INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS
|
|
- Sherilyn Elliott
- 5 years ago
- Views:
Transcription
1 INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR WATER HEATER SUPPLY SHUTOFF VALVE WITH A / THERMAL EXPANSION CONTROL VALVE IGC a8 1. PURPOSE 1.1 The purpose of this standard is to establish an acceptable minimum standard for water heater supply shutoff valve with a / thermal expansion control valves. Its purpose is to serve as a guide for producers, distributors, architects, engineers, contractors, installers, inspectors and users; to promote an understanding regarding materials, manufacture and installation; and to provide for identifying thermal expansion control devices that conform to this standard. 1.2 The provisions of this standard are not intended to prevent the use of any alternate material or method of construction, provided any such alternate meets the intent and requirements of this document and changes are amended to this standard. 2. SCOPE 2.1 This standard covers the test methods and performance requirements applicable for water heater supply shutoff valve with a / thermal expansion control valves for use on closed plumbing systems. 3. REFERENCE STANDARDS 3.1 All standards referenced herein shall be the current edition of that standard. IAPMO IGC 85 IAPMO IGC 157 MSS-SP-25 MSS-SP-110 Thermal Expansion Relief Valves Ball Valves Standard Marking System for Valves, Fittings, Flanges and Unions Ball Valves Threaded, Socket-Welding, Solder Joint, Grooved and Flared Ends 4. DEFINITIONS 4.1 Thermal Expansion Control Valve. An auxiliary device used to control thermal expansion in a closed plumbing system that is used in conjunction with a thermal expansion relief valve. Copyright 2006 by International Association of Plumbing and Mechanical Officials. All rights reserved. Printed in the United States of IGC a Wtr Htr Shtoff 1 of 3
2 4.2 Thermal Expansion Relief Valve. A safety device used to provide overpressure protection in a closed plumbing system. 4.3 Thermal Relief Pressure. The internal pressure at which the thermal expansion control valve begins to relieve pressure to control thermal expansion in a closed plumbing system. 4.4 Set Pressure. The pressure at which a thermal expansion relief valve is designed to relieve pressure from a water supply system. 5. GENERAL REQUIREMENTS 5.1 The water heater supply shutoff valve with a /thermal expansion control valve shall consist of a ball valve with integral thermal expansion control valve. The water heater supply shutoff valve with a /thermal expansion control device shall be constructed to provide thermal expansion relief at a pressure of 25 psig or more below the manufacturer s set pressure rating of the primary thermal expansion relief valve defined in IAPMO IGC The supply shutoff valve shall meet the design and testing requirements of MSS- SP-110 or IGC 157. Production testing shall be performed prior to integration of the thermal expansion control valve End connections such as threaded, socket-welding, solder joint, grooved and flared end shall comply with the requirements in MSS-SP-110 or IGC 157. Alternative end connections shall comply with the applicable ASTM standard. 5.3 The thermal expansion control valve shall be of a spring loaded check design. The drainage fitting may be supplied by the manufacturer. The minimum orifice diameter of the drainage fitting shall be inch. Production testing shall be performed prior to integration with the shutoff valve. 5.4 Materials. The valve body and its operating parts shall be made of compatible corrosion resistant materials. An internal spring used in the thermal expansion control valve shall be made of material having corrosion resistance equal to that of AISI 302 stainless steel. 5.5 Drainage pipe or tube shall be piped in a vertical or downward sloping position to a suitable drain and shall terminate at least 3 inches above the drain. As an alternate, an air gap may be installed at the outlet of the thermal expansion control valve. The minimum internal diameter of the drainage pipe or tubing shall be inch. 5.6 Representative samples of the water heater supply shutoff valve with a /thermal expansion control valve shall be subjected to the tests described in these requirements. Copyright 2006 by International Association of Plumbing and Mechanical Officials. All rights reserved. Printed in the United States of IGC a Wtr Htr Shtoff 2 of 3
3 6. PERFORMANCE REQUIREMENTS 6.1 Hydrostatic Test. The water heater shutoff/thermal expansion control valve shall withstand for one (1) minute, without leakage, an internal hydrostatic pressure equal to 90% of the thermal relief pressure setting Thermal Relief Test. The valve shall be installed in a test fixture simulating a closed piping system with a thermal expansion relief valve. The media shall be water. All air is to be removed from the system. Raise the internal pressure in the valve equal to 90% of the thermal relief pressure setting. Valve shall not leak when held for (1) minute. Continue to raise water pressure The water is to be slowly heated until the thermal expansion control valve begins to relieve pressure, indicated by dripping or flow from the thermal expansion control valve. The thermal