Operated Level Controllers
CONTENTS Float Operated Level Controllers IM0015 Nov. 2014 PAGE Introduction 1 Scope 1 Description 1 Specification 1 Control Installation 2 INTRODUCTION Side Mount Back Mount Prior to installing, the instructions
More informationHill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide
Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide Secondary Coolant System Start-Up Procedures June 2006 Produced by the Hill PHOENIX Learning Center DISCLAIMER This
More informationOperating Instructions
Operating Instructions Before operating the thin film evaporator, please be aware of all safety concerns associated with this experiment: Burn hazard from the column and steam lines, Chemical hazards associated
More informationDESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE
February 9, 1998 Foam 101a A BLADDER TANK WITH 1. DESCRIPTION A Wet Pipe Bladder Tank Foam/Water System is a standard wet pipe automatic sprinkler system capable of discharging a foam/water solution automatically
More informationMODEL 1329 Tank Gauge
SERVICE INSTRUCTIONS FOR PETRO-METER 1329 GAUGE SERVICE INSTRUCTIONS MODEL 1329 Tank Gauge www.petro-meter.com Petro-Meter 1329 series Service Instructions HOW TO DETERMINE IF A PETRO-METER IS IN GOOD
More informationInstallation, operating and maintenance Instructions for Seemag bypass level indicator
Issue: S Date: 05-09-14 Type G35 General information The Seetru bypass magnetic level indicator, abbreviate SEEMAG, serves to show the filling level of fluids in tanks, basins, tubes etc. The Seemag operates
More informationTECHNICAL DATA. Q = C v P S
Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler
More informationAir Ball! Evaluation copy
Air Ball! Computer 24 Do you ever wonder how the National Basketball Association (NBA) decides how much air should be in the basketballs used during a game? The NBA measures the pressure inside the ball
More informationLaboratory Mortar Mixer (Testing)
TomTom-Tools GmbH Zelgli 20 8905 Arni info@tomtom-tools.com Switzerland www.tomtom-tools.com User Manual Version February 22, 2015 Laboratory Mortar Mixer (Testing) 1 Introduction The Laboratory Mortar
More informationFour common PRESSURE CALIBRATION PAIN POINTS
Four common PRESSURE CALIBRATION PAIN POINTS Pressure calibration is often critical to process control systems, helping to optimize operations and ensure plant safety. While pressure instrumentation can
More informationTECHNICAL DATA. Q= Cv S
Page 1 of 13 1. DESCRIPTION The Viking 4 inch Model G-4000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry
More informationVarea-Meter Flowmeters. For Metering and Controlling Flows of Process Fluids
Varea-Meter Flowmeters For Metering and Controlling Flows of Process Fluids Product Descriptions Our broad line of rotametertype flowmeters provides reliable readout, transmission, and control of liquids
More informationAPI MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks
API MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks 1. Scope This document describes procedures for determining or confirming the fill condition of
More informationTECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13
Page 1 of 13 1. Description The Viking 2 Model G-2000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler
More informationLAKOS Waterworks. PWC Series Sand Separators. Installation & Operation Manual LS-829 (10/12)
LAKOS Waterworks PWC Series Sand Separators Installation & Operation Manual LS-829 (10/12) Table of Contents Separator Operation... 3 Individual Model Details.... 4 Flow vs. Pressure Loss Chart 4 Installation
More informationBAPI Pressure Line of Products - FAQs
Table of Contents 1. Several manufacturers produce pressure transmitters, why should I purchase from BAPI?... p. 2 2. BAPI makes several styles of pressure transmitters. What are the features of each?...
More informationRejuvenation Instructions
Rejuvenation Instructions #401 Air Systems UPR This NRI covers the following: Understanding the applications and operation of flow meters. Understand the application and operation of test pressure gauges.
