Field Instruction. Stringing new bare conductors above or below live bare overhead conductors

Similar documents
Field Instruction. The purpose of this instruction is to inform all Horizon Power workers of the safety requirements when working from a EWP.

Field Instruction. Protect Horizon Power employees and contractors from a potential hazard.

Field Instruction. This instruction outlines the minimum requirements for all Horizon Power workers who undertake Vegetation Management Work.

Methods of installation of ADSS fiber optic cables

DM# High Voltage Live Work Procedures Distribution Insulated Stick

Original Date of Issue: 04/09

SAFETY QUALITY TECHNOLOGY. Guidance on Safe Isolation Procedures

I. Purpose... 1 II. Introduction... 2 III. General and Safety Precautions... 2 IV. Reference Documents... 3 V. Installation Overview...

Work Standard CABLE PULLING OPERATIONS

Chapter 8 Sagging, Terminations, and Suspensions Table of Contents

HOW TO PREPARE FOR THE LEVEL A CRANESAFE CERTIFICATION ASSESSMENT

Chapter 5 Site Considerations and Set-ups Table of Contents

CS10 # Network Safety Performance Objectives (2016)

Warning CABLE REPLACEMENT INSTRUCTIONS. Questions? - Call Telpro Inc. Customer Service at or

Safe Work Method Statement LRB TREE SERVICES 6 Behland St, Kearneys Spring QLD, 4350 ABN

PSSI 6 Demarcation of Work Areas in Substations

PSSI 12 Low Voltage Apparatus

List all key terms and acronyms used in the procedure, and their definitions.

GUIDELINES FOR USE GUARD

Change Crossarm Insulator with Hotsticks

ELECTRIC OPERATING PROCEDURES Date: 11/01/06

Vacuum Excavation in the vicinity of the Wellington Electricity Network

September 27, DOE-RL-92-36, Hanford Site Hoisting and Rigging Manual. Wire Rope. Page 1 CONTENTS

TRADE AREA: ELECTRICAL INDUSTRY

Once the job has been planned and the site has been inspected according to WHS and site requirements it is important to follow work procedure and

Construction & Building Industry Safety Guideline. Overhead Power Line Earthing

F OVERHEAD CONSTRUCTION & STRINGING EQUIPMENT WIRE GRIPS WIRE GRIPS SELECTION CHART PATENTED HI-TOOL TRIGGER GRIP

This Procedure details the procedures to be followed in order to achieve Safety from the System when:

Intermediate Angle, 0-25, Drilling detail. Angle 26-50, Baulk Plates, Pole Details. Termination Poles, ABC Details

WI Rev C Page 1 of 17

You may order this publication from WCB Publications and Videos, Please quote ordering number BK60.

Buckingham Mfg. Co., Inc. OX BLOCK TM Instructions and Warnings

Safe Work Method Statement Transmission Field Protection Services

Buckingham Mfg. Co., Inc. OX BLOCK TM Instructions and Warnings

Winchline n a box WINCH LINE SELECTION GUIDE. Wire Rope Winchlines are superior to most other winchlines found in the market place due to the

INSTALLATION PROCEDURE FOR OPGW FIBER OPTIC CABLES

CORPORATE SAFETY MANUAL

HV RUBBER GLOVE WORKING

Installation Guideline for Placing Fiber Optic Cable into an Underground Duct

PRO Lifting Operations

Premium PowerPoint Presentation. Rigging Review

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,

Care and inspection of wire rope

CITB Construction site safety update

Chapter 2 Rigging. Cutting Wire Rope. Anchoring Wire Rope to Drum. Winding Wire Rope Onto Drum

Crane & Rigging Brain Teasers

C&G 2395 Exam Paper April Section A - All questions carry equal marks. Answer all three questions. Show all calculations.

Electrical Safety Work Practices

Lift-All Wire Rope & Slings

FATAL AND SEVERE RISK PROGRAM

TLILIC2001 Licence to Operate a Forklift Truck

"RIGGING SAFETY IN CONSTRUCTION ENVIRONMENTS"

Cable Grip Fitting Procedure General

SINGLE BRAID INSPECTION

Managing Mobile Crane Hazards. Paul Satti Construction Safety Council. Hazards of Working Around Cranes. Key Concepts:

WIRE ROPE PULLING MACHINE

Field Instruction. This instruction applies to Horizon Power employees and contractors involved in Horizon Power s underground projects.

