Online Publication Date: 19 January, 2012 Publisher: Asian Economic and Social Society

Similar documents
MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS

Nandkumar Wagh, D.M. Deshpande

Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI

Understanding Dissolved Gas Analysis (DGA) Techniques and Interpretations

A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION

A Revised Framework for the Transformer DGA Guide

Categorizing Faults via DGA. GE Grid Solutions M&D

Online DGA-monitoring of power transformers

Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks

Dissolved Gas Analysis - Past, Present and Future

DISSOLVED GAS ANALYSIS OF POWER TRANSFORMERS

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS

Draft Guide for the Interpretation of Gases in Oil Immersed Transformers

PROPOSAL FOR AN IMPROVEMENT IN TRANSFORMER DIAGNOSIS BY DGA USING EXPERT SYSTEM.

Since the beginning of production of oil for transformers

Research Article. Fault diagnosis of power transformer based on chemical properties of insulation oil

A New Approach for Transformer Incipient Fault Diagnosis Based on Dissolved Gas Analysis (DGA)

TRANSFORMER SERVICE. Dissolved gas analysis and oil condition testing

Condition Monitoring of Power Transformer Using Dissolved Gas Analysis of Mineral Oil: A Review

* Analysis of TCG ( Total Combustible Gas ) and 6 kinds of Gases * High Sensitivity for C 2

DGA Tools: Duval Triangles and Pentagons

Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers

Power Transformer Fault Diagnosis Based on Dissolved Gas Analysis Using a Fuzzy Neural Network Approach in a Real Data Base

FAULT DIAGNOSIS IN DEAERATOR USING FUZZY LOGIC

EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS

Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers

Improved Monitoring of Dissolved Transformer Gases on the Basis of a Natural Internal Standard (NIS)

An Intelligent Fault Diagnosis Approach for Power Transformers Based on Support Vector Machines. Hao Xu

Mathieu Guertin. Morgan Schaffer Inc. Canada. Director Europe, Russia and Africa. A cost effective strategy for smart grid technology adoption

A Novel Gear-shifting Strategy Used on Smart Bicycles

TRANSFORMER RELIABILITY AND DISSOLVED-GAS ANALYSIS. Delta-X Research Inc, Victoria BC, and 2 IREQ, Varennes QC CANADA

Dynamic Behaviour of Fault Gases and Online Gas Sensors. Germany

OPTIMIZATION OF SINGLE STAGE AXIAL FLOW COMPRESSOR FOR DIFFERENT ROTATIONAL SPEED USING CFD

IEEE Guide for the Interpretation of Gases Generated in Oil-Immersed Transformers

Wind turbine Varying blade length with wind speed

Analysis of Dissolved Gas in transformer oil by conventional Techniques and Artificial Intelligence approach-a Review.

APPLICATION NOTE. Fast Analysis of Coal Mine Gas Using the INFICON 3000 Micro GC ABSTRACT

Software Reliability 1

CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO Walnut Lake Rd th Street Houston TX Garner, IA 50438

Application of Bayesian Networks to Shopping Assistance

Session Number: 3 High Voltage Power Transformer Dissolved Gas Analysis, Measurement and Interpretation Techniques

Fitness for Service Assessment of Ageing Pressure Vessel Experiencing External Corrosion: A Case Study

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12

Reliability of Safety-Critical Systems Chapter 3. Failures and Failure Analysis

Measuring Heterogeneous Traffic Density

Fuzzy modeling and identification of intelligent control for refrigeration compressor

Analysis of Pressure Rise During Internal Arc Faults in Switchgear

Diagnostics of HV bushings through oil sampling and analysis. Experience with GSU transformers

Implementation of Safety Instrumented Systems using Fuzzy Risk Graph Method

Managing on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution power transformers

" High Voltage Switch Yards & How Safe are these really" <Peter Rhodes> <Principal and High Voltage Solution. Com Ltd>

Novel empirical correlations for estimation of bubble point pressure, saturated viscosity and gas solubility of crude oils

C Dissolved Gas Analysis Of Load Tap Changers. Working Group

MIL-STD-883G METHOD

LOW PRESSURE EFFUSION OF GASES adapted by Luke Hanley and Mike Trenary

ENVIRONMENTAL AND POLLUTANTS GAS ANALYZERS

Ball Beating Lubrication in Refrigetation Compressors

Analysis of hazard to operator during design process of safe ship power plant

Safety Analysis Methodology in Marine Salvage System Design

Fatigue Life Evaluation of Cross Tubes of Helicopter Skid Landing Gear System

You Just Experienced an Electrical Failure, What Should You Do Next? By Don Genutis Hampton Tedder Technical Services

International Journal of Technical Research and Applications e-issn: , Volume 4, Issue 3 (May-June, 2016), PP.

