Balancing HVAC Hydronic Systems Part 3: Flow Measurement Valves

Similar documents
MANUAL FLOW CONTROL 2-1/2" - 18" QUICKSET FLOW CHART

HVAC Hydronic Pumps: B&G Triple Duty Valve for Proportional Balance

Lesson 6: Flow Control Valves

This portion of the piping tutorial covers control valve sizing, control valves, and the use of nodes.

Hydronic Systems Balance

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

AUTOMATIC FLOW CARTRIDGES. Competition Analysis Not All Automatics Are Created Equal

Exercise 2-3. Flow Rate and Velocity EXERCISE OBJECTIVE C C C

Full Range Pressure Compensating Variable Flow Control

TECHNICAL DATA Q= C. Table 1 - Specifications

Pressure Independent Control Series

SFC. SKYLINE FLOW CONTROLS INC. The Leader of Accurate and Reliable Flow Measurement DESCRIPTION & APPLICATIONS: ADVANTAGES:

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No

Lab 3 Introduction to Quantitative Analysis: Pumps and Measurements of Flow

RadKits (Piping Packages)

ONSITE PROVING OF GAS METERS. Daniel J. Rudroff WFMS Inc West Bellfort Sugar Land, Texas. Introduction

130400A 1/2 NPT Female A 3/4 NPT Female A 1 NPT Female A 1 1/4 NPT Female A 1 1/2 NPT Female A 2 NPT Female

Bell & Gossett ESP-Systemwize Pump Selections

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A

Some system examples

T208VR Series Tank Blanketing Vacuum Regulator

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

Valve Sizing Considerations. Steven Hocurscak Metso Automation

Model 420-HY Pressure Regulating Hydrant Valve

LAKOS Waterworks. PWC Series Sand Separators. Installation & Operation Manual LS-829 (10/12)

STAD Series. Balancing and control valves. Technical Data Sheet. WattsIndustries.com

TECHNICAL DATA. Table 1 - Specifications

Wet pipe low flow foam/water system

TECHNICAL DATA NOTICE

Cover Page for Lab Report Group Portion. Head Losses in Pipes

The Discussion of this exercise covers the following points:

HOW TO NOT MEASURE GAS - ORIFICE. Dee Hummel. Targa Resources

Rate of Flow Valve Series 120

IT STARTS AT THE SOURCE - RE-CALIBRATING YOUR PLANT METERS

Wilo Triple Duty Valve / Triple Service Valve Installation and operating instructions

WW-730. Pressure Sustaining/Relief Control Valve

HERZ-Motorised flow controler

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

Balancing Valves. Applications/ Features: Ordering Information: Accessories:

Sizing Pulsation Dampeners Is Critical to Effectiveness

A centrifugal pump consists of an impeller attached to and rotating with the shaft and a casing that encloses the impeller.

Cover Page for Lab Report Group Portion. Compressible Flow in a Converging-Diverging Nozzle

PRODUCT INFORMATIONAL BULLETIN

Cover Page for Lab Report Group Portion. Pump Performance

Injection Systems INSTALLATION AND OPERATING GUIDE HI FLO VERTICAL TANK SYSTEMS

IWCF Equipment Sample Questions (Surface Stack)

Process Dynamics, Operations, and Control Lecture Notes - 20

Chapter 9 System Design Procedures

TECHNICAL DATA. Page 1 of 12

SB AXIAL FLOW VALVES

Restriction Orifice. Single or Multi Stage Orifice to. Reduce Pressure or. Limit the Flow Rate

Model MC Circuit Setter Hose Kits Supply Valve Options: Ball Valve, UBY

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

Tech Tips. Service Call: Adjustable Hydraulic Valves Flow controls Pressure controls Sequence valves Holding valves

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION

CHAPTER 7 : SMOKE METERS AND THEIR INSTALLATIONS

Installation Manual. Model # SF-3W 9/16/03 REV 1. Arch Chemicals, Inc Lower River Road. P.O. Box 800 Charleston, TN PULSAR

INDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR NPTEL ONLINE CERTIFICATION COURSE. On Industrial Automation and Control

STAP. Differential pressure controller DN 15-50

SINGLE VALVE WITH LOW-FLOW BYPASS

TECHNICAL DATA. than the water inlet pressure to the concentrate

PRO SINK -R 1 and 2. Dilution system CONTENTS

Foam Mixers & Proportioning Systems

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4

COMPARING PLUG & SEAT REGULATORS & CONTROL VALVES. Lamar Jones. Equipment Controls Company 4555 South Berkeley Lake Road Norcross, GA 30071

FILTER BYPASS CONTROL

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

FUNDAMENTALS OF PRESSURE REGULATORS ROBERT BENNETT MANAGER OF TRAINING ELSTER AMERICAN METER

Figure 4 Figure 5 Figure 6

Installation Instructions

SUBMITTAL NOTES PROJECT: Ross Model 50RWR-A Pilot Operated Surge Relief Valve with Hydraulic Anticipation. Size: inch / mm

LINE PROPORTIONERS LP NPR260 Approvals: UL, ULC

A REVIEW OF THE 2000 REVISIONS TO ANSI 2530/API MPMS 14.3/AGA REPORT NO. 3 - PART2 Paul J. LaNasa CPL & Associates

Operating Instructions

1 Exam Prep. Tabs and Highlights

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

SIZING AND CAPACITIES OF GAS PIPING

INTERNATIONAL STANDARD

Integral type Differential pressure flowmeter VNT Series

GW DRY PIPE VALVE INSTALLATION & OPERATION 100mm (4 ) 150mm (6 )

