Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25 Trip Units

Similar documents
Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

Innovative Techniques for Mitigating Arc Flash Exposure

CMC Series Moulded Case Circuit Breaker Cielo Electric

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

MaxSB - Low Voltage Switchboard

S(U)200 series SU200M, SU200MR, and S200UDC UL 489 series

Protection of motor circuits

CEAG HandRail LED. Hand rail mounted Luminaire for all applications

5KP-HR Series. TVS Diodes Axial Leaded 5 kw > 5KP-HR series. Description. Uni-directional

The IEC61508 Operators' hymn sheet

Analysis of Pressure Rise During Internal Arc Faults in Switchgear

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

Recent changes in workplace safety regulations have heightened the awareness of hazards associated with electrical arcs.

Copeland Discus with CoreSense Diagnostics January 2011

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

Circuit breakers PR 60

For Air Pressure. AP-30 Series. Digital Display & Digital Control. EASY-TO-SEE 2-color display. Two-color digital display pressure sensor

Pushbuttons and Indicating Lights

Minimum Approach Distances (MAD)

Why do I need to do an Arc-Flash Analysis?

GRUNDFOS DATA BOOKLET. Hydro Solo-E. Complete pressure boosting systems 50/60 Hz

C&G 2395 Exam Paper April Section A - All questions carry equal marks. Answer all three questions. Show all calculations.

Infrared Thermography Inspection Guidelines. Date Issued:

CLASS CC/CD CCMR SERIES FUSES

Page 2 of 46 Prepared by: Engr. Ram Sankar

Class CC/CD CCMR Series FUSES

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

SPIRIT III Radiometer Saturation Effect

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

TVS Diodes Axial Leaded 30 kw > 30KPA-HRA series. Features. 30 kw 8.0 W 400 A. -55 to 175 C. Notes: 8.0 C/W

15KPA-HRA Series. TVS Diodes Axial Leaded 15 kw > 15KPA-HRA series. Descritions

Meta-MEC Manual Motor Starters

TECHNICAL PAPER PRESENTATION

RPS900W Redundant Power Supply. Installation Guide.

Zelio Relays RSL Slim Interface Plug-In Relays

DX 3 RCDs. Technical data Nature and consequences of electrical risks Direct and indirect contact. Direct contacts

Electrical Shore Connections

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

Effective March 2015 Supersedes S August 2002

Self Heating Sensing Applications

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

ARC FLASH HAZARD ANALYSIS

ATTACHMENT 2 REQUIREMENTS MILLE LACS ENERGY COOPERATIVE S SCHEDULE 3 DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS TABLE OF CONTENTS.

Advanced Pump Control for Irrigation Applications

Dimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

Field Certification Certificate of Compliance

Solaris Nitrogen. Installation Guide. Solaris Nitrogen Installation Guide Rev 1 PN IG /09/16

COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

MEDIUM VOLTAGE DIN Fuse-Links

INSTALLATION,OPERATION AND MAINTENANCE INSTRUCTIONS DRY AIR COOLER

Confidence comes with knowing you are Code-Ready.

STCP 08-2 Issue 004: Circuit Live Trip & DAR Tests

UNDERSTANDING ARC FLASH REQUIREMENTS

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

Ultima. X Series Gas Monitor

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

FULL STAINLESS STEEL EXPLOSION-PROOF SOLUTIONS OIL & GAS I OFFSHORE AND ONSHORE

10 Best Practices for Electrosurgical Unit Testing

Technical Data. General specifications. Rated operating distance s n 2 mm

Technical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm. Short-circuit protection

PERIODIC INSPECTION REPORT FOR AN ELECTRICAL INSTALLATION

Safety switch renewal parts

Online DGA-monitoring of power transformers

ASDX Series Silicon Pressure Sensors

Functional Example CD-FE-I-029-V30-EN Safety-related controls SIRIUS Safety Integrated