Temperature Influence on the Flammability Limits of Heat Treating Atmospheres

INTERNATIONAL STANDARD

MINUTES OF MEETING BUSHING SUBCOMMITTEE OF THE IEEE/PES TRANSFORMER COMMITTEE MINNEAPLOS, MN OCT 17, 2007

Internal Arc Simulation in MV/LV Substations. Charles BESNARD 8 11 June 2009

To Enhance the Engineering Properties of Clay Bricks with use of Fly Ash

BASIC PHYSICS APPLIED TO ANAESTHESIOLOGY

Review of oxygen deficiency requirements for graham s ratio

LINEAR TRANSFORMATION APPLIED TO THE CALIBRATION OF ANALYTES IN VARIOUS MATRICES USING A TOTAL HYDROCARBON (THC) ANALYZER

Dissolved Oxygen Guide

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV

Calibration Requirements for Direct Reading Confined Space Gas Detectors

ASSESSING THE RELIABILITY OF FAIL-SAFE STRUCTURES INTRODUCTION

Results of mathematical modelling the kinetics of gaseous exchange through small channels in micro dischargers

Detection of Proportion of Different Gas Components Present in Manhole Gas Mixture Using Backpropagation Neural Network

ISO INTERNATIONAL STANDARD

Hydrogen Cooling System

Figure Vapor-liquid equilibrium for a binary mixture. The dashed lines show the equilibrium compositions.

COAL MINES TECHNICAL SERVICES, GAS DETECTION RELATED SERVICES FOR MINES RESCUE

Gait Recognition with Fuzzy Classification Using Shoulder Body Joint

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles

Optimization of Separator Train in Oil Industry

Investigations into the identification and control of outburst risk in Australian underground coal mines

CP Chapter 13/14 Notes The Property of Gases Kinetic Molecular Theory

Applications Note: Use of "pentane equivalent" calibration gas mixtures

Behavior of Gases. Gases are mostly The molecules in a gas are separate, very small and very

Technical Manual. Sensepoint XCD Gas Detector

Under pressure pushing down

Application of the probabilistic-fuzzy method of assessing the risk of a ship manoeuvre in a restricted area

Gas volume and pressure are indirectly proportional.

Discovery HP-TGA 75/750. Site Preparation Guide

Advanced Test Equipment Rentals ATEC (2832) OMS 600

Chemistry HP Unit 6 Gases. Learning Targets (Your exam at the end of Unit 6 will assess the following:) 6. Gases

UNIT 10 - GASES. Notes & Worksheets - Honors

Electrochemical Carbon Monoxide Gas Sensor (Model:ME3-CO) Manual. Version 1.2 Valid from May 1 st 2014

Applied Technology and Best Practices in CEE. Conference

Standard Operating Procedure for H 2 S and SO 2 Converter

u = Open Access Reliability Analysis and Optimization of the Ship Ballast Water System Tang Ming 1, Zhu Fa-xin 2,* and Li Yu-le 2 " ) x # m," > 0

UNIVERSITY OF WATERLOO

Transcription:

Online Publication Date: 19 January, 2012 Publisher: Asian Economic and Social Society Prediction of Faults using Hydrocarbon Gases Data of Mineral Oil Immersed Power Transformers using Computer Intelligence Indra Getzy David (Department of Electrical Engineering, Govt. College of Engineering Tirunelveli, South India) M.Rajaram (University of Technology, Tirunelveli, South India) Citation: Indra Getzy David, M.Rajaram (2011): Prediction of Faults using Hydrocarbon Gases Data of Mineral Oil Immersed Power Transformers using Computer Intelligence Journal of Asian Scientific Research, Vol.2, No.1,pp.6-13.

