MODEL RCW NON-INTERLOCK PREACTION SYSTEM

Similar documents
GENERAL DESCRIPTION MODEL RCW DRY SYSTEM CONFIGURATION. Technical Support Airpark Dr. Standish, MI 48658

MODEL RCW DRY SYSTEM VALVE

MODEL UM UNIVERSAL MANIFOLD ASSEMBLY (With or Without Control Valve) 1¼", 1½", 2", 2½", 76.1mm, 3", 4", 6",165.1mm, 8"

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

TECHNICAL DATA. Deluge Valves 211a. November 30, 2007 DELUGE VALVE MODEL E-1 ANGLE STYLE 3 (DN80), 4 (DN100) & 6 (DN150)

TECHNICAL DATA. Trimpac 257a. September 16, 2013

TECHNICAL DATA. Trimpac 244a. September 16, 2013

TECHNICAL DATA. Trimpac 256a. October 31, 2013

TECHNICAL DATA. Deluge Valves 218a. November 30, 2007 DELUGE VALVE MODEL F-1 STRAIGHT THROUGH STYLE 2-1/2 (DN65) - 8 (DN200)

INSTALLATION OPERATION MAINTENANCE

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA DELUGE VALVE, MODEL F-1 STRAIGHT THROUGH STYLE

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE. 4. TECHNICAL DATA Approvals:

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA OBSOLETE

TECHNICAL DATA. Q = C v P S

Preaction System with DV-5 Deluge Valve Single Interlock, Supervised Electric Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description

TECHNICAL DATA Q= C. Table 1 - Specifications

Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Electric Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA. Q = C v P S

Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)

TECHNICAL DATA. Table 1 - Specifications

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

Preaction System with DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description

TECHNICAL DATA. Q= Cv S

TECHNICAL DATA. Trimpac 247a_Euro. September 16, 2013

TECHNICAL DATA. Q = C v P S

MODEL UMC UNIVERSAL MANIFOLD CHECK ASSEMBLY

Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Dry Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)

MODEL UMC UNIVERSAL MANIFOLD CHECK ASSEMBLY

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA OBSOLETE

Model DPV-1 Dry Pipe Valve External Resetting. General Description. Technical Data. Page 1 of 20 AUGUST 2018 TFP1020. Worldwide Contacts

TECHNICAL DATA. Page 1 of 12

TECHNICAL DATA CAUTION

Worldwide Contacts. End Connection

TECHNICAL DATA. Dry 132a. October 1, 2008

TECHNICAL DATA ACCELERATOR MODEL E-1

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY PNEUMATIC RELEASE. 1. DESCRIPTION (Refer to Figures 1, 2 or 3.

a pilot sprinkler were to be closed after its initial operation, for example a remote manual control station).

Features. Model DDX-LP Dry Pipe Valve System 4 (100mm), 6 (150mm) & 165mm Sizes

TECHNICAL DATA CAUTION

Worldwide Contacts.

Technical Data. UL Listing is based on the following criteria:

Wet pipe low flow foam/water system

Anti-flood device Model B-1

Model DDX-LP Dry Pipe Valve System 8 (200mm) Features. Differential latching clapper-type, lighweight, dependable construction.

Instructions for Installation, Operation, Care and Maintenance

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

TECHNICAL DATA. than the water inlet pressure to the concentrate

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

FireLock NXT Preaction Valve with Series 798 Pneumatic/Pneumatic Actuator

DV-5 Preaction Type A Valve EN12845 Compliance. General Description. Page 1 of 16 DECEMBER 2016 TFP1484. Worldwide Contacts.

Services Department for information concerning the use of the ACC-1 for use with dry pipe valves other than the Model DPV-1.

