1 CHAPTER 12 February 15, 2006 WATER LOSS PROCEDURES 1. WATER LOSS PROCEDURES 1.1 The loss of water on the fire ground is a very serious situation, and something all members should strive to prevent. The importance of an accurate hose stretch cannot be overstated. Even after the hose stretch has been successfully completed and water is flowing at the correct pressure and volume, problems can occur that can threaten safety. Three such problems include: KINKS BURST LENGTH STRETCHING SHORT 1.2 These three problems can severely impact an operation. Each one will affect the water supply, and if not handled quickly and efficiently, can jeopardize the lives of both civilians and firefighters. 2. KINKS 2.1 Water loss due to kinks is the more common problem. Kinks constitute a water loss when they are severe enough to reduce the extinguishment capabilities of a hose line. When this occurs and is recognized by any member, an Urgent message shall be transmitted via the handie-talkie. It is essential that the Incident Commander, units operating on the fire floor and the floors above be notified of a water loss situation. Note: The engine officer shall ensure that the fire is confined by closing a door and/or all members are moved to a safe area of refuge if necessary. 2.2 Kinks are also the easiest problem to correct. The proper stretching and positioning of hose lines will greatly reduce the occurrence of kinks. 2.3 The control firefighter is responsible for estimating the correct amount of hose to reach the seat of the fire. Effectively controlling the number of lengths in the hose stretch will minimize kinks. Stretching one additional length of hose may be desirable to allow the nozzle team to be re-directed to a more distant area or to diminish the impact should a burst length occur and a length of hose needs to be removed from the stretch. The key is to have extra hose, but NOT an excessive amount. 2.4 All members operating at an incident, both engine and ladder, are responsible for eliminating kinks from the hose stretch. Kinks that cause a loss of water will compromise safety. 2.5 All members shall monitor handie-talkie communications. An indication that there are kinks is when the engine officer calls for additional pressure and the ECC responds that sufficient pressure is being supplied, but a reduction in flow is showing on the outlet flowmeter. Once it is determined the reduction in water flow is due to kinks, they must be located and quickly removed. Do not correct kinks by increasing the pressure. 1

2 2.6 The engine officer must initiate action to correct the problem of kinks in the hoseline. This shall include dispatching the control firefighter to find and correct the problem and/or requesting assistance from the Incident Commander. This problem should also be addressed by the second due engine (water resource unit), if at the scene. 2.7 The engine officer must notify the Incident Commander and all units on the fire floor and floors above when the problem is corrected. 3. BURST LENGTH 3.1 A burst length constitutes a water loss when it is severe enough to reduce the extinguishment capabilities of the hoseline. A burst length will severely affect an operation and will take a considerable amount of communication, coordination and time to correct. 3.2 An indication of a burst length is when the engine officer reports there is little or no water and the ECC sees an adequate pressure reading and an increased flow showing on the outlet flowmeter with the pumps RPMs increasing automatically. 3.3 Once a water loss due to a burst length is confirmed by any member, an Urgent message shall be transmitted. It is essential that the Incident Commander, members operating on the fire floor and floors above be notified. The engine officer must take immediate action to correct this problem. 3.4 All engine companies are required to store an extra length of 1¾ hose, with a controlling nozzle attached, on the apparatus in an easily accessible location. This hose or the 2½ hose folds on the apparatus for standpipe operations can be used to replace a burst length or added to a short stretch as necessary. The engine officer shall dispatch a member to obtain the appropriate replacement length. 3.5 To determine how to correct a burst length problem, first locate the burst length in the stretch. Once the location is verified and after the water has been shut down, there are two ways to correct a burst length: If enough hose is available, remove the burst length and reattach the existing couplings. Replace the burst length with a new length of hose, when there is not enough existing hose available in the stretch. Note: The above shall only be accomplished upon the engine officer s orders, after the fire has been confined by closing a door and/or members have moved to a safe area of refuge. 3.6 Once the burst length has been replaced, the engine officer is notified and in turn notifies the ECC to start water. The engine officer must notify the Incident Commander and all units on the fire floor and floors above when the problem is corrected. 2

3 The following is a quick reference chart: Line Pressure is the pressure necessary to obtain the correct water flow. Line pressure is determined by the size + number of lengths of hose + nozzle pressure and elevation. 4. SHORT STRETCH The importance of an accurate stretch cannot be overstated. The key is to have extra hose but not an excessive amount. The opposite problem is not stretching enough hose initially or the nozzle team cannot be re-directed to extinguish fire in a more distant area. If a hand line is stretched short, the corrective actions that needs to be taken will be determined by the size of the hose line (1¾ or 2½ ), and whether or not shutting down the water supply is suitable to the fire condition. 3

