DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS

Similar documents
MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS

Online DGA-monitoring of power transformers

Categorizing Faults via DGA. GE Grid Solutions M&D

Understanding Dissolved Gas Analysis (DGA) Techniques and Interpretations

Since the beginning of production of oil for transformers

Improved Monitoring of Dissolved Transformer Gases on the Basis of a Natural Internal Standard (NIS)

Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers

Dissolved Gas Analysis - Past, Present and Future

Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI

A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION

A Revised Framework for the Transformer DGA Guide

Research Article. Fault diagnosis of power transformer based on chemical properties of insulation oil

Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers

DGA Tools: Duval Triangles and Pentagons

Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks

Nandkumar Wagh, D.M. Deshpande

Dynamic Behaviour of Fault Gases and Online Gas Sensors. Germany

Mathieu Guertin. Morgan Schaffer Inc. Canada. Director Europe, Russia and Africa. A cost effective strategy for smart grid technology adoption

TRANSFORMER SERVICE. Dissolved gas analysis and oil condition testing

DISSOLVED GAS ANALYSIS OF POWER TRANSFORMERS

* Analysis of TCG ( Total Combustible Gas ) and 6 kinds of Gases * High Sensitivity for C 2

A New Approach for Transformer Incipient Fault Diagnosis Based on Dissolved Gas Analysis (DGA)

Diagnostics of HV bushings through oil sampling and analysis. Experience with GSU transformers

EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS

C I R E D 18 th International Conference on Electricity Distribution Turin, 6 th to 9 th June 2005

ASTM 3612/TOGA/Dissolved Gas GC Revised October 2013

Online Publication Date: 19 January, 2012 Publisher: Asian Economic and Social Society

Draft Guide for the Interpretation of Gases in Oil Immersed Transformers

Guide for the Sampling of Oil from Trench COTA Bushings for DGA

Automated Determination of Dissolved Gases in Water Anne Jurek. Abstract: Discussion:

Automated Determination of Dissolved Gases in Water Anne Jurek

Managing on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution power transformers

FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO

For many applications, there is no technical reason anymore to keep the oil volumes of a transformer with vacuum type OLTC separated

PROPOSAL FOR AN IMPROVEMENT IN TRANSFORMER DIAGNOSIS BY DGA USING EXPERT SYSTEM.

CTB3365x Introduction to Water Treatment

Condition Monitoring of Power Transformer Using Dissolved Gas Analysis of Mineral Oil: A Review

Rapid and Reliable Detection of Dissolved Gases in Water

Automated Determination of Dissolved Gases in Water By Headspace Calibration of Mixed Gases Anne Jurek

APPLICATION NOTE. Fast Analysis of Coal Mine Gas Using the INFICON 3000 Micro GC ABSTRACT

Analysis of Pressure Rise During Internal Arc Faults in Switchgear

AN EXPERIMENTAL AND ANALYTICAL STUDY OF PLASMA CLOSING SWITCHES FILLED WITH ENVIRONMENTALLY FRIENDLY GASES

Power Transformer Fault Diagnosis Based on Dissolved Gas Analysis Using a Fuzzy Neural Network Approach in a Real Data Base

Session Number: 3 High Voltage Power Transformer Dissolved Gas Analysis, Measurement and Interpretation Techniques

Analysis of Dissolved Gas in transformer oil by conventional Techniques and Artificial Intelligence approach-a Review.

ON-LINE MONITORING OF REGULATOR TRANSFORMER AT THE MARGEM DIREITA SS IN ITAIPU. M. E. G. ALVES* Treetech Sistemas Digitais Ltda.

TRANSFORMER RELIABILITY AND DISSOLVED-GAS ANALYSIS. Delta-X Research Inc, Victoria BC, and 2 IREQ, Varennes QC CANADA

C Dissolved Gas Analysis Of Load Tap Changers. Working Group

Experiment 18 Properties of Gases

NEULOG OXYGEN LOGGER SENSOR GUIDE

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

This test shall be carried out on all vehicles equipped with open type traction batteries.

Performance Overview calibration Laboratory EP Instruments Messtechnik und Kalibrierung GmbH

Gases&Technology. Measurement of Impurities in Helium Using the Dielectric Barrier Discharge Helium Ionization Detector. FEATURE.

Using Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems. J.C.M. VAN ROSSUM * Prysmian Group NL The Netherlands

Cryogenics is the science of ultra low temperatures. Low temperatures are achieved by the liquefaction of gases.

