N2 BLAST Datasheet Preaction single interlock electric c/w N 2 Blast Nitrogen generating system Remote controlled unit
|
|
- Emerald Wilkerson
- 5 years ago
- Views:
Transcription
1 (System shown is a self contained unit) FireFlex N 2 Blast description The FIREFLEX N2 Blast integrated system consists of an integrated single interlock Electric release preaction automatic sprinkler system combined with a Nitrogen generating system, factory-assembled in a single cabinet. All the necessary components are integrated. The FIREFLEX N2 Blast is fully tested at factory. The FIREFLEX N2 Blast System uses the N2 Blast Nitrogen generator system Type 1 FPS-250 or FPS-750 system, made by South-Tek Systems. All the deluge valves are rated up to a maximum of 250 psi WWP (1724 kpa) max. and are available in the following diameters: 1½" (40 mm) 3" (80 mm) 6" (150 mm) 2" (50 mm) 4" (100 mm) Warning: 6" (150 mm) available with N2 Blast Type 1 FPS-750 only. Features Inhibits corrosion with 98%+ pure Nitrogen Trouble-free design for safe and easy application Available in 2 cabinet sizes Uses South-Tek N2 Blast Best value in nitrogen generation technology Limits the liability of early pipe replacement Uses the Viking deluge valve Trim is fully assembled and tested at the factory All trims are galvanized steel, Listed and Approved for 250 psi (17.2 bar) service maximum Quick connections to water supply and drain on left side, and sprinkler riser on top of unit, all available with grooved end or flanged fittings No open drain cup inside unit Separate unlocked access hatch to emergency manual release Compact, aesthetic and easy to move User-friendly standardized owner's manual with every unit Unique serial number on every unit Uses UL, ULC and/or FM Approved components Designed in accordance with NFPA Standards Sturdy 14 gauge steel cabinet painted fire red with oven baked polyester powder on phosphate base Textured rust proof finish Neoprene gasket on all doors to eliminate vibrations Manufactured under ISO-9001 quality control procedures Prewired to a terminals block 1 of 14 FM-076D-0-115D
2 System configurations Single Interlock Preaction combined with N2 Blast Type 1 FPS-250 (250 gallons system) Single Interlock Preaction combined with N2 Blast Type 1 FPS-750 (750 gallons system) Systems hydraulic limitations The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. Designers should refer to the appropriate NFPA Standards and any other applicable codes for their final design. Also refer to FireFlex Systems Inc. appropriate user manuals and to manufacturer's data sheets for additional details. Systems limitations indicated below are nominal flow limitations. Piping Equivalent Lengths w/o System size Usage Range shut off valve (in.) (gpm) Piping Equivalent Lengths c/w shut off valve (m.) (ft.) (m.) (ft.) GPM 1½ Drain 250 PSIG w.p. Sequence of operation Preaction operation 1. The activation of the detection condition is necessary to cause the deluge valve actuation. 2. Detection condition: Single zone (the operation of one detector in the protected area is required to fulfill the detection condition). Crossed zone (the operation of two detectors in the protected area is required to fulfill the detection condition). 3. The activation of the detection condition alone will activate the solenoid valve (F1) open, causing the deluge valve to open and allowing water to enter the system piping. The alarm pressure switch (C1) will activate. Water will not discharge into the protected area since all sprinkler heads are closed. When a sprinkler head opens, water will flow. 4. The opening of an automatic sprinkler OR damage to system piping without the detection condition satisfied will activate the low air supervisory (E4) switch contact but will not allow the water to enter the system piping. 5. Operation of the emergency manual release will depressurize the priming chamber, causing the deluge valve to open and allowing water to enter the system piping and water will discharge through any open sprinklers.the alarm pressure switch (C1) will activate. N2 Blast Nitrogen generator system operation 1. The initial air supply fill of the piping system within 30 minutes as per NFPA 13 is accomplished using the initial fill air compressor. This compressor is equipped with a factory-adjusted ON/OFF pressure switch which is tied into the sprinkler system piping. It is factory-set at 10 and 20 psi for the cut-in and cut-out pressures respectively. There is a "low air" supervisory pressure switch which monitors system piping air/nitrogen pressure at all times. It is factory-set at 12 psi to provide a "low air" supervisory signal. 2. The nitrogen generation/maintenance air compressor is supplied as an integral part of the STS N2-Blast Nitrogen Generation System. It is equipped with a factory-adjusted ON/OFF pressure switch which is tied into the nitrogen storage tank. It is factory-set at 65 psi and 75 psi for the cut-in and cut-out pressures respectively. The Viking D-2 Air Pressure Maintenance Device is installed and factory-adjusted to 20 psi (normal system air/nitrogen pressure) downstream of the nitrogen storage tank. As the system continually purges with Nitrogen, the APMD will continually draw from the Nitrogen storage tank to maintain supervisory pressure (20 psi). Should the N2- Blast generator run for more than 6 hours consecutively, the Leak Detection System (LDS) will automatically shut it down and activate a trouble contact. 3. The air and nitrogen supply systems are fully integrated and fully automatic in the FireFlex - N2- Blast. No shut-off or bypass valve is required. The nitrogen generator is equipped with a BlastOff Leak Detection System (LDS). Should the nitrogen generator compressor fail or a leak occur that can not be compensated by the nitrogen generating system, the preaction system air compressor will act as a back-up and start-up at 10 psi system pressure. FM-076D-0-115D 2 of 14