More informationIT STARTS AT THE SOURCE - RE-CALIBRATING YOUR PLANT METERS
IT STARTS AT THE SOURCE - RE-CALIBRATING YOUR PLANT METERS NYS AWWA Spring Conference Saratoga Springs, New York April 25, 2017 Robert Lucas, P.E. WHAT ARE WE TALKING ABOUT? Types of Flow Measuring Devices
More informationBUBBLER CONTROL SYSTEM
BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air
More informationImproving distillation tower operation
Improving distillation tower operation Measuring differential pressure across long sections of distillation columns has always been challenging, but purpose-built sensor systems provide a solution Fast
More informationOEM Manual. MODEL ½ Digit DRUM SCALE
OEM Manual MODEL 4020-3 ½ Digit DRUM SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA & Canada) Phone:
More informationB. Assemble the Method-25 sample train with a heated probe/filter.
6/30/2015 VOC Reporting, Inc. Method 25 Heated Controller Operating Instructions. pg. 1 of 5 INSTRUCTIONS FOR EPA METHOD-25 FIELD SAMPLE COLLECTION USING A VRi HEATED PROBE AND FILTER ASSEMBLY Introduction:
More informationSpecifications and information are subject to change without notice. Up-to-date address information is available on our website.
www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is available on our website. web: www.smar.com/contactus.asp LD302 - AssetView HMI LD302
More informationTroubleshooting Guide: 640 Pediatric Exam Table with Midmark Scale
Troubleshooting Guide: 640 Pediatric Exam Table with Midmark Scale Contents Description Refer To: Scale Troubleshooting Chart Troubleshooting Error Codes Error Messages Adjustments / Repair Procedures
More informationR E D I C O N T R O L S
R E D I C O N T R O L S Operation & Maintenance Manual Portable Service Purger for Low Pressure Chillers Model: PSP-LP-1B For Refrigerants R-11, R-113, R-114 & R-123 & Other Similar Refrigerants File Literature
More informationO&M Receiving and Inspection. Storage of Water Treatment Media
O&M 105.1 Receiving and Inspection 1. Equipment should be checked against the Bill of Lading to verify that the number of pieces received matches those shipped. 2. Equipment should be carefully inspected
More information6900 Maintenance Instruction System Flush
Equipment Required FA74005 Damper Drain Tube FA16005 Cover Removal Tool FA900005 Beaker 0.25 Litre FA900003 Solvent Cleaning Bottle FA940021 Syringe Polypropylene 50 ml as required FA999045 Gloves Latex
More informationOC Panel High Limit Aquastat Kit, Manual Reset p/n
OC Panel High Limit Aquastat Kit, Manual Reset p/n 233202 Instruction Sheet APPLICATION The OC (Option Control) Panel High Limit Aquastat Kit provides electronic temperature sensing in a UL limit-rated
More informationGlove Box Installation Manual
Glove Box Installation Manual 1998 by M. Braun Company File: GB-UNI-INS.DOC! Edition 08-00 by M. Boutin! Subject to be changed without notice Glovebox Installation Your Glove box has been fully assembled,
More informationInert Air (N2) Systems Manual
INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing
More informationPRESSURE REGULATOR LBM SERIES
VIRTUAL CATALOGUE FAIL TO OPEN REGULATOR HIGH FLOW COEFFICIENT WIDE PRESSURE-REGULATION RANGE FAST RESPONSE PRESSURE REGULATOR LBM SERIES FULL SEAL AT ZERO FLOW CAN BE SUPPLIED WITH MINIMUM / MAXIMUM PRESSURE
More informationD05 Pressure Regulating Valves
D05 Pressure Regulating Valves FEATURES PRODUCT DATA Noncorroding unitized cartridge contains all working parts and is easily replaceable. Includes built-in strainer and thermal bypass. Balanced seat construction
More informationModel: 43T. Bermad Pressure Relief Valve
Model: 43T Bermad Pressure Relief Valve Installation Operation Maintenance Manual () Rev.C1_01.08.17 Page 1 of 10 Safety First BERMAD believes that the safety of personnel working with and around our equipment
More informationLocation of CC Number if not located with the identification:
This checklist is used for Technical Policy U. Evaluating electronic digital indicators submitted separate from a measuring element. This section is intended for lab testing only. Is permanence necessary?