GENERAL GUIDELINES FOR PROPER RIGGING PRACTICES AND INSPECTION & REMOVAL CRITERIA FOR SLINGS PER OSHA

Low Voltage Electricity System Safety Rules & Associated Safety Guidance

2.2. Anchorage Point A secure point of attachment for Lifelines, lanyards or deceleration devices.

FALL PROTECTION GUIDELINE

Serial Number: Lot Number: Purchase Date: General Factors Accepted / Rejected Supportive Details or Comments. Accepted Rejected.

THOR 10 HAMMER CAGE INSTRUCTIONS

C&G 2395 Exam Paper June Section A-All questions carry equal marks. Answer all three questions. Show all calculations.

Field Instruction. This instruction applies to Horizon Power employees and contractors involved in Horizon Power s underground projects.

SAFE WORK PROCEDURE. Location of Equipment Written By: Approved By: Date Created Last Revision

WORK METHOD STATEMENT ELECTRICAL

VL SHEAVES/CABLE UPGRADE KIT INSTRUCTIONS

GUIDELINES FOR USE -GUARD

PHOENIX, AZ USA

Moor, Tend Mooring And Unmoor Ship - Supervisor Level -

Safe Work Practices (SWP) SWP (6) FALL PROTECTION PROGRAM

Proof load is the load applied in performance of a proof test. Proof test is a nondestructive tension test performed by the sling manufacturer or an

1.0 Scope and Application

cricket Premier Portable Cage Winch System Heavy Duty Parks Parks Cages Wooden Bays Stumps Netting Sundries cricket

Flexfence Swaging Unit. Product Manual. Release 02/16.

1 SafeClaw Anchorage Connectors

Installation and Operating Instructions for Automotive Winch Synthetic Rope

OSHA s new walking working surfaces standards

Hoisting Equipment Cable puller & Accessories

GUIDELINES FOR HEALTH AND SAFETY

Minimum Safety Requirements for Contractors Working on Railway Property

References: EM Section 15 OSHA UFGS

3/4 SafeClaw Anchorage Connectors

TOWER INSTALLATION MANUAL For A.R.E. Guyed Pipe Towers Short Towers 43, 64 and 85 feet tall

OPERATOR`S MANUAL ELECTRIC WINCH WARNING

GOLDEN SAFETY RULES AFT DR

Operation of Embrey Excavator Shears Safe Work Procedure PTES_HSE_SWP_039. Name Date Signature. Author Jarred Hearle 27/11/2015

For ELECTRIC ANCHOR WINCH Models: T Pontoon 35 T sw Salt Water Series Coastal 35

Figure 1 - Parts Identification. Copyright 2002, DB Industries, Inc.

Scissor Lift Safety Policy Training Course (GS600) Material

7 Hazard assessment 8 Worker participation 9 Hazard elimination and control

Pre-Climbing Inspections

F OVERHEAD CONSTRUCTION & STRINGING EQUIPMENT WIRE GRIPS HI-TOOL NGK WIRE GRIPS (MADE IN JAPAN)

OMG Southeast & Southwest RIGGING SAFETY PROGRAM (29 CFR Part , , , , , & ANSI B30.5, ANSI B30.

This training does not attempt to cover all safety regulations or precautions.

Rigging Safety. 1 Copyright 2014 by PEC Safety Management, Inc. PPT-SM-RIGGING 2014

Electrical safety code of practice Working near overhead and underground electric lines

PARALLEL CORE INSPECTION

USER S INSTRUCTION MANUAL FOR THE INSTALLATION, OPERATION & MAINTENANCE OF THE GUARDIAN TEMPORARY HORIZONTAL LIFELINE SYSTEM

Transcription:

5.10 Stringing, Tensioning and Sagging Conductors/Cables Purpose The purpose of this instruction is for all Horizon Power workers who undertake the stringing and tensioning of bare overhead conductors under an Electrical Access Permit (EAP) for distribution line work. Scope This instruction applies to the following situations: Working on existing overhead bare conductors Stringing new bare conductors above or below live bare overhead conductors Tensioning of bare conductors above or below live bare overhead conductors Additional requirements when working with existing 3/2.75 and 7/1.6 steel and 7/16 (7/.064) or smaller copper conductors Installing line crossover gantries near live overhead lines This instruction does not apply too: Low Voltage (LV) live work methods High Voltage(HV) live work procedures for glove and barrier (G&B) Distribution stick (DIS) Safety Before commencement of work, a risk assessment must be carried out using the Risk Analysis Procedure (OSH-3.6-1-02), to identify and document the hazards and risks associated with the task and ensure appropriate control measures are implemented. It is important that, appropriate control measures must be identified, documented and implemented in order to control Hazards to Low as Reasonable Practicable (ALARP). It is important that, appropriate control measures must be identified, documented and implemented to lessen or control the identified hazards. The stringing of bare (open-aerial) conductors, above or below, to bare live HV or LV overhead conductors is not permitted. If running conductors parallel to live open-aerial conductor s consideration must be given to maintaining clearance (SAD) from the swing conductors being pulled. In this situation, the live conductors must be isolated, proved deenergised, earthed or short-circuited and an EAP issued Always treat all conductors as energised until proven otherwise, and an EAP is issued Always ensure there is a portable earth (HV) or shorting kit (LV) between the line workers and any potential source of supply, including induced voltages Consider the risk from induced voltages. See Field Instruction 8.3 - Induced voltages Ensure conductor ground clearances are maintained. See Field Instruction 5.11 - Conductor clearances CS10 # 2226091 FI 5.10 Stringing, Tensioning and Sagging Conductors/Cables Page 1 of 7

Ensure minimum approach distances (SADs) are maintained from energised conductors and apparatus. See Field Instruction 2.17 - Safe Approach Distances (SADs) SADs to live HV can never be reduced even if HV insulated mats and covers are applied as a precautionary measure Conductors must be controlled at all times and not dragged on the ground, maintain tension during pulling process All LV insulated covers and mats must comply with AS 4202-1994 - Insulating covers for electrical purposes and be visually inspected prior to use Ensure appropriate PPE is worn according to F.I 2.1 Glove protection CAUTION Pre-formed dead-end wraps must not be used to tension or pull through conductors, use the correct pulling equipment such as pulling sock and swivel or tension come-along Instruction Inspection of existing bare overhead conductors and poles Prior to commencement of any work on existing bare overhead conductors, conduct an inspection of the conductor, pole and its attachments. The conductors and pole either side of the structure to be worked on must also be inspected. If stringing more than one bay, all conductors and poles to be worked on must be inspected. For more on pole inspection, see Field Instruction 5.2 - Poles Inspection and Support Prior to Commencement of Work The following must be considered when inspecting conductors and attachments for damage and/or signs of weakness: Corrosion and deterioration Condition type terminations Check condition- type of joints in mid-span Annealing (changing the physical characteristic of the metal) Signs of conductor clash and burning Damage by lightning Damaged or broken strands Cracked or broken insulators Metal fatigue Conductor creep or slippage Vibration damage at tie wires and armour rods Cracked or broken cross-arms CS10 # 2226091 FI 5.10 Stringing, Tensioning and Sagging Conductors/Cables Page 2 of 7