3 Standard equipment Deluge valve The Viking Model F-1 Deluge Valve is a quick-opening, differential diaphragm flood valve with one moving mechanism. The deluge valve is used to control water flow in preaction sprinkler systems. The valve is held closed by system water pressure trapped in the priming chamber, keeping the outlet chamber and system piping dry. In fire conditions, when the releasing system operates, pressure is released from the priming chamber. The deluge valve clapper opens to allow water to flow into the system Preaction riser check valve The Viking 1-½ and 2 spring loaded In-Line check valve is a general purpose rubber-faced check valve approved for use in fire-service systems. The Spring Loaded In-Line check valve is manufactured with a brass body, brass seat, and a rubber-faced clapper assembly. The Viking 3, 4 and 6 Easy Riser Swing check valve is a general purpose rubber-faced check valve approved for use in fire service systems. The valve is for use in preaction system risers. Water supply control valve The water inlet control valve is a supervised, indicating butterfly valve. Purpose of this vale is to manually shutoff the preaction system. Solenoid valve The high pressure solenoid valve is a two-way type with one inlet and one outlet. It is a packless, internal pilot operated valve, suitable for use in releasing water pressure from the priming chamber of Viking Deluge Valves. The solenoid valve has floating diaphragm construction, which requires a minimum pressure drop across the valve to operate properly. IN OUT 3 of 14 FM-076D-0-115D
4 Standard equipments (continued) Low air supervisory switch The low pressure switch monitors the pressure within the sprinkler piping should a loss of the air below 12 Psi occur. The pressure switch contacts transfer indicating supervisory signal. POTTER PS40-1A Alarm pressure switch The alarm pressure switch monitors the water flow within the sprinkler piping. Should the Deluge Valve clapper opens to allow water to flow into the sprinkler piping. The alarm pressure switch will activate, indicating a water flow signal POTTER PS10-1A Releasing circuit disconnect switch The releasing circuit disconnect switch is used to disable the releasing solenoid. When the key is set to Disable, the releasing solenoid will be disconnected from the control panel s releasing circuit, causing a trouble signal and preventing accidental discharge during maintenance or inspection. N2 Blast Nitrogen generator South-Tek Systems utilizes Membrane technology in the N2-Blast Corrosion Inhibiting Systems in order to efficiently separate Nitrogen molecules from the air we breathe. Membrane technology, used in our smaller applications, has a simple air flow design, is wall-mounted and easy to service. PSA technology is more cost effective and energy efficient in larger Fire Protection Systems, those requiring more Nitrogen to compensate for the NFPA acceptable leak rate. BlastOff Leak detection system Unless the leak rate is catastrophic, the supervisory low pressure alarm on the FPS will not activate. Minor leaks cause the air compressor and N2-Blast to run excessively in order to maintain supervisory pressure. The unnecessary additional run-time decreases the lifespan of the equipment. The Patent Pending BlastOff - Leak Detection System is designed to detect significant leaks before they compromise the FPS and the Nitrogen Generation System. It has an internal audible alarm and dry contact for wiring into the Building Monitoring System (BMS) and will also alarm if the air compressor or the N2- Blast is not working properly. Nitrogen generator storage cylinder Type 1 Nitrogen Generation Systems include a 16 gallon Nitrogen receiver tank (12.2 dia x 44.8 H). Nitrogen generated by the N2-Blast is stored in the tank, and then sent to the sprinkler system through the Nitrogen air pressure maintenance device. N2 Blast AutoPurge System High purity Nitrogen must be equally distributed throughout the entire sprinkler piping system in order to effectively inhibit corrosion. The Patent Pending AutoPurge System provides a low volume, constant purge of Nitrogen within sprinkler piping. The rate in which gas is evacuated from the sprinkler piping is within NFPA guidelines and allows breathing to occur. The AutoPurge System also assists in drying out the residual water from a hydro test. Computational Fluid Dynamics modeling proves that this is the most effective way to ensure that high purity Nitrogen reaches all branches within the sprinkler piping. Install one AutoPurge System per system at a high point. There is a Label on one side of the housing that lists the proper setting for a variety of zone sizes. The Label list: Gallons in Zone, and APS Flow Setting. The Flow Setting is labeled from A-E and has three Settings in between each letter. Nitrogen generator air pressure maintenance device FIREFLEX N2 Blast use the Viking Model D-2 Air Pressure Maintenance Device (APMD) which is a pressure regulator that automatically reduces the supply air pressure to a preset requirement when connected to a constantly maintained air supply. The APMD is used to regulate the nitrogen pressure to 20 psi in the sprinkler piping at the specified system pressure for FIREFLEX N2 Blast system. FM-076D-0-115D 4 of 14
5 Optional preaction equipment Shut-off valve & sight glass (optional) The Shut-off Valve & Sight Glass Option is intended to be used for applications where testing of the system operation without filling the sprinkler piping network is desirable and where it is critical that all functions of the preaction system be tested under actual discharge conditions. Main drain valve Sight glass assembly Shut-off valve Riser check valve Semi-flange inlet / outlet (optional) When required by the user, FIREFLEX N 2 Blast units can be provided in a semi-flanged configuration. The semi flanged option provides flanged fittings only on the water inlet pipe (left side) and on the system riser outlet. The drain manifold is provided with a threaded connection (left side). The rest of the fittings are the same as usual with the main components being provided in the standard flanged / grooved configuration. Point flashlight HERE Deluge valve Flange fitting outside cabinet Main water supply control valve Riser check valve Deluge valve FM-076Z-0-4B-1 Anti-column device option The model LD-1 anti-column device is an optional trim component designed for use with preaction sprinkler systems. The anti-column device automatically prevents an unwanted water column from establishing within the system riser. On preaction sprinkler systems the anticolumn device prevents water from columning downstream of the easy riser check valve. Threaded drain output Flange fitting outside cabinet FM-076Z-0-4B-2 Main water supply control valve From Sprinkler Riser To Drain Collector FM-061H-0-146A 5 of 14 FM-076D-0-115D
