DEVELOPMENT AND TESTING OF AIR EXCHANGE RATE METHODS TO IMPROVE COST EFFECTIVENESS WHILE MAINTAINING ACCURACY

Size: px
Start display at page:

Download "DEVELOPMENT AND TESTING OF AIR EXCHANGE RATE METHODS TO IMPROVE COST EFFECTIVENESS WHILE MAINTAINING ACCURACY"

Transcription

1 DEVELOPMENT AND TESTING OF AIR EXCHANGE RATE METHODS TO IMPROVE COST EFFECTIVENESS WHILE MAINTAINING ACCURACY Prepared by: Joachim Eberharter and James Elliot (Tetra Tech, Inc., Santa Barbara, CA) Bill Mills and Katya Sayenko (Tetra Tech, Inc., Lafayette, CA) Introduction Tetra Tech, Inc. (Tetra Tech) was contracted by the United States Air Force (USAF), Air Force Center for Engineering and the Environment (AFCEE) to conduct experiments designed to validate an innovative and cost-effective methodology for estimating the air exchange rate (AER) of a building. The objective of the work was to quantitatively validate the methodology against a standard American Society for Testing and Materials (ASTM) method (ASTM E741-00). Research for this study was conducted at (1) Cape Canaveral Air Force Station (CCAFS), Florida; (2) former Kelly Air Force Base (AFB), Texas; and (3) Travis AFB, California. The AER of a building is critical in determining whether vapor intrusion (VI) may result in unacceptable concentrations of volatiles in indoor air. A building with relatively high rates of VI may never develop high indoor air concentrations, as vapors will be continually flushed out of the building and replaced with ambient air. Conversely, a building with very low AER could be subject to significant buildup of indoor air concentrations, even with a relatively low concentration source or low rate of intrusion. Commonly used methods of measuring AERs tend to be somewhat cumbersome and costly; however, during previous vapor intrusion investigations conducted at CCAFS, Travis AFB, former Kelly AFB, and Vandenberg AFB, a relatively simple and cost-effective method for determining AERs was developed and used (Tetra Tech 2009a, b, c, d). The method consists of instantaneously releasing a finite quantity of helium (He) inside a building and then measuring the helium concentration in the air over time as it dissipates. A formula is then applied to the results to calculate the building AER. The purpose of the recent experiments conducted at CCAFS, Kelly AFB, and Travis AFB, and discussed in this paper, was to conduct side by side comparisons of the He release methodology with an existing published method, with the objective of validating the He method as a tool for use at other sites. A modified version of ASTM Method E was used to obtain an independent estimate of the AERs at three buildings while simultaneously deploying the helium methodology. The ASTM method used involves the release of a tracer gas into a building at a constant, known rate, and then measuring concentrations in the building air. A formula is then applied to calculate the AER. An additional method using a single data point from a SUMMA canister sample was also developed during this study to allow for further testing comparisons. 1

2 Air Exchange Rate Study: Former Kelly AFB Of the three site investigations, Building 1416, Former Kelly Air Force Base is chosen as an example. A summary of results at all installations investigated is also provided subsequently. Building Description and Indoor Volume Estimates Building 1416 is an approximately 2,400-square-foot, single story slab-on-grade structure. The building consists of five areas: an entry way room, class room, shop, restroom, and paint room (Figure 1). The paint room has a vaulted ceiling, while the remaining rooms have drop ceilings. The paint room and the shop have an uncovered concrete floor, while the entry, classroom, and restroom have linoleum floors. As shown on Figure 1, the front door and the double doors leading from the shop area into the paint room were closed during the experiment. The paint room was excluded from the experiment. Figure 1 Floor Plan of Building 1416 illustrating components of the AER experiment. Experimental Design The following sections provide details of the former Kelly AFB field experiments and Table 1 summarizes the field activities conducted during the period of the experiment. 2

3 Table 1 Summary of Field Activities at Building 1416, Former Kelly AFB 22 March March 2011 Arrive at Building 1416 and set up components of AER experiments Upon arrival, HVAC system was on but not operating due to the moderate outside temperatures. The thermostat was adjusted to cause the HVAC system to start up and the blower fan to operate. Steady flow of SF 6 tracer gas into building initiated at 1526 Continuous logging of SF 6 concentrations in the Shop initiated at 1526 Helium from six 111-cf cylinders released into building at 0625 Indoor air samples for on-site field meter and off-site laboratory analysis of He collected over course of eight hours Discrete indoor air samples collected for off-site analysis of SF 6 at 0655 and 1025 SF 6 analyzer carried through building periodically to collect readings from each room 2 collocated SUMMA canisters deployed in Shop next to SF 6 analyzer at 0655 to collect 3.5-hour and 9-hour time-integrated samples for He and SF 6 analyses Final He sample collected at 1425 (8 hours after He release) SF 6 gas turned off at 1655 Site cleaned up and restored to condition as found SF 6 Tracer Gas Release The release of SF 6 tracer gas into Building 1416 for the ASTM method started prior to sampling and continued for the duration of the experiment through 23 March The SF 6 tracer gas was released as a 4.0 percent mixture of SF 6. Throughout the experiments, the SF 6 gas analyzer logged the SF 6 concentration at 10-minute intervals in the center of the Shop. The instrument was set to continually monitor the SF 6 concentration and to log the minimum, maximum, and average concentrations during each 10-minute interval. Helium Gas Release The He source for the former Kelly AFB experiment was six 111 cubic-foot cylinders of at least 99 percent pure He, which were placed at the locations shown on Figure 1. The valves were fully opened simultaneously by the field crew and the tanks allowed to empty into the building. The cylinders emptied in approximately 90 seconds. The cylinders were weighed before and after release to estimate the mass of helium released. Kelly AFB Implementation Composite indoor air samples of He were collected in Tedlar bags for He analysis at 15, 30, 60, 90, 120, 180, 240, 360, and 480 minutes (8 hours) after the release. Concentrations of SF 6 were continuously logged with the portable SF 6 gas analyzer and discrete measurements were collected in each room approximately once per hour. In addition, two time-integrated indoor air samples for SF 6 and He analysis were collected from the Shop in two collocated 6-liter SUMMA canisters. The SUMMA tests were experimental and are not part of the protocol developed from this investigation, but air exchange rates were calculated using this method and compared to predictions generated using the methods described above. 3

4 Experimental Results The He concentrations in the composite Tedlar bag samples and the time integrated SUMMA canister samples collected during the experiments at Building 1416 are presented in Table 2. A plot of the logged SF 6 concentrations is presented in Figure 2. Sample ID HVAC On (23 March 2011) Table 2 Helium Concentrations in Building 1416 at Former Kelly AFB Elapsed Time¹ (minutes) Collection Time Field Result² (ppmv) Laboratory Result³ (ppmv) 1416-HON :40 36,000 21, HON :55 26,000 15, HON :25 16,300 9, HON :55 10,975 7, HON :25 8,425 5, HON :25 4,625 3, HON :25 2,300 1, HON : ND 1416-HON :25 75 ND 1416-SUMMA-3.5HR :55 10:25 NA 7, SUMMA-9HR :55 15:55 NA 3,500 Definitions: HVAC heating, ventilation and air conditioning system NA not applicable ND not detected ppmv part per million by volume Notes: 1 Elapsed time since release of He. 2 Instrument detection level for He was 25 ppmv 3 Laboratory detection level for He was 500 ppmv 4

