THE IMPORTANCE OF SUCTION LINES

Similar documents
Pressure = 15.2 bar TXV. 10K super heat. Pressure = 1.82 bar. Line temp = 8 C. Line temp = 9 C

Single- or Two-Stage Compression

THE IMPACT ON ENERGY CONSUMPTION CAUSED BY PRESSURE DROP IN A COMPRESSED AIR SYSTEM

Using P-T Analysis As A Service Tool

Ball Beating Lubrication in Refrigetation Compressors

Low GWP R-404A Alternatives for Commercial Refrigeration. Barbara H. Minor Dr. Frank Rinne DuPont Fluorochemicals

Troubleshooting Guide. Pg. 1

Technology issues regarding Blends of Refrigerants Buffalo Research Laboratory

AE R8 December 2004 Reformatted November Copelametic Two-Stage Compressors Application and Service Instructions

POWER FLUSH KIT INSTRUCTIONS

V46 Series 2-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

CO 2 radial piston compressor (transcritical)

Research of Variable Volume and Gas Injection DC Inverter Air Conditioning Compressor

Two-Stage Linear Compressor with Economizer Cycle Where Piston(s) Stroke(s) are Varied to Optimize Energy Efficiency

Industry Guidelines POLYETHYLENE (PE) PIPES AND FITTINGS FOR COMPRESSED AIR ISSUE 6.8

Influence of Volumetric Displacement and Aspect Ratio on the Performance Metrics of the Rotating Spool Compressor

Seminar 65 Compression Challenges for Low GWP Refrigerants

An Investigation of Liquid Injection in Refrigeration Screw Compressors

Capacity and pressure similar to R-507. Flooded systems. Low temperature (-46.7 C). R22 replacement as long as the condenser has the right size.

Refrigeration Scroll For Parallel Applications

Gas Vapor Injection on Refrigerant Cycle Using Piston Technology

Test on a Twin-Screw Compressor

Updated Performance and Operating Characteristics of a Novel Rotating Spool Compressor

CO 2. (R744) Service Station Presentation. Contents. Goals Basic functions Specification Recovery R477 Vacuum Charge Safety Other features Prototype

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1

V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

TECHNICAL BULLETIN DESIGNING A FUNCTIONAL COMPRESSED AIR SYSTEM

OIL AND GAS INDUSTRY

Development of a High Pressure, Oil Free, Rolling Piston Compressor

New Energy-saving Air Compressors

Application of Computational Fluid Dynamics to Compressor Efficiency Improvement

Development of Large Capacity CO2 Scroll Compressor

LGWP & HC Refrigerants Solubility Tests Performed in Running Scroll Compressor

Pipeline Flooding, Dewatering and Venting Dr Aidan O'Donoghue, Pipeline Research Limited, Glasgow, Scotland

AIR HAMMERS MODEL NO: CAT138/CAT139 OPERATING & MAINTENANCE INSTRUCTIONS PART NO: / GC064

A Chiller Control Algorithm for Multiple Variablespeed Centrifugal Compressors

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

COMPRESSED AIR DISTRIBUTION SYSTEMS

Inprocess Operator Training Programme

SPIROVENT VACUUM DEGASSERS

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE

Refrigeration and Air Conditioning Technical leaflet

TRANSCRITICAL CO 2 IN AUSTRALIAN SUPERMARKETS. Mike Baker Baker Refrigeration M. IE Aust, C P ENG, M. AIRAH

Energy savings in commercial refrigeration equipment: High Pressure control implementation

Scroll Compressor Performance With Oil Injection/Separation

Applied Fluid Mechanics

Level 3 Cambridge Technical in Engineering 05822/05823/05824/05825/05873 Unit 3: Principles of mechanical engineering

4 ANGLE GRINDER MODEL NO: CAT 52 PART

Displacement 12, , Maximum flow rate (at 1450 rpm) bar.