Data Sheet Issue A

Speed control assembly model A-1

Instructions for Installation, Operation, Care and Maintenance

Features. Model DDX-LP Dry Pipe Valve System 2 (50 mm), 2½ (65 mm), 3 (80 mm), 76 mm, 4 (100 mm), 6 (150 mm), 165 mm & 8 (200mm) Listings & Approvals

Model: 43T. Bermad Pressure Relief Valve

FireLock NXT Dry Valve. System No. Submitted By Spec Sect Para Location Date Approved Date

Data Sheet Issue A. Wet Pilot Line Single Interlock Preaction System 8 (200 mm) Size

Data Sheet Issue A

OBSOLETE DESIGN DATA. Foam 301a. February 9, 1998

Fire Protection Equipment

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

Data Sheet Issue B

Data Sheet Issue B

TotalPac X Single interlock Preaction system Electric release

OBSOLETE. Wet pipe low flow manifold system

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

Data Sheet Issue A. Wet Pilot Line Single Interlock Preaction System 2 (50mm), 2 1 / 2. (65mm). 3 (80mm) & 76mm Sizes

TECHNICAL DATA OBSOLETE

Instructions for Installation, Operation, Care, and Maintenance

SPECIFICATIONS ATTENTION

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4

Instructions for Installation, Operation, Care and Maintenance

I T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

ASTRA - DRY PIPE VALVES GROOVE/GROOVE

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

Features. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200)

Double Interlock Preaction System - Type F 2"(50mm), 2-1/2"(65mm), 3" (80mm) & 76mm Sizes

Data Sheet Issue A

NOTICE The Model DPV-1 Dry Pipe Valves and

Instructions for Installation, Operation, Care, and Maintenance

DRY-PIPE, DELUGE, PREACTION VALVES & ACCESSORIES. Table of Contents

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

Data Sheet Issue A

Instructions for Installation, Operation, Care and Maintenance

Bermad Pressure Reducing. Model: 42T

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

Bermad Model:

Transcription:

0 Airpark Dr. Standish, MI 8658 989-86-58 www.globesprinkler.com Technical Support 989--00 techservice@globesprinkler.com MODEL RCW NON-INTERLOCK PREACTION SYSTEM GENERAL DESCRIPTION The Globe Model RCW non-interlock preaction valve is a hydraulically operated external resetting differential latching style valve designed for use where quickopening and total fl ooding of sprinkler system piping is desired. The Model RCW valve is used as an automatic water control valve in non-interlock preaction applications. The Model RCW valve serves as the primary water control valve installed in the water supply to a non-interlock preaction sprinkler system incorporating automatic sprinklers with supervisory air monitoring the integrity of the system piping. Setting of the Model RCW non-interlock preaction system requires water in the pressure chamber being maintained on the plunger rod. The pressure on the plunger rod which keeps the latch against the clapper closed keeps the supply water from entering the sprinkler system piping. Water pressure is provided to the pressure chamber through a connection to the main water supply at a point upstream of the system main control valve. This connection also supplies water pressure up to the solenoid valve, and to a dry pilot actuator. In the standby condition, the valve is normally closed and will automatically activate (trip) upon the activation of the detection system, which may be electrical or mechanical in nature depending on the type of system, or an operation of an automatic sprinkler as a result of a fi re condition. The RCW valve may also be operated by means of a manual release, which is provided in the trim of all non-interlock preaction valve trim confi gurations, to override the automatic detection system. When heat from a fi re opens an automatic sprinkler, or operates an electric device, water pressure in the pressure chamber decays through either the dry pilot actuator or solenoid valve respectively. The loss in pressure chamber pressure results in the movement of the push rod assembly, releasing the lever/roller assembly from the clapper. The system water supply pressure forces the valve clapper open resulting in water fl ow into the system piping making water available to the automatic sprinklers. Upon system activation, fi re alarm signaling is provided by means of fl owing water through the alarm port/intermediate chamber and associated alarm line trim. Water discharges from the automatic sprinkler once the operating element of the automatic sprinkler is activated by the heat of the fi re. The flow of water activates a pressure switch which in turn notifi es local alarms and/or an alarm signaling monitoring service. After the main control valve has been shut, the system drained and the detection system has been reset, the RCW non-interlock preaction MODEL RCW NON-INTERLOCK INTERLOCK PREACTION valve is easily set/reset by means of pushing the reset knob. The reset knob returns the clapper to the closed position, without needing to remove the cover plate of the valve. Note: See technical datasheet GFV-565 for solenoid valve selection and panel compatibility. More information can be found on the dry pilot actuator operation in technical datasheet GFV-5. TECHNICAL DATA Approvals 00 psi (.6 Bar)-cULus/FM Maximum System Working Pressure (Dependent on solenoid valve selection- Standard offering 5 psi (2 Bar)) 00 psi (.6 Bar)- culus/fm End Connections Groove x Groove Materials of Construction See Technical Datasheet GFV 0 for materials of construction for the Model RCW Valve *Patents Pending OCT GFV- Page of

