CLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD. 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems.

Size: px
Start display at page:

Download "CLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD. 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems."

Transcription

1 Page 1 of 7 CLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD 1. SCOPE 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems. 1.2 The piping system as used herein is intended to include the pipe, valves and fittings. Vessels, process equipment, instruments and relief devices are not included Option: Flanged connections, packings of valves, and instruments which can produce leaks to the environment, may be included in this test, at the owner s discretion. 1.3 The acceptance of piping systems under this specification is for pressure tightness only. 1.4 This Leak Test procedure qualifies as a Sensitive Leak Test as per ASME B31.3, para CLASS D-- SENSITIVE LEAK TEST GAS AND BUBBLE METHOD: 2.1 This test is performed by pressurizing the system with a gas, to 1 BAR (15 psig). This creates a pressure differential across a leak. Leaks are detected by applying a commercial bubble forming solution to all joints. The locations of leaks are indicated by the formation of bubbles This test may be performed at pressures greater than 1 BAR (15 psig). However, all conditions of G4S and G4Q shall be met when a higher pressure is used. 2.2 A complete line or section of line containing several valves and branches may be tested at one time. 2.3 CAUTION: PNEUMATIC TESTING should be used only as a last alternative. Carefully planned and supervised procedures shall be used to guard against the hazards of latent energy of compressed gases. 2.4 The Owner is responsible to assure that all conditions and safety concerns identified in G4D are addressed. 3. TEST MATERIALS AND SERVICES

2 Page 2 of The detection fluid shall be a commercial bubble forming test fluid, such as SNOOP or SHERLOCK, or equivalent. Soaps, detergents and/or industrial compounds that are designated specifically to be used as cleaning agents shall not be used in bubble forming solutions. SNOOP is a registered trademark of the Nupro Co., Willoughby, Ohio.SHERLOCK is a registered trademark of Winton Products Company, Inc., Charlotte, North Carolina For testing of stainless steel, nickel or chromium alloys, the fluid shall have a sulfur and halogen content of less than 10 ppm of each For testing of parts made of polyethylene or structural plastic, the test fluid shall not promote environmental stress cracking (E.S.C.) For testing of oxygen systems, the test fluid shall meet the requirement of MIL-L-25567D. 3.2 Air compressors shall be equipped with discharge filters for removal of water, oil and foreign matter. Maximum discharge temperature of lubricated air compressors shall be 150C (300F). 3.3 Pneumatic tests shall be made with air, nitrogen or other gases, as specified in the technical job instructions, work order or construction order. 4. PREPARATION FOR TEST 4.1 The line schedule issued should give the Common Product Piping Specification for each line and may include material, size, insulation, etc., and the required Test Pressure, Test Class (Method) and other requirements of the pipe specifications A set of marked-up or highlighted Piping and Instrument Drawings (P&ID s) may be used. The purpose is to identify the boundaries of separate piping systems to be tested, the locations of isolation blanks, valve positions, double block and bleed valve arrangements, location of pressure injection or connection points, location of pressure gauge(s), recorders for pressure, temperature and other instrumentation used to validate the test. 4.2 In the absence of a line schedule, the Test Pressure and Test Class (Method) required may be covered in the job Piping Material Specification, contract technical job instructions, construction order, or for maintenance jobs, by Work Order. If not specified, refer to the appropriate Common Product Pipe Specification.

3 Page 3 of Prior to testing, a thorough visual inspection shall be made for defects such as improper materials, poor gasket installation and loose joints. All bolts shall be made up tight in the system to be tested. The surface of the piping to be tested shall be clean and free of oil, grease, paint, weld slag, or other contamination. Weld joints shall not be painted or covered before performing this test. 4.4 Pneumatic testing shall be done before hydrostatic testing (Class C), if hydrostatic testing is also specified. 4.5 Flanged joints may be taped shut using a suitable adhesive coated paper tape such as duct tape or masking tape When tape is used, the tape shall be applied very carefully to insure an airtight seal all around both flanges. A small vent hole shall be punched in the tape, at a location preferably on top. 4.6 Piping systems connected to equipment shall be isolated from the equipment by means of a line blind, prior to cleaning and testing. If a valve is connected to the equipment, the blind shall be between the valve and the equipment, with the valve in the open position Where piping can not be isolated from equipment for testing, or it is desirable to include equipment in leak testing, the equipment may be included in the test provided: The piping system Test Pressure does not exceed either manufacturer s test pressure or a pressure limit imposed by the position and condition of the equipment The equipment does not contain any internals or materials that may be damaged by testing No rotating equipment may be included in any piping system leak test. 4.7 Valves shall be left open during the testing. If a valve is located at the end of a line, a blind flange or plug shall be installed. Where a valve can not be tested in the open position, consider: Blank the upstream side of the valve Remove the valve and install a blind flange Remove the valve and install a flanged test spool where continuity of the line is required for purpose of the test.