Valve Losses in Reciprocating Compressors

E 328 E 498 Tank top mounting Connection up to G1½ / -24 SAE and SAE 2 Nominal flow rate up to 600 l/min / gpm

COMMERCIAL REFRIGERATION SYSTEMS WITH CO 2 AS REFRIGERANT

CROT-6 CROT-10 CRO-4. for Compressor Overload Protection

Installation, commissioning and servicing instructions

Development of Scroll Compressors for R410A

SELECTION CRITERIA FOR SAFETY VALVE

Moyno ERT Power Sections. Operational Guidelines

Case 12 Multistage Centrifugal Refrigeration System Halocarbon Refrigerant

Crusher Bearings: Knowing the Basics Leads to Better Care

Performance Measurement of Revolving Vane Compressor

Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide

Best Practices Pneumatics Machine & Design. Written by Richard F. Bullers, CFPPS as published in Fluid Power Journal, July/August 2016

Performance Monitoring Examples Monitor, Analyze, Optimize

System Soft-optimization Tests of Refrigerant R-32 in a 6-ton Rooftop Packaged Air-Conditioner

R-410A 50% R-32 50% R-125.

Scroll Compressor Operating Envelope Considerations

Nitrogen Supply System

Optimizing Compressed Air Storage for Energy Efficiency

E 158 E 198 E 248. Tank top mounting Connection up to G11 / 4 Nominal flow rate up to 250 l/min e d

E 084 Tank top mounting Connection up to G1 / -16 SAE Nominal flow rate up to 80 l/min / 21.1 gpm

SOLAR AUTOMATIC AIR VENTS AND DEAERATORS FOR SOLAR INSTALLATIONS NEW: AUTOCLOSE DOMESTIC COMMERCIAL SPIRO EXCEPTIONAL GUARANTEE

Soft-optimization test of R-410A alternative refrigerant R-32 in a split condensing unit - Phase II

Sizing Pulsation Dampeners Is Critical to Effectiveness

Versions. Benefits. Balancing DN15-32 DN40 DN50 DN15, DN20, DN25, DN32, DN40, DN50. Dimensions

E 328 E 498 Tank top mounting Connection up to G1½ and SAE 2 Nominal flow rate up to 600 l/min

Capacity Modulation of Linear Compressor for Household Refrigerator

SERIES 30. Spring Operated Tank Blanketing Valve PROTECTOSEAL.

FloCon Commissioning Modules DESIGN GUIDE - JUNE Variable Flow Systems & Solutions brought to you by Hurlstones

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles

Multifunctional Screw Compressor Rotors

Modeling and Testing of an Automobile AC Scroll Compressor, Part II: Model Validation

The Compact, Portable, Efficient and Economical Solution to boost Shop Compressed Air Pressure by 2 or 3 times

ATD LB PRESSURE BLASTER INSTRUCTION MANUAL

INSTALLATION INSTRUCTIONS FOR SSI WIDEBAND DIFFUSER

PLEASE READ CAREFULLY BEFORE INSTALLING OR USING MEGA POOL SAVER MPS 1100

Official Journal of the European Union L 92/3

1 DRIVE INDUSTRIAL IMPACT WRENCH

Tradition & Technology

OPERATING INSTRUCTIONS

CHECK VALVES APPLICATIONS

MITIGATING PIPE AND RISER HYDRAULIC PIPELINE ISSUES WITH THE I-RISER PLUS

VB-7213 Series. Application. Features. Applicable Literature. 1/2" to 2" Screwed NPT Stem Up Open, Two-Way Valves General Instructions

29 Pressure, Temperature relationship of a gas

Customer Responsibilities. Important Customer Information. Cary 4000/5000/6000i UV-Vis spectrophotometer Site Preparation Checklist

Impact Fatigue on Suction Valve Reed: New Experimental Approach

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES

Characterizers for control loops

Finding leaks in Main Cryogenic Heat Exchangers without shutdown

VB-7263 Series. Application. Features. Applicable Literature

Transcription:

THE IMPORTANCE OF SUCTION LINES Analysis and connection to compressors Unicla Cat. No. B1801

Copyright 2018 All rights reserved No part of this document shall be reproduced in whole or in part without the permission of Unicla International Limited. This includes reproduction or copies in any form or by any means including photocopying, printing or electronic media. IMPORTANT DISCLAIMER This is a guideline document containing professional information using representative graphs, charts and tables. Manufacturers specifications must be consulted for specific guidelines and performance data. Unicla published data, specific to all models, is available in promotional literature and from Unicla International Limited on request or through your Unicla supplier. Unicla International Ltd expressly disclaims all and any liability and responsibility to any person or business as a result of any actions taken on the basis of information in this publication.

