TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

Similar documents
TECHNICAL DATA. than the water inlet pressure to the concentrate

Wet pipe low flow foam/water system

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

OBSOLETE DESIGN DATA. Foam 301a. February 9, 1998

OBSOLETE. Wet pipe low flow manifold system

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

TECHNICAL DATA OBSOLETE

TECHNICAL DATA. Page 1 of 12

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

TECHNICAL DATA CAUTION

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

TECHNICAL DATA Q= C. Table 1 - Specifications

TECHNICAL DATA. Table 1 - Specifications

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY PNEUMATIC RELEASE. 1. DESCRIPTION (Refer to Figures 1, 2 or 3.

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

TECHNICAL DATA. Trimpac 257a. September 16, 2013

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE. 4. TECHNICAL DATA Approvals:

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which

TECHNICAL DATA. Trimpac 256a. October 31, 2013

TECHNICAL DATA. Dry 132a. October 1, 2008

TECHNICAL DATA. Trimpac 244a. September 16, 2013

TECHNICAL DATA DELUGE VALVE, MODEL F-1 STRAIGHT THROUGH STYLE

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA. Deluge Valves 211a. November 30, 2007 DELUGE VALVE MODEL E-1 ANGLE STYLE 3 (DN80), 4 (DN100) & 6 (DN150)

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA OBSOLETE

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Trimpac 247a_Euro. September 16, 2013

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Deluge Valves 218a. November 30, 2007 DELUGE VALVE MODEL F-1 STRAIGHT THROUGH STYLE 2-1/2 (DN65) - 8 (DN200)

SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company

Anti-flood device Model B-1

INSTALLATION OPERATION MAINTENANCE

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION

VERTICAL BLADDER TANK

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

HORIZONTAL BLADDER TANK

TECHNICAL DATA ACCELERATOR MODEL E-1

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA. Q= Cv S

TECHNICAL DATA CAUTION

FOAM TANK (1/2) DATA SHEET

Bladder Tank Installation & System Design Information

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

FOAM TANK (1/2) DATA SHEET

Speed control assembly model A-1

End Connection. Thread x Thread N/A N/A N/A N/A Flange x Flange N/A

VIKING OBSOLETE CONCENTRATE CONTROL SYSTEM OPERATING, MAINTENANCE, AND FILLING MANUAL. Vertical And Horizontal Bladder Tanks

Data Sheet Issue A

Model DDX-LP Dry Pipe Valve System 8 (200mm) Features. Differential latching clapper-type, lighweight, dependable construction.

TECHNICAL DATA OBSOLETE

Bermad Model:

Features. Model DDX-LP Dry Pipe Valve System 4 (100mm), 6 (150mm) & 165mm Sizes

CONCENTRATE CONTROL SYSTEM

TotalPac X Single interlock Preaction system Electric release

Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)

GENERAL DESCRIPTION MODEL RCW DRY SYSTEM CONFIGURATION. Technical Support Airpark Dr. Standish, MI 48658

Instructions for Installation, Operation, Care and Maintenance

Model 420-HY Pressure Regulating Hydrant Valve

Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Dry Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

BLADDER TANK PROPORTIONING SYSTEM PRE-PIPED

BALANCED PRESSURE PROPORTIONERS

TECHNICAL DATA OBSOLETE

BACK PRESSURE / SUSTAINING

I T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

BERMAD Fire Protection Hydraulic Control Valves

MWEA MAINTENANCE SEMINAR SPECIALTY VALVES POWER GLOBES

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

CASH VALVE TYPE KP BACK PRESSURE VALVES

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

BACK PRESSURE / SUSTAINING

FireLock NXT Preaction Valve with Series 798 Pneumatic/Pneumatic Actuator

Data Sheet Issue A

SINGLE VALVE WITH LOW-FLOW BYPASS

MODEL RCW NON-INTERLOCK PREACTION SYSTEM

TECHNICAL DATA NOTICE

MODEL RCW DRY SYSTEM VALVE

FireLock NXT Dry Valve. System No. Submitted By Spec Sect Para Location Date Approved Date

Features. Model DDX-LP Dry Pipe Valve System 2 (50 mm), 2½ (65 mm), 3 (80 mm), 76 mm, 4 (100 mm), 6 (150 mm), 165 mm & 8 (200mm) Listings & Approvals

Horizontal Bladder Tanks

Bermad Pressure Reducing. Model: 42T

Vertical Bladder Tanks

Tech Tips. Service Call: Adjustable Hydraulic Valves Flow controls Pressure controls Sequence valves Holding valves

ASTRA - DRY PIPE VALVES GROOVE/GROOVE

N2 BLAST Datasheet Preaction single interlock electric c/w N 2 Blast Nitrogen generating system Remote controlled unit

a pilot sprinkler were to be closed after its initial operation, for example a remote manual control station).

