Installation Instructions for use by heating contractor
|
|
- Sharlene Long
- 6 years ago
- Views:
Transcription
1 Installation Instructions for use by heating contractor Auxilliary Low Gas Pressure Switch Part No CM2 186 Part No CM2 246 to 620 (TX) for use with: Vitocrossal CM2 boilers Safety and Installation Requirements Please ensure that these instructions are read and understood before starting any service work. Failure to comply with these instructions may cause product/property damage, severe personal injury and/or loss of life. Working on the equipment The installation, adjustment, service and maintenance of this product must be performed by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers. There are no user serviceable parts on the boiler, burner or control. Ensure that main power to the equipment being serviced is off. Ensure that the main fuel supply valve to the boiler is closed. Take precautions to avoid accidental activation of power or fuel during service work. Do not perform service work on any component part without ensuring safe operation of the heating system. When replacing parts, use original Viessmann or Viessmann approved replacement parts. Refer to the applicable boiler Installation Instructions. Installation Steps IMPORTANT Low pressure switches are suitable for making and/or breaking a circuit when the medium pressure changes relative to the setpoint. The setpoint can be set in the field by an adjustable dial with an integrated scale. CAUTION Low gas pressure can cause the heating system to shut down. Codes Refer to current CAN/CSA B149.1 and.2 or National Fuel Gas Code ANSI Z223.1/NFPA 54, as well as local codes for gas piping requirements and sizing. Pipe size to the boiler must be determined based on: - pipe length - number of fittings - type of gas - maximum input requirements of all gas appliances in the residence. IMPORTANT Design piping layout in such a way that piping does not interfere with serviceable components. All electrical wiring is to be done in accordance with the latest edition of CSA C22.1 Part 1 and/or local codes. In the U.S. use the National Electrical Code ANSI/NFPA /2018 Please file in Service Binder
2 Installation - CM2 186 to 311 (equipped with Vitotronic 100 GC1/300 GW2) Installation steps 1. Disconnect boiler power supply. 2. If the boiler has already been installed, shut off main gas supply to the boiler and disconnect gas supply piping. 3. Supply and install gas piping components as required (see illustration on page 5). 4. Route cable beneath the top rail 1 as shown. Secure using plug-in cable retainers as shown. 5. Make electrical s as shown below. 6. Set the low gas pressure switch to 4.5 wc. 1 Low gas pressure cable (field supplied) 7. Open gas supply to the burner. Note: The setting must be higher then the GW1 pressure switch (4 w.c.) located on the gas valve. If a 4 w.c. setting is required then the GW1 pressure switch must be set below 4 w.c. 8. Using an approved gas leak detector, check gas line and low gas pressure switch. 9. Reconnect power to the boiler. Note: External vent line is not required. If necessary the d NPT vent opening on the Honeywell low gas pressure switch can be used. CM2 Boiler G Low pressure gas switch 21 (through COM LWCO) 22 NO A A Low gas pressure switch (Honeywell C 6097A 1012) 2
3 Installation - CM2 400 to 620 TX (equipped with Vitotronic 300 GW5B) Installation steps 1. Disconnect boiler power supply. 2. If the boiler has already been installed, shut off main gas supply to the boiler and disconnect gas supply piping. 3. Supply and install gas piping components as required (see illustration on page 5). 4. Route supplied cable beneath the top rail 1 as shown. Secure using plug-in cable retainers as shown. 5. Remove jumper from terminals 19 and 20 and make electrical s as shown between the boiler and the low gas pressure switch as required. 6. Set the low gas pressure switch to 4.5 wc. 1 Low gas pressure cable (supplied) 7. Open gas supply to the burner. Note: The setting must be higher then the GW1 pressure switch (4 w.c.) located on the gas valve. If a 4 w.c. setting is required then the GW1 pressure switch must be set below 4 w.c. 8. Using an approved gas leak detector, check gas line and low gas pressure switch. 9. Reconnect power to the boiler. Note: External vent line is not required. If necessary the d NPT vent opening on the Honeywell low gas pressure switch can be used. A CM2 Boiler Low pressure gas switch Cable color G Green (GN) 19 COM Black (BK) 20 NO White (WT) A Low gas pressure switch (Honeywell C 6097A 1012) 3