4 Note: The following procedures are NOT in priority order and shall only be accomplished upon the engine officer s orders, after the fire has been confined by closing the door and/or after moving to a safe area of refuge. 4.1 Water shut down is required when adding hose to the back of the stretch with a 1¾ or 2½ hand line. The ECC when ordered will shut down and drain the line at the pumper. In the case of a standpipe operation, shut down the line at the floor outlet. The ECC and/or other members will add an additional length(s) of 1¾ or 2½ hose to the stretch at the pumper or floor outlet. The ECC or other members will notify the engine officer when the connections are complete and will re-supply water to the hand line upon the engine officer s orders. Adding hose to the back of the stretch will require that hose be moved up along the entire length of the stretch in order for the line to advance. This may be impractical where more that four lengths of hose was originally deployed. Note: If the 6 lead lengths of 1¾ hose have already been stretched, only a length(s) of 2½ hose can be added. 4.2 Water shut down is NOT required when adding hose to the front of the stretch. This procedure will vary depending if the hand line is 1¾ or 2½ hose ¾ HOSE LINE: A length of 1¾ hose with the nozzle attached is brought to the front of the line. The tip is removed from the original nozzle (Figure 1) and an extra length(s) is added by connecting the female butt to the shut-off (Figure 2). In order to charge the new lead length(s), open the shut-off from the original nozzle, which is acting as an inline gate (Figure 3). This procedure will allow units to add lengths of hose without shutting down the water supply at the pumper. Note: The engine officer will ensure that this shut-off does not accidentally get shut down. 4.4 For a fire in a non-fireproof multiple dwelling without a well hole, sufficient hose may be found by raising the already charged hose line over the newel post onto the railing ½ HOSELINE: A length(s) of 2½ hose with a nozzle attached is brought to the front of the line. The tip is removed from the nozzle (Figure 4) and a 1½ x 2½ increaser is connected to the shut-off (Figure 5). The new length(s) of 2½ hose is added by connecting the female butt to the fitting on the shut-off (Figure 6). In order to charge the new lead length(s), open the shut-off from the original nozzle, which is acting as an inline gate (Figure 7). The engine officer will ensure that this shut-off does not accidentally get shut down. There will be a slight reduction in water flow (GPM), due to the friction loss of the additional fitting and hose, which can be compensated for by increasing the pressure at the floor outlet and/or pumper. This procedure allows units to add lengths of hose without shutting down the water supply at the pumper or floor outlet. 4

5 4.6 When connecting the 1½ x 2½ increaser to the shut-off, the shut-off handle will have to be pulled back slightly to allow the lugs on the fitting to clear the handle (Figure 5). 4.7 The 1½ x 2½ increaser shall be carried in the standpipe kit connected to the extra 2½ nozzle for easy access (Figure 8). 4.8 Through training and professionalism the Department will reduce the number incidents where these problems occur, and if/when they do occur, address them quickly and efficiently, without compromising an operation. CORRECTING A SHORT STRETCH IN A 1¾ LINE 5

6 N OTE: A 1¾ H OSE S HALL NOT B E U SED T O R EPLACE A 2½ L EAD L ENGTH 6

SMOKE CONTROL USING POSITIVE PRESSURE FANS

SMOKE CONTROL USING POSITIVE PRESSURE FANS SMOKE CONTROL USING POSITIVE PRESSURE FANS 1. INTRODUCTION 1.1 This circular outlines operational guidelines for smoke and CO control using positive pressure fans (PPF) at fires and emergencies. Fans can

More information

FIRE LOGISTICS AND MATH EDUCATION A Rumpke Public Outreach Program

FIRE LOGISTICS AND MATH EDUCATION A Rumpke Public Outreach Program FIRE LOGISTICS AND MATH EDUCATION A Rumpke Public Outreach Program Welcome & Introductions Identify emergency exits to all participants. Identify location of restroom facilities. Cover any other related

More information

Wilson County Emergency Management Agency 110 Oak Street Lebanon, Tennessee 37087

Wilson County Emergency Management Agency 110 Oak Street Lebanon, Tennessee 37087 SOG Name: One and Two Family Dwellings SOG Number: 403.18 Effective Date: February 2, 2015 Approved: Joey Cooper, Director Reviewed: Scope This procedure will provide an organized method in which to carry

More information

INSTRUCTOR GUIDE REFERENCES: PUMPING APPARATUS DRIVER/OPERATOR HANDBOOK, FIRST EDITION, IFSTA

INSTRUCTOR GUIDE REFERENCES: PUMPING APPARATUS DRIVER/OPERATOR HANDBOOK, FIRST EDITION, IFSTA TOPIC: RELAY PUMPING OPERATIONS LEVEL OF INSTRUCTION: TIME REQUIRED: ONE HOUR INSTRUCTOR GUIDE MATERIALS: APPROPRIATE AUDIO VISUAL SUPPORT REFERENCES: PUMPING APPARATUS DRIVER/OPERATOR HANDBOOK, FIRST

More information

Essentials of Fire Fighting

Essentials of Fire Fighting Essentials of Fire Fighting 6 th Edition Certified Volunteer Firefighter Chapter 14 Water Supply Learning Objectives Explain the ways water supply system components are used by firefighters. Describe types

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 14 Hydraulics Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 14 Hydraulics Revised DRIVER OPERATOR Page 1 of 14 HYDRAULICS Hydraulics applied in the dynamic fire ground environment is an art that comes with study and experience. The following describes the factors that must be mastered

More information

A PARTIAL GUIDE TO MCFRS SAFE STRUCTURAL FIREFIGHTING POLICY. Section II Rapid Intervention

A PARTIAL GUIDE TO MCFRS SAFE STRUCTURAL FIREFIGHTING POLICY. Section II Rapid Intervention A PARTIAL GUIDE TO MCFRS SAFE STRUCTURAL FIREFIGHTING POLICY Section II Rapid Intervention PURPOSE The purpose of this presentation is to provide clarification for when necessary and expand on the new

More information

Head to Head Demo Comparison Sheet

Head to Head Demo Comparison Sheet Head to Head Demo Comparison Sheet Task Force Tips Crossfire Portable/Deck Mount Monitor The purpose of this document is to encourage you to compare TFT products head to head, apples to apples, with like

More information

APPROVED BY: On Original EFFECTIVE DATE: September 14 th 2009

APPROVED BY: On Original EFFECTIVE DATE: September 14 th 2009 CULPEPER COUNTY VOLUNTEER FIRE AND RESCUE ASSOCIATION, INC. Standard Operating Guidelines CHAPTER: Operations SUBJECT: Rapid Intervention Team (RIT) WRITTEN BY: Fire Committee SUPERSEDES: NUMBER O-09-03

More information

Varying pump capacity affects the required hoseline diameter

Varying pump capacity affects the required hoseline diameter Slide 1 Rural Fire Command by Larry Davis Issue #34 October 2005 H 2 O On The Go Varying pump capacity affects the required hoseline diameter 1 Slide 2 Training America s Rural Fire & Emergency Responders

More information

INSTRUCT-O-GPAM THE HANDS-ON TRAINING GUIDE FOR THE FIRE INSTRUCTOR FIRE HOSE AND NOZZLES

INSTRUCT-O-GPAM THE HANDS-ON TRAINING GUIDE FOR THE FIRE INSTRUCTOR FIRE HOSE AND NOZZLES INSTRUCT-O-GPAM THE HANDS-ON TRAINING GUIDE FOR THE FIRE INSTRUCTOR VOLUME XIV, ISSUE 1 FIRE HOSE AND NOZZLES JANUARY 1993 FIRE HOSE AND NOZZLES This is a two-part lesson covering Fire Hose and Nozzles.