relief pressure of the valve is to be within ±10% of the thermal relief pressure setting on the valve. The test water temperature may not exceed 190 F Cycle Test. A thermal expansion control valve set at 125 psig shall be connected to a water supply and pressurized to 140 psig at ambient temperature. The pressure shall be reduced until the valve reseats and seals. A method shall be employed to activate the assembly for 10,000 cycles. There shall be no signs of failure or leakage during the cycle test. 7. MARKING AND IDENTIFICATION 7.1 Valves shall be permanently marked or tagged with the following: (d) (e) (f) Manufacturer's name or trademark; nominal size of shutoff valve; model number; set pressure and maximum temperature rating; a flow arrow indicating direction of flow for the shutoff valve; the words If control valve fails, discard and replace with new control valve 7.2 Installation Instructions Each valve shall be provided with installation instructions that contain the following: a statement prohibiting threads at the discharge end of the relief line, a statement requiring the discharge line to be secured to prevent movement of the line during discharge, a statement requiring that the drainage line be piped independently of the of the water heater relief valve drain. Accepted: 6/98 Revised 1/2000, 4/2002, 10/2006, 12/2006 Copyright 2006 by International Association of Plumbing and Mechanical Officials. All rights reserved. Printed in the United States of IGC a Wtr Htr Shtoff 3 of 3
4 INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR WATER HEATER SUPPLY SHUTOFF VALVE WITH A THERMAL EXPANSION CONTROL VALVE IGC PURPOSE 1.1 The purpose of this standard is to establish an acceptable minimum standard for water heater supply shutoff valve with a thermal expansion control valves. Its purpose is to serve as a guide for producers, distributors, architects, engineers, contractors, installers, inspectors and users; to promote an understanding regarding materials, manufacture and installation; and to provide for identifying thermal expansion control devices that conform to this standard. 1.2 The provisions of this standard are not intended to prevent the use of any alternate material or method of construction, provided any such alternate meets the intent and requirements of this document and changes are amended to this standard. 2. SCOPE 2.1 This standard covers the test methods and performance requirements applicable for water heater supply shutoff valve with a thermal expansion control valves for use on closed plumbing systems. 3. REFERENCE STANDARDS 3.1 All standards referenced herein shall be the current edition of that standard. IAPMO IGC 157 MSS-SP-25 MSS-SP-110 Ball Valves Standard Marking System for Valves, Fittings, Flanges and Unions Ball Valves Threaded, Socket-Welding, Solder Joint, Grooved and Flared Ends 4. DEFINITIONS 4.1 Thermal Expansion Control Valve. An auxiliary device used to control thermal expansion in a closed plumbing system that is used in conjunction with a thermal expansion relief valve. Copyright 2008 by International Association of Plumbing and Mechanical Officials. All rights reserved. Printed in the United States of IGC Wtr Htr Shtoff 1 of 3
5 4.2 Thermal Expansion Relief Valve. A safety device used to provide overpressure protection in a closed plumbing system. 4.3 Thermal Relief Pressure. The internal pressure at which the thermal expansion control valve begins to relieve pressure to control thermal expansion in a closed plumbing system. 4.4 Set Pressure. The pressure at which a thermal expansion relief valve is designed to relieve pressure from a water supply system. 5. GENERAL REQUIREMENTS 5.1 The water heater supply shutoff valve with a thermal expansion control valve shall consist of a ball valve with integral thermal expansion control valve. The water heater supply shutoff valve with a thermal expansion control device shall be constructed to provide thermal expansion relief at or below the manufacturer s set pressure rating. 5.2 The supply shutoff valve shall meet the design and testing requirements of MSS- SP-110 or IGC 157. Production testing shall be performed prior to integration of the thermal expansion control valve End connections such as threaded, socket-welding, solder joint, grooved and flared end shall comply with the requirements in MSS-SP-110 or IGC 157. Alternative end connections shall comply with the applicable ASTM standard. 5.3 The thermal expansion control valve shall be of a spring loaded check design. The drainage fitting may be supplied by the manufacturer. The minimum orifice diameter of the drainage fitting shall be inch. Production testing shall be performed prior to integration with the shutoff valve. 5.4 Materials. The valve body and its operating parts shall be made of compatible corrosion resistant materials. An internal spring used in the thermal expansion control valve shall be made of material having corrosion resistance equal to that of AISI 302 stainless steel. 5.5 Drainage pipe or tube shall be piped in a vertical or downward sloping position to a suitable drain and shall terminate at least 3 inches above the drain. As an alternate, an air gap may be installed at the outlet of the thermal expansion control valve. The minimum internal diameter of the drainage pipe or tubing shall be inch. 5.6 Representative samples of the water heater supply shutoff valve with a thermal expansion control valve shall be subjected to the tests described in these requirements. 6. PERFORMANCE REQUIREMENTS Copyright 2008 by International Association of Plumbing and Mechanical Officials. All rights reserved. Printed in the United States of IGC Wtr Htr Shtoff 2 of 3