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

Authors: Mário Rui da Cunha Pereira, Hands on Science

COAL MINES TECHNICAL SERVICES, GAS DETECTION RELATED SERVICES FOR MINES RESCUE

GAS FILLING MACHINES PROCESS MONITORING PRESSURE BALANCE

INTERNATIONAL STANDARD

Advanced Test Equipment Rentals ATEC (2832) OMS 600

An Experimental Investigation on the Lightning Impulse Breakdown Characteristics of SF 6 -based Mixture Gases

CORONA DISCHARGE IN SULPHUR HEXAFLUORIDE-NITROGEN GAS MIXTURE

ASTM WK Standard Test Method for Dissolved Gases. Anne Jurek Applications Chemist

TECHNICAL PAPER PRESENTATION

Dissolved Oxygen and measurement possibilities. Berno Lüpkes, 15 th March 2017

What is photosynthesis? Photosynthesis II: Dissolved O2

Testing Distribution Switchgear for Partial Discharge

29th Monitoring Research Review: Ground-Based Nuclear Explosion Monitoring Technologies

CHEM 355 EXPERIMENT 7. Viscosity of gases: Estimation of molecular diameter

The Study of Bubbly Gas-Water Flow Using

Safety Analysis Methodology in Marine Salvage System Design

(2 pts) Draw the line of best fit through the data and estimate the concentration of Fe in your sample solution.

Ball Beating Lubrication in Refrigetation Compressors

TIGHTNESS. Glass sealing Thanks to our glass-sealing technology, ODU products can meet the most demanding tightness requirements.

An Investigation of Liquid Injection in Refrigeration Screw Compressors

Operating Instructions MANUAL. KIT DKU 4.0 and Accessories

Introductory Lab: Vacuum Methods

Power Unit 075. Maintain Substation Circuit Breakers

Faults diagnostics of high-voltage equipment based on the analysis of the dynamics of changing of the content of gases

Research of the Relationship between Partial Discharge and Gas Decomposition Products in SF 6 Insulated Equipment

Real-time Analysis of Industrial Gases with Online Near- Infrared Spectroscopy

SF 6 Product Guide. Gas Analysis Instruments and Accessories

DEVICES FOR FIELD DETERMINATION OF WATER VAPOR IN NATURAL GAS Betsy Murphy MNM Enterprises 801 N. Riverside Drive Fort Worth, Texas 76111

DESIGN AND PERFORMANCE OF THE NEW SARTORIUS 1 KG VACUUM MASS COMPARATOR AT PTB

Hot Work Program. University of Wisconsin-Platteville Reviewed 4/2016

Portable Gas Analyzers

Level MEASUREMENT 1/2016

Applied Technology and Best Practices in CEE. Conference

PositionMaster EDP300 Extended Diagnostics. Compact, well-proven, and flexible

About ABB Micafil Facts

Discussion and guidance on the definition and qualification of porous loads

Multiple Gas#5 GC configuration Jan 2016

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles

Neil Kane Managing Director EMT UK

The benefits of the extended diagnostics feature. Compact, well-proven, and flexible

Figure. Experimental set up of catalyst, reactants and product syringes.

Research Question How does the concentration of catalase affect the speed of the decomposition reaction of Hydrogen Peroxide into oxygen and water?

An Intelligent Fault Diagnosis Approach for Power Transformers Based on Support Vector Machines. Hao Xu

Transcription:

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS M. Jovalekic 1*, D. Vukovic 1 and S. Tenbohlen 1 1 Institute of Power Transmission and High Voltage Technology (IEH) University Stuttgart, Germany *Email: m.jovalekic@ieh.uni-stuttgart.de Abstract: Dissolved gas in oil analysis has been used for many years successfully for diagnosis and condition monitoring of mineral oil filled transformers. In future the diagnostic methods have to be transferred to natural esters. In this article we present the results from experiments, which represent electrical and thermal faults and the suitability of existing mineral oil interpretation methods is considered. The investigated fluid was Envirotemp FR3 TM. Where possible the amount and relation of the gases are compared to mineral oil gassing behaviour. The partial discharge experiments were carried out at three different intensity levels. After analysis of the oil samples with a gas-phase chromatograph, it becomes evident that FR3 fluid behaves similar to mineral oil. Hydrogen is the key gas, but the gas generation rate is considerably higher. Samples were also taken during a series of 90 lighting impulses (1,2/50µs). In this case the key gases' ratios are similar to the mineral oil ones (H 2, C 2 H 4, C 2 H 2 ) with a lower generation rate. The thermal ageing experiments lasted 8 weeks at 150 C. Like in mineral oil, the CO 2 and CO ratios are the predominant indicators. In this case the Duval diagnostic method fits to FR3 fluid. In the hotspot experiments the temperature was adjusted to 300, 500 and 700 C and kept constant. Again the diagnostic results with the Duval method delivered the best findings. One can conclude that the gas generation rate was higher for FR3 fluid in case of partial discharges and lower for arcing experiments. It cannot be said with certainty which dielectric fluid has higher gas generation under electrical stress. For thermal faults many common diagnostic methods failed, but the Duval method worked quite reasonably. 1. INTRODUCTION In the moment there is an observable interest for the filling of power transformers with natural esters due to the ecological and thermal advantages (higher flash point) over mineral oil, which could outweigh the disadvantages. With the adoption of the new insulating liquid many aspects of the thermal and electrical design of transformers have to be considered. Additionally the diagnostic and condition monitoring methods have also to be adjusted. This is the motivation of the work presented in this paper. Thermal and electrical stresses and faults are generated in the laboratory in a controlled environment. The gassing behaviour of the natural ester FR3 is then observed by means of gas chromatograph measurements. The amount of gases and their quotients are compared to the ones of mineral oil. Furthermore the application of conventional DGA interpretation methods is evaluated. Figure 1: Glove box with argon atmosphere 2. EXPERIMENTS The oil samples from the experiments are analysed with a gas chromatograph involving headspace technique. It means that the gas concentrations above the analysed liquid are measured. With these values it is possible to calculate back to the original dissolved gas amounts in the insulating fluid. Because of this it is necessary to sample the vials carefully in a glove box with argon atmosphere (Fig. 1) in order to avoid contamination with the gases from the atmosphere. The used gas chromatograph (Fig. 2) detects H 2, CO, CO 2, CH 4, C 2 H X and the C 3 H X. Figure 2: Gas chromatograph with automatic sampler

2.1. Electrical stress with partial discharges The aim of these experiments was to generate partial discharges (PD) of different intensities and durations and to analyse the generated gases. The test cell has a volume of 1.5 litres. To generate the partial discharges a point plate configuration with a gap distance of 40 mm was chosen. The point is an Ogura needle with 3µm tip radius. A double pressboard barrier is used to generate stable and continuous partial discharges. The distance between barriers was 5 mm and the distance between nearest barrier and plate electrode was 10 mm. The cell was made of Perspex in order to obtain a partial discharge free test setup (Fig. 3). This has been proven by measurements with PD-free electrodes. The measurement system was a conventional one with a coupling capacitance. The intensity of the PDs is quantified in apparent charge in coulombs. Figure 4: Gases generated under 700-1000pC PDs (FR3) Figure 3: Partial discharge test cell with point plate configuration and barriers Figure 5: Gases generated under 1000pC PDs in FR3 Three different PD intensities were generated: a low intensity with 700-100 pc, a medium with 1000 pc and a high one with 2000 pc. The inception voltage was between 34 and 58 kv. The experiments lasted three hours. Every hour an pause is made and an oil-sample of 50 ml was taken with a syringe. Results of partial discharge experiments The observed key gases for FR3 are H2 and CO. Acetylene (C2H2) and methane are typical secondary gases (Fig. 4-6). This behaviour is different to mineral oil, which has a considerable lower gas generation and CO is missing (Fig. 7). Figure 6: Gases generated under 2000pC PDs in FR3

