HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

Similar documents
S and SF Inverted Bucket Steam Traps

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

DF1 and DF2 Diffusers

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

TSS21 Sealed Thermostatic Steam Tracer Trap

SCA Series Inverted Bucket Steam Traps

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

PV4 and PV6 Piston Valves

AVC32 Carbon Steel Air Vent for Steam Systems

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

CA10S, CA14 and CA14S Air and Gas Traps

TP1 and TP2 Temporary Cone Shaped Strainers

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

Dri-Line Mk3 Monnier Compressed Air Drain Trap

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

AVM7 Stainless Steel Thermostatic Air Vent

CA44, CA44S, CA46 and CA46S Air and Gas Traps

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

DCV6 Disc Check Valve

CVS10 Sanitary Check Valves

CP10 Sensor Installation and Maintenance Instructions

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems

FV Flash Vessel Installation and Maintenance Instructions

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

PC10HP Pipeline Connector (ASME 600)

Manual Actuated Boiler Blowdown Valves

Fig 1, Fig 12, Fig 13, Fig 14, Fig 16 and Fig 16L Strainers Installation and Maintenance Instructions

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

FT16 Ball Float Steam Trap Installation and Maintenance Instructions

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

Airodyn, BRair and BRoil Compressed Air Drain Traps

MF2M Monnier Miniature Compressed Air Filter

APT14, APT14HC and APT14SHC Spares 2

IX1 Spirax-Monnier International Compressed Air Filter Installation and Maintenance Instructions

SRV66 Sanitary Pressure Reducing Valve

BPT13 Balanced Pressure Thermostatic Steam Traps

CS10-1 Stainless Steel Clean Steam Separator

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

TW Temperature Control Valve

Thermocirc Installation and Maintenance Instructions

SRV2S Pressure Reducing Valve

MFP14-PPU (Vented) Automatic Packaged Pump Units

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

BDV1 and BDV2 Blowdown / Depressurisation Valves

BT6-B Sanitary Balanced Pressure Thermostatic Steam Trap

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

ML3M Monnier Miniature Compressed Air Lubricator

BCV31 DN40 - Blowdown Control Valve

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

M70i ISO and M80i ISO Stainless Steel Ball Valves for Sanitary Systems Installation and Maintenance Instructions

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

BRV71 and BRV73 Pressure Reducing Valves

TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

BCV31 DN20 - Blowdown Control Valve

Spirax Compact FREME Flash Recovery Energy Management Equipment

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

1. General safety information. 2. General product information. 3. Installation. 4. Commissioning. 5. Operation. 6. Maintenance. 7.

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

Type 130 and HL10 'Safeguard High Limit Control' Installation and Maintenance Instructions

M111 Spiraflo Transducer

RJ check valves Installation and Maintenance Instructions

BSA and BSAT Bellows Sealed Stop Valves Installation and Maintenance Instructions

MPC1M, MPC2M and MPC2AM Monnier High Efficiency Compressed Air Filter / Regulators

595-K/L and 596-K/L Series Self Operated Valves Installation and Maintenance Instructions

QuickHeat TM Packaged Heat Exchanger Solutions

Vane Flow Switches Colima FLU Series

CA46S Austenitic Stainless Steel Air and Gas Trap DN40 and DN50

PC3_ and PC4_ Pipeline Connectors

BCVi43 Blowdown Control Valve

SRV461S and SRV463S Stainless Steel Direct Acting Pressure Reducing Valves

IP2M, IP2AM and IP2DM Monnier International Compressed Air Filter/ Regulators

LP31 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance

STERI-TROL Clean Service 'S' Series Two-port Control Valves DN15 (½") to DN100 (4")

Transcription:

0670350/4 IM-S03-11 ST Issue 4 HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information HM Series 3. Installation 4. Commissioning 5. Operation 6. Maintenance HM34 Series 7. Spare parts Copyright 2016 IM-S03-11 ST Issue 4 1 Printed in France

