Smoke and heat Ventilator Testing

Similar documents
CORESTA RECOMMENDED METHOD N 6

CONTENTS 1. INTRODUCTION DESCRIPTION OF TEST SAMPLE TEST RIG GENERAL ARRANGEMENT TEST SEQUENCE...7

vento specification sheet

Measuring range Δp (span = 100%) Pa

Third measurement MEASUREMENT OF PRESSURE

THE WAY THE VENTURI AND ORIFICES WORK

AerE 343L: Aerodynamics Laboratory II. Lab Instructions

Lab. Manual. Fluid Mechanics. The Department of Civil and Architectural Engineering

Welcome to Aerospace Engineering

Automatic Isokinetic Sampler. ST5 Evo

I.CHEM.E. SYMPOSIUM SERIES NO. 97 BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES

Instruction Manual. Pipe Friction Training Panel

Automatic Isokinetic Sampler. ST5 Evo

01 18/11/2013 correction of the reference of the product 1 4 5

ROSE-HULMAN INSTITUTE OF TECHNOLOGY Department of Mechanical Engineering. Mini-project 3 Tennis ball launcher

ENGINEERING AUSTRALIA PTY. LTD.

Cover Page for Lab Report Group Portion. Drag on Spheres

COMPUTATIONAL FLOW MODEL OF WESTFALL'S LEADING TAB FLOW CONDITIONER AGM-09-R-08 Rev. B. By Kimbal A. Hall, PE

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT

Lab 1c Isentropic Blow-down Process and Discharge Coefficient

OBJECTIVE METHODOLOGY

Effects of wind incidence angle on wind pressure distribution on square plan tall buildings

High-speed pressure sensor Model CPT6140

Tutorial. BOSfluids. Relief valve

International Journal of Research in Advent Technology Available Online at:

P-5215 Differential Pressure Transmitter

Avai 193 Fall 2016 Laboratory Greensheet

Applied Fluid Mechanics

Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations

The Discussion of this exercise covers the following points:

Effect of Inlet Clearance Gap on the Performance of an Industrial Centrifugal Blower with Parallel Wall Volute

Gas Vapor Injection on Refrigerant Cycle Using Piston Technology

Paper 2.2. Operation of Ultrasonic Flow Meters at Conditions Different Than Their Calibration

External Pressure Coefficients on Saw-tooth and Mono-sloped Roofs

Measurement of Pressure. The aerofoil shape used in wing is to. Distribution and Lift for an Aerofoil. generate lift due to the difference

CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS

AF100. Subsonic Wind Tunnel AERODYNAMICS. Open-circuit subsonic wind tunnel for a wide range of investigations into aerodynamics

rpbsafety.com Samoset Rd Royal Oak, MI USA OF THE NOVA 3 ABRASIVE BLASTING SUPPLIED AIR RESPIRATOR

628 Differential Pressure Decay Leak Tester

NSAI Agrément Approval Scheme for. Certified Air Tightness Tester Scheme Master Document

Predicted Dispense Volume vs. Gravimetric Measurement for the MICROLAB 600. November 2010

Heat Engine. Reading: Appropriate sections for first, second law of thermodynamics, and PV diagrams.

CHAPTER 3 RESULTS AND DISCUSSION

WP2 Fire test for toxicity of fire effluents

CEILING DIFFUSERS technical CONTROL THE AIR YOU BREATHE. types -CD, CAB. Europair Africa a division of Performancair Products Africa (Pty) Ltd

Influence of Reynolds number on Cd of Critical flow venturi nozzle and validation with ISO standards

Cover Page for Lab Report Group Portion. Lift on a Wing

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

Universities of Leeds, Sheffield and York

Radiator thermostats type RA2000, valve bodies type RA-FN (series D) and RA-G

INSTRUMENTS A THERMAL MASS FLOW SENSOR USING A CONSTANT DIFFERENTIAL TEMPERATURE ABOVE THE AMBIENT GAS TEMPERATURE

Mitos Fluika Pressure and Vacuum Pumps Datasheet

Available online at ScienceDirect. Procedia Engineering 112 (2015 )

Underwater measurement of photosynthetically active radiation

BAPI Pressure Line of Products - FAQs

Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios

SEMEM3-78 Testing and calibrating instrumentation and control equipment and circuits

OPENINGS AND REINFORCEMENTS 26

Single Pressure/ vacuum decay leak rate, loss, rate of loss, or occlusion tests with standard Cv valves.