Table of Contents Introduction...1 Suction line analysis...1 Suction line pressure drop...2 Hose selection...3 Hose fitting selection...5 A fault in the line...6 Improper line routing...7 Oil flow...8

Introduction The correct hose and pipe size connecting the main components in any mobile or transport air-conditioning system is important, however it is in the suction line where extreme care should be taken in the design and size, to ensure adequate flow of refrigerant is present in the system at all times. and temperature conditions in the suction line can be used as excellent diagnosis tools for system performance. By analysing the suction line properly, correct refrigerant levels, systems faults and capacity can be determined quite easily. Low refrigerant level is the most common fault causing adverse conditions in the line and system, including incorrect sizing and design of the line it self. This booklet will cover the main system features adversely affected by poor suction line performance. Suction line analysis A suction line analysis is completed by taking both pressure and temperature measurements between the two points A and B as shown in diagram 1. In this normal healthy suction line the pressure is the same at both points (1.82 bar or -1 C), and the temperature is 8 C at point A and 9 C at point B. This means only 1 C additional temperature (or super heat) has been picked up in the line during operation, which is very typical and normal for most systems. The super heat at any particular point is calculated by taking the actual line temperature and deducting the saturation temperature of the refrigerant (Refer to R134a and Temperature Chart) at the same point. = 15.2 bar = 78 C TXV C 10K super heat Discharge UX330 A B = 1.82 bar = 8 C = 1.82 bar = 9 C erature increases slightly with no pressure drop 8 C 9 C hose internal closeup Diagram 1. System operating normally with Unicla UX330 operating at 2000 rpm, High side15.2 bar. Low side 1.82 bar. Superheat 10K. Sub-cooling 5K. capacity is 12.8 kw. 1.

Measuring point A B C Position outlet suction discharge drop 1.82 bar 1.82 bar 15.2 bar *From R134a pressure and temperature chart. Degrees Kelvin or K is the primary unit of temperature measurement in the physical sciences, and is often used in conjunction with degrees Celsius and whenever reference is made to super heat in a refrigeration system. Both K and C have the same magnitude. Table 1. Suction line and discharge line analysis of normal system shown in diagram 1. Nil Nil Nil Refrigerant temp* -1 C -1 C 58 C Line temp 8 C 9K Normal 9 C 78 C Superheat and pressure drop 10K 20K Diagnosis Normal Normal Capacity and power consumption (kw) 18 16 14 12 10 8 6 4 2 1.82 Bar low side CONDITIONS High side Low side Superheat Sub cooling 15.2 bar 1.82 bar 10K 5K 0 0 0.5 1 1.5 2 2.5 3 3.5 4 revolution (x 1000 r.p.m) Graph 1. Suction line pressure drop The most prominent feature of poor refrigerant flow in the suction line is the decrease in compressor capacity and cooling. This poor refrigerant flow can easily be diagnosed by analysing the line for pressure drop between point A and B as shown in diagrams 1 and 2. No erence in pressure between these two points TXV indicates a healthy functional line (diagram 1), however if excessive pressure drop is present, an investigation should be undertaken to determine the cause. The most common is low refrigerant level,which should be discounted first by removing the refrigerant from the system and measuring the quantity = 15.2 bar 20K super heat and pressure drop C = 106 C DANGEROUS LEVEL Discharge UX330 to ensure the correct level is present according to the system requirement. Once the correct refrigerant level is determined, and the pressure drop is still present, then an investigation into the line itself is required. The following diagram 2 shows the reduction in cooling capacity of the same Unicla UX330 compressor (shown in diagram 1) operating in typical conditions on a system with a suction line pressure drop of 1.2 bar. Capacity reduction is a hefty 65%. = 1.82 bar 8 C A = 8 C = 0.62 bar B decreases with pressure drop while super heat increases hose internal closeup 5 C = 5 C Note: This capacity reduction of 65% is assumed without considering further adverse effects on the condenser performance which would increase capacity reduction even further. Diagram 2. Unicla UX330 compressor is operating at 2000 rpm, high side 15.2 bar. Low side 0.62 bar at the compressor and 1.82 bar at the evaporator. Superheat and pressure drop is 20K. Sub-cooling 5K. capacity is 4.5 kw which is a reduction of 65% from 8 kw shown in diagram 1. 2.

