It is essential that the maintenance staff is qualified for electrical works and follows safety procedures.
|
|
- Melvyn Barber
- 6 years ago
- Views:
Transcription
1 MAINTENANCE OF POWER FACTOR CORRECTION EQUIPMENTS Procedures, suggestions and traceability The purpose of this document is to propose a maintenance method that allows to identify the elements to be maintained in Power Factor Correction equipments. The shortage or even the lack of appropriate maintenance can lead to equipment faults, injures to people, animals or objects, for which the constructor can not be considered responsible. due to the flammable materials which capacitors are made of, Power Factor Correction equipments are be considered as fire hazardous devices in case of malfunctions or faults. Therefore it is fundamental to follow guidelines written in the standard CEI and the constructor directives defined in the installation and user manual. Power Factor Correction equipments have variable working conditions depending where they are installed:. Harmonics, moisture, temperature, time and operating conditions affect the natural and inevitable decline of the capacitors, therefore it s not possible to calculate Mean Time Between Failures (MTBF) to plan predictive maintenance of all the elements. Preventive maintenance has to be planned and registered to plot the trend of measured electrical quantities over time.(as suggested by CEI standard for electric substations maintenance). At the bottom of this document you can find a facsimile which could be useful 1. Pre-installation controls During installation it is necessary to verify the tightening of the screws of all the power connections, because transport could cause loosening. Furthermore it is necessary to inspect the total integrity of the equipment and of all the elements inside to make sure that no damage has occurred to the equipment during transport. 2. Maintenance safety measures It is essential that the maintenance staff is qualified for electrical works and follows safety procedures. Before working inside Power Factor Correction equipment Wait at least 20 minutes after power disconnection, to allow components cooling and capacitors discharge. 3. Preventive or ordinary maintenance Lifetime, electrical and mechanical reliability of the equipment are closely related to proper maintenance. Predictive maintenance can t be applied, then we recommend to schedule the tests as in the table below. Frequency of maintenance works is suggested, but maintenance planning is at customer s choice. It s also specified that periodicity of such inspections it s referred to 8 working hours per day, for 5 days per week, in the operating class of 55 C, without harmonic distortion. In the table below there are three different type of maintenance, that have to be followed with different frequencies depending on the operating year of the equipment.
2 TYPE OF CHECK EXECUTION MODE TYPE A MAINTENANCE 1 Check tightening torque of all power connections 2 Verify the integrity of the protection devices (fuse, varistors of static PFC equipments, ) 3 Clean the air ducts, grids, of the cabinet. In IP equipments clean or replace filters. 4 Clean the cabinet, removing powders or foreign bodies, to avoid triggering of partial discharges. Clean particularly the elements that could cause insulation problems (busbars supporting insulator, contactors, top plate of the capacitors, etc.) 5 Make sure no condensation is present on the live parts of the equipment 6 Check the integrity of the insulation of the electrical cables and of the auxiliary circuits 1 Verify the correct operation of the regulator 2 Check the integrity of the capacitor s discharge resistors 3 Make sure that the overpressure device of each capacitor is not activated 4 Check the current of each bank on each phase TYPE B MAINTENANCE In manual mode switch on each bank and verify if its contactor is properly closing and opening. Return the regulator on Automatic mode and make sure that with connected inductive loads ( motors, transformers, discharge lamps, etc ) inductive LED switches on. Measure the current on each phase with a current clamp, recording the values and comparing them with the rated ones. In case of decreases bigger than 5% from rated value, you have to measure the capacitance of each capacitor and if necessary replace them all (to replace capacitors see paragraph 4.1). Otherwise, if measured current of one or more phases is higher than 1.4 times the rated value, it means that the current harmonics level (THDi) is too high for that type of Power Factor Correction equipment. We suggest to contact us for an instrumental inspection.
3 5 Make sure the ventilation system is working properly For this purpose you can use an hot air blower to heat the control thermostat (at 35 C they shall close and operate the fans for the air expulsion) and the alarm thermostats (at about 50 C they shall open, opening the auxiliary circuit, disconnecting the capacitor banks). 1 Verify the absence of smut on screws or near the exit terminals (power cables) of the contactors. Pay special attention to the contactors of the first and the second banks, because they are connected/disconnected more frequently than the others. 2 Verify the absence of oxidation and/or corrosion on each component, particularly of the copper busbars/cables and over the enclosure surfaces 3 Verify that there are no deformities in the insulation of power cables, caused by too high operating temperature, especially on the exit of inductances terminals and on the connections of the fuse holders. 4 Verify the conditions of the surfaces: coatings or other treatments. For static Power Factor correction equipments verify with the same procedure also the efficiency of fans under the heat sinks. TYPE C MAINTENANCE 3.1 First operating year More frequent inspections are suggested compared to the following years, to monitor the adjustment of the equipment during its first operating year. - After 3 months: TYPE A maintenance - After 6 months: TYPE A and TYPE B maintenance - After 9 months: TYPE A maintenance - After 12 months: TYPE A, TYPE B and TYPE C maintenance 3.2 From the second operating year After a first monitoring period of the equipment, from the second year it is recommended to perform maintenance works every 6 months. However, life expectancy of the equipments depends on operating conditions and it is up to the customer the decision to perform more frequent maintenance works in case of more intensive use. For example, in a very wet or polluted setting (powdery, saline, ), more cleaning are necessary, as well as particular temperature conditions or operating conditions of the capacitors at a voltage higher than the nominal one (included within 30%), even if restricted to short time intervals (minutes within 24 hours), leads to a decrease of capacitors life expectancy.