Aerodynamic Analysis of a Symmetric Aerofoil

BURNERS NOZZLE MIX SINGLE TUNNEL MULTIPLE TUNNEL

Operational experiences with the EuroLoop Liquid Hydrocarbon Flow Facility

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

International Journal of Technical Research and Applications e-issn: , Volume 4, Issue 3 (May-June, 2016), PP.

4 Testing Agency Guide. 4.1 U.S. Army Corps of Engineers (USACE) Standard for Air Leakage

HON 219 Pressure Reducer (D119a)

Overview of types. T5-R B2/R B2 en v Subject to changes 1 / 4. k vs (Sequence 2)

CIVL473 Fundamentals of Steel Design

Long Win s Educational Facilities for Fluid Mechanics

Gas Measurement Fundamentals Certification. Curriculum

Guidance on room integrity testing and its interpretation

AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR

Statesville, NC. Results of AM ASHRAE 110 Laboratory Fume Hood Performance Evaluations Venturi Hood

Fluid Flow. Link. Flow» P 1 P 2 Figure 1. Flow Model

AIR EJECTOR WITH A DIFFUSER THAT INCLUDES BOUNDARY LAYER SUCTION

CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF PRESSURE METROLOGY

Air Leakage Detailing & Awareness Services

CONTROL VALVE TESTING

POWER Quantifying Correction Curve Uncertainty Through Empirical Methods

AIAA Brush Seal Performance Evaluation. P. F. Crudgington Cross Manufacturing Co. Ltd. Devizes, ENGLAND

CHAPTER 7 : SMOKE METERS AND THEIR INSTALLATIONS

TECHNICAL SCHEDULE TS16 SMOKE VENTS

THEORY OF WINGS AND WIND TUNNEL TESTING OF A NACA 2415 AIRFOIL. By Mehrdad Ghods

Two interconnected rubber balloons as a demonstration showing the effect of surface tension

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

Radiator thermostats type RA2000, valve bodies type RA-FN (series D) and RA-G

The Discussion of this exercise covers the following points:

COMPAFLOW. Compressed Air. Volumetric flow. Gas. Mass flow. Steam. Net volumetric flow. Liquid

Experiment 8: Minor Losses

Flow in a shock tube

EFFECTS OF WATER SPRAYS AND SCRUBBER EXHAUST ON FACE METHANE CONCENTRATIONS

TWO PHASE FLOW METER UTILIZING A SLOTTED PLATE. Acadiana Flow Measurement Society

Subsonic Wind Tunnel 300 mm

INDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR NPTEL ONLINE CERTIFICATION COURSE. On Industrial Automation and Control

MacroFlo Calculation Methods IES Virtual Environment 6.4

Glass tube flowmeters Series 2000

pren CEN standard-draft pr EN 12261

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12

Gerald D. Anderson. Education Technical Specialist

Tilt Detection Using Accelerometer and Barometric Measurements

Transcription:

Instituut vir Termodinamika en Meganika Institute for Thermodynamics and Mechanics Smoke and heat Ventilator Testing by CJ Zietsman and GR Smith November 2005 Departement Meganiese Ingenieurswese Privaat Sak X1 7602 MATIELAND Suid-Afrika Tel: (021) 808 4376 Faks: (021) 808 4958 E-pos: meganies@ing.sun.ac.za STELLENBOSCH Department of Mechanical Engineering Private Bag X1 7602 MATIELAND South Africa Fax: +27 (0) 21 808 4958 Tel: +27 (0) 21 808 4376 E-mail: meganies@ing.sun.ac.za

- 2 - Table of contents Introduction... 3 1 Coefficient of Discharge... 3 1.1 Calculations:... 6 1.2 Results and Comments... 7 2 Rain Testing... 12 2.1 Results and Comments... 12 3 Wind Load Testing... 15 3.1 Results and Comments... 15 4 Temperature Rise... 15 4.1 Results and Comments... 16 5 Fatigue Testing... 17 6 Conclusion... 18