6 6.1 Thermal Relief Test. The valve shall be installed in a test fixture simulating a closed piping system with a thermal expansion relief valve. The media shall be water. All air is to be removed from the system. Raise the internal pressure in the valve equal to 90% of the thermal relief pressure setting. Valve shall not leak when held for (1) minute. Continue to raise water pressure until the thermal expansion control valve begins to relieve pressure, indicated by dripping or flow from the thermal expansion control valve. The thermal relief pressure of the valve is to be within ±10% of the thermal relief pressure setting on the valve. The test water temperature may not exceed 190 F. 6.2 Cycle Test. A thermal expansion control valve set at 125 psig shall be connected to a water supply and pressurized to 140 psig at ambient temperature. The pressure shall be reduced until the valve reseats and seals. A method shall be employed to activate the assembly for 10,000 cycles. There shall be no signs of failure or leakage during the cycle test. 7. MARKING AND IDENTIFICATION 7.1 Valves shall be permanently marked or tagged with the following: (d) (e) (f) Manufacturer's name or trademark; nominal size of shutoff valve; model number; set pressure and maximum temperature rating; a flow arrow indicating direction of flow for the shutoff valve; the words If control valve fails, discard and replace with new control valve 7.2 Installation Instructions Each valve shall be provided with installation instructions that contain the following: a statement prohibiting threads at the discharge end of the relief line, a statement requiring the discharge line to be secured to prevent movement of the line during discharge, a statement requiring that the drainage line be piped independently of the of the water heater relief valve drain. Accepted: 6/98 Revised 1/2000, 4/2002, 10/2006, 12/2006, 1/2008 Copyright 2008 by International Association of Plumbing and Mechanical Officials. All rights reserved. Printed in the United States of IGC Wtr Htr Shtoff 3 of 3
IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC PURPOSE
INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC 157-20067 1 PURPOSE 1.1 The purpose of this standard is to establish an acceptable standard
More informationPresented to the IAPMO Standards Review Committee on March 7, 2016
Summary of Substantive Changes between the 2015 edition of ASSE 1070/ASME A112.1070/CSA B125.70, Water Temperature Limiting Devices, the 2004 edition of ASSE 1070, Water Temperature Limiting Devices, and
More informationAmerican Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM
American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1048 - REVISED: 2009 Double Check Detector Fire Protection Backflow Prevention Assemblies Separate, complete laboratory
More informationASSE International Product (Seal) Listing Program
ASSE International Product (Seal) Listing Program ASSE 1070-2015 / ASME A112.1070-2015 / CSA B125.70-15 Performance Requirements for Water Temperature Limiting Devices Manufacturer: Contact Person: E-mail:
More informationModel MTB-ASME Vertical Bladder Tanks
DATA SHEET Model MTB-ASME Vertical Bladder Tanks Features n UL Listed for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationHorizontal Bladder Tanks
DATA SHEET Horizontal Bladder Tanks Features UL Listed and FM Approved for use with various ANSUL proportioners and foam concentrates 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationVertical Bladder Tanks
DATA SHEET Vertical Bladder Tanks Features UL Listed and FM Approved for use with various ANSUL proportioners and foam concentrates 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationModel MTB-ASME Vertical Bladder Tanks
DATA SHEET Model MTB-ASME Vertical Bladder Tanks Features n UL Listed for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationModel MTB-ASME Horizontal Bladder Tanks
DATA SHEET Model MTB-ASME Horizontal Bladder Tanks Features n UL Listed and FM Approved for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure
More informationSECTION DOMESTIC WATER PIPING
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Specification Sections, apply to this Section. B. Related Sections
More informationINTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS MATERIAL AND PROPERTY STANDARD FOR
INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS MATERIAL AND PROPERTY STANDARD FOR SPECIAL USE SUCTION FITTINGS FOR SWIMMING POOLS, SPAS AND HOT TUBS (FOR SUCTION SIDE AUTOMATIC SWIMMING
More informationMSC Guidelines for Refrigeration Machinery
Procedure Number E1-32 Revision Date: 07/27/10 S. J. Kelly, CDR, Chief of Engineering Division References: a. 46 CFR Part 56.50-105 Low Temperature Piping b. 46 CFR Part 58.20 Refrigeration Machinery c.