Technicians and engineers should be aware when a pressure drop is present in a suction line, the line temperature at the compressor is almost always lower than the line at the evaporator (see points A and B in diagram 2), which is commonly mis-diagnosed as a healthy condition with cool refrigerant returning to the compressor. This actual condition is quite the opposite because the pressure is down and quantity or mass flow of refrigerant is severely reduced. The complete analysis of the suction line with pressure drop, and its relationship to the discharge line is shown in the table 2 below. The effect on the compressor is quite dramatic, the combination of the pressure drop and even more superheat accumulation in line amounts to a total of 20K. Calculated as follows: 7K (pressure drop) + 4K (extra superheat in the line) + 9K (original superheat in evaporator) = 20K Measuring point A B C Position outlet suction discharge drop 1.82 bar 0.62 bar 15.2 bar Nil Nil Nil Refrigerant temp* -1 C -15 C 58 C Line temp 8 C 9K Normal *From R134a pressure and temperature chart. Degrees Kelvin or K is the primary unit of temperature measurement in the physical sciences, and is often used in conjunction with degrees Celsius and whenever reference is made to super heat in a refrigeration system. Both K and C have the same magnitude. Table 2. Suction line and discharge line analysis of system with suction line pressure drop as shown in diagram 2. 5 C 106 C Superheat and pressure drop 20K 48K Diagnosis Reduced capacity overheating Capacity and power consumption (kw) 18 16 14 12 10 8 6 1.82 Bar low side 0.62 Bar low side No pressure drop in suction line - and system with full capacity CONDITIONS High side 15.2 bar Low side 1.82 bar Superheat 10k Sub cooling 5k With pressure drop in suction line - and system with reduced capacity 4 CONDITIONS High side 15.2 bar Low side 0.62 bar 2 Superheat 20K Sub cooling 5K 0 0 0.5 1 1.5 2 2.5 3 3.5 4 revolution (x 1000 r.p.m) Graph 2. This high level of superheat in the suction line reveals the lack of proper refrigerant flow and reduction of capacity at the compressor and system (as shown in graph 2). It also reduces the cooling of the compressor which is evident by the high discharge line temperature of 106 C, which places the compressor and its lubricant in the danger zone for a breakdown or complete failure. A tip to remember is at 2000 rpm, systems with Unicla 45 cc to 330 cc compressors will produce discharge line superheat levels equal to approximately double the level of combined suction line temperature and pressure drop. In this example 2 x 20 C = 40 C, as compared to actual discharge line temperature of 48 C. In most cases, any discharge line with super heat levels in excess of 40 C, is not only placing the compressor in danger, but is also an indication of possible pressure drop or restriction in the suction line causing capacity reduction. In these situations, both symptoms are undesirable and corrective action is required by repairing or replacing the suction to the correct size or condition. Hose selection To secure good suction line performance, it is imperative the correct hose or pipe size is implemented in the system. Suction line pressure drop is commonly caused by under sizing of the hose or pipe diameter as it relates to the refrigerant flow required for the system. The basic principle of this is, larger diameter hose is required as the length of the suction line increases, or when refrigerant flow demand increases in the line from higher compressor capacity and rpm. The rules used by Unicla and Burgaflex for suction line size calculations are outlined in the ASHRAE Hand Book, Refrigeration Volume, 2006 Edition. This provides for suction line hose or pipe size recommendations so any pressure drop from friction is no greater than approximately I K change in saturation temperature in the line when operating at 0 C. 3.