4 Installation - CM2 186 to 620 TX (equipped with Vitotronic 300 GW6B) Installation steps 1. Disconnect boiler power supply. 2. If the boiler has already been installed, shut off main gas supply to the boiler and disconnect gas supply piping. 3. Supply and install gas piping components as required (see illustration on page 5). 4. Route supplied cable beneath the top rail 1 as shown. Secure using plug-in cable retainers as shown. 5. Remove jumper from terminals 26 and 27 and make electrical s as shown between the boiler and the low gas pressure switch as required.. 6. Set the low gas pressure switch to 4.5 wc. 1 Low gas pressure cable (supplied) 7. Open gas supply to the burner. Note: The setting must be higher then the GW1 pressure switch (4 w.c.) located on the gas valve. If a 4 w.c. setting is required then the GW1 pressure switch must be set below 4 w.c. 8. Using an approved gas leak detector, check gas line and low gas pressure switch. 9. Reconnect power to the boiler. Note: External vent line is not required. If necessary the d NPT vent opening on the Honeywell low gas pressure switch can be used. CM2 Boiler Low pressure gas switch Cable color 26 (G) Green (GN) 26 (L) COM Black (BK) 27 (L) NO White (WT) 4 A DIN rail (junction box) B Auxiliary low gas pressure switch (Honeywell C 6097A 1012)
5 Operation Operation When sufficient gas pressure is available, the low gas pressure switch contact terminals 3(COM) and 2(NO) will close. The burner control is then energized and the system will operate normally. When sufficient gas pressure is no longer available, the low gas pressure switch contact terminals 3(COM) and 2(NO) will open. The burner control will stop operating and generate a fault C1 at the boiler control. To restart the boiler, press the low gas pressure switch reset button (only once) and reset the boiler control fault. If the fault persists, verify the gas supply pressure. There should be a minimum operating pressure of 4.5 w.c., if not contact your local gas company. Gas Piping Components A Nipple (supplied with boiler) B Elbow (supplied with boiler) C Reducing tee (kit part) D Short nipple kit (field supplied) E Manual gas shutoff valve (supplied with boiler) F Ground joint union (recommended) (field supplied) G Reducing bushing kit (only for ) H Short nipple (kit part) I Low gas pressure switch* * the switch can be installed in the gas line anywhere near the boiler. Note: Typical gas piping shown. 5
6 6
7 7
8 Technical information subject to change without notice. Printed on environmentally friendly (recycled and recyclable) paper.
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT ALPKT57- INSTALLATION INSTRUCTIONS PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements... Table of Contents INSTALLATION
More informationInstallation Instructions
48011HW NATURAL GAS TO PROPANE CONVERSION KIT 58HDX, 359AAV, PG9YAB, PG9YAA Installation Instructions SAFETY REQUIREMENTS Installing and servicing heating equipment can be hazardous due to gas and electrical
More informationPropane Conversion Kit Instruction
Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates Logamax plus GB62-80 kw 270,000 btu/hr Logamax plus GB62-00 kw 35,000 btu/hr This kit and instructions are for converting the
More informationPropane Conversion Kit Instruction
Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates GB142-24 84,800 btu/hr GB142-30 106,000 btu/hr GB142-45 160,900 btu/hr GB142-60 214,800 btu/hr This kit and instructions are
More informationNatural Gas to L.P. Gas Conversion Kit
Natural Gas to L.P. Gas Conversion Kit For Bosch 80% AFUE Gas Furnace, BGS80 Model Installation Instructions 3124627 2 Natural Gas to L.P. Gas Conversion Kit Installation Instructions Data subject to change
More informationPropane Conversion Kit Instruction
Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates GB42-24 84,800 btu/hr Tab. GB42-30 06,000 btu/hr GB42-45 49,000 btu/hr GB42-60 24,800 btu/hr This kit and instructions are