More information

Township of Cumru Fire Department 03/12/2008 Standard Operating Guidelines Page: 1 of 8 Section 15.05

Township of Cumru Fire Department 03/12/2008 Standard Operating Guidelines Page: 1 of 8 Section 15.05 Standard Operating Guidelines Page: 1 of 8 15.05 Scope: This procedure will provide an organized method in which to carry out the fire ground functions in a timely and safe manner. Discussed will be the

More information

PHILADELPHIA FIRE DEPARTMENT HIGH PRESSURE FIRE HYDRANT SYSTEM PFD TRAINING MANUAL SUPPLEMENT ENGINE PRACTICES SUPPLEMENT 101 PAGE 1

PHILADELPHIA FIRE DEPARTMENT HIGH PRESSURE FIRE HYDRANT SYSTEM PFD TRAINING MANUAL SUPPLEMENT ENGINE PRACTICES SUPPLEMENT 101 PAGE 1 PHILADELPHIA FIRE DEPARTMENT HIGH PRESSURE FIRE HYDRANT SYSTEM PFD TRAINING MANUAL SUPPLEMENT ENGINE PRACTICES SUPPLEMENT 101 PAGE 1 SUPPLEMENT 101 101. HIGH PRESSURE FIRE HYDRANT SYSTEM The High Pressure

More information

FIRE FIGHTER II - SKILLS PERFORMANCE SHEET

FIRE FIGHTER II - SKILLS PERFORMANCE SHEET Fire Fighter II Skill Stations: NFPA 1001 2013 Edition Station A Fire Ground Communications & Operations / Interior Attack Coordination MANDATORY STATION Station B Sprinkler Drain/Pressures RANDOM STATION

More information

Enabling Objectives (EO): EO Identify certain practices that could be considered unsafe and result in injury or death.

Enabling Objectives (EO): EO Identify certain practices that could be considered unsafe and result in injury or death. Instructor Guide Topic: Personal Safety Awareness (Revised 6/2010) Teaching and Learning Domain: Cognitive Time Required: 2 hours Materials: Appropriate visuals and chalkboard or easel pad References:

More information

SKILL VERIFICATION BOOK FIREFIGHTER I MODULE I FIRE PROTECTION BUREAU. Assigned to: Name:

SKILL VERIFICATION BOOK FIREFIGHTER I MODULE I FIRE PROTECTION BUREAU. Assigned to: Name: Assigned to: Name: Skill Book Initiated: Department/District: Identification Number: SKILL VERIFICATION BOOK FIREFIGHTER I MODULE I Third Edition September 2004 Meeting the requirements of NFPA 1001, 2002

More information

Chapter 16 Test. Directions: Write the correct letter on the blank before each question.

Chapter 16 Test. Directions: Write the correct letter on the blank before each question. Chapter 16 Test Name: Date: Directions: Write the correct letter on the blank before each question. Objective 1: Explain the way vaporization and steam relate to the extinguishing properties of water.

More information

KILGORE FIRE DEPARTMENT

KILGORE FIRE DEPARTMENT Page 1 of 13 KILGORE FIRE DEPARTMENT Operations/ SOP Directive Issue Date: 01/01/2013 237 Effective: 01/01/2013 COMPANY PERFORMANCE STANDARDS 237.1 Purpose The purpose of this procedure is to define and

More information

Apparatus Operator Refresher Training Program

Apparatus Operator Refresher Training Program Division of Training In-Service Training Program Apparatus Operator Refresher Training Program 1 Single Engine / Single Line Operation Refresher Evolution #1 Objective: Charging single handlines at correct

More information

Chapter 1 FF I Orientation and Fire Service History

Chapter 1 FF I Orientation and Fire Service History Chapter 1 FF I Orientation and Fire Service History After completing this lesson, the student shall be able to describe how the history and culture of the fire service influence its basic mission, the

More information

Pumping Apparatus Driver/Operator Apparatus Testing. Chapter Test. Directions: Write the correct letter on the blank before each question.

Pumping Apparatus Driver/Operator Apparatus Testing. Chapter Test. Directions: Write the correct letter on the blank before each question. Chapter 15 Test Name: Date: Directions: Write the correct letter on the blank before each question. Objective 1: Distinguish among preperformance tests for pumping apparatus. 1. Which standard is commonly

More information

ESCONDIDO FIRE DEPARTMENT TRAINING MANUAL ENGINE MODULE HOSE PAGE 1 OF 24 Attack Hose Lays Revised

ESCONDIDO FIRE DEPARTMENT TRAINING MANUAL ENGINE MODULE HOSE PAGE 1 OF 24 Attack Hose Lays Revised HOSE 12-01-16 PAGE 1 OF 24 To effectively attack and extinguish a fire, hose lines must be removed from the apparatus and advanced to the location of the fire. The techniques used to advance hose lines

More information

To establish a guideline for the safe and effective deployment of apparatus, personnel, and resources at the scene of structural fires.