4 Page 4 of Test blinds shall be installed between existing piping and new piping to prevent introducing cleaning and testing medium into existing lines, or pressurizing the existing system Test blinds shall be capable of withstanding the test pressure. 4.9 Leak tests shall include as much instrument process piping as possible. Where an instrument process line contains more than one block valve, all valves shall be open except the one nearest the instrument Instruments and similar special equipment shall be protected against overpressure during cleaning and testing by disconnecting the piping between the closed block valves and the instruments. Direct operated or self-contained regulators and float actuated devices are to be removed or blocked and vented Control valves, pressure reducing valves, level controllers, level switches, orifice plates, turbine meters, massflow meters, vortex meters and other instruments or fittings designated by the Owner, shall be removed from the lines before cleaning and replaced before testing. All such items shall be cleaned separately after removal. Where control valves are closed, the line shall not be tested until the valve has been opened by the Owner. The line bore orifice spacers and gaskets or spare rings furnished with meter runs shall be installed prior to cleaning and remain in place during testing Check available drawings for any specific installation or operating instruction pertaining to expansion joints. Test pressure shall not exceed the maximum allowable specified test pressure of the expansion joint Expansion joints having tie-rods shall be tested as part of the piping system unless otherwise specified. The tie-rod nuts must be hand tight, with no slack under the outside nuts Expansion joints not having tie-rods may be removed or isolated from the test Insulation will not be allowed on systems under test except on those parts which have had a documented certified shop or mill test Spring support travel stops shall not be removed until all testing has been completed Prior to administration of the test visually observe the

5 Page 5 of 7 piping system to assure it is properly prepared. 5. ADMINISTRATION OF TEST 5.1 All tests shall be witnessed and accepted by the Owner or Owner designee The presence of the Owner or Owner designee is not necessary while initial checking of lines for leaks is in progress. 5.2 Special precautions shall be taken if testing is to be performed in the open air, with regard to weather such as wind or rain or other influences which may affect the accuracy of the test results Portable shields may be erected around areas to be tested, if necessary to prevent weather conditions from interfering with bubble leak tests The surface temperature of the piping or component to be tested shall be from 4 Deg C (40 Deg F) to 52 Deg C (125 Deg F) inclusive, throughout the test. Local heating or cooling is permitted provided the surface temperature remains within the stated range during the test. Bubble leak testing may be performed when the surface temperature is colder than 4 Deg C (40 Deg F) provided that a commercial bubble forming solution is used that is specifically manufactured for bubble leak testing at the coldest surface temperature that will be encountered during the test. 5.3 Illumination at the specific test area shall be a minimum of 1000 lux (100 footcandles). Verification of illumination is not required for external bubble leak tests performed during daylight hours. Otherwise, the light source, technique and illumination verification by light meter shall be demonstrated one time and documented. 5.4 Access to the area being bubble leak tested shall be sufficient to place the eye within 0.6 m (24 inches) of the surface under immediate observation. The angle between the line of sight and the surface under immediate examination shall not be less than 30 degrees. Mirrors may be used to improve the angle of vision. 5.5 Pressure gauges shall be of a suitable scale capacity for the Test Pressure, having a dial at least 115 mm (4-1/2 ) in diameter. The Test Pressure should be approximately 60% of full scale. The maximum pressure capacity shall not exceed three times the particular Test Pressure. Gauges will have established traceable identities and shall be accurate to within 1% of full scale. There

6 Page 6 of 7 shall be a minimum of two pressure gauges for each test Pressure gages used for testing shall be calibrated at least every six months. Calibration shall be traceable to individual gages for verification. Records of calibration shall be made available upon request. 5.6 The pressure differential should be created before the fluid is applied, to prevent clogging of small leaks. Prior to the beginning of bubble testing, the test pressure shall be held for a minimum of 15 minutes A commercial bubble test fluid shall be applied to all joints under examination, including each vent hole for taped flanges, flanged joints, valves stems, packing glands, and completely coat each threaded or welded joint Care shall be used in applying the fluid, to prevent the formation of bubbles; the bubble forming solution shall be applied by spraying, brushing or flowing the solution onto the test area such that a thin film of solution covers the area The surface shall be examined at the time of the solution application for the presence of large leaks, and after 2 minutes for the presence of small leaks Leaks detected shall be marked for correction and the subsequent inspection. 5.7 The first leakage check shall be made at 0.3 BAR (5 psig) MAXIMUM. Any detectable leaks shall be eliminated before proceeding. The leakage test may be repeated at higher pressures not to exceed 1 BAR (15 psig) or the specified test pressure, whichever is lower, as approved by the Owner. 5.8 Variations of pressure and volume due to temperature changes will be taken into account in determining whether the pressure during test is satisfactory, at the end of the test. All attempts shall be made to stabilize the temperature of the test, prior to starting the test. 5.9 Over tightening of a valve in an effort to make it hold may be cause for rejection of the valve by the Owner.

7 Page 7 of 7 6. RETESTS 6.1 In the event that a piping system or any part fails to pass the test prescribed, a new test shall be applied after repairs and corrections have been made. This retest shall include all parts of a connected system which may have passed a test previously, but have been affected by the corrections made or by a delay attending to the corrections. 7. POST TEST 7.1 At the completion of the test, all blinds, plugs and caps used to isolate equipment, vessels and instruments shall be removed, flange faces and threads inspected for damage, and piping reconnected. Special care is required when reconnecting these points to avoid leaks. 7.2 New gaskets shall be used when re-installing flanged items or reconnecting to flanged equipment. Gaskets removed after tests shall not be reused. 7.3 Vent and drain connections shall be capped, plugged or blanked after completion of test according to pipe specifications or technical job instructions. 7.4 All valves shall be placed in the open or closed position as determined by the Owner.