As an example, the system operating as shown in diagram 1 would require a suction line diameter of mm (7/8 ) if the length was 3 to 6 metres, or mm (1,1/8 ) diameter if the length was 10 to 12 metres. The following diagram shows erent suction hose sizes applicable to a system operating with a Unicla UX330 compressor running at 2000 rpm with hose lengths varying from 2 metres to 18 metres. 1 1/8 diameter 18 m length 1,1/8 diameter 12 m length 1,1/8 diameter 6 m length 7/8 diameter 2 m length UX330 7/8 1,1/8 1,1/8 1 1/8 2 m 6 m As the length of the line increases so must the diameter 12 m 18 m Diagram 3. A system with a 330 cc compressor operating at 2000 rpm will require erent size diameter suction lines as the length of the line increases. Mobile and transport air-conditioning applications are challenged by variable compressor speeds due to the same variable speed from the vehicle engine driving the actual compressor. System designers should take into account the optimum speed of operation for the compressor when calculating the suction line size for the system. Or alternatively, if the system is regularly reaching a particular over-speed point or maximum continuous rpm levels, then the suction line capacity and size should be calculated around this. The following table shows further examples of various hose size requirements for a Unicla 330 cc compressor operating at erent rpm levels. 330 series compressors 3m pipe length 6m pipe length 10m pipe length 12m pipe length 18m pipe length RPM RPM (kw) Temp (K) Press (kpa) size mm (inch) Temp (K) Press (kpa) size mm (inch) Temp (K) Press (kpa) size mm (inch) Temp (K) Press (kpa) size mm (inch) Temp (K) Press (kpa) size mm (inch) 1000 6.25 0.46 7.7 19 (3/4) 0.92 9.4 19 (3/4) 0.71 7.3 0.86 8.8 0.34 3.5 1500 9.25 0.94 9.6 19 (3/4) 0.87 8.9 0.38 3.9 0.45 4.6 0.68 7 2000 11.2 0.70 7.1 0.36 3.7 0.6 6.2 0.73 7.5 1.1 11.2 2500 12.9 0.89 9.1 0.46 4.7 0.77 7.9 0.93 9.5 0.48 5 35 (1,3/8) 3000 13.25 0.99 10.1 0.51 5.2 0.85 8.7 10.5 10.6 0.54 5.5 35 (1,3/8) Table 3. 4.

Hose fitting selection The most common mistake made by system designers and technicians in the field is determining the suction hose size based on the dimensions or size of the connection points on the evaporator or the compressor. As an example, if a system has #10 fittings at both the compressor and evaporator, and the correct hose requirement is to utilise a #12 line, the correct course of action is to use single step up fittings (#10 - #12) at each end so the #12 hose can be used. It is a complete mis-conception to assume the advantages of using step-up fittings and #12 hose in this example, are negated by the fact only #10 connection points are at each end. The most ideal situation would be to have #12 sizes over the complete suction line, however the effect of simply having #10 connection points at the ends is minimal, whereas the effects of total pressure drop in the line from using #10 over the complete line could be quite serious. To take this point even further, the requirement to step up the hose size from the available connection point can sometimes necessitate going to the next size again. So to achieve this, double step up Burgaclip fittings are now available from Burgaflex as shown in the following diagram. Hose fitting selection for extended suction lines BURGACLIP BURGACLIP Discharge fittings Suction fittings Female oring THREAD SIZE: THREAD SIZE: Female oring - straight 3/4-14 UNF (#8) 7/8-14 UNF (#10) - straight Unicla UX330 rear hose port #8 - #8 NO STEP UP #10 - #10 #8 - #10 SINGLE STEP UP #10 - #12 #8 - #12 DOUBLE STEP UP #10 - #16 Diagram 4. Burgaclip female oring (FOR) step up fittings available across #8 to #16 hose and fitting range. 5.

A fault in the line drop in the suction line can also be caused by a fault or restriction in the line. In the case of a rubber hose suction line, this can be a kink caused by a sharp bend, or the hose delaminating or swelling from excessive thermal fatigue, contamination or old age. A metal line could also have a kink from a sharp bend, or a simple dent caused from an impact on the outside of the pipe. Diagram 5 shows how such a fault causes a restriction in the line which results in an undesirable pressure drop. The effects of this are the same as described in diagram 2 where system capacity is reduced. = 15.2 bar = 106 C DANGEROUS LEVEL TXV 20K super heat and pressure drop C Discharge UX330 A B = 1.82 bar = 8 C = 0.62 bar = 5 C Hose blockage/restriction caused by de-lamination, scaling, dent or kink. Cross-section of hose showing a fault Diagram 5. Unicla compressor operating with a fault in the suction line causing the same consequences as an undersized line as shown in diagram 2. 6.