Journal of Asian Scientific Research, Vol.2, No.1, pp.6-13 Prediction of Faults using Hydrocarbon Gases Data of Mineral Oil Immersed Power Transformers using Computer Intelligence Abstract Author (s) Indra Getzy David Department of Electrical Engineering, Govt. College of Engineering Tirunelveli, South India E-mail: getzy_wilson@yahoo.co.in This work proposes the separation of Faults diagnosed from Hydrocarbon Gas Data Collected from Dissolved Gas Analysis of Power Transformers over a period of a Decade in the area of Tirunelveli District in South India. The condition of Power Transformers is diagnosed using Fuzzy Set Theory. (FST) Simulations are compared with conventional methods. The computational Efficiency,Reliability and Success are evaluated and compared. FST is found to be more reliable,efficient and its success rate is also high. M. Rajaram University of Technology, Tirunelveli, South India. E-mail: rajaramgct@rediffmail.com Key words: Hydrocarbon Gases, DGA, MATLAB Simulink, Roger Fuzzy System Introduction Dissolved Gas Analysis has been used extensively for more than 40 years. It is a very efficient tool for the early diagnosis of fault assurance and increases the opportunity for precautionary measure. Most of the Electrical facilities in South India were commissioned in the late 1950s.FIG.1.shows the Distribution Growth since 1957 in TamilNadu[website of TNEB].In certain Substations and Distribution areas, the Electrical Switch Gear and Systems are more than 50 years of age. Depending upon the usage of the Equipment and Environmental conditions, they may be at the nearer end of their useful lives. Transformers are some of the most efficient Electrical Machines with some large units able to transfer 99.75% of their input power to their output. In larger Transformers part of the problem is removal of heat. Mineral oils are used for insulation and the windings immersed in this oil transfer heat to the oil thereby getting cooled. The oils are the mixture of many different Hydrocarbon Molecules which decompose under high Thermal and Electrical Stress within the transformer during the period of service.the critical changes are the breaking of Carbon- Hydrogen and Carbon-Carbon bonds as a result of which different gases are formed due to the presence of individual Hydrocarbon and the distribution of Energy and the Temperature in the neighbourhood of the fault. The causes of fault gases can be divided into three categories [Joseph B.DiGiorgio]. b)pyrolysis or Thermal Heating c)arcing These three categories differ mainly in the intensity of energy that is dissipated per unit time per unit volume by the fault. The most severe intensity of energy dissipation occurs at Arcing, less with Heating and least with Corona. The fault gases that can be found in a unit are Hydrocarbons like HydrogenH 2, Methane CH 4, Ethane C 2 H 6, Ethylene C 2 H 4, Acetylene C 2 H 2 and carbon oxides such as CO,CO 2 in addition to nofault gases like N 2 and O 2.The majority of gases that are found indicative of faults are also those that are more soluble in Oil. At a pressure of 760 mm Hg and 25 o C temperature, the solubility of gases in Transformer oil is found to be as shown in Table 1. Table 1. Solubility Of Gases H 2 7 % by volume N 2 8.6 % by volume CO 9.0 % by volume O 2 16 % by volume CH 4 30 % by volume CO 2 120 % by volume C 2 H 6 280 % by volume C 2 H 4 280 % by volume C 2 H 2 400 % by volume a)corona or Partial Discharge 6