Model: 43T. Bermad Pressure Relief Valve

Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Electric Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)

Technical Data. UL Listing is based on the following criteria:

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

Features. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200)

Transcription:

Foam 302 a 1. DESCRIPTION (Refer to Figure 1 on page 302 e.) The Viking Low-Flow Foam/Water Proportioning System is a UL Listed and FM Approved system, for use with 3M and Viking brand foam concentrate. This sprinkler system consists of the following: 1. A standard single-interlocked preaction sprinkler system, using a Viking flow control valve with pressure regulating deluge trim. 2. A Viking Easy Riser check 3. A release module for the supplemental detection system. 4. An in-line balanced-pressure foam concentrate proportioning assembly (ILBP). 5. A hydraulically actuated Viking Halar -coated concentrate control 6. Foam concentrate that is UL Listed and FM Approved for use with the Viking system. This system was developed to provide an accurate foam/water solution at much lower flow ranges than a conventional concentrate controller. The low-flow foam system will also provide positive foam injection throughout the full range of system flows. It will provide a rich foam solution at low flows, which makes it ideal for use on closed-head preaction sprinkler systems. Therefore, it is now possible to obtain the desired concentrate percentage at lower flows, which results in the operation of fewer sprinklers on the preaction system to achieve the desired foam/water solution percentage. The Viking low-flow foam system combines the advantages of a conventional foam pump/ilbp system, but without the additional maintenance or cost of a foam pump. Although the system cannot be re-filled while it is in operation, it requires less service than a foam pump system, while maintaining the dependability of a bladder tank system. The Viking preaction low-flow foam system also allows for the use of multiple foam discharge points with variable pressure. It is capable of sizing the proportioner specifically for the area of application, while using only a single source of foam concentrate supply. Water supply pressure to the bladder Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve. tank must be provided from an upstream source, preceding the pilot regulating control valve and preferably near a main fire water source, pump, or centrally located bladder tank. The inlet foam concentrate pressure to balancing valve (xx) must be 15-20 psig (103-138 kpa) higher for the Viking ILBP assembly than the water inlet pressure to the concentrate controller (CC) (B) at each proportioner location. The balancing valve (42) senses inlet water pressure and balances the foam concentrate pressure to match water pressure at inlet of foam concentrate to metering orifice of (CC). At initial flow conditions of the sprinkler system (low flow), the foam/water mixture is rich in foam concentrate--approximately 6% for 3% mixtures--until the flow rate reaches the indicated minimum flow rate of the ILBP. To obtain the pressure differential between foam concentrate and water pressure, the pilot pressure regulating valve on the pressure regulating deluge trim must be adjusted to reduce the water pressure to the ILBP to meet the required pressure differential between gauges (38 and 30). For best results, the pilot pressure regulating deluge valve (E) should be set using the downstream dual pressure gauge (30) of the pressure control valve (B) and the water pressure gauge (38) pilot pressure control valve (E). For existing sprinkler systems which are restricted in flow and pressure capacity, this system should not be used without supplementing the available supply pressure. The minimum pressure to the ILPB (B) is 40 psi (276 kpa) in flow condition, which requires 55-60 psi (381-415 kpa) at point of usage for ILBP foam concentrate pressure. NOTE: The system requires a minimum P, also a maximum P of 50 psig (345 kpa) between foam concentrate pressure vs. water pressure. If this P is exceeded, the foam water solution will proportion rich (higher than 3.9%) at low flows listed. 2. OPERATION Actuation of the supplemental detection system (pneumatically or electrically) will release the priming water pressure in the deluge valve s priming chamber, allowing the deluge valve to open and filling the preaction system with water. While water flows through the Easy Riser check valve, water will flow out the lower port of the Easy Riser check valve and pressurize the sensing end of the pressure operated relief valve (PORV) which will release the prime pressure of the control valve, allowing it to open and supply foam concentrate to the ILBP. Foam/water solution will be proportioned throughout the system (normally 1%, 3%, or 6%). When a sprinkler head activates, the foam water solution will proportion at a richer concentration unless additional sprinklers open and reach the lower flow rate of the ILBP. The bladder tank is already pressurized by the water supply valve and piping. System water pressure in the space between the flexible bladder and the inside surface of the tank causes the bladder to collapse, forcing foam concentrate out through the foam concentrate supply piping, through the Halar concentrate control valve, and to the balancing valve of the ILBP assembly. The balancing valve senses the inlet water pressure upstream of the concentrate controller and adjusts the foam concentrate pressure to the same water pressure as the inlet to the metering orifice. 3. DISCHARGE DEVICES Standard spray sprinklers Approved with specific foam concentrate and specific fuel being protected. Non-aspirating spray nozzles. Manual monitors or oscillating monitors. Hose reels and hand lines. 4. GENERAL INSTRUCTIONS AND WARNINGS A. Refer to the general notes and warnings (pages 750 a through 755 d) under the tab "Design Notes" in the Viking Foam Systems Engineering and Design B. Refer to specific technical data sheets, acceptable installation standards, codes, and Authority Having Jurisdiction for additional installation, operation, and maintenance instructions. C. Inspections: The system must be inspected and tested in accordance with NFPA 25. See Section Form No. F_091698 New issue, January 21, 1999.