To establish a guideline for the safe and effective deployment of apparatus, personnel, and resources at the scene of structural fires. Buxton Fire-Rescue Standard Operating Guideline Subject: Structural Fire (3) Section: Operations at Structure Fires (2) Page 1 of 7 Purpose: To establish a guideline for the safe and effective deployment

More information

FSRS Relative Point Value Guide

FSRS Relative Point Value Guide FSRS Relative Point Value Guide Note: This document has been produced by PIAL as a "guide" to show each 's impact to your total score. Certain ideal scenarios were assumed to determine the score in the

More information

UNIT OBJECTIVES Upon completion of this unit of study, the student should be able to:

UNIT OBJECTIVES Upon completion of this unit of study, the student should be able to: BASIC FIRE FIGHTER ORIENTATION AND COMMUNICATIONS Orientation and Communications 1 UNIT OBJECTIVES Upon completion of this unit of study, the student should be able to: 1. Identify the organization of

More information

FIRE FIGHTER II SKILL PERFORMANCE CHECK SHEETS NFPA FIRE FIGHTER II SKILL STATION MENU

FIRE FIGHTER II SKILL PERFORMANCE CHECK SHEETS NFPA FIRE FIGHTER II SKILL STATION MENU FIRE FIGHTER II SKILL STATION MENU STATION TASK(S) A FIREGROUND OPERATIONS/FIRE COMMUNICATIONS MANDATORY B SPRINKLER DRAIN/PRESSURES RANDOM C PITOT GAUGE USE RANDOM D INSPECTION/MAINTENANCE: GENERATOR,

More information

INSTRUCTOR GUIDE MATERIALS: TWO FULLY EQUIPPED PUMPERS STATIC AND PRESSURIZED WATER SOURCES

INSTRUCTOR GUIDE MATERIALS: TWO FULLY EQUIPPED PUMPERS STATIC AND PRESSURIZED WATER SOURCES COURSE: FIREFIGHTER PRE-BASIC SESSION REFERENCE: 5 TOPIC: SUPPLY LINES AND SALVAGE LEVEL OF INSTRUCTION: TIME REQUIRED: THREE HOURS INSTRUCTOR GUIDE MATERIALS: TWO FULLY EQUIPPED PUMPERS STATIC AND PRESSURIZED

More information

second test was conducted using at 3/4inch nozzle to determine a practical maximum pressure for the pump.

second test was conducted using at 3/4inch nozzle to determine a practical maximum pressure for the pump. I am writing this memo to you from the perspective of a fire apparatus operator and tester. Though I offer this collection of my observations and opinions, I do so voluntarily but with the full integrity

More information

PERFORMANCE CRITERIA AND INSTRUCTIONS

PERFORMANCE CRITERIA AND INSTRUCTIONS JPR Task(s): Roll Fire Hose OMMISSION ON FIRE PROTETION PERSONNEL STANDARDS AND EDUATION OMMONWEALTH OF KENTUKY FIREFIGHTER 1 OMPETENY EVALUATION andidate #: Skill No. 1-31 PERFORMANE RITERIA AND INSTRUTIONS

More information

Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs (NFPA 1002, 2014 Edition)

Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs (NFPA 1002, 2014 Edition) Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs ( Edition) JPR # Task Initial Certification JPR Requirement: 15 Mandatory Renewal JPR Requirement: 100% of All JPRs (including

More information

FIREGROUND HYDRAULICS

FIREGROUND HYDRAULICS INTRODUCTION This section is designed to give pump operators a quick and fairly easy process for determining fire ground hydraulics. Supplying water is a critical part of the control, and the efficient

More information

NATURAL GAS RESPONSE SOG

NATURAL GAS RESPONSE SOG SCOPE NATURAL GAS RESPONSE SOG This guideline shall apply to all members of the Stoney Point Fire Department and shall be adhered to by all members. PURPOSE The purpose of this guideline is to explain

More information

Title- FIREFIGHTER ASSIST AND SEARCH TEAM POLICY

Title- FIREFIGHTER ASSIST AND SEARCH TEAM POLICY Department of Emergency Response And Communications Cortland County 911 Public Safety Building; Suite 201 54 Greenbush Street Cortland, New York 13045 300-004 Title- FIREFIGHTER ASSIST AND SEARCH TEAM

More information

Idaho Fire Service Technology Fire Fighter II

Idaho Fire Service Technology Fire Fighter II ICS Skill Requirements Skill Sheet: 1 STANDARD: 6.1.2 TASK: Organize, coordinate, and function within an incident management system. PERFORMANCE OUTCOME: The candidate shall be able to determine the need

More information

Chapter 14 Water Shuttle Operations

Chapter 14 Water Shuttle Operations 1. Which of the following statements about water shuttle operations is TRUE? A. Water shuttle operations may create a dramatic hose failure B. Water shuttle operations are safer than relay pumping operations

More information

II-28 STOKES BASKET OPERATIONS

II-28 STOKES BASKET OPERATIONS 1 II-28 STOKES BASKET OPERATIONS Anchor Slings- (2) high strength nylon webbing straps with D-rings on both ends used to set an anchor. Max working load of 10,000 lbs. Bight- Element of knot formed by

More information

Fire Apparatus Operator: Pumper

Fire Apparatus Operator: Pumper Fire Apparatus Operator: Pumper Skill Sheet Package Based on NFPA 1002: Standard on Fire Apparatus Driver/Operator Professional Qualifications, 2014 Edition. Alabama Fire College February 2016 revised

More information

Blue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION

Blue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION Blue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION Install your Blue River Technologies Port-A-Poly mixing system in a clean dry area.

