A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION

Similar documents
MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS

Understanding Dissolved Gas Analysis (DGA) Techniques and Interpretations

Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers

Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI

Online DGA-monitoring of power transformers

A Revised Framework for the Transformer DGA Guide

TRANSFORMER SERVICE. Dissolved gas analysis and oil condition testing

Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks

Nandkumar Wagh, D.M. Deshpande

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS

Since the beginning of production of oil for transformers

Categorizing Faults via DGA. GE Grid Solutions M&D

Dissolved Gas Analysis - Past, Present and Future

EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS

DGA Tools: Duval Triangles and Pentagons

Online Publication Date: 19 January, 2012 Publisher: Asian Economic and Social Society

Draft Guide for the Interpretation of Gases in Oil Immersed Transformers

Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers

DISSOLVED GAS ANALYSIS OF POWER TRANSFORMERS

Condition Monitoring of Power Transformer Using Dissolved Gas Analysis of Mineral Oil: A Review

Research Article. Fault diagnosis of power transformer based on chemical properties of insulation oil

PROPOSAL FOR AN IMPROVEMENT IN TRANSFORMER DIAGNOSIS BY DGA USING EXPERT SYSTEM.

A New Approach for Transformer Incipient Fault Diagnosis Based on Dissolved Gas Analysis (DGA)

* Analysis of TCG ( Total Combustible Gas ) and 6 kinds of Gases * High Sensitivity for C 2

Improved Monitoring of Dissolved Transformer Gases on the Basis of a Natural Internal Standard (NIS)

Power Transformer Fault Diagnosis Based on Dissolved Gas Analysis Using a Fuzzy Neural Network Approach in a Real Data Base

TRANSFORMER RELIABILITY AND DISSOLVED-GAS ANALYSIS. Delta-X Research Inc, Victoria BC, and 2 IREQ, Varennes QC CANADA

Mathieu Guertin. Morgan Schaffer Inc. Canada. Director Europe, Russia and Africa. A cost effective strategy for smart grid technology adoption

Describe Flammable Gas Measurement

ISO INTERNATIONAL STANDARD. Welding consumables Gases and gas mixtures for fusion welding and allied processes

Diagnostics of HV bushings through oil sampling and analysis. Experience with GSU transformers

ON-LINE MONITORING OF REGULATOR TRANSFORMER AT THE MARGEM DIREITA SS IN ITAIPU. M. E. G. ALVES* Treetech Sistemas Digitais Ltda.

Advanced Test Equipment Rentals ATEC (2832) OMS 600

INTERNATIONAL STANDARD

FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO

Analysis of Dissolved Gas in transformer oil by conventional Techniques and Artificial Intelligence approach-a Review.

Hydro Plant Risk Assessment Guide

You should be able to: Describe Equipment Barometer Manometer. 5.1 Pressure Read and outline 5.1 Define Barometer

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV

Managing on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution power transformers

Guide for the Sampling of Oil from Trench COTA Bushings for DGA

CP Chapter 13/14 Notes The Property of Gases Kinetic Molecular Theory

COAL MINES TECHNICAL SERVICES, GAS DETECTION RELATED SERVICES FOR MINES RESCUE

Session Number: 3 High Voltage Power Transformer Dissolved Gas Analysis, Measurement and Interpretation Techniques

Misuse of Combustible Gas Meters

What I have learned about SF 6 gas testing.a Practical explanation

CP Chapter 13/14 Notes The Property of Gases Kinetic Molecular Theory

ISO 9539 INTERNATIONAL STANDARD. Gas welding equipment Materials for equipment used in gas welding, cutting and allied processes

PLANT OPERATIONS AND TECHNOLOGY I & II: REAL TIME FURNACE AIR IN- LEAKAGE MONITORING ON COAL, OIL AND/OR GAS FIRED BOILERS

SUBSTATION MAINTENANCE ELECTRICAL OPERATING PROCEDURE

An Intelligent Fault Diagnosis Approach for Power Transformers Based on Support Vector Machines. Hao Xu