A4 Operation Manual. Fig.1-1 Controller Socket Diagram

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

ES18 Security Theory/Regulations Answer Schedule

POW ER EN GIN EER S, LLC Electrical Engineering, Power, Lighting, Technical Studies and Utility Consulting

Preview to the 2018 NFPA 70E, the Standard for Electrical Safety in the Workplace

Engineering Technical Report 128. Risk Assessment for BT Operators Working In a ROEP Zone. Draft for Approval

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

Multistack BACnet Solution: MS70/90 Standard Chiller Module

Proto Matrix Musashi 3 Upgrade Manual

Aquavar SOLO 2 Frequently Asked Questions

Certificate of compliance

AEROSPACE PART AND MATERIAL CROSS-REFERENCE

Meta-MEC Manual Motor Starters

A4s Operation Manual

Vestas Cold Climate Solutions and next stepsclimate Offerings

Customer Responsibilities

DATA SHEET. BZD23 series Voltage regulator diodes DISCRETE SEMICONDUCTORS Jun 10. Product specification Supersedes data of October 1991

CP3R Quick Start Manual

GCMSD-Headspace Analysis SOP

VLT 2000 Series. How to size your VLT

CPN1 Quick Start Manual

MIL-STD-883G METHOD

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards. Instructions Guide for Civil Engineering Structures

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

TeSys protection components

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information

Established since ZANE GULFSTREAM Get the most out of your swimming pool with Zane solar pool heating.

SM6. instructions for use. connection with compartment for incoming cable from the top. MV distribution factory built assemblies at your service

Testing Distribution Switchgear for Partial Discharge

Sharing practice: OEM prescribed maintenance. Peter Kohler / Andy Webb

Service Instructions. Syntron Control Model: CSCR-1-B (115V)

CONTENTS TABLE OF MAIDA S HISTORY TERMINOLOGY & GENERAL SPECIFICATIONS. iii. LEAD CODES and TAPE & REEL STANDARD SERIES 1 HC SERIES 17

Transcription:

Series NRX NF and RF Circuit Breakers PXR 20/25 Trip Units Contents Description Page Revision notes....2 PXR catalog number convention....3 PXR 20 trip units....4 PXR 25 trip units....5 Curves Long Delay I 2 t and Short Delay Flat Response:....TC013001E....6 Long Delay I 2 t and Short Delay I 2 t Response....TC013002E....7 Long Delay I 0.5 t and Short Delay Flat Response:....TC013003E....8 Long Delay I 0.5 t and Short Delay I 2 t Response:....TC013004E....9 Long Delay I 1 t and Short Delay Flat Response:....TC013005E.... 10 Long Delay I 1 t and Short Delay I 2 t Response:....TC013006E.... 11 Long Delay I 4 t and Short Delay Flat Response:....TC013007E.... 12 Long Delay I 4 t and Short Delay I 2 t Response:....TC013008E.... 13 Ground (Earth) Flat Response:... TC013009E.... 14 Ground (Earth) I 2 t Response:....TC013010E... 15 Instantaneous Response:....TC013011E... 16 High Instantaneous Response:....TC013012E... 17 Maintenance Mode Protection Response:....TC013013E... 18

Revision notes Note: Unless noted below, all curves remain unchanged from their prior revision. 2

Application Data AD013001EN PXR catalog number convention Table 1. Breakdown of the PXR Trip Unit Catalog Numbering Convention. General curve notes: 1. These curves apply to 50Hz and 60Hz applications. 2. These curves are comprehensive for Series NRX NF/RF (IZMX 16/40) style circuit breakers including all frame sizes, ratings and constructions. The total clearing times shown include the response time for the trip unit, the breaker opening and the interruption of the current. The bottom of the time band is the minimum commit to trip time. 3. These curves apply to an ambient of -20 C to +50 C. Trip Unit temperature above 85 C will cause an over-temperature trip and light the Long cause of trip LED. 4. The end of the curve is determined by the application or the interrupting rating of the circuit breaker. 3

