Fire test of ventilated and unventilated wooden façades

Size: px
Start display at page:

Download "Fire test of ventilated and unventilated wooden façades"

Transcription

1 Fire test of ventilated and unventilated wooden façades Lars Boström, Charlotta Skarin, Mathieu Duny, Robert McNamee SP Technical Research Institute of Sweden SP Report 216:16

2 Fire test of ventilated and unventilated wooden façades Fire test of ventilated and unventilated wooden façadesfire test of ventilated and unventilated wooden façades Lars Boström, Charlotta Skarin, Mathieu Duny, Robert McNamee

3 3 Abstract Fire test of ventilated and unventilated wooden façades Three large scale façade tests in accordance with SP Fire 15 as well as an ad hoc SBI test have been carried out. The façade tests included an inert façade made of lightweight concrete, one façade with a plywood cladding and finally a façade with plywood cladding with a fully ventilated cavity behind the cladding. The SBI test was made with plywood without ventilation cavity. The aim of the tests was to perform well controlled tests with numerous of measurements including heat release rate, heat from the combustion chamber, temperature on the façade surface, heat flux, plume temperatures and temperatures in the ventilation cavity. The results from the tests will be used for validation of simulation techniques as well as input for further development of the façade test methodology. Conclusions from the study were that the surface temperature for charring of the plywood cladding in this configuration was in the region of C and that the energy release originated from the façade during the test was almost twice as high when there was a 2 mm wide cavity behind the plywood cladding. Key words: fire test, facade, wood, ventilation cavity SP Sveriges Tekniska Forskningsinstitut SP Technical Research Institute of Sweden SP Report 216:16 ISBN ISSN Borås 216

4 4 Contents Abstract 3 Contents 4 Preface 5 Summary 6 1 Introduction Background Limitations 7 2 Experimental setup SP Fire Test method Test specimens Instrumentation and measurements 11 3 Experimental setup SBI 14 4 Test results General observations Fire source Heat release rate Thermal exposure on the façade above the combustion chamber Thermal exposure and heat flux one storey above the combustion chamber Thermal exposure two storeys above the combustion chamber Surface temperature Temperature 1 mm above the combustion chamber Temperature 27 mm above the combustion chamber Temperature 345 mm above the combustion chamber Temperature 4 mm above the combustion chamber Temperature 5 mm above the combustion chamber Plume temperature at different heights Plume temperature 1 mm above the combustion chamber Air temperature 27 mm above the combustion chamber Air temperature 345 mm above fuel source Air temperature 4 mm above combustion chamber Air temperature 5 mm above combustion chamber Temperature below the eave Results from SBI test 65 5 Analysis and discussion Fire source Fire spread on the surface Position of measurements Measurement of fire spread on a material Effect of ventilation cavity 76 6 Conclusions 78 7 References 79

5 5 Preface The façade is an important part of a building. It forms the envelope of the building, and has several functions. When combustible materials are used, or there are other risks in case of fire, i.e. large parts of the façade may fall down, it is necessary to evaluate the behavior of the façade when exposed to fire. The present project has mainly been an experimental study, involving large test specimens. We would like to thank the eminent group of technicians who have taken care of all practical details within a very pressed time schedule, no one named, no one forgotten. We would also like to thank Mr. Pär Johansson for valuable discussions on what, how and where to do all the different measurements and what the results might represent. The project is part of a collaboration between Centre Scientifique et Technique de Bâtiment (CSTB) in Paris, France, and SP Fire Research in Borås, Sweden, who both have financially supported the study.

6 6 Summary Three well documented façade fire tests in accordance with SP Fire 15 have been carried out. The tests consisted of one inert façade, one façade with a plywood cladding and finally one façade with a plywood cladding with a fully ventilated cavity behind the cladding. In all three tests numerous of measurements were made such as heat release rate, heat from the combustion chamber, surface temperatures, plume temperatures, heat flux, and temperatures in the ventilation cavity. In addition to the full scale façade tests, a SBI test was made in order to evaluate how flame spread on the surface can be determined by temperature measurements. There are some different aims with the study. Firstly, the experiments should be well documented and measurements should be done so the results can be used for validation of different simulation techniques, such as CFD (Computational Fluid Dynamics) modelling. Another aim was to assemble good data for the ongoing development of the next generation façade test methodology. Currently there are many different façade test methods, often national methods, which makes it difficult for industry. There is thus a demand for a harmonized test method. In the present study techniques for measurement of flame spread on a surface as well as how to measure or determine the heat exposure to the test specimen has been investigated. The present report is mainly an assembly of test results and a description of the tests carried out. The analysis of the results is limited, and more extended analysis will be published elsewhere. Furthermore, the tests made are limited to one type of combustible material, i.e. plywood, and thus more data will be needed for validation of the technique to measure fire spread on the surface and in cavities. Conclusions from the study were that the surface temperature for charring of the plywood cladding in this configuration was in the region of C and that the energy release originated from the façade during the test was almost twice as high when there was a 2 mm wide cavity behind the plywood cladding.

7 7 1 Introduction 1.1 Background Façades are important from several perspectives for a building. It forms the envelope of the building and shall thus be the protection towards the outdoor climate, it is an important part controlling the energy demand of the building and it is also the face of the building and has thus architectural requirements. The façade has thus a number of functions for the building. During the last decades the use of combustible materials in buildings has increased, partly as a consequence of higher demands on energy efficient buildings. In order to determine the fire risks for different types of façade systems a good and reliable test methodology is needed. There are presently a large number of different test methods used around the world [1] which all have certain advantages but also disadvantages. In Sweden the test method SP Fire 15 [2] is currently used, but it is currently under a major revision. The Swedish test method was originally developed in the middle of the 198-ties as a part of a large study including burning of 14 façades with a fully developed room fire as a heat source [3]. The fire exposure was optimised in the SP Fire 15 test to correspond to the large test. In the large scale tests the fire load density was 11 MJ/m 2 of total surface area of the enclosure. The enclosure dimensions were 4 x 2.2 x 2.6 m 3 with the opening factor.6 m 1/2. During the tests approximately 5% of the fuel was burning outside the chamber. This factor is dependent on the geometry of the enclosure and on fuel parameters such as composition and geometry. In the SP Fire 15 test the fire source is 6 litres of heptane burning in trays with attached flame suppressors. The present study has the aim to give input data for the revision of SP Fire 15 as well as contribute with valuable data for validation of CFD modelling (Computational Fluid Dynamics). Another part of the study is to measure the difference in flame spread of combustible façade claddings with and without a ventilation cavity. One important aspect is how the flame spread on the surface, and in the cavity shall be determined. Presently the flame spread is determined by visual observations after the fire test in SP Fire 15, i.e. by visual observation of what type of damage has occurred, and how high up on the façade. This is a blunt tool, which in some cases is dependent on the persons doing the observation especially when much soot, tar and char is mixed in the area where the flame front is. In other methods measurements or estimations are done in different ways. In the British method BS [4] temperature is measured a distance of 5 mm from the surface at different heights. In the international standard ISO [5] a surface temperature as well as a temperature 1 mm from the surface are measured, in addition to heat flux measurements at different heights. 1.2 Limitations Only one test has been performed on each type of test setup. Even if the tests have been performed under controlled conditions, the fire behaviour in the combustion chamber and how it is evolving and protrude out of the combustion chamber might slightly change from test to test since it is a free burning test, i.e. it is not possible to control how the burning takes place and evolves in the combustion chamber. The aim of the present study was mainly to collect data for future analysis. The content of this report is therefore primarily a presentation of all measurements done, and a short

8 8 discussion on trends observed. Only a limited analysis of the results is included in the present report. These data will be used in other projects aiming for more thorough analysis.

9 9 2 Experimental setup SP Fire Test method The experiments has been based on the Swedish test method SP Fire 15 [2]. In the present tests the façade cladding has been mounted on a lightweight concrete backing with the maximum density of kg/m 3. Openings for two fictitious windows have been used in the tests. The total area of the façade was 4 x 6 m (width x height). A principle drawing of the façade rig is presented in Figure 1. Fictitious window A Lightweight concrete wall Steel frame Eave Storey 1 Storey 2 Storey Heat flux meter Fire Room A Fire Source Section A-A mm Figure 1. Test rig used in SP Fire 15 [2]. The fire source was two trays with the dimensions x mm filled with 3 litres of heptane each, placed so the total size of the fire source was x mm. On top of the tray a flame suppressor was installed, see figure 2.

10 1 Flame suppressor Heptane Water Tray of steel sheet x x mm Water to raise the surface of the heptane fuel to the lower edge of the flame suppressor at the start of the fire test. Fire Source - Heptane mm 2 Flame suppressor of perforated steel sheet, hole Ø=25 mm, center distance 4 mm. mm Figure 2. Principle drawing of the fire source. There is an air intake directly behind the fuel source with the dimensions 314 x mm, centrally placed 5 mm from the back wall of the fire room, see figure 3. Figure 3. Drawing of the fire room. The test rig was placed in the large fire hall at SP Fire Research in Borås, Sweden. The fuel trays as well as the heptane and water used were conditioned to the room temperature before any tests were performed. When filling the fuel into the trays first the right amount of heptane was filled. Thereafter water was added until the liquid surface reached the bottom surface of the flame suppressor.