CLASS DH - PNEUMATIC TESTING - GREATER THAN 1 BAR (15 PSIG)

CLASS DH - PNEUMATIC TESTING - GREATER THAN 1 BAR (15 PSIG) Page 1 of 10 CLASS DH - PNEUMATIC TESTING - GREATER THAN 1 BAR (15 PSIG) 1. SCOPE 1.1 To provide definitive requirements for HIGH PRESSURE PNEUMATIC testing of piping systems according to ASME B31.3. This

More information

HYDROSTATIC LEAK TEST PROCEDURE

HYDROSTATIC LEAK TEST PROCEDURE This information is proprietary and shall not be disclosed outside your organization, nor shall it be duplicated, used or disclosed for purposes other than as permitted under the agreement with Kinetics

More information

Perform Pressure & Leak Test, Tubing & Piping. Module 12306

Perform Pressure & Leak Test, Tubing & Piping. Module 12306 Perform Pressure & Leak Test, Tubing & Piping Module 12306 Instrumentation Trainee Task Module 12306 PERFORM PRESSURE AND LEAK TEST, TUBING AND PIPING Objectives Upon completion of this module, the trainee

More information

ANDERSON GREENWOOD SERIES 9000 POSRV INSTALLATION AND MAINTENANCE INSTRUCTIONS

ANDERSON GREENWOOD SERIES 9000 POSRV INSTALLATION AND MAINTENANCE INSTRUCTIONS Procedure-assembly-functional test and performance requirements 1 SCOPE 1.1 This document establishes the general procedure for assembly, functional testing and normal performance requirements of low Series

More information

TEST SPECIFICATION NYT-909-C

TEST SPECIFICATION NYT-909-C 748 Starbuck Ave, Watertown, NY 13601 Phone: +1-315-786-5200 Engineering Fax: +1-315-786-5673 TEST SPECIFICATION NYT-909-C CODE OF TESTS FOR TESTING "AB" TEST RACK P/N 702546 & 702612 ISSUE NO. 5 1.0 THE

More information

INSTALLATION, MAINTENANCE & OPERATING INSTRUCTIONS 2-4 REDUCED PORT/ FULL PORT (5700/6700) ANSI CLASS 150/300/600/900/1500/2500 TRUNNION BALL VALVES

INSTALLATION, MAINTENANCE & OPERATING INSTRUCTIONS 2-4 REDUCED PORT/ FULL PORT (5700/6700) ANSI CLASS 150/300/600/900/1500/2500 TRUNNION BALL VALVES PBV-USA,Inc. 12735 Dairy Ashford. Stafford, Texas USA 77477 281-340-5400; 800-256-6193 FAX: 281-340-5499 INDUSTRIAL BALL VALVES IM0 69 April 2001 Rev 9 INSTALLATION, MAINTENANCE & OPERATING INSTRUCTIONS

More information

Installation, Operation and Maintenance Manual for Back Pressure Regulator

Installation, Operation and Maintenance Manual for Back Pressure Regulator Installation, Operation and Maintenance Manual for Back Pressure Regulator Model 8860 2009 Groth Corporation IOM-8860 Rev. B 12541 Ref. ID: 95565 Page 2 of 13 Table of Contents I. INTRODUCTION 3 II. DESIGN

More information

Design DSA Steam-Atomized Desuperheater

Design DSA Steam-Atomized Desuperheater Instruction Manual DSA Desuperheater Design DSA Steam-Atomized Desuperheater Contents Introduction............................... 1 Scope of Manual......................... 1 Description..............................

More information

Fisher DVI Desuperheater Venturi Inline

Fisher DVI Desuperheater Venturi Inline Instruction Manual DVI Desuperheater Fisher DVI Desuperheater Venturi Inline Contents Introduction... 1 Scope of Manual... 1 Description... 1 Principle of Operation... 2 Installation... 3 Operating Instructions...

More information

MODEL 200 KNIFE GATE VALVES INSTALLATION & MAINTENANCE MANUAL

MODEL 200 KNIFE GATE VALVES INSTALLATION & MAINTENANCE MANUAL MODEL 200 KNIFE GATE VALVES INSTALLATION & MAINTENANCE MANUAL Index 1. List of components / General arrangement 2. Description 3. Handling 4. Installation 5. Actuators / Operation 6. Maintenance a. Changing

More information

Flange Bolt Torquing. for Resistoflex Plastic-Lined Piping Products. Torquing. Retorquing. Hydrotesting. Annual retorquing

Flange Bolt Torquing. for Resistoflex Plastic-Lined Piping Products. Torquing. Retorquing. Hydrotesting. Annual retorquing Flange Bolt Torquing for Resistoflex Plastic-Lined Piping Products Torquing When assembling flange connections, always use a full complement of clean, new high strength A193-B7 bolting. If using stainless

More information

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A APCO ARV CLEAN WATER AIR RELEASE VALVES Model 50A Instruction D12013 February 2017 Instructions These instructions provide installation, operation and maintenance information for APCO ARV Clean Water Air

More information

Atmospheric relief valve type 1100 Installation and maintenance instructions

Atmospheric relief valve type 1100 Installation and maintenance instructions SAPAG 1. Description Sapag atmospheric relief valves type 1100 have been selected for installation because of their performance features, reliability and ease of maintenance. They are designed to protect

More information

Fisher DSA Steam-Atomized Desuperheater

Fisher DSA Steam-Atomized Desuperheater Instruction Manual DSA Desuperheater Fisher DSA Steam-Atomized Desuperheater Contents Introduction... 1 Scope of Manual... 1 Description... 1 Principle of Operation... 2 Installation... 2 Operating Instructions...