6 Preaction system - Air supply Direct air compressor (Style A ) Used only for the sprinkler piping network of the preaction system. Air supply style "A" includes the air compressor mounted inside the FIREFLEX N2 Blast cabinets with its supervisory trim and options. Compressors are of the tankless, oiless piston type and are factory piped to the sprinkler system riser, all within the FIREFLEX N2 Blast cabinets. Compressors are available in four (4) sizes: 1/6HP 1/2HP 1/3HP 1HP This section replaced by Dehydrator option (when used) E4 (plugged with SureFire trim) Copper tubing TO OPTIONAL ACCELERATOR (plugged when not used) Pressure relief valve Compressor Service Factor Amp (S.F.A) rating Compressor Size (HP) 115Vac / 60Hz 230Vac / 60Hz 1/6 5.0 Amp. 2.5 Amp. 1/3 7.4 Amp. 3.7 Amp. 1/ Amp. 5.0 Amp Amp. 9.0 Amp. 115 / 220 Vac 60Hz Compressor selection Table: H.P 40 PSI System capacity to fill system to 20 PSI in 30 minutes * 1/ gal. 1/ gal. 1/ gal gal. * For systems with maximum water supply pressure up to 250 PSI (1724 kpa) WARNING The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. 2 TO DRAIN COLLECTOR 1 TO SPRINKLER RISER 3 TO PNEUMATIC ACTUATOR (plugged when not used) CONTRACTOR'S HYDROSTATIC TEST PORT (system side) FM-061H-0-118C Air Pressure Maintenance Device (Style B ) Used only for the sprinkler piping network of the preaction system, when an external air supply is provided by others (tank mounted compressor or plant air) and piped to the air inlet port of the unit. Air supply style "B" provides an Air Pressure Maintenance Device (APMD) trim, factory mounted in the FIREFLEX N2 Blast cabinets. This section replaced by Dehydrator option (when used) E4 (plugged with SureFire trim) TO PNEUMATIC ACTUATOR (plugged when not used) 3 Contractor external Air or Nitrogen connection TO OPTIONAL ACCELERATOR (plugged when not used) 1 TO SPRINKLER RISER FM-061H-0-119B CONTRACTOR'S HYDROSTATIC TEST PORT (system side) FM-076D-0-115D 6 of 14
7 Details & field wiring diagrams P & ID Autopurge System Sprinkler N2 Blast Compressor Preaction Compressor Air Maintenance Device/s (AMD/s) Supplied by Fireflex Riser towards the nozzles Tank Provided with brackets and Strap Low Air Pressure Switch Preaction Air Kit Preaction System Nitrogen Air 7 of 14 FM-076D-0-115D
8 Cabinet with main components, shown without door(s) FM-06LM-0-1A-1 FM-076D-0-115D 8 of 14
9 Trim diagram To Air Supply System Trim E4 1 F5 FIELD CONNECTION TO SPRINKLER PIPING NETWORK TO RELEASE SYSTEM TRIM AND OPTIONAL ACCELERATOR (when used) C1 F4 D2 B10 D3 B8 C2 B5 B11 A1 F3 To Air Supply System Trim 2 B7 D1 B9 B13 FIELD CONNECTION TO OPEN DRAIN (left side only) B12 B3 B4 B2 B1 FIELD CONNECTION TO WATER SUPPLY (left side only) TotalPac Base (shown without enclosure) CONTRACTOR'S HYDROSTATIC TEST PORT (water supply side) FM-076Z-0-58A Trim Components: A1 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 Deluge valve Priming valve Strainer 1/16" Restricted orifice Spring loaded check valve Alarm test valve Flow test valve Drip check valve Drain check valve Pressure operated relief valve (PORV) Emergency release valve Prime pressure water gauge & valve Water supply pressure gauge & valve Clapper check valve C1 C2 D1 D2 D3 F1 Alarm pressure switch Connection to water motor gong (strainer supplied by contractor) Water supply control valve Riser check valve Main drain valve 24Vdc N.C. Solenoid valve 9 of 14 FM-076D-0-115D
10 Wiring diagram TBB WIRING OF INPUT POWER SOURCE 120VAC, 60Hz LINE NEUTRAL GROUND GROUND NEUTRAL LINE N2BLAST NITROGEN GENERATING SYSTEM 20A MAX PREACTION AIR COMPRESSOR 1HP MAX WITH AIR OPTION "A" ONLY Refer to Local Electrical Codes for wiring size. NOTES: All devices are factory wired. All devices are shown in their normal supervisory state. Contacts are rated: Pressure switches: 2A, 30VDC 10A, 125/250VAC Supervisory switches: 0.5A, 125VDC 0.25A, 250VDC 5A, 1/6HP, 125/250VAC Relay module: 0.45A 125VDC 0.35A, 250VDC 16A, 30VDC 16A, 250VAC Use dry contacts with power limited circuits only. EOL devices (not included) must be compatible with the Release Control Panel used. Branch circuit for air compressor shall not be the same as the N2Blast Nitrogen Generating System. OPTIONAL USED ONLY WITH NYC OPTION CHICAGO OPTION LOS ANGELES OPTION WATER FLOW EOL PREACTION LOW AIR PRESSURE SUPERVISORY EOL MAIN VALVE EOL SOLENOID VALVE BYBASS SWITCH SUPERVISORY EOL 24 VDC * SHUT-OFF VALVE EOL C NO MAIN VALVE NC TBC C OPTIONAL TBA SHUT-OFF VALVE NO NC N2BLAST LOW AIR PRESSURE SUPERVISORY EOL LOW AIR PRESSURE ALARM EOL * Needed for keyswitch LEDs operation WATER FLOW SWITCH PREACTION LOW AIR PRESSURE SWITCH MAIN VALVE SUPV SWITCH N2BLAST LOW AIR PRESSURE RELAY S N.C. SOLENOID VALVE (see table below for ratings) LED POWER RELEASING CIRCUIT DISCONNECT SWITCH SHUT-OFF VALVE SUPV SWITCH LOW AIR PRESSURE SWITCH MAIN VALVE SUPV SWITCH SHUT-OFF VALVE SUPV SWITCH NOTE: Contacts provided for connection to the building's central Fire Alarm Panel. FM-061H-0-211B SOLENOID VALVE ELECTRICAL RATINGS Viking P/N Description Pressure Voltage Watts DC Amps (De-energized) Rating NC 24 VDC 10.0 DC 416 ma 300 psi (2 068 kpa) Notes: 1. Solenoid Valve is UL Listed as Fire Protection Special System Water Control Release Service (UL 429A Product category VLTR). 2. Voltage Drop: For proper operation, make sure that voltage at the solenoid valve is at least 85% of nameplate rating. FM-076D-0-115D 10 of 14