2 IM-S03-11 ST Issue 4

1. Safety information Safe operation of this product can only be guaranteed if it is properly installed, commissioned, used and maintained by qualified personnel (see Section 1.11 ) in compliance with the operating instructions. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. 1.1 Intended use Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended use / application. The product listed below complies with the requirements of the European Pressure Equipment Directive 97/23/EC and carries the mark when so required. The product falls within the following Pressure Equipment Directive categories: Product Group 2 Gases Group 2 Liquids HM and HM34 SEP SEP i) The product has been specifically designed for use on steam, air or water / condensate which are in Group 2 of the above mentioned Pressure Equipment Directive. The products use on other fluids may be possible but, if this is contemplated, Spirax Sarco should be contacted to confirm the suitability of the product for the application being considered. ii) Check material suitability, pressure and temperature and their maximum and minimum values. If the maximum operating limits of the product are lower than those of the system in which it is being fitted, or if malfunction of the product could result in a dangerous overpressure or overtemperature occurrence, ensure a safety device is included in the system to prevent such over-limit situations. iii) Determine the correct installation situation and direction of fluid flow. iv) Spirax Sarco products are not intended to withstand external stresses that may be induced by any system to which they are fitted. It is the responsibility of the installer to consider these stresses and take adequate precautions to minimise them. v) Remove protection covers from all connections before installation. 1.2 Access Ensure safe access and if necessary a safe working platform (suitably guarded) before attempting to work on the product. Arrange suitable lifting gear if required. 1.3 Lighting Ensure adequate lighting, particularly where detailed or intricate work is required. IM-S03-11 ST Issue 4 3

1.4 Hazardous liquids or gases in the pipeline Consider what is in the pipeline or what may have been in the pipeline at some previous time. Consider: flammable materials, substances hazardous to health, extremes of temperature. 1.5 Hazardous environment around the product Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases, extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive noise, moving machinery. 1.6 The system Consider the effect on the complete system of the work proposed. Will any proposed action (e.g. closing isolation valves, electrical isolation) put any other part of the system or any personnel at risk? Dangers might include isolation of vents or protective devices or the rendering ineffective of controls or alarms. Ensure isolation valves are turned on and off in a gradual way to avoid system shocks. 1.7 Pressure systems Ensure that any pressure is isolated and safely vented to atmospheric pressure. Consider double isolation (double block and bleed) and the locking or labelling of closed valves. Do not assume that the system has depressurised even when the pressure gauge indicates zero. 1.8 Temperature Allow time for temperature to normalise after isolation to avoid danger of burns. 1.9 Tools and consumables Before starting work ensure that you have suitable tools and /or consumables available. Use only genuine Spirax Sarco replacement parts. 1.10 Protective clothing Consider whether you and/or others in the vicinity require any protective clothing to protect against the hazards of, for example, chemicals, high / low temperature, radiation, noise, falling objects, and dangers to eyes and face. 1.11 Permits to work All work must be carried out or be supervised by a suitably competent person. Installation and operating personnel should be trained in the correct use of the product according to the Installation and Maintenance Instructions. Where a formal permit to work system is in force it must be complied with. Where there is no such system, it is recommended that a responsible person should know what work is going on and, where necessary, arrange to have an assistant whose primary responsibility is safety. Post warning notices if necessary. 4 IM-S03-11 ST Issue 4