More informationBest Practices in Measuring Tank Level
Whitepaper Best Practices in Measuring Tank Level What to Know About Measuring Tank Level OVERVIEW Whether you are looking for a solution to solve a water supply issue to a building or trying to monitor
More informationTechnical Information
Technical Information Installation, Operation, Installation, Operation and Maintenance and Maintenance Manual Manual Balston Model 75700-K728 Nitrogen Generator Figure 1-75700-K728 Overall Dimensions These
More informationTECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY
Page 1 of 13 1. DESCRIPTION The Viking 3 Model G-3000 Dry Valve Riser Assembly is equipped with a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry
More informationRate of Flow Valve Series 120
SPECIFICATIONS Rate of Flow Valve Series DIMENSIONS The OCV Series 120 Rate of Flow control valve is designed to control or limit flow to a predetermined rate, regardless offl uctuations in downstream
More informationGas Measurement Fundamentals Certification. Curriculum
Gas Certification Institute, LLC P.O. Box 131525 Houston, Texas 77219-1525 281-598-7200 Phone 281-598-7199 Fax contact@gascertification.com www.gascertification.com Curriculum Copyright 2007-2012 Gas Certification
More informationOperating Instructions
Operating Instructions Preparation for Start-up 1. If the computer system is logged off, log into the computer system. Log into the operator account on the computer. Please ask your TA for username and
More informationWet pipe low flow foam/water system
December 6, 2010 Foam 14a 1. The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with Viking supplied foam concentrates. This system consists of a standard
More informationManual for continuous distillation
Manual for continuous distillation 1. Week 1: Objectives: Run the column at total reflux. When steady state is reached, take the sample from the top and bottom of the column in order to determine the overall
More informationVehicle-mounted meters, pump supplied
Purpose This inspection procedure outline (IPO) defines the minimum tests which must be performed to ensure that basic volumetric measuring devices comply with the legislation. Application Vehicle-mounted
More information1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI US Edition
Siemens AG 07 SITRANS LH00 Transmitter for hydrostatic level Overview Function U const. p U I EM The pressure transmitter SITRANS LH00 is a submersible sensor for hydrostatic level measurement. The pressure
More informationDESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection
February 9, 1998 Foam 201a 1. DESCRIPTION A Deluge Bladder Tank Foam/Water System is a standard deluge system capable of discharging a foam/water solution automatically through open sprinklers, spray nozzles,
More informationGM Series Dual-Block Multi-Function Gas Control Valves
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series
More informationAC : MEASUREMENT OF HYDROGEN IN HELIUM FLOW
AC 2010-2145: MEASUREMENT OF HYDROGEN IN HELIUM FLOW Randy Buchanan, University of Southern Mississippi Christopher Winstead, University of Southern Mississippi Anton Netchaev, University of Southern Mississippi
More informationTECHNICAL MANUAL CALIBRATION PROCEDURE FOR PRESSURE GAUGE. This publication replaces T.O. 33K dated 30 January 2012.
TECHNICAL MANUAL CALIBRATION PROCEDURE FOR GAUGE This publication replaces T.O. 33K6-4-427-1 dated 30 January 2012. Distribution Statement C - Distribution authorized to U. S. Government agencies and their
More informationLab 1: Pressure and surface tension. Bubblers, gravity and the mighty paper clip.