More information

High-Rise Fireground Field Experiments Results

High-Rise Fireground Field Experiments Results High-Rise Fireground Field Experiments Results These graphs show average times for each critical task by crew size. Percentage calculations for all the charts were based on the overall time from detection

More information

Pump Stages. By Tom Murray

Pump Stages. By Tom Murray Pump Stages By Tom Murray As is often the case, we in the fire service tend to make things more difficult than they need to be. I believe this is the situation when discussing the pros and cons of single,

More information

DISCLAIMER TSS is simply providing current information so you can make sound tactical decisions.

DISCLAIMER TSS is simply providing current information so you can make sound tactical decisions. Objectives Identify and secure an adequate water supply. Perform a 360 degree Size Up. Develop an appropriate IAP. Make the appropriate hose line selection, hose stretch and water application based on

More information

The term MAYDAY typically will be used in the following situations:

The term MAYDAY typically will be used in the following situations: Page: 1 of 6 This procedure identifies individual, company, and command level activities for the search and rescue of a lost or trapped firefighter(s). LOST OR TRAPPED FIREFIGHTER The rescue of trapped

More information

Flow Material Length. Weight GPM LPM. Style 3095

Flow Material Length. Weight GPM LPM. Style 3095 Akron Municipal Eductors feature a large, easy to read, and removable metering dial with infinite settings between 0% and 6%. Detents at 1 4, 1 2, 1, 3 and 6%. The Eductors are rated to flow at 200 psi

More information

Fire and Rescue Operations Chapter 03 2 In, 2 Out and Rapid Intervention March 2009

Fire and Rescue Operations Chapter 03 2 In, 2 Out and Rapid Intervention March 2009 Division 06 Fire and Rescue Operations Chapter 03 2 In, 2 Out and Rapid Intervention March 2009 POLICY A procedure for the deployment and operations of personnel when functioning as a member of the Rapid

More information

Driver Releasal Manual

Driver Releasal Manual Driver Releasal Manual In order to participate in the DPO program, the candidate must: o Possess a valid Virginia Driver s License o Be 18 years of age o Be covered under the County insurance policy o

More information

FIRE FIGHTER II JPR: FFII-1A

FIRE FIGHTER II JPR: FFII-1A JPR: FFII-1A STANDARD: 6.1.2 Task: Implement Incident Management System. General Requirements The candidate shall demonstrate the ability to determine need for command, organize and coordinate an incident

More information

Essentials of Fire Fighting 6 th Edition Firefighter I

Essentials of Fire Fighting 6 th Edition Firefighter I 1 Essentials of Fire Fighting 6 th Edition Firefighter I Chapter 14 Water Supply Learning Objective 1 2 Explain the ways water supply system components are used by firefighters. 14 2 There are two types

More information

PHILADELPHIA FIRE DEPARTMENT OPERATIONAL PROCEDURE # 38 DECEMBER, 2001

PHILADELPHIA FIRE DEPARTMENT OPERATIONAL PROCEDURE # 38 DECEMBER, 2001 PHILADELPHIA FIRE DEPARTMENT OPERATIONAL PROCEDURE # 38 SUBJECT: RAPID INTERVENTION TEAM (RIT) 1. PURPOSE The purpose of this Operational Procedure is to define the responsibilities of a Rapid Intervention

More information

Apparatus Operator/Pumper

Apparatus Operator/Pumper Skill Number: AOP-1 Operate Fixed Systems Objective: 4.3.7 (A) (B) 1. The candidate shall be provided with the equipment to complete this objective including apparatus. 2. The candidate uses safety precautions.

More information

Skill Sheet 17-I-2. Attack a structure fire above, below, and at ground level Interior attack. (NFPA 1001, , )

Skill Sheet 17-I-2. Attack a structure fire above, below, and at ground level Interior attack. (NFPA 1001, , ) Skill Sheet 17-I-2 Objective 22: Attack a structure fire above, below, and at ground level Interior attack. (NFPA 1001, 5.3.10, 5.3.13) Student Name: Date: Directions For this skills evaluation checklist,

More information

TurboDraft Fire Eductor

TurboDraft Fire Eductor TurboDraft Fire Eductor Operating Manual Introduction The TurboDraft is designed to be used for rural water supply operations. Many of us take for granted that there is a fire hydrant on every corner.

More information

Iowa s s Minimum Training Standard. How to Be Prepared?

Iowa s s Minimum Training Standard. How to Be Prepared? Iowa s s Minimum Training Standard How to Be Prepared? Volunteer Firefighters Volunteer Fact Sheet Volunteers comprise 73% of firefighters in the Unites States. Communities served by Volunteer Firefighters

More information

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS SEC Project No. 1803007-000 November 20, 2006 TABLE OF CONTENTS I. ABSTRACT...1 II. INTRODUCTION...1 III. HISTORY...2 IV. VARIABLE SPEED

More information

Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs (NFPA 1002, 2009 Edition)

Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs (NFPA 1002, 2009 Edition) Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs () JPR # Task Initial Certification JPR Requirement: 15 Mandatory Renewal JPR Requirement: 100% of All JPRs (including all subsections)

More information

Fire Apparatus Operator: Pumper

Fire Apparatus Operator: Pumper Fire Apparatus Operator: Pumper Skill Sheet Package Based on NFPA 1002: Standard on Fire Apparatus Driver/ Operator Professional Qualifications, 2017 Edition. Alabama Fire College August, 2018 revised

More information

FIRE CHIEF S ASSOCIATION OF BROWARD COUNTY

FIRE CHIEF S ASSOCIATION OF BROWARD COUNTY FIRE CHIEF S ASSOCIATION OF BROWARD COUNTY Uniform Rapid Intervention Crew and Mayday Operations I. Purpose Adopted September 6th, 2012 A. To provide operational procedures for Rapid Intervention Crew

More information

2017 Volunteer Week - Course Descriptions

2017 Volunteer Week - Course Descriptions 2017 Volunteer Week - Course Descriptions 40 Hour Course - S130/S190/L180 Introduction to Wildland Firefighting S190 This course provides instruction in the primary factors affecting the start and spread