5 Figure 2 Plot of logged SF 6 concentrations measured on-site at former Kelly AFB Building 1416 and laboratory sample results. The MIRAN gas analyzer was set to continuously monitor SF 6 concentrations and to log the measurements every 10 minutes. Figure 2 shows the maximum, minimum, and average SF 6 concentrations logged for each 10-minute period. The sudden drop in SF 6 concentrations immediately following the release of He was also noted after the He releases during the CCAFS experiments, suggesting that the release of He into the building space may displace a measurable amount of SF 6 gas. Six cylinders of He represent approximately 650 cubic feet of pure He, which represents approximately 4.6 percent of the total indoor air volume of Building 1416; however, this volume is not sufficient to account for the total drop in SF 6 concentration. The SF 6 concentration is likely also affected by ingress and egress through the front door beginning immediately prior to He release and continuing throughout the experiment. Air Exchange Rate Analysis Analyses of the AER data for each of the three buildings investigated for this study include the following: Analysis of He release methods: For these methods, He was released instantaneously and AERs were calculated based on the decay in He concentrations and using three leastsquares (LS) methods. 5

6 Analysis of ASTM methods: For these methods SF 6 was released continuously at a known rate, and AERs were calculated. These tests were conducted simultaneously with the He tests. A modification was made to the ASTM method for this project to allow the ASTM methods to be excecuted under conditions that were not at steady-state (not at equilibrium). This was useful because data collected during the project clearly showed the SF 6 tracer concentrations were not at steady-state during the tests. Comparison of He-release results and SF 6 -release results. The three LS methods are all similar to each other, and differ primarily in that for LS method #1 (LS-1), the initial well-mixed He concentration (C0) is used in the equations to calculate AER, while for method #2 (LS-2) and method #3 (LS-3), C0 is not required to calculate the AER, although it can be estimated from the sample data. For LS-1, C0 is calculated in one of two ways: either by directly calculating the difference in weights of the He cylinders before and after He release, or using the vendor provided volume of the cylinders. These analyses are presented for the site chosen as an example, former Kelly AFB. Figure 3 illustrates the temporal relationships between the AER tests conducted at Building Also shown is when the instantaneous He release occurred, and the beginning and end of the SF 6 release. 6

7 Figure 3 Relationship between air exchange rate tests for former Kelly AFB. By examining Table 3 and Table 4 and cross-comparing results from the 13 different tests, the results are shown to be generally consistent between methods. Tests #3 and #4, using lab data, show that methods LS-1 produces higher air exchange rates (~22.2/day) than LS-2 or LS-3 (14.7/day to 16.5/day). One hypothesis for this is that He is being lost from the Tedlar bags between the time of sample collection and the time of sample analysis. Since method LS-1 uses a well-mixed initial He concentration (C0) and if He were lost from the first sample, the LS-1 method would tend to predict a higher air exchange rate. Methods LS-2 and LS-3 are less affected because C0 is not imposed as for LS-1. 7

8 8 Table 3 Air Exchange Rates, Day -1, Over Interval Shown

9 Table 4 Summary of Air Exchange Rate Analysis for Former Kelly AFB Tracer Range (day -1 ) Average (day -1 ) Results for Short Duration Tests (3 4 hours), March 23, 2011 He SF 6 LS SUMMA SUMMA Finite Difference Results of Long Duration Tests (8 9 hours) He SF 6 Definitions: He helium LS least squares method SF6 sulfur hexafluoride LS SUMMA SUMMA Finite Difference Discussion Including Summary From all Three Sites Cape Canaveral Air Force Station From the comparative AER tests completed at CCAFS, the following conclusions can be reached regarding the two types of tests (He and SF 6 ): The tests generate comparable results. Less field equipment is needed for the He tests, reducing costs and reducing the possibility of equipment failure. The weight of the He released can be accurately estimated, and this is a useful feature of the He tests. This information is directly used in the AER tests to eliminate a source of uncertainty. It is straightforward to implement an uncertainty analysis of results for the He methods, so that confidence intervals of results can be estimated. For the SF 6 methods, such an analysis is more difficult to implement, and was not attempted during this work. Safety issues are of less concern for He. SF 6 concentration limits to protect human health exist, although it is likely not to be an issue for well-designed tests. SF 6 is a greenhouse gas with a high global warming potential, and is being phased out as a tracer gas. These conclusions tend to favor the use of He tests over SF 6 tests. However, SF 6 continuous release tests may be superior to the He instantaneous tests in the duration of the tests. Typically He tests last only a fraction of the day, while SF 6 tests can continue for a day or more. It may be desirable to design He tests that last longer in order to get a more accurate estimate of daily AERs. 9

10 Former Kelly Air Force Base The major conclusions from the field investigations at former Kelly AFB are: As at CCAFS, the AERs calculated from the SF 6 and He release methods were similar. All of the data analysis methods were successfully completed indicating that the methods are robust. Travis Air Force Base The AERs for Building 1130 at Travis AFB were the highest encountered at any of the buildings investigated. Using lab data the LS results ranged from 47.1/day to 86.7/day. Using field data the results were less: 36.6/day to 50.8/day. The difference in results based on field data vs. lab data appears to be related to loss of He from the sample containers during transport to the laboratory. Several SF 6 tests were completed and average AER values were within the range of LS results obtained from the He tests. Also, two SUMMA tests were completed, and AERs ranged from 27/day to 39/day. While the calculated AERs exhibited more variability than for previous sites, the values generally agreed by a factor of two. Overall, the results from Travis AFB are consistent with results from CCAFS and Former Kelly AFB, and indicate that the instantaneous He release method yields similar results to the ASTM method. Cost Comparison There are a variety of options for implementing the two methods that will impact the total cost; for example, field analysis only, laboratory analysis only, or both field and laboratory analysis. Due to the wide range in AERs at different buildings, it is advisable to use field meters when conducting either test so that the approach (e.g. number of samples collected or SF 6 flow rate) can be adjusted in response to site specific conditions. Therefore, for cost comparison purposes, two scenarios were compared: (1) implementing the methods using both field and laboratory analysis and (2) using field measurements only. For both scenarios, unit costs and labor rates are estimates based on experience implementing the methods during this study. Actual costs vary based on location and other factors. The cost of the He methodology is significantly lower than the SF 6 tests for both scenarios. The primary factors driving the higher expense of the SF 6 method are the cost of the SF 6 gas and the regulator and rotameter required to release it at a known, steady rate, and the cost of the Portable SF 6 analyzer. The difference in cost is less for scenario 1 vs. scenario 2 due to the cost of analyzing multiple samples for He. Protocol for Estimating Air Exchange Rate Using Concentration Decay of Instantaneously Released Helium Tracer Gas The protocol developed covers the methodology used for estimating the air exchange rate (AER) of a building, or portion (zone) of a building, and by evaluating the concentration decay rate of instantaneously released helium (He) tracer gas. Three mathematical methods to estimate AERs from field-collected data were developed from basic principles. These methods are presented in the protocol and are solvable using Excel spreadsheets. The major assumption that guides these 10