Foam 302 b January 21, 1999 8, "Inspection and Maintenance" on page 302 c. D. Warning: Any system maintenance or testing which involves placing a control valve or detection system out of service may eliminate the fire protection capabilities of that system. Prior to proceeding, notify all Authorities Having Jurisdiction. Consideration should be given to employment of a fire patrol in the affected area. E. The valve, trim, bladder tank, and appurtenances must be installed in an area NOT subject to freezing temperatures or physical damage. 5. DESIGN AND INSTALLATION (Refer to Figure 1 on page 302 e.) Warning: All portions of the foam/water system that are subject to freezing must be located in a heated area. A. Refer to "Special Notes" on page 302 d and the general notes and warnings located in the "Design Notes" section of the Viking Foam Systems Engineering and Design B. Install the flow control valve with pilot pressure regulating deluge trim and the Easy Riser check valve in accordance with the Viking Engineering and Design Data book and Figure 1 on page 302 e. C. Install the in-line balanced proportioning assembly in the riser level with the top of the bladder tank. This will help prevent the foam concentrate from draining or siphoning from the tank into the water supply piping due to expansion of foam in the bladder tank. (See Special Notes A and B, page 302 d.) D. Install foam solution test valve (25**) and system isolation valve (26**), if they are required at these locations. These valves are shown in an optional location based on the concentrate controller being downstream of the system riser These test valves are required in accordance with NFPA 16 and NFPA 16A. E. Install the Viking hydraulically actuated control valve (D) and associated trim as indicated in Figure 1 on page 302 e, trim charts, or technical data pages. F. Install bladder tank (A) in accordance with the manufacturer s instructions with connections as shown on Figure 1 on page 302 e and herein described. 1. Locate the tank as close as practical to the system riser. 2. Allow enough room around the tank to service the bladder. 3. Allow access to the tank for filling from barrels of foam concentrate. 4. Install the pipe from the riser to the tank as indicated on Figure 1. The bladder tank water supply piping (16) must be connected below the pilot pressure regulating deluge valve (E). Install the piping from the tank (A) to the ILBP (B) as straight as possible. 5. All valves and devices should be located for easy access for operation and maintenance. G. All valves should be closed, including the water supply control valve (8), the PORV water supply ball valve, the tank water supply control valve, the 1 2 ball valve, the concentrate control shut-off valve, and the foam solution test H. Pressurize System. 1. Verify that the water supply control valve (9) is closed, the tank water supply control valve (10) is closed, and then place the pressure regulating deluge valve (E) in service as follows (see installation instructions on Viking technical data sheet). Open system isolation valve (17**) if it was 2. Set release and detection system according to installation instructions for a single-interlocked (pneumatic or electric release) preaction system. 3. Prime the Viking pressure regulating deluge valve (E) by opening the priming valve on the preaction deluge valve (E) trim. Prime the Halar -coated concentrate control valve by opening the concentrate control priming valve (21). Bleed off any air pressure trapped in the priming line to the Viking control valve by opening the three-way pressure gauge valve (27). Once air pressure has been relieved, close the three-way valve to maintain pressure on gauge (27). 4. When pressure in the pilot pressure regulating preaction deluge valve (E) and the concentrate control valve (D) priming chambers equal system water supply pressure, turn on system water supply by opening water supply valve (9), and place alarm test shut-off valve in alarm position. 5. Place bladder tank (A) in service by following manufacturer s instructions, but SLOWLY open the concentrate control shut-off valve (22***) to allow foam concentrate to flow slowly to the Viking control valve (D). With system fully set, fully open and secure the water supply control valve (15). 6. Verify normal valve positions and secure them in proper position. (See "System Components" section on page 302 c.) 7. Check for and repair any leaks. I. Testing the foam concentrate swing check valve: After a flow test or proportioning test has been conducted, follow the four steps below to check the foam concentrate swing check valve (24) to ensure that it maintains a positive seal between the concentrate control deluge valve (D) and the preaction riser. 1. Bleed off any pressure which may have been trapped between the outlet chamber of the concentrate control deluge valve (D) and the swing check valve (24) by placing a container under the foam concentrate auxiliary drain valve (29) and slowly opening the 2. Drain excess foam concentrate into container. Should the leakage continue, check the priming pressure gauge (27) on the Viking concentrate control deluge valve to ensure that the valve is primed and 3. If the foam concentrate auxiliary drain valve (29) continues to leak foam concentrate, then the concentrate control valve must be checked for proper operation and be repaired if necessary. For repair, follow the procedure indicated in Section 6-D of foam technical data page 101 e, entitled "Wet-Pipe Foam/Water System using AFFF or ATC". 4. If water continues to leak from the foam concentrate auxiliary drain valve (29), the foam concentrate check valve (24) clapper rubber and seat should be maintained. For re-