11 11 Even when the test is carried out indoors, in the large test hall, the ventilation in the hall creates a wind. Some measurements have been done showing that the wind is in the order of.1-.5 m/s, and in the direction parallel to the face of the façade rig, going from right to left side of the façade. 2.2 Test specimens Three different tests were carried out. The first test was made without any cladding on the lightweight concrete, i.e. an inert façade. In the second test a cladding of 24 mm thick plywood was mounted directly onto the lightweight concrete, i.e. no ventilation cavity behind the plywood. In the third test plywood was mounted with a ventilation cavity of approximately 2 mm between the lightweight concrete and the plywood. The plywood was bought at a local store for building materials, and it was a standard product for the Swedish market, with the dimensions 1 x 2 mm 2. Samples were taken from the plywood for measurement of moisture content and density. These measurements were made approximately at the time of the tests. The plywood had a moisture content of 6.5 % and the density at that moisture content was determined to 489 kg/m 3. The plywood was mounted on the whole front surface of the test rig, except at the fictitious windows. In order to get an air cavity behind the plywood for Test 3, strips of mineral wool, with density of 18 kg/m 3, was used. These strips had a thickness of 2 mm (giving an air gap of 2 mm) and a width of approximately 3 mm. The mineral wool strips where mounted along all vertical edges of the plywood boards, i.e. they were not acting as fire stops in the vertical direction, although they were acting as fire stops in horizontal direction in the cavity. 2.3 Instrumentation and measurements The tests were performed with a lot of extra instrumentation in addition to the required instrumentation in accordance with SP Fire 15. Figure 4 shows the placement of different measuring devices on the surface of the test specimens. Devices C1-C19 are.5 mm wire diameter thermocouples, type K. The measuring point of the thermocouples were made with Quick-Tips, i.e. a small metal ring, diameter 3 mm and length 2 mm, that clamps the two wires together. The weight of a this size Quick-Tip is.1 g. In all tests the tip of the thermocouple (the Quick-Tip) was pressed into the surface of the exposed surface of the façade, i.e. the measurement represents approximately the surface temperature of the façade. In Test 3, plywood with a cavity, thermocouples were also mounted in the plywood surface on the cavity side at the same positions as on the front surface. Devices PT1-PT6 are conventional x mm plate thermometers, i.e. the same devices as used in fire resistance furnaces, see for example EN [6]. PT1-PT3 were placed on a distance mm from the combustion chamber and pointing towards the fire, see also Figure 7. PT4-PT6 were mounted on the surface of the façade and pointing outwards. Plate thermometers have an time constant of between 1 and 2 minutes [7].

12 12 Device HF1 is a Schmidt Boelter heat flux meter. The device was mounted flush with the surface of the fictitious window which is specified in SP Fire 15 [2]. Figure 4. Placement of measuring devices on the test specimens. PT1-PT3 are placed mm outwards from the combustion chamber and directed towards the fire. In addition to these measurements temperature was also measured at a distance and mm from the façade with.5 mm type K thermocouples with a welded tip. These temperature measurements were performed at the same positions as thermocouples C2, C3, C6, C7, C13, C14, C17 and C18. The same positions were also used in Test 3 in the ventilation cavity where the thermocouples were mounted in the centre between the lightweight concrete and the plywood, that is 1 mm from the plywood surface. Furthermore, as specified in SP Fire 15, two.5 mm type K thermocouples with a welded tip were positioned mm below the eave at the top of the façade rig (see figure 1), at a distance mm and mm from the façade surface, and at the centre line of the specimen.

13 13

14 14 3 Experimental setup SBI A complimentary test was performed with the Single Burning Item (SBI) method, EN [8]. The SBI test is not a suitable method for testing façades due to several reasons, but it can be used for evaluation of the temperature measurements used for determination of fire spread on the façade surface. In the test two panels are used, one large wing with the dimensions 1. x 1.5 m 2 (width x height), and a small wing with the dimensions.49 x 1.5 m 2. In the bottom corner between the two panels a sand burner is used, which is burning with a constant effect of 3 kw. In the present study a total of 4 thermocouples were mounted on the surface of the test specimen, 2 thermocouples on the large wing, and 2 thermocouples on the small wing, see figure 5. The thermocouples were positioned at different heights, as shown in figure 5, and at different distance from the corner (,, and mm). Figure 5. Position of temperature measurements and type of hot tip of the thermocouples. The thermocouples were all of the same type,.5 mm diameter wire and of type K. The hot tip of the thermocouples, i.e. the tip where the two wires are connected, where prepared in four different ways.

15 15 At a height of mm and 7 mm above the floor level the tip was made with a Quick- Tip, i.e. a cylinder with diameter 3 mm and length 2 mm and a weight of.1 g, is clamped around the two wires. The Quick-Tip is then pressed into the surface of the specimen so it will be flush with the surface. This is a robust method which enables the measuring point to be pressed into the surface. Although, the thermal inertia is higher due to the mass of the Quick-Tip, compared with welded wires, and thus the response time is slightly longer for this type of thermocouple. At the height mm and 9 mm the thermocouple was welded to a copper disc with diameter 1 mm, i.e. the same type used for measurement of surface temperature in fire resistance tests in accordance with EN [6], but without using the insulation pad. The thermocouple and the copper disc were attached to the surface by clamping and tape. With this type of thermocouple the measured temperature is in principle averaged over a larger area, i.e. the area of the highly conductive copper disc. Although, the copper disc protects the underlying material for radiation from the fire, but it may be possible to detect eventual fire spread on the surface around the copper disc. At the height mm and mm a welded tip of the thermocouples were used. The wire was attached to the test specimen by clamping and tape. This type of thermocouple tip has the lowest thermal inertia and thus it gives the fastest response time in this study. Although, it is more difficult to mount it flush to the surface for estimations of surface temperature. At the height 8 mm the thermocouples were welded to a horizontal steel wire, i.e. all thermocouples were fixed to the same steel wire. The steel wire was clamped to the test specimen. The idea with this type of mounting was mainly to have a method for easy mounting of thermocouples.

16 16 4 Test results 4.1 General observations Three tests were performed indoors in the large test hall at SP. In Test 1 the backing material of the façade rig consisted of lightweight concrete and was used without any further cladding. In Test 2 the lightweight concrete was covered with the plywood cladding. In Test 3 the same type of plywood cladding was used, with a 2 mm air gap, cavity, between the lightweight concrete and the plywood. The lightweight concrete on the façade rig, i.e. the inert façade, was in equilibrium with approximately 5 % relative humidity, and had a density of 55 kg/m 3. The moisture content and the density of the plywood was measured at the time of testing. The moisture content was 6.5 % and the density at that moisture content was determined to 489 kg/m 3. Table 1 gives some general information regarding the three tests made. Table 1. General information on the tests Test 1 Test 2 Test 3 Test date (morning) (afternoon) (morning) Initial air temperature 18.8 C 17.3 C 18. C Initial relative humidity 38 % 4 % 49 % Temperature of heptane and water 19.2 C 16.2 C 15.9 C In tables 2-4 the visual observations made during the test are presented. It shall be noted that the visual observations represent the observations made during the tests, and that the actual issue observed may have occurred earlier than the noted time. Table 2. Visual observations during Test 1 inert façade. Time min:s Observations : The fire source of heptane is ignited. The test starts. 3:3 Smoke emerges out from the fire room. 4: Dark smoke emerges out from the fire room. 4:1 Flames and dark smoke emerge out from the fire room. 4:35 Some flames reach up to the lower edge of the lower window opening. 5:3 Some flames reach up to the upper edge of the lower window opening. 7: Flames reach half the height of the façade. 8:2 Flames reach up to the lower edge of the upper window opening. 1:3 Flames reach half the height of the façade. 12:5 Some flames reach up to the lower edge of the upper window opening. 14: Some flames reach just above the lower edge of the upper window opening. 15:3 Some flames reach up to the lower edge of the upper window opening. 16:5 The flames cease. 17: Flames reach just out from the fire room. Dark smoke comes out from the fire room. 18: The test terminates. The fire source has become extinct. The test specimen is extinguished with water.

17 17 Table 3. Visual observations during Test 2 plywood without cavity. Time min:s Observations : The fire source of heptane is ignited. The test starts. 3: Smoke emerges out from the fire room. 4:1 Flames and dark smoke emerge out from the fire room. 4:3 Flames reach up to the lower edge of the lower window opening. 5: Flames reach above the upper edge of the lower window opening. 5:25 Flames reach the eave. 5:5 It burns along the upper edge of the lower window opening. The plywood panel between the window openings glows. 7: It burns in the lower left corner of the upper window opening. 9: Flames reach up to the lower edge of the upper window opening. 1: Flames cease and reach half the height of the façade. 11:45 Flames along the right side of the façade reach up to the upper edge of the upper window opening. 12:15 Flames reach the eave. It burns in the lower right corner of the upper window opening. 13: It burns along the left side of the upper window opening. 13:45 It burns in the plywood panel on the right side between the window openings. 14:3 Flames along the left side of the façade reach up to the lower edge of the upper window opening. 15:3 Flames reach half the height of the façade. Small glowing pieces from the plywood fall down in front of the façade. 16: Flames reach up to the upper edge of the lower window opening. 16:15 Flames reach up to the lower edge of the lower window opening. 16:3 Flames reach just out from the fire room. 17:15 The test terminates. The fire source has become extinct. The test specimen is extinguished with water.

18 18 Table 4. Visual observations during Test 3 plywood with cavity. Time min:s Observations : The fire source of heptane is ignited. The test starts. 3:- Smoke emerges out from the fire room. 4: 4:25 Flames and dark smoke emerge out from the fire room. 5: Flames reach up to the lower edge of the lower window opening. 5:45 Flames reach up to the upper edge of the upper window opening. 6: It burns along the upper edge of the lower window opening 6:3 It burns along the lower edge of the upper window opening along the left side. 7:3 Flames reach the eave. 9:4 It burns along the upper edge of the lower window opening and along the lower edge of the upper window opening. 1:3 Flames reach almost to the eave. 11: It burns along the left side of the upper window opening. 11:2 It burns in the upper left corner of the upper window opening. 11:4 It burns along the upper edge of the upper window opening. 12:1 The lower left panel is not attached to the wall on the right side. 12:4 Flames reach the eave. 13: Part from the lower left panel falls down in front of the façade. 13:4 Some small burning pieces on the floor in front of the façade. 14: Flames reach above the eave. 14:2 It glows in the air gap by the eave. 16: Flames above the eave. 17: Flames cease. Dark smoke. 17:45 The test terminates. The fire source has become extinct. The test specimen is extinguished with water. Photographs taken during the tests are presented in figure 6. It can be noted that visual observations on the flame spread can be difficult due the extensive smoke production during the tests.