More information

NAVSEA STANDARD ITEM. 2.2 T9074-AS-GIB-010/271, Requirements for Nondestructive Testing Methods

NAVSEA STANDARD ITEM. 2.2 T9074-AS-GIB-010/271, Requirements for Nondestructive Testing Methods NAVSEA STANDARD ITEM ITEM NO: 009-53 DATE: 29 JUL 2011 CATEGORY: II 1. SCOPE: 1.1 Title: Bolted Bonnet Steam Valve; repair (shop) 2. REFERENCES: 2.1 S9086-CJ-STM-010/CH-075, Fasteners 2.2 T9074-AS-GIB-010/271,

More information

Standard Pneumatic Test Procedure Requirements for Piping Systems

Standard Pneumatic Test Procedure Requirements for Piping Systems the pressure equipment safety authority Standard Pneumatic Test Procedure Requirements for Piping Systems AB-522 Edition 2, Rev. 1 Issued 2016-10-24 Table of Contents FOREWORD... 1 1.0 INTRODUCTION...

More information

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures Operations & Service Manual TESCOM 50-4X Series Safety, Installation & Start-Up Procedures Do not attempt to select, install, use or maintain this product until you have read and fully understood this

More information

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax:

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax: 2 Table Of Contents 1. Introduction 3 2. About this Manual 3 3. Contacting YZ Systems 3 4. Vessel Components 4 5. Specifications 5 6. Application 6 7. Theory of Operation 7 8. DuraSite Installation & Use

More information

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING Contents All Products... Gb-1 Control Valves... Gb-2 Control Valve Actuators... Gb-3 Regulators... Gb-3 Relief Valves... Gb-4 Instruments, Switches, and Accessories... Gb-4 Products Covered by Battery

More information

INSTALLATION, OPERATION and MAINTENANCE MANUAL

INSTALLATION, OPERATION and MAINTENANCE MANUAL INSTALLATION, OPERATION and MAINTENANCE MANUAL TRUNNION MOUNTED BALL VALVE NEXTECH I ValvTechnologies, Inc. 5904 Bingle Road Houston, Texas 77092 U.S.A. Email: sales@valv.com www.valv.com 705_Nextech IOM

More information

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the 1151 METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS 1.0 Scope and Application. 1.1 Analytes. Analyte Volatile Organic Compounds (VOC) CAS No. No CAS number assigned 1.2 Scope. This method

More information

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator. RS(H)10,15 USER MANUAL Read the complete manual before installing and using the regulator. WARNING INCORRECT OR IMPROPER USE OF THIS PRODUCT CAN CAUSE SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE. Due to

More information

TECHNICAL DATA CAUTION

TECHNICAL DATA CAUTION Page 1 of 6 1. DESCRIPTION The Viking Model D-2 Accelerator is a quick-opening device, with an integral anti-flood assembly, used to increase the operating speed of a differential type dry pipe valve.

More information

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE INSTALLATION, OPERATION & MAINTENANCE MANUAL INTERFACE DEVICES, INC. 230 Depot Road, Milford, CT 06460 Ph: (203) 878-4648, Fx: (203) 882-0885, E-mail: info@interfacedevices.com

More information

Ontario ENGINEERING STANDARD SPECIFICATION 1.0 PURPOSE

Ontario ENGINEERING STANDARD SPECIFICATION 1.0 PURPOSE SPEC-5044 1/6 1.0 PURPOSE This specification describes the minimum requirements for the cleaning, handling and packaging of oxygen service piping and components. This applies to new installations, repairs,

More information

OPERATING AND MAINTENANCE MANUAL

OPERATING AND MAINTENANCE MANUAL Series 4300 Engineered Performance TABLE OF CONTENTS 0 INTRODUCTION 1 1 Scope 1 2 Description 1 3 Specifications 1 0 INSTALLATION 1 1 Mounting 1 2 Piping 1 1 Connecting Process Pressure 2 2 Vent Connections

More information

Un-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs

Un-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs Un-Pressurized Orefice Fittings FIO EZ Parts List and Operation Instructions TECHNICAL MANUAL Dn 2-6 Class 150-600 Lbs US US 2 FIO EZ - MT 108-US - 05-2016 FIO EZ Important Instructions US Pietro Fiorentini

More information

Oxygen Usage Best Practice Guide

Oxygen Usage Best Practice Guide Oxygen Usage Best Practice Guide 1. Introduction Oxygen enriched systems possess a risk of fire and explosion since ignition and combustion hazards are present in all oxygen systems, and oxygen related

More information

Type Testing of Rising Stem Valves Equipped with Graphite Packing for Fugitive Emissions

Type Testing of Rising Stem Valves Equipped with Graphite Packing for Fugitive Emissions Type Testing of Rising Stem Valves Equipped with Graphite Packing for Fugitive Emissions 1 Scope This standard specifies the requirements and acceptance criteria (100 ppmv) for fugitive emission type testing

More information

Types S100K and S102K Pressure Regulators

Types S100K and S102K Pressure Regulators Instruction Manual Form 5624 Types S0K and S2K 01/01 Types S0K and S2K Pressure Regulators W7478-1 Figure 1. Types S0K and S2K Pressure Regulator Introduction Scope of Manual This manual provides instructions

More information

Components for air preparation and pressure adjustment. OUT port position ( ) connected Rear side. of IN port. Air tank. directly.