11 Cabinet The FIREFLEX N2 Blast cabinet is made of sturdy 14 gauge steel. Refer to figure 4 for dimensions. All surfaces are rust proof coated, inside and outside, with fire red, oven baked polyester powder on phosphate base. Cabinet is provided with two doors, all provided with a neoprene gasket to avoid vibrations, giving the access to the pressure gauges reading and the manual emergency release. The cabinet assembly is pre-assembled, pre-wired, and factory tested under ISO-9001 conditions. Refer to figures 2 & 3 for installation and clearances details. Electrical junction boxes are integrated inside the cabinet for connection of the supervisory and alarm devices contacts. Knockouts are pre-punched for the installing contractor as indicated on figure 1. Figure 1 - knockouts details Top of Cabinet High voltage 2½" Low voltage 2½" Typ. 8½" 3¾" 3" FM-061H-0-68B-12 Figure 2 - Floor anchoring template F 5'' Ø3/4" E G FM-061H-1-49B-6 Size E F G 46" 15" 48" 25" 54" 21" 56" 27" Figure 3 - Required clearance 12'' MIN 12'' MIN 22'' MIN FM-061H-1-49B-7 Size A 46" 24" 54" 32" 11 of 14 FM-076D-0-115D
12 Figure 4 - Cabinet dimensions D P TBA, TBB & TBC Q TBB TBA & TBC CONTROL PANEL (except for Remote Controlled Unit) CONTROL PANEL OPTIONAL SHUT-OFF VALVE ØB SPRINKLER RISER SCH.40 GROOVED OUTLET F SPRINKLER RISER SCH.40 GROOVED OUTLET S R N DRAIN - SCH.40 GROOVED OUTLET ØA ØC M WATER INLET SCH.40 GROOVED OUTLET G T FM-06LM-0-2A System Size A B C D E F G H J K L M N P Q R S T 1½" 2" 1½" 2" 46" 25" 77¼" 4" 8¾" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 37½" 44¾" 50" 2" 2" 2" 2" 46" 25" 77¼" 4" 8¾" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 37¾" 45" 50" 3" 4" 3" 2" 46" 25" 77¼" 4" 10" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 44" 47¾" 50" 4" 4" 4" 2" 54" 31" 81¼" 4" 10" 11½" 13¾" 3¾" 2½" 2½" 23¾" 11½" 48½" 53" 58" 6" 6" 6" 2" 54" 31" 81¼" 4" 11" 13" 13¾" 5¼" 2¾" 2¾" 25" 13" 59¼" 65¼ 58" Dimensions are nominal and may vary by ¼ FM-076D-0-115D 12 of 14
13 13 of 14 FM-076D-0-115D
14 1935, Lionel-Bertrand Blvd. Boisbriand QC Canada J7H 1N8 Tel.: Fax: Toll Free: Web: FM-076D-0-115D 14 of 14
TotalPac X Single interlock Preaction system Electric release
DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical and mechanical
More informationTECHNICAL DATA. Q = C v P S
January 6, 2012 Preaction 333a 1. Description Viking supervised Surefire Preaction Systems Utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated Viking G-3000P Valve comes complete
More informationTECHNICAL DATA. Q = C v P S
January 6, 2012 Preaction 348a 1. Description Viking supervised Surefire Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated Viking G-6000P Valve comes complete
More informationTECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE
1 of 10 1. DESCRIPTION (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system
More informationTECHNICAL DATA. Q = C v P S
Preaction 346a 1. Description The 6 Model G-6000P Electric Release Preaction System Riser Assembly can be used as a Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction
More informationTECHNICAL DATA OBSOLETE
April 9, 2009 Preaction 326a 1. DESCRIPTION Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilizing the Viking G-4000P Deluge Valve. The small profi le, lightweight,
More informationTECHNICAL DATA. Q = C v P S
January 6, 2012 Preaction 331a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated
More informationTECHNICAL DATA. Q = C v P S
January 6, 2012 Preaction 347a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated
More informationTECHNICAL DATA. Trimpac 257a. September 16, 2013
September 16, 2013 Trimpac 257a 1. DESCrIpTION DESCRIPTION The Viking Double SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-2 and D-2B used with either a Model E or F Deluge Valve (A.1), a Viking
More informationSouth-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS)
South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System Designed for: Dry or Preaction Fire Protection Systems (FPS) 1.0 Description of Work 1.1 The Fire Sprinkler Contractor shall provide
More informationTECHNICAL DATA. Trimpac 256a. October 31, 2013
October 31, 2013 Trimpac 256a 1. DESCRIPTION The Viking SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-1 and D- 1B used with either a Model E or F Deluge Valve (A.1), a Viking Easy Riser check valve
More informationTECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY
Page 1 of 13 1. DESCRIPTION The Viking 3 Model G-3000 Dry Valve Riser Assembly is equipped with a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry
More informationTECHNICAL DATA. Q = C v P S
Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler
More informationTECHNICAL DATA. Q= Cv S
Page 1 of 13 1. DESCRIPTION The Viking 4 inch Model G-4000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry
More informationTECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13
Page 1 of 13 1. Description The Viking 2 Model G-2000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler
More informationTECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which
January 27, 2012 307a 1. (Refer to Figures 1-3.) A Viking Non-Interlocked Preaction system utilizes a Viking Deluge Valve to control water flow into system piping equipped with closed sprinklers. Under
More informationTECHNICAL DATA. Trimpac 251a. Spetember 16, 2013
Spetember 16, 2013 Trimpac 251a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-6 and B-6B is a factory assembled trim package for a double interlocked preaction system with an electric/pneu-lectric release
More informationTECHNICAL DATA. TRIMPAC Model B-5 & B-5B
September 16, 2013 Trimpac 250a 1. DESCRIPTION DEsCRIPTIoN is a factory assembled trim package for a ed an electric/pneumatic release module in a metal enclosure. The standard trim normally required on
More informationTECHNICAL DATA. Dry 132a. October 1, 2008
October 1, 2008 Dry 132a 1. Description Viking High Pressure (HP) Dry Systems utilize a Viking Model E or Model F Deluge Valve to control the water supply to system piping equipped with closed sprinklers.