4 - Every 6 months: TYPE A, TYPE B and TYPE C maintenance If after the measure of the electrical absorption on each capacitor bank, measured currents are less than the rated values, it s recommended to perform this type of inspection more frequently than six months. 4. Replacing out of order components If a fault that needs maintenance work occurs, it s important to analyse the power factor correction equipment to ensure its restore and duration. About this, it s not sufficient to replace the faulty element, but it s necessary to verify the status of all the components related to the failure detected. Therefore especially with old equipments it could be necessary to replace all the components (capacitors, contactors etc.), or better replace the entire capacitor bank. Faulty elements (capacitors, fuses, contactors, ) must be replaced with elements of the same type of the original ones. 4.1 Replacing capacitors Before operate make sure that each capacitor is discharged, short-circuiting electrical terminals. If a capacitor out of order is found, it is strongly recommended to replace all the capacitors that belong to the same bank. When a capacitor is replaced also its discharge resistor must be replaced. It s recommended to verify also female Faston. If they are oxidized, or if insertion or disconnection is loose (that is tightening torque of the male Faston is too low), it is recommended to replace also female Faston connectors 6.3mm, better if they have a cog against accidental disconnection. 5. Dismantling and disposal The dismantling must be performed by qualified personnel. All capacitors are PCB free and contain castor oil. Capacitors, components and enclosures disposal must be managed in compliance with the European Directives, and / or in compliance with the local regulations. Comar Condensatori S.p.A. is not responsible for improper disposal, which remains in charge to the owner of the equipment. In the European Countries disposal must be done in compliance with the European Waste identification Code (EWC 2002).
5 Maintenance sheet for a PFC equipment in the 1st year of operation P. F. Correction equipment Identification Number KVAr -.. V check 1 Check of the tightening torque of all power connections Maintenance company External Name.. Internal Department.. Check of the integrity of the protection devices (fuse, varistors of static 2 P. F. correction equipments, ) 3 Cleaning of air ducts of the equipment 4 Cleaning of the cabinet, removing powders or foreign bodies 5 Check of absence of condensation on the live parts of the equipment Check of the integrity of the insulation of the electrical cables and of the 6 auxiliary circuits 7 Check of the correct operation of the regulator 8 Check of capacitor s discharge resistors 9 Check of the overpressure device of each capacitor 10 Check of the current of each bank on each phase Check of the proper operation of the ventilation system and for static P. F. correction equipments check of the efficiency of fans under the heat 11 sinks Check of absence of smut on screws or near the exit terminals of the 12 contactors 13 Check of absence of oxidation and/or corrosion on each component 14 Check of absence of deformities in the insulation of power cables 15 Check of the conditions of surfaces: coatings or other treatments After 3 months After 6 months Supervisor signature Notes In columns Result write OK if maintenance operation is positive, X if maintenance work is necessary. Write down the type of work in the specific column. Column Sign contains the sign of the person who does maintenance works. Column Date contains the execution date of the maintenance operation.
6 check 1 Check of the tightening torque of all power connections 2 Maintenance sheet for a PFC equipment in the 1st year of operation Check of the integrity of the protection devices (fuse, varistors of static P. F. correction equipments, ) 3 Cleaning of air ducts of the equipment 4 Cleaning of the cabinet, removing powders or foreign bodies 5 6 Check of absence of condensation on the live parts of the equipment Check of the integrity of the insulation of the electrical cables and of the auxiliary circuits 7 Check of the correct operation of the regulator 8 Check of capacitor s discharge resistors 9 Check of the overpressure device of each capacitor 10 Check of the current of each bank on each phase Check of the proper operation of the ventilation system and for static P. F. correction equipments check of the efficiency of fans under the heat sinks Check of absence of smut on screws or near the exit terminals of the contactors 13 Check of absence of oxidation and/or corrosion on each component 14 Check of absence of deformities in the insulation of power cables 15 Check of the conditions of surfaces: coatings or other treatments After 9 months After 12 months Supervisor signature Notes In columns Result write OK if maintenance operation is positive, X if maintenance work is necessary. Write down the type of work in the specific column. Column Sign contains the sign of the person who does maintenance works. Column Date contains the execution date of the maintenance operation.