Components for air preparation and pressure adjustment. OUT port position ( ) connected Rear side. of IN port. Air tank. directly. Components preparation and pressure adjustment ABP Overview ABP is a component that enables boosting by s only up to twice primary pressure (.0MPa max.) in combination with using air tank but not using

More information

1200B2 Series Service Regulators. Instruction Manual

1200B2 Series Service Regulators. Instruction Manual 00B Series Service Regulators Instruction Manual 00B Series Service Regulators 0 Elster American Meter 00B Series Service Regulators General Information The 00B Series Service Regulators are available

More information

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection February 9, 1998 Foam 201a 1. DESCRIPTION A Deluge Bladder Tank Foam/Water System is a standard deluge system capable of discharging a foam/water solution automatically through open sprinklers, spray nozzles,

More information

Manual Actuated Boiler Blowdown Valves

Manual Actuated Boiler Blowdown Valves Manual Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Operation 5. Maintenance 6. Spare parts p.1 1. Safety

More information

1800C and 1800C-HC Series Service Regulators

1800C and 1800C-HC Series Service Regulators 1800C and 1800C-HC Series Service Regulators Installation Instructions www.elster-americanmeter.com General Information: The 1800C and 1800C-HC Regulators are available as Full Capacity Internal Relief

More information

PRO-50 Instrument Supply Regulator

PRO-50 Instrument Supply Regulator Features CRN Approved The PRO-50 Regulator has been granted a Canadian Registration Number. Sour Service Capability Available in NACE configurations that comply with NACE MR0175/MR0103. Environmental limits

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

PROCEDURE TWO-PLY TESTABLE BELLOWS D 1 OF 5 TWO PLY BELLOWS TEST PROCEDURE

PROCEDURE TWO-PLY TESTABLE BELLOWS D 1 OF 5 TWO PLY BELLOWS TEST PROCEDURE PROCEDURE TWO-PLY TESTABLE BELLOWS D 1 OF 5 TWO PLY BELLOWS TEST PROCEDURE Prepared by: Pathway Piping Solutions Daniel L. Edgar, PE Pine Valley, Ca 91962 Phone: (619) 473-8248 FAX: (619) 473-8148 Pathway

More information

Temperature Controllers

Temperature Controllers IM0004 April 2013 CONTENTS T-12 Thermostat PAGE Introduction 1 Scope 1 Description 1 Specification 1 Temperature Controllers 2 INTRODUCTION CAUTION Prior to installing, the instructions provided herein

More information

INSTRUCTIONS FOR MODEL SSC LOW DELIVERY PRESSURE GAS REGULATORS

INSTRUCTIONS FOR MODEL SSC LOW DELIVERY PRESSURE GAS REGULATORS INSTRUCTIONS FOR MODEL SSC LOW DELIVERY PRESSURE GAS REGULATORS THIS BOOKLET CONTAINS PROPRIETARY INFORMATION OF ADVANCED SPECIALTY GAS EQUIPMENT CORP. AND IS PROVIDED TO THE PURCHASER SOLELY FOR USE IN

More information

1805 Series Relief Valves

1805 Series Relief Valves Instruction Manual Form 1211 1805 Series October 2011 1805 Series Relief Valves! WARNING Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion

More information

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS READ ALL INSTRUCTIONS PRIOR TO INSTALLATION AND OPERATION TO AVOID POSSIBLE INJURY Warning: Always consider any accumulator to contain pressure until proven

More information

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

IFTGS14 Ball Float Steam Trap ½ and ¾ with Integral Spiratec Sensor 6150350/3 IM-P615-12 ST Issue 3 IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation

More information

CARTRIDGE FILTERS TECHNICAL MANUAL MT 080. Installation, commissioning and maintenance instructions. 08/02 Edition

CARTRIDGE FILTERS TECHNICAL MANUAL MT 080. Installation, commissioning and maintenance instructions. 08/02 Edition CARTRIDGE FILTERS TECHNICAL MANUAL MT 080 Installation, commissioning and maintenance instructions 08/02 Edition 1 2 CONTENTS 1.0 PAGE INTRODUCTION 1.1 MAIN FEATURES 1.2 OPERATION 1.3 CLOSING OF HEAD WITH

More information

ROTATING DISK VALVES INSTALLATION AND MAINTENANCE 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6

ROTATING DISK VALVES INSTALLATION AND MAINTENANCE 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6 Sub Section INDEX Page Number 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6 6. INSTALLATION AND OPERATION 6 7. MAINTENANCE 8 8. REPAIR 9 9. ASSEMBLY 10 10.

More information

Safety. April 2018 Supersedes all previous publications 2018 Chevron Phillips Chemical Company LP

Safety. April 2018 Supersedes all previous publications 2018 Chevron Phillips Chemical Company LP Technical Note 802 Leak Testing of Polyethylene Pipe For Municipal and Industrial Applications Part 1 Pre-Test Considerations Leak testing may be used to find leaks in a newly constructed or newly modified

More information

GILMONT ACCUCAL FLOWMETERS

GILMONT ACCUCAL FLOWMETERS OPERATING MANUAL GILMONT ACCUCAL FLOWMETERS 28W092 Commercial Ave. Barrington, IL U.S.A. 60010-2392 (847) 381-4888 (847) 381-7053 (Fax) 800-962-7142 www.barnant.com e-mail: barnant@barnant.com A-1299-0766