11 methods is that the He tracer gas is released instantaneously such that it becomes well-mixed in the building before sampling begins (typically 15 to 30 minutes after release). The results from this step-by-step protocol pertain only to those conditions of weather and building operation (e.g., heating, ventilation, and air conditioning [HVAC] system status) that prevail during the measurements. It is assumed that the He concentration within the test building can be characterized by a single value throughout the building. This test method has been evaluated and validated against an established method described in American Society for Testing and Materials (ASTM) Method E modified for this project. The method was validated using test buildings with volumes up to approximately 30,000 cubic-feet (cf). Overall Conclusions The primary objective of this project was to develop cost-effective, simple methods for determining AERs. Simplified methods to determine AERs were developed from a combination of field investigations and least-squares algorithms. The AERs calculated for the three test buildings (Facility 1381, Building 1416, and Building 1130) using instantaneous He release and the LS methods compared well with the AERs calculated using the modified ASTM method with SF 6 tracer gas. The resuls of this study demonstrate that the He release methodology provides a cost-effective, easy to implement method of measuring building specific AERs. References Tetra Tech, Inc. (2009a) Investigation and Validation of Multiple Lines of Evidence to Assess Vapor Intrusion at Cape Canaveral Air Force Station, FL for US Air Force School of Aerospace Medicine (USAFSAM/OE) at Brooks City-Base, TX. Tetra Tech, Inc. (2009b) Investigation and Validation of Multiple Lines of Evidence to Assess Vapor Intrusion at Kelly Air Force Base, TX for US Air Force School of Aerospace Medicine (USAFSAM/OE) at Brooks City-Base, TX. Tetra Tech, Inc. (2009c) Investigation and Validation of Multiple Lines of Evidence to Assess Vapor Intrusion at Travis Air Force Base, CA for US Air Force School of Aerospace Medicine (USAFSAM/OE) at Brooks City-Base, TX. Tetra Tech, Inc. (2009d) Investigation and Validation of Multiple Lines of Evidence to Assess Vapor Intrusion at Vandenberg Air Force Base, CA for US Air Force School of Aerospace Medicine (USAFSAM/OE) at Brooks City-Base, TX. 11

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage William M. Pitts, Jiann C. Yang, Kuldeep Prasad, and Marco Fernandez National Institute of Standards

More information

VS Series Leak Detectors for Vacuum Furnaces LEAK DETECTION FOR VACUUM FURNACES

VS Series Leak Detectors for Vacuum Furnaces LEAK DETECTION FOR VACUUM FURNACES VS Series Leak Detectors for Vacuum Furnaces LEAK DETECTION FOR VACUUM FURNACES VS Series Leak Detectors for Vacuum Furnaces indicate the presence of a leak. If the vacuum level is slow to reach the original

More information

Environmental. Gas Canister sampling and analysis. EQLF, Cambridge, July 20 th Right Solutions Right Partner

Environmental. Gas Canister sampling and analysis. EQLF, Cambridge, July 20 th Right Solutions Right Partner Environmental Gas Canister sampling and analysis EQLF, Cambridge, July 20 th 2017 Right Solutions Right Partner www.alsglobal.co.uk 1 Right Solutions Right Partner Overview Direct soil gas and sub-slab

More information

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV 16-1 INTRODUCTION 16-1.1 Purpose. The purpose of this chapter is to familiarize divers with the techniques used to mix divers breathing gas. 16-1.2 Scope. This chapter

More information

Homeostasis and Negative Feedback Concepts and Breathing Experiments 1

Homeostasis and Negative Feedback Concepts and Breathing Experiments 1 Homeostasis and Negative Feedback Concepts and Breathing Experiments 1 I. Homeostasis and Negative Feedback Homeostasis refers to the maintenance of relatively constant internal conditions. For example,

More information

Chapter 13 Gases, Vapors, Liquids, and Solids

Chapter 13 Gases, Vapors, Liquids, and Solids Chapter 13 Gases, Vapors, Liquids, and Solids Property is meaning any measurable characteristic of a substance, such as pressure, volume, or temperature, or a characteristic that can be calculated or deduced,

More information

A SEMI-PRESSURE-DRIVEN APPROACH TO RELIABILITY ASSESSMENT OF WATER DISTRIBUTION NETWORKS

A SEMI-PRESSURE-DRIVEN APPROACH TO RELIABILITY ASSESSMENT OF WATER DISTRIBUTION NETWORKS A SEMI-PRESSURE-DRIVEN APPROACH TO RELIABILITY ASSESSMENT OF WATER DISTRIBUTION NETWORKS S. S. OZGER PhD Student, Dept. of Civil and Envir. Engrg., Arizona State Univ., 85287, Tempe, AZ, US Phone: +1-480-965-3589

More information

CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO Walnut Lake Rd th Street Houston TX Garner, IA 50438

CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO Walnut Lake Rd th Street Houston TX Garner, IA 50438 CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO. 10 Jerry Paul Smith Joel Clancy JPS Measurement Consultants, Inc Colorado Engineering Experiment Station, Inc (CEESI) 13002 Walnut Lake

More information

Traceable calibration of automatic weighing instruments in dynamic operation

Traceable calibration of automatic weighing instruments in dynamic operation Traceable calibration of automatic weighing instruments in dynamic operation Matej Grum* Metrology Institute of the Republic of Slovenia, Grudnovo nabrežje 17, 1000 Ljubljana, Slovenia Abstract. The article

More information

RADON SCREENING SURVEY FOLLOW-UP RADNOR CENTER Radnor Road, Bethesda, Maryland 20817

RADON SCREENING SURVEY FOLLOW-UP RADNOR CENTER Radnor Road, Bethesda, Maryland 20817 RADON SCREENING SURVEY FOLLOW-UP RADNOR CENTER 7000 Radnor Road, Bethesda, Maryland 20817 EXECUTIVE SUMMARY Date of Test Report: 3/25/16 Follow-Up Round of Testing: Initial Follow-up Post Remediation #

More information

LOW PRESSURE EFFUSION OF GASES adapted by Luke Hanley and Mike Trenary

LOW PRESSURE EFFUSION OF GASES adapted by Luke Hanley and Mike Trenary ADH 1/7/014 LOW PRESSURE EFFUSION OF GASES adapted by Luke Hanley and Mike Trenary This experiment will introduce you to the kinetic properties of low-pressure gases. You will make observations on the

More information

MCPS RADON TESTING. Executive Summary: Pine Crest Elementary School

MCPS RADON TESTING. Executive Summary: Pine Crest Elementary School E NGINEERS P LANNERS S CIENTISTS C ONSTRUCTION M ANAGERS 936 RIDGEBROOK ROAD SPARKS, MD 21152 410-316-7800 (FAX) 410-316-7935 MCPS RADON TESTING Executive Summary: Pine Crest Elementary School Date of

More information

RADON SCREENING SURVEY FOLLOW-UP MONTGOMERY VILLAGE MIDDLE SCHOOL Watkins Mill Road, Montgomery Village, Maryland 20886

RADON SCREENING SURVEY FOLLOW-UP MONTGOMERY VILLAGE MIDDLE SCHOOL Watkins Mill Road, Montgomery Village, Maryland 20886 RADON SCREENING SURVEY FOLLOW-UP MONTGOMERY VILLAGE MIDDLE SCHOOL 19300 Watkins Mill Road, Montgomery Village, Maryland 20886 EXECUTIVE SUMMARY Date of Test Report: 3/24/16 Follow-Up Round of Testing:

More information

Laboratory Hardware. Custom Gas Chromatography Solutions WASSON - ECE INSTRUMENTATION. Engineered Solutions, Guaranteed Results.