Prediction of Faults using Hydrocarbon... analysis using simulink in MATLAB is the Rogers Ratio Method[R.R.Rogers(1978)]. The total volume of evolved gas is an indicator of the magnitude of incipient faults.to determine the volume, in gallons, of Total Dissolved Gases Combustible in insulating oil (TDGCv) the following Equation is used.[ IEEE standards C57.104 TM-(2008)]. Fig.1.Distribution Growth Since 1957 Over a temperature range 0 to 80 degree Centigrade some gases increase in solubility upto 79 % while others decrease their solubility up to 66 %.[Wan, Yat How and Marzuki Khalid (1999).].By extracting the dissolved gases in the oil, they are separated,identified and quantitatively determined by DGA method.eventhough the data from DGA is found to be inconsistent,since it detects the gases in the oil phase giving the earliest possible detection of an incipient fault, the DGA technique is a very efficient tool. Thermal Faults The decomposition of mineral oil (from 150 o C to 500 o C) produces relatively large quantities of the low molecular weight gases, such as H 2,CH 4 and trace quantities of the higher molecular weight gases Ethylene (C 2 H 4 ) and Ethane(C 2 H 6 ).As the fault temperature in mineral oil increases to modest temperatures, the Hydrogen concentration exceeds that of Methane,but now the temperatures are accompanied by significant quantities of higher molecular weight gases -First Ethane and then Ethylene.At the upper of the Thermal Fault Range, increasing quantities Hydrogen and Ethylene and traces of Acetylene (C 2 H 2 ) may be produced.[ieee standards C57.104 TM-(2008)]. The presence of Acetylene suggests a high temperature fault,perhaps an arc has occurred in the oil in a Transformer, the presence of Methane suggests that if a fault has occurred- it is a lower energy electrical or thermal fault. Electrical Faults a)low Intensity Discharges: Produce mainly Hydrogen with decreasing quantities of Methane and trace quantities of Acetylene.As the intensity of discharge increases,the Acetylene, and Ethylene concentrations rise significantly. b)high Intensity Arcing: As the intensity of Electrical Discharge reaches Arcing or continuing Discharge proportions that produce temperatures from 700 o C to 1800 o C, the quantity of Acetylene becomes pronounced. Probability of Transformer Failure In this work Evaluation of possible types of faults is carried out by analysis of separate combustible HydroCarbon Gases. The method used for the TDGCv=FG(V)/1000000;Where FG (Fault Gases) is the sum of H 2, CH 4, C 2 H 6, C 2 H 4, C 2 H 2 and C [micro litres/litre] V is the volume of oil in transformer [litres (gallons)] TDCGv is the total dissolved combustible gas volume [litres (gallons)] This straight forward method is useful for completely oil-filled (conservator type) transformers with conditions that produce small quantities of fault gas. These conditions warrant continuous monitoring; this fault case volume method continues to be useful as fault conditions enlarge, with the added advantage that it permits continuous monitoring of insulation deterioration in spite of any oil handling activity that includes degasification. Diagnosis The diagnostic theories based upon the thermal degradation principles employ an array of ratios of certain key combustible gasses as the fault type indicators. These five ratios are [Dr.Joseph B.DiGiorgio and, Wan, Yat How and Marzuki Khalid (1999)] Ratio 1 (R1) = CH 4 /H 2 Ratio 2 (R2) = C 2 H 2 /C 2 H 4 Ratio 3 (R3) = C 2 H 2 /CH 4 Ratio 4 (R4) = C 2 H 6 /C 2 H 2 Ratio 5 (R5) = C 2 H 4 /C 2 H 6 The Rogers method utilizes ratios 1,2 and 5. The Roger s method does not depend on specific gas concentration to exist in the transformer for the diagnosis to be valid but the Doernenburg [IEEE standards C57.104 TM- (2008)]ratio utilizes ratios 1,2,3 and 4and requires significant levels of gases to be present in order for the diagnosis to be valid.. However Rogers suggests that the method be used only when the normal limits of individual gases(refer Table 2) have been exceeded. A four level criterion has been developed to classify risks to transform as when there is no previous dissolved gas history, for continued operation at various combustible gas levels. The criterion uses both concentrations for separate 7