More information

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012 Installation Guide English September 2012 299H Series Introduction This Installation Guide provides instructions for installation, startup, and adjustment of 299H Series regulators. To receive a copy of

More information

BUTTERFLY VALVES Series 800

BUTTERFLY VALVES Series 800 BUTTERFLY VALVES Series 800 WARNING Before proceeding read ALL instructions and become familiar with the equipment and associated drawings. Follow ALL applicable safety regulations and codes for pressurized

More information

Fluid Sealing Association

Fluid Sealing Association Fluid Sealing Association STANDARD FSA-PSJ-701-06 PIPING SYSTEMS NON-METALLIC EXPANSION JOINT HYDROTESTING AND VACUUM TESTING 994 Old Eagle School Road, Suite 1019 Wayne, Pennsylvania 19087-1866 Phone:

More information

SALCO PRODUCTS, INC. PRESSURE RELIEF VALVE STORAGE, INSTALLATION, OPERATING, MAINTENANCE/TESTING, AND INSPECTION INSTRUCTIONS

SALCO PRODUCTS, INC. PRESSURE RELIEF VALVE STORAGE, INSTALLATION, OPERATING, MAINTENANCE/TESTING, AND INSPECTION INSTRUCTIONS STORAGE INSTRUCTIONS Until it is time to install a new or reconditioned valve on the car, the valve must be kept in its original packaging in order to protect it from dirt and damage. INSTALLATION INSTRUCTIONS

More information

SECTION PRESSURE TESTING OF PIPING

SECTION PRESSURE TESTING OF PIPING SECTION 15044 PRESSURE TESTING OF PIPING PART 1 - GENERAL 1.01 DESCRIPTION A. Scope of Work: This section specifies the leakage and pressure testing of piping. B. Testing Records: PART 2 - PRODUCTS 2.01

More information

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Welker Sampler Model GSS-1 The information in this manual has been carefully checked for accuracy and is intended to be used as a guide to operations. Correct

More information

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow Model: FP 450-80 Installation Operation Maintenance PAGE 1 OF 5 1. Safety First BERMAD believes that the safety of personnel

More information

Bray/ VAAS O-Ported Series Knife Gate Valve 770/780 Series Operation and Maintenance Manual

Bray/ VAAS O-Ported Series Knife Gate Valve 770/780 Series Operation and Maintenance Manual Bray/ VAAS Knife Gate Valve 770/780 Series Operations and Maintenance Manual Table of Contents Definition of Terms 1 Safety Instructions 1 Introduction 2 Unpacking 2 Storage 2 Installation 2 Commissioning

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

Valve Inspection & Testing

Valve Inspection & Testing Inspection & Testing in accordance with API 598 Valve Inspection & Testing Shell Test (Body Hydro Test): - Each valve shall be tested in accordance with ASME B 16.34 for ASME valves. Shell test pressure

More information

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE February 9, 1998 Foam 101a A BLADDER TANK WITH 1. DESCRIPTION A Wet Pipe Bladder Tank Foam/Water System is a standard wet pipe automatic sprinkler system capable of discharging a foam/water solution automatically

More information

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator. LRS(H)4 USER MANUAL Read the complete manual before installing and using the regulator. WARNING INCORRECT OR IMPROPER USE OF THIS PRODUCT CAN CAUSE SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE. Due to the

More information

Binks SG-2 Plus TM Rotary 2 QT. PRESSURE CUP

Binks SG-2 Plus TM Rotary 2 QT. PRESSURE CUP Binks SG-2 Plus TM Rotary 2 QT. PRESSURE CUP Model No. 80-651 Rotary Agitator INTRODUCTION Binks SG-2 TM Plus Rotary 2 Qt. Pressure Cup is ideal for component spraying and industrial applications where

More information

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection 1170850/1 IM-P117-36 ST Issue 1 MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection Installation and Maintenance Instructions 1. Safety information 2. General product information

More information

INSTALLATION & MAINTENANCE INSTRUCTION

INSTALLATION & MAINTENANCE INSTRUCTION ARCHON Industries, Inc Liquid Level Gauges Models: BT-LLG ND-LLG INSTALLATION & MAINTENANCE INSTRUCTION Instruction No.: 1014.2 Revision Issued: 3/01/03 Approved: Engineering Manager Warning ONLY QUALIFIED

More information

Types 749B and R130 Changeover Manifolds

Types 749B and R130 Changeover Manifolds Instruction Manual MCK-1179 Types 749B and R130 June 2012 Types 749B and R130 Changeover Manifolds TYPE HSRL-749B TYPE 64SR/122 TYPE R130/21 TYPE 749B/21 Figure 1. Changeover Manifolds and Regulator Assemblies

More information

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual Fisher Controls Instruction Manual Type S301 & S302 Gas Regulators October 1981 Form 5180 WARNING Fisher regulators must be installed, operated, and maintained in accordance with federal, state, and local

More information

1800CPB2 Service Regulators

1800CPB2 Service Regulators SB 8520.5 1800CPB2 Service Regulators Maximum Inlet Pressure 125 PSIG Table of Contents 1800CPB2 Regulator Information................ 2-3 1800CPB2 Capacity Performance................ 4-6 1-1/4" Models,

More information

Eaton Filtration, LLC

Eaton Filtration, LLC Eaton Filtration, LLC 900 Fairmount Avenue, Elizabeth, NJ 07207 Phone: 908-787-1000 Fax: 908-351-7893 E-Mail: filtration@eaton.com Web: www.filtration.eaton.com Installation, Operation & Service Manual