More informationASSE International Product (Seal) Listing Program. ASSE Performance Requirements for Air Valve and Vent Inflow Preventer
ASSE International Product (Seal) Listing Program ASSE 1063-2016 Performance Requirements for Air Valve and Vent Inflow Preventer Manufacturer: Contact Person: E-mail: Address: Laboratory: Laboratory File
More informationAmerican Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM
American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1019 - REVISED: 2011 Wall Hydrant with Backflow Protection and Freeze Resistance MANUFACTURER: CONTACT PERSON: E-MAIL:
More informationHYDROSTATIC LEAK TEST PROCEDURE
This information is proprietary and shall not be disclosed outside your organization, nor shall it be duplicated, used or disclosed for purposes other than as permitted under the agreement with Kinetics
More information1200B2 Series Service Regulators. Instruction Manual
00B Series Service Regulators Instruction Manual 00B Series Service Regulators 0 Elster American Meter 00B Series Service Regulators General Information The 00B Series Service Regulators are available
More informationSummary of Substantive Changes between the 2012 and 2018 editions of CSA B125.3 Plumbing Fittings
Summary of Substantive Changes between the 2012 and 2018 editions of CSA B125.3 Plumbing Fittings Presented to the IAPMO Standards Review Committee on October 15, 2018 General: The changes to this standard
More information1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor)
1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1. According to NFPA 99, SCFM is an acronym for. a) Surface Conditions at Fahrenheit Mercury b) Standard Conditions
More informationTECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE
1 of 10 1. DESCRIPTION (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system
More informationAmerican Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM
American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1003 - REVISED: 2009 Water Pressure Reducing Valves for Domestic Water Distribution Systems MANUFACTURER: CONTACT
More informationFluid Sealing Association
Fluid Sealing Association STANDARD FSA-PSJ-701-06 PIPING SYSTEMS NON-METALLIC EXPANSION JOINT HYDROTESTING AND VACUUM TESTING 994 Old Eagle School Road, Suite 1019 Wayne, Pennsylvania 19087-1866 Phone:
More informationASSE International Product (Seal) Listing Program
Manufacturer Contact Person Address ASSE International Product (Seal) Listing Program ASSE 07-05 / ASME A.9.07-05 / CSA B5.7-5 Pressurized Flushing Devices for Plumbing Fixtures Laboratory File Number
More informationANDERSON GREENWOOD SERIES 9000 POSRV INSTALLATION AND MAINTENANCE INSTRUCTIONS
Procedure-assembly-functional test and performance requirements 1 SCOPE 1.1 This document establishes the general procedure for assembly, functional testing and normal performance requirements of low Series
More information1800C and 1800C-HC Series Service Regulators
1800C and 1800C-HC Series Service Regulators Installation Instructions www.elster-americanmeter.com General Information: The 1800C and 1800C-HC Regulators are available as Full Capacity Internal Relief
More informationOPERATING AND MAINTENANCE MANUAL
Series 4300 Engineered Performance TABLE OF CONTENTS 0 INTRODUCTION 1 1 Scope 1 2 Description 1 3 Specifications 1 0 INSTALLATION 1 1 Mounting 1 2 Piping 1 1 Connecting Process Pressure 2 2 Vent Connections
More informationCombination Air Valve
Combination Air Valve For Sewage and Wastewater Model C50 Installation, Operation and Maintenance Manual (IOM) Table of Contents General... Page 2 Safety... Page 2 Operational Data... Page 3 Materials
More informationType 1367 High-Pressure Instrument Supply System with Overpressure Protection
Instruction Manual D100343X012 Type 1367 November 2017 Type 1367 High-Pressure Instrument Supply System with Overpressure Protection TYPE 252 FILTER 2ND-STAGE TYPE 67CF FILTER-STYLE REGULATOR INLET TYPE
More informationTECHNICAL DATA. Q = C v P S
January 6, 2012 Preaction 333a 1. Description Viking supervised Surefire Preaction Systems Utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated Viking G-3000P Valve comes complete
More informationBERMAD Waterworks. Combination Air Valve. Air Valves Series. Typical Applications. Features & Benefits. Additional Features.