19 19 Test 1. Time: 9: min:s Test 2. Time: 9: min:s Test 3. Time: 7: min:s Test 1. Time: 12: min:s Test 2. Time: 11: min:s Test 3. Time: 12: min:s Test 1. Time: 15: min:s Test 2. Time: 14: min:s Test 3. Time: 13: min:s Figure 6. Photos taken during the test, Test 1 to the left, Test 2 in the centre, and Test 3 to the right.

20 2 4.2 Fire source The temperature from the fire source was measured by three plate thermometers placed.5 m from the opening of the combustion chamber (measured from the inner side of the lightweight concrete). The plate thermometers were pointing towards the fire, and would thus measure the heat exposure mainly from the fire source, see figures 4 and 7. Air intake Fire source PT (Plate thermometer) 1 Figure 7. Position of plate thermometers in front of the combustion chamber. The measured temperatures in front of the combustion chamber from each test are presented in figures 8 1. It is clearly shown in the growth phase in the figures that the flames from the combustion chamber is more intense on the left side compared with the right side in all tests, which also was noted visually during the tests. During the growth phase the buoyancy force in the plume is apparently not strong enough to create a vertical flow speed high enough to counteract the side winds in the laboratory. It can also be noted that it is generally hotter in the centre, but there are shorter periods during the tests where it is hotter on the left side.

21 21 8 Test 1 - inert facade 7 PT1 PT2 PT Figure 8. Temperature measured with plate thermometers.5 m from the combustion chamber in Test 1, inert façade. PT1 on left side, PT2 at the centre, and PT3 on the right side. 8 Test 2 - plywood without cavity 7 PT1 PT2 PT Figure 9. Temperature measured with plate thermometers.5 m from the combustion chamber in Test 2, plywood façade without ventilation gap. PT1 on left side, PT2 at the centre, and PT3 on the right side.

22 22 8 Test 3 - plywood with cavity 7 PT1 PT2 PT Figure 1. Temperature measured with plate thermometers.5 m from the combustion chamber in Test 3, plywood façade with a ventilation gap. PT1 on left side, PT2 at the centre, and PT3 on the right side. A mean temperature from the three plate thermometers in each test is shown in figure 11. The start of the third test was slower compared to the two first tests. Therefore a small time compensation of 3 seconds have been subtracted for the third test. The results show that the initial phase of the fire is very similar in all tests, and the duration of the tests is the same. Although there is a difference in the interval from 5 minutes up to 15 minutes, where the façade with plywood cladding had both the highest and lowest temperatures. The plywood façade with cavity gap showed the lowest temperatures in front of the combustion chamber.

23 23 8 Mean temperature from each test 7 Test 1 - inert facade Test 2 - plywood without ventilation Test 3 - plywood with ventilation Figure 11. Mean temperature measured with plate thermometers.5 m from the combustion chamber. 4.3 Heat release rate The heat release rate was measured by collecting the exhaust gases in a hood above the façade test rig [9]. The measured heat release rate is presented in figure 12. It can be noted that the initial phase of the test, up to 5 minutes, is similar in all tests, i.e. no difference between a combustible surface and an inert façade. From 5 minutes up to 1 minutes, the behaviour of the two tests with plywood is similar, i.e. the ventilation cavity does not influence on the heat release rate. The heat release rate increases with approximately kw for the combustible façades compared with the inert one. After 1 minutes into the tests, the heat release rate start to increase again, and here a difference shows up between the unventilated plywood façade and the one with a ventilation cavity. After 15 minutes the peak is reached in Test 3, and the heat release rate is approximately kw higher compared to the peak value obtained with plywood façade without ventilation, and more than kw compared to the inert façade.

24 24 3 Heat release rate (kw) 2 1 Test 1 - Inert facade Test 2 - plywood without ventilation Test 3 - plywood with ventilation Figure 12. Heat release rate measured during the fire tests. The total energy produced during the tests has been calculated as the area below the heat release curves. In Test 1 the total released energy was determined to 155 MJ, in Test 2 it was 187 MJ, and in Test 3 it was 214 MJ. Thus the additional energy from the plywood in Test 2 was 32 MJ, and in Test 3 the additional energy from the plywood was 59 MJ. This means that the additional energy from the plywood is almost doubled by the ventilation cavity. 4.4 Thermal exposure on the façade above the combustion chamber The thermal exposure was measured with a plate thermometer placed 75 mm above the upper edge of the combustion chamber, plate thermometer PT4 in figure 4. The plate thermometer was mounted on the façade surface pointing outwards. The measurement thus represent the heat exposure to the façade surface. The results from the three tests are presented in figure 13. It is clear that on the height 75 mm above the combustion chamber there is almost no difference in heat exposure towards the façade, i.e. if there is a contribution from the burning plywood to the thermal exposure 75 mm above the combustion chamber, it is minimal compared with the thermal exposure from the combustion chamber. Theoretically it is also possible that there is no contribution from combustion from the surface material originated in this zone as the diffusion flames from the combustion chamber has a very low oxygen content, i.e. release of pyrolysis gasses happens from the materials in this zone but the actual burning is higher up in the fire plume where more oxygen is blended in.

25 Test 1 - inert facade Test 2 - plywood without cavity Test 3 - plywood with cavity Figure 13. Thermal exposure to the façade 75 mm above the combustion chamber as measured with a plate thermometers directed outwards. 4.5 Thermal exposure and heat flux one storey above the combustion chamber In the centre of the fictitious window one storey above the combustion chamber the thermal exposure towards the window was measured with a plate thermometer, i.e. 2.1 m above the upper edge of the opening to the combustion chamber, plate thermometer PT5 shown in figure 4. The measured temperatures are shown in figure 14. As expected the inert façade show the lowest temperature. Comparing the two plywood façades the temperature development is similar during the first 8 minutes, at that time the temperature is approximately 65 C. Thereafter the temperature in the window cavity during the test of the specimen without air cavity behind the plywood cladding starts to decrease slowly, whereas the temperature continues to increase for the specimen with a ventilation gap behind the plywood cladding and reaches a maximum of 75 C after 13 minutes. It is clear that a combustible façade cladding increases the heat exposure to the window one storey above the fire source, and that a ventilation gap behind the combustible cladding increases the heat exposure even further.

26 Test 1 - inert facade Test 2 - plywood without cavity test 3 - plywood with cavity Figure 14. Thermal exposure one storey above the fire source measured with plate thermometer directed outwards. In addition to the temperature, the heat flux was measured with a Schmidt Boelter total heat flux meter at the centre of the fictitious window (gauge HF1 shown in figure 4). The measured heat fluxes are shown in figures 15 and 16. In figure 16, the mean heat flux for each minute is shown. Heat flux (kw/m 2 ) Test 1 - inert facade Test 2 - plywood without cavity Test 3 - plywood with cavity Figure 15. Heat flux measured one storey above the fire source.

27 Test 1 - inert facade Test 2 - plywood without cavity Test 3 - plywood with cavity 6 Heat flux (kw/m 2 ) Figure 16. Heat flux (mean valued over one minute) measured one storey above the fire source. 4.6 Thermal exposure two storeys above the combustion chamber In the centre of the fictitious window two storeys above the combustion chamber the temperature exposure towards the window was measured with a plate thermometer, i.e. 4,8 m above the upper edge of the opening to the combustion chamber, plate thermometer PT6 shown in figure 4. The measured temperatures are shown in figure 17. At this height there is a clear difference between the tests. The ventilation cavity used in Test 3 has a significant effect on the heat exposure to the fictitious window two stories above the fire room. After 15 minutes the temperature is over C in Test 3. When comparing Test 1 and Test 2, i.e. the inert façade and the plywood cladding without cavity, the difference between these tests is relatively small. The façade with plywood cladding have a faster temperature rise between 5 and 7 minutes, after which the temperature stabilizes between -25 C. The inert façade has a slower temperature rise, but it reaches almost as high in temperature.

28 28 7 Test 1 - inert facade Test 2 - plywood without cavity Test 3 - plywood with cavity Figure 17. Thermal exposure two storeys above the fire source measured with plate thermometer directed outwards. 4.7 Surface temperature The surface temperature was measured by.5 mm wire diameter thermocouples type K with a Quick-Tip as described above. The Quick-Tip of the thermocouple was forced into the surface, measuring the temperature of the surface during the test. A total of 19 thermocouples, C1-C19, was used on the fire exposed surface of the façade. In the third test, with a cavity behind the plywood cladding, an additional 19 thermocouples, C21- C39, were positioned on the cavity side of the plywood, opposite C1-C19. Thermocouple C21 is positioned opposite C1, thermocouple C22 opposed to C2, and so on. The positions of thermocouple C1-C19 are shown in figure Temperature 1 mm above the combustion chamber The measured temperatures on the surface at a level 1 mm above the edge of the opening of the combustion chamber are presented in figures 18 2, one figure for each test. The results clearly show that the fire was more severe on the left side.

29 29 7 Test 1 - inert facade C1 C2 C3 C Figure 18. Temperature on the surface during Test 1, 1 mm above the combustion chamber C1 C2 C3 C4 Test 2 - plywood without cavity Figure 19. Temperature on the surface during Test 2, 1 mm above the combustion chamber.

30 3 9 8 Test 3 - plywood with cavity 7 C1 C2 C3 C Figure 2. Temperature on the surface during Test 3, 1 mm above the combustion chamber Test 3 - plywood with cavity Surface temperature in the cavity C21 C22 C23 C Figure 21. Temperature on the surface of the plywood in the cavity 1 mm above the combustion chamber. The temperature was measured on the surface of the plywood in the cavity during Test 3. The results from these measurements are shown in figure 21 above. Unlike the temperatures measured on the outward surface, which decreases at the end of the tests, the temperature increases rapidly.

31 31 Figure 22 display the mean temperature of all thermocouples at this level presented for each test, as well as the mean surface temperature on the plywood surface in the cavity. As the figure shows there is a substantial difference on the temperature level between the combustible cladding and the inert façade. 8 Mean surface temperature in each test 7 Mean test 1 Mean test 2 Mean test 3 Mean test 3 - cavity Figure 22. Mean surface temperature at a level 1 mm above the upper edge of the combustion chamber Temperature 27 mm above the combustion chamber The measured temperatures on the surface at a level 27 mm above the edge of the opening of the combustion chamber are presented in figures 23 25, one figure for each test. The results clearly show that the fire was more severe on the left side.