Foam 302 c pair, follow the procedure as indicated in section 6-A of foam technical data page 101 e, titled "Wet Pipe Foam/Water System using AFFF or ATC". 6. PERFORMANCE REQUIREMENTS Viking low-flow foam systems are available in sizes 3, 4, 6, and 8 (80 mm, 100 mm, 150 mm, and 200 mm). For flow and concentrate characteristics, see foam technical data pages 870 c and 870 d. The 3 (80 mm) low-flow foam system assembly requires either a 2 or 4 (50mm or 100 mm) pressure regulating valve, depending on the flow of the system. 7. PLACING THE SYSTEM IN SERVICE OR REMOVING THE SYSTEM FROM SERVICE Refer to foam data pages 301 d and 301 e, entitled "Preaction Foam/Water System using AFFF or AFC", for the preaction portion of the system. Refer to the Viking Engineering and Design Data book, "Pilot Pressure Regulated Deluge System" technical data page 521 b for electric release, and page 522 b for pneumatic release for placing the valve in service, and setting the discharge pressure and testing the 8. INSPECTION AND MAINTENANCE Refer to foam data page 301 e, Section 7, and page 301 f, of the Viking Foam Systems Engineering and Design Data book for inspection and maintenance instructions for the preaction foam/water system. Refer to the Viking Engineering and Design Data book under "Pressure Regulation" tab, "Equipment" sub tab for information regarding the pressure regulating components of the system. 9. TROUBLE SHOOTING Refer to foam data page 301 e, Section 8, and page 301 f, of the Viking Foam Systems Engineering and Design Data book for trouble shooting the preaction foam/water portion of the system. Refer to the Viking Engineering and Design Data book under "Pressure Regulation" tab, "Equipment" sub tab for information regarding the pressure regulating components of the system. 10. EMERGENCY INSTRUCTIONS Refer to foam data page 301 e of the Viking Foam Systems Engineering and Design Data book for emergency instructions regarding the preaction foam/water system portion of the system. 11. LABORATORY APPROVALS AND LISTINGS As a complete Viking system: UL Listed. Viking Bladder tank: UL Listed, FM Approved, and ASME, Section Vlll. Certified. Viking pilot operated pressure regulating deluge trim: UL Listed. Viking ILBP: UL Listed and FM Approved. Viking foam concentrate and 3M foam concentrate: UL Listed and FM Approved. Note: The Listings and Approvals for the Viking low-flow foam system are based on a complete system as indicated and described in "Preaction Low-Flow Foam System" technical data pages 302 a- e. Any alteration to the system configuration will void the Listings and Approvals as well as any Viking warranty. 12. REFERENCES A. Viking Engineering and Design 1. Technical data page 531 a-d, entitled "Model C-1 Pilot Pressure Regulating Valve". 2. Technical data covering the Model H-1 Flow Control Valve. 3. Technical data page 815 a-e, covering the Model F-1 Easy Riser Swing Check Valve. 4. "Pressure Regulation" tab. B. Viking Foam Systems Engineering and Design 1. Technical data page 101 a-f, entitled "Wet-pipe Foam/Water System using AFFF or ATC". 2. Technical data page 301 a-e, entitled "Preaction Foam/ Water System using AFFF or ATC". 3. "Tanks" sub tab. 4. "Proportioning Devices" sub tab. 5. Technical data covering Model E-2 Halar -Coated Deluge Valves. 13. SYSTEM COMPONENTS (For Figure 1 on page 302 e, Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.) A. Foam concentrate bladder tank, complete with items 1-7: 1. Water drain/fill valve, normally 2. Fill line mater shut-off valve, normally 3. Concentrate drain/fill valve, normally 4. Fill cup/sight gauge shut-off valve, normally 5. Sight gauge assembly The trim for this assembly varies with the type of foam concentrate to be used. Refer to foam technical data pages 830 a-u for specific details. 6. Tank water vent valve, normally 7. Diaphragm concentrate vent valve, normally B. Viking in-line balanced pressure proportioner assembly (ILBP) including concentrate controller with metering orifice: 24. Check 30. Duplex gauge, ILBP piping (stainless steel or brass). 42. Spool balancing valve with TFE lined stainless steel braided hose and fittings. Delta P foam vs. water, minimum 15 psi (103 kpa). C. Easy Riser check D. Concentrate control valve (CCV)-- Hydraulically actuated Halar - coated Viking deluge 17. PORV (connected to nonpressurized side of Easy Riser check valve). 18..125" restricted orifice. 19. 1 /2 spring-loaded check 20. 1 /2 Y strainer. 21. 1 /2 ball valve, normally open. 27. Priming water pressure gauge and three-way valve, including CCV trim. 29. 1 /2 foam concentrate auxiliary drain E. Pilot Pressure Regulating Deluge valve: 31. Viking Model H-1 Flow Control Valve. 32. Viking Model C-1 Pilot Pressure Regulating Valve. 33. Viking Model A-1 Speed Control Assembly. 34. Check 35. Priming 36. Restricted orifice. 37. Strainer. 38. Water supply gauges.