More information

STANDARD OPERATING GUIDELINE

STANDARD OPERATING GUIDELINE DATE ISSUED: Purpose The purpose of this guideline is to establish procedures for when it becomes necessary to provide emergency assistance to a firefighter(s) that is/are lost, incapacitated or unable

More information

Rapid Intervention Teams

Rapid Intervention Teams Rapid Intervention Teams High Country Training Center Training On Demand Captain T. Houston, LDFR Objectives Review air management principles Identify the components of a Mayday call Describe the steps

More information

Volunteer Firefighter Applicant Information Package

Volunteer Firefighter Applicant Information Package Volunteer Firefighter Applicant Information Package INTRODUCTION TO THE KINGSVILLE FIRE DEPARTMENT The Kingsville Fire Department provides emergency fire and rescue service to the residents of the Town

More information

Idaho Fire Service Technology Pumping Apparatus Driver/Operator Skill Sheet: 1

Idaho Fire Service Technology Pumping Apparatus Driver/Operator Skill Sheet: 1 Skill Sheet: 1 Standard 4.2.1, 4.2.2 Task: Perform and document routine test, inspection and servicing functions on specified systems and components. Performance Outcome: Given a fire department pumping

More information

Developed by Lieutenant Randy Stuart, Engineer Matt Hintzman and Firefighter Chris Sandoli November 2010

Developed by Lieutenant Randy Stuart, Engineer Matt Hintzman and Firefighter Chris Sandoli November 2010 W ATER S UPPLY O PERATIONS M UNICIPAL/SUBURBAN (1.1) Developed by Lieutenant Randy Stuart, Engineer Matt Hintzman and Firefighter Chris Sandoli November 2010 NFPA 1142 Standard on Water Supplies for Suburban

More information

Number of Pages: 13 SOG Number: 1-13

Number of Pages: 13 SOG Number: 1-13 Purpose: The purpose of this SOG is to establish command procedures, identify optional levels of rapid intervention capability, minimum training and equipment requirements for functioning RIT teams and

More information

Upon completion of this unit of study, the student should be able to: 1. Identify the parts of a water distribution system.

Upon completion of this unit of study, the student should be able to: 1. Identify the parts of a water distribution system. Water Supply - 1 UNIT OBJECTIVES Upon completion of this unit of study, the student should be able to: 1. Identify the parts of a water distribution system. 2. Identify the causes of increased resistance

More information

TSI FLOWMETERS PRACTICAL GUIDANCE NOTE FOR FIRE FIGHTING STAFF AND

TSI FLOWMETERS PRACTICAL GUIDANCE NOTE FOR FIRE FIGHTING STAFF AND TSI FLOWMETERS PRACTICAL GUIDANCE NOTE FOR FIRE FIGHTING STAFF AND TSI FLOWMETERS PRACTICAL GUIDANCE NOTE FOR FIRE FIGHTING STAFF CONTENTS 1 Objectives of TSI Guidance Note- What you can expect to learn.

More information

PROPERTY INSURANCE ASSOCIATION OF LOUISIANA

PROPERTY INSURANCE ASSOCIATION OF LOUISIANA PROPERTY INSURANCE ASSOCIATION OF LOUISIANA WATER HAULING GUIDELINES NOTE: Effective immediately, Fire Departments in Louisiana who receive credit for water hauling will receive their credit through a

More information

Topic: Forward Lay/Offensive Fire Attack Reference #: DG 16-6 orig Level of Instruction: In service personnel Time Required: 3 hours

Topic: Forward Lay/Offensive Fire Attack Reference #: DG 16-6 orig Level of Instruction: In service personnel Time Required: 3 hours Topic: Forward Lay/Offensive Fire Attack Reference #: DG 16-6 orig 14-08 Level of Instruction: In service personnel Time Required: 3 hours Instructor Preparation: This drill requires basic preparation

More information

Cozumel Turbodraft. Operational Considerations

Cozumel Turbodraft. Operational Considerations Cozumel Turbodraft Operational Considerations Safety Guidelines Safety Guidelines 1. Carefully read and follow all operating instructions before putting the TurboDraft unit into service. 2. Be sure all

More information

Checklist For Planning And Conducting The LSA Materials (Class 7-Radioactive) Emergency Response Drill

Checklist For Planning And Conducting The LSA Materials (Class 7-Radioactive) Emergency Response Drill Drill Package Page: 1 of 7 Checklist For Planning And Conducting The LSA Materials (Class 7-Radioactive) Emergency Response Drill Drill Date (For additional information refer to the Guidance for Planning,

More information

Engine Compan. pany y Operations. Firefighting and Emergency Operations Volume I - General Firefighting Procedures Book 2 Issued November 2003

Engine Compan. pany y Operations. Firefighting and Emergency Operations Volume I - General Firefighting Procedures Book 2 Issued November 2003 Fire and Rescue Departments of Northern Virginia Firefighting and Emergency Operations Volume I - General Firefighting Procedures Book 2 Issued November 2003 Engine Compan pany y Operations Developed through

More information

POINT PLEASANT BEACH FIRE DEPARTMENT. Firefighter Assistance Search Team (F.A.S.T.) Standard Operating Guideline

POINT PLEASANT BEACH FIRE DEPARTMENT. Firefighter Assistance Search Team (F.A.S.T.) Standard Operating Guideline POINT PLEASANT BEACH FIRE DEPARTMENT Firefighter Assistance Search Team (F.A.S.T.) Standard Operating Guideline Purpose: The purpose of the F.A.S.T. is to provide a back up team of trained firefighters