Laboratory Hardware. Custom Gas Chromatography Solutions WASSON - ECE INSTRUMENTATION. Engineered Solutions, Guaranteed Results. Laboratory Hardware Custom Gas Chromatography Solutions Engineered Solutions, Guaranteed Results. WASSON - ECE INSTRUMENTATION Laboratory Hardware Wasson-ECE Instrumentation offers hardware-only solutions

More information

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12 LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/ This experiment will introduce you to the kinetic properties of low-pressure gases. You will make observations on the rates with which selected

More information

Nitrogen subtraction on reported CO 2 emission using ultrasonic flare gas meter

Nitrogen subtraction on reported CO 2 emission using ultrasonic flare gas meter Nitrogen subtraction on reported CO 2 emission using ultrasonic flare gas meter Kjell-Eivind Frøysa, Christian Michelsen Research AS, Bergen, Norway Henning Ekerhovd, StatoilHydro ASA, Kollsnes, Norway

More information

MCPS RADON TESTING. Executive Summary: College Gardens Elementary School

MCPS RADON TESTING. Executive Summary: College Gardens Elementary School E N G I N E E R S P L A N N E R S S C I E N T I S T S C O N S T R U C T I O N M A N A G E R S 936 RIDGEBROOK ROAD SPARKS, MD 21152 410-316-7800 (FAX) 410-316-7935 MCPS RADON TESTING Executive Summary:

More information

This test shall be carried out on all vehicles equipped with open type traction batteries.

This test shall be carried out on all vehicles equipped with open type traction batteries. 5.4. Determination of hydrogen emissions page 1 RESS-6-15 5.4.1. This test shall be carried out on all vehicles equipped with open type traction batteries. 5.4.2. The test shall be conducted following

More information

Physical Analysis Model Report

Physical Analysis Model Report Physical Analysis Model Report Developed by The University of Kentucky and KYPIPE LLC Prepared for the National Institute of Hometown Security 368 N. Hwy 27 Somerset, KY 42503 November 19, 2012 This research

More information

VAPOR PRESSURE AND ENTHALPY OF VAPORIZATION OF A PURE LIQUID: THE ISOTENISCOPE METHOD

VAPOR PRESSURE AND ENTHALPY OF VAPORIZATION OF A PURE LIQUID: THE ISOTENISCOPE METHOD Physical Chemistry Laboratory Experiment I-3b VAPOR PRESSURE AND ENTHALPY OF VAPORIZATION OF A PURE LIQUID: THE ISOTENISCOPE METHOD References: See relevant sections of undergraduate Physical Chemistry

More information

MEMORANDUM. Investigation of Variability of Bourdon Gauge Sets in the Chemical Engineering Transport Laboratory

MEMORANDUM. Investigation of Variability of Bourdon Gauge Sets in the Chemical Engineering Transport Laboratory 1 MEMORANDUM TO: FROM: Prof. Davis Hubbard Prof. Faith A. Morrison DATE: 22 April 2014 RE: Investigation of Variability of Bourdon Gauge Sets in the Chemical Engineering Transport Laboratory Introduction

More information

Ozobot Bit Classroom Application: Boyle s Law Simulation

Ozobot Bit Classroom Application: Boyle s Law Simulation OZO AP P EAM TR T S BO RO VE D Ozobot Bit Classroom Application: Boyle s Law Simulation Created by Richard Born Associate Professor Emeritus Northern Illinois University richb@rborn.org Topics Chemistry,

More information

EXPERIMENT 8 Ideal Gas Law: Molecular Weight of a Vapor

EXPERIMENT 8 Ideal Gas Law: Molecular Weight of a Vapor EXPERIMENT 8 Ideal Gas Law: Molecular Weight of a Vapor Purpose: In this experiment you will use the ideal gas law to calculate the molecular weight of a volatile liquid compound by measuring the mass,

More information

APPLICATION NOTE. GC Integrated Permeation Device

APPLICATION NOTE. GC Integrated Permeation Device GC Integrated Permeation Device GC-integrated Design PPB to PPM Level Calibration No Cylinders or Regulators Required Option for Dual Ovens Cost Effective, Safe, Clean, Flexible, NIST Traceable Keywords:

More information

29th Monitoring Research Review: Ground-Based Nuclear Explosion Monitoring Technologies

29th Monitoring Research Review: Ground-Based Nuclear Explosion Monitoring Technologies IMPROVED CALIBRATION AND OPERATION OF A STABLE-GAS QUANTIFICATION MANIFOLD AS PART OF A RADIOXENON COLLECTION SYSTEM ABSTRACT Richard M. Williams, James C. Hayes, and Randy R. Kirkham Pacific Northwest

More information

HAP e-help. Obtaining Consistent Results Using HAP and the ASHRAE 62MZ Ventilation Rate Procedure Spreadsheet. Introduction

HAP e-help. Obtaining Consistent Results Using HAP and the ASHRAE 62MZ Ventilation Rate Procedure Spreadsheet. Introduction Introduction A key task in commercial building HVAC design is determining outdoor ventilation airflow rates. In most jurisdictions in the United States, ventilation airflow rates must comply with local

More information

STRUCTURED INQUIRY: Investigating Surface Area to Volume Ratio in Cells

STRUCTURED INQUIRY: Investigating Surface Area to Volume Ratio in Cells STRUCTURED INQUIRY: Investigating Surface Area to Volume Ratio in Cells Introduction: All organisms are composed of cells. The size and shape of a cell determines how well it can deliver nutrients to its

More information

CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS

CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS T. Gélain, C. Prévost Institut de Radioprotection et de Sûreté Nucléaire (IRSN), Saclay, France Abstract In order to better understand the risks due

More information

CHE 4115 Chemical Processes Laboratory 2 Experiment 1. Batch Distillation

CHE 4115 Chemical Processes Laboratory 2 Experiment 1. Batch Distillation CHE 4115 Chemical Processes Laboratory 2 Experiment 1 Batch Distillation BACKGROUND Distillation is one of the most commonly used unit operations in chemical engineering. In general, a distillation operation

More information

LINEAR TRANSFORMATION APPLIED TO THE CALIBRATION OF ANALYTES IN VARIOUS MATRICES USING A TOTAL HYDROCARBON (THC) ANALYZER