More informationACCESSORY KIT INSTALLATION MANUAL
ACCESSORY KIT INSTALLATION MANUAL LP (PROPANE) CONVERSION KIT 1NP0366 FOR USE WITH MODELS: G8C & GF8 This conversion kit shall be installed by a qualified service agency in accordance with these instructions
More informationSPECIFICATIONS ATTENTION
VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane
More informationACCESSORY KIT INSTALLATION INSTRUCTIONS
ACCESSORY KIT INSTALLATION INSTRUCTIONS 1NP0680 - PROPANE CONVERSION FOR USE WITH MODELS: PM8, PC8, PM9, PC9, FL9M, FL9C, FC9M, FC9C This conversion kit is to be installed by a qualified service agency
More informationInstallation Instructions
LP and High Altitude LP Gas Conversion Kit For United States Installations Installation Instructions For Model Series *G6/PGF1 Furnaces, *L1/PGC1 Furnaces, and *R4/PPG1 Gas/Electric Appliances using Honeywell
More informationNatural Gas to L.P. Gas Conversion Kit
Natural Gas to L.P. Gas Conversion Kit For Bosch 96% AFUE Gas Furnace, BGH96 Model Installation Instructions 3124627 2 Natural Gas to L.P. Gas Conversion Kit Installation Instructions Data subject to change
More informationNatural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)
Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet) INSTALLATION INSTRUCTIONS For R7 Series Light Commercial Packaged Gas Electric Units IIMPORTANT: Please
More informationGAS VALVE RETROFIT KIT Pull Through Tube Heater Models
GAS VALVE RETROFIT KIT Pull Through Tube Heater Models DESCRIPTION: This kit is designed to replace existing Honeywell gas valves #VR8205P and #VR8205Q with White-Rodgers gas valves #36J23 and #36J58 respectively
More informationINSTALLATION GUIDE Gas Rangetops
INSTALLATION GUIDE Gas Rangetops Contents Wolf Gas Rangetops........................... 3 Safety Instructions............................ 4 Gas Rangetop Specifications.................... 5 Gas Rangetop
More information/2004 US/CA
630 9765 0/004 US/CA For the contractor Propane Conversion Kit Instructions Sealed Combustion Gas Boiler Logano GA44 This kit and instructions are for converting the GA44 model boilers from Natural Gas
More informationInstallation Instructions For Natural Gas Conversion
Installation Instructions For Natural Gas Conversion (Kit Part No. 1175405) This kit is designed to convert PGX4 and PX4 Two -Stage Gas units for use with Natural Gas. Table 1 Heating Value at Altitude
More informationINSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles
INSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles MODELS MLS TYG48C ML-769368-Z1 TYG60C ML-766505-Z www.wolfrange.com TYG48C ITW Food Equipment Group, LLC An Illinois Tool Works Company 3600 North
More informationInstallation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS
LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS Installation Instructions For Model Series *G7/*GC2 Furnaces and Appliances Using Honeywell Gas Valves. BEFORE THE CONVERSION
More informationTightness controls TC 1 3 and TC 4
Tightness controls TC 1 3 and TC 4 Test of both safety valves Short test period thanks to logical decision-making in the program sequence Adjustable test period which can be adapted to different systems
More informationUNIVERSAL GAS FRYER Instruction Manual Model #8065NS
Part No. 88847 Revised: August 2004 UNIVERSAL GAS FRYER Instruction Manual Model #8065NS Cincinnati, OH 45241-4807 USA GAS SAFETY PRECAUTIONS OPERATING INSTRUCTIONS UNPACKING AND ASSEMBLY After unpacking
More informationEDUCATION DEPARTMENT ACCU-TEST
ABN 17 100 208 964 EDUCATION DEPARTMENT ACCU-TEST GAS SAFETY SHUT OFF SYSTEM Operating & Installation Manual Head Office (Melbourne) Sydney Brisbane (Distributor) 1/5 Samantha Court 2/14 Welder Road 17
More information36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS
INLET PRESS TAP WTE-RODGERS 36E96-314 DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL
More informationFor use with select HPC Fire Pits ONLY- refer to product catalog or website. 100K BTU Maximum WARNING: FOR OUTDOOR USE ONLY
For use with select HPC Fire Pits ONLY- refer to product catalog or website. 100K BTU Maximum : FOR OUTDOOR USE ONLY Small Tank LP Kit (STLPK) Installation & Operation Instructions Installation We suggest
More informationOperator: Save these instructions for future use!