PXR 20 trip units LSI LSIG LSI W/Maintenance Mode LSIG W/Maintenance Mode Figure 1. PXR 20 Trip Units. 4

Application Data AD013001EN PXR 25 trip units LSI LSIG LSI W/Maintenance Mode LSIG W/Maintenance Mode Figure 2. PXR 25 Trip Units. 5

Curves Long Delay I 2 t and Short Delay Flat Curves 1. Long Delay pickup is 110% of the Ir setting (0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 0.95, 1.0) with ±5% 2. Long Delay Time Settings 0.5s to 24s have +0%/-30% 3. If Thermal Memory is enabled, trip times may be shorter than indicated in this curve. 4. Short Delay pickup settings have ±10% 5. If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value. 6. With ZSI enabled, tripping times for 3-phase faults, no aux. power will be a maximum of 75ms for 60Hz and 80ms for 50Hz. Figure 3. PXR 20/25 Long Delay I 2 t and Short Delay Flat Response Curve Number: TC013001E August 2016. 6

Application Data AD013001EN Long Delay I 2 t and Short Delay I 2 t Curves 1. Long Delay pickup is 110% of the Ir setting (0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 0.95, 1.0) with ± 5% 2. Long Delay Time Settings 0.5s to 24s have +0% /-30% 3. If Thermal Memory is enabled, trip times may be shorter than indicated in this curve. 4. Short Delay pickup settings have ±10% 5. Short Time delay (0.5, 0.4, 0.3) I 2 t slopes have a +0%/-30% tolerance, 0.1s slope has a +0%/-40% 6. If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value. 7. With ZSI enabled, tripping times for 3-phase faults, no aux. power will be a maximum of 75ms for 60Hz and 80ms for 50Hz. Figure 4. PXR 20/25 Long Delay I 2 t and Short Delay I 2 t Response Curve Number: TC013002E August 2016. 7

Long Delay I 0.5 t and Short Delay Flat Curves 1. Long Delay pickup is 110% of the Ir setting (0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 0.95, 1.0) with ±5% 2. Long Delay Time Settings 0.5, 1, 2, 4, 7, 10, 12, 15, 20, 24s (not all shown) have +0%/-30% 3. If Thermal Memory is enabled, trip times may be shorter than indicated in this curve. 4. Short Delay pickup settings of 1.5, 2, 2.5, 3, 4, 5, 6, 7, 8, 10 (not all shown) have ±10% 5. If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value. 6. With ZSI enabled, tripping times for 3-phase faults, no aux. power will be a maximum of 75ms for 60Hz and 80ms for 50Hz. Figure 5. PXR 20/25 Long Delay I 0.5 t and Short Delay Flat Response Curve Number: TC013003E August 2016. 8

Application Data AD013001EN Long Delay I 0.5 t and Short Delay I 2 t Curves 1. Long Delay pickup is 110% of the Ir setting (0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 0.95, 1.0) with ± 5% 2. Long Delay Time Settings 0.5, 1, 2, 4, 7, 10, 12, 15, 20, 24s (not all shown) have +0%/-30% 3. If Thermal Memory is enabled, trip times may be shorter than indicated in this curve. 4. Short Delay pickup settings of 1.5, 2, 2.5, 3, 4, 5, 6, 7, 8, 10 (not all shown) have ±10% 5. Short Time delay (0.5, 0.4, 0.3) I 2 t slopes have a +0%/-30% tolerance, 0.1s slope has a +0%/-40% 6. If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value. 7. With ZSI enabled, tripping times for 3-phase faults, no aux. power will be a maximum of 75ms for 60Hz and 80ms for 50Hz. Figure 6. PXR 20/25 Long Delay I 0.5 t and Short Delay I 2 t Response Curve Number: TC013004E August 2016. 9