32 32 45 Test 1 - inert facade C5 C6 C7 C Figure 23. Temperature on the surface during Test 1, 27 mm above the combustion chamber. 8 Test 2 - plywood without cavity 7 C5 C6 C7 C Figure 24. Temperature on the surface during Test 2, 27 mm above the combustion chamber.

33 33 8 Test 3 - plywood with cavity 7 C5 C6 C7 C Figure 25. Temperature on the surface during Test 3, 27 mm above the combustion chamber. The temperature was measured on the surface of the plywood in the cavity during Test 3. The results from these measurements are shown in figure 26. Unlike the temperatures measured on the outward surface, which decreases at the end of the tests, the temperature increases rapidly Test 3 - plywood with cavity Surface temperature of plywood in cavity C25 C26 C27 C Figure 26. Temperature on the surface of the plywood in the cavity 27 mm above the combustion chamber.

34 34 In figure 27 the mean temperature of all thermocouples at this level presented for each test, as well as the mean surface temperature on the plywood surface in the cavity. As the figure shows there is a substantial difference on the temperature level between the combustible cladding and the inert façade. 7 Mean surface temperature in each test Mean test 1 Mean test 2 Mean test 3 Mean test 3 - cavity Figure 27. Mean surface temperature at a level 27 mm above the upper edge of the combustion chamber Temperature 345 mm above the combustion chamber The measured temperatures on the surface at a level 345 mm above the edge of the opening of the combustion chamber are presented in figures 28 3, one figure for each test. The results clearly show that the fire was more severe on the left side.

35 35 35 Test 1 - inert facade C9 C1 C Figure 28. Temperature on the surface during Test 1, 345 mm above the combustion chamber. 8 Test 2 - plywood without cavity 7 C9 C1 C Figure 29. Temperature on the surface during Test 2, 345 mm above the combustion chamber.

36 36 8 Test 3 - plywood with cavity 7 C9 C1 C Figure 3. Temperature on the surface during Test 3, 345 mm above the combustion chamber. The temperature was measured on the surface of the plywood in the cavity during Test 3. The results from these measurements are shown in figure 31. At this level the temperature in the surface of the plywood in the cavity do not show the same increasing temperatures at the end of the test Test 3 - plywood with cavity Surface temperature of plywood in cavity C29 C3 C Figure 31. Temperature on the surface of the plywood in the cavity 345 mm above the combustion chamber.

37 37 In figure 32 the mean temperature of all thermocouples at this level is presented for each test, as well as the mean surface temperature on the plywood surface in the cavity. As the figure shows there is a substantial difference on the temperature level between the combustible cladding and the inert façade. It can also be noted that the mean surface temperature in Test 3 is approximately the same on the outer surface as on the surface in the cavity at the end of the test. 8 7 Mean surface temperature in each test Mean test 1 Mean test 2 Mean test 3 Mean test 3 - cavity Figure 32. Mean surface temperature at a level 345 mm above the upper edge of the combustion chamber Temperature 4 mm above the combustion chamber The measured temperatures on the surface at a level 4 mm above the edge of the opening of the combustion chamber are presented in figures 33 35, one figure for each test. The results clearly show that the fire was more severe on the left side in Test 2 and Test 3. In Test 1, however, the temperature readings show a more centrally exposure at this level.

38 C12 C13 C14 C15 Test 1 - inert facade Figure 33. Temperature on the surface during Test 1, 4 mm above the combustion chamber. 7 Test 2 - plywood without cavity C12 C13 C14 C Figure 34. Temperature on the surface during Test 2, 4 mm above the combustion chamber.

39 39 7 Test 3 - plywood with cavity C12 C13 C14 C Figure 35. Temperature on the surface during Test 3, 4 mm above the combustion chamber. The temperature was measured on the surface of the plywood in the cavity during Test 3. The results from these measurements are shown in figure 36. At this level the temperature in the surface of the plywood in the cavity is continuously increasing, and accelerating at the end of the test Test 3 - plywood with cavity Surface temperature of plywood in cavity C32 C33 C34 C Figure 36. Temperature on the surface of the plywood in the cavity 4 mm above the combustion chamber.

40 4 In figure 37 the mean temperature of all thermocouples at this level is presented for each test, as well as the mean surface temperature on the plywood surface in the cavity. As the figure shows there is a substantial difference on the temperature level between the combustible cladding and the inert façade. Mean surface temperature in each test Mean test 1 Mean test 2 Mean test 3 Mean test 3 - cavity Figure 37. Mean surface temperature at a level 4 mm above the upper edge of the combustion chamber Temperature 5 mm above the combustion chamber The measured temperatures on the surface at a level 5 mm above the edge of the opening of the combustion chamber are presented in figures 38 4, one figure for each test. The results clearly show that the fire was more severe on the left side of the specimen in all three tests.

41 C16 C17 C18 C19 Test 1 - inert facade Figure 38. Temperature on the surface during Test 1, 5 mm above the combustion chamber. Test 2 - plywood without cavity C16 C17 C18 C Figure 39. Temperature on the surface during Test 2, 5 mm above the combustion chamber.

42 42 45 Test 3 - plywood with cavity C16 C17 C18 C Figure 4. Temperature on the surface during Test 3, 5 mm above the combustion chamber. The temperature was measured on the surface of the plywood in the cavity during Test 3. The results from these measurements are shown in figure 41. At this level the temperature in the surface of the plywood in the cavity is continuously increasing, but decreasing at the end of the test Test 3 - plywood with cavity Surface temperature of plywood in cavity C36 C37 C38 C Figure 41. Temperature on the surface of the plywood in the cavity 5 mm above the combustion chamber.

43 43 In figure 42 the mean temperature of all thermocouples at this level is presented for each test, as well as the mean surface temperature on the plywood surface in the cavity. As the figure shows there is a substantial difference on the temperature level between the combustible cladding and the inert façade. Mean surface temperature in each test Mean test 1 Mean test 2 Mean test 3 Mean test 3 - cavity Figure 42. Mean surface temperature at a level 5 mm above the upper edge of the combustion chamber. 4.8 Plume temperature at different heights The temperature was also measured mm and mm from the surface, i.e. in the plume, with.5 mm thermocouples wires type K with welded tip. The thermocouples were fixed on long screws that were fixed to the façade surface. The gas temperature in the cavity in Test 3 was also measured with the same type of thermocouples, and the measurements were made in the centre of the cavity, i.e. 1 mm from the surface. Details about the positions are explained in the text following figure Plume temperature 1 mm above the combustion chamber Measurements mm from the surface The measured temperature mm from the surface at a level 1 mm above the edge of the opening of the combustion chamber is presented in figures 43 45, one figure for each test. The results clearly show that the fire was more severe on the left side of the specimen in all three tests.

44 Test 1 - inert facade 7 A1 A Figure 43. Temperature in the plume mm from the surface during Test 1, 1 mm above the combustion chamber A1 A2 Test 2 - plywood without cavity Figure 44. Temperature in the plume mm from the surface during Test 2, 1 mm above the combustion chamber.

45 45 9 Test 3 - plywood with cavity 8 7 A1 A Figure 45. Temperature in the plume mm from the surface during Test 3, 1 mm above the combustion chamber. In figure 46 is the mean temperature of the two thermocouples mm from the surface shown for each test. The results are similar to the temperatures measured on the surface at the same level, figure 22, i.e. the lowest temperatures in Test 1, and highest in Test Mean temperature mm from surface Mean test 1 Mean test 2 Mean test Figure 46. Mean plume temperature mm from the surface at a level 1 mm above the upper edge of the combustion chamber.

46 Measurements mm from the surface The temperature was also measured mm from the surface, but only in Test 1, i.e. the inert façade. The measured temperature is shown in figure 47. A mean temperature (mean of two measurements) is presented in figure 48 for the measurement of temperature mm as well as mm from the surface. 8 7 Test 1 - inert facade B1 B Figure 47. Temperature in the air mm from the surface during Test 1, 1 mm above the combustion chamber. 8 7 Mean mm from surface Mean mm from surface Test 1 - inert facade Figure 48. Mean temperature during Test 1, mm and mm from the surface, measured 1 mm above the fire source.

47 Measurements in the cavity The temperature was also measured in the cavity in Test 3, centrally between the lightweight concrete backing and the plywood. The test results at a level 1 mm above the fire source are shown in figure 49. D1 D2 Test 3 - plywood with cavity Temperature in cavity Figure 49. Temperature in the cavity 1 mm above the fire source during Test Air temperature 27 mm above the combustion chamber Measurements mm from the surface The measured temperature mm from the surface at a level 27 mm above the edge of the opening of the combustion chamber is presented in figures 5 52, one figure for each test. The results clearly show that the fire was more severe on the left side of the specimen in all three tests.

48 48 Test 1 - inert facade A3 A Figure 5. Temperature in the air mm from the surface during Test 1, 27 mm above the combustion chamber. 8 Test 2 - plywood without cavity 7 A3 A Figure 51. Temperature in the plume mm from the surface during Test 2, 27 mm above the combustion chamber.

49 Test 3 - plywood with cavity 7 A3 A Figure 52. Temperature in the air mm from the surface during Test 3, 27 mm above the combustion chamber. In figure 53 is the mean temperature of the two thermocouples mm from the surface shown for each test. The results are similar to the temperatures measured on the surface at the same level, figure 27, i.e. the lowest temperatures in Test 1, and highest in Test 2. 7 Mean temperature mm from surface Mean test 1 Mean test 2 Mean test Figure 53. Mean plume temperature mm from the surface at a level 27 mm above the upper edge of the combustion chamber.