Journal of Asian Scientific Research, Vol.2, No.1, pp.6-13 gases and the total concentration of all combustible gases.[ IEEE standards C57.104 TM-(2008)]. Table-2 Limit Concentrations Of Dissolved Gas Key gas Concentrations L (Micro litres/litre(ppm)) Hydrogen(H 2 ) 100 Methane(CH 4 ) 120 Carbon Monoxide(CO) 350 Acetylene(C 2 H 2 ) 1 Ethylene(C 2 H 4 ) 50 Ethane(C 2 H 6 ) 65 Condition 1 : TDCG below this level indicates the transformer is operating satisfactorily. Any individual combustible gas exceeding specified levels should prompt additional investigation. Condition 2 : TDCG within this range indicates greater than normal combustible gas level. Any individual combustible gas exceeding specified levels should prompt additional investigation. Action should be taken to establish a trend.faults may be present. Condition 3 : TDCG within this range indicates a high level of decomposition Any individual combustible gas exceeding specified levels should prompt additional investigation.immediate action should be taken to establish a trend.faults are probably present. Condition 4 : TDCG exceeding this value indicates excessive decomposition.continued operation could result in failure of the transformer. Proceed immediately with caution. The Dissolved key gas concentration limits (ppm) for each condition is shown in Table 3. Evaluation of possible type of fault by the Rogers ratio method: The Rogers ratio method uses only three ratios(r1,r2,r5).this method is also based on the thermal degradation principle. Table 4 gives the values for the three key gas ratios corresponding to suggested diagnoses. These ratios according to Rogers are applicable to both gases taken from the gas space and gases extracted from the oil.the fault types given in Table 4have been chosen from the fault types originally suggested by Rogers. Fuzzy Rogers Ratio System Fuzzy Rogers Ratio system uses the 5 fault gases which are Acetylene, Ethylene, Methane, Hydrogen and Ethane to determine 9 transformer conditions. Therefore, the structure for the Fuzzy Rogers Ratio system can be illustrated as in Figure 3 where the ratios are identified as the input parameters while the 9 interpretation results based on the different combination of ratios are identified as the output parameter as listed below. The test results of DGA for data collected from Electricity Board are tabulated below for a few random samples. The remarks predicts suspected occurrence of Thermal Fault above 100 0 C due to Overheating. Out of the 551 samples collected from various Transformers located at different substations 329 samples are no fault data and 137 are recommended resampling by the TNEB Test Lab. These 137 samples were tested with Rogers Ratio Simulink and Fuzzy Rogers Ratio System and the results are compared. Table 3- Dissolved Key Gas Concentrations Status Dissolved Key gas concentration limits [µl/l(ppm)] Hydrogen ( H 2 ) Methane (CH 4 ) Acetylene (C 2 H 2 ) Ethylene (C 2 H 4 ) Ethane (C 2 H 6 ) Carbon Monoxide ( CO ) Carbon Dioxide (CO 2 ) TDCG a Condition1 100 120 1 50 65 350 2500 720 Condition2 101-700 121-400 2-9 51-100 66-100 351-570 2500-4000 721-120 Condition3 701-1800 401-1000 10-35 101-200 101-150 571-1400 4001-10000 1921-4630 Condition4 >1800 >1000 >35 >200 >150 >1400 >10000 >4630 a TDCG value does not include CO 2,which is not a combustible gas. 8

Prediction of Faults using Hydrocarbon... Table 4-Rogers Ratio For Key Gases Case R2 C2H2/C2H4 R1 CH4/H2 R5 C2H4/C2H6 Suggested fault diagnosis 0 <0.1 >0.1 to <1.0 <1.0 Unit normal 1 2 <0.1 <0.1 <1.0 Low energy density arcing-pd 0.1 to 3.0 0.1 to 1.0 >3.0 Arcing-High energy discharge 3 <0.1 >0.1 to <1.0 1.0 to 3.0 Low temperature thermal 4 <0.1 >1.0 1.0 to 3.0 Thermal<700deg 5 <0.1 >1.0 >3.0 Thermal>700deg Rogers Simulink Model in MATLAB is shown in Fig.2. Fault Fault Type Ranges of gas ratio code C 2 H 2 /C 2 H 4 CH 4 /H 2 C 2 H 4 /C 2 H 6 0 No fault <0.1 0.1-1.0 <1.0 1 Low energy partial <0.1 <0.1 <1.0 discharges 2 High energy partial 0.1-3 <0.1 <1.0 discharges 3 Low energy discharges >0.1 0.1-1.0 >1.0 4 High energy discharges 0.1-3 0.1-1.0 >3.0 5 Low temperature fault <0.1 0.1-1.0 1.0-3.0 150 o C 6 Low temperature fault 150- <0.1 >0.1 <1.0 300 o C 7 Medium temperature fault <0.1 >0.1 1.0-3.0 300-700 o C 8 High temperature fault>700 o C <0.1 >0.1 >3.0 The Ratios are fuzzified[zimmerman,h.j. (1986) and R.Naresh,Veena Sharma Vashisth, and Manisha (2008]using the following Linguistic variables and membership functions as shown below. Methane Ethane 9