BERMA Waterworks Combination Air Valve Model C7 BERMA C7 is a high quality combination air valve for a variety of water networks and operating conditions. It evacuates air during pipeline filling, allows
More information1 Exam Prep. Tabs and Highlights
1 Exam Prep NFPA 14: Standard for the Installation of Standpipe and Hose Systems Tabs and s These 1 Exam Prep tabs are based on the NFPA 14: Standard for the Installation of Standpipe and Hose Systems,
More informationTECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1
November 30, 1994 534 a 1. PRODUCT NAME VIKING 2" (50mm), 3" (75mm), 4" (100mm), 6" (150mm) 2. MANUFACTURER THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone:
More informationType S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual
Fisher Controls Instruction Manual Type S301 & S302 Gas Regulators October 1981 Form 5180 WARNING Fisher regulators must be installed, operated, and maintained in accordance with federal, state, and local
More informationSTANDARD SPECIFICATION FOR SPLIT TEES (HOT TAP MATERIAL)
STANDARD SPECIFICATION FOR SPLIT TEES (HOT TAP MATERIAL) TEE (HOT TAPPING MATERIAL) S-04-02-040 Page 1 of 7 1.0 SCOPE This specification covers the basic requirements for the design, manufacture and supply
More informationSmart Water Application Technologies (SWAT) TM
Smart Water Application Technologies (SWAT) TM Equipment Functionality Test Protocol Version 2.3 June 2014 SWAT Committee 8280 Willow Oaks Corporate Drive Suite 400 Fairfax, VA 22031 www.irrigation.org
More informationSABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company
CIF A Tyco International Company 1 Foam Concentrate CIF 3% AFFF -UL Listed -UL Canada Listed 6% AFFF 6 parts AFFF concentrate to 94 parts water -UL Listed- Foam Liquid -UL Canada Listed 3% FLUOROPROTEIN
More informationSeries 8500 Expansion Compensators. Catalog 674H
Series 8500 Expansion Compensators Catalog 674H 500 Laminated Bellows Expansion J Series 8500 on Joints Expansion Compensators Sizes 3/4" through 4" Threaded, welded, flanged and grooved steel pipe joints
More informationWSC Performance Standard and Recommended Installation Procedures for Sanitary Water Well. Pitless Adapters, Pitless Units, And Well Caps
WSC Performance Standard and Recommended Installation Procedures for Sanitary Water Well Pitless Adapters, Pitless Units, And Well Caps History of the WSC PAS Standard he Water Systems Council (WSC) has
More informationAmerican Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM
American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1018 - REVISED: 2001 Trap Seal Primer Valves - Potable Water Supplied MANUFACTURER: CONTACT PERSON: E-MAIL: ADDRESS:
More informationTypes S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device
Instruction Manual Form 5492 Types S108K and S109K May 1999 Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device Introduction Fisher regulators must be installed, operated
More informationTECHNICAL DATA Q= C. Table 1 - Specifications
September 25, 2013 Pressure Regulation 537a 1. Description The Model B-3 Pilot Operated Pressure Control Valve is a factory assembled unit. The unit consists of a Model J-2 Halar coated Flow Control Valve,
More informationWATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity
WATER HEATER THERMAL EXPANSION TANKS Owner s Manual Safety Instructions Installation Maintenance Warranty Models: 2-5 Gallon Capacity Thank You for purchasing this Thermal Expansion Tank. Properly installed
More informationR600 and HSRL Series Instruction Manual
Instruction Manual MCK 2141 November 2009 R600 and HSRL Series Instruction Manual! Warning Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion
More informationTECHNICAL DATA. Q = C v P S
January 6, 2012 Preaction 348a 1. Description Viking supervised Surefire Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated Viking G-6000P Valve comes complete
More informationR122H, R222, R232A, and R232E Series Instruction Manual
Instruction Manual MCK 2156 R122H, R222, R232A, and R232E Series October 2012 R122H, R222, R232A, and R232E Series Instruction Manual Failure to follow these instructions or to properly install and maintain
More information29 SERIES - SAFETY VALVE
INDUSTRIES, INC. 29 SERIES - SAFETY VALVE INSTALLATION, OPERATION, & MAINTENANCE Part I Document Number: ES1016-1 Revision Level: A Issued By: David Edmonds Date: 6/20/04 Approved By: Date: 10/4/04 Conbraco
More informationPIP PNE00012 Piping Examination and Leak Test Guide
October 2017 Piping PIP PNE00012 Piping Examination and Leak Test Guide PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has
More informationSummary of Substantive Changes between the 2004 e1 and 2017 editions of ASSE 1011, Hose Connection Vacuum Breakers
Summary of Substantive Changes between the 2004 e1 and 2017 editions of ASSE 1011, Hose Connection Vacuum Breakers Presented to the IAPMO Standards Review Committee on October 15, 2018 General: The changes
More informationCOMMITTEE DRAFT. API 520 Part I 10 th Edition Ballot Item 2.1. This ballot covers the following item:
This ballot covers the following item: API 520 Part I 10 th Edition Ballot Item 2.1 2008 12 Modify guidance to PRV datasheets (Line 17) to assist user s with determining the temperature to use for selecting
More informationTECHNICAL DATA. Q = C v P S
January 6, 2012 Preaction 347a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated
More informationWHEATLEY Series 822/820 Swing Check Valve
Document Number: TC003001-12 Revision: 02 WHEATLEY Series 822/820 Swing Check Valve Installation, Operation, and Maintenance Manual TABLE OF CONTENTS BILL OF MATERIALS...3 SCOPE...4 INSTALLATION AND OPERATION
More informationv. Size shall be specified on drawings.