More informationFeatures. Model DDX-LP Dry Pipe Valve System 4 (100mm), 6 (150mm) & 165mm Sizes
Bulletin 357 Rev. E Model DDX-LP Dry Pipe Valve System 4 (100mm), 6 (150mm) & 165mm Sizes Bulletin 357 Rev. E Features 1. 2. 3. 4. 5. 6. 7. 8. 9. Differential-type valve, lightweight, dependable construction.
More informationModel DDX-LP Dry Pipe Valve System 8 (200mm) Features. Differential latching clapper-type, lighweight, dependable construction.
Bulletin 335 Model DDX-LP Dry Pipe Valve System 8 (200mm) Bulletin 335 Features 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Differential latching clapper-type, lighweight, dependable construction. Low Air Pressurized
More informationTECHNICAL DATA. than the water inlet pressure to the concentrate
Foam102a 1. DESCRIPTION The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with 3M foam concentrates. This system consists of a standard wet pipe sprinkler
More informationData Sheet Issue A
Features 1. Differential latching clappertype, lighweight, dependable construction. 2. Low Air Pressurized System, 8 psi -to- 26 psi (0,6 bar to- 1,8 bar) 3. Reset externally. Cover removal is not required.
More informationTECHNICAL DATA. Trimpac 244a. September 16, 2013
September 16, 2013 Trimpac 244a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-1 and B-1B is a factory-assembled trim package with an electric release module in a metal enclosure. The standard trim normally
More informationType 1 - Nitrogen Generation System. Designed for: Dry or Pre-Action Fire Protection Systems (FPS) with a total capacity up to 750 gallons
Type 1 - Nitrogen Generation System Designed for: Dry or Pre-Action Fire Protection Systems (FPS) with a total capacity up to 750 gallons 1.0 Nitrogen Generation Corrosion Inhibiting System 1.1 The Fire
More informationType 3 - PSA Nitrogen Generation System
Type 3 - PSA Nitrogen Generation System Designed for: Dry or Pre-Action Fire Protection Systems (FPS) with a total capacity from 6,000 to 18,000 gallons 1.0 Nitrogen Generation Corrosion Inhibiting System
More informationTECHNICAL DATA. Trimpac 247a_Euro. September 16, 2013
September 16, 2013 Trimpac 247a_Euro 1. DESCRIPTION DEsCrIpTIoN TRIMPAC Model B-11 LPCB Type 1 is a factory assembled trim package for a single interlocked electric release module in a metal enclosure.
More informationTECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.
Foam 302 a 1. DESCRIPTION (Refer to Figure 1 on page 302 e.) The Viking Low-Flow Foam/Water Proportioning System is a UL Listed and FM Approved system, for use with 3M and Viking brand foam concentrate.
More informationFeatures. Model DDX-LP Dry Pipe Valve System 2 (50 mm), 2½ (65 mm), 3 (80 mm), 76 mm, 4 (100 mm), 6 (150 mm), 165 mm & 8 (200mm) Listings & Approvals
Bulletin 337 Rev. A Model DDX-LP Dry Pipe Valve System 2 (50 mm), 2½ (65 mm), 3 (0 mm), 76 mm, 4 (100 mm), 6 (150 mm), 5 mm & (200mm) Bulletin 337 Rev. A Features 1. Differential latching clapper-type,
More informationTECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)
Page 1 of 8 1. DESCRIPTION The Viking Model F-1 Deluge Valve is a quick opening, differential diaphragm, flood valve with one moving mechanism. The Deluge Valve is used to control water flow in Deluge
More informationECS Protector Nitrogen Generator PGEN-30 (PGEN-30E)
ECS Protector PGEN-30 (PGEN-30E) Specifications For use under U.S. Patents 8,720,591, 9,144,700 and 9,186,533 Dimensions (cabinet): 24.5 (W) x 52.5 (H) x 8.5 (D) (622mm(W) x 1,334mm(H) x 216mm(D)) Dimensions
More informationFeatures. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200)
Features 1. Differential latching clapper-type, lightweight, dependable construction. 2. Low Air Pressurized System, psi -to- 2 psi (0,6 bar -to- 1,9 bar) Max 3. Reset externally. Cover removal is not
More informationTECHNICAL DATA DELUGE VALVE, MODEL F-1 STRAIGHT THROUGH STYLE
Page 1 of 10 1. DESCRIPTION The Viking Model F-1 Deluge Valve is a quick opening, differential diaphragm and flood valve with one moving mechanism. The Deluge Valve is used to control water flow in Deluge
More informationTECHNICAL DATA. Inlet Type Outlet Type OBSOLETE. 4. TECHNICAL DATA Approvals:
February 11, 2005 Deluge Valves 218 a 1. PRODUCT NAME Viking Model F-1 Deluge Valve 8" - Manufactured since 2002 4" & 6" - Manufactured since 2003 2-1/2" & 3" - Manufactured since 2004 2. MANUFACTURER
More informationTECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY PNEUMATIC RELEASE. 1. DESCRIPTION (Refer to Figures 1, 2 or 3.