FIGURE :NON-INTERLOCK PREACTION ACTUATION SCHEMATIC VALVE SIZE NOMINAL INSTALLATION DIMENSIONS INCHES (MM) A B C D E F G H I J " (DN00). (8).96 () 8.6 (9) 5.05 (82) 6.92 (0) 2. (2).06 (9). ().62 (295) 9.5 (2) 6" (DN). (8).96 () 9. (2) 5.8 (02) 6.9 ().9 () 8.5 (5). (68).6 (296) 9. (2) FIGURE 2:NON-INTERLOCK PREACTION TRIM DIMENSIONS OCT GFV- Page 2 of

FIGURE : " RCW NON-INTERLOCK PREACTION ACTUATION TRIM ARRANGEMENT 5 55 6 8 8 2 28 5 5 5 2 5 6 56 2 5 2 29 8 9 6 22 2 0 9 5 8 2 2 9 6 2 5 2 8 62 5 FROM AIR MAINTENANCE DEVICE 66 2 NOTE: SOLENOID INCLUDED. IF OTHER THAN STANDARD, INFORM CUSTOMER SERVICE AT TIME OF ORDER 9 5 52 52 8 9 ITEM NO. PART NO. DESCRIPTION QTY. ITEM NO. PART NO. DESCRIPTION QTY. 0802-G 2" x " GALV. NIPPLE 22-G /" x /2" GALV. STREET ELBOW 2 8-G 2" 90 GALV. ELBOW 80 " CHECK VALVE (FxF) 006-G /2" x " GALV. NIPPLE 5 -G /2" x /2" x /" GALV. TEE 2 00-G /2" x /2" GALV. NIPPLE G580 SOLENOID VALVE WITH 2V DC COIL 5 005-G /2" x /2" GALV. NIPPLE 2 8 95 /2" RESTRICTOR 6 200 VELOCITY CHECK VALVE 9 0-G /" GALV. UNION 696-R /2" BALL VALVE MXF - RED HANDLE 2 0 00-G /" x 2" GALV. NIPPLE 8 -G /" x /2" x /" GALV. TEE 9-GR /2" BALL VALVE MxM - GREEN HANDLE 9 98 DRIP ASSEMBLY 2 008-G /2" x 5" GALV. NIPPLE 0-G /" x /2" GALV. NIPPLE 68 /" -WAY VALVE 2 2 005-G /" x /2" GALV. NIPPLE 00 PS-0-2 ALARM SWITCH 00-G /" GALV. PLUG 5 00 PS-0-2 ALARM SWITCH 009-D -/2" WATER GAUGE (00PSI) 2 6 00-G /2" x " GALV. NIPPLE 5 00-D -/2" AIR GAUGE (0PSI) -G /2" GALV. ELBOW 5 6 0-G /2" GALV. STREET ELBOW 2 8 -G " GALV. STREET ELBOW 00-G /2" GALV. CROSS 2 9 99-R 2" BALL VALVE (FxF) - RED HANDLE 8 00-G /" GALV. PLUG 0800-G 2" CLOSE GALV. NIPPLE 2 9 86 /" CHECK VALVE MxF 5 8-G 2" x 2" x " GALV. TEE 0-G /2" GALV. UNION 52 0-G " x 2" GALV. NIPPLE 2 05-G /2" x /" x /2" GALV. TEE 5 002-G /2" x 2" GALV. NIPPLE 2 22 06 /" TUBE CONNECTOR 55 00-G /" x /2" GALV. NIPPLE 2 M-60 /" COPPER TUBE - 56 55 DRY PILOT ACTUATOR 2 06 /2" ELBOW TUBE CONNECTOR 5 0-G /2" GALV. TEE 06 /2" TUBE CONNECTOR 2 62 5 /" PRESSURE RELIEF VALVE (ADJ. PSI) FACTORY SET @ 5PSI M-59 /2" COPPER TUBE - 66 00-G /2" x 6" GALV. NIPPLE 2 9 /2" Y-STRAINER 2 802 /2" CHECK VALVE MxF 28 96 /2" SPRING LOADED CHECK VALVE 08-G /2" x 2" GALV. NIPPLE 29 9-R /2" BALL VALVE MxM - RED HANDLE 8 696-GR /2" BALL VALVE MxF - GREEN HANDLE 002-G /" GALV. CROSS 9 00-G /" x 6" GALV. NIPPLE 2 2-G /" x /2" GALV. REDUCING ELBOW 8 02-G /2" x 9" GALV. NIPPLE OCT GFV- Page of