Dissolved Oxygen Guide

MEASURING VOLUME & MASS

Chapter 5 TEST: Gases

NZQA unit standard 7145 version 9 Page 1 of 5. Design and maintain effective ventilation systems for an underground coal mine

Applications Note: Use of "pentane equivalent" calibration gas mixtures

To compare one gas to another, it is convenient to define a set of conditions: Standard Temperature and Pressure

Chapter 7. Coal Cargoes. Properties and Characteristics 7.1

Experiment 18 Properties of Gases

Real-time Analysis of Industrial Gases with Online Near- Infrared Spectroscopy

FCTechnik. flox[control] Gas Control Units for Aluminium Production. for aluminium production flox[control] flox[on] FC Technik 1

4.) There are no forces of attraction or repulsion between gas particles. This means that

ENVIRONMENTAL AND POLLUTANTS GAS ANALYZERS

Sampling Considerations for Equilibrium Dissolved Oxygen [DO] Sensors

DSC 204 HP Phoenix. High-Pressure Differential Scanning Calorimetry up to 15 MPa Method, Technique and Applications

ISO INTERNATIONAL STANDARD

C Dissolved Gas Analysis Of Load Tap Changers. Working Group

Ultima. X Series Gas Monitor

Protective Atmospheres, Measurement Technologies and Troubleshooting Tools

Unit 9: Gas Laws REGENTS CHEMISTRY

Barrier Development and Evaluation Methodology. D.S. Musgrave 1 1 Thermal Visions, Inc., Granville, USA

Atmospheric Hazards. Hazardous Atmosphere 3/29/2017. Oxygen deficiency and enrichment Flammable gases and vapors Toxic contaminants

Unit 10: Gas Laws. Monday Tuesday Wednesday Thursday Friday. 10 Review for Cumulative Retest. 17 Chem Think Gas Laws Tutorial- Computer Lab-

Dr. Rogers Chapter 5 Homework Chem 111 Fall 2003

Flammability Chart. Gas Formula Ignition

Dynamic Behaviour of Fault Gases and Online Gas Sensors. Germany

A. What are the three states of matter chemists work with?

Name Chemistry Pre-AP

Mass Flow Controller (MFC) for Gases

Temperature Influence on the Flammability Limits of Heat Treating Atmospheres

Name /74. MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.

Applied Technology and Best Practices in CEE. Conference

Matching Vacuum Pump to Process

Permitted MSS Emissions Tracking, Recordkeeping, and Reporting. Presented by ACES April 24, 2008

Gases NO CALCULATORS MAY BE USED FOR THESE QUESTIONS

Review of oxygen deficiency requirements for graham s ratio

Carolina Narrow Fabric Company

A quantitative software testing method for hardware and software integrated systems in safety critical applications

CHEMISTRY - CLUTCH CH.5 - GASES.

CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO Walnut Lake Rd th Street Houston TX Garner, IA 50438

States of Matter. Q 7. Calculate the average of kinetic energy, in joules of the molecules in 8.0 g of methane at 27 o C. (IIT JEE Marks)

Section 8.1 Properties of Gases Goal: Describe the kinetic molecular theory of gases and the units of measurement used for gases.

Standard Operating Procedure for H 2 S and SO 2 Converter

Unit 11 Gas Laws Chapters 13 of your textbook

4/26/16. Section 1 Understanding Solutions. Solutions and Suspensions. Solutions and Suspensions. Solutions and Suspensions. Solvents and Solutes

Quebec Quebec Tel : Fax : MSDS: Methane, Oxygen in Nitrogen Mixture PRODUCT INFORMATION

Point level switches for safety systems

Intrinsic safety 101 hazardous locations

Chapter 13 Gases, Vapors, Liquids, and Solids

Transcription:

A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION Athira K Anil 1, Archana R 2 1 PG Student, Electrical and Electronics Engineering, FISAT, Kerala, India 2 Associate Professor, Electrical and Electronics Engineering, FISAT, Kerala, India ABSTRACT Power transformers are important equipment of power system. The fault free operation of power transformers is a factor of major economic importance. Dissolved Analysis (DGA) of transformer oil is one of the most effective power transformer condition monitoring tools. It has been proven that the generation of certain gases within a transformer is an excellent indicator that a failure is pending. DGA is a sensitive and reliable technique for detecting incipient fault condition in oil-immersed transformers. The overall health condition of the transformer strongly depends on the quality of insulation system within the power transformer. This paper deals with different DGA approaches such as Key, Dornenburg Ratio, Rogers Ratio, IEC Ratio, Nomograph and Duval Triangle Method. Key Method uses individual gas levels for detecting faults. Dornenburg Ratio Method and Rogers Ratio method uses the ratio of gas concentrations to indicate fault types. IEC Ratio Method uses the same three ratios as in Rogers Ratio Method but suggests different ratio ranges and interpretations. Nomograph method improves the accuracy by graphically representing the fault gas data. Duval triangle method uses values of three gases and they are transformed into triangular coordinates. The life of a transformer mainly depends on the life of its insulation system. Degree of polymerization, amount of CO and CO 2, amount of furans, interfacial tension and acid number, oxygen level and moisture are the potential factors that affect the quality of insulation in a transformer. This study compares the effectiveness of dissolved gas analysis methods and also different factors affecting the insulation strength of the transformer. Keyword: - Dissolved Analysis, Power Transformers, Interfacial Tension, Insulation, Furans. 1. INTRODUCTION Power transformers are vital link in power system. Monitoring and diagnostic techniques are essential to decrease maintenance and to improve reliability of the equipment. The fault free operation of power transformers is a factor of major economic importance and safety in power supply utilities. The electrical windings in a power transformer consist of paper insulation immersed in insulating oil, hence transformer oil and paper insulation are essential sources to detect incipient faults, fast developing faults and generally reflects the health condition of the transformers. and electrical stresses that occur within normal operating transformers cause insulation oil to break down and to release small quantities of gases. The composition of these gases depends on the fault type. es produced due to oil decomposition are hydrogen (H 2 ), methane (CH 4 ), ethane (C 2 H 6 ), ethylene (C 2 H 4 ) and acetylene (C 2 H 2 ). Paper decomposition produces carbon monoxide (CO) and carbon dioxide (CO 2 ) [1-2]. Dissolved gas analysis (DGA) is a sensitive and reliable technique for detecting incipient fault conditions in oilimmersed transformers. DGA requires routine oil sampling and modern technologies for online gas monitoring. DGA approaches can evaluate the ageing process, deteriorating cellulose material of the transformer oil, the degree of polymerization and Furan analysis. By sampling and examining the insulating oil of transformers, ratios of C-1533 www.ijariie.com 189