CAUTION All damaged conductors must be repaired using full tension compression joint applicable to conductor size and type, dead-end pre-forms and amour rods are not acceptable repair methods Stringing equipment Stringing equipment may consist of but not limited to the following items: Tension equipment (Dynamometer, Site board, Beat method tools, Abney level, Theodolite) Cable drums and Cable drum stands Cable trailers Ropes Rollers Sheaves Stockings Stringing documentation and support items (e.g beat charts, thermometer, etc) Swivels, and Winches. All stringing equipment should be in good working order e.g. free-running pulleys, free from cracks and chips and metal fatigue, safety catches working correctly, brakes functioning, calibrated tensioning equipment. A functioning brake on conductor/cable payout equipment must be installed to prevent conductor/cable runaway and to also control the slack (tension) of the conductor/cable. The weight carry-capacity (WLL) of all equipment designed to carry load should be rated for the desired job. This should include the equipment s anchoring device (sling) and the structure on which the equipment is to be anchored too. When loading cable drums onto cable drum stands or specifically design self-loading winch drum trailers correct loading methods shall be adhered to, with consideration given to the weight of the full cable drum (gross weight), direction of feed-in or feed-out of conductor or cable, correct securing method of both the cable stand/trailer to vehicle and cable drum to stand/trailer. Loads should never be lifted over personnel and risk mitigation should include exclusion zones. Stringing methods The stringing of conductor or cable can be completed by the following methods: Layout, Conductor/Cable Pull through, or Pilot rope Pull through. These methods are documented in trade qualification training material associated to UETTDRIS54 Install and maintain poles, structures and overhead conductors and cables. When using one of these stringing methods the crew must adhere to the following requirements: When running out conductor s (Layout method) it is necessary to protect the conductor against abrasions and picking up contaminants. You must not drag conductors along the CS10 # 2226091 FI 5.10 Stringing, Tensioning and Sagging Conductors/Cables Page 3 of 7

ground (Layout method), or over hard surfaces such as cross-arm or other pole hardware (Pull through method). Damage to conductor/cable via external effects e.g. vehicles, damaging surfaces, cable drum surfaces, excessive tension, kinking conductor/cable. When running conductors/cables it is important to keep the sagging conductor/cable free from vehicle and pedestrian traffic. This can be mitigated through traffic and pedestrian management or a gantry structure. Clear and concise communication between all relevant parties string conductors and cables e.g. conductor/cable party-end, Winching party-end and Personnel walking the line (Cable/conductor stocking joint). The distribution worker walking the line ensure the joint does not get snagged up on rollers, trees or other obstructions. The following control measures can be used to control the risk of contact with energised conductors and / or apparatus: Isolate all or part of the bare live overhead mains and obtain an EAP Apply insulated covers and mats (Secured to prevent covers, sleeves and or tiger tails moving and exposing the live apparatus) to the adjacent live LV conductors and / or apparatus Maintain SADs Use safety observers Remove live line taps / clamps or drop out fuses Remove solid taps to increase SADs LV tee-offs and conductor crossings above and below the length of the new conductor pull must also be isolated and the work carried out under an EAP, unless controls can be implemented to mitigate any risk. Controls may include: Application of insulated covers and mats (Secured to prevent covers, sleeves and or tiger tails moving and exposing the live apparatus) to the live conductors and apparatus Use of temporary LV cross-arms to increase clearances Use of captive rollers Use of safety observers Use of radios for communication and monitoring Installation of gantries Installation of scaffold and netting Tensioning of the conductors is not permitted from any structure containing live conductors or apparatus; however back hanging on a live structure is permitted. A pulling sock and swivel mechanism must be used between the winch rope and the new conductor. Back to back pulling socks with a swivel mechanism must be used when using existing conductor to pull through conductor. When pulling through the new conductor using the existing conductors to a split drum cable winch extra care will need to be taken due to the risk of: Existing conductor joints snagging in the rollers during the pull Existing conductor joints failing during the pull Existing conductors failing due to age and deterioration CS10 # 2226091 FI 5.10 Stringing, Tensioning and Sagging Conductors/Cables Page 4 of 7