7 Maintenance sheet for a PFC equipment from the 2nd year of operation P. F. Correction equipment - Identification Number KVAr -.. V Maintenance company External Name.. Internal Department.. Every 6 months check Result Sign Date operation Check of the tightening torque of all power connections Check of the integrity of the protection devices (fuse, varistors of static P. F. correction equipments, ) Cleaning of air ducts of the equipment Cleaning of the cabinet, removing powders or foreign bodies Check of absence of condensation on the live parts of the equipment 6 Check of the integrity of the insulation of the electrical cables and of the auxiliary circuits Check of the correct operation of the regulator 7 Check of capacitor s discharge resistors 8 Check of the overpressure device of each capacitor 9 Check of the current of each bank on each phase 10 Check of the proper operation of the ventilation system and for static P. F. correction 11 equipments check of the efficiency of fans under the heat sinks 12 Check of absence of smut on screws or near the exit terminals of the contactors Check of absence of oxidation and/or corrosion on each component 13 Check of absence of deformities in the insulation of power cables 14 Check of the conditions of surfaces: coatings or other treatments 15 Supervisor signature Notes In columns Result write OK if maintenance operation is positive, X if maintenance work is necessary. Write down the type of work in the specific column. Column Sign contains the sign of the person who does maintenance works. Column Date contains the execution date of the maintenance operation.
LENNOX SLP98UHV DIAGNOSTIC CODES
Code Status of Equipment Action required to clear and recover - Idle mode (Decimal blinks at 1 Hertz -- 0.5 second ON, 0.5 second OFF) A Cubic feet per minute (cfm) setting for indoor blower (1 second
More informationDesign Rules for PFC Systems
P o w e r Q u a l i t y S o l u t i o n s www.epcos.com/pfc The collection of PQS is a library with in-depth information on PFC applications, case studies and reference projects. It also serves as a helpdesk
More informationMaintaining electrical equipment/systems
Unit 037 Maintaining electrical equipment/systems Level: 2 Credit value: 15 NDAQ number: 500/9514/6 Unit aim This unit covers the skills and knowledge needed to prove the competences required to cover
More informationQPEO2/037N Credit Value: 15 QCF Level: 2 GLH: 68 Maintaining electrical equipment/systems
Performing Engineering Operations QPEO2/037N Credit Value: 15 QCF Level: 2 GLH: 68 Maintaining electrical equipment/systems Learner Name: 2013 Excellence, Achievement & Learning Ltd EAL Assessment Route
More informationMANUAL DIRECT PURGE OPTION. UNION Instruments GmbH CWD2005 PLUS. General information, safety standards and regulations for direct purge option
MANUAL DIRECT PURGE OPTION UNION Instruments GmbH CWD2005 PLUS General information, safety standards and regulations for direct purge option Version: V1.00 Stand: 24.03.2010 Union Instruments GmbH Zeppelinstr.
More informationMoveRoll Conveyor Operating and Maintenance Manual
MoveRoll Conveyor Operating and Maintenance Manual 1. Read this first! This manual contains information for protection of personnel in the roll handling area from possible injury and/or equipment damage.
More informationGround Fault Circuit Interrupter(GFCI) Policy
NewStar Netronics, LLC American Products for the World Ground Fault Circuit Interrupter(GFCI) Policy 3926 East 3 rd Street Tulsa, OK 74112 Phone (918)894-5006 Fax (918)836-9909 tech@newstarnetronics.com
More informationOperating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073
Operating instructions Safety Rope Emergency Stop Switches UK ZB0052 / ZB0053 ZB0072 / ZB0073 7390878 / 02 03 / 2011 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4
More informationPowerFlex 70/700/753/755 & 1336 Drive Maintenance Schedule (For 24/7 Operation)
PowerFlex 70/700/753/755 & 1336 Drive Maintenance Schedule (For 24/7 Operation) Years 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Commissioning Activities S Air-cooling system Liquid-cooling system
More informationMP15 Jockey Pump Controller
Setup and Operating Instructions MP15 Jockey Pump Controller This manual provides general information, installation, operation, maintenance, and system setup information for Metron Model MP15 Jockey Pump
More informationPre-filter for Brushless Blower Instruction Manual
Pre-filter for Brushless Blower 781-70-702 Instruction Manual Minebea Co., Ltd. Industrial Machinery Business Unit 251-8531 1-1-1 Katase,Fujisawa,kanagawa Contact Us Industrial Machinery Product Sales
More informationInstruction Manual Otoflash G171 UV-flash-device for Light Curing
Instruction Manual Otoflash G171 UV-flash-device for Light Curing Index 1) General Information 2) Initial Operation of Device 3) Important Notes 4) Use with timer 5) Exchanging the flash module 6) Maintenance,