Long Delay I 1 t and Short Delay Flat Curves 1. Long Delay pickup is 110% of the Ir setting (0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 0.95, 1.0) with ±5% 2. Long Delay Time Settings 0.5, 1, 2, 4, 7, 10, 12, 15, 20, 24s (not all shown) have +0%/-30% 3. If Thermal Memory is enabled, trip times may be shorter than indicated in this curve. 4. Short Delay pickup settings have of 1.5, 2, 2.5, 3, 4, 5, 6, 7, 8, 10 (not all shown) ±10% 5. If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value. 6. With ZSI enabled, tripping times for 3-phase faults, no aux. power will be a maximum of 75ms for 60Hz and 80ms for 50Hz. Figure 7. PXR 20/25 Long Delay I 1 t and Short Delay Flat Response Curve Number: TC013005E August 2016. 10

Application Data AD013001EN Long Delay I 1 t and Short Delay I 2 t Curves 1. Long Delay pickup is 110% of the Ir setting (0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 0.95, 1.0) with ±5% 2. Long Delay Time Settings 0.5, 1, 2, 4, 7, 10, 12, 15, 20, 24s (not all shown) have +0%/-30% 3. If Thermal Memory is enabled, trip times may be shorter than indicated in this curve. 4. Short Delay pickup settings of 1.5, 2, 2.5, 3, 4, 5, 6, 7, 8, 10 (not all shown) have ±10% 5. Short Time delay (0.5, 0.4, 0.3) I 2 t slopes have a +0%/-30% tolerance, 0.1s slope has a +0%/-40% 6. If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value. 7. With ZSI enabled, tripping times for 3-phase faults, no aux. power will be a maximum of 75ms for 60Hz and 80ms for 50Hz. Figure 8. PXR 20/25 Long Delay I 1 t and Short Delay I 2 t Response Curve Number: TC013006E August 2016. 11

Long Delay I 4 t and Short Delay Flat Curves 1. Long Delay pickup is 110% of the Ir setting (0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 0.95, 1.0) with ±5% 2. Long Delay Time Settings 0.5s to 7s have +0%/- 30% 3. If Thermal Memory is enabled, trip times may be shorter than indicated in this curve. 4. Short Delay pickup settings of 1.5, 2, 2.5, 3, 4, 5, 6, 7, 8, 10 (not all shown) have ±10% 5. If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value. 6. With ZSI enabled, tripping times for 3-phase faults, no aux. power will be a maximum of 75ms for 60Hz and 80ms for 50Hz. 7. For the Long Time I 4 t slope only, all settings above 7 seconds will default to a maximum allowable 7 second time delay band. Figure 9. PXR 20/25 Long Delay I 4 t and Short Delay Flat Response Curve Number: TC013007E August 2016. 12

Application Data AD013001EN Long Delay I 4 t and Short Delay I 2 t Curves 1. Long Delay pickup is 110% of the Ir setting (0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 0.95, 1.0) with ±5% 2. Long Delay Time Settings 0.5s to 7s have +0%/- 30% 3. If Thermal Memory is enabled, trip times may be shorter than indicated in this curve. 4. Short Delay pickup settings of 1.5, 2, 2.5, 3, 4, 5, 6, 7, 8, 10 (not all shown) have ±10% 5. Short Time delay (0.5, 0.4, 0.3) I 2 t slopes have a +0%/-30% tolerance, 0.1s slope has a +0%/-40% 6. If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value. 7. With ZSI enabled, tripping times for 3-phase faults, no aux. power will be a maximum of 75ms for 60Hz and 80ms for 50Hz. 8. For the Long Time I 4 t slope only, all settings above 7 seconds will default to a maximum allowable 7 second time delay band. Figure 10. PXR 20/25 Long Delay I 4 t and Short Delay I 2 t Response Curve Number: TC013008E August 2016. 13

