TATTVAM ENVIRONMENTAL AND ENGINEERING SOLUTIONS, LLC. Indoor Air Quality Report for Weston Public Schools Weston, CT.

Similar documents
Presented By: Kary S. Amin Nova Environmental, Inc. Nova Environmental, Inc.

UNDERSTANDING & INTERPRETING MATERIAL SAFETY DATA SHEETS. Introduction to Understanding MSDS's

Standards of Practice Respiratory Protection: Appendix C

Iowa Exceedances of the National Ambient Air Quality Standards, 2013 (Reported Through October 8 th ) Iowa DNR Ambient Air Monitoring Group

CSU Channel Islands Lead Operations and Maintenance Program

3 8210Plus/8210/8110S Particulate Respirator User Instructions (Keep these instructions for reference)

Material Safety Data Sheet acc. to ISO/DIS 11014

SAMPLING GUIDELINES FOR THE BI-AIR FILTER CASSETTE

VAV SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES

MATERIAL SAFETY DATA SHEET

Concordia College Moorhead, Minn.

3M MATERIAL SAFETY DATA SHEET 3M(TM) ESPE(TM) RELYX(TM) VENEER CEMENT TRY-IN PASTE REFILLS 02/24/2005

240 COLOR PAK - ALUMINUM STONE 6 POUCHES Version 2.0 Print Date 10/24/2012 REVISION DATE: 07/08/2012

RESPIRABLE CRYSTALLINE SILICA PROGRAM July 2018

SILICONES UNLIMITED, INC. MATERIAL SAFETY DATA SHEET

Material Safety Data Sheet acc. to ISO/DIS 11014

SILICA EXPOSURE MEASUREMENT IN REAL-TIME FOR CONSTRUCTION

ANSI / ASSE Z88.2 American National Standard Practices for Respiratory Protection (1992 rev. versus 2015 rev.)

Industrial Hygiene Sampling. Husqvarna Construction Products

ALBUQUERQUE PUBLIC SCHOOLS RESPIRATORY PROTECTION PROGRAM

Chapter 4: Monitoring and Sampling. Chapter 4: Monitoring and Sampling

Natural Ventilation Solutions for Urban Designs to incorporate Acoustic Considerations

OSHA Final Rule: Occupational Exposure to Respirable Crystalline Silica

INTERPRETATION IC OF ANSI/ASHRAE STANDARD VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY

SAFETY DATA SHEET OX Industries, Constantine, MI 700 Centreville Road Constantine, MI / Prepared 7/24/2015

: UNIVERSAL COLOR PACK SHADOW GRAY-cs

MATERIAL SAFETY DATA SHEET

Material Safety Data Sheet

Health & Safety Policy and Procedures Manual SECTION 34 HYDROGEN SULFIDE (H2S) PROGRAM

Material Safety Data Sheet acc. to ISO/DIS 11014

Carolina Narrow Fabric Company

Respiratory Protection

Use only for the purpose on the product label.

The MSDS format adheres to the standards and regulatory requirements of the United States and may not meet regulatory requirements in other countries.

Respiratory Protection Self Inspection Checklist

Respiratory Protection Self-Inspection Checklist

SAFETY DATA SHEET. Inhalation of vapor or spray mist. Eye contact with the product, vapor or spray mist.

MATERIAL SAFETY DATA SHEET

TECHNICAL BULLETIN September 17, 2001

Section 1 - PRODUCT AND COMPANY IDENTIFICATION. Section 2 - HAZARDS IDENTIFICATION

Title: Hexavalent Chromium Compliance. Preparer: Owner: Approver: Texas EHS EHS Team Member

MATERIAL SAFETY DATA SHEET Nano Mold Coating HC Version 1 R1 Print Date: Revision Date: POTENTIAL HEALTH EFFECTS

Safety Data Sheet. SECTION 1: Identification. SECTION 2: Hazard identification

MATERIAL SAFETY. St. Paul, Minnesota or (651) (24 hours)

MATERIAL SAFETY DATA SHEET Complies with OSHA Hazard Communication Standard 29 CFR

MATERIAL SAFETY DATA SHEET Complies with OSHA Hazard Communication Standard 29 CFR