More information

Float Operated Level Controllers

Float Operated Level Controllers CONTENTS Float Operated Level Controllers IM0015 Nov. 2014 PAGE Introduction 1 Scope 1 Description 1 Specification 1 Control Installation 2 INTRODUCTION Side Mount Back Mount Prior to installing, the instructions

More information

FLANGED TWO-PIECE BALL VALVES

FLANGED TWO-PIECE BALL VALVES INTRODUCTION This instruction manual includes installation, operation, and maintenance information for FNW flanged split-body ball valves. This manual addresses lever operated ball valves only. Please

More information

TECHNICAL DATA. than the water inlet pressure to the concentrate

TECHNICAL DATA. than the water inlet pressure to the concentrate Foam102a 1. DESCRIPTION The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with 3M foam concentrates. This system consists of a standard wet pipe sprinkler

More information

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors 1130050/4 IM-P113-02 ST Issue 4 UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors Installation and Maintenance Instructions 1. Safety information 2. General product information

More information

Anderson Greenwood Series 93 Positive Pressure POSRV Installation and Maintenance Instructions

Anderson Greenwood Series 93 Positive Pressure POSRV Installation and Maintenance Instructions Before installation these instructions must be fully read and understood Installation and maintenance instructions for Series 93 Positive Pressure Pilot Operated Safety Relief Valves (POSRV). The intent

More information

Date of Issue: July 2016 Affected Publication: API Specification 16C, Choke and Kill Equipment, Second Edition, March 2015 ADDENDUM 1

Date of Issue: July 2016 Affected Publication: API Specification 16C, Choke and Kill Equipment, Second Edition, March 2015 ADDENDUM 1 Date of Issue: July 2016 Affected Publication: API Specification 16C, Choke and Kill Equipment, Second Edition, March 2015 ADDENDUM 1 Page 16, Section 4.6, delete the entire section and renumber all subsequent

More information

Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device

Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device Instruction Manual Form 5492 Types S108K and S109K May 1999 Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device Introduction Fisher regulators must be installed, operated

More information

USER INSTRUCTIONS. NAF Duball DL Ball Valves. Installation Operation Maintenance. Experience In Motion. flowserve.com

USER INSTRUCTIONS. NAF Duball DL Ball Valves. Installation Operation Maintenance. Experience In Motion. flowserve.com USER INSTRUCTIONS NAF Duball DL Ball Valves FCD NFENIM4167-01-A4 01/17 Installation Operation Maintenance 1 Experience In Motion Contents SAFETY 3 1 General 3 2 Lifting 4 3 Receiving Inspection 4 4 Installation

More information

1800CPB2 Service Regulators Maximum Inlet Pressure 125 PSIG

1800CPB2 Service Regulators Maximum Inlet Pressure 125 PSIG A C E D SB-8520.2 1800CPB2 Service Regulators Maximum Inlet 125 PSIG AMC Quality System QMI is Accredited by: C R E D I T ISO 9001 Certified Certificate #006697 R E ANSI RAB G I S T R A R Dutch Council

More information

SECTION BUTTERFLY VALVES

SECTION BUTTERFLY VALVES SECTION 15112 BUTTERFLY VALVES PART 1 GENERAL 1.01 SUMMARY A. All butterfly valves shall be of the tight closing, rubber seated type and fully comply with the latest revision of AWWA Standard C504, Class

More information

9.0 Equipment Cleaning and Repair

9.0 Equipment Cleaning and Repair 9.0 Equipment Cleaning and Repair Introduction The following sections provide an overview of procedures and techniques used to prepare phosgene equipment for maintenance and return the equipment to service,

More information

HPIC D Hydrostatic Test Pump PRODUCT INFORMATION AND OPERATING INSTRUCTIONS

HPIC D Hydrostatic Test Pump PRODUCT INFORMATION AND OPERATING INSTRUCTIONS WIDDER TOOLS HPIC-10000-D Hydrostatic Test Pump PRODUCT INFORMATION AND OPERATING INSTRUCTIONS Description: The WIDDER Hydrostatic Test Systems C Series is a portable, selfcontained, air driven hydrostatic

More information

Assembly-, installation- and maintenance instruction manual for bladder accumulators IBV / EBV , top reparable

Assembly-, installation- and maintenance instruction manual for bladder accumulators IBV / EBV , top reparable Page 1 von 8 Assembly-, installation- and maintenance instruction manual for bladder accumulators IBV / EBV 100-575, top reparable Content Seite 0 Legend 2 1 Overview 2 2 Accumulator assembly and installation

More information

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS TYPE BV2-LD

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS TYPE BV2-LD INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS TYPE BV2-LD 1. Storage & Protection 1.1. Storage The valves stay in the open position during the transportation. For incoming QC must check: a. Packing

More information

3/8" Dr. Air Butterfly Impact Wrench

3/8 Dr. Air Butterfly Impact Wrench 8192106 3/8" Dr. Air Butterfly Impact Wrench Owner s Manual Read and understand all instructions before use. Retain this manual for future reference. Specifications Construction: Polished aluminum and

More information

Spray Gun 134-A. 1 Liter High- Pressure Gel Coat. Usage Instructions & Parts List