FIGURE : 6" RCW NON-INTERLOCK PREACTION ACTUATION TRIM ARRANGEMENT 6 8 82 2 28 5 5 2 5 6 56 5 2 5 5 55 2 29 2 68 8 0 22 9 2 8 2 6 8 62 6 9 9 5 FROM 5 2 AIR MAINTENANCE DEVICE 6 66 2 5 2 5 2 9 NOTE: SOLENOID INCLUDED. IF OTHER THAN STANDARD, INFORM CUSTOMER SERVICE AT TIME OF ORDER 9 5 52 52 8 ITEM NO. PART NO. DESCRIPTION QTY. ITEM NO. PART NO. DESCRIPTION QTY. 0802-G 2" x " GALV. NIPPLE 22-G /" x /2" GALV. STREET ELBOW 2 8-G 2" 90 GALV. ELBOW 80 " CHECK VALVE (FxF) 006-G /2" x " GALV. NIPPLE 2 5 -G /2" x /2" x /" GALV. TEE 2 00-G /2" x /2" GALV. NIPPLE 6 G580 SOLENOID VALVE WITH 2V DC COIL 5 005-G /2" x /2" GALV. NIPPLE 2 8 95 /2" RESTRICTOR 6 200 VELOCITY CHECK VALVE 9 0-G /" GALV. UNION 696-R /2" BALL VALVE MxF - RED HANDLE 2 0 00-G /" x 2" GALV. NIPPLE 8 -G /" x /2" x /" GALV. TEE 9-GR /2" BALL VALVE MxM - GREEN HANDLE 9 98 DRIP ASSEMBLY 2 008-G /2" x 5" GALV. NIPPLE 0-G /" x /2" GALV. NIPPLE 68 /" -WAY VALVE 2 2 005-G /" x /2" GALV. NIPPLE 00 PS-0-2 ALARM SWITCH 00-G /" GALV. PLUG 5 00 PS-0-2 ALARM SWITCH 009-D -/2" WATER GAUGE (00PSI) 2 6 00-G /2" x " GALV. NIPPLE 2 5 00-D -/2" AIR GAUGE (0PSI) -G /2" GALV. ELBOW 5 6 0-G /2" GALV. STREET ELBOW 2 8 -G " GALV. STREET ELBOW 00-G /2" GALV. CROSS 2 9 99-R 2" BALL VALVE (FxF) - RED HANDLE 8 00-G /" GALV. PLUG 0800-G 2" CLOSE GALV. NIPPLE 2 9 86 /" CHECK VALVE MxF 5 8-G 2" x 2" x " GALV. TEE 0-G /2" GALV. UNION 52 0-G " x 2" GALV. NIPPLE 2 05-G /2" x /" x /2" GALV. TEE 5 002-G /2" x 2" GALV. NIPPLE 22 06 /" TUBE CONNECTOR 55 00-G /" x /2" GALV. NIPPLE 2 M-60 /" COPPER TUBE - 56 55 DRY PILOT ACTUATOR 2 06 /2" ELBOW TUBE CONNECTOR 5 0-G /2" GALV. TEE 06 /2" TUBE CONNECTOR 2 62 5 /" PRESSURE RELIEF VALVE (ADJ. PSI) FACTORY SET @ 5PSI M-59 /2" COPPER TUBE - 66 00-G /2" x 6" GALV. NIPPLE 2 9 /2" Y-STRAINER 68 002-G /" x 2 /2" GALV. NIPPLE 28 96 /2" SPRING LOADED CHECK VALVE 2 802 /2" CHECK VALVE MxF 29 9-R /2" BALL VALVE MxM - RED HANDLE 08-G /2" x 2" GALV. NIPPLE 002-G /" GALV. CROSS 8 696-GR /2" BALL VALVE MXF - GREEN HANDLE 2 2-G /" x /2" GALV. REDUCING ELBOW 9 00-G /" x 6" GALV. NIPPLE 82 0-G /2" x0" GALV. NIPPLE OCT GFV- Page of