1.12 Handling Manual handling of large and/or heavy products may present a risk of injury. Lifting, pushing, pulling, carrying or supporting a load by bodily force can cause injury particularly to the back. You are advised to assess the risks taking into account the task, the individual, the load and the working environment and use the appropriate handling method depending on the circumstances of the work being done. 1.13 Residual hazards In normal use the external surface of the product may be very hot. If used at the maximum permitted operating conditions the surface temperature of some products may reach temperatures in excess of 425 C (797 F). Many products are not self-draining. Take due care when dismantling or removing the product from an installation (refer to Maintenance instructions ). 1.14 Freezing Provision must be made to protect products which are not self-draining against frost damage in environments where they may be exposed to temperatures below freezing point. 1.15 Disposal Unless otherwise stated in the Installation and Maintenance Instructions, this product is recyclable and no ecological hazard is anticipated with its disposal providing due care is taken. 1.16 Returning products Customers and stockists are reminded that under EC Health, Safety and Environment Law, when returning products to Spirax Sarco they must provide information on any hazards and the precautions to be taken due to contamination residues or mechanical damage which may present a health, safety or environmental risk. This information must be provided in writing including Health and Safety data sheets relating to any substances identified as hazardous or potentially hazardous. 1.17 Working safely with cast iron products on steam Cast iron products are commonly found on steam and condensate systems. If installed correctly using good steam engineering practices, it is perfectly safe. However, because of its mechanical properties, it is less forgiving compared to other materials such as SG iron or carbon steel. The following are the good engineering practices required to prevent waterhammer and ensure safe working conditions on a steam system. Safe Handling Cast Iron is a brittle material. If the product is dropped during installation and there is any risk of damage the product should not be used unless it is fully inspected and pressure tested by the manufacturer. IM-S03-11 ST Issue 4 5

Prevention of water hammer Steam trapping on steam mains: 30-50 metre intervals Steam Gradient 1:100 Trap set Gradient 1:100 Trap set Trap set Steam Condensate Condensate Condensate Steam Mains - Do's and Don'ts: Flow Flow Steam Steam 6 IM-S03-11 ST Issue 4

Prevention of tensile stressing Pipe misalignment: Installing products or re-assembling after maintenance: 1 3 7 1 3 5 6 4 4 2 2 8 Do not over tighten. Use correct torque figures. Flange bolts should be gradually tightened across diameters to ensure even load and alignment. Thermal expansion: Guides Short distance Fixing point Axial movement Axial movement Guides Guides Medium distance Limit rods Fixing point Limit rods Guides Small lateral movement Large lateral movement Small lateral movement Large lateral movement IM-S03-11 ST Issue 4 7

2. General product information 2.1 Description The Spirax Sarco HM Series inverted bucket steam trap is manufactured in cast iron and has an integral strainer as standard. It is designed to be installed in horizontal pipework and will operate on steam pressures up to 14 bar g (203 psi g). The Spirax Sarco HM34 series inverted bucket trap is similar to the HM Series but is manufactured in carbon steel and will operate on steam pressures up to 32 bar g (464 psi g). Note: For further information see the following Technical Information Sheets, TI-S03-02 for the HM Series and TI-P072-01 for the HM34 Series, which gives full details of:- Materials, sizes and pipe connections, dimensions, weights, operating ranges and capacities. Fig. 1 HM00 (½") and HM10 (¾") Fig. 3 HM34 (½" and ¾") Fig. 2 HM12 (1") 8 Fig. 4 HM34 (1") IM-S03-11 ST Issue 4

2.2 Sizes and pipe connections HM Series ½" (HM00), ¾" (HM10) and 1" (HM12) screwed BSP or NPT. DN15 (HM003), DN20 (HM103) and DN25 (HM123) standard flange BS 4504 and DIN PN16. HM34 Series ½", ¾" and 1" screwed BSP or NPT and socket weld ends BS 3799 Class 3000 DN15, DN20 and DN25 standard flange BS 4504 PN40. Flanges also available ANSI 150 and ANSI 300. 2.3 Materials Trap HM Series HM34 Series Cover Cast iron Cast steel Body ½" and ¾" Cast iron Forged steel 1" Cast iron Cast steel Internals Stainless steel Stainless steel Note: For further information on materials see the following Technical Information Sheets: TI-S03-02 for the HM Series and TI-P072-01 for the HM34 Series. IM-S03-11 ST Issue 4 9