- 3 - Introduction Air ventilators are used to ventilate hot air between the ceiling and roof of a building to regulate its temperature. They are also (more importantly) smoke ventilators in the occurrence of a fire and a requirement for safety regulations of buildings. The type of air ventilator which was tested consists of various louvers connected to a spring-loaded mechanism which forces the louvers open in the incident of a fire. The spring-loaded mechanism is triggered with a diffusible link which breaks when its yield-temperature is exceeded. The air ventilator was tested to BS 7346-1:1990 standards. Several tests were conducted which were coefficient of discharge; rain testing, wind-load testing, temperature rise and fatigue testing. The set up of these tests together with their results are explained in their various sections. Coefficient of Discharge The aim of this experiment was to determine the coefficient of discharge C D for when the louvers open and the leakage coefficient C D when the louvers are closed. The apparatus, an atmospheric draft tunnel, is being discussed together with the BS standards guide lines for the test set up. The ventilator was tested in closed and fire open configurations and the results are provided in forms of tables and figures. Apparatus: Atmospheric open-loop draft tunnel with manometers and calibrated orifice plate The wind tunnel (figure 1.1) consists of a radial fan (1) that draws air uniformly through the ventilator, where the wet- and dry bulb temperatures, as well as the turbulence level, are measured. The static pressure difference is measured across the ventilator at points located in the duct wall (2). After the ventilator, the air passes through an insulated connecting section (3) followed by a venturi (4). The purpose of the venturi arrangement tends to minimize the nonuniformity of the air-stream velocity. The air flow is determined by measuring the pressure drop across one or more elliptical nozzles mounted in plate (5) located between two perforated plates (6) which straighten the flow.

- 4 - ΔP s ΔP n 2 3 4 6 5 6 1 Figure 1.1 Atmospheric open loop draft tunnel Figure 1.2 Ventilator connected to draft tunnel Figure 1.3 describes the test set up for the ventilator before it is connected to the wind tunnel.

- 5 - Test set up: 0.2 V A View X B V 0.2 V C Y Ventilator 0.2 Y 0.2 Y D 0.2 V AB Unobstructed for 1.5 Y V Direction of air flow To fan X 0.2 V CD 1.5 Y Measuring section Figure 1.4 Test set up for ventilator to British standards

- 6 - Calculations: By graphical or calculation methods, determine the best straight line through the plotted points of 2 Q n against differential pressure, and passing through zero where Q n is the air flow through the ventilator in m 3 /s. If all the points lie within ±5% differential pressure of the best line, then the values from any point on the line may be used in the calculation of C D as the derived value of C D will be independent of flow rate throughout the range tested. If isolated points fall outside the ±5% band, then the tests shall be repeated at the relevant flow rates to check the validity of the data. If groups of points fall outside the ±5% band indicating that the tests results do not follow a linear relationship between and plot C D against 2 Q n and differential pressure, then calculate C D for each of the test points Q n and determine the best line (curve) through the points. If the points fall within ±5% of C D of the best line, then values from points on the line may be used in the interpolation of C D. Derived data shall include at least the values of C D at the minimum, median and maximum test flow rates. Flow measurements shall be in accordance with BS 1042 (air flow measurement accuracy ±0.25%, pressure difference accuracy ±0.25%), using instruments that carry a current calibration certificate, traceable to a defined national standard. Calculate the air density from the equation 346.8 P 1000 273 T where P is the barometric pressure in mbar T is the ambient temperature in C

- 7 - Calculate the theoretical flow, Qt in m3/s, from the equation Q where t A 2 P s A is the ventilator throat area in m 2 P s is the static pressure difference at the test flow rate in Pa is the air density in kg/m 3 Calculate the coefficient of the ventilator from the aerodynamics tests using equation where Q CD Q n t Q n is the actual flow determined by test Results and Comments The ventilator subjected to the tests is smaller than the actual size used in practice. Therefore it was suspected that the mechanisms which are responsible for the opening of the ventilator might have a negative effect on the discharge coefficient. The discharge coefficient test was then repeated without its opening mechanisms. The leakage coefficient test was conducted with the louvers closed and was calculated with the same method as the discharge coefficient which was explained in section 1.1. The results are shown in the following data tables and figures.

Discharge coefficient Table 1.1-8 - Test data for fire open configuration with mechanisms No. Barometric Pressure Abient Air Temperature Air Density Static Pressure Difference Ventilator Throat Area N/m2 C kg/m 3 Pa m 2 1 101860 16.2 1.21677 13.74575 0.22755 2 101860 16.2 1.21587 28.39460 0.22755 3 101860 16.2 1.21489 43.94619 0.22755 4 101860 16.2 1.21368 63.17367 0.22755 5 101860 16.2 1.21231 85.79117 0.22755 6 101860 16.2 1.21071 111.65255 0.22755 7 101860 16.2 1.20892 138.18840 0.22755 8 101860 16.2 1.20516 195.64125 0.22755 9 101860 16.2 1.20237 237.37302 0.22755 10 101860 16.2 1.19936 284.08466 0.22755 Table 1.2 Test results for fire open configuration with mechanisms No. Volume Flow ( Q n ) Volume Flow ( Q n 2 ) Correlation Values ( Q n 2 ) Percentage Difference Theoretical Flow, ( Q t ) Coefficient of Discharge m 3 /s % m 3 /s C d 1 0.57034 0.32529 0.31459-3.40 1.08161 0.527 2 0.81191 0.65920 0.65544-0.57 1.55513 0.522 3 1.01374 1.02767 1.01729-1.02 1.93546 0.524 4 1.20812 1.45955 1.46466 0.35 2.32171 0.520 5 1.40853 1.98396 1.99092 0.35 2.70712 0.520 6 1.60378 2.57211 2.59266 0.79 3.09033 0.519 7 1.79697 3.22909 3.21009-0.59 3.44055 0.522 8 2.12010 4.49482 4.54688 1.15 4.10014 0.517 9 2.35004 5.52268 5.51789-0.09 4.52156 0.520 10 2.57590 6.63528 6.60476-0.46 4.95269 0.520