INLET PRESS TAP WHITE-RODGERS 36E93-304 Delay-Opening Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
More informationPropane Conversion Kit Instructions
604 8 0/ US/CA For heating engineers Propane Conversion Kit Instructions Logano G4 X gas-fired boiler This conversion kit and the accompanying instructions are for conversion of G4 X gas-fired boilers
More informationG196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve
Installation Instructions Issue Date August 19, 2008 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied
More informationC645A-E Pressure Switches
C645A-E Switches FEATURES PRODUCT DATA C645A,B,D,E GENERAL C645A,B with Window C645C The C645 pressure switches are safety devices used in positive-pressure or differential-pressure systems to sense gas
More informationGas Conversion Kits CERAMIC HEATER SERIES (1, 2, 3, 4 Burner Units)
DESCRIPTION These kits are designed to convert from one gas type to another (eg. from NATURAL to PROPANE or from PROPANE to NATURAL) only for new heaters (5 years or newer) by replacing the gas valve spring
More informationGAS SUPPLY APPLICATION GUIDE
GAS SUPPLY APPLICATION GUIDE Natural Gas or Propane Modulating & Condensing Boilers and Water Heaters This document applies to the following models: Boilers AM 399B AM 500B AM 750B AM 1000B Gas-Fired Boilers
More information36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS
INLET PRESS TAP WTE-RODGERS 36E54-214 DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
More informationINSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)
P/N 126905-01 Rev. B 11/2016 INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235) For All Single, Dual and Triple Burner Natural and Propane/LP Gas Logs P126905-01 For
More informationG196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve
Installation Instructions Issue Date March 13, 2013 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied
More informationInstructions for High Altitude Conversion
6304 38 0/ US/CA For heating engineers Instructions for High Altitude Conversion Logano G334 X gas-fired boiler This conversion kit and the accompanying instructions are for conversion of G334 X gas-fired
More information36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve
Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION
More information36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS
INLET PRESS TAP WHITE-RODGERS 36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
More informationPressure Switch for gas and air
Switch for gas and air GAO-A4 GMH-A4 GML-A4 UL Listed UL 353 File # MH 16628 CSA Certified CSA C22.2 No. 13 and No. 0 Certification file # 201527 FM Approved Class 3510, 3530 File # J.I. 1Y919.AF Commonwealth
More informationPressure Switch for gas and air
Switch for gas and air GAO-A4 GMH-A4 GML-A4 UL Listed UL 353 File # MH 16628 CSA Certified CSA C22.2 No. LR 53222 Certification file # 201527 FM Approved Class 3510, 3530 File # J.I. 1Y919.AF Commonwealth
More informationOC Panel High Limit Aquastat Kit, Manual Reset p/n
OC Panel High Limit Aquastat Kit, Manual Reset p/n 233202 Instruction Sheet APPLICATION The OC (Option Control) Panel High Limit Aquastat Kit provides electronic temperature sensing in a UL limit-rated
More informationWARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only