specific gas concentrations, their generation rates and total combustible gases are often used as the attributes for classification by diverse DGA approaches. 2. DGA INTERPRETATION SCHEMES Various DGA methods have been used by organizations and utilities to assess transformer conditions. These DGA interpretation schemes are based on empirical assumptions and practical knowledge gathered by experts worldwide. Interpretation schemes are generally based on defined principles such as gas concentrations, key gases, key gas ratios and graphical representations. Key Analysis, Dornenberg and Rogers Ratio Methods, Nomograph, IEC Ratio and Duval Triangle are the common schemes mentioned in IEEE Standard C57.104-2008. 2.1 Key Method The Key Method is based on the quantity of fault gases that are released from the insulating oil as the chemical structure breaks at varying temperatures in the transformer [3-4]. The presence of the fault gases depends on the temperature or energy that disrupts the chemical structure of the insulating oil. This method uses individual gas levels for detecting faults. The significant and proportion of the gases are called key gases. Table -1: Key es and their Fault Interpretations Key es O 2 & N 2 CH 4 & C 2 H 6 C 2 H 4 CO & CO 2 H 2 C 2 H 2 Fault Type Non-fault condition Low temperature overheating of oil High temperature overheating of oil Overheating of cellulose insulation Corona Arching This test is important and most frequently performed because it provides the first indication of a problem. The hydrocarbon molecules of mineral oil decompose and form active hydrogen and hydrocarbon fragments, which then combine into gases. This method relates key gases to fault types and attempts to detect four fault types, including overheating of oil, overheating of cellulose, partial discharge (corona) and arching. The concentrations of key gases are expressed in parts per million (ppm). This method is simple, but they are not widely accepted as reliable diagnostic tools for power transformers. 2.2 Dornenburg Ratio Method This method uses the ratio of gas concentrations to indicate fault types. ratio methods use coding schemes that assign certain combinations of codes to specific fault types. A fault condition is detected when a gas combination fits the code for a particular fault. The codes are generated by calculating ratios of gases concentrations and comparing the ratios with predefined values derived experience and continually modified. The Dornenburg Ratio Method [5] uses four gas concentration ratios such as CH 4 /H 2, C 2 H 2 /C 2 H 4, C 2 H 2 /CH 4 and C 2 H 6 /C 2 H 2, which can be used to identify thermal faults, corona discharge and arching. Each successive ratio is compared with certain values and if all four succeeding ratios for a specific fault fall within the predetermined values, the diagnosis is confirmed. In this scheme, the ratio procedure is considered correct if the gas concentrations (in ppm) for H 2, CH 4, C 2 H 2 and C 2 H 4 exceed twice the relevant L1 concentrations shown in Table 2. However, the method may obtain numerous no interpretation results due to incomplete ratio ranges. C-1533 www.ijariie.com 190

Table -2: Concentration of Dissolved Key L1 Concentrations (ppm) Hydrogen (H 2 ) 100 Methane (CH 4 ) 120 Carbon monoxide ( CO) 350 Acetylene (C 2 H 2 ) 35 Carbon monoxide ( CO) 50 Acetylene (C 2 H 2 ) 65 Suggested Fault Diagnosis Decomposition Table -3: Dornenburg Ratio Method Concentration Ratios CH 4 /H 2 C 2 H 2 /C 2 H 4 C 2 H 2 /CH 4 C 2 H 6 /C 2 H 2 >1.0 >0.1 <0.75 <1.0 <0.3 <0.1 >0.4 >0.2 Corona <0.1 <0.01 Not significant <0.3 <0.1 >0.4 >0.2 Arching >0.1 <0.1 >0.01 <0.1 >0.75 >1.0 >0.3 >0.1 <0.4 <0.2 2.3 Rogers Ratio Method The most common gas ratio method is the Rogers Ratio Method [6], which distinguishes more thermal fault types compared to the Dornenburg Ratio Method. Instead of needing significant concentrations of the key gases, the Rogers Ratio Method can be used when the concentrations exceed the values listed in Table 2 (rather than double). Values of three gas ratios and suggested fault types are shown in Table 4. Table -4: Ratios for Key es- Rogers Ratios Method Suggested Fault Type C 2 H 2 /C 2 H 4 CH 4 /H 2 C 2 H 4 /C 2 H 6 Normal <0.1 >0.1 to <1 <1 Partial discharge <0.1 <0.1 <1 Arching 0.1 to 3 0.1 to 1 >3 Low temperature thermal fault fault <700 C fault >700 C <0.1 >0.1 to <1 1 to 3 <0.1 >1 1 to 3 <0.1 >1 >3 C-1533 www.ijariie.com 191