Bird-caging at the split drum due to loss of tension and/or lack of flexibility of the old conductors Tensioning bare conductors Tensioning bare conductors above live LV conductors is not permitted unless using approved glove and barrier (G&B) High Voltage Live Work procedures. Conductors must be tensioned using the relevant sag charts, see Stringing Tables for Aluminium and Steel Conductors for Distribution Lines: http://dm.horizonpower.com.au/otcs/llisapi.dll/properties/255045 In conjunction with a thermometer, dynamometer or conductor beat charts and a distance wheel or range-finder The final tensioning of the conductors must be carried out using a rated mechanical tensioning device (e.g. strap-hoist, canker, pull-lift etc.) along with the correct come-along clamp Back-hanging of bare conductors on live structures Back hanging of any conductor above live HV is not permitted. When back hanging below live HV, ensure the following: SADs are maintained SADs can be maintained when the conductors are pulled up to tension conductors are controlled at all times HV there must be a portable earth between the line worker and all possible points of supply (e.g. bottom of the HV fuse holder) LV there must be an LV shorting kit between the line worker and all possible points of supply Conductors to be back-hung must have any attachments (e.g. jumpers or live line taps/clamps) properly secured (bent back and secured to the main conductor using cable ties or tie wire) so that there is absolutely no risk of them becoming free during the backhanging process Back-hanging above bare live LV conductors is not permitted unless the bare live LV conductors and apparatus can be fully insulated and/or covered Collecting Samples of Aged Conductors Collecting samples of aged conductors is an important and necessary work task as it helps to estimate the years of remaining life left in the conductor before it fails due to corrosion or age. Samples should be collected when the opportunity arises or when the conductor is suspected of being of substandard quality. Examples of opportunities when it may be possible to collect samples: During a repair of a broken conductor Capacity upgrades of existing overhead conductors Demolition of existing overhead feeder Fault conditions where new conductor is required CS10 # 2226091 FI 5.10 Stringing, Tensioning and Sagging Conductors/Cables Page 5 of 7

Collection of samples for analyses should be coordinated and recorded at the local depot. Each sample collected should not be less than 1 metre in length. Ensure the following information is attached to each sample: Feeder name / number Date of sample collection Pole pic ID numbers (sample taken between) Conductor sample size (e.g. AAAC 19/3.25) Year conductor installed (if known) Number of prior faults (if known) Environmental description ( coastal, agricultural, industrial high pollution area) Reason for removal (e.g. fault, conductor upgrade, demolition) Additional requirements for 3/2.75, 7/1.6 steel and 7/16 (7/.064) or smaller copper conductors Due to the corrosive nature and reduced tensile strength of these conductors, extra care must be taken when tensioning existing conductors. The following must be done prior to commencing any work that will affect the tension and/or mechanical loading of these conductors: A normal inspection, as previously described in the Inspection of existing bare overhead conductors and poles section An inspection of the conductor and fittings on the pole to be worked on and for two spans either side From the inspection, determine the degree of deterioration of the conductor and fittings and establish whether the conductor is safe to work on If the inspection determines that the conductor could break during the work: Do not carry out any work if there are energised conductors or apparatus on the same poles Notify Network Operations (HPCC) Arrange for an outage of all energised conductors or apparatus prior to making the repairs Tensioning bare 3/2.75, 7/1.6 steel and 7/16 (7/.064) or smaller copper conductors There is an increased risk of conductor slippage within the come-along clamp when tensioning these smaller size conductors. A come-along clamp with a locking grip mechanism can be used to help reduce this risk, as shown in Figure 1, below. CS10 # 2226091 FI 5.10 Stringing, Tensioning and Sagging Conductors/Cables Page 6 of 7

Figure 1: Come-along clamp with locking grip mechanism and safety latch References Occupational Safety & Heath Act 1984 Occupational Safety & Health Regulations 1996 SHMS OSH-3.6-1-02 Job Risk Analysis (JRA) Procedure SHMS OSH-3.6-1-26 Personal Protective Equipment Electrical Safety Standards Field Instruction 2.6 Worksite Clothing / Personal Protective Equipment Requirements Field Instruction 2.17 Safe Approach Distances Field Instruction 2.23 Job Hazard and Risk Management (JRA) Field Instruction 5.2 Poles Inspection and Support Prior to Commencement of Work Field Instruction 5.11 Conductor Clearances Field Instruction 8.1 Portable Earthing Requirements Field Instruction 8.3 Induced Voltages High Voltage Live Work Manual AS 4202-1994 Insulating covers for electrical purposes Stringing Tables for Aluminium and Steel Conductors for Distribution Lines http://dm.horizonpower.com.au/otcs/llisapi.dll/properties/255045 Low Voltage Aerial Bundled Cable (ABC) Manual http://dm.horizonpower.com.au/otcs/llisapi.dll/properties/2369134 CS10 # 2226091 FI 5.10 Stringing, Tensioning and Sagging Conductors/Cables Page 7 of 7