SPECIFICATION FOR VACUUM INSULATED PIPING Part 1 General 1. Submittals a. After award of contract and before executing any manufacturing, shop drawings and specifications shall be submitted to the customer
More informationa pilot sprinkler were to be closed after its initial operation, for example a remote manual control station).
Technical Services: Tel: (800) 8-9 / Fax: (800) 9-00 Model DV- Deluge Valve, Diaphragm Style, -/ thru 8 Inch (DN40 thru DN00), Deluge System Dry Pilot Actuation General Description The Model DV- Deluge
More informationVERTICAL BLADDER TANK
Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Tight Spaces UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure
More informationWHEATLEY Series 500 Swing Check Valve
Document Number: TC003001-13 Revision: 02 WHEATLEY Series 500 Swing Check Valve Installation, Operation, and Maintenance Manual TABLE OF CONTENTS BILL OF MATERIALS...3 SCOPE...5 INSTALLATION AND OPERATION
More informationHORIZONTAL BLADDER TANK
Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Low Ceilings UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure
More informationTECHNICAL DATA OBSOLETE
April 9, 2009 Preaction 326a 1. DESCRIPTION Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilizing the Viking G-4000P Deluge Valve. The small profi le, lightweight,
More informationWet pipe low flow foam/water system
December 6, 2010 Foam 14a 1. The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with Viking supplied foam concentrates. This system consists of a standard
More informationMEGR-1912 Instruction Manual
MEGR-1912 PRESSURE REGULATOR Instruction Manual- Look Inside For: Description Installation Start-Up Maintenance Parts Ordering Parts List Marshall Excelsior Company Marshall, MI 49068 269-789-6700 FAX
More informationEnd Connection. Thread x Thread N/A N/A N/A N/A Flange x Flange N/A
Worldwide Contacts www.tyco-fire.com Model RV-1 Pressure Relief Valve, Pilot-Operated, Globe and Angle Body Styles General Description Valves, through inch (DN50 through DN00), are factory assembled and
More information64 Series Pressure Reducing Regulators
Instruction Manual Form 1245 64 Series March 2006 64 Series Pressure Reducing Regulators W1943 Figure 1. 64 Series Regulator Introduction Scope of Manual This manual provides instructions for the installation,
More informationVALVE MANUFACTURERS ASSOCIATION API 622 API 624
VALVE MANUFACTURERS ASSOCIATION API 622 API 624 Written by Rich Davis Manager Business Development Western Hemisphere & China Flexitallic L.P., Deer Park, Texas Presented By: Steve Butler, Shell Global
More informationInstallation Operation Maintenance
682 Seal Cooler New generation seal cooler to meet and exceed the seal cooler requirements stated in the 4th Edition of API Standard 682 Installation Operation Maintenance Experience In Motion Description
More informationNoth American 7347 High Pressure Gas Regulators
Combustion Noth American 7347 High Pressure Gas s Bulletin 7347 7347 s reduce high gas supply pressures to practical use levels. Since capacities will vary with the pressure drop across the regulator (see
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 33 1000 - WATER DISTRIBUTION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationTypes S100K and S102K Pressure Regulators
Instruction Manual Form 5624 Types S0K and S2K 01/01 Types S0K and S2K Pressure Regulators W7478-1 Figure 1. Types S0K and S2K Pressure Regulator Introduction Scope of Manual This manual provides instructions
More informationBall Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65
Data Sheet 819346-02 Issue Date: 05/17 Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300, 50, 65 UNA 45hl MAX, UNA 46hl MAX, UNA 46Ahl MAX UNA 45v MAX with cover for mounting electrode
More informationTECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)
Page 1 of 8 1. DESCRIPTION The Viking Model F-1 Deluge Valve is a quick opening, differential diaphragm, flood valve with one moving mechanism. The Deluge Valve is used to control water flow in Deluge
More information299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012