LINEAR TRANSFORMATION APPLIED TO THE CALIBRATION OF ANALYTES IN VARIOUS MATRICES USING A TOTAL HYDROCARBON (THC) ANALYZER LINEAR TRANSFORMATION APPLIED TO THE CALIBRATION OF ANALYTES IN VARIOUS MATRICES USING A TOTAL HYDROCARBON (THC) ANALYZER Michael T Tang, Ph.D. Grace Feng Greg Merideth Rui Huang Matheson Gas Applied Lab

More information

TWO PHASE FLOW METER UTILIZING A SLOTTED PLATE. Acadiana Flow Measurement Society

TWO PHASE FLOW METER UTILIZING A SLOTTED PLATE. Acadiana Flow Measurement Society TWO PHASE FLOW METER UTILIZING A SLOTTED PLATE Acadiana Flow Measurement Society Gerald L. Morrison Presented by: Mechanical Engineering Department Daniel J. Rudroff 323 Texas A&M University Flowline Meters

More information

Gas Accumulation Potential & Leak Detection when Converting to Gas

Gas Accumulation Potential & Leak Detection when Converting to Gas Gas Accumulation Potential & Leak Detection when Converting to Gas Coal to Gas / PCUG Conference Chattanooga, TN October 29, 2013 Robert G. Mudry, P.E. Airflow Sciences Corporation Introduction Coal to

More information

It s Just Calibration How Hard Can It Be?

It s Just Calibration How Hard Can It Be? It s Just Calibration How Hard Can it Be? Deever Bradley, P.E. Environmental Resources Management Bart Leininger, P.E. Principal Ashworth Leininger Group Camarillo, CA 4/3/18 Page 1 Objectives Proper instrument

More information

TP Validating a dynamic grid model with tracer gas injection and analysis

TP Validating a dynamic grid model with tracer gas injection and analysis International Gas Research Conference 2014 TP3-12 433 Validating a dynamic grid model with tracer gas injection and analysis S.C. Brussel, R. Warmerdam, J. Weda, E. Hardi,T. van Onna, N. Ligterink, H.

More information

PURE SUBSTANCE. Nitrogen and gaseous air are pure substances.

PURE SUBSTANCE. Nitrogen and gaseous air are pure substances. CLASS Third Units PURE SUBSTANCE Pure substance: A substance that has a fixed chemical composition throughout. Air is a mixture of several gases, but it is considered to be a pure substance. Nitrogen and

More information

THERMODYNAMICS OF A GAS PHASE REACTION: DISSOCIATION OF N 2 O 4

THERMODYNAMICS OF A GAS PHASE REACTION: DISSOCIATION OF N 2 O 4 THERMODYNAMICS OF A GAS PHASE REACTION: DISSOCIATION OF N 2 O 4 OBJECTIVES 1. To measure the equilibrium constant, enthalpy, entropy, and Gibbs free energy change of the reaction N2O4(g) = 2 NO2(g). 2.

More information

Diagnosis of Fuel Evaporative System

Diagnosis of Fuel Evaporative System T S F S 0 6 L A B E X E R C I S E 2 Diagnosis of Fuel Evaporative System April 5, 2017 1 objective The objective with this laboratory exercise is to read, understand, and implement an algorithm described

More information

Field Evaluation of ASTM E in Relation to Control Room Habitability Testing and Boundary Maintenance in Nuclear Power Plants.

Field Evaluation of ASTM E in Relation to Control Room Habitability Testing and Boundary Maintenance in Nuclear Power Plants. Field Evaluation of ASTM E741-00 in Relation to Control Room Habitability Testing and Boundary Maintenance in Nuclear Power Plants. Presented By Clinton B. Summers Eric M. Banks NUCON International, Inc.

More information

Evaluation of the Mass Technology Precision Mass Measurement System on Bulk Field-Constructed Tanks (120,000 Gallon Vertical Tank Evaluation)

Evaluation of the Mass Technology Precision Mass Measurement System on Bulk Field-Constructed Tanks (120,000 Gallon Vertical Tank Evaluation) Evaluation of the Mass Technology Precision Mass Measurement System on Bulk Field-Constructed Tanks (120,000 Gallon Vertical Tank Evaluation) Final Report PREPARED FOR: Mass Technology Corporation March

More information

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the 1151 METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS 1.0 Scope and Application. 1.1 Analytes. Analyte Volatile Organic Compounds (VOC) CAS No. No CAS number assigned 1.2 Scope. This method

More information

Quick run through of the four projects

Quick run through of the four projects 1 Quick run through of the four projects 2 3 4 Vandenberg AFB Study Site. Mobile lab in center. San dune environment. Ground water contamination of TCE at ~18 to 20 feet bgs. 5 This research program addressed

More information

Application Note AN-107

Application Note AN-107 SPEC Sensor TM Characterization & Calibration Considerations Scope This document is provided to describe the considerations needed to characterize, calibrate, verify and validate the measurement performance

More information

A Conceptual Understanding of Leakage During Soil-Gas Sampling

A Conceptual Understanding of Leakage During Soil-Gas Sampling A Conceptual Understanding of Leakage During Soil-Gas Sampling Dominic C. DiGiulio, Ph.D. U.S. Environmental Protection Agency Office of Research and Development National Risk Management Research Laboratory

More information

Hydrostatics Physics Lab XI

Hydrostatics Physics Lab XI Hydrostatics Physics Lab XI Objective Students will discover the basic principles of buoyancy in a fluid. Students will also quantitatively demonstrate the variance of pressure with immersion depth in

More information

Transient Analyses In Relief Systems

Transient Analyses In Relief Systems Transient Analyses In Relief Systems Dirk Deboer, Brady Haneman and Quoc-Khanh Tran Kaiser Engineers Pty Ltd ABSTRACT Analyses of pressure relief systems are concerned with transient process disturbances

More information

ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Squire-Cogswell

ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Squire-Cogswell ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Squire-Cogswell Squire Cogswell / Aeros Instruments, Inc. 1111 Lakeside Drive Gurnee, IL 60031 Phone: (800) 448-0770 Fax: (847) 855-6304 info@squire-cogswell.com

More information

DETERMINATION OF TETRAHYDROTHIOPHENE IN AMBIENT AIR BY GAS CHROMATOGRAPHY WITH A PFPD DETECTOR COUPLED TO A PRECONCENTRATION TECHNOLOGY

DETERMINATION OF TETRAHYDROTHIOPHENE IN AMBIENT AIR BY GAS CHROMATOGRAPHY WITH A PFPD DETECTOR COUPLED TO A PRECONCENTRATION TECHNOLOGY DETERMINATION OF TETRAHYDROTHIOPHENE IN AMBIENT AIR BY GAS CHROMATOGRAPHY WITH A PFPD DETECTOR COUPLED TO A PRECONCENTRATION TECHNOLOGY Nengbing Xu, Hongmei Ying and Libo Zhu Ningbo Environmental Monitoring