STANDARD OPERATING PROCEDURES

Material Safety Data Sheet(MSDS) CMS Graphite Powder 1. IDENTIFICATION OF THE SUBSTANCE AND THE COMPANY

M a t e r i a l S a f e t y D a t a S h e e t

What I have learned about SF 6 gas testing.a Practical explanation

INSULPERM AND INSULPERM GEOFOAM SAFETY DATA SHEET

Hydrogen Sulfide (H 2 S) Program

Northeast Biomanufacturing Center and Collaborative. Hazard Communication Program (HCP) NBC-HCP-000

Material Safety Data Sheet

Material Safety Data Sheet Magnesium stearate

MATERIAL SAFETY DATA SHEET FILE NO.: MSDS-Inter-103Rh MSDS DATE: 11/07/2011 Product Name MAXPAR Nucleic Acid Intercalator, 103Rh

MATERIAL SAFETY. St. Paul, Minnesota or (651) (24 hours)

MATERIAL SAFETY DATA SHEET

Activated Carbon %

Safety Data Sheet. SECTION 1: Identification. SECTION 2: Hazard identification

Safety Data Sheet. Product identifier. Details of the supplier of the safety data sheet

Material Safety Data Sheet L-Phenylalanine

LEGIONELLA MANAGEMENT PROCEDURE

HAZARD COMMUNICATION SELF INSPECTION CHECKLIST

THIS MSDS IS OFFERED IN CANADIAN-FRENCH UPON REQUEST. ON PEUT DEMANDER CETTE MSDS A LA LANGUE FRANCAISE-CANADIENNE.

SILICA WEBINAR. Chris Chipponeri Chief Operations Officer Hazard Management Services, Inc.

Ingredient CAS Number Weight % ACGIH TLV PEL STEL Distillates (petroleum), % - 35% 5 mg/m3 5 mg/m3 10 mg/m3

ALPHAGUARD M-PRIME - 1 GALLON Version 1. Print Date 04/18/2012 REVISION DATE: 10/05/2011

MATERIAL SAFETY DATA SHEET MSDS DATE: 3/13/12

SAFETY DATA SHEET. AccuStandard, Inc SECTION 1 - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION Product Identifiers

Confined Space Program

Material Safety Data Sheet acc. to ISO/DIS 11014

MATERIAL SAFETY DATA SHEET

EMERGENCY PHONE: or (651) (24 hours)

SAFETY DATA SHEET CLEARGUM LG SECTION 1: Identification of the substance/mixture and of the company/undertaking

Material Safety Data Sheet acc. to ISO/DIS 11014

RESPIRATORY PROTECTION PROCEDURE

MATERIAL SAFETY DATA SHEET

EMI SUPPLY INC. MATERIAL SAFETY DATA SHEET

MATERIAL SAFTEY DATA SHEET

Ingredient CAS Number Weight % ACGIH TLV PEL STEL Methyltriacetoxysilane % - 5% TWA 10ppm TWA 10ppm 15ppm

SAFETY DATA SHEET SECTION

Application Note 13: Electron Microscope Decontamination

LABORATORY FUME HOOD SPECIFICATION AND MAINTENANCE PROGRAM

SAFETY DATA SHEET Wellmade WPC (Wood Plastic Composite Flooring)

DuPont Sealant for Tyvek Fluid Applied System

Particulate Respirator N95

Mechanical Technical Report 1 ASHRAE Standard 62.1 Ventilation Compliance Evaluation

Manhattan Fire Protection District

Respirable Crystalline Silica

RAZE DR 8810 MATERIAL SAFETY DATA SHEET ESSENTIALLY SIMILAR TO OSHA FORM 174

MATERIAL SAFETY DATA SHEET MSDS DATE: 7/08/09 SCENT WINTERGREEN SUPERSEDES: 6/23/08

Material Safety Data Sheet Taurine

CHEMICAL PRODUCT AND COMPANY IDENTIFICATION

Revision Date: March 8, 2017 Version No.: 2 SECTION 1 IDENTIFICATION OF THE SUBSTANCE / MIXTURE AND OF THE COMPANY / UNDERTAKING

The Following information is based on material prepared by the American Lung Association

MATERIAL SAFETY DATA SHEET

: Trim-Kut Grinding Disc

IC Sentinel Applications Guide for Healthcare Environmental Air Quality Monitoring