More informationMedium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories
Power Capacitors Catalog Data CA230003EN Supersedes January 2017 COOPER POWER SERIES Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories General
More informationPRAHER PLC-MP AQUASTAR MANAUL 2009
PRAHER PLC-MP AQUASTAR MANAUL 2009 1. Copyrights This Operating Manual contains copyright-protected information. All rights reserved to Praher Kunststofftechnik GmbH. This Operating Manual is designed
More informationErik Backström, High Voltage breakers, After Sales & Service High voltage SF 6 live tank circuit breakers After Sales & Service Training course
Erik Backström, High Voltage breakers, After Sales & Service High voltage SF 6 live tank circuit breakers After Sales & Service Training course description LTB72,5-170 D with BLK222 & FSA1 Level A & B
More informationAE R1 February 2015
February 2015 CoreSense Diagnostics for Copeland Scroll UltraTech Air Conditioning Compressors TABLE OF CONTENTS Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to
More informationProject: Consultant : MEP Contractor: PREPARED BY: DORMAN SMITH SWITCHGEAR - DUBAI REVIEWED BY CONSULTANT : Page 1 of 15
PRCEDURES FR RUTINE TESTING F CAPACITR BANKS Consultant : MEP Contractor: Project: PREPARED BY: DRMAN SMITH SWITCHGEAR - DUBAI NAME: REVIEWED BY CNSULTANT : NAME: SIGNATURE: SIGNATURE: Page 1 of 15 Table
More informationSafety Powder Spray Systems
Instruction Sheet P/N 107 952C Safety Powder Spray Systems 1. Introduction This section contains general safety instructions for using your Nordson equipment. Task- and equipment-specific warnings are
More informationOperating Instructions
ELECTRIC AND GAS FRYER AUTOMATIC BASKET LIFT SYSTEM Operating Instructions 302 Spencer Lane P.O. Box 5369 San Antonio, Texas 78201 (800) 525-8130 (210) 731-5000 Fax: (210) 731-5099 www.ultrafryer.com PREFACE
More informationA4s Operation Manual
A4s Operation Manual Safety Instruction Please read this manual carefully, also with related manual for the machinery before use the controller. For installing and operating the controller properly and
More informationNordel GRID DISTURBANCE AND FAULT STATISTICS
Nordel GRID DISTURBANCE AND FAULT STATISTICS Table contents Table contents Page 1 Introduction... 3 1.1 Contact persons... 4 1.2 Guidelines the statistics... 4 1.3 Voltage levels in the Nordel network...
More informationAQUARIUS. Operating Instructions for the. Type 70 Electrolytic Gas Soldering / Welding Unit. Table of Contents
AQUARIUS Operating Instructions for the Type 70 Electrolytic Gas Soldering / Welding Unit Table of Contents 1. Important General Remarks 2 2. Safety Instructions 2 3. Description of the Soldering Unit
More informationSAFETY PRECAUTIONS FOR THE BLACK BEARD S BEACH WATER PARK
SAFETY PRECAUTIONS FOR THE BLACK BEARD S BEACH WATER PARK The following safety precautions are for the Black Beard s Beach Water Park and are based on the Operations Manual Warranties & As-Builts for the
More informationOperating Instructions
Operating Instructions Light-metal Ex d enclosures / flameproof enclosure > 8265/0 Empty enclosure > 8265/4 Control panel, integrated in Ex e enclosure > 8265/5 Control panel Table of Contents 1 Table
More informationSEMEM3-65 Servicing anaesthetic and ventilation equipment
Overview This unit identifies the competences you need to carry out servicing activities on anaesthetic and ventilation equipment, in accordance with approved procedures. You will be required to service
More informationTROUBLESHOOTING FOR PRO COOLING UNIT
TROUBLESHOOTING FOR PRO COOLING UNIT General maintenance of procool 10 Troubleshooting chart (1) Troubleshooting chart (2) Connector details Water circulation parts Jumpers Contents page GENERAL MAINTENANCE
More informationTWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3
TWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3 The following tasks parallel the Jr. Tech (JT-1, 2, 3) description and development plan and use the Refrigeration and Air conditioning
More informationMAINTENANCE AND OPERATING MANUAL
MAINTENANCE AND OPERATING MANUAL Cyclone condensate separator Type ASA EN EN Maintenance and operating manual Purpose and appropriate use Dear Customer, thank you for choosing our product. In order to
More informationFilm Capacitors Power Factor Correction
Series/Type: Ordering code: Date: November 2009 Version: 2 Content of header bars 1 and 2 of data sheet will be automatically entered in headers and footers! Please fill in the table and then change the
More informationANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS
Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This
More informationAUTOMATIC GAS MANIFOLDS
AUTOMATIC GAS MANIFOLDS Phoenix Pipeline Products Limited. Unit 8, McKenzie Industrial Park, Tel No.: 44 (0) 161 428 7200 Bird Hall Lane, Fax No.: 44 (0) 161 428 7010 Stockport, Email: info@p3-phoenix.com
More informationRPS900W Redundant Power Supply. Installation Guide.