Spray Gun 134-A. 1 Liter High- Pressure Gel Coat. Usage Instructions & Parts List 1 Liter High- Pressure Gel Coat Spray Gun 134-A Usage Instructions & Parts List www.fibreglast.com 1.800.821.3283 385 Carr Drive Brookville, OH 45309 Operating Instructions & Suggestions This is a high

More information

Leak testing of Valves. Standards for acceptable Rates of Valve Leakage

Leak testing of Valves. Standards for acceptable Rates of Valve Leakage Leak testing of Valves Standards for acceptable Rates of Valve Leakage American Petroleum Institute (API) The API standard 598: Valve Inspection and Testing, covers the testing and inspection requirements

More information

Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia

Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia - 1-122.6010.6 These instructions describe the installation, operation and maintenance of the subject equipment. Failure

More information

Section GATE VALVES

Section GATE VALVES Section 02521 PART 1 GENERAL 1.01 SUMMARY This Section includes the furnishing and installation of gate valves for isolation and dead-end service as shown on Plans and as specified herein. 1.02 MEASUREMENT

More information

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION INSTALLATION INSTRUCTIONS CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION The CVS Controls 67CFR Filter regulator is a pressure reducing supply regulator typically used for pneumatic

More information

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , &

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , & REDQ Regulators Model 411B Barstock Design Powreactor Dome Regulator OPERATION AND MAINTENANCE Contents Scope..............................1 Installation..........................1 General Description....................1

More information

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve. Foam 302 a 1. DESCRIPTION (Refer to Figure 1 on page 302 e.) The Viking Low-Flow Foam/Water Proportioning System is a UL Listed and FM Approved system, for use with 3M and Viking brand foam concentrate.

More information

FLANGED MULTI-PORT BALL VALVES

FLANGED MULTI-PORT BALL VALVES INTRODUCTION This instruction manual includes installation, operation and maintenance information for flanged multi-port ball valves. This manual addresses lever operated ball valves only. Please refer

More information

v. Size shall be specified on drawings.

v. Size shall be specified on drawings. SPECIFICATION FOR VACUUM INSULATED PIPING Part 1 General 1. Submittals a. After award of contract and before executing any manufacturing, shop drawings and specifications shall be submitted to the customer

More information

SAPAG. Safety valves, type 5700 Storage, Use, Operation and Maintenance Instructions. IMPORTANT NOTICE

SAPAG. Safety valves, type 5700 Storage, Use, Operation and Maintenance Instructions.  IMPORTANT NOTICE SAPAG IMPORTANT NOTICE Contents Important notice 1 0 Valve identification 2 1 Storage 2 2 Installation 2 3 Operation 2 4 Maintenance 3 4.1 Dismantling 3 4.2 Inspection 3 4.3 Repair 3 4.4 Assembly 4 4.5

More information

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator. RHPS Series RD(H)F40 User Manual Read the complete manual before installing and using the regulator. 2 WARNING Before removing a regulator from the system for service, you must depressurize system purge

More information

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions PREVIOUS REFERENCE NO. IMP02355 0231150/13 IMF0501ENISS2 CMGT S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions 1. Safety information 2. General product information

More information

TECHNICAL DATA. Page 1 of 12

TECHNICAL DATA. Page 1 of 12 Page 1 of 12 1. DESCRIPTION The Viking Regulating Valve is a direct-acting, single-seated, spring-loaded diaphragm valve. When installed as a pilot regulating valve on a Viking Model H or J Flow Control

More information

FLANGED TWO-PIECE BALL VALVES

FLANGED TWO-PIECE BALL VALVES INTRODUCTION This instruction manual includes installation, operation, and maintenance information for FNW flanged split-body ball valves. This manual addresses lever operated ball valves only. Please

More information

TBV OPERATION AND MAINTENANCE MANUAL SERIES 2800: FLANGED BALL VALVE. For technical questions, please contact the following:

TBV OPERATION AND MAINTENANCE MANUAL SERIES 2800: FLANGED BALL VALVE. For technical questions, please contact the following: TBV OPERATION AND MAINTENANCE MANUAL SERIES 2800: FLANGED BALL VALVE For technical questions, please contact the following: Engineering Department 1537 Grafton Road Millbury, MA 01527 Phone: (508) 887-9400

More information

Pipeline Systems PIP PLSC0019 Specification for Pressure Testing HDPE Plastic Pipeline Systems

Pipeline Systems PIP PLSC0019 Specification for Pressure Testing HDPE Plastic Pipeline Systems November 2017 Pipeline Systems PIP PLSC0019 Specification for Pressure Testing HDPE Plastic Pipeline Systems PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry

More information

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES THIS BOOKLET CONTAINS PROPRIETARY INFORMATION OF ADVANCED SPECIALTY GAS EQUIPMENT CORP. AND IS PROVIDED TO THE PURCHASER SOLELY FOR USE

More information

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002 Installation Guide English May 2002 Type ACE97 Introduction This installation guide provides instructions for installation, startup, and adjustment. To receive a copy of the instruction manual, contact

More information

GREIG FILTERS, INC. OPERATION MANUAL

GREIG FILTERS, INC. OPERATION MANUAL GREIG FILTERS, INC. OPERATION MANUAL MODEL DCFH 3P 15/3 100 S4 DOE/222 DUAL CARTRIDGE FILTER HOUSING TABLE OF CONTENTS I. INTRODUCTION II. CARTRIDGE FILTER HOUSING UNIT A. OPERATION B. INSTALLATION C.

More information