MATERIAL SAFETY. St. Paul, Minnesota or (651) (24 hours)

Transcription:

TATTVAM ENVIRONMENTAL AND ENGINEERING SOLUTIONS, LLC Indoor Air Quality Report for Weston Public Schools Weston, CT prepared for: Weston Public Schools 25 School Road Weston, CT November 17th, 2016 Tattvam IAQ Project # 16-101

Table of Contents Introduction Assessment and Monitoring Observations and Results of Sampling Conclusion Appendix A: Table of Real Time Measurements 2

Introduction and Engineering Solutions, LLC () was retained by Weston Public Schools to conduct Indoor Air Quality and Mold Testing at the four (4) schools at Weston, CT. The schools include the Elementary School, Intermediate School, the Middle School and Weston High School Assessment and Monitoring On November 5 th 2016, performed an indoor air quality assessment at the above referenced facilities. As requested by the client, the assessment included sampling for Temperature, Relative Humidity, Concentration of Dioxide, and Concentration of Monoxide, in accordance with ASHRAE 113 standards. The assessment also included a collection of mold samples, airborne particulates and real time measurement of Volatile Organic Compounds. The following sampling scheme was employed: Monitoring baseline indoor air quality parameters including temperature, relative humidity, carbon monoxide, and carbon dioxide. Monitoring for these parameters was conducted with a Supco IAQ55 Monitor. Airborne mold testing was performed utilizing Zefon International Incorporated s Air-O-Cell sampling device following manufacture supplied recommended sampling procedures. Monitor airborne respirable particulate (PM10), This testing was done using an MIE PDR-1000 personal data RAM. Monitor total Volatile Organic Compounds (VOC s). This testing was done using an Industrial Scientific VX500 Photo Ionization Detector. Results of Sampling The following air quality parameters were measured during the testing. Baseline Indoor Air Quality Parameters Temperature: The indoor temperatures ranged from are tabulated in Appendix A. In comparing this data to the American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) guidelines for thermal environmental conditions for Human Occupancy, it is determined that the indoor temperature data was within the acceptable range of operative temperature and humidity. 3

Relative Humidity: The indoor relative humidity readings are tabulated in Appendix A. The relative humidity was within the ASHRAE acceptable range of operative temperature and humidity as outlined in ASHRAE Standard 55-2004. Monoxide: The indoor carbon monoxide concentration reading on this day was 0 ppm. LEED EQc3.2 IAQ Management Plan for Testing Before Occupancy and U.S. Environmental Protection Agency National Ambient Air Quality Standard outlines the maximum limit as 9 ppm. Dioxide: According to the ASHRAE Standard 62-2001, Ventilation for Acceptable Indoor Air Quality, the difference between the indoor and outdoor concentrations should be less than 700 ppm. The concentrations observed were well within recommended range. Volatile Organic Compounds (VOC s): The indoor VOC concentration readings below the allowable maximum concentration limit of 500 μg/m3 the LEED Green Building Rating System for Existing Buildings required by the U.S. Green Building Council. 4

Mold Assessment The inspection involved a walk-through of the buildings to visually look for potential sources of biological agents (mold) and evidence of current or past water damage or excessive moisture. Evidence that active mold (fungal) growth is occurring is most often sensory (visual identification or odor perception) and may be confirmed by source sampling. There was no visual mold observed or water damage observed. There was no condensate or moisture observed on indoor surfaces or walls of the areas that were inspected. Destructive methods were not used to investigate for mold. Generally, destructive methods are only used when conditions indicate that mold may be present in an inaccessible area. Mold Spore Air Sampling Background Information on Mold According to the US EPA Office of Air and Radiation, Indoor Environments Division (6609-J) EPA 402-K-Ol-00l, March 2001: Molds can be found almost anywhere; they can grow on virtually any organic substance, as long as moisture and oxygen are present. There are molds that can grow on wood, paper, carpet, foods, and insulation. When excessive moisture accumulates in buildings or on building materials, mold growth will often occur, particularly if the moisture problem remains undiscovered or unaddressed. It is impossible to eliminate all mold and mold spores in the indoor environment. However, mold growth can be controlled indoors by controlling moisture. Sampling Method Sampling for airborne mold spores was conducted in all the buildings using Air-O- CeIl Air Sampling cassettes. Air-O-Cell Air Sampling cassettes are a sampling device designed for the rapid collection and analysis of a wide range of airborne aerosols. Air was sampled at a flow rate of 15 liters per minute (Ipm). Samples were then analyzed by microscopic examination at a certified lab and the results have been reported in fungal spores per cubic meter of air (spores/m3). Sampling Interpretation At this time there are no U.S. Environmental Protection Agency, OSHA or other Federal standards or threshold limits for mold or mold spores in an indoor environment. This is due to naturally diverse and variable exposure, the absence of measurement and health response data, and differing immunogenic susceptibilities 5