RPS900W Redundant Power Supply Installation Guide www.edge-core.com Installation Guide RPS900W Redundant Power Supply Single DC Output Port with Dual Output Voltages RPS900W E10013-CS-R01 1500000081A
More informationNORDIC AND BALTIC GRID DISTURBANCE STATISTICS 2014
NORDIC AND BALTIC GRID DISTURBANCE STATISTICS 2014 21.10.2015 REGIONAL GROUP NORDIC 1 INTRODUCTION... 4 1.1 DESCRIPTION OF THE REPORT... 4 1.2 CONTACT PERSONS... 5 1.3 VOLTAGE LEVELS IN THE NORDIC AND
More informationFlow controller Type ED/CCB311 Instruction manual
Flow measurement Flow controller Type ED/CCB311 1. GENERAL DESCRIPTION page 4 2. DETAILED DESCRIPTION page 4 3. PIPE - EXPLOITATION page 5 4. PREVENTIVE MAINTENANCE page 5 5. REPLACEMENT OF THE CONTACT
More informationTABLE OF CONTENTS 2 TALAS DRYER 4 TALAS MEASURER 7 TALAS PORTABLE DRYER 9 TALAS LEAKER 11 TALAS STARTER 14 TALAS AUXILIARY 17 APPENDICES
TABLE OF CONTENTS 2 TALAS DRYER 4 TALAS MEASURER 7 TALAS PORTABLE DRYER 9 TALAS LEAKER 11 TALAS STARTER 14 TALAS AUXILIARY 17 APPENDICES ALL PICTURES SHOWN ARE FOR REFERENCE ONLY ACTUAL PRODUCT MAY VARY
More informationReferences 6 k thermal overload relays, adjustable from 0.11 to 16 A
s 6 k thermal overload relays, adjustable from 0.11 to 16 A 3-pole relays with screw clamp terminals These overload relays are designed for the protection of motors. They are compensated and phase failure
More informationACCESSORY KIT INSTALLATION MANUAL
ACCESSORY KIT INSTALLATION MANUAL LP (PROPANE) CONVERSION KIT 1NP0366 FOR USE WITH MODELS: G8C & GF8 This conversion kit shall be installed by a qualified service agency in accordance with these instructions
More informationManual Power relay SR853
Manual Power relay SR853 Rev. 0 SR853 manual page2 Safety Guidelines for explosion proof devices Application and Standards This instruction manual applies to explosion protected control systems of protection
More informationFurther technical information is available on
1 of 5 Manufacture address : Bartec Technor AS Dusavikveien 39 4007 Stavanger Norway Further technical information is available on www.bartec-technor.no Note on instructions When working in hazardous areas,
More informationAIR COMPRESSOR. Failure to follow all instructions as listed below may result in electrical shock, fire, and/or serious personal injury.
2 GALLON AIR COMPRESSOR Model: 7517 DO NOT RETURN TO STORE. Please CALL 800-348-5004 for parts and service. CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or grind materials
More informationRigel 601 CHECKBOX. Instruction Manual. 348A551 Issue 2.0. April Seaward Electronic Ltd. Issue 2.0
Rigel 601 CHECKBOX Instruction Manual 348A551 Issue 2.0 April 2006 2006 Seaward Electronic Ltd. Issue 2.0 Limited Warranty & Limitation of Liability Rigel Medical guarantees this product for a period of
More informationErection, maintenance and disposal Inverted installation. Zinc oxide silicone-housed surge arresters PEXLIM R-X, Q-X and P-X
Erection, maintenance and disposal Inverted installation Zinc oxide silicone-housed surge arresters PEXLIM R-X, Q-X and P-X 1 Important information The following instruction is valid for PEXLIM R-X, PEXLIM
More informationTECHNICAL DATA. TRIMPAC Model B-5 & B-5B
September 16, 2013 Trimpac 250a 1. DESCRIPTION DEsCRIPTIoN is a factory assembled trim package for a ed an electric/pneumatic release module in a metal enclosure. The standard trim normally required on
More information* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22.
*09005087* DB_BA_EN_ME01_S Rev.A 12/16 *09005087* d e v e l o p i n g s o l u t i o n s Data Sheet and Operating Manual ME01 Digital manometer Table of Contents ME01 ## # 87 # HL S#### Dust explosion protection
More informationCP10 Sensor Installation and Maintenance Instructions
4030150/9 IM-P403-26 EMM Issue 9 CP10 Sensor Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Maintenance 5. Spare parts Copyright 2017
More informationMooney * Noise Controller Installation, Operation, and Maintenance Manual
GE Oil & Gas Mooney * Noise Controller Installation, Operation, and Maintenance Manual imagination at work Scope This manual provides instructions for installation, operation and maintenance of the Mooney
More informationVERSION 1 SUMP PUMP PIT UNIT KAWAMOTO PUMP ASIA CO.,LTD.