Natural Gas High Altitude Conversion Kit United States Installations Only Installation Instructions Light Commercial Packaged Gas Electric Units R7TQ Series 6, - 7 1/2, & 10 Ton (2,001 FT - 10,000 FT)
More informationINSTALLATION & OPERATION MANUAL FOR Stockpot Range
INSTALLATION & OPERATION MANUAL FOR Stockpot Range MODELS MLS VSP100 ML-052822 VSP200 ML-052823 VSP200F ML-769292 www.vulcanhart.com MODELS MLS WSPR1 ML-760600 WSPR2 ML-760601 WSPR2F ML-769292 www.wolfrange.com
More informationPressure switch for gas and air
Pressure switch for gas and air GAO-A4 GMH-A4 GML-A4 UL Listed UL 353 File # MH 16628 CSA Certified CSA C22.2 No. LR 53222 Certification # 201527 FM Approved Class 3510, 3530 File # J.I. 1Y919.AF GXX_A4
More informationBGA158 Series CE Approved Class A Shutoff Gas Valve
Installation Instructions BGA158 Issue Date August 24, 2011 BGA158 Series CE Approved Class A Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated gas valve that
More informationDual Solenoid Gas Valve Installation
Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing or servicing FLYNN Gas Products. Carefully follow all instructions in this bulletin and all instructions
More informationINSTALLER: THIS MANUAL MUST BE LEFT WITH THE APPLIANCE. CONSUMER: KEEP THIS MANUAL FOR FUTURE REFERENCE. WARNING
FIRE PIT INSTALLATION AND OPERATING INSTRUCTIONS 401601RD MODELS: 401642FPM, 401654FPM, 801654FPM, 801686FPM, 821649FPM, 821686FPM 401601SQ MODELS: 401643FPM, 401667FPM, 401658FPM 401600RCT MODELS: 401767FPM-18,
More informationBGA158 Series CE Approved Class B Shutoff Gas Valve
Installation Instructions BGA158 Issue Date March 22, 2016 BGA158 Series CE Approved Class B Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated shutoff valve
More informationACCESSORY KIT INSTALLATION INSTRUCTIONS
ACCESSORY KIT INSTALLATION INSTRUCTIONS PROPANE CONVERSION - INDUCED COMBUSTION FURNACES 1NP0501 FOR USE WITH 95% MODELS: TG9S, GG9S (130,000 BTU ONLY) FOR USE WITH 80% MODELS: TG(8,L)S, GG(8,L)S (130,000
More information36H SERIES Combination Gas Valve
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION The 36H series combination gas valve is
More informationGM-7000 Series CE Approved Gas Control Valve
Installation Instructions GM-7000 Issue Date November 9, 2012 GM-7000 Series CE Approved Gas Control Valve Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing
More informationO.K. Safety first CDN USA. Table of Contents. Approvals. Attention IFGC CSA UL ANSI NFPA
S06 & S02 Valve Proving System Installation Instructions USA CDN Table of Contents Table of Contents... Page 1 Approvals... Page 1 Attention... Page 1 Specification... Page 2 Mounting.... Page 3 Wiring...
More informationTECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4
Page 1 of 5 Telephone: 29-95-9501 Technical Services: 877-8-5 Fax: 29-8-0 Email: techsvcs@vikingcorp.com Model F Dry Valve with Trim Valve Size Part Number 17PTR 175PTR 17PTR Standard Trim Sets include
More informationAutomatic Valve Proving Control
ISO 9001 Automatic Valve Proving Control 7 696 LDU11 UL recognized FM approved Features Performs leak test of the gas shut-off valves before start-up and/or immediately after burner shut-down No inlet
More informationGas Conversion Kits Push Through (Positive Pressure) Tube Heater Models
DESCRIPTION These kits are designed to convert from one gas type to another (eg. from NATURAL to PROPANE or from PROPANE to NATURAL) when equipped with White-Rodgers DSI gas valves number 36J23 or 36J58.