INSTALLATION AND MAINTENANCE INSTALLATION Proper operation of the RCW Valve (i.e., opening of the RCW Valve as during a fi re condition) is highly dependent on the correct installation of the trim. It is necessary to install the trim components as described in the fi gures above for the valve to function properly. Failure to do so may prevent the valve from functioning and could void Listings, Approvals, and/or the manufacturer's warranty. All tubing directed to the "drip cup" must have smooth bends. Abrupt changes in direction or kinks in the tubing could result in a restriction of fl ow and an adverse effect on the functionality of the valve. The Model RCW Valve must be installed in an accessible and visible location, which is maintained at or above a minimum temperature of 0ºF (ºC). The RCW Valve must be installed in the vertical orientation. All valves must be installed in accordance with the appropriate installation standard (i.e. NFPA, NFPA 5 or other). All electrical connections must be made per the applicable installation standard and/or the National Electric Code (i.e. NFPA 0, NFPA 2 or other). Proper hydrostatic test procedure must be followed per NFPA. The velocity check valve must be replaced with a plug temporarily, the pressure chamber must be vented during the hydrostatic test procedure by opening the manual release valve and the clapper must be latched in the open position. NON-INTERLOCK PREACTION VALVE SETTING PROCEDURE The following steps are to be followed for initial setting of the Model RCW non-interlock preaction system valve, after a trip test of the fi re protection system or, after any system operation. STEP. Close the main control valve. STEP 2. Close the pressure chamber supply control valve and the system air supply valve. STEP. Open the main drain valve, lower body drain valve, and all low point drain valves and auxiliary drain valves on the system. Open the manual emergency release control valve. Depress the plunger of the automatic drain valve to verify that it is not under pressure and that the system piping is completely drained. After system is completely drained, close all low point and auxiliary drain valves that were open. The manual emergency release control valve and main drain valve should remain open until directed in the following steps. STEP. Depress the reset plunger located at the top of the pressure chamber to reset the clapper of the RCW valve (the sound of the clapper falling into position should be heard). Close the manual emergency release control valve. STEP 5. Open the remote test valve. Replace any operated automatic sprinklers that operated with the same type, i.e. Orientation, orifi ce, temperature, and thermal sensitivity. Close the remote test valve. STEP 6. The detection system is to be cleared and reset in accordance with the detection system and/or control panel manufacturer s instructions. Once reset, verify the solenoid valve is closed (deenergized). When closed, the solenoid valve should have no magnetic charge on the nut on the top of the coil. Test the nut to make sure it is has no magnetic charge by contacting the nut with a conductive item such as a screwdriver. If still magnetized, the detection system/panel is not properly set for service. STEP. Open the system air supply valve to re-establish normal system air pressure. STEP 8. Open the manual emergency release control valve and then the pressure chamber supply control valve. Slowly close the manual emergency release control valve and allow pressure to build up in the pressure chamber, up to the dry pilot actuator and solenoid valve. STEP 9. Observe all drain tubing at the drip cup. If any leakage is observed, the source of the leakage must be identifi ed and corrected. STEP 0. Partially open the main control valve. Slowly close the main drain valve when water discharges from the drain connection. Observe the supply pressure gauge and the pressure chamber gauge, they should indicate the same pressure reading. Depress the plunger on the automatic drip check valve for leaks. If leakage is apparent, the cause of the leakage must be identifi ed and corrected. If there are no leaks, open the system control valve fully. STEP. Clear/reset the releasing control panel to clear any supervisory conditions that connected to the system control valve. Once the panel is reset and clear, the system is set for service. TESTING Reference NFPA, Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems. Before proceeding with any tests involving water fl ow, the following precautions need to be taken: STEP. Check the location where the test connection discharges to make sure that all is clear and that there is no possibility of the water fl ow causing damage or injury. STEP 2. Check the end of the test connection to make sure that it is unobstructed. To achieve a satisfactory test, there must be an unrestricted fl ow of water when the test valve is wide open. STEP. Check for alarm connections to a central station or fi re department. If such connections are found, give proper notice to the signal receiving station before proceeding with the test. Note: A main drain test may also operate local fire alarms unless they are temporarily disabled. NON-INTERLOCK PREACTION TRIP TEST PROCEDURE Proper operation of the RCW Valve (i.e., opening of the RCW Valve as during a fi re condition) must be verifi ed, at or more frequently than described by the applicable Inspection OCT GFV- Page 5 of