Installation Guide English September 2012 299H Series Introduction This Installation Guide provides instructions for installation, startup, and adjustment of 299H Series regulators. To receive a copy of
More informationSERIES SAFETY VALVE
R Manufactured by Conbraco Industries, Inc. 10-600 SERIES SAFETY VALVE INSTALLATION, OPERATION, & MAINTENANCE Part I Document Number: ES-1325 Revision Level: B Issued By: T.HAMILTON Date: 3/3/16 Approved
More informationPreparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable
GEP-6075 Rev. B 101574 Ref. I.D.: 16973 Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable WARNING USER SHOULD READ AND THOROUGHLY UNDERSTAND THESE
More informationTECHNICAL DATA. Table 1 - Specifications
Page 1 of 6 1. DESCRIPTION Model A-3 Pilot Operated Pressure Control Valves are factory assembled units. Each unit consists of a Model H-2 Halar coated Flow Control Valve, a Speed Control Valve, a Model
More informationDESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE
February 9, 1998 Foam 101a A BLADDER TANK WITH 1. DESCRIPTION A Wet Pipe Bladder Tank Foam/Water System is a standard wet pipe automatic sprinkler system capable of discharging a foam/water solution automatically
More informationISO INTERNATIONAL STANDARD. Cryogenic vessels Pressure-relief accessories for cryogenic service Part 1: Reclosable pressure-relief valves
INTERNATIONAL STANDARD ISO 21013-1 First edition 2008-06-15 Cryogenic vessels Pressure-relief accessories for cryogenic service Part 1: Reclosable pressure-relief valves Récipients cryogéniques Dispositifs
More informationPIP PN03SA0S03 Piping Material Specification 3SA0S03 Class 300, 304/304L Stainless Steel, Socket Weld, C.A.-None, Low Temperature Process
February 2018 Piping PIP PN03SA0S03 Piping Material Specification 3SA0S03 Class 300, 304/304L Stainless Steel, Socket Weld, C.A.-None, Low Temperature Process PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES
More informationTECHNICAL DATA. Q = C v P S
Preaction 346a 1. Description The 6 Model G-6000P Electric Release Preaction System Riser Assembly can be used as a Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction
More informationSECTION BUTTERFLY VALVES
SECTION 15112 BUTTERFLY VALVES PART 1 GENERAL 1.01 SUMMARY A. All butterfly valves shall be of the tight closing, rubber seated type and fully comply with the latest revision of AWWA Standard C504, Class
More informationTypes 749B and R130 Changeover Manifolds
Instruction Manual MCK-1179 Types 749B and R130 June 2012 Types 749B and R130 Changeover Manifolds TYPE HSRL-749B TYPE 64SR/122 TYPE R130/21 TYPE 749B/21 Figure 1. Changeover Manifolds and Regulator Assemblies
More informationSample C ylinde rs, Acce ssorie s, and O utage Tube s
www.swagelok.com Sample C ylinde rs, cce ssorie s, and O utage s Features Sizes from 10 to 3785 cm 3 (1 gal) Working pressures up to 5000 psig (344 bar) 304L and 316L stainless steel and alloy 400 2 Sample
More informationMSS STANDARD PRACTICE SP-61 This MSS Standard Practice was developed under the consensus of the MSS Technical Committee 114 and the MSS Coordinating C
MSS SP-61-2009 Pressure Testing of Valves Standard Practice Developed and Approved by the Manufacturers Standardization Society of the Valve and Fittings Industry, Inc. 127 Park Street, NE Vienna, Virginia
More informationTECHNICAL DATA. Q = C v P S
Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler
More informationSECTION PRESSURE TESTING OF PIPING
SECTION 15044 PRESSURE TESTING OF PIPING PART 1 - GENERAL 1.01 DESCRIPTION A. Scope of Work: This section specifies the leakage and pressure testing of piping. B. Testing Records: PART 2 - PRODUCTS 2.01
More informationDiscussion on Fugitive Emissions Standards Rich Davis
Discussion on Fugitive Emissions Standards Rich Davis Business Development Manager Flexitallic LP Emissions Standards API 622 Type Testing of Process Valve Packing for Fugitive Emissions (under revision)
More informationTECHNICAL DATA. Dry 132a. October 1, 2008
October 1, 2008 Dry 132a 1. Description Viking High Pressure (HP) Dry Systems utilize a Viking Model E or Model F Deluge Valve to control the water supply to system piping equipped with closed sprinklers.