This method is effective because it correlates the results of numerous failure investigations with the gas analysis of each case. Since the method does not consider dissolved gases below normal concentration values, a precise implementation of the method may still misinterpret data. 2.4 IEC Ratio Method This method uses the same three ratios as in Rogers Ratio Method but suggests different ratio ranges and interpretations. The fault diagnosis scheme recommended by the International Electrotechnical Commission (IEC) [7] deals with four conditions such as normal ageing, partial discharge of low and high energy density, thermal faults and electrical faults of varying intensity. IEC 60599-1978 (first version) is based on simple coding scheme while IEC 60599-1999 (second version) uses revised ratio ranges directly. 3D graphical representation of ratio ranges is another improvement of second version. Faults that cannot be diagnosed are plotted onto the graph so that its nearest distance to a certain fault region can then be observed. Table 5 shows the interpretations. Table -5: Suggested IEC Ratio Method Diagnosis Case Characteristic fault C 2 H 2 /C 2 H 4 CH 4 /H 2 C 2 H 4 /C 2 H 6 PD Partial discharges Not significant <0.1 <0.2 D1 D2 Discharges of low energy High energy discharges >1 0.1-0.5 >1 0.6-2.5 0.1-1 >2 T1 faults<300 C Not significant >1 but Not significant <1 T2 T3 faults>300 C and <700 C faults>700 C <0.1 >1 1-4 <0.2 >1 >4 2.5 Nomograph Method The Nomograph Method [7] improves the accuracy by incorporating gas ratios and the concept of Key threshold. It simplifies interpretation by graphically presenting fault gas data. A nomograph is a series of vertical logarithmic scales for representing the concentration of individual gases as straight lines drawn between adjacent scales. The line connects points representing the values of individual gas concentrations. The diagnostic tool for determining fault types is straight lines. Fault types are identified by visually comparing the slopes of line segments with the keys at the bottom of the nomograph. Position of lines related to the concentration scales indicates the fault severity. An arrow is used to indicate the threshold value of each vertical scale. For the slope of a line to be considered significant, at least one of the two tie points should exceed the threshold value. The fault is not considered significant if the tie point lies above a threshold value. 2.6 Duval Triangle Method This method uses values of only three gases CH 4, C 2 H 2 and C 2 H 4 and their location in a triangular map [8]. es are transformed into triangular co-ordinates. There are six potential fault zones within the triangle. This method is easily performed but careless implementation can obtain false diagnosis. The permissible amount of dissolved gases C-1533 www.ijariie.com 192

should be determined before using this method to analyze transformers. One drawback of the gas ratio methods is that some results can fall outside codes and gives no interpretations. This does not occur in Duval Triangle Method because it is a closed system. It always provides a diagnosis, with a low percentage of wrong diagnosis. Fig. 1 shows the coordinates and fault zones of Duval Triangle. Fig -1: Coordinates and Fault Zones in the Duval Triangle Method 3. TRANSFORMER HEALTH CONDITION The quality of insulation system within power transformers reflects the overall health condition of the transformer. A timely and reliable maintenance decision along with the remaining operational life estimation of the asset can be identified through the measurements of some parameters reflecting the degradation rate of the transformer dielectric insulation 3.1 Degree of Polymerization (DP) DP is defined as the number of monomeric units in a macromolecule or polymer. The cellulose molecule is made up of a long chain of glucose rings which form the mechanical strength of molecule and the paper. When cellulose is aged by thermal stress, the molecular chains are broken. When the insulation is new, the DP is typically between 1000 and 1400 [1]. When DP reaches around 200, the insulation has reached the end of life. All mechanical strength of the insulation has been lost and the transformer must be replaced. 3.2 Amount of CO & CO 2 CO increment rate in insulating oil along with CO 2 /CO ratio provide valuable information about paper degradation activity. IEEE Standard C57.104 Guide for the Interpretation of es Generated in -Immersed Transformers [3] gives status conditions based on accumulated values of CO 2 and CO. CO 2 value in between 0-2500 ppm and CO value in between 0-350 ppm indicates normal operation. CO 2 value greater than 10000 ppm and CO value greater than 1400 ppm indicate imminent risk and complete degradation of the paper insulation. 3.3 Oxygen Level Under the same temperature conditions, cellulose insulation in low oxygen oil will last 10 times longer than insulation in high oxygen oil. Above 2000 ppm, oxygen in the oil greatly accelerates paper deterioration. If the oxygen level reaches 10000 ppm, the oil should be de-gassed. High atmospheric gases normally indicate that a leak has developed in a bladder and diaphragm in the conservator. C-1533 www.ijariie.com 193