More information

**ALL SHADED SKILLS MUST BE SIGNED OFF BEFORE LIVE FIRE TESTING MAY OCCUR**

**ALL SHADED SKILLS MUST BE SIGNED OFF BEFORE LIVE FIRE TESTING MAY OCCUR** UTAH FIRE SERVICE CERTIFICATION SYSTEM FIREFIGHTER I NFPA 1001, 2013 Edition FIREFIGHTER I TRAINING RECORD / IN-HOUSE COMPREHENSIVE EXAM NAME: DEPARTMENT: **ALL SHADED SKILLS MUST BE SIGNED OFF BEFORE

More information

rd Quarter Continuing Education Hazardous Materials Defensive Actions/ Emergency Decon

rd Quarter Continuing Education Hazardous Materials Defensive Actions/ Emergency Decon 2007 3 rd Quarter Continuing Education Hazardous Materials Defensive Actions/ Emergency Decon This Continuing Education exercise is designed to cover the general responsibilities of a response to a possible

More information

Manhattan Fire Protection District

Manhattan Fire Protection District Section: TRAINING Page 1 of 14 Section 1: Purpose Section 2: Scope Section 3: Enforcement Section 4: Definitions Section 5: Member Requirements Section 6: Extensions Section 7: Class Content Classification

More information

Irrigation System Winterization and Pressurization Procedures

Irrigation System Winterization and Pressurization Procedures Irrigation System Winterization and Pressurization Procedures Introduction Any time that an irrigation system is filled and pressurized, or when the system is drained and water flushed from the system,

More information

Standard Operating Procedures S.O.P. Sample Template Drafted by: Oklahoma State Firefighters Association Educational Advisory Committee

Standard Operating Procedures S.O.P. Sample Template Drafted by: Oklahoma State Firefighters Association Educational Advisory Committee Standard Operating Procedures S.O.P. Sample Template Drafted by: Oklahoma State Firefighters Association Educational Advisory Committee ** Remember Safety First ** INTRODUCTION Remember, the following

More information

Township Of Jackson, Fire District 3, Station 55 Standard Operating Guidelines TWO IN TWO OUT

Township Of Jackson, Fire District 3, Station 55 Standard Operating Guidelines TWO IN TWO OUT Guideline # 310.06 Township Of Jackson, Fire District 3, Station 55 Standard Operating Guidelines TWO IN TWO OUT Date: 3/07 R PURPOSE To establish standard guidelines and procedures that will serve to

More information

TECHNICAL DATA. than the water inlet pressure to the concentrate

TECHNICAL DATA. than the water inlet pressure to the concentrate Foam102a 1. DESCRIPTION The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with 3M foam concentrates. This system consists of a standard wet pipe sprinkler

More information

San Ramon Valley Fire Protection District

San Ramon Valley Fire Protection District San Ramon Valley Fire Protection District March, 2009 Company Performance Standards i Introduction This manual establishes a series of standard incident-based company evolutions for District use. Collectively,

More information

Fire Apparatus Operator Aircraft Rescue and Fire Fighting

Fire Apparatus Operator Aircraft Rescue and Fire Fighting Fire Apparatus Operator Aircraft Rescue and Fire Fighting Skill Sheet Package Based on NFPA 1002: Standard on Fire Apparatus Driver/ Operator Professional Qualifications, 2014 Edition. Alabama Fire College

More information

Water Supply for Suburban and Rural Firefighting

Water Supply for Suburban and Rural Firefighting FIRE AND RESCUE DEPARTMENTS OF NORTHERN VIRGINIA FIREFIGHTING AND EMERGENCY OPERATIONS MANUAL Water Supply for Suburban and Rural Firefighting Second Edition Issued: 2003 Revised: November 2017 ACKNOWLEDGEMENTS

More information

EXIT WINDOW USING PERSONAL SAFETY SYSTEM (PSS) WITH REMOTE ANCHOR

EXIT WINDOW USING PERSONAL SAFETY SYSTEM (PSS) WITH REMOTE ANCHOR October 1, 2007 EXIT WINDOW USING PERSONAL SAFETY SYSTEM (PSS) WITH REMOTE ANCHOR 1. EQUIPMENT Personal Harness and Personal Safety System. 2. OBJECTIVE To enable a firefighter to remove themselves from

More information

Cedarville Township Volunteer Fire Department Fire Department Standard Operating Guidelines 2008

Cedarville Township Volunteer Fire Department Fire Department Standard Operating Guidelines 2008 Cedarville Township Volunteer Fire Department Fire Department Standard Operating Guidelines 2008 1. Your personal safety is your first priority 2. Always operate equipment safely and under control. A vehicle

More information

CHAPTER 2 2 EMERGENCY PROCEDURES EMERGENCY PROCEDURES. Emergency Response Plan and Procedures

CHAPTER 2 2 EMERGENCY PROCEDURES EMERGENCY PROCEDURES. Emergency Response Plan and Procedures CHAPTER 2 EMERGENCY PROCEDURES 2 EMERGENCY PROCEDURES 3. Communication Systems To relay accurate information quickly, use reliable communications equipment, develop procedures, and train personnel. A backup

More information

SUBJECT: RAPID INTERVENTION CREW (RIC) SOG DATE ADOPTED: OCTOBER 18, 2012 REVISED: PAGES: 7

SUBJECT: RAPID INTERVENTION CREW (RIC) SOG DATE ADOPTED: OCTOBER 18, 2012 REVISED: PAGES: 7 JOINT RESPONSE AGREEMENT MODEL STANDARD OPERATING GUIDELINE SUBJECT: RAPID INTERVENTION CREW (RIC) SOG DATE ADOPTED: OCTOBER 18, 2012 REVISED: PAGES: 7 SCOPE and PURPOSE Butler County firefighters often

More information

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection February 9, 1998 Foam 201a 1. DESCRIPTION A Deluge Bladder Tank Foam/Water System is a standard deluge system capable of discharging a foam/water solution automatically through open sprinklers, spray nozzles,