Improper line routing drop in the suction line can also be caused by improper routing which is commonly caused by installation of the hose or pipe over a complex or extended circuit between the evaporator and compressor, particularly as seen on many heavy machinery and large transport vehicles. The most significant influence on pressure drop in these applications is the number of sharp turns in the line, or when an upward slope before the compressor is introduced. When both of these design events occur at the same time, Unicla engineers refer to this as the staircase affect. An example of this is shown in diagram 6 below. System capacity reduction as shown in diagram 2 also occurs in this situation if the hose size is not sufficient to compensate for the method of routing. TXV = 15.2 bar 20K super heat and pressure drop C = 106 C DANGEROUS LEVEL Discharge UX330 A B = 1.82 bar = 8 C = 0.62 bar = 5 C Diagram 6. Unicla compressor operating with with multiple bends and upward slope in the suction line. System designers should avoid routing the suction line in this way wherever possible, however when multiple sharp turns cannot be avoided, then particular attention must made to the suction line size. The following Unicla table, as previously mentioned in this booklet, is an excellent guideline for this purpose. Each suction line size shown in this table assumes two bends in the line 90 are allowed if the pressure erence is to be <1K, and for every two additional bends 90, the line must be increased by one size as shown in the table. The system as shown in diagram 6 above has 6 bends, which means two size steps are required. Therefore assuming the line is 6 metres in length and compressor optimum capacity requirement is at 1500 rpm, the line size must increase from 7/8 ( mm) to 1,1/8 ( mm). The effects of the upward slope would require further analysis and another step in size may be needed which is best done under practical test during system validation. 330 series compressors RPM 1000 RPM (kw) 6.25 Temp (K) 0.46 3m pipe length Press (kpa) 7.7 size mm (inch) 19 (3/4) Temp (K) 0.92 6m pipe length Press (kpa) 9.4 size mm (inch) 19 (3/4) 10m pipe length 12m pipe length 18m pipe length 6 metre line size with 2 or less Press size Temp Press size Temp Press size mm mm mm bends 90 (kpa) (inch) (K) (kpa) (inch) (K) (kpa) (inch) = 7/8 ( mm) Temp (K) 0.71 7.3 0.86 8.8 0.34 3.5 1500 9.25 0.94 9.6 19 (3/4) 0.87 8.9 0.38 3.9 0.45 4.6 0.68 7 2000 2500 3000 11.2 12.9 13.25 0.70 0.89 0.99 7.1 9.1 10.1 0.36 0.46 0.51 3.7 4.7 5.2 0.6 0.77 0.85 6.2 7.9 8.7 0.73 0.93 10.5 7.5 9.5 10.6 1.1 0.48 0.54 11.2 5 5.5 35 (1,3/8) 35 (1,3/8) 6 metre line size with 6 bends 90 = 1,1/8 ( mm) 7.