SUMP PUMP PIT UNIT FEATURES All needed parts are assembled and united as a sump pit and easy to install for short period. Sump tank is made of SUS with epoxy coating and pipe is integrated by stainless
More informationSingle-Phase Pad-Mounted Distribution. Single-Phase Pad-Mounted Distribution Transformers KVA
62-10 Single-Phase Pad-Mounted Distribution Catolog Transformers Section Howard Industries, Inc. Certifi ed to ISO 9001:2015 62-10 Single-Phase Pad-Mounted Distribution Transformers 5-500 KVA 10002179
More informationA4 Operation Manual. Fig.1-1 Controller Socket Diagram
A4 Operation Manual Safety Instruction Please read this manual carefully, also with related manual for the machinery before use the controller. For installing and operating the controller properly and
More informationCOMPRESSOR MANUAL. (888)
COMPRESSOR MANUAL www.ultimadentalsystems.com (888) 900-8584 Table of Contents Introduction..Page 2 Quick Compressor Start Guide....Page 3-5 Compressor Pump Diagram....Page 6 Compressor Frame Diagram....Page
More informationColumbus Instruments
0215-003M Portable O 2 /CO 2 /CH 4 Meter User s Manual Columbus Instruments 950 NORTH HAGUE AVENUE TEL:(614) 276-0861 COLUMBUS, OHIO 43204, USA FAX:(614) 276-0529 1 www.colinst.com TOLL FREE 1-800-669-5011
More informationAC1810 / AC1810-A TECHNICAL SPECIFICATIONS. Operating Pressure psi ( kgs/cm²) [AC1810] Displacement. Net Weight
Technical Specifications Operating Instructions Maintenance Information Troubleshooting Guide Parts Diagrams AC1810 / AC1810-A THE EVOLUTION OF PERFECTION CAUTION: Before attempting to use or service this
More informationTECHNICAL DATA. Trimpac 251a. Spetember 16, 2013
Spetember 16, 2013 Trimpac 251a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-6 and B-6B is a factory assembled trim package for a double interlocked preaction system with an electric/pneu-lectric release
More information! Warning, refer to accompanying documents.
About this Manual To the best of our knowledge and at the time written, the information contained in this document is technically correct and the procedures accurate and adequate to operate this instrument
More informationAirbrush Diaphragm Compressor AS06
Operation Manual Airbrush Diaphragm Compressor AS06 ARTICEL 34200 Read and follow the operating instructions and safety information before using for the first time. Technical changes reserved! Due to further
More informationPORTABLE WORK LIGHT MODEL NO: CL6FS OPERATION INSTRUCTIONS PART NO: GC0315
PORTABLE WORK LIGHT MODEL NO: CL6FS PART NO: 4003530 OPERATION INSTRUCTIONS GC0315 INTRODUCTION Thank you for purchasing this CLARKE Worklight. Before attempting to use this product, please read this manual
More informationINSTRUCTION MANUAL Pressure Relief Device LPT
INSTRUCTION MANUAL Pressure Relief Device LPT 5COV475800 LPT REV00 CONTENT: 1 SAFETY 1.1 Safety instructions 2 1.2 Specified applications 2 1.3 Safety notes on the equipment operation 2 2 PRESSURE RELIEF
More information2-1- Shipping Receiving Lifting Location on Site Installation Stages 6
NEUTRAL GROUNDING RESISTORS INSTALLATION, OPERATION & MAINTENANCE MANUAL Contents 1- SAFETY INSTRUCTIONS... 3 1-1- Compliance with Instructions in this Manual. 3 1-2- Guidance Notes Installation.... 3
More informationUn-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs
Un-Pressurized Orefice Fittings FIO EZ Parts List and Operation Instructions TECHNICAL MANUAL Dn 2-6 Class 150-600 Lbs US US 2 FIO EZ - MT 108-US - 05-2016 FIO EZ Important Instructions US Pietro Fiorentini
More information200 PSI HIGH-FLOW AIR SOURCE KIT
200 PSI HIGH-FLOW AIR SOURCE KIT 50% Duty Compressor on 2.0 Gallon Air Tank PART NO. 20008 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of
More informationAMP Oil Free Manual AMP 50-8-TC AMP 50-6-D AMP General User and Maintenance Instructions
AMP Oil Free Manual AMP 50-8-TC AMP 50-6-D AMP 50-24 General User and Maintenance Instructions Silentaire Technology 8614 Veterans Memorial Dr. Houston, TX 77088 800-972-7668 Fax 832-327-0669 www.silentaire.com
More informationCONFINED SPACE AWARENESS
Document Number: HSE09-001 June 1, 2013 AWARENESS Author: A Holland MAPP Construction - Corporate 344 Third Street Baton Rouge, LA 70801 (225) 757-0111 MAPP Construction - Houston 1511 Katy Freeway, Suite
More informationGSA POLICY ON LOCAL EXHAUST AND OTHER VENTILATION (FUME CUPBOARDS)
GSA POLICY ON LOCAL EXHAUST AND OTHER VENTILATION (FUME CUPBOARDS) Local Exhaust Ventilation Inspection & Maintenance 1 LOCAL EXHAUST AND OTHER VENTILATION Contents 1. Introduction 2. Design specifications
More informationSpiratec ST14, ST16 and ST17 Sensor Chambers and sensors
0862050/1 IM-P086-18 MI Issue 1 Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors Installation and Maintenance Instructions 1. Safety Information 2. General product information 3. Installation 4.