50 Measurements mm from the surface The temperature was also measured mm from the surface, but only in Test 1, i.e. the inert façade. The measured temperature is shown in figure 54. A mean temperature (mean of two measurements) is presented in figure 55 for the measurement of temperature mm as well as mm from the surface. 45 Test 1 - inert facade 35 B3 B Figure 54. Temperature in the plume mm from the surface during Test 1, 27 mm above the combustion chamber Mean mm from surface Mean mm from surface Test 1 - inert facade Figure 55. Mean temperature during Test 1 mm and mm from the surface measured 27 mm above the fire source.

51 Measurements in the cavity The temperature was also measured in the cavity in Test 3, centrally between the lightweight concrete backing and the plywood. The test results at a level 27 mm above the fire source are shown in figure D3 D4 Test 3 - plywood with cavity Temperature in cavity Figure 56. Temperature in the cavity 27 mm above the fire source during Test Air temperature 345 mm above fuel source Measurements mm from the surface The measured temperature mm from the surface at a level 345 mm above the edge of the opening of the combustion chamber is presented in figures 57 59, one figure for each test. Also on this height the results show that the fire was more severe on the left side of the specimen in all three tests.

52 52 45 Test 1 - inert facade A5 A Figure 57. Temperature in the air mm from the surface during Test 1, 345 mm above the combustion chamber. 8 Test 2 - plywood without cavity 7 A5 A Figure 58. Temperature in the air mm from the surface during Test 2, 345 mm above the combustion chamber.

53 Test 3 - plywood with cavity 7 A5 A Figure 59. Temperature in the air mm from the surface during Test 3, 345 mm above the combustion chamber. In figure 6 is the mean temperature of the two thermocouples mm from the surface shown for each test. The results are similar to the temperatures measured on the surface at the same level, figure 32, i.e. the lowest temperatures in Test 1, and approximately the same temperature in Test 2 and Test 3 except at the end of the test where Test 3 show higher temperature.. 7 Mean temperature mm from surface Mean test 1 Mean test 2 Mean test Figure 6. Mean air temperature mm from the surface at a level 345 mm above the upper edge of the combustion chamber.

WP2 Fire test for toxicity of fire effluents

WP2 Fire test for toxicity of fire effluents Pagina 3 di 89 TRA SFEU VTT 22.6.2009 v.2 WP2 Fire test for toxicity of fire effluents Task 2.1.2 Development of small-scale test method for fire effluents Step 1: Use of modeling Plans according to DoW:

More information

SBI Testing Programme

SBI Testing Programme Reaction to fire behaviour SBI Testing Programme Single Burning Item (pren13823 final draft September ) Mounting and Fixing conditions for EPS boards Xavier ALLANIC KNAUF CRD Date of Publication : 24/2/4

More information

Available online at ScienceDirect

Available online at  ScienceDirect Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 62 ( 203 ) 29 225 The 9 th Asia-Oceania Symposium on Fire Science and Technology An experimental study on buoyant spilled thermal

More information

Test Report No Insulguard Fire Resistance Enclosure. Insulguard Australia Bentleigh, Victoria

Test Report No Insulguard Fire Resistance Enclosure. Insulguard Australia Bentleigh, Victoria Test Report No. 4548 Product: Insulguard Fire Resistance Enclosure Client: Insulguard Australia Bentleigh, Victoria Nature of tests: Limited testing to: AS/NZS 3000:2007 - Wiring rules AS/NZS 60695.11.5:2005

More information

REPORT INVESTIGATION OF 3M CLEAN AND STRIP DISKS IN EXPLOSIVE ATMOSPHERES. Client: 3M Norge A/S. Authors: Bjørnar A. Johnsen Geir H.

REPORT INVESTIGATION OF 3M CLEAN AND STRIP DISKS IN EXPLOSIVE ATMOSPHERES. Client: 3M Norge A/S. Authors: Bjørnar A. Johnsen Geir H. REPORT INVESTIGATION OF 3M CLEAN AND STRIP DISKS IN EXPLOSIVE ATMOSPHERES Client: 3M Norge A/S Authors: Bjørnar A. Johnsen Geir H. Pedersen Bergen, June 2005 Ref. no.: GexCon-05-A440400-1 Rev. no.: 01

More information

Study on Fire Plume in Large Spaces Using Ground Heating

Study on Fire Plume in Large Spaces Using Ground Heating Available online at www.sciencedirect.com Procedia Engineering 11 (2011) 226 232 The 5 th Conference on Performance-based Fire and Fire Protection Engineering Study on Fire Plume in Large Spaces Using

More information

Users Guide for the Vertical Bunsen Burner Test for Cabin and Cargo Compartment Materials FAA Handbook Chapter 2

Users Guide for the Vertical Bunsen Burner Test for Cabin and Cargo Compartment Materials FAA Handbook Chapter 2 Issue 1.1: May 2010 REF: FAA Chapter 2 Bunsen Burner Test Manual.doc Users Guide for the Vertical Bunsen Burner Test for Cabin and Cargo Compartment Materials FAA Handbook Chapter 2 Issued by: Fire Testing

More information

Experimental Study of Hydrogen Release Accidents in a Vehicle Garage

Experimental Study of Hydrogen Release Accidents in a Vehicle Garage Experimental Study of Hydrogen Release Accidents in a Vehicle Garage Erik Merilo Mark Groethe James Colton Seiki Chiba Poulter Laboratory SRI International 3rd International Conference on Hydrogen Safety

More information

Numerical Modelling of Unchannelled Balcony Spill Plumes using FDS 5

Numerical Modelling of Unchannelled Balcony Spill Plumes using FDS 5 Numerical Modelling of Unchannelled Balcony Spill Plumes using FDS 5 By Ho Yong Tiong Supervised by Dr Michael Spearpoint Associate Professor Charles Fleischmann Fire Engineering Research February 2012

More information

REPORT NUMBER: G COQ-004 rev 1 ORIGINAL ISSUE DATE: May 18, 2010 REVISION DATE: June 7, 2010

REPORT NUMBER: G COQ-004 rev 1 ORIGINAL ISSUE DATE: May 18, 2010 REVISION DATE: June 7, 2010 TEST REPORT REPORT NUMBER: G100017878COQ-004 rev 1 ORIGINAL ISSUE DATE: May 18, 2010 REVISION DATE: June 7, 2010 EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C.

More information

- Comparison of Long and Wide Enclosures

- Comparison of Long and Wide Enclosures Fires in Enclosures with Single Ventilation Openings - Comparison of Long and Wide Enclosures IAN R THOMAS Centre for Environmental Safety and Risk Engineering Victoria University of Technology PO Box

More information

Experiment 1 Introduction to Some Laboratory Measurements

Experiment 1 Introduction to Some Laboratory Measurements Experiment 1 Introduction to Some Laboratory Measurements Introduction In this experiment you will familiarize yourself with the English & metric systems of measurement, weigh with a centigram balance,

More information

Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations

Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations Grzegorz Kubicki, Ph.D. Department of Environmental Engineering, Warsaw University of Technology

More information

TECHNICAL BULLETIN CRYOGENIC APPLICATION SERVICES. website:

TECHNICAL BULLETIN CRYOGENIC APPLICATION SERVICES.  website: TECHNICAL BULLETIN SERVICES website: email: www.pipingtech.com info@pipingtech.com copyright 2009 Piping Technology & Products, Inc. SERVICES Objective TECHNICAL BULLETIN To determine the amount of ice

More information

Barrier Development and Evaluation Methodology. D.S. Musgrave 1 1 Thermal Visions, Inc., Granville, USA

Barrier Development and Evaluation Methodology. D.S. Musgrave 1 1 Thermal Visions, Inc., Granville, USA Barrier Development and Evaluation Methodology D.S. Musgrave 1 1 Thermal Visions, Inc., Granville, USA 1. Introduction: Vacuum insulation is now a rapidly expanding market and technical advances are being

More information

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage William M. Pitts, Jiann C. Yang, Kuldeep Prasad, and Marco Fernandez National Institute of Standards

More information

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars.

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars. Simply a question of better measurement SCHMIDT Flow Sensor SS 20.261 The cost-effective alternative in pressurised systems up to 10 bars. Compressed air technology Industrial processes A cost analysis

More information

PTB Ex PT Scheme. Procedure Instruction of program Explosion Pressure - Test Round 2017

PTB Ex PT Scheme. Procedure Instruction of program Explosion Pressure - Test Round 2017 Procedure Instruction of program Explosion Pressure - Test Round 2017 Content 1 General Performance... 2 2 Measurand / Characteristic of interest... 2 3 Test Item and Configurations... 2 3.1 Components...

More information

Experimental Analysis of Inclined Narrow Plate-Fins Heat Sink under Natural Convection

Experimental Analysis of Inclined Narrow Plate-Fins Heat Sink under Natural Convection Experimental Analysis of Inclined Narrow Plate-Fins Heat Sink under Natural Convection A.A.WALUNJ 1, D.D.PALANDE 2 1,2 PG student, Mechanical Department, MCOERC, Nashik Abstract Steady state natural convection

More information

ACCUMULATION OF HYDROGEN RELEASED INTO A VENTED ENCLOSURE - EXPERIMENTAL RESULTS

ACCUMULATION OF HYDROGEN RELEASED INTO A VENTED ENCLOSURE - EXPERIMENTAL RESULTS ACCUMULATION OF HYDROGEN RELEASED INTO A VENTED ENCLOSURE - EXPERIMENTAL RESULTS Hooker, P. 1, Willoughby, D. 2, Hall, J. 3 and Hoyes, J. 4 1 Major Hazards Unit, HSL, Harpur Hill, Buxton, SK17 9JN, U.K,

More information

INTERACTION BETWEEN WIND-DRIVEN AND BUOYANCY-DRIVEN NATURAL VENTILATION Bo Wang, Foster and Partners, London, UK

INTERACTION BETWEEN WIND-DRIVEN AND BUOYANCY-DRIVEN NATURAL VENTILATION Bo Wang, Foster and Partners, London, UK INTERACTION BETWEEN WIND-DRIVEN AND BUOYANCY-DRIVEN NATURAL VENTILATION Bo Wang, Foster and Partners, London, UK ABSTRACT Ventilation stacks are becoming increasingly common in the design of naturally