More informationG92 Series BASOTROL Automatic Pilot Gas Valve
Installation Instructions Issue Date September 17, 2008 G92 Series BASOTROL Automatic Pilot Gas Valve Installation IMPORTANT: Only qualified personnel should install or service BASO Gas Products. These
More informationG96 Series BASOTROL Dual Operator Valve
Installation Instructions 9. Issue Date February 22, 2013 G96 Series BASOTROL Dual Operator Valve Applications The G96 valves are combination, dual operator, automatic valves available with or without
More informationPressure Switch for gas and air GGAO-A4
Pressure Switch for gas and air GGAO-A4 CSA Certified CSA C22.2 No. LR 53222 Certification file # 201527 Commonwealth of Massachusetts Approved Product Approval code G3-0106-191 Gas pressure switch Codes
More informationGas Pressure Switch for DMV safety shutoff valves
Gas Switch for DMV safety shutoff valves GAO-A GMH-A GML-A UL Listed UL 353 File # MH 1668 CSA Certified CSA C. No. LR 53 File # 0157 FM Approved Class 3510, 3530 File # J.I. 1Y9A9.AF Commonwealth of Massachusetts
More information36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS
36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING
More informationVR8205S,T Direct Ignition Combination Gas Controls
VR805S,T Direct Ignition Combination Gas Controls INSTALLATION INSTRUCTIONS APPLICATION TheVR805S,T Direct Ignition Combination Gas Controls are used in gas-fired appliances with up to 70 ft 3 /hr capacity
More informationGas Pressure Switch for DMV safety shutoff valves
Gas Switch for DMV safety shutoff valves GAO-A GMH-A GML-A UL Listed UL 353 File # MH 1668 CSA Certified CSA C. No. LR 53 File # 0157 FM Approved Class 3510, 3530 File # J.I. 1Y9A9.AF Commonwealth of Massachusetts
More informationConversion instructions from natural gas to propane
6 720 804 895 202/0 EN-US For heating engineers Conversion instructions from natural gas to propane Room air-independent special gas-fired boiler Logano GA24 This conversion kit and the instructions are
More informationSL G3. Warning
Important: If converting from Propane to Natural Gas - order the Natural Gas Conversion Parts Kit (IBC Part # P-307) from your authorized IBC Distributor. Use the Propane Gas conversion parts kit if the
More informationINSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F29, F30, F31, F32 & F33
INSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F29, F30, F31, F32 & F33 FOR TWO-STAGE 90 PLUS DOWNFLOW/HORIZONTAL (-GTK) MODELS Recognize this symbol as an indication of Important Safety Information
More informationGas Valve Replacement Kit
Kit Part Number:PGRKIT01 Parts List 1. Honeywell VK8115V 2. /Orifice Gasket. Torx Screws ( pcs) 4. Venturi/Blower Housing Gasket 5. # 25 Torx Wrench. 1 2 4 Recommended tools: A. Pipe Wrench. B. Phillips
More informationVR46.5V(A)/VR86.5V(A) SERIES
VR46.5V(A)/VR86.5V(A) SERIES COMACT COMBINATION GAS CONTROS WITH INTEGRATED 1:1 GAS/AIR REGUATOR FOR AUTOMATIC IGNITION SYSTEMS SECIFICATIONS INSTRUCTION SHEET Subject to change without notice. rinted
More informationFire's Edge. Fire Pit or Fire Pit Insert Model 100A-M (Manual Operation) OWNER S MANUAL / OPERATING AND MAINTENANCE INSTRUCTIONS
Fire's Edge Fire Pit or Fire Pit Insert Model 100A-M (Manual Operation) OWNER S MANUAL / OPERATING AND MAINTENANCE INSTRUCTIONS For your safety: If you smell gas: 1. Shut off gas to the appliance 2. Extinguish
More informationGas Pressure Switch for DMV safety shutoff valves
Gas Pressure Switch for DMV safety shutoff valves GAO-A GMH-A GML-A UL Listed UL File # MH 668 CSA Certified CSA C. No. LR File # 07 FM Approved Class 0, 0 File # J.I. Y9A9.AF Commonwealth of Massachusetts
More informationBGA158, BGA171 and BGA110 Series Shutoff Gas Valve
Installation Instructions BGA Series Issue Date October 3, 2017 BGA158, BGA171 and BGA110 Series Shutoff Gas Valve Applications The BGA Series shutoff gas valve is an electrically operated gas valve that
More informationGas Fired Residential Heating Boilers
USER S INFORMATION MANUAL Gas Fired Residential Heating Boilers Models 0042B, 0066B, 0090B, 0135B, 0180B Type H WARNING: If the information in this manual is not followed exactly, a fire or explosion may
More informationVR8200A Continuous Pilot Combination Gas Controls
SUPER TRADELINE VR800A Continuous Pilot Combination Gas Controls Application These continuous pilot combination gas controls are used in gas-fired appliances that have up to 00 cfh capacity of natural
More informationV8200A,C,H,M and VR8200A,C,H,M Continuous Pilot Combination Gas Controls
V800A,C,H,M and VR800A,C,H,M Continuous Pilot Combination Gas Controls APPLICATION These continuous pilot combination gas controls are used in gas-fired appliances up to 00 cfh capacity of natural gas.