Oil flow A well designed R134a air-conditioning system will have an adequate balance of oil quantity to refrigerant level in the system, which is referred to by Unicla engineers as the System Oil Quantity (SOQ). As a general rule this is recommended to be a minimum of 20% of oil to refrigerant ratio, calculated by volume. For example a system with 4000 grams of R134a refrigerant should have 800 cc of oil (4000 x 20/100 = 800 cc). It should be noted erent systems are able to operate with erent SOQ levels. Some systems may be capable of having less oil, which in theory promotes slightly better heat transfer in the system heat exchangers, whereas other systems may need more oil due to some design issue in the system circuit that compromises the oil return rate to the compressor. The SOQ must be sufficient to ensure the compressor maintains the correct oil level so that all the components in the compressor receive adequate lubrication at all times. In normal refrigeration and air-conditioning circuits there is always a percentage of this oil discharged from the compressor as part of the compression process, and circulates in the system. This amount of oil circulating in the system is referred to as the oil in circulation (OIC), which includes the combination of oil mixed with the refrigerant (miscible oil) and oil accumulating in various system components other than the compressor. This is erent to the the oil circulation ratio (OCR), which is the mass flow rate of oil, usually shown as grams/sec, expressed as a percentage or fraction of the total refrigerant and oil flow rate. Different systems will have varying levels of OCR and OIC, however for this booklet only OIC will be studied for the purposes of showing the effects of the suction line on oil and refrigerant flow. A typical heavy vehicle airconditioning system as shown in diagram 7 will be used as an example. This system is a 12 kw system operating with a Unicla UX330 compressor and a R134a refrigerant charge of 4 kg. It has normal oil level behaviour, correct hose sizes and good refrigerant flow. Normal system Low side High side Oil flow (typical) with correct oil flow TXV Condenser Reciever dryer Good pressure and flow in the suction line, 1.82 bar at both ends Oil circulation constant and returning to compressor UX330 Correct oil in sump Diagram 7. sump maintains correct oil level, and circulation of oil in the system is constant Capacity and power consumption (kw) 18 1.82 Bar low side 16 14 12 10 8 CONDITIONS High side 15.2 bar Low side 1.82 bar Superheat 10K Sub cooling 5K 6 4 2 0 0 0.5 1 1.5 2 2.5 3 3.5 revolution (x 1000 r.p.m) 4 8.

The normal system oil flow as shown in diagram 6 will stabilise at various points to approximate levels as shown in table 4 and illustrated in diagram 8. This occurs after commissioning, and operation of the system for an extended period, and includes oil soaking which is the amount of oil soaked into the system components such as hoses, receiver drier, pipes and inner walls of heat exchangers. System Capacity 12 kw Refrigerant 4 kg R134a SOQ (system oil quantity) 800 cc (20% of refrigerant charge) OIC (oil in circulation) 576-672 cc (72-84% of SOQ, or 12-14% of total system refrigerant and oil-4800 grams) Oil soaking 8-40 cc (1-5% of SOQ) Oil in the compressor 120-240 cc (15-30% of SOQ) Table 4. Oil levels and circulation at various points in the system after commissioning and extended operation Normal system with correct oil flow Low side High side Oil flow (typical) TXV Condenser Reciever dryer Good pressure and flow in the suction line, 1.82 bar at both ends SOQ 20 % of refrigerant charge (20% x 4000 = 800 cc) Oil soaked 1-2 Oil circulation constant and returning to compressor Correct oil in sump 15-30% of SOQ UX330 OIC 72-84% Diagram 8. Oil circulation and soaking levels after commissioning and stabilisation of the system 9. %

However, if restricted flow in the suction line occurs from incorrect sizing or a fault, both refrigerant and oil return to the compressor is reduced. Diagram 9 shows some typical system oil levels when a normal system as shown in diagram 6 has this condition. Oil flow Low side High side Oil flow (typical) with a restriction resulting in no oil in low side TXV Condenser Oil banking up in evaporator Reciever dryer 20% Reduced pressure and flow in the suction line, 1.82 bar at evaporator and 0.82 at the compressor (1 bar pressure drop) is sufficient to cause no oil return to the compressor. Oil level Increased OIC to 95-100% Only 0-5% of oil in compressor UX330 Increased compressor temperature DANGEROUS LEVEL No oil in sump Diagram 9. Diagram 9 shows the dangerous conditions placed on the compressor from lack of oil return caused by a simple pressure drop in the suction line of 1 bar. This compressor will eventually fail due to insufficient lubrication and cooling. Also OIC has increased with additional oil accumulating in the evaporator which further reduces the system capacity and efficiency. 10.

Notes 11.

Notes 12.

HEAD OFFICE Unicla Interntional Limited Unit 1109, 11/F, Manhattan Centre, 8 Kwai Cheong Road, Kwai Chung, N.T., Hong Kong PHONE: +852 24 0180 FAX: +852 24 0680 EMAIL: sales@unicla.hk www.unicla.hk Unicla Australia 14 Motorway Circuit Ormeau, Queensland 4208 Australia PHONE: +61 7 5549 4033 FAX: +61 7 5549 4044 EMAIL: sales@unicla.hk www.unicla.hk Unicla Cat. No. B1601