More information

MCPS RADON TESTING. Executive Summary: Poolesville Elementary School

MCPS RADON TESTING. Executive Summary: Poolesville Elementary School E N G I N E E R S P L A N N E R S S C I E N T I S T S C O N S T R U C T I O N M A N A G E R S 936 RIDGEBROOK ROAD SPARKS, MD 21152 410-316-7800 (FAX) 410-316-7935 MCPS RADON TESTING Executive Summary:

More information

Calculation of Trail Usage from Counter Data

Calculation of Trail Usage from Counter Data 1. Introduction 1 Calculation of Trail Usage from Counter Data 1/17/17 Stephen Martin, Ph.D. Automatic counters are used on trails to measure how many people are using the trail. A fundamental question

More information

MCPS RADON TESTING. Executive Summary: Olney Elementary School

MCPS RADON TESTING. Executive Summary: Olney Elementary School E N G I N E E R S P L A N N E R S S C I E N T I S T S C O N S T R U C T I O N M A N A G E R S 936 RIDGEBROOK ROAD SPARKS, MD 21152 410-316-7800 (FAX) 410-316-7935 MCPS RADON TESTING Executive Summary:

More information

Blast Damage Consideratons for Horizontal Pressure Vessel and Potential for Domino Effects

Blast Damage Consideratons for Horizontal Pressure Vessel and Potential for Domino Effects A publication of CHEMICAL ENGINEERING TRANSACTIONS VOL. 26, 2012 Guest Editors: Valerio Cozzani, Eddy De Rademaeker Copyright 2012, AIDIC Servizi S.r.l., ISBN 978-88-95608-17-4; ISSN 1974-9791 The Italian

More information

Single-Interval Gas Permeability Testing

Single-Interval Gas Permeability Testing Single-Interval Gas Permeability Testing Dominic DiGiulio, Ph.D. Office of Research and Development National Risk Management Research Laboratory Ground-Water and Ecosystem Restoration Division Ada,Oklahoma

More information

Chapter Capacity and LOS Analysis of a Signalized I/S Overview Methodology Scope Limitation

Chapter Capacity and LOS Analysis of a Signalized I/S Overview Methodology Scope Limitation Chapter 37 Capacity and LOS Analysis of a Signalized I/S 37.1 Overview The Highway Capacity Manual defines the capacity as the maximum howdy rate at which persons or vehicle can be reasonably expected

More information

RADIATION PROCEDURES MANUAL Procedure Cover Sheet

RADIATION PROCEDURES MANUAL Procedure Cover Sheet RADIATION PROCEDURES MANUAL Procedure Cover Sheet Procedure Title: Calibration of Eberline Portable Particulate Noble Gas Monitor Procedure Number: TSO-08-13-REV 1 Effective Date: July 1, 2008 Approved

More information

Generating Calibration Gas Standards

Generating Calibration Gas Standards Technical Note 1001 Metronics Inc. Generating Calibration Gas Standards with Dynacal Permeation Devices Permeation devices provide an excellent method of producing known gas concentrations in the PPM and

More information

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any

More information

Hydraulic and Economic Analysis of Real Time Control

Hydraulic and Economic Analysis of Real Time Control Hydraulic and Economic Analysis of Real Time Control Tom Walski 1, Enrico Creaco 2 1 Bentley Systems, Incorporated, 3 Brian s Place, Nanticoke, PA, USA 2 Dipartimento di Ingegneria Civile ed Architettura,

More information

Gerald D. Anderson. Education Technical Specialist

Gerald D. Anderson. Education Technical Specialist Gerald D. Anderson Education Technical Specialist The factors which influence selection of equipment for a liquid level control loop interact significantly. Analyses of these factors and their interactions

More information

Lab 3 Introduction to Quantitative Analysis: Pumps and Measurements of Flow

Lab 3 Introduction to Quantitative Analysis: Pumps and Measurements of Flow Georgia Institute of Technology School of Earth and Atmospheric Sciences EAS 4641, Spring 2008 Lab 3 Introduction to Quantitative Analysis: Pumps and Measurements of Flow Purpose of Lab 3: 1) To gain a

More information

UNITY 2 TM. Air Server Series 2 Operators Manual. Version 1.0. February 2008

UNITY 2 TM. Air Server Series 2 Operators Manual. Version 1.0. February 2008 UNITY 2 TM Air Server Series 2 Operators Manual Version 1.0 February 2008 1. Introduction to the Air Server Accessory for UNITY 2...2 1.1. Summary of Operation...2 2. Developing a UNITY 2-Air Server method

More information

Experiment 13 Molar Mass of a Gas. Purpose. Background. PV = nrt

Experiment 13 Molar Mass of a Gas. Purpose. Background. PV = nrt Experiment 13 Molar Mass of a Gas Purpose In this experiment you will use the ideal gas law to calculate the molar mass of a volatile liquid compound by measuring the mass, volume, temperature, and pressure

More information

KWA. Evaluation of the MassTech 001 Tank Integrity Test System. EPA Forms Obtained From

KWA. Evaluation of the MassTech 001 Tank Integrity Test System. EPA Forms Obtained From Evaluation of the MassTech 001 Tank Integrity Test System EPA Forms Obtained From http://www.kwaleak.com PREPARED FOR MassTech International Limited KWA February 26, 1995 Ken Wilcox Associates, Inc. 1125

More information

White Paper. Chemical Sensor vs NDIR - Overview: NDIR Technology:

White Paper. Chemical Sensor vs NDIR - Overview: NDIR Technology: Title: Comparison of Chemical Sensor and NDIR Technologies TSN Number: 25 File:\\MII- SRV1\Metron\Bridge_Analyzers\Customer_Service_Documentation\White_Papers\25_G en EGA NDIR vs Chemical Sensor.docx Created

More information

Testing the Vented, 7-Liter Induction Chamber. Report 6 April 2008

Testing the Vented, 7-Liter Induction Chamber. Report 6 April 2008 Report 6 April 2008 Page 1 of 11 Report 6 April 2008 The final review and approval of this document before its release to the client is the responsibility of the following person at Technical Safety Services.