Ground (Earth) Flat Curves 1. Ground Pickup settings shown are for Residual sensing with a tolerance of ± 10%. Pick up settings for Source Ground/Zero Sequence sensing have a tolerance of ± 15%. 2. Ground slope Flat, trip time tolerance is +0ms/- 80ms for all settings except 0.1s setting is +0ms/- 40ms 3. If Thermal Memory is enabled, trip times may be shorter than indicated in this curve. 4. With ZSI enabled, tripping times for 3-phase faults, no aux. power will be a maximum of 75ms for 60Hz and 80ms for 50Hz. Figure 11. PXR 20/25 Ground (Earth) Flat Response Curve Number: TC013009E August 2016. 14

Application Data AD013001EN Ground (Earth) I 2 t Curves 1. Ground Pickup settings shown are for Residual sensing with a tolerance of ± 10%. Pick up settings for Source Ground/Zero Sequence sensing have a tolerance of ± 15%. 2. If Thermal Memory is enabled, trip times may be shorter than indicated in this curve. 3. Break point is at 0.625 x In from I 2 t to flat. 4. Ground slope: I 2 t, tolerance is: 0.1s, 0.2s: +0%/-40% 0.3s, 0.4s, 0.5s: +0%/-30% 5. With ZSI enabled, tripping times for 3-phase faults, no aux. power will be a maximum of 75ms for 60Hz and 80ms for 50Hz. Figure 12. PXR 20/25 Ground (Earth) I 2 t Response Curve Number: TC013010E August 2016. 15

Instantaneous Curves 1. The Instantaneous pickup settings have a ±10% Figure 13. PXR 20/25 Instantaneous Response Curve Number: TC013011E August 2016. 16

Application Data AD013001EN High Instantaneous Curves 1. The 90kA peak curve applies to IEC and UL 489 Selective NF (IZMX16) frame Series NRX breakers 2. The 167 ka peak curve applies to RF (IZM40) frame Series NRX breakers with an (Icu) interrupting rating of 100kA and above. 3. The 138 ka peak curve applies to UL 489 Selective Series NRX RF frame series with an (Icu) interrupting rating of 85kA and above. 4. The 18-6 7kA peak curves apply to UL 489 Switchboard Protective Series NRX breakers with the instantaneous asymmetrical peak value of 22.5 times the frame current rating. 5. The Instantaneous pickup settings have a ±10% 6. This protection is functional even when the Instantaneous is set to the OFF position. 7. The PXR trip unit will light the Instantaneous LED for a High Instantaneous trip. 8. The total High Instantaneous clearing times shown are conservative and consider the maximum response times of the trip unit, the circuit breaker opening, and the interruption of the current under factors that contribute to worst case conditions, such as: maximum rated voltages, single phase interruption, and minimum power factor. Faster clearing times are possible depending on the specific system conditions. Figure 14. PXR 20/25 High Instantaneous Response Curve Number: TC013012E August 2016. 17

Maintenance Mode Curves 1. Reduction Pickup settings have a ±20% 2. The trip unit will light the Instantaneous LED for a Maintenance Mode protective trip. Figure 15. PXR 20/25 Maintenance Mode Protection Response Curve Number: TC013013E August 2016. 18

Application Data AD013001EN 19

At Eaton, we re energized by the challenge of powering a world that demands more. With over 100 years experience in electrical power management, we have the expertise to see beyond today. From groundbreaking products to turnkey design and engineering services, critical industries around the globe count on Eaton. We power businesses with reliable, efficient and safe electrical power management solutions. Combined with our personal service, support and bold thinking, we are answering tomorrow s needs today. Follow the charge with Eaton. Visit eaton.com/electrical. Eaton Electrical Sector 1000 Eaton Boulevard Cleveland, OH 44122 United States 877-ETN-CARE (877-386-2273) Eaton.com 2016 Eaton All Rights Reserved Printed in USA Publication No. AD013001EN / TBG001334 August 2016 Eaton is a registered trademark. All other trademarks are property of their respective owners.