- 9 - Table 1.3 Test data for fire open configuration without mechanisms No. Barometric Pressure Abient Air Temperature Air Density Static Pressure Difference Ventilator Throat Area N/m2 C kg/m 3 Pa m 2 1 101650 13 1.22848 8.30000 0.22755 2 101650 13 1.22757 32.05783 0.22755 3 101650 13 1.22658 79.23082 0.22755 4 101650 13 1.22536 126.80570 0.22755 5 101650 13 1.22396 194.48768 0.22755 6 101650 13 1.22235 233.07906 0.22755 7 101650 13 1.22935 0.00000 0.22755 8 101650 13 1.22935 0.00000 0.22755 9 101650 13 1.22935 0.00000 0.22755 10 101650 13 1.22935 0.00000 0.22755 Table 1.4 Test data for fire open configuration without mechanisms No. Volume Flow ( Q n ) Volume Flow ( Q n 2 ) Correlation Values ( Q n 2 ) Percentage Difference Theoretical Flow, ( Q t ) Coefficient of Discharge m 3 /s % m 3 /s C d 1 0.63967 0.40918 0.43177 5.23 0.83646 0.765 2 1.20651 1.45566 1.43505-1.44 1.64451 0.734 3 1.88344 3.54733 3.42715-3.51 2.58638 0.728 4 2.33904 5.47111 5.43623-0.64 3.27363 0.715 5 2.87237 8.25053 8.29442 0.53 4.05652 0.708 6 3.14586 9.89643 9.92412 0.28 4.44370 0.708

Differential Pressure, (Pa) - 10-300 250 200 150 100 50 Without Mechanisms 0 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 Q n 2 Figure 2.4 Graph of differential pressure versus Q n 2 without mechanisms for fire open configuration with and Leakage coefficient Table 1.5 Test data for leakage coefficient when louvers are closed No. Barometric Pressure Abient Air Temperature Air Density Static Pressure Difference Ventilator Throat Area N/m2 C kg/m 3 Pa m 2 1 101860 16.2 1.21458 67.21796 0.22755 2 101860 16.2 1.21382 125.04840 0.22755 3 101860 16.2 1.21284 198.54599 0.22755 4 101860 16.2 1.21168 285.36035 0.22755 5 101860 16.2 1.21032 387.71022 0.22755 6 101860 16.2 1.20878 501.78798 0.22755 7 101860 16.2 1.20703 631.63481 0.22755 8 101860 16.2 1.20512 773.38864 0.22755

Differential Pressure, (Pa) - 11 - Table 2.6 Test data for leakage coefficient when louvers are closed No. Volume Flow ( Q n ) Volume Flow ( Q n 2 ) Correlation Values ( Q n 2 ) Percentage Difference Theoretical Flow, ( Q t ) Coefficient of Discharge m 3 /s % m 3 /s C d 1 0.22778 0.05189 0.05138-0.99 2.3939849 0.095 2 0.30539 0.09327 0.09488 1.70 3.2662840 0.093 3 0.38371 0.14724 0.15017 1.95 4.1173743 0.093 4 0.46064 0.21219 0.21547 1.52 4.9384881 0.093 5 0.53904 0.29056 0.29246 0.65 5.7596514 0.094 6 0.61293 0.37569 0.37827 0.68 6.5566063 0.093 7 0.68767 0.47289 0.47594 0.64 7.3614831 0.093 8 0.76394 0.58361 0.58257-0.18 8.1522255 0.094 800 700 600 500 400 300 200 100 0 0.0 0.1 0.2 0.3 0.4 0.5 0.6 Q n 2 Figure 2.5 Graph of differential pressure versus Q n 2 for closed louvers The ventilator is not to size according to BS 7346-1: 1990. The dimensions of the smallest ventilator are specified as 1.2m by 1.2m. The size of the tested ventilator is 0.615m by 0.37m. It can be seen from figures 2.4 and 2.5 that the test results are very linear as required by the BS. The accuracy is denoted by the percentage differences in tables 2.2, 2.4 and 2.6 and is within 5% as also required by the BS. The average coefficient of discharge for the fire open position is 0.521 with the mechanisms and 0.726 without the mechanisms. It can now be concluded that the discharge coefficient of the actual