More information

RADON SCREENING SURVEY FOLLOW-UP GEORGIAN FOREST ELEMENTARY SCHOOL Regina Drive, Silver Spring, Maryland 20906

RADON SCREENING SURVEY FOLLOW-UP GEORGIAN FOREST ELEMENTARY SCHOOL Regina Drive, Silver Spring, Maryland 20906 RADON SCREENING SURVEY FOLLOW-UP GEORGIAN FOREST ELEMENTARY SCHOOL 3100 Regina Drive, Silver Spring, Maryland 20906 EXECUTIVE SUMMARY Date of Test Report: 3/4/16 Follow-Up Round of Testing: Initial Follow-up

More information

Thermodynamics ERT 206 Properties of Pure Substance HANNA ILYANI ZULHAIMI

Thermodynamics ERT 206 Properties of Pure Substance HANNA ILYANI ZULHAIMI Thermodynamics ERT 206 Properties of Pure Substance HANNA ILYANI ZULHAIMI Outline: Pure Substance Phases of pure substance Phase change process of pure substance Saturation temperature and saturation pressure

More information

Evaluation of Regression Approaches for Predicting Yellow Perch (Perca flavescens) Recreational Harvest in Ohio Waters of Lake Erie

Evaluation of Regression Approaches for Predicting Yellow Perch (Perca flavescens) Recreational Harvest in Ohio Waters of Lake Erie Evaluation of Regression Approaches for Predicting Yellow Perch (Perca flavescens) Recreational Harvest in Ohio Waters of Lake Erie QFC Technical Report T2010-01 Prepared for: Ohio Department of Natural

More information

How to Test Air Change Effectiveness

How to Test Air Change Effectiveness How to Test Air Change Effectiveness Presenter : Mark Jacobson Queensland Commissioning Manager 13 th June 2012 Presentation Agenda What is Air-Change Effectiveness (ACE)? Why is it important? Green Star

More information

13.1!"#$#%"&'%()$*+%,+-.$+/*$#

13.1!#$#%&'%()$*+%,+-.$+/*$# 343%%%%%%%%%5)"./$+%67%%%%%!"#$# 13.1!"#$#%"&'%()$*+%,+-.$+/*$#!"#$%&'($)*!"#$%&'($)+ If you want to understand how gases behave such as why fresh air rushes into your lungs when certain chest muscles

More information

Process Simulator Evaluates Blower and Valve Control Strategies for WWTP Aeration

Process Simulator Evaluates Blower and Valve Control Strategies for WWTP Aeration Process Simulator Evaluates Blower and Valve Control Strategies for WWTP Aeration inshare By Steve Kestel and Tilo Stahl (BioChem Technology) and Matthew Gray (Keystone Engineering Group) Introduction

More information

VENTILATION EFFICIENCIES OF A DESK-EDGE-MOUNTED TASK VENTILATION SYSTEM

VENTILATION EFFICIENCIES OF A DESK-EDGE-MOUNTED TASK VENTILATION SYSTEM VENTILATION EFFICIENCIES OF A DESK-EDGE-MOUNTED TASK VENTILATION SYSTEM D Faulkner *, WJ Fisk, DP Sullivan and SM Lee Indoor Environment Dept., Lawrence Berkeley National Lab, Berkeley, CA, USA ABSTRACT

More information

Diffusivity in Gases Experiment ver 5.10b

Diffusivity in Gases Experiment ver 5.10b Diffusivity in Gases Experiment ver 5.0b number of experimental techniques have been developed for the measurement of the diffusivity in gases. Both steady-state and unsteady-state methods are used. However,

More information

Tel: FAX: Risk Assessment for Exposure to Respirable Dusts Generated from the Use of Chalks and Pastels

Tel: FAX: Risk Assessment for Exposure to Respirable Dusts Generated from the Use of Chalks and Pastels Duke University Medical Center Department of Community & Family Medicine Division of Occupational & Environmental Medicine Box 3834 Duke University Medical Center Durham, NC 27710 April 26, 2003 Risk Assessment

More information

Regional Analysis of Extremal Wave Height Variability Oregon Coast, USA. Heidi P. Moritz and Hans R. Moritz

Regional Analysis of Extremal Wave Height Variability Oregon Coast, USA. Heidi P. Moritz and Hans R. Moritz Regional Analysis of Extremal Wave Height Variability Oregon Coast, USA Heidi P. Moritz and Hans R. Moritz U. S. Army Corps of Engineers, Portland District Portland, Oregon, USA 1. INTRODUCTION This extremal

More information

Laboratory Hardware. Custom Gas Chromatography Solutions WASSON - ECE INSTRUMENTATION. Custom solutions for your analytical needs.

Laboratory Hardware. Custom Gas Chromatography Solutions WASSON - ECE INSTRUMENTATION. Custom solutions for your analytical needs. Laboratory Hardware Custom Gas Chromatography Solutions Custom solutions for your analytical needs. Laboratory Hardware Wasson-ECE Instrumentation offers hardware-only solutions for advanced chromatography

More information

MCPS RADON TESTING. Executive Summary: John F. Kennedy High School

MCPS RADON TESTING. Executive Summary: John F. Kennedy High School E NGINEERS P LANNERS S CIENTISTS C ONSTRUCTION M ANAGERS 936 RIDGEBROOK ROAD SPARKS, MD 21152 410-316-7800 (FAX) 410-316-7935 MCPS RADON TESTING Executive Summary: John F. Kennedy High School Date of Test

More information

Gases. Unit 10. How do gases behave?

Gases. Unit 10. How do gases behave? Gases Unit 10 How do gases behave? Gases are perhaps the most mysterious of all of the phases of matter. For the most part gases are invisible to us, and it was once believed that in the air there is no

More information

AIR POLLUTION AND ENERGY EFFICIENCY. A transparent and reliable hull and propeller performance standard. Submitted by Clean Shipping Coalition (CSC)

AIR POLLUTION AND ENERGY EFFICIENCY. A transparent and reliable hull and propeller performance standard. Submitted by Clean Shipping Coalition (CSC) E MARINE ENVIRONMENT PROTECTION COMMITTEE 63rd session Agenda item 4 MEPC 63/4/8 23 December 2011 Original: ENGLISH AIR POLLUTION AND ENERGY EFFICIENCY A transparent and reliable hull and propeller performance

More information

Testing the Vented, 2-Liter Induction Chamber. Report 14 October 2004

Testing the Vented, 2-Liter Induction Chamber. Report 14 October 2004 Report 156August 2004 Page 1 of 17 Report 14 October 2004 The final review and approval of this document before its release to the client is the responsibility of the following person at Technical Safety

More information

EUROPEAN NEW CAR ASSESSMENT PROGRAMME (Euro NCAP) SLED TEST PROCEDURE FOR ASSESSING KNEE IMPACT AREAS

EUROPEAN NEW CAR ASSESSMENT PROGRAMME (Euro NCAP) SLED TEST PROCEDURE FOR ASSESSING KNEE IMPACT AREAS www.euroncap.com EUROPEAN NEW CAR ASSESSMENT PROGRAMME (Euro NCAP) SLED TEST PROCEDURE FOR ASSESSING KNEE IMPACT AREAS Version 1.0a December 2004 Sled Test Procedure for Assessing Knee Impact Areas (V1.0a)

More information

Comparative temperature measurements in an experimental borehole heat exchanger. Vincent Badoux 1, Rita Kobler 2

Comparative temperature measurements in an experimental borehole heat exchanger. Vincent Badoux 1, Rita Kobler 2 European Geothermal Congress 2016 Strasbourg, France, 19-24 Sept 2016 Comparative temperature measurements in an experimental borehole heat exchanger Vincent Badoux 1, Rita Kobler 2 1 GEOTEST AG, Bernstrasse

More information

Performance Overview calibration Laboratory EP Instruments Messtechnik und Kalibrierung GmbH

Performance Overview calibration Laboratory EP Instruments Messtechnik und Kalibrierung GmbH Performance Overview calibration Laboratory EP Instruments Messtechnik und Kalibrierung GmbH 1 D-K-15143-01-00 Services around the measurement technology in Germanys most accurate DAkkS laboratory*. Whether