More informationBUZZI UNICEM USA PENSACOLA TERMINAL MILTON, FLORIDA
BUZZI UNICEM USA PENSACOLA TERMINAL MILTON, FLORIDA May, 2017 Infrared Inspection Report Buzzi Unicem Terminal 6266 Da Lisa Road Milton, Florida, 32583 Company Contact Andy Rogers Project: 04110517 2605
More informationOperating instructions. Surge arrester Type MVR
Operating instructions Surge arrester Type MVR Content 1 About this document...3 1.1 Validity...3 1.2 Target group...3 2 Safety...3 2.1 Symbols and advices...3 2.2 Basic safety precautions...4 2.2.1 Product
More informationBest Practice for Calibrating LTH Conductivity Instruments
Application Note Best Practice for Calibrating LTH Conductivity Instruments As accurate process measurement becomes an everyday requirement it is vital to be able to calibrate conductivity instruments
More informationSM6. instructions for use. connection with compartment for incoming cable from the top. MV distribution factory built assemblies at your service
SM6 Anglais MV distribution factory built assemblies at your service instructions for use connection with compartment for incoming cable from the top foreword... 3 symbols and conventions... 3 as per iso
More informationA32W PRO ROBOT. User Manual. paddlepalace.com P P
A32W PRO ROBOT paddlepalace.com P 1-800-547-5891 P 503-777-2266 Paddle Palace A32W Pro P Two throw wheels, for multiple spin options P Multiple Oscillation Options P Very durable, made with high quality
More informationOperating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL
Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. Table of Contents
More informationOperating Instructions
Operating Instructions Ex d Enclosures in Light Metal / Flameproof Encapsulation > 8265/0 Empty Enclosure > 8265/4 controller, installed in Ex e enclosure > 8265/5 controller Contents 1 Contents 1 Contents...2
More informationPreparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable
GEP-6075 Rev. B 101574 Ref. I.D.: 16973 Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable WARNING USER SHOULD READ AND THOROUGHLY UNDERSTAND THESE
More informationWater Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems
Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems Name of Property: Address: Phone Number: Inspector: Contract No.: Date: This Report Covers: Monthly Quarterly Annual Other
More informationRoller AC Servo System
Safely Instruction Roller AC Servo System HMI-15 User Manual Please read this manual carefully, also with related manual for the machinery before use the controller. For installing and operating the controller
More informationGovernment of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE
Government of Bermuda Department of Maritime Administration 2015 027 BERMUDA SHIPPING NOTICE Maintenance and Inspection of Fixed Carbon Dioxide Fire Extinguishing Systems Ref: SOLAS 74/88 as amended, Regulation
More informationArran LED Floodlight Luminaire
Arran LED Floodlight Luminaire INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Important: Please read these instructions carefully before installing or maintaining this equipment. Good electrical
More informationElectrical, electronic and control engineering at the operational level
STCW Code Table A-III/6 Specification of minimum standard of for electro-technical officers Ref: https://www.edumaritime.net/stcw-code Source: IMO Function: Electrical, electronic and control engineering
More informationUSER S MANUAL BASIC HORIZONTAL OIL-LUBRICATED MICROCOMPRESSOR Reference: RCMPBH
USER S MANUAL BASIC HORIZONTAL OIL-LUBRICATED MICROCOMPRESSOR Reference: RCMPBH THIS MANUAL IS INTENDED FOR TECHNICAL STAFF IN CHARGE OF THE INSTALLATION, THE OPERATION AND THE MAINTENANCE OF THIS PRODUCT
More informationTEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125
TEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125 Model: VC-40-VYC Table of contents 1. - Installing the test bench 1.1.1- Connecting the compressed air / nitrogen source 1.1.2- Maximum test pressure according
More informationOperating Instructions of BROSA tension load cells, types 0111, 0113
Operating Instructions of BROSA tension load cells, types 0, 03. Description of BROSA tension load cells. Structure and function The BROSA type 0 and 03 tension load cells transmit and measure the tensile
More informationMAINTENANCE RECOMMENDATIONS
MAINTENANCE RECOMMENDATIONS COOLING SYSTEM: Very high secondary currents are developed in resistance welding equipment. This, coupled with compact design, high upset temperatures, and fast cycle times,
More informationR E D I C O N T R O L S
R E D I C O N T R O L S Operation & Maintenance Manual Portable Service Purger for Low Pressure Chillers Model: PSP-LP-1B For Refrigerants R-11, R-113, R-114 & R-123 & Other Similar Refrigerants File Literature