OBSOLETE DESIGN DATA. Foam 301a. February 9, 1998

Residential Pressure Booster Systems

DS05C,D,G Dial Set Pressure Regulating Valves

BACK PRESSURE / SUSTAINING

STANDARD FOR CONTROL VALVE SEAT LEAKAGE

Spring Loaded Regulators Constant Loaded Regulators Twin Parallel Flow Regulators Field Service Regulators

Flow meter. bellow vaporizer. APL valve. Scavenging system

PCMTV Pressure independent control valves, DN20-DN32 with integrated flow limiter for thermal emitters and differential pressure regulator

BACK PRESSURE / SUSTAINING

FloCon Commissioning Modules DESIGN GUIDE - JUNE Variable Flow Systems & Solutions brought to you by Hurlstones

1805 Series Relief Valves

Cover Page for Lab Report Group Portion. Compressible Flow in a Converging-Diverging Nozzle

Pumping Systems for Landscaping Pumps, Controls and Accessories. Mark Snyder, PE

Bermad Pressure Reducing. Model: 42T

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY PNEUMATIC RELEASE. 1. DESCRIPTION (Refer to Figures 1, 2 or 3.

TECHNICAL DATA CAUTION

PumpAgents.com - Click here for Pricing/Ordering Nominal psi (bar) Cut-In Cut-Out

FUNDAMENTAL PRINCIPLES OF SELF-OPERATED PRESSURE REDUCING REGULATORS. John R. Anderson Emerson Process Management Fluid Controls Institute

Blue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION

Transcription:

Balancing HVAC Hydronic Systems Part 3: Flow Measurement Valves Monday Morning Minutes by Norm Hall, August 20, 2018 The flow balance of a hydronic system is a critical component in the commissioning of an HVAC hydronic system. The common balance and flow measurement valves we use to accomplish the balance of the system break down into categories of manual and automatic balance. Today, the R. L. Deppmann Monday Morning Minutes looks at the types of valves and the advantages and disadvantages of both. Monday, August 20, 2018 In the prior MMM, I showed a system out of balance with more flow rate than needed going to the zone closest to the pump. Take a look at the simple sketch below and assume the first terminal unit has less pressure drop than the second one. At the design flow rate, the pressure drop from the pump discharge through the first zone and back to the pump suction is less than the same trip through the second zone. As a result, the water takes the path of least resistance and flows more through the nearer zone.

The goal of the balance valve is to increase the pressure drop in the zone flowing too much water. If we cause the right amount of pressure drop or pipe restriction in the first zone, the flow will decrease in that zone and increase in the second zone. You could use a hammer to reduce the area in the pipe but you only get one shot and you can t read the flow rate to see if you achieved your goal! Manual Balance Valves Ball Butterfly Valves: The Simplest Balancing Valves The first balance valve used in hydronic systems was the variable orifice balance valve. If you think about it, plug valves, ball valves, and butterfly valves are all variable orifice balance valves. If you throttle the valve, the hole the water goes through is reduced in size and therefore the pressure drop increases. Way back in the 1940s and 1950s, this was the balance valve used. The contractor throttled the valve and used thermometers and pressure gauges to determine if they were

close enough to call the system balanced. It was the art that started the Balancing Contractor Industry. Today, we may still use these devices as balance valves, but we couple them with a separate, properly installed flow measuring device. Variable Orifice Balance and Flow Measurement Valve: The Bell & Gossett Circuit Setter The Bell & Gossett Circuit Setter was the first combination balance and flow measuring valve to have national distribution. It is a ball valve or globe valve with ports across the valve and charts to read the throttled differential to flow ratio depending on where the calibrated dial is set. Advantages: Disadvantages: 1. Probably the best advantage of this device is how recognizable it is. The industry can recognize the Circuit Setter installed 3 years ago or three decades ago. B&G has re-engineered the product over time but kept the flow characteristics the same. The chart you use today is the chart you can use on the same size older valve. 2. Much lower straight lengths of pipe are required for accurate measurement (3 diameters upstream and 1 downstream). 3. High repeatability and 5% accuracy. 4. In stock everywhere. 1. The prime disadvantage is reading flow rates less than ¾ GPM while requiring high-pressure drops. You can set the valve to read less than ½ GPM but there is not much throttle capability.

Constant Orifice Balance and Flow Metering Valve: Griswold Quickset and B&G Venturi The venturi type balancing valve is different from the circuit setter. A modified venturi is a small orifice with smooth entrance and exit paths. It is modified because a true venturi would be significantly longer. This is two devices joined together. The differential is read across the fixed orifice. The flow is throttled across a separate ball or butterfly valve. The differential across the orifice is read in inches. Some might argue the pressure drop is significantly less. For example, a balanced Quickset might read 40 inches while the circuit setter reads 40 feet. This is a little misleading since the equivalent of the 40 feet was throttled across the ball or butterfly valve. Even full open, the ball valve portion of the Quickset has some pressure drop that remains unread. Advantages: 1. Easier to read during the balancing. These devices may have a different sized opening or throat areas. So the inside of the flow meter changes depending on the flow. This allows the contractor to read enough differential for a more accurate setting. 2. Griswold s Quickset has a unique design that allows for no pipe diameters required after an elbow. Other brands will have 4-5 pipe diameters required.

Disadvantages: 1. The advantage of multiple throat diameters becomes a disadvantage if the tag is ever lost. Since each throat has a different chart to read, if you don t know the throat used, you don t know what chart to use. 2. The other disadvantage is the sheer number of manufacturers in the space. The B&G Circuit Setter or even the Griswold Quickset are recognizable years from now without the tag. If the specification is wide open to all manufacturers, there may be an issue of knowing who manufactured the valve. Next week, the R. L. Deppmann Monday Morning Minutes will look at automatic balance valves.