More informationBGA158, BGA171 and BGA110 Series Shutoff Gas Valve
Installation Instructions BGA Series Issue Date October 3, 2017 BGA158, BGA171 and BGA110 Series Shutoff Gas Valve Applications The BGA Series shutoff gas valve is an electrically operated gas valve that
More informationTECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1
Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a
More information1800CPB2 Pilot-Loaded Service Regulators
1800CPB2 Pilot-Loaded Service Regulators Technical Bulletin www.elster-americanmeter.com Table of Contents 1800CPB2 Regulator Information................ 2-3 1800CPB2 Capacity Performance................
More informationTECHNICAL DATA. than the water inlet pressure to the concentrate
Foam102a 1. DESCRIPTION The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with 3M foam concentrates. This system consists of a standard wet pipe sprinkler
More informationINTERLOCKED METAL HOSE
INTERLOCKED METAL HOSE HOSE FUNDAMENTALS Penflex interlocked metal hoses are made for a variety of specialized industrial applications and are available in a wide range of metals, styles and sizes. Interlocked
More informationLeak testing of Valves. Standards for acceptable Rates of Valve Leakage
Leak testing of Valves Standards for acceptable Rates of Valve Leakage American Petroleum Institute (API) The API standard 598: Valve Inspection and Testing, covers the testing and inspection requirements
More informationTECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13
Page 1 of 13 1. Description The Viking 2 Model G-2000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler
More informationAnti-flood device Model B-1
December 4, 2009 Dry Systems 123a 1. DESCRIPTION The Anti-flood Device is required when Viking accelerators are installed on dry systems according to Viking Model E-1 Accelerator Trim Charts. In the SET
More informationTECHNICAL DATA. Q= Cv S
Page 1 of 13 1. DESCRIPTION The Viking 4 inch Model G-4000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry
More informationCLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD. 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems.
Page 1 of 7 CLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD 1. SCOPE 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems. 1.2 The piping system as used herein is
More informationHomestead Series 820 AWWA Butterfly Valves
Homestead Series 820 AWWA Butterfly Valves Dependable Valves for Water & Wastewater Service BODY: The ductile iron body meets or exceeds the design strength requirements of the AWWA C504 standards. Flange
More informationWATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL
Capital Controls Series 71V3000 The Series 71V3000 electrically-heated vaporizer automatically vaporizes and superheats liquid chlorine, sulfur dioxide or ammonia at a rate controlled by the gas feed system.
More informationQuick closing oil drain valve, type QDV 15 REFRIGERATION AND AIR CONDITIONING. Technical leaflet
Quick closing oil drain valve, type QDV 15 REFRIGERATION AND AIR CONDITIONING Technical leaflet Introduction QDV is a quick closing oil drain valve, designed particularly for draining oil from systems
More informationLoss Prevention Standard
Loss Prevention Standard LPS 1186: Issue 3.1 Requirements and testing methods for check valves This standard specifies the design and performance requirements for check valves used in wet automatic sprinkler
More informationSTANDARD FOR CONTROL VALVE SEAT LEAKAGE
11-3 STANDARD FOR CONTROL VALVE SEAT LEAKAGE 1. PURPOSE 1.1 This standard establishes a series of seat leakage classes for control valves and defines the test procedures. 2. SCOPE & LIMITATIONS 2.1 Selection
More informationWHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual
WHEATLEY SERIES 500 SWING CHECK VALVE STANDARD INTEGRAL SEAT & OPTIONAL REMOVABLE SEAT 2" FP - 6" FP 150# - 1500# 8" FP - 12" FP 150# - 900# API 6D and B16.34 2" FP - 4" FP 5000# DRILLING PRODUCTION VALVE
More informationCERTIFICATION OF COMPLIANCE OF THE USER S DESIGN SPECIFICATION
CERTIFICATION OF COMPLIANCE OF THE USER S DESIGN SPECIFICATION I, the undersigned, being experienced and competent in the applicable field of design related to pressure vessel requirements relative to
More information