More informationSYSCO ST JOHN'S MOUNT PEARL, NEWFOUNDLAND
SYSCO ST JOHN'S MOUNT PEARL, NEWFOUNDLAND October, 2016 Infrared Inspection Report Sysco St. John s 10 Old Placentia Road Mount Pearl, NF A1N 4P5 Company Contact: David Shaw Project: C261016 2605 CHARTER
More informationMODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank
IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock or Electrocution: MODEL NUMBER: 20008 200 PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank IMPORTANT: It is
More informationTo Loughborough University (LU) Facilities Management (FM) Health and Safety Policy
Annex I To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance 1. Introduction a. These Safety
More informationHydro Dome GRUNDFOS INSTRUCTIONS
GRUNDFOS INSTRUCTIONS Hydro Dome Installation and operating instructions Montage- und Betriebsanleitung Notice d installation et d entretien Istruzioni di installazione e funzionamento Instrucciones de
More information97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO
97C COMPRESSOR KIT 12V PART NO. 00097 97C COMPRESSOR KIT 24V PART NO. 02497 98C COMPRESSOR KIT PART NO. 00098 97C 98C IMPORTANT: It is essential that you and any other operator of this product read and
More information3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289
3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for
More informationMODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE
MODEL NUMBER: M20005 AIR SOURCE KIT 30% Duty Compressor on 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE USER MANUAL IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock
More informationCFSW. Hinges with built-in safety multiple switch
CFSW. Hinges with built-in safety multiple switch ELESA Original design Elesa Standards Main dimensions Fitting Weight Code Description L B f ±0.2 f 1 ±0.2 H h 1 h 2 d 3 d 4 C [Nm]# g 426601 CFSW.110-6-2NO+2NC-C-A
More informationElectro-Pneumatic Converter YT-940 SERIES
Electro-Pneumatic Converter YT-940 SERIES PRODUCT MANUAL VERSION 1.00 Contents 1. Introduction 3 1.1 General information for the users. 3 1.2 Manufacturer Warranty 3 1.3 Explosion Proof Warning. 4 2. Product
More information200 PSI FAST-FILL AIR SOURCE KIT
200 PSI FAST-FILL AIR SOURCE KIT 55% Duty Compressor on 2.0 Gallon Air Tank PART NO. 20007 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of
More informationThese Instructions apply to all low-voltage installations where Operations Manager HV in Statnett has authority as Operations Manager LV.
Based on the Norwegian document number 1172636 rev. 15 Page: 1 of 7 1 Governing policy and legislation Instruction related to work on or in the vicinity of low-voltage installations are subordinate to
More informationAutoChanger Installation & User Guide Issue 2
1 INDEX Page 1. Introduction... 3 2. AutoChanger Components Guide 4 3. Installation. 5-11 a) Installation Guidelines.. 5 b) Installation Retrofit... 6-11 c) Installation New... 11 4. AutoChanger User Guide
More informationMinimum standard of competence for electro-technical officers (STCW Reg III/6) Electrical, electronic and control engineering at the operational level
Minimum standard of for electro-technical officers (STCW Reg III/6) Function: Electrical, electronic and control engineering at the operational level Monitor the Basic understanding of the Examination
More informationOperating Manual. R280 Pressure regulator made of brass. 1. Intended Use
Pressure regulator made of brass Operating Manual 1. Intended Use Line or outlet pressure regulators- /reducer for Air, gases and liquids which is designed to effect reduction to a downstream pressure
More informationTECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1
Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a
More informationType CAP. CapSwitcher. Capacitor Switching Device kv 38 kv INSTALLATION & INSTRUCTION MANUAL
Type CAP CapSwitcher Capacitor Switching Device 15.5 kv 38 kv INSTALLATION & INSTRUCTION MANUAL Safety Information DANGER THE EQUIPMENT COVERED IN THIS MANUAL SHOULD BE HANDLED, INSTALLED, AND MAINTAINED
More informationSafe Schools: A Health and Safety Check
Name of School: Optional Information Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: Use of Electrical Equipment Self-Inspection Checklist Guidelines: This checklist covers
More informationSUBSTATION MAINTENANCE ELECTRICAL OPERATING PROCEDURE
Page 1 of 6 A. PURPOSE AND SCOPE This procedure establishes safe working practices for handling sulfur hexafluoride (SF 6 ) gas and release minimization practices. This document also specifies methods
More information