Results of hotspot experiments Key gases in this experiment are CO, CO 2 and propylene - C 3 H 6 (Fig. 11-13). The experiments at the highest temperature had to be stopped, because the gas generation ratio was too high resulting in unacceptable big gas bubbles in the vessel. Detectable and linearly accumulated were also hydrogen, ethane and ethylene. Figure 7: Gases generated under 2000pC PDs in mineral oil 2.2. Electrical stress with arcing In this experimental setup a similar test cell was used, but a point-point electrode configuration was used. The distance between the electrodes was 10 mm. The breakdowns were generated with a 10 stage Marx lightning impulse generator. Previously an experiment with AC breakdown failed, because the breakdowns weren t periodic and appraisable and as consequence it wasn t possible to quantify the released energy. The peak voltage value of the standard lighting impulse (1.2/50µs) was 140 kv. The energy per breakdown was 580 J. Series of 10, 20, 30, 50, 70 and 90 breakdowns were conducted, where again after each series an oil sample was taken for analysis. Results of arcing experiments As for mineral oil the key gas for arcing in FR3 is acetylene. The gas generation ratio is similar for both insulating liquids. Although in mineral oil more H 2 is produced (Figures 9 and 10). 2.3. Thermal stress with hotspot The goal of this experiment is to emulate a hotspot inside the transformer. A glass cylinder with a volume of 15 litres is used. Inside the cylinder is a resistherm wire, which depending on the flowing current settles at the desired temperature. The 600 mm long wire is connected to the cylinder covers and lies in the middle of the oil filled cylinder (Fig. 8). It is heated to three different temperatures: 300 C, 500 C and 700 C. The experiments lasted, depending on the temperature, several hours to several days. 2.4. Thermal ageing Metal sealed vessels, having a total volume of 5 litres were filled with both mineral oil and FR3. Besides fluids they contained same proportional mass ratio of materials commonly existing in real power transformers (cooper, aluminium, iron, zinc and cellulose). For each fluid two vessels were used in order to obtain more reliable results. These vessels were tight sealed and closed in an oven under temperature of 150 C for 63 days. In certain intervals (about one week) the oven was opened and fluid samples were taken for gas chromatograph analysis. Results of ageing experiment Same as for mineral oil identified key gas in FR3 was CO 2. For FR3, besides CO as a secondary gas in mineral oil, a certain amount of C 3 H 6 was identified. Gas generation for these gases is higher in FR3 than in mineral oil (Fig. 14 and 15). Non-constant increase of generated gases can be attributed to problems occurring during the sampling. Namely, while taking the fluid sample with a syringe for short time the test vessel was exposed to the atmosphere in order to depressurize it. This could allow for some of atmosphere gases to disturb the gas concentration in the test vessel. 3. CONCLUSION The obtained dissolved gas-in-oil concentrations and ratios can be applied to various existing DGA interpretation methods. These are e.g. the Duval triangle method, Doernenburg Ratios, GE method, IEC60599, Rogers Ratios, Müller-Schliesing-Soldner and a new fuzzy based method developed at the IEH. Generally they vary in the choice and number of considered key gases and their ratios. Duval, GE and IEH method gave the expected results. This doesn t mean that the other methods were wrong. Often they had more criteria and were more precise, which resulted in fault codes that in the interpretation scheme are not defined. At this point one can state, that the relevant gases for the fault diagnosis are generated and detectable. In case of partial discharges the gassing of FR3 is higher and for arcing lower than for mineral oil. The gas production in FR3 for thermal faults is high enough to be used for diagnostic methods too. Figure 8: Hotspot experiment setup For future experiments it is necessary to determine more precise solubility coefficients (k-factors) for the

calculation of the dissolved gas concentration in ester from the measured gas concentration in the headspace volume. Also there is considerable space for improving the test setup involving better sealing In order to increase the confidence in the measured absolute values. Finally one can conclude that the existing diagnostic methods will even give better results by adjusting the key gas ratios for FR3. Further improvement is also possible with not so strict, but fuzzy ratios in order to avoid situation, where the fault pattern is completely undefined. 4. REFERENCES [1] Zhongdong Wang, Imad U. Khan, I. Cotton, and S. Northcote. Dissolved gas analysis of alternative fluids for power transformers. IEEE Electrical Insulation Magazine, 23(5):5-14, Sept.-Oct. 2007. [2] Duval M., The Duval Triangle for Load Tap Changers, Non-Mineral Oils and Low Temperature Faults in Transformers, IEEE Electrical Insulation Magazine, Vol. 24 Issue 6 pp. 22-29, Nov.-Dec. 2008 [3] http://diagnostic.ieh.uni-stuttgart.de The Institute of Power Transmission and High Voltage Technology (IEH) provides a website, where all the introduced diagnostic methods can be applied to given gas concentrations [3]. Figure 9: gas generation for arcing in FR3 Figure 10: gas generation for arcing in mineral oil

Figure 11: gassing of FR3 at a hotspot temperature of 300 C. Figure 12: gassing of FR3 at a hotspot temperature of 500 C. Figure 13: gassing of FR3 at a hotspot temperature of 700 C.

Figure 14: Gas generation for FR3 under aging Figure 15: Gas generation for mineral oil under aging