3.4 Furans Furan is a heterocyclic organic compound, consisting of a five-membered aromatic ring with four carbon atoms and one oxygen. When cellulose insulation decomposes due to overheating, furans are developed. The most important is 2-furfuraldehyde. In healthy transformers, there are no detectable furans in the oil, or they are less than 100 ppb (parts per billion). When significant damage to paper insulation has occurred, furan level increases to 3000 ppb and it indicates the end of expected life of paper insulation. 3.5 Moisture Moisture, especially in the presence of oxygen, is hazardous to transformer insulation. Each time the moisture is doubled in a transformer, the life of the insulation is doubled by one-half. The life of the transformer is the life of the paper and the life of the paper is extended by keeping out moisture and oxygen. When the transformer is energized, water begins to migrate to the coolest part of the transformer and the site of the greatest electrical stress. This location is normally the insulation in the lower one-third of the winding. Paper insulation has a much greater affinity for water than oil. 3.6 Interfacial Tension and Acid Number Interfacial tension (IFT) is the force that holds the surface of a particular phase together and is normally measured in dynes per centimeter. Clean oil will make a very distinct line on top of the water and give an IFT number of 40 to 50 dynes per centimeter. As oil ages, it is contaminated by tiny particles of the oil and paper insulation. Then particles in oil weaken interfacial tension and lower the IFT number. must be reclaimed when the IFT number falls to 25 dynes per centimeter to prevent sludging [1]. Acid number is the mass of potassium hydroxide (KOH) in milligrams that is required to neutralize one gram of chemical substance. Acid number is used to quantify the amount of acid present in the oil. High acid number indicates more acid in the oil. New transformer oil contains practically no acid. Oxidation of insulation and oil forms acids as transformer ages. Acid attacks metals inside the tank and form more sludge. Sludging begin when acid number reaches 0.40. So the oil should be reclaimed when the acid number reaches 0.20 mg KOH/gm. 4. CONCLUSION Fig -2: Service Limits for Transformer The key objective in fault gases analysis is correctly diagnosing that fault that generated by the detected gases. This study analyzed six most common methods of Dissolved Analysis: Key, Dornenburg Ratio, Rogers Ratio, IEC Ratio, Nomograph and Duval Triangle Method. The factors which play an important role in the quality of transformer oil and paper insulation are also studied. Using multiple DGA techniques to analyze transformer faults may obtain different or conflicting fault interpretations. Most DGA approaches rely on expert analysis, which could be insensitive to slowly developing and insignificant faults. Therefore, optimizing the combination of various diagnostic techniques is an important issue. C-1533 www.ijariie.com 194

6. REFERENCES [1] Hydroelectric Research and Technical Services Group, Facilities, Instructions, Standards and Techniques; Transformer Diagnostics, US Department of Interior Bureau of Reclamation, Vol. 3-31, 2003. [2] M Arshad, Remnant Life Estimation Model Using Fuzzy Logic for Power Transformer Asset Management, Ph.D thesis, Curtain University of Technology, Australia, 2005 [3] IEEE guide for the interpretation of gases generated in oil-immersed transformers, IEEE Standard C57.104-2008 [4] Guide for the sampling of gases and of oil-filled electrical equipment and for the analysis of free and dissolved gases. IEC Standard 6057, 2005 [5] Dornenburg E, Strittmatter W. Monitoring oil-cooled transformers by gas analysis. Brown Boveri Review 1974, 61:238-247 [6] Rogers RR, IEEE and IEC codes to interpret incipient faults in transformers using gas in oil analysis, IEEE Transactions on Electrical Insulation 1978, 13:349-354 [7] Mineral oil-impregnated electrical equipment in service-guide to the interpretation of dissolved and free gases analysis. IEC Standard 60599, 2007 [8] Duval M. A review of fault detectable by gas-in-oil analysis in transformers. IEEE Electrical Insulation Magazine 2002, 18:8 C-1533 www.ijariie.com 195