Testing and Maintenance Standard (i.e. NFPA ) or by the Local AHJ. Globe Sprinkler Corporation recommends performing a trip test annually. The steps to perform a trip test are as follows: STEP. If a partial fl ow trip test is required perform the following additional steps, if a normal fl ow test is being performed continue to Step 2:. Close the main control valve. 2. Open the main drain valve.. Open the main control valve one turn beyond the position at which water just begins to fl ow from the main drain valve.. Close the main drain valve. 5. In step be sure to close the main control valve quickly after the trip of the valve has been verifi ed. STEP 2. Test the Non-interlock Preaction releasing panel in accordance with the manufacturer s instructions to energize the solenoid valve or open the test connection at the end of the system. Either operation will cause the valve to trip. STEP. Verify that the RCW Valve has tripped, as indicated by the fl ow of water into the system and activation of the water fl ow alarm. STEP. Close the system s Main Control Valve. STEP 5. Close the Diaphragm Chamber Supply Control Valve. STEP 6. Reset the RCW Non-interlock Preaction Valve in accordance with the Non-interlock Preaction Valve Setting Procedure. NON-INTERLOCK PREACTION- WATERFLOW ALARM TEST PROCEDURE Testing of the system water fl ow alarms must be performed as described by the applicable Inspection Testing and Maintenance Standard (i.e. NFPA ) or as described by the Local AHJ. To test the water fl ow alarm, open the Alarm Test Valve, which will allow a fl ow of water to the Pressure Alarm Switch and/or Water Motor Alarm. Upon satisfactory completion of the test, close the Alarm Test Valve. MAINTENANCE Note: All valves should be carefully inspected, tested, and maintained in accordance with NFPA or other applicable Standard. It is important to ensure a clean water supply free of debris and solid particles such as sand, gravel, or mud. If, during an inspection of a water control valve, sediment or free particles of matter are noted, a further examination of internal valve parts is necessary. All deposits should be removed from all operating parts and ports. Vent holes through intermediate chamber should be thoroughly cleaned and fl ushed with clean water. Where diffi culty in performance is experienced, the manufacturer or its authorized representative shall be contacted before any fi eld adjustment is to be made. Clapper Facing. The rubber clapper facing should be checked for wear or damage to determine that it is free of dirt and other foreign substances. If found to be worn or damaged (e.g., foreign matter embedded in the surface), the facing should be replaced. If it is dirty, it should be cleaned. Compounds which could damage the rubber facing must never be used. Seat Ring. The seat ring should be checked for nicks and for stones, dirt or other foreign matter lodged in the grooves or holes. It should be cleaned thoroughly. If the seat ring is found to be damaged, valve should be replaced. Alarm Line Check Valve. The ¾ check valve connected to the intermediate chamber should be checked for clapper and seat condition. RCW Valve. Main Drain Valve and all controlling valves which are normally closed when the deluge valve is in the set position should be checked to be sure that they are fully closed and not leaking. ORDERING INFORMATION The RCW Valve with Non-Interlock Preaction; Electric, Wet Pilot, or Dry Pilot Actuation trim can be ordered pre-trimmed or non-assembled as separate items. The standard offering comes with galvanized nipples and fi ttings (Standard galvanized trim is not domestic). For non-assembled the following items must be ordered separately: RCW Water Control Valve Non-Interlock Preaction Electric Actuation Trim (Solenoid Valve Ordered Separately) or; Non-Interlock Preaction Wet Pilot Trim or; Non-Interlock Preaction Dry Pilot Trim Automatic Air Supply (Air Maintenance Device) Accessories (as needed) Pre-Trimmed With Model GLR00G Control Valve Electric actuation standard solenoid valve is the Parker 2 VDC; 5 psi rated solenoid. If different solenoid valve is desired, inform Customer Service at time of order placement. Pre-Trimmed RCW Non-Interlock Electric Actuation w/ BFV Contol Valve Specify: RCW Non-Interlock Electric Pretrimmed w/ BFV(specify valve size), PN: Inch G x G.................... 66-B Inch G x G.................... 66-B-LP 6 Inch G x G.................... 0-B 6 Inch G x G.................... 0-B-LP DN (65, mm) GXG.......... 0-D-B DN (65, mm) GXG.......... 0-D-B-LP OCT GFV- Page 6 of