- 12 - size ventilator used in the industry lies between these two values of 0.521 and 0.726. The average coefficient of leakage is 0.094 for when the louvers are closed. Rain Testing The weatherproof characteristics of natural/smoke ventilators in the closed position were tested at a variety of angles by driving rain at them. A draught tunnel was used instead of a wind machine as specified in the BS to create a wind speed of 13m/s across the ventilator. A water nozzle was used to create a rainfall of 75mm/h and the details of the ventilator under tests were recorded. The rainfall was measured with a rain meter connected to the test rig (figures 3.2 and 3.5). The test positions of the ventilator will now be explained together with the results. Results and Comments Wind direction Rain θ Top view Side view Figure 3.1 Rain test configuration 1

- 13 - Figure 3.2 Picture of ventilator in rain test (configuration 1) The ventilator was tested at different angles in configuration 1 where the values of θ were 0, 15, 30, 45, 90 degrees. There were no leakages. Wind direction Rain 45 Top view Side view Figure 3.3 Rain test configuration 2 (flat) Wind direction Rain θ Top view Side view Figure 3.4 Rain test configuration 2 at an angle

- 14 - Figure 3.5 Picture of ventilator in rain test (configuration 2) The ventilator was tested at different angles in configuration 1 where the values of θ were 0, 45, 90 degrees. There were no leakages. Wind direction Top view Figure 3.6 Rain test configuration 3 (flat)

- 15 - Wind direction Rain θ Top view Side view Figure 3.7 Rain test configuration 3 at an angle This was only tested in a horizontal position and there were no leaks. It can now be concluded that the ventilator succeeded the rain tests to British standards (BS 7346-1:1990). Wind Load Testing The ventilator was connected to a fan unit with a short wind tunnel section. The pressure on the ventilator was measured with a pressure transducer. The load on the ventilator was 2.4 kn/m 2 for suction and pressure. Fan unit Figure 4.1 Ventilator on wind pressure test rig Results and Comments The ventilator did not fail during this test. The ventilator was not to size and smaller than the actual ventilators used in the industry. It is not possible to comment on what the outcome of this test would have been if the ventilator area was larger. A larger area will influence the outcome of the test negatively. Temperature Rise

Temperature [deg C] - 16 - This test simulated the rise in temperature above a developing fire. The aim of this test was to determine at what temperature the diffusible link fails which causes the ventilator to open. Two sets of conditions were simulated: a) a slowly developing fire producing a slow rate of rise in temperature; b) a rapidly developing fire producing a rapid rate of rise in temperature. Ventilator Radiation shield Gas burner Figure 5.1 Ventilator on fire test rig Results and Comments The results for the slow and fast temperature rise are shown in figures 5.1 and 5.2. The temperatures at the point where the louvers opened is depicted on these figures. It can be seen that the louvers opened when the temperature of the diffusible link was 73 C for the slow temperature rise test and 89.1 C for the fast temperature rise test. It was expected that the temperature of the diffusible link at its yield point would be higher during the fast temperature rise test. The reason for this is that the temperature measured of diffusible link was its surface temperature and not its average temperature. The convective heat transfer from the hot air to the diffusible link and the melting of the diffusible link is time dependant. The surface temperature of the diffusible link increased while its melting process occurred relatively slowly compared to the temperature rise. 100 90 80 70 60 50 40 30 20 10 0 73.72 0 5 10 15 20 25 Time [min]

Temperature [deg C] - 17 - Figure 5.2 Graph of temperature versus time of the diffusible link and outside environment for the slow temperature rise test 100 90 80 70 60 50 40 30 20 10 0 0 20 40 60 80 100 120 140 160 180 200 Time [s] 89.1 Figure 5.3 Graph of temperature versus time of the diffusible link and outside environment for the fast temperature rise test Fatigue Testing The ventilator was opened and closed 30000 times without any breakages. A pneumatic actuator was used to open and close the ventilator and a counter was used to count the cycles. Figure 6.1 Photo of the test set up for the fatigue testing of the ventilator

- 18 - Conclusion The air ventilator was successfully tested to BS 7346-1:1990 standards. The test setups and results were explained. The only discrepancy of these tests was that the ventilator is not to size according to the BS standards.