Lab 1: Pressure and surface tension. Bubblers, gravity and the mighty paper clip. CEE 3310 - Summer 2012 SAFETY The major safety hazard in this laboratory is a shock hazard. Given that you will be working
More informationModel DE-1, VDE-1 and DE-2 Air Release Heads
SPECIFICATIONS Model DE-1, VDE-1 and DE-2 Air Release Heads Bulletin SS03030 Issue/Rev. 0.7 (8/17) Smith Meter Air Eliminator The Smith Meter Model DE Air Release Heads are dual-electric float switch devices
More informationASPHALT PAVING LEVEL 1
ASPHALT PAVING LEVEL 1 Module 3: Yield Calculations: Tack Coat and Mix Spread Rate FDOT Course Module 3 1 Welcome the students to the third module in this course that covers tack coat and mix spread rates,
More informationInstallation and Operation Manual
Manual Static pressure transducer with controller Differential static pressure transducer with analog output and optional PI control mode Large diaphragm element with differential transformer Transducer
More informationModule 6. Tightness Testing
Module 6 Tightness Testing IGE / UP / 1B New Tightness Testing Procedure Covers pipework up to 35mm and installation volumes of 0.035m3 Objectives By the end of Module 6, Tightness Testing and Direct Purging
More informationPressure Measurement Single-range transmitters for general applications
Siemens AG 07 Overview Function U const. p U I EM Sensor Connection for auxiliary power supply Vent pipe with humidity filter Protective conductor connection/ Equipotential bonding Diaphragm The pressure
More informationEquipment and Accessories. ROMIL LiQuiSure. Designed for High Purity Containment & Dispensing PURE CHEMISTRY
Designed for High Purity Containment & Dispensing To maintain the high purity of ROMIL products during use and handling, we have developed a special range of equipment and accessories under the LiQuiSure
More informationTECHNICAL DATA. Q = C v P S
Preaction 346a 1. Description The 6 Model G-6000P Electric Release Preaction System Riser Assembly can be used as a Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction
More informationInstallation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.
Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow Model: FP 450-80 Installation Operation Maintenance PAGE 1 OF 5 1. Safety First BERMAD believes that the safety of personnel
More informationPoppetted Coaxial Drop Tube Assembly for use with Auto Limiter II. Installation Instructions
Poppetted Coaxial Drop Tube Assembly for use with Auto Limiter II Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838
More informationT EK-SUB 4800C 19 mm Submersible Level Transmitter
Technology Solutions T EK-SUB 4800C 19 mm Submersible Level Transmitter Instruction Manual Document Number: IM-4800C www.tek-trol.com Table of Contents 1 Safety Instructions... 2 1.1 Intended Use... 2
More informationPressure measurement Applying remote seal, isolation diaphragms between process fluids and transmitters
ABB MEASUREMENT & ANALYTICS WHITE PAPER Pressure measurement Applying remote seal, isolation diaphragms between process fluids and transmitters Remote seals protect transmitters when measuring difficult
More informationDelayed Coker Safe Sampling Tar or Spalled Coke
Delayed Coker Safe Sampling Tar or Spalled Coke Presented by Mitch Moloney of ExxonMobil mitchell.j.moloney@exxonmobil.com @ Galveston TX coking.com May-2013 a MJ Moloney - ExxonMobil May-2012 coking.com
More informationCOMPAFLOW. Compressed Air. Volumetric flow. Gas. Mass flow. Steam. Net volumetric flow. Liquid
Volumetric flow Compressed Air Mass flow Gas Net volumetric flow Steam Liquid Universal compact orifice flow meter combines a compact orifice flow sensor and sotiphicated converter One-piece flow sensor,
More informationIn Response to a Planned Power Outage: PPMS EverCool II Shut Down and Re-start Procedure
PPMS Service Note 1099-412 In Response to a Planned Power Outage: PPMS EverCool II Shut Down and Re-start Procedure Introduction: Loss of electricity to the PPMS EverCool II should not cause damage to
More informationHorizontal Bladder Tanks
DATA SHEET Horizontal Bladder Tanks Features UL Listed and FM Approved for use with various ANSUL proportioners and foam concentrates 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationACCURATE PRESSURE MEASUREMENT FOR STEAM TURBINE PERFORMANCE TESTING
ACCURATE PRESSURE MEASUREMENT FOR STEAM TURBINE PERFORMANCE TESTING Blair Chalpin Charles A. Matthews Mechanical Design Engineer Product Support Manager Scanivalve Corp Scanivalve Corp Liberty Lake, WA
More information