2.4 Limiting conditions HM HM34 Maximum body designed conditions PN16 PN40 PMA Maximum allowable pressure 16 bar g (232 psi g) 40 bar g (580 psi g) TMA Maximum allowable temperature 300 C (572 F) 300 C (572 F) PMO Maximum operating pressure 16 bar g (232 psi g) 40 bar g (580 psi g) TMO Maximum operating temperature 300 C (572 F) 300 C (572 F) Designed for a maximum cold hydraulic test pressure of: 24 bar g (348 psi g) 60 bar g (870 psi g) 2.5 Operating range HM Series Temperature C 300 200 100 0 0 Steam saturation curve 2 4 6 8 10 12 14* 16 Pressure bar g The product must not be used in this region. *PMO Maximum operating pressure recommended for saturated steam 14 bar g (203 bar g). PMX - Maximum differential pressure Size Maximum differential pressure bar 4 8.5 10 12.5 14 Screwed Flanged ½" HM00/8 HM00/7 HM00/6 ¾" HM10/10 HM10/8 HM10/7 1" HM12/12 HM12/10 HM12/7 DN15 HM003/8 HM003/7 HM003/6 DN20 HM103/10 HM103/8 HM103/7 DN25 HM123/12 HM123/10 HM123/7 Note: The pressure limit of the flange type should be greater than the pressure limit of the internal mechanism selected. 10 IM-S03-11 ST Issue 4

HM34 Series Temperature C 300 200 100 0 0 Steam saturation curve 10 20 30 32* 40 Pressure bar g The product must not be used in this region. *PMO Maximum operating pressure recommended for saturated steam 32 bar g (464 bar g). PMX - Maximum differential pressure Size Maximum differential pressure bar 4 8.5 12 20 32 DN15 - ½" HM34/8 HM34/7 HM34/6 HM34/5 HM34/4 DN20 - ¾" HM34/10 HM34/8 HM34/7 HM34/6 HM34/5 DN25-1" HM34/12 HM34/10 HM34/8 HM34/6 HM34/5 Note: The pressure limit of the flange type should be greater than the pressure limit of the internal mechanism selected. IM-S03-11 ST Issue 4 11

3. Installation Note: Before actioning any installation observe the 'Safety information' in Section 1. Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended installation. 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 Check materials, pressure and temperature and their maximum values. If the maximum operating limit of the product is lower than that of the system in which it is being fitted, ensure that a safety device is included in the system to prevent overpressurisation. Determine the correct installation situation and the direction of fluid flow. Remove protective covers from all connections. The trap must be installed with the body upright so that the bucket is rising and falling vertically. When superheat conditions exist the trap body may need to be primed with water prior to steam being turned on to avoid steam blowing through the trap. Inverted bucket steam traps do not permit rapid release of air. On process applications, in particular, this can lead to slow warm-up times and waterlogging of the steam space. A separate external air vent is therefore required in parallel to vent air efficiently. Any bypass should be positioned above the trap. If it is below, and is leaking or left open, the waterseal could be blown away leading to steam wastage (see Fig. 5). Where inverted bucket traps are fitted in exposed conditions the possibility of freezing damage can be reduced by thermal insulation. Traps must be installed in a horizontal pipeline with the strainer pocket at the bottom. The inlet of the trap should be below the drain point of the plant being drained, so that a waterseal can be maintained around the open end of the bucket. A small drop leg should precede the trap - typically 150 mm (6"). Where the trap discharges into a closed condensate return system or where there is a lift at the trap, a check valve should be fitted downstream of the trap. If the trap has to be installed at a higher point than the drainage point then a small bore riser into a 'U' seal should be used. A check valve should be fitted before the trap to prevent the loss of the internal waterseal. See Fig. 6. Note: If the trap is to discharge to atmosphere ensure it is to a safe place, the discharging fluid may be at a temperature of 100 C (212 F). 4. Commissioning After installation or maintenance ensure that the system is fully functioning. Carry out tests on any alarms or protective devices. 5. Operation Under most conditions the trap will discharge condensate with a blast type action. Under low load and/or low pressure applications the discharge may tend to 'dribble'. Condensate is discharged at steam temperature so due care must be given to the site of the discharge. 12 IM-S03-11 ST Issue 4