Page 1 of 8 1. DESCRIPTION A Viking Pilot Pressure Regulated Deluge System utilizes a Viking Flow Control Valve to control water flow into the deluge system. The flow control valve must be installed with
More informationTECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.
Page 1 of 8 1. DESCRIPTION A Viking Pilot Pressure Regulated Deluge System utilizes a Viking flow control valve to control water flow into the deluge system. The flow control valve must be installed with
More informationDESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE
February 9, 1998 Foam 101a A BLADDER TANK WITH 1. DESCRIPTION A Wet Pipe Bladder Tank Foam/Water System is a standard wet pipe automatic sprinkler system capable of discharging a foam/water solution automatically
More informationWet pipe low flow foam/water system
December 6, 2010 Foam 14a 1. The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with Viking supplied foam concentrates. This system consists of a standard
More informationFM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate
December 6, 2010 Foam 31a 1. Description With Multiple Pilot Pressure Regulating Foam/Water Deluge Systems Supplied by a Bladder Tank, multiple pilot pressure regulating foam risers can be supplied from
More informationInstructions for Installation, Operation, Care and Maintenance
Model B1 Accelerator with Integral Accelo-Check Bulletin 323 Rev. E Bulletin 323 Rev. E Instructions for Installation, Operation, Care and Maintenance Features 1. Quickens the operation of dry pipe valves.
More informationTECHNICAL DATA Q= C. Table 1 - Specifications
September 25, 2013 Pressure Regulation 537a 1. Description The Model B-3 Pilot Operated Pressure Control Valve is a factory assembled unit. The unit consists of a Model J-2 Halar coated Flow Control Valve,
More informationTECHNICAL DATA. Page 1 of 12
Page 1 of 12 1. DESCRIPTION The Viking Regulating Valve is a direct-acting, single-seated, spring-loaded diaphragm valve. When installed as a pilot regulating valve on a Viking Model H or J Flow Control
More informationTECHNICAL DATA OBSOLETE
August 2, 2006 Foam 70a 1. DESCRIPTION A Hi-Expansion Foam System is a standard deluge system capable of discharging a foam/water solution automatically through open Hi-Ex Generators. A Hi-Expansion Foam
More informationTECHNICAL DATA. Deluge Valves 211a. November 30, 2007 DELUGE VALVE MODEL E-1 ANGLE STYLE 3 (DN80), 4 (DN100) & 6 (DN150)
November 30, 2007 Deluge Valves 211a DESCRIPTION The Viking Model E-1 Deluge Valve is a quick-opening, differential diaphragm, fl ood valve with one moving mechanism. The deluge valve is used to control
More informationTECHNICAL DATA. Pressure Regulation 531a. April 24, 2009
April 24, 29 Pressure Regulation 531a 1. DESCRIPTION The Viking Regulating Valve is a direct-acting, single-seated, spring-loaded diaphragm valve. When installed as a pilot regulating valve on a Viking
More informationECS Protector Nitrogen Inerting Vent (PAV-WN)
ECS Protector (PAV-WN) U.S. Pat. No. 8,636,023, 9,526,933 and 9,717,935 B2 Specifications Stock Number: Service Pressure: Regulator Setting: System Connection: Temperature Range: Dimensions: Weight: Clear
More informationDESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection
February 9, 1998 Foam 201a 1. DESCRIPTION A Deluge Bladder Tank Foam/Water System is a standard deluge system capable of discharging a foam/water solution automatically through open sprinklers, spray nozzles,
More informationNGP-250/500 Nitrogen Generator Quick Start Guide
NGP-250/500 Nitrogen Generator Quick Start Guide Version: A July 2013 Potter Electric Signal Company, LLC 5757 Phantom Dr., Suite 125 P. O. Box 42037 Hazelwood, MO 63042 Phone: (314) 595-6900 Document
More informationTECHNICAL DATA. Table 1 - Specifications
Page 1 of 6 1. DESCRIPTION Model A-3 Pilot Operated Pressure Control Valves are factory assembled units. Each unit consists of a Model H-2 Halar coated Flow Control Valve, a Speed Control Valve, a Model
More informationData Sheet Issue A
Features 1. Differential-type valve, lightweight, dependable construction. 2. Low Air Pressurized System, 10 psi -to- 26 psi (0,7 bar -to- 1,8 bar). 3. Reset externally.cover removal is not required. 4.
More informationDESIGN DATA. Dry 105a. September 5, 2008
September 5, 2008 Dry 105a 1. Description Dry and Preaction Systems require a dependable source of clean dry air under the proper pressure. The air supply must be adequate to restore normal air pressure
More informationTECHNICAL DATA CAUTION
Page 1 of 12 1. DESCRIPTION The Viking Model C-2 Pilot Pressure Regulating Valve is a direct-acting, single-seated, spring-loaded diaphragm valve. When installed as a pilot regulating valve on a Viking
More informationFireLock NXT Dry Valve. System No. Submitted By Spec Sect Para Location Date Approved Date
The patent-pending Victaulic Series 768 FireLock NXT is a low differential, latched clapper valve that uses a unique direct acting diaphragm to separate system water supplies from dry-pipe sprinkler systems.