More informationH15 Series BASO 100% Shutoff, Automatic Pilot Valve
Installation Instructions Issue Date February 22, 2013 H15 Series BASO 100% Shutoff, Automatic Pilot Application The H15 Series pilot valves provide safe lighting and complete shutoff of pilot and main
More informationSPECIFICATIONS. Normally closed automatic shutoff valve with proof of closure. Fast opening, fast closing. ATTENTION
SV/614 Installation Manual -P/N 80128 - Ed. 01/08 SV-(DLE) 10../614 Safety Shutoff Valve with Proof of Closure Installation Instructions 1 6 SV/614 SV-DLE/614 SPECIFICATIONS Normally closed automatic shutoff
More informationInstallation Instructions
Page 5750-S-1 Installation Instructions General These mounting instructions for Circular INCINO- PAK Burners are in addition to the specific instructions offered for other Maxon component items: Shut-Off
More informationQPL... Pressure Switches. Siemens Building Technologies HVAC Products
7 221 Pressure Switches QPL... The pressure switches are used for monitoring gas or air pressures. When the pressure falls below the switching point, the associated electrical circuit will open or switch
More informationinstallation instructions
installation instructions GAS CONVERSION KIT PROPANE-TO-NATURAL P/N 315572-71201 4GAD 6GAD Cancels: IIK 4G-50-4 IIK 4G-50-5 7/15/91 NOTE: Read the entire instructions before starting the installation.
More informationBGC258 Series BASOTROL Gas Valve
Installation Instructions BGC258 Issue Date September 6, 2017 BGC258 Series BASOTROL Gas Valve Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing or servicing
More informationINSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F13, RXGY-F27 AND RXGY-F28
INSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F13, RXGY-F27 AND RXGY-F28 FOR TWO-STAGE (GPL/GPR/GPE/GLL/GLR/GLE) MODELS Recognize this symbol as an indication of Important Safety Information THESE
More informationSteam System Best Practices 14 Best Practices for Guide Lines for Boiler Plant Log Books
Steam System Best Practices 14 Best Practices for Guide Lines for Boiler Plant Log Books 1. SCOPE OF BOILER LOGBOOK PROGRAM In all cases, there are minimum tasks and functions for an operator to perform
More informationVR8305 Direct Ignition Combination Gas Control
Honeywell VR8305 Direct Ignition Combination Gas Control Application These direct ignition combination gas controls are used in gas-fired appliances with capacities up to 300 feet 3 /hour at inch wc pressure
More informationGS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GS-20/25 GS-40/45 Issue Date 1298 GS-20/25 and GS-40/45 Series Single-block Multi-function Gas
More informationACCESSORY KIT INSTALLATION INSTRUCTIONS PROPANE CONVERSION - INDUCED COMBUSTION FURNACES 1NP0347
ACCESSORY KIT INSTALLATION INSTRUCTIONS PROPANE CONVERSION - INDUCED COMBUSTION FURNACES 1NP0347 FOR USE WITH 90% + MODELS: GF9S, GY9S, GM9S, PS9, FL9S, FC9S, PT9, FL9T, FC9T, GM9T, PV9, FL9V, FC9V, GM9V,
More informationWARNING: Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings FOR YOUR SAFETY
Form CP-UD-GC Obsoletes I-UD-GC (Version E) Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters General and Warnings All gas conversion must be done by a qualified
More informationOWNERS MANUAL INSTALLATION, OPERATION, & MAINTENANCE INSTRUCTIONS
OWNERS MANUAL INSTALLATION, OPERATION, & MAINTENANCE INSTRUCTIONS 1128 Sherborn Street Corona, CA 92879-2089 (951) 281-1830 FAX (951) 281-1879 ICRA SERIES CHINESE RANGES All Imperial Mfg. Co. equipment
More informationGAS FRYER Instruction Manual Model #5099NS
Part No. 89932 Revised: March 2004 GAS FRYER Instruction Manual Model #5099NS Cincinnati, OH 45241-4807 USA GAS SAFETY PRECAUTIONS GAS FUNNEL CAKE FRYER 2 MODEL #5099NS GAS FUNNEL CAKE FRYER SAFETY PRECAUTIONS
More informationLENNOX SLP98UHV DIAGNOSTIC CODES