Air vent Bypass 'HM' trap Fig. 5 Check valve Check valve 'HM' trap Fig. 6 IM-S03-11 ST Issue 4 13

6. Maintenance Note: Before actioning any maintenance program observe the 'Safety information' in Section 1. Warning The body/cover gasket and strainer cap gasket contain a thin stainless steel support ring which may cause physical injury if not handled and disposed of carefully. 6.1 Before undertaking any maintenance on the trap it must be isolated from both the supply line and return line and any pressure allowed to safely normalise to atmosphere. The trap should then be allowed to cool. When reassembling, ensure that all joint faces are clean. 6.2 How to fit the valve and seat assembly: - Undo the cover bolts and nuts (2) and remove the cover from the body. - Unhook the bucket (4) from the valve lever (10). - Remove the valve guide plate by undoing the two screws (5). - Remove the seat (8) from the cover. - Ensure all joining faces are clean and then screw in the new seat to the recommended tightening torque. Use a small amount of joining paste on the threads. - Fit new valve guide plate with the two screws supplied and refit the new lever. Ensure that the valve and seat are aligned correctly before finally tightening the guide plate screws. - Hook the bucket to the lever and ensure gasket faces on the body cover are clean. - Using a new cover gasket (7) refit the cover to the body ensuring the small ferrule (11) is positioned correctly. Tighten cover bolts / nuts to the recommended tightening torque (see Table 1). 6.3 How to clean / replace the strainer screen: - Undo the strainer cap (13) and remove the screen (12) and gasket (14). - Clean or replace the strainer screen (12). - Ensure threads are clean. - Refit new strainer cap gasket and locate the screen in the strainer cap. - Screw into the body and tighten to the recommended torque (see Table 1). 14 IM-S03-11 ST Issue 4

2 Table 1 Recommended tightening torques Item no. or mm Nm (lbf ft) HM ½" and ¾" M6 x 25 15-16 (11-12) Valve seat assembly 6 5 8 10 2 HM34 1" M12 x 45 85-95 (61-68) ½" and ¾" M8 x 30 25-28 (18-20) 1" M12 x 45 25-28 (18-20) 4 11 HM ½" and ¾" 13 50-55 (36-40) 7 8 HM34 1" 13 80-88 (57-63) ½" and ¾" 13 50-55 (36-40) 1" 13 80-88 (57-63) HM ½" and ¾" 22 M28 90-100 (64-72) 13 HM34 1" 27 M32 125-145 (89-104) ½" and ¾" 22 M28 90-100 (64-72) 1" 27 M32 125-145 (89-104) Fig. 7 HM Series shown 12 14 13 2 IM-S03-11 ST Issue 4 15

7. Spare parts The spare parts available are shown in heavy outline. Parts drawn in a grey line are not supplied as spares. Available spares Valve and seat assembly 5, 6 (2 off), 8, 10 Bucket 4 Cover gasket and ferrule (packet of 3 each) 7, 11 Strainer screen 12 Strainer screen gasket (packet of 3) 14 Set of cover bolts and nuts (set of 6) (HM34 only) 2 How to order spares Always order spares by using the description given in the column headed 'Available spares' and state the size and series of the trap. Example: 1 - Valve and seat assembly for DN15 HM34/7 Spirax Sarco inverted bucket steam trap. 16 IM-S03-11 ST Issue 4

2 6 5 8 10 Valve seat assembly 4 11 7 12 14 13 Fig. 8 HM Series shown 2 IM-S03-11 ST Issue 4 17