More information

An Investigative and Synoptic Review on Helium Liquefaction Using a Commercial 4 K Gifford- McMahon Cryocooler

An Investigative and Synoptic Review on Helium Liquefaction Using a Commercial 4 K Gifford- McMahon Cryocooler An Investigative and Synoptic Review on Helium Liquefaction Using a Commercial 4 K Gifford- McMahon Cryocooler Mahesh N 1, S A Mohan Krishna 2 1 PG Student, Vidyavardhaka College of Engineering, Mysore,

More information

MIL-STD-883G METHOD

MIL-STD-883G METHOD STEADY-STATE LIFE 1. PURPOSE. The steady-state life test is performed for the purpose of demonstrating the quality or reliability of devices subjected to the specified conditions over an extended time

More information

Sprinkler Protection for Cloud Ceilings. SUPDET 2013 Jason Floyd, Ph.D. 28 February 2013

Sprinkler Protection for Cloud Ceilings. SUPDET 2013 Jason Floyd, Ph.D. 28 February 2013 Sprinkler Protection for Cloud Ceilings SUPDET 2013 Jason Floyd, Ph.D. 28 February 2013 Background Cloud ceilings are a popular architectural feature Lack of clear guidance in the code for sprinkler installation

More information

The ongoing experimental programs at IRSN on

The ongoing experimental programs at IRSN on 2 1 Recent results from experimental research on fire J.-M. SUCH (IRSN) C. CASSELMAN (IRSN) L. RIGOLLET (IRSN) H. PRETREL (IRSN) L. AUDOUIN (IRSN) The ongoing experimental programs at IRSN on organic compound

More information

Experimental determination of deflagration explosion characteristics of methane air mixture and their verification by advanced numerical simulation

Experimental determination of deflagration explosion characteristics of methane air mixture and their verification by advanced numerical simulation Structures Under Shock and Impact XII 169 Experimental determination of deflagration explosion characteristics of methane air mixture and their verification by advanced numerical simulation M. Mynarz,

More information

Effect of airflow direction on human perception of draught

Effect of airflow direction on human perception of draught Effect of airflow direction on human perception of draught J. Toftum, G. Zhou, A. Melikov Laboratory of Indoor Environment and Energy Department of Energy Engineering Technical University of Denmark Abstract

More information

F13.11 PARALLEL HINGES F13 PROJECT-OUT WINDOWS AND TOP HUNG WINDOWS

F13.11 PARALLEL HINGES F13 PROJECT-OUT WINDOWS AND TOP HUNG WINDOWS F13 PROJECT-OUT WINDOWS AND TOP HUNG WINDOWS F13.11 01.06.2018 Waregemstraat 5-9870 Zulte - Belgium - T. +32 9 388 88 81 - F. +32 9 388 88 21 - commercial@sobinco.com - www.sobinco.com CONTENTS 1. General...F13.11.03

More information

MITIGATE GAS COMBUSTION IN CASE OF INTERNAL ARC

MITIGATE GAS COMBUSTION IN CASE OF INTERNAL ARC MITIGATE GAS COMBUSTION IN CASE OF INTERNAL ARC Jérôme DOUCHIN Yann CRESSAULT Raphael Danjoux Schneider Electric France Toulouse University France FLIR France Jerome.douchin@ cressault@laplace.univ-tlse.fr

More information

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12 LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/ This experiment will introduce you to the kinetic properties of low-pressure gases. You will make observations on the rates with which selected

More information

STANDARD PROCEDURE OF A TIGHTNESS TEST OF A SOLAR COLLECTOR BOX. (EUROSUN 2000 SOLAR CONGRESS)

STANDARD PROCEDURE OF A TIGHTNESS TEST OF A SOLAR COLLECTOR BOX. (EUROSUN 2000 SOLAR CONGRESS) STANDARD PROCEDURE OF A TIGHTNESS TEST OF A SOLAR COLLECTOR BOX. (EUROSUN 2000 SOLAR CONGRESS) Ole Holck and Svend Svendsen Department of Buildings and Energy, Technical University of Denmark Building

More information

ANALYSIS OF HEAT TRANSFER THROUGH EXTERNAL FINS USING CFD TOOL

ANALYSIS OF HEAT TRANSFER THROUGH EXTERNAL FINS USING CFD TOOL ANALYSIS OF HEAT TRANSFER THROUGH EXTERNAL FINS USING CFD TOOL B. Usha Rani 1 and M.E Thermal 2 1,2 Asst.Professor, Dadi Institute of Engineering and Technology, India Abstract-The rate of heat transfer

More information

Ventilation of Small Multispan Greenhouse in Relation to the Window Openings Calculated with CFD

Ventilation of Small Multispan Greenhouse in Relation to the Window Openings Calculated with CFD Ventilation of Small Multispan Greenhouse in Relation to the Window Openings Calculated with CFD J.B. Campen Plant Research International Wageningen The Netherlands Keywords: greenhouse design, wind direction,

More information

Comparison of Large-Scale Vented Deflagration Tests to CFD Simulations for Partially Congested Enclosures

Comparison of Large-Scale Vented Deflagration Tests to CFD Simulations for Partially Congested Enclosures Comparison of Large-Scale Vented Deflagration Tests to CFD Simulations for Partially Congested Enclosures Peter A. Diakow, Project II Consultant, Baker Engineering and Risk Consultants, Inc. J. Kelly Thomas,

More information

U S F O S B u o y a n c y And Hydrodynamic M a s s

U S F O S B u o y a n c y And Hydrodynamic M a s s 1 U S F O S B u o y a n c y And Hydrodynamic M a s s 2 CONTENTS: 1 INTRODUCTION... 3 2 ACCURACY LEVELS... 3 2.1 LEVEL-0... 3 2.2 LEVEL-1... 3 2.3 PANEL MODEL... 3 3 EX 1. SINGLE PIPE. NON FLOODED... 4

More information

HYDROGEN FAST FILLING TO A TYPE IV TANK DEVELOPED FOR MOTORCYCLES

HYDROGEN FAST FILLING TO A TYPE IV TANK DEVELOPED FOR MOTORCYCLES HYDROGEN FAST FILLING TO A TYPE IV TANK DEVELOPED FOR MOTORCYCLES Yamada, E. 1, Hiraki, W. 2, and Muramatsu, H. 3 1 FC-EV Research Division, Japan Automobile Research Institute, 1328-23 Takaheta, Osaka,

More information

A computational study on structural barrier to vertical spread of window spill plume along building exterior façade under external wind

A computational study on structural barrier to vertical spread of window spill plume along building exterior façade under external wind 2nd International Conference on Information, Electronics and Computer (ICIEAC 2014 A computational study on structural barrier to vertical spread of window spill plume along building exterior façade under

More information

REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION

REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION Mads Mysen* 1, Axel Cablé 1, Peter G. Schild 1, and Kari Thunshelle 1 1 SINTEF Building and Infrastructure Forskningsveien

More information

APPLICATION NOTES DELOMATIC 4, DM-4 GAS

APPLICATION NOTES DELOMATIC 4, DM-4 GAS APPLICATION NOTES DELOMATIC 4, DM-4 GAS Emission control Lambda sensor p/t regulation Combustion chamber temperature regulation Emission control configuration Emission control curve Document no.: 4189340653C

More information

What is air track? 1 Introduction

What is air track? 1 Introduction What is air track? 1 Introduction The SAHF model was thought up by Australian Shan Raffel in the early 2000 s. After much debate with colleagues, and under the influence of American Ed Hartin the model

More information

Australian Wool Testing Authority Ltd - trading as AWTA Product Testing A.B.N

Australian Wool Testing Authority Ltd - trading as AWTA Product Testing A.B.N A.B.N 43 6 14 16 1st Floor, 191 Racecourse Road, Flemington, Victoria 331 P.O Box 24, North Melbourne, Victoria 351 Phone (3) 9371 24 Fax (3) 9371 2499 Test Number : 14-762 Issue Date : 5/11/214 Port Melbourne

More information

EFFECTS OF SIDEWALL OPENINGS ON THE WIND LOADS ON PIPE-FRAMED GREENHOUSES

EFFECTS OF SIDEWALL OPENINGS ON THE WIND LOADS ON PIPE-FRAMED GREENHOUSES The Seventh Asia-Pacific Conference on Wind Engineering, November 8-12, 29, Taipei, Taiwan EFFECTS OF SIDEWALL OPENINGS ON THE WIND LOADS ON PIPE-FRAMED GREENHOUSES Yasushi Uematsu 1, Koichi Nakahara 2,

More information

EXPERIMENTAL STUDY OF WIND PRESSURES ON IRREGULAR- PLAN SHAPE BUILDINGS

EXPERIMENTAL STUDY OF WIND PRESSURES ON IRREGULAR- PLAN SHAPE BUILDINGS BBAA VI International Colloquium on: Bluff Bodies Aerodynamics & Applications Milano, Italy, July, 2-24 8 EXPERIMENTAL STUDY OF WIND PRESSURES ON IRREGULAR- PLAN SHAPE BUILDINGS J. A. Amin and A. K. Ahuja

More information

CONTENTS 1. INTRODUCTION DESCRIPTION OF TEST SAMPLE TEST RIG GENERAL ARRANGEMENT TEST SEQUENCE...7

CONTENTS 1. INTRODUCTION DESCRIPTION OF TEST SAMPLE TEST RIG GENERAL ARRANGEMENT TEST SEQUENCE...7 Page 2 of 22 CONTENTS 1. INTRODUCTION...3 2. DESCRIPTION OF TEST SAMPLE...4 3. TEST RIG GENERAL ARRANGEMENT...6 4. TEST SEQUENCE...7 5. SUMMARY AND CLASSIFICATION OF TEST RESULTS...8 6. WATERTIGHTNESS

More information

Internal Arc Simulation in MV/LV Substations. Charles BESNARD 8 11 June 2009

Internal Arc Simulation in MV/LV Substations. Charles BESNARD 8 11 June 2009 Internal Arc Simulation in MV/LV Substations Charles BESNARD 8 11 June 2009 The Internal Arc Fault The fault A highly energetic and destructive arc (10, 20, 40 MJ!) The effects and the human risks Overpressures