of individuals. Relationships between health effects and environmental microorganisms must be determined through the combined contributions of medical, epidemiological, and environmental evaluations. Air sampling for mold and mold spores is interpreted by: Comparing indoor airborne concentrations to outdoor mold spore concentrations. Total indoor airborne concentration levels higher than levels outside the building would indicate the possible presence of a fungal reservoir and amplification inside the building. Comparing species of mold inside and outside the building. Mold spores found inside and not outside the building could indicate a possible fungal reservoir and amplification inside the building. The presence of high airborne concentrations of indicator species, such as stachbotrys, which can indicate an excessive moisture problem or a possible health hazard that should not typically be present in healthy indoor environments. Mold Analysis: Laboratory results indicated the presence of certain fungi however, the spores/m3 observed were less than the outside ambient. In general, indoor levels of molds are usually 30-80% of outdoor levels and the distribution of spore types should be similar, which is the case in all schools. Conclusion Based upon the assessment and inspection in these facilities, has made the following conclusion: The indoor air quality at the Weston Public School buildings meets the requirements in the applicable standards of ASHRAE Standards for Acceptable Indoor Air quality and OSHA Permissible Exposure limits (PEL S). All readings observed were within acceptable range. Respectfully Submitted, and Engineering Solutions, LLC. Indu Nambiar Environmental Engineer 6

APPENDIX A 7

Room/ Area Temperature F Relative Humidity % IAQ PARAMETERS dioxide Elementary School monoxide Volatile Organic Compounds Respirable Particulates (mg/m 3 ) Main Lobby 68.3 29.8 504 0.0 0.0 0.001 South 68.6 29.1 490 0.0 0.0 0.000 Hallway Cafeteria 67.4 30.9 469 0.0 0.2 0.000 S-38 68.9 30.6 469 0.0 0.0 0.001 S-44 69.9 28.7 466 0.0 0.1 0.000 S-40 71.5 29.4 470 0.0 0.0 0.000 S-43 71.4 26.6 484 0.0 0.0 0.000 Library 69.5 29.0 466 0.0 0.0 0.001 Gym 70.0 28.7 458 0.0 0.0 0.000 N-24 71.3 28.4 536 0.0 0.3 0.012 N-21 72.0 27.6 478 0.0 0.1 0.000 Training Rm 75.5 27.8 463 0.0 0.0 0.000 N-10 74.4 27.5 475 0.0 0.0 0.000 N-8 75.6 30.9 459 0.0 0.0 0.002 N-6 74.5 30.7 496 0.0 0.0 0.000 E-35 70.5 29.6 470 0.0 0.0 0.002 E-32 71.2 28.0 469 0.0 0.0 0.000 E-31 72.2 28.8 472 0.0 0.0 0.000 West - 70.4 27.0 485 0.0 0.2 0.000 hallway Intermediate School Main Lobby 71.1 31.8 489 0.0 0.0 0.001 School Nurse 71.0 29.9 461 0.0 0.0 0.000 18 70.6 29.3 459 0.0 0.0 0.000 D-136 71.3 29.0 452 0.0 0.0 0.000 Main office 71.5 29.7 463 0.0 0.0 0.000 Library 71.6 29.2 440 0.0 0.0 0.004 Gym 69.5 30.1 440 0.0 0.0 0.000 Room 121 70.1 29.4 451 0.0 0.0 0.000 Copy Area 71.4 28.3 447 0.0 0.0 0.000 Room 213 71.7 27.4 409 0.0 0.0 0.000 Room 219 72.4 27.8 462 0.0 0.0 0.000 Custodial 72.4 27.1 449 0.0 0.0 0.000 Closet Room 215 71.6 27.5 454 0.0 0.0 0.000 Second Floor Hallway 71.4 27.2 432 0.0 0.0 0.000 8