More informationINSTALLATION OPERATION MAINTENANCE
Bermad Electrically Controlled On-Off Deluge Valve Model: 400E-3D INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 1. Safety First BERMAD believes that the safety of personnel working
More informationTECHNICAL DATA. Deluge Valves 218a. November 30, 2007 DELUGE VALVE MODEL F-1 STRAIGHT THROUGH STYLE 2-1/2 (DN65) - 8 (DN200)
November 30, 2007 Deluge Valves 218a DESCRIPTION The Viking Model F-1 Deluge Valve is a quick opening, differential diaphragm and fl ood valve with one moving mechanism. The Deluge Valve is used to control
More informationPreaction System with DV-5 Deluge Valve Single Interlock, Supervised Electric Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description
Worldwide Contacts www.tycofire.com Preaction System with DV5 Deluge Valve Single Interlock, Supervised Electric Actuation / thru 8 Inch (DN thru DN00) General Description The TYCO DV5 Supervised Single
More informationTECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1
November 30, 1994 534 a 1. PRODUCT NAME VIKING 2" (50mm), 3" (75mm), 4" (100mm), 6" (150mm) 2. MANUFACTURER THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone:
More informationTECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1
Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a
More informationTECHNICAL DATA ACCELERATOR MODEL E-1
Page 1 of 10 1. PRODUCT DESCRIPTION The Viking Model E-1 Accelerator is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating
More informationFM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate
December 6, 2010 Foam 21a 1. Description With Multiple Foam/Water Deluge Systems Supplied by a Bladder Tank, multiple deluge foam risers can be supplied from a single foam concentrate source. Where a bladder
More informationSINGLE VALVE WITH LOW-FLOW BYPASS
CONTROL VALVES Pressure Reducing Valve Sizing Guide Sizing pilot operated reducing valves is not a complicated process. It starts with determining requirements and following these guidelines in valve size
More informationOBSOLETE. Wet pipe low flow manifold system
June 1, 2008 Foam 15a 1. Description Multiple risers can be supplied from a single proportioning device. A riser manifold is installed with various riser types and sizes that are to supply foam solution
More informationOBSOLETE DESIGN DATA. Foam 301a. February 9, 1998
February 9, 1998 Foam 301a A BLADDE TANK WITH HYDAULICALLY ACTUATED DELUGE CONCENTATE CONTOL VALVE 1. DESCIPTION A Preaction Bladder Tank Foam/Water System is a standard preaction system capable of discharging
More informationPreaction System with DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description
Worldwide Contacts www.tycofire.com Preaction System with DV5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation /2 thru 8 Inch (DN thru DN200) General Description The DV5 Supervised Single
More informationPreaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Electric Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Electric Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description
More informationGENERAL DESCRIPTION MODEL RCW DRY SYSTEM CONFIGURATION. Technical Support Airpark Dr. Standish, MI 48658
077 Airpark Dr. Standish, MI 8658 989-8-583 www.globesprinkler.com Technical Support 989-1-00 MODEL RCW DRY SYSTEM GENERAL DESCRIPTION The Globe Model RCW* dry valve is a hydraulically operated external
More informationTECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4
Page 1 of 5 Telephone: 29-95-9501 Technical Services: 877-8-5 Fax: 29-8-0 Email: techsvcs@vikingcorp.com Model F Dry Valve with Trim Valve Size Part Number 17PTR 175PTR 17PTR Standard Trim Sets include
More informationTechnical Data. UL Listing is based on the following criteria:
Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve with Trim Inch and 6 Inch (DN and DN5) General Description The TYCO DV-5 Deluge Valve with Trim is a diaphragm-style valve that depends upon water
More informationMODEL RCW NON-INTERLOCK PREACTION SYSTEM
0 Airpark Dr. Standish, MI 8658 989-86-58 www.globesprinkler.com Technical Support 989--00 techservice@globesprinkler.com MODEL RCW NON-INTERLOCK PREACTION SYSTEM GENERAL DESCRIPTION The Globe Model RCW
More informationTECHNICAL DATA CAUTION
Page 1 of 6 1. DESCRIPTION The Viking Model D-2 Accelerator is a quick-opening device, with an integral anti-flood assembly, used to increase the operating speed of a differential type dry pipe valve.
More informationPreaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General
More informationPreaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Dry Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Dry Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General
More informationWater Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems
Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems Name of Property: Address: Phone Number: Inspector: Contract No.: Date: This Report Covers: Monthly Quarterly Annual Other
More informationMODEL RCW DRY SYSTEM VALVE
077 Airpark Dr. Standish, MI 8658 989-86-583 www.globesprinkler.com Technical Support 989-1-2600 techservice@globesprinkler.com MODEL RCW DRY SYSTEM VALVE GENERAL DESCRIPTION The Globe Model RCW* dry valve
More informationTECHNICAL DATA OBSOLETE
January 11, 2007 Dry 122a PRODUCT DESCRIPTION The Viking Model E-1 Accelerator is a quick-opening device. When installed with the required external Anti-fl ood Device, the assembly is designed to increase
More informationFireLock NXT Preaction Valve with Series 798 Pneumatic/Pneumatic Actuator
(DOUBLE-INTERLOCKED, PNEUMATIC/PNEUMATIC RELEASE) HANG THESE INSTRUCTIONS ON THE INSTALLED VALVE FOR EASY FUTURE REFERENCE WARNING WARNING Failure to follow instructions and warnings can cause product
More informationValve Proving System VDK 200 A S06*
Valve Proving System VDK 200 A S06* Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter
More informationValve Proving System VDK 200 A S02
Valve Proving System VDK 200 A S02 Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter
More informationTECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION
Page 1 of 6 1. DESCRIPTION The Model B-1 Anti-flood Device is required when Viking accelerators are installed on dry systems according to Viking Model E-1 Accelerator Trim Charts. In the SET condition,
More informationAnti-flood device Model B-1
December 4, 2009 Dry Systems 123a 1. DESCRIPTION The Anti-flood Device is required when Viking accelerators are installed on dry systems according to Viking Model E-1 Accelerator Trim Charts. In the SET
More informationVERTICAL BLADDER TANK
Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Tight Spaces UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure
More informationFIRE SPRINKLER PRODUCTS PRODUCT CATALOG
AGF Manufacturing Inc. FIRE SPRINKLER PRODUCTS PRODUCT CATALOG CAT-AGF_2018 3/18 Reliability, Versatility, Code Compatibility All orders MUST be received by AGF Manufacturing, Inc. in a written format
More informationCash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified
Cash Valve PILOT OPERATED BACK PRESSURE VALVE ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 01 Certified KP HIGH CAPACITY PILOT OPERATED BACK PRESSURE VALVE DESCRIPTION The Cash Valve Type KP is a pilot
More informationMaterials Performance November Nitrogen generator inhibits corrosion within fire protection systems
Materials Performance November 2014 Nitrogen generator inhibits corrosion within fire protection systems When dry and pre-action fire protection systems experience internal corrosion in their piping network,
More informationBERMAD Waterworks. Level Control Valve with Altitude Pilot. 700 Series. Model X. Features and Benefits. Major Additional Features
Level Control Valve with Altitude Pilot High level reservoirs & water towers Energy cost critical systems Systems with poor water quality Inherent refreshing Level sustaining at reservoir outlet The Level
More informationHORIZONTAL BLADDER TANK
Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Low Ceilings UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure
More informationa pilot sprinkler were to be closed after its initial operation, for example a remote manual control station).
Technical Services: Tel: (800) 8-9 / Fax: (800) 9-00 Model DV- Deluge Valve, Diaphragm Style, -/ thru 8 Inch (DN40 thru DN00), Deluge System Dry Pilot Actuation General Description The Model DV- Deluge
More information1 Exam Prep. Tabs and Highlights
1 Exam Prep NFPA 14: Standard for the Installation of Standpipe and Hose Systems Tabs and s These 1 Exam Prep tabs are based on the NFPA 14: Standard for the Installation of Standpipe and Hose Systems,
More informationStandard Operating and Maintenance Instructions for Pumping System Model PS-90
Standard Operating and Maintenance Instructions for Pumping System Model PS-90 High Pressure Equipment Company 2955 West 17th Street, Suite 6 PO Box 8248 Erie, PA 16505 USA 814-838-2028 (phone) 814-838-6075
More informationInert Air (N2) Systems Manual
INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing
More informationFIRE PROTECTION PRODUCTS
AGF Manufacturing Inc. FIRE PROTECTION PRODUCTS PRODUCT CATALOG CAT-AGF_V002 1/15 Reliability, Versatility, Code Compatibility AGF Product Catalog Table of Contents COLLECTa ndrain Auxiliary Drains Model
More informationBUBBLER CONTROL SYSTEM
BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air
More informationFire Protection Equipment
123456 Fire Protection Equipment #SVL500 Model F Preaction Valves "Automatic" Sprinkler 150 Gordon Drive Exton, PA 19341 USA Tel: (610) 3631400 8006262682 Fax: (610) 5249073 8008586857 www.kiddefire.com
More informationBACK PRESSURE / SUSTAINING
In many liquid piping systems, it is vital that line pressure is maintained within relatively narrow limits. This is the function of the 108 Pressure Relief / Back Pressure Series of the OCV control valves.
More informationInstructions for Installation, Operation, Care and Maintenance
Instructions for Installation, Operation, Care and Maintenance Double Interlock Preaction System Type F 8 (200 mm) Size Bulletin 745 Available with 75 psi (2, bar) or 250 psi (7,2 bar) Pneumatic Pressure
More informationAutomatic Valve Proving Control
ISO 9001 Automatic Valve Proving Control 7 696 LDU11 UL recognized FM approved Features Performs leak test of the gas shut-off valves before start-up and/or immediately after burner shut-down No inlet
More informationBermad Pressure Reducing. Model: 42T
Bermad Pressure Reducing Pilot Operated Pressure Control Valve Model: 42T Installation Operation Maintenance Manual (IOM) REV. 27.7.17 Page 1 of 12 Safety First BERMAD believes that the safety of personnel
More informationDouble Interlock Preaction System - Type F 2"(50mm), 2-1/2"(65mm), 3" (80mm) & 76mm Sizes
Instructions for Installation, Operation, Care, and Maintenance 10-26 PSI (0,7 1,8 bar) Pneumatic Supervising Pressure With Electric / Pneumatic Actuation Type F System Bulletin 738 Rev. B Double Interlock
More informationLPS Product Guide. LPS Series Nitrogen Generators. N2-GEN LPS TM - Layup Protection System Copyrighted All Rights Reserved
LPS Product Guide N2-GEN LPSTM LPS Series Nitrogen Generators N2-GEN LPS TM - Layup Protection System Copyrighted All Rights Reserved - 2014 p 888 526 6284 e info@southteksystems.com w www.southteksystems.com
More informationSPECIFICATIONS ATTENTION
VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane
More information