More information

CRYSTALLIZATION FOULING IN PACKED COLUMNS

CRYSTALLIZATION FOULING IN PACKED COLUMNS CRYSTALLIZATION FOULING IN PACKED COLUMNS D. Großerichter and J. Stichlmair Lehrstuhl für Fluidverfahrenstechnik, Technische Universität München, Munich, Germany ABSTRACT Fouling due to crystallization

More information

The VINNOVA water mist research project: A description of the 250 m 3 machinery space tests

The VINNOVA water mist research project: A description of the 250 m 3 machinery space tests Magnus Arvidson Tommy Hertzberg The VINNOVA water mist research project: A description of the 250 m 3 machinery space tests SP Swedish National Testing and Research Institute SP Fire Technology SP REPORT

More information

WIND CLIPPER KTS ILLUM SCALE INC DEC CLIPPER WIND SYSTEM

WIND CLIPPER KTS ILLUM SCALE INC DEC CLIPPER WIND SYSTEM CLIPPER WIND KTS ILLUM SCALE DEC INC CLIPPER WIND SYSTEM TABLE OF CONTENTS INTRODUCTION PRE-TEST OF INSTRUMENT INSTALLING THE MASTHEAD SENSOR UNIT INSTALLING THE DISPLAY NORMAL OPERATION CHANGING THE

More information

ICHEME SYMPOSIUM SERIES NO. 144

ICHEME SYMPOSIUM SERIES NO. 144 EXPLOSION VENTING - THE PREDICTED EFFECTS OF INERTIA By Steve Cooper - Stuvex Safety Systems Limited Explosion venting is an established and well used method of primary explosion protection within industry.

More information

Numerical Investigation of Air Bubbles Evolution and Coalescence from Submerged Orifices Based on OpenFOAM

Numerical Investigation of Air Bubbles Evolution and Coalescence from Submerged Orifices Based on OpenFOAM Numerical Investigation of Air Bubbles Evolution and Coalescence from Submerged Orifices Based on OpenFOAM Pan Feng, He Ying, Li-zhong Mu 2018-7-6 Dalian University of Technology, China Outline Background

More information

FIRE MODELLING OF ENERGY-EFFICIENT APARTMENT BUILDINGS Consideration of air-tightness and mechanical ventilation

FIRE MODELLING OF ENERGY-EFFICIENT APARTMENT BUILDINGS Consideration of air-tightness and mechanical ventilation FIRE MODELLING OF ENERGY-EFFICIENT APARTMENT BUILDINGS Consideration of air-tightness and mechanical ventilation Simo Hostikka, Rahul Kallada Janardhan, Umar Riaz, and Topi Sikanen 1 Aalto University simo.hostikka@aalto.fi

More information

Smoke and heat Ventilator Testing

Smoke and heat Ventilator Testing Instituut vir Termodinamika en Meganika Institute for Thermodynamics and Mechanics Smoke and heat Ventilator Testing by CJ Zietsman and GR Smith November 2005 Departement Meganiese Ingenieurswese Privaat

More information

TECHNICAL BENEFITS OF CJS / RAISE HSP. Technical Advantages

TECHNICAL BENEFITS OF CJS / RAISE HSP. Technical Advantages TECHNICAL BENEFITS OF CJS / RAISE HSP Technical Advantages The HSP is designed for low- to mid- volume applications at flow rates of 1 cubic meter to 30 c. m per day. The benefits are in the details. The

More information

Rotary air valves used for material feed and explosion protection are required to meet the criteria of NFPA 69 (2014)

Rotary air valves used for material feed and explosion protection are required to meet the criteria of NFPA 69 (2014) Rotary air valves used for material feed and explosion protection are required to meet the criteria of NFPA 69 (2014) 12.2.4.2. 12.2.4.2 rotary valve design criteria (close clearance) 12.2.4.3 THE DESIGN

More information

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS M. Jovalekic 1*, D. Vukovic 1 and S. Tenbohlen 1 1 Institute of Power Transmission and High Voltage Technology (IEH) University

More information

Visual Observation of Nucleate Boiling and Sliding Phenomena of Boiling Bubbles on a Horizontal Tube Heater

Visual Observation of Nucleate Boiling and Sliding Phenomena of Boiling Bubbles on a Horizontal Tube Heater Proceedings of the 2 nd World Congress on Mechanical, Chemical, and Material Engineering (MCM'16) Budapest, Hungary August 22 23, 216 Paper No. HTFF 146 DOI:.11159/htff16.146 Visual Observation of Nucleate

More information

Welding. Module

Welding. Module Welding Module 19.2.4 Module 19.2.4 Describe the oxy fuel gas welding process. Process: setting up the equipment, leak testing, oxy-fuel gas mixing, flame adjustment (including oxidizing, neutral and carburizing

More information

INF.41/Add.1/Rev.1. Economic Commission for Europe Inland Transport Committee

INF.41/Add.1/Rev.1. Economic Commission for Europe Inland Transport Committee Economic Commission for Europe Inland Transport Committee Working Party on the Transport of Dangerous Goods INF.41/Add.1/Rev.1 Joint Meeting of the RID Committee of Experts and the Working Party on the

More information

TESTING APPLICATION STANDARD (TAS)

TESTING APPLICATION STANDARD (TAS) TESTING APPLICATION STANDARD (TAS) No. 00(A)-9 TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE AND/OR INCREASED WINDSPEED RESISTANCE OF SOFFIT VENTILATION STRIP AND CONTINUOUS OR INTERMITTENT VENTILATION

More information

Testing of Active Flow Control actuators at harsh environment

Testing of Active Flow Control actuators at harsh environment Testing of Active Flow Control actuators at harsh environment Ionut BRINZA (INCAS) 6 th CEAS CONFERENCE 16-20 October 2017 Bucharest ROMANIA Introduction Results of the harsh environment tests Conclusions

More information

NT FIRE 049 COMBUSTIBLE PRODUCTS: COMMODITY CLASSIFICATION FIRE TEST PROCEDURE TABLE OF CONTENTS NORDTEST METHOD NT FIRE (16)

NT FIRE 049 COMBUSTIBLE PRODUCTS: COMMODITY CLASSIFICATION FIRE TEST PROCEDURE TABLE OF CONTENTS NORDTEST METHOD NT FIRE (16) NORDTEST METHOD NT FIRE 049 1 COMBUSTIBLE PRODUCTS: COMMODITY CLASSIFICATION FIRE TEST PROCEDURE Key words: Combustible products, commodity classification, fire test procedure 1(16) NT FIRE 049 Edition

More information

Influencing Factors Study of the Variable Speed Scroll Compressor with EVI Technology

Influencing Factors Study of the Variable Speed Scroll Compressor with EVI Technology Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2016 Influencing Factors Study of the Variable Speed Scroll Compressor with EVI Technology

More information

«DO160/ED14» - Jessica France

«DO160/ED14» - Jessica France Training Workshop «DO160/ED14» - Jessica France DO160/ED14 Specificities of Mechanical and Climatic aspects Edouard ZUNDEL Systems Qualification Engineer for Mechanical and Climatic aspects 1 The reference

More information

CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS

CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS - 56 - CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS Gloth O., Rudolf A. ILF Consulting Engineers Zürich, Switzerland ABSTRACT This article investigates the

More information

Product Technical Bulletin #48

Product Technical Bulletin #48 AN INTEGRATED SOLUTIONS PROVIDER Product Technical Bulletin #48 Current-Carrying Capacity of R-Series Connectors AirBorn Proprietary Page 1 AN INTEGRATED SOLUTIONS PROVIDER R-Series Current-Carrying Capacity

More information

THE WAY THE VENTURI AND ORIFICES WORK

THE WAY THE VENTURI AND ORIFICES WORK Manual M000 rev0 03/00 THE WAY THE VENTURI AND ORIFICES WORK CHAPTER All industrial combustion systems are made up of 3 main parts: ) The mixer which mixes fuel gas with combustion air in the correct ratio

More information

Calculating Total Uncertainty of Temperature Calibration with a Dry Block. Calibration White Paper. Beamex.

Calculating Total Uncertainty of Temperature Calibration with a Dry Block. Calibration White Paper. Beamex. Beamex Calibration White Paper info@beamex.com Calculating Total Uncertainty of Temperature Calibration with a Dry Block World-class calibration solutions Calculating Total Uncertainty of Temperature Calibration

More information

M E M O R A N D U M. NFPA Technical Committee on Fire Tests. NFPA 252 First Draft TC FINAL Ballot Results (F2016)

M E M O R A N D U M. NFPA Technical Committee on Fire Tests. NFPA 252 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Tests Kelly

More information

Gas density monitor With integrated transmitter Model GDM-100-TI

Gas density monitor With integrated transmitter Model GDM-100-TI SF 6 gas solutions Gas density monitor With integrated transmitter Model GDM-100-TI grid Products WIKA data sheet SP 60.05 for further approvals see page 5 Applications Gas density monitoring of closed

More information

Design Review Agenda

Design Review Agenda Design Review Agenda 1) Introduction, Motivation, and Previous Work a. Previous Work and Accomplishments i. Platform Launches ii. Successful Test Firings 2) More In-Depth Design Overview of the Existing

More information

Nitrogen subtraction on reported CO 2 emission using ultrasonic flare gas meter

Nitrogen subtraction on reported CO 2 emission using ultrasonic flare gas meter Nitrogen subtraction on reported CO 2 emission using ultrasonic flare gas meter Kjell-Eivind Frøysa, Christian Michelsen Research AS, Bergen, Norway Henning Ekerhovd, StatoilHydro ASA, Kollsnes, Norway

More information

PRESSURE REGULATORS AND FLOWMETERS, ALL MEDICAL GASES

PRESSURE REGULATORS AND FLOWMETERS, ALL MEDICAL GASES PRESSURE REGULATORS ALL MEDICAL GASES In this section we propose our pressure regulators (FM series, MU and MERCURY ) and our Rs flowmeters for applications other than oxygen therapy (presented in the

More information

Deborah Houssin-Agbomson, Jean-Yves Letellier, Philippe Renault, Simon Jallais

Deborah Houssin-Agbomson, Jean-Yves Letellier, Philippe Renault, Simon Jallais AN EXPERIMENTAL STUDY DEDICATED TO WIND INFLUENCE ON HELIUM BUILD-UP AND CONCENTRATION DISTRIBUTION INSIDE A 1-M 3 SEMI-CONFINED ENCLOSURE CONSIDERING HYDROGEN ENERGY APPLICATIONS CONDITIONS OF USE. Deborah

More information

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles International Journal of Engineering Research and Development e-issn: 7-067X, p-issn: 7-00X, www.ijerd.com Volume 3, Issue 4 (August ), PP. 33-39 Experimental Analysis on Vortex Tube Refrigerator Using

More information

Irrigation &Hydraulics Department lb / ft to kg/lit.