PRE-TRIMMED WITHOUT GROOVED BFV CONTROL VALVE Pre-Trimmed RCW Non-Interlock Electric Actuation Specify: RCW Non-Interlock Electric Pretrimmed (specify valve size), PN: Inch G x G.................... 66 Inch G x G.................... 66-LP 6 Inch G x G.................... 0 6 Inch G x G.................... 0-LP DN (65, mm) GXG.......... 0-D DN (65, mm) GXG.......... 0-D-LP NON-ASSEMBLED Valve body ordered separately Solenoid Valve Included Trim Kit includes extra pieces to accommodate different size valves RCW Water Control Valve Specify: RCW Valve Only (specify valve size) inch RCW GxG................. 00 inch RCW GxG................. 00-LP 6 inch RCW GxG................. 5 6 inch RCW GxG................. 5-LP DN (65, mm) RCW GXG..... 5-D DN (65, mm) RCW GXG..... 5-D-LP Model H-, H-2 or H- Air Maintenance Device Specify: Model (Specify Model) Air Maintenance Device (see Part Number below) H-............................ 585 H-2............................ 595 H-............................ 600 See Technical Literature G- and G-2 for more information on Air Maintenance Devices Note: 00 psi (.6 Bars) Pressure Gauges Standard (600 psi (.2 Bars)) Ordered Separately) PN............................ 00-D NOTE: See trim drawings for trim replacement part numbers See Technical Data Sheet GFV0 for RCW Valve replacement part numbers GLOBE PRODUCT WARRANTY Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List). RCW Non-Interlock Electric Trim Kit inch or 6 inch or DN Specify: RCW Non-Interlock Electric Trim Kit, PN Non-Interlock Electric Trim Kit....... 65 Non-Interlock Electric Trim Kit....... 65-LP Solenoid Valve A Solenoid Valve compatible with the anticipated maximum water supply pressure and releasing panel when ordering an electric actuation trim. Refer to Technical Data Sheet GFV565 for ordering information. Specify: 2 VDC, (5 psi, 0 psi or 00 psi) Solenoid Valve: ASCO 5 psi (2 Bar) UL/FM...... G89G ASCO 00 psi (. Bar) UL/FM..... GHV2900 *Skinner 5 psi (2 Bar) UL/FM..... G580 Skinner 0 psi (.2 Bar) UL/FM.... G5802 *Standard 0 Airpark Dr. Standish, MI 8658 Ph. 989-86-58 Technical Support -800-28-028 techservice@globesprinkler.com www.globesprinkler.com OCT GFV- Page of