Code Status of Equipment Action required to clear and recover - Idle mode (Decimal blinks at 1 Hertz -- 0.5 second ON, 0.5 second OFF) A Cubic feet per minute (cfm) setting for indoor blower (1 second
More informationTECHNICAL DATA. Trimpac 257a. September 16, 2013
September 16, 2013 Trimpac 257a 1. DESCrIpTION DESCRIPTION The Viking Double SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-2 and D-2B used with either a Model E or F Deluge Valve (A.1), a Viking
More informationGas Conversion Kit Pilot Ignition Heaters
INSTALLATION INSTRUCTIONS Gas Conversion Kit Pilot Ignition Heaters View these instructions online at www.lbwhite.com Kit Contents: DESCRIPTION QTY. Instructions 1 Burner Orifi ce 1 Pilot Orifi ce 1 Variable
More informationINSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F23, F24, F25, F26, F38, F39, F40 & F41
INSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F23, F24, F25, F26, F38, F39, F40 & F41 FOR MODULATING DOWNFLOW/HORIZONTAL AND DEDICATED HORIZONTAL MODELS (-GGD, -GGE, -GGF)! Recognize this symbol
More informationSL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302
SL 40-399 G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302 If converting from Propane to Natural Gas, order the Natural Gas Conversion Parts Kit (IBC Part # P-303) from your authorized IBC Distributor.
More informationTECHNICAL DATA. Trimpac 256a. October 31, 2013
October 31, 2013 Trimpac 256a 1. DESCRIPTION The Viking SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-1 and D- 1B used with either a Model E or F Deluge Valve (A.1), a Viking Easy Riser check valve
More informationGM Series Dual-Block Multi-Function Gas Control Valves
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series
More informationUSER S INFORMATION MANUAL
USER S INFORMATION MANUAL UPFLOW, DOWNFLOW, UPFLOW/HORIZONTAL & HORIZONTAL ONLY INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this
More informationInstallation Instructions For Propane Gas Conversion (Kit Part No ) This kit is designed for conversion to Propane Gas
Installation Instructions For Propane Gas Conversion (Kit Part No. 1173859) This kit is designed for conversion to Propane Gas Table 1 LP Gas Orifice Kits and Sizes Elevation Above Sea Level 0 to 2000
More informationINSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1*
INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1* THIS KIT CONTAINS: AOPS7741 (NATURAL TO PROPANE CONVERSION PARTS FOR MODEL SIZE, 50) AOPS7742(NATURAL
More informationSERVICE MANUAL. UDS / UDH Series Ultra Low NOx Direct Vent Water Heaters. Troubleshooting Guide and Instructions for Service
UDS / UDH Series Ultra Low NOx Direct Vent Water Heaters SERVICE MANUAL Troubleshooting Guide and Instructions for Service (To be performed ONLY by qualified service providers) Models Covered by This Manual:
More informationPressure Dump Valve Service Kit for Series 2300 Units
Instruction Sheet Pressure Dump Valve Service Kit for Series 00 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00 applicator tanks when the unit
More informationINSTALLATION OPERATION MAINTENANCE
Bermad Electrically Controlled On-Off Deluge Valve Model: 400E-3D INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 1. Safety First BERMAD believes that the safety of personnel working
More informationUL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM-20/25 GM-40/45 Issue Date 1298 UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function
More informationIPG IGNITION GAS PILOTS BACK-LOADED GAS
INSTRUCTIONS IPG IGNITION GAS PILOTS BACK-LOADED GAS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS For Burner Kit replacement of 553010021 Burners in GUI, GDI & GNI Gas Furnaces Using Natural Gas Please read these instructions completely before attempting installation. SAFETY
More information