More information

Kinetic-Molecular Theory

Kinetic-Molecular Theory GASES Chapter Eleven Kinetic-Molecular Theory! Recall that our only previous description of gases stated that gases completely fill and take the shape of their containers.! The Kinetic-Molecular Theory

More information

Diffusivity in Gases Experiment ver 05.10a

Diffusivity in Gases Experiment ver 05.10a Diffusivity in Gases Experiment ver 05.0a number of experimental techniques have been developed for the measurement of the diffusivity in gases. Both steady-state and unsteady-state methods are used. However,

More information

Gas Measurement Fundamentals Certification. Curriculum

Gas Measurement Fundamentals Certification. Curriculum Gas Certification Institute, LLC P.O. Box 131525 Houston, Texas 77219-1525 281-598-7200 Phone 281-598-7199 Fax contact@gascertification.com www.gascertification.com Curriculum Copyright 2007-2012 Gas Certification

More information

Control of Nuclear Gloveboxes and Enclosures Using the No- Moving-Part Vortex Amplifier (VXA)

Control of Nuclear Gloveboxes and Enclosures Using the No- Moving-Part Vortex Amplifier (VXA) Control of Nuclear Gloveboxes and Enclosures Using the No- Moving-Part Vortex Amplifier (VXA) ABSTRACT M.J. Crossley AEA Technology ES. Inc. 1100 Jadwin Ave, Richland, WA 99352, USA This paper describes

More information

STANDARD OPERATING PROCEDURES

STANDARD OPERATING PROCEDURES PAGE: 1 of 14 CONTENTS 1.0 SCOPE AND APPLICATION 2.0 METHOD SUMMARY 3.0 SAMPLE PRESERVATION, CONTAINERS, HANDLING AND STORAGE 4.0 INTERFERENCE AND POTENTIAL PROBLEMS 5.0 EQUIPMENT/APPARATUS 6.0 REAGENTS

More information

Figure Vapor-liquid equilibrium for a binary mixture. The dashed lines show the equilibrium compositions.

Figure Vapor-liquid equilibrium for a binary mixture. The dashed lines show the equilibrium compositions. Another way to view this problem is to say that the final volume contains V m 3 of alcohol at 5.93 kpa and 20 C V m 3 of air at 94.07 kpa and 20 C V m 3 of air plus alcohol at 100 kpa and 20 C Thus, the

More information

Permitted MSS Emissions Tracking, Recordkeeping, and Reporting. Presented by ACES April 24, 2008

Permitted MSS Emissions Tracking, Recordkeeping, and Reporting. Presented by ACES April 24, 2008 Permitted MSS Emissions Tracking, Recordkeeping, and Reporting Presented by ACES April 24, 2008 1 Agenda Introductions Overview of Current MSS Permitting Program Status Discussion of Model MSS Permit Requirements

More information

LAB : Using A Spark Timer

LAB : Using A Spark Timer LAB : Using A Spark Timer Read through the whole lab and answer prelab questions prior to lab day. Name: F1 Introduction A spark timer is used to make accurate time and distance measurements for moving

More information

Evaluating the Design Safety of Highway Structural Supports

Evaluating the Design Safety of Highway Structural Supports Evaluating the Design Safety of Highway Structural Supports by Fouad H. Fouad and Elizabeth A. Calvert Department of Civil and Environmental Engineering The University of Alabama at Birmingham Birmingham,

More information

Neil Kane Managing Director EMT UK

Neil Kane Managing Director EMT UK Neil Kane Managing Director EMT UK SF6 Measurement, Analysis, Diagnostics and Leak Detection Our goals at EMT are to supply Maintenance Operatives with the very best tools to protect both personnel and

More information

SECTION 2 HYDROLOGY AND FLOW REGIMES

SECTION 2 HYDROLOGY AND FLOW REGIMES SECTION 2 HYDROLOGY AND FLOW REGIMES In this section historical streamflow data from permanent USGS gaging stations will be presented and discussed to document long-term flow regime trends within the Cache-Bayou

More information

Improve Process Reliability

Improve Process Reliability Convenient Conductivity Calibration to Meet Pharmacopeia Regulations Pharmacopeias require that conductivity measurement systems be periodically calibrated to ensure their precision. The range of accessories

More information

Measurement Device Deployment & Interpretation of Results. Topic 3 - Audio 33. Key Points

Measurement Device Deployment & Interpretation of Results. Topic 3 - Audio 33. Key Points Topic 3 - Audio 33 Short-Term Tests (2 days to 90 days) All exterior doors and windows need to be closed during the test. People can go in and out but not leave doors and windows propped open. No requirement

More information

ENHANCED PARKWAY STUDY: PHASE 2 CONTINUOUS FLOW INTERSECTIONS. Final Report

ENHANCED PARKWAY STUDY: PHASE 2 CONTINUOUS FLOW INTERSECTIONS. Final Report Preparedby: ENHANCED PARKWAY STUDY: PHASE 2 CONTINUOUS FLOW INTERSECTIONS Final Report Prepared for Maricopa County Department of Transportation Prepared by TABLE OF CONTENTS Page EXECUTIVE SUMMARY ES-1

More information

Paper 2.2. Operation of Ultrasonic Flow Meters at Conditions Different Than Their Calibration

Paper 2.2. Operation of Ultrasonic Flow Meters at Conditions Different Than Their Calibration Paper 2.2 Operation of Ultrasonic Flow Meters at Conditions Different Than Their Calibration Mr William Freund, Daniel Measurement and Control Mr Klaus Zanker, Daniel Measurement and Control Mr Dale Goodson,

More information

FIRE PROTECTION. In fact, hydraulic modeling allows for infinite what if scenarios including:

FIRE PROTECTION. In fact, hydraulic modeling allows for infinite what if scenarios including: By Phil Smith, Project Manager and Chen-Hsiang Su, PE, Senior Consultant, Lincolnshire, IL, JENSEN HUGHES A hydraulic model is a computer program configured to simulate flows for a hydraulic system. The

More information

Effects of Traffic Signal Retiming on Safety. Peter J. Yauch, P.E., PTOE Program Manager, TSM&O Albeck Gerken, Inc.

Effects of Traffic Signal Retiming on Safety. Peter J. Yauch, P.E., PTOE Program Manager, TSM&O Albeck Gerken, Inc. Effects of Traffic Signal Retiming on Safety Peter J. Yauch, P.E., PTOE Program Manager, TSM&O Albeck Gerken, Inc. Introduction It has long been recognized that traffic signal timing can have an impact

More information

MET 335W Fluid Mechanics Laboratory. Lab 1: Bourdon Tube Calibration. Nick Peak

MET 335W Fluid Mechanics Laboratory. Lab 1: Bourdon Tube Calibration. Nick Peak MET 335W Fluid Mechanics Laboratory Lab 1: Bourdon Tube Calibration Nick Peak January 15, 2018 Purpose The purpose of this experiment is to test the accuracy of a bourdon pressure gauge. This is accomplished

More information