Irrigation &Hydraulics Department lb / ft to kg/lit. CAIRO UNIVERSITY FLUID MECHANICS Faculty of Engineering nd Year CIVIL ENG. Irrigation &Hydraulics Department 010-011 1. FLUID PROPERTIES 1. Identify the dimensions and units for the following engineering

More information

SIMULATION OF ENVIRONMENTAL FLIGHT CONDITIONS

SIMULATION OF ENVIRONMENTAL FLIGHT CONDITIONS SIMULATION OF ENVIRONMENTAL FLIGHT CONDITIONS BY ADVANCED ALTITUDE SIMULATION Klaus SCHÄFER Institute of Space Propulsion, German Aerospace Centre (DLR) Lampoldshausen, 74239 Hardthausen, Germany klaus.schaefer@dlr.de

More information

Reflow Oven HHL3000 INSTRUCTION MANUAL POHUA - jedyny autoryzowany przedstawiciel w Polsce

Reflow Oven HHL3000 INSTRUCTION MANUAL POHUA - jedyny autoryzowany przedstawiciel w Polsce POHUA - jedyny autoryzowany przedstawiciel w Polsce www.pohua.pl AOYUE TONGYI ELECTRONIC EQUIPMENT FACTORY Jishui Industrial Zone, Nantou, Zhongshan City, Guangdong Province, P. R. China www.aoyue.com

More information

SET OF EUROLEAGUE BACKSTOP UNITS (Reference PK120)

SET OF EUROLEAGUE BACKSTOP UNITS (Reference PK120) SET OF EUROLEAGUE BACKSTOP UNITS (Reference PK120) DESCRIPTION The EUROLEAGUE backstop unit is mainly designed for multi-sports pavilions and installations where the highest-level basketball competitions

More information

CALMO

CALMO ---------------------------------------------------- Sound attenuator with recessed connection for rectangular ducts ---------------------------------------------------------------------- GENERAL is, due

More information

ZIN Technologies PHi Engineering Support. PHi-RPT CFD Analysis of Large Bubble Mixing. June 26, 2006

ZIN Technologies PHi Engineering Support. PHi-RPT CFD Analysis of Large Bubble Mixing. June 26, 2006 ZIN Technologies PHi Engineering Support PHi-RPT-0002 CFD Analysis of Large Bubble Mixing Proprietary ZIN Technologies, Inc. For nearly five decades, ZIN Technologies has provided integrated products and

More information

Installation, use and maintenance instructions. Gas burner (5)

Installation, use and maintenance instructions. Gas burner (5) Installation, use and maintenance instructions Gas burner MODEL GAS 4 TYPE 516 T80 291 (5) TECHNICAL FEATURES Thermal output 180-470 kw 154.800-404.200 kcal/h Fuel Natural gas Pci 8-10 kwh/m 3 = 7000-8600

More information

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners BULLETIN MT2035-07/05 Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners M/MR Series M411, M511, M611 M420, M520, M620, MR410, MR510, MR610 MR212D, MR212E, MR212G and MR212J (Flanged),

More information

Thermal Profiling the Reflow Process

Thermal Profiling the Reflow Process Thermal Profiling the Reflow Process The Nomadics TCProfile system is a cost-effective instrument to measure the temperature characteristics of any process where the thermal profile is important to the

More information

Series Environmental Chambers

Series Environmental Chambers 3119-600 Series Environmental Chambers Challenges in Non-Ambient Testing Testing at non-ambient temperatures adds another layer of challenges to your testing laboratory. Ensuring you get accurate and stable

More information

OP CHECKLIST FOR 1D CONSOLIDATION LABORATORY TEST

OP CHECKLIST FOR 1D CONSOLIDATION LABORATORY TEST Page 1 of 5 WORK INSTRUCTIONS FOR ENGINEERS NHB Compiled by : LSS Checked by : GSS Approved by : OP-3-31. CHECKLIST FOR 1D CONSOLIDATION LABORATORY TEST Page 2 of 5 31.0 CHECKLIST ITEMS *(refer to respective

More information

CALEFFI. Ball zone valves. series /03 GB

CALEFFI. Ball zone valves. series /03 GB all zone valves series cert. n ISO / Function Zone valves are used to automatically shut-off the flow of carrier fluid distributed to a system. Specifically: -In central heating systems, they support the

More information

Panel diffuser ELASTOX -P

Panel diffuser ELASTOX -P Pioneering for You Series documentation version 12/2016 2 Application ƒƒfor fine-bubble compressed air aeration within the biological treatment stage ƒƒdepending on application and basin geometry: Use

More information

Drilling Efficiency Utilizing Coriolis Flow Technology

Drilling Efficiency Utilizing Coriolis Flow Technology Session 12: Drilling Efficiency Utilizing Coriolis Flow Technology Clement Cabanayan Emerson Process Management Abstract Continuous, accurate and reliable measurement of drilling fluid volumes and densities

More information

CERTIFICATE OF APPROVAL No ME 5088

CERTIFICATE OF APPROVAL No ME 5088 CERTIFICATE OF APPROVAL No ME 5088 1 Unit C, Alexander Bell Centre, Hopkinson Way, West Portway Business Park, Andover, Hampshire, SP10 3UR Tel: 01264 333305 Have been assessed against the requirements

More information

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE - 247 - AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE J D Castro a, C W Pope a and R D Matthews b a Mott MacDonald Ltd, St Anne House,

More information

AIR BEARINGS IN HIGH PRECISION SYSTEMS

AIR BEARINGS IN HIGH PRECISION SYSTEMS AIR BEARINGS IN HIGH PRECISION SYSTEMS I. Crăcăoanu 1 and F. Bremer 1 1 Royal Philips Electronics, Philips Innovation Services, Eindhoven, The Netherlands Abstract: In high precision system applications

More information

13kW Patio Heater. Assembly & User Instructions

13kW Patio Heater. Assembly & User Instructions 13kW Patio Heater Assembly & User Instructions GUARANTEE The Memphis patio heater is made by Universal Innovations to an exacting quality standard and is covered by the following guarantee: THIS PRODUCT

More information

Owner s Manual Installation and Operation

Owner s Manual Installation and Operation Owner s Manual Installation and Operation Models: RED40-N-AU RED40ST-N-AU Ref No: GMK10107 AS4553:2008 Important operating and maintenance instructions included. NOTICE DO NOT DISCARD THIS MANUAL Read,

More information

Bauman Machine Inc. COMPRESSED GAS CYLINDER SAFETY

Bauman Machine Inc. COMPRESSED GAS CYLINDER SAFETY Bauman Machine Inc. COMPRESSED GAS CYLINDER SAFETY Many industrial and laboratory operations require the use of compressed gases for a variety of different operations. Compressed gases present a unique

More information

The Usage of Propeller Tunnels For Higher Efficiency and Lower Vibration. M. Burak Şamşul

The Usage of Propeller Tunnels For Higher Efficiency and Lower Vibration. M. Burak Şamşul The Usage of Propeller Tunnels For Higher Efficiency and Lower Vibration M. Burak Şamşul ITU AYOC 2014 - Milper Pervane Teknolojileri Company Profile MILPER is established in 2011 as a Research and Development

More information

Leak Checking Large Vacuum Chambers

Leak Checking Large Vacuum Chambers Leak Checking Large Vacuum Chambers Technical Overview Vacuum Technologies Introduction Understanding the pump-down characteristics of a large vacuum vessel is critical for determining whether the vacuum

More information

The Agility Association of Canada

The Agility Association of Canada Check list to Prepare for Equipment Inspection 2018 Introduction: requires that all equipment used at sanctioned events be inspected and approved at least four months before a host s first trial, and regularly

More information

THE EXAMINATION OF COMFORT AND CROSS INFECTION IN A DISPLACEMENT VENTILATED ROOM

THE EXAMINATION OF COMFORT AND CROSS INFECTION IN A DISPLACEMENT VENTILATED ROOM THE EXAMINATION OF COMFORT AND CROSS INFECTION IN A DISPLACEMENT VENTILATED ROOM Piotr Grzelecki Master Thesis on Indoor Environmental Engineering Aalborg University The Faculty of Engineering and Science

More information

OPTIMIZING THE LENGTH OF AIR SUPPLY DUCT IN CROSS CONNECTIONS OF GOTTHARD BASE TUNNEL. Rehan Yousaf 1, Oliver Scherer 1

OPTIMIZING THE LENGTH OF AIR SUPPLY DUCT IN CROSS CONNECTIONS OF GOTTHARD BASE TUNNEL. Rehan Yousaf 1, Oliver Scherer 1 OPTIMIZING THE LENGTH OF AIR SUPPLY DUCT IN CROSS CONNECTIONS OF GOTTHARD BASE TUNNEL Rehan Yousaf 1, Oliver Scherer 1 1 Pöyry Infra Ltd, Zürich, Switzerland ABSTRACT Gotthard Base Tunnel with its 57 km

More information

Diaphragm pop-pop engine

Diaphragm pop-pop engine Diaphragm pop-pop engine By Jean-Yves Based on some knowledge got from previous engines we decided to build a new one in order to test various diaphragms. Therefore, where the diaphragm is usually pinched

More information