Room/ Area Temperature F Relative Humidity % IAQ PARAMETERS dioxide Middle School monoxide Volatile Organic Compounds A06 69.3 31.9 451 0.0 0.0 Respirable Particulates (mg/m 3 ) 0.000 A03 69.5 31.8 450 0.0 0.0 0.000 A05 66.5 32.5 447 0.0 0.0 0.001 A04 66.8 33.4 446 0.0 0.0 0.022 A07 67.7 34.6 443 0.0 0.0 0.000 A09 69.9 32.3 486 0.0 0.0 0.000 B-11 68.2 31.6 452 0.0 0.0 0.001 B-09 67.1 32.5 448 0.0 0.2 0.000 B-05 67.0 35.8 442 0.0 0.0 0.000 B-07 67.8 35.2 522 0.0 0.0 0.000 C-24 68.3 34.4 506 0.0 0.0 0.003 C-21 69.3 33.3 474 0.0 0.0 0.000 Cafeteria 69.6 33.1 467 0.0 0.0 0.000 H-3 Tech 70.3 33.2 460 0.0 0.0 0.003 H-8 70.5 32.4 462 0.0 0.0 0.000 H-6 70.0 32.8 469 0.0 0.0 0.000 G-8 69.7 33.6 452 0.0 0.0 0.000 G-7 70.4 33.8 454 0.0 0.0 0.000 G-5 69.2 33.7 476 0.0 0.0 0.000 G-3 69.8 33.4 465 0.0 0.1 0.017 F-8 71.9 33.1 476 0.0 0.0 0.000 F-5 72.1 31.0 465 0.0 0.0 0.000 F-3 70.8 31.8 456 0.0 0.0 0.004 O/S Ambient 66.4 35.7 423 0.0 0.0 0.000 O/S Bathroom 70.9 33.2 468 0.0 0.0 0.000 High School Library 72.3 28.7 455 0.0 0.0 0.00 o/s Cafeteria 70.5 30.0 481 0.0 0.0 0.000 Gym 1A 71.2 33.1 491 0.0 0.0 0.000 O/S Basketball 75.7 37.3 479 0.0 0.0 0.000 training area F6 Training Room 72.6 28.8 477 0.0 0.0 0.001 C-12 71.3 29.4 444 0.0 0.0 0.000 C- Hallway 71.5 29.4 440 0.0 0.0 0.000 9

Room/ Area Temperature F Relative Humidity % IAQ PARAMETERS dioxide High School (Contd.) monoxide Volatile Organic Compounds Respirable Particulates (mg/m 3 ) B-10 70.5 29.1 441 0.0 0.1 0.000 B-6 68.0 28.6 464 0.0 0.0 0.001 O/S Office 71.0 30.3 489 0.0 0.0 0.000 Girl s 0.000 bathroom O/S 70.3 31.5 436 0.0 0.0 B- Hallway 68.6 33.6 452 0.0 0.0 0.000 B-1 30.1 0.0 0.0 0.000 C-2 70.5 31.5 448 0.0 0.0 0.000 Auditorium 68.0 32.2 445 0.0 0.0 0.004 C-15 71.5 30.1 441 0.0 0.0 0.000 C-3 71.4 29.1 462 0.0 0.0 0.000 D7 75.3 25.7 458 0.0 0.0 0.000 D- Hallway 74.0 27.4 449 0.0 0.0 0.000 D-6 72.8 27.8 445 0.0 0.2 0.000 C-5 71.6 28.7 443 0.0 0.0 0.000 Main Lobby 70.9 33.2 468 0.0 0.0 0.000 G-4 69.3 31.9 451 0.0 0.0 0.000 G-5 69.5 31.8 450 0.0 0.0 0.000 G-7 66.5 32.5 447 0.0 0.0 0.000 E- Hallway 68.2 30.2 446 0.0 0.0 0.000 Locker Area 67.6 30.8 489 0.0 0.0 0.000 10