More information

TESTING SKILLS PORTABLE FIRE EXTINGUISHERS

TESTING SKILLS PORTABLE FIRE EXTINGUISHERS PORTABLE FIRE EXTINGUISHERS #1 Selecting the Appropriate Fire Extinguisher Subject: Fireground Operations Section 101 NFPA 1001 5.3.16 Firefighter I OBJECTIVE Extinguish incipient Class A, Class B, and

More information

TOPIC: EVALUATING FIREFIGHTER PROFICIENCY MATERIALS: PERSONAL PROTECTIVE CLOTHING AS REQUIRED FOR EACH EVOLUTION

TOPIC: EVALUATING FIREFIGHTER PROFICIENCY MATERIALS: PERSONAL PROTECTIVE CLOTHING AS REQUIRED FOR EACH EVOLUTION 1 MFRI Drill of the Month INSTRUCTOR GUIDE TOPIC: EVALUATING FIREFIGHTER PROFICIENCY LEVEL OF INSTRUCTION: TIME REQUIRED: SIX HOURS MATERIALS: PERSONAL PROTECTIVE CLOTHING AS REQUIRED FOR EACH EVOLUTION

More information

Suffolk County YMCA 123 Main Street East Hampton, NY 11937

Suffolk County YMCA 123 Main Street East Hampton, NY 11937 Suffolk County YMCA 123 Main Street East Hampton, NY 11937 Contact Information: Director of Operations Deanna Meunier (631) 329-6884 Deanna.meunier@ymca.org Emergency Contacts: Director of Communications

More information

GEORGIA FIREFIGHTER STANDARDS AND TRAINING FIREFIGHTER I EQUIPMENT & FACILITIES LIST

GEORGIA FIREFIGHTER STANDARDS AND TRAINING FIREFIGHTER I EQUIPMENT & FACILITIES LIST GEORGIA FIREFIGHTER STANDARDS AND TRAINING FIREFIGHTER I EQUIPMENT & FACILITIES LIST Purpose To ensure that the test site will have the required equipment and facilities to a conduct Firefighter I skills

More information

College of Eastern Idaho. Fire Service Technology IFSAC. Firefighter Certification Program. Firefighter I

College of Eastern Idaho. Fire Service Technology IFSAC. Firefighter Certification Program. Firefighter I College of Eastern Idaho Fire Service Technology IFSAC Firefighter Certification Program The following skills sheets are meant to be printed 2 sided. This allows the candidate to view the instructions

More information

RESOURCE; IFSTA ESSENTIALS OF FIREFIGHTING 4 TH AND 5 TH EDITION

RESOURCE; IFSTA ESSENTIALS OF FIREFIGHTING 4 TH AND 5 TH EDITION RESOURCE; IFSTA ESSENTIALS OF FIREFIGHTING 4 TH AND 5 TH EDITION 1 DIFFERENT TYPES OF ROPE CONSTRUCTION /CLASIFICATIONS PROPER CARE OF YOUR ROPE RECORD KEEPING AND STORAGE OF ROPES SEVERAL KNOTS USED IN

More information

CLEARWATER FIRE AND RESCUE DEPARTMENT STANDARD OPERATING PROCEDURE APPROVED BY: EFFECTIVE DATE: 10/12/07 REVISION DATE:

CLEARWATER FIRE AND RESCUE DEPARTMENT STANDARD OPERATING PROCEDURE APPROVED BY: EFFECTIVE DATE: 10/12/07 REVISION DATE: CLEARWATER FIRE AND RESCUE DEPARTMENT STANDARD OPERATING PROCEDURE SUBJECT: Truck Company SUB PAGE 1 OF 6 APPROVED BY: JAMIE D. GEER, FIRE CHIEF, FIRE AND RESCUE DEPARTMENT FORMS REQUIRED: NOTE: Current

More information

Fire Apparatus Operator (FAO)

Fire Apparatus Operator (FAO) Fire Apparatus Operator (FAO) 1106 NATURE OF WORK This is skilled fire fighting work in combating, extinguishing, and preventing fires, in responding to render emergency medical services, in responding

More information

New Hire Physical Agility Process 2018

New Hire Physical Agility Process 2018 New Hire Physical Agility Process 2018 It is important that you dress in clothes and shoes that would be comfortable to exercise in. Applicants participating in the physical agility test will wear a fire

More information

Florissant Valley Fire Protection District Monthly Training Schedule

Florissant Valley Fire Protection District Monthly Training Schedule Florissant Valley Fire Protection District Monthly Training Schedule March 2013 Weekly Skill Drill Summary *Required by All Individuals* Subject Dates Description and Requirement Extension Ladders March

More information

Emergency Response Plan

Emergency Response Plan Regulatory Citation What It Is Who It Applies To OSHA - 29 CFR 1910.120(q)(1) - Emergency Response Plan Standard improves the ability of employees and employers to respond to emergencies caused by releases

More information

Driver Operator Pumps: Basic Pump Operations

Driver Operator Pumps: Basic Pump Operations Driver Operator Pumps: Basic Pump Operations 5 Skills Total NFPA 1002, Standard for Driver Operator Professional Qualifications, 2014 Edition Driver Operator Pumps: Basic Pump Operations Skills Book NFPA

More information

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE February 9, 1998 Foam 101a A BLADDER TANK WITH 1. DESCRIPTION A Wet Pipe Bladder Tank Foam/Water System is a standard wet pipe automatic sprinkler system capable of discharging a foam/water solution automatically

More information

Des Plaines Fire Dept. Engineer Program

Des Plaines Fire Dept. Engineer Program Des Plaines Fire Dept. Engineer Program Lieutenants Palenik, Gross, Owen, Butenschoen, Engineer Felde New Developments 1. Laminated fluid specs on the rigs 2. Maintenance repair request updates 3. Locations

More information