Foam 302 d January 21, 1999 39. Drain 40. Air bleed valve and pressure gauge. 41. Downstream pressure gauge. 42. Emergency release. F. Accessory trim (order each item separately): 8. Water supply control valve, normally open. 13. CCV release piping to PORV. 14. 1 /2 PORV water supply ball valve, normally open. 15. Tank water supply control valve, normally open. 16. Water supply piping to bladder tank. 22. Concentrate control shut-off valve, normally open*** 23. Foam concentrate discharge piping. 24. Foam concentrate swing check 25. Foam solution test valve, normally closed** SPECIAL NOTES 26. System isolation valve, normally open** **Optional location for required test valves ***Full port bronze body with 316 Stainless Steel trim and ball (2 and under). Cast iron body OS & Y with bronze trim and seats (over 2 ). A. Provide a minimum of five pipe diameters of straight pipe on the inlet and outlet of the concentrate controller (B) to minimize the turbulence inside the concentrate controller. Warning: If the outlet to the foam solution test valve (25**) is located closer than five pipe diameters, there may be turbulence at high flow rates. B. The release of the concentrate control valve and the preaction valve must NOT be combined. The concentrate control valve must be primed and released separately from the pressure regulating preaction valve to ensure open position of the concentrate control valve clapper. C. Figure 1 is a general schematic of the required piping arrangement. Refer to the appropriate technical data page for specific information regarding the valve, tank, and related trim and devices. D. The technical information, statements, and recommendations contained in this manual are based on information and tests which, to the best of our knowledge, are dependable. They represent general guidelines only, and the accuracy or completeness thereof are not guaranteed, as conditions of handling and usage are outside Viking s control. The purchaser should determine the suitability of the product for its intended use and assumes all risks and liability whatsoever in connection therewith. E. A strainer is not required in the foam concentrate discharge piping (23) of bladder tank systems per NFPA Standards. F. The foam deluge CCV (D) does not require any trim, except for a 1 /2 priming line (28), 1 /2 auxiliary drain valve (29), and gauge with three-way valve (27). Plug all remaining valve trim outlets. Refer to the "Valves" sub tab in the "Equipment" section of this foam technical data book to find the correct trim kit part number for the corresponding size of foam concentrate control Halar -coated deluge valve (D) required.

Foam 302 e Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve. Figure 1