Journal of Asian Scientific Research, Vol.2, No.1, pp.6-13 Ethylene Acetylene Hydrogen FIG.4 MEMBERSHIP FUNCTION OF ATTRIBUTES Input variable R2=C 2 H 2 /C 2 H 4 Input variable R1=CH 4 /H 2 Input variable R5=C 2 H 4 /C 2 H 6 OUTPUT VARIABLES= OUTPUT FIG.5 INPUT AND OUTPUT VARIABLES 10

Prediction of Faults using Hydrocarbon... FIG.6 SAMPLE TEST OUTPUT FOR R1=1.16; R2=1.06; R5=1.77 TABLE-5 HYDROCARBON GASES FROM DGA DATA-Date of Commissioning 08.11.2005 HC Values in ppm 16 MVA,110/11kV H 2 CH 4 C 2 H 6 C 2 H 4 C 2 H 2 CO 2 CO Remarks By Lab Expert Sample I-03.01.2006 46 168 37 286 2 840 - Sample II-17.01.2006 64 224 49 376 2 1164 - Thermal Fault of above 100 0 C Sample III-06.02.2006 38 219 52 377 1 1340 - Due to Overheating Sample IV-16.03.2006 29 189 75 353 2 1454 - Sample V-11.04.2008 14 67 42 111 0 1223 - Resample Sample VI-07.08.2008 22 94 43 138 3 1823 - SampleVII-27.04.2009 25 96 50 158 6 1964 - Satisfactory IV.RESULTS TABLE-6 RESULTS Conventional Rogers Ratio Simulink Model Samples taken: 137 Consistent : 83 Inconsistent : 54 Success : 64 Failure : 19 % of Success : 80 Efficiency : 77 Fuzzy Rogers Ratio System Samples taken: 137 Consistent : 95 Inconsistent : 42 Success : 87 Failure : 08 % of Success : 91 Efficiency : 92 11

Journal of Asian Scientific Research, Vol.2, No.1, pp.6-13 References [1]Dr.Joseph B.DiGiorgio, Dissolved Gas Analysisof Mineral OilInsulating Fluids [2] Wan, Yat How and Marzuki Khalid (1999). Transformer Fault Diagnosis Using Fuzzy Logic Interpretations. Conference Proceeding of InstrumentAsia99 (CIA99) Technical Symposium. Singapore. [3]R.R.Rogers, IEEE and Iec Codes to Interpret Faults in Transformers, using Gas in oil Analysis,IEEE Trans.Electr.Insul,Vol EI-13 No 5,October 1978. [4]IEEE standards C57.104 TM-2008 IEEE Guide for the Interpretation of Gases generated in Oil Immersed Transformers,IEEE power and Energy Society Revision of Std C57,104-1991. [5]Zimmerman,H.J. Fuzzy Sets,Decision making and Expert Systems,1986. Boston:Kluver Academic Publishers. [6]R.Naresh,Veena Sharma Vashisth, and Manisha An Integrated Neural Fuzzy Approach for Fault Diagnosis of Transformers,IEEETrans on Power Delivery,vol.23,No.4,OCTOBER 2008. [7]Website of Tamil Nadu Electricity Board. Fuzzy Inference Fuzzification Defuzzification R1 R2 R5 0 1 2 3 4 5 6 7 8 Rogers Ratio Code Transformer Faults FIG.3 FUZZY ROGERS RATIO SYSTEM 12

Prediction of Faults using Hydrocarbon... FIG.2. ROGERS SIMULINK MODEL IN MATLAB Indra Getzy David received her B.E.[EEE] and M. E. [CSE]degrees from Govt. College of Technology Coimbatore, then affiliated to the University of Madras and Bharathiar University,South India in 1982 and 1990, respectively. She worked in the Public Works Department as an Assistant Engineer [electrical] for a period of an year where she was doing estimation and execution of the Electrical Works for the Bharathiar University Buildings Division in Coimbatore, TamilNadu, SouthIndia. Presently she is an Associate Professor in the Department of Electrical Engineering, Govt. College of Engineering Tirunelveli, South India. To her credit she has nearly three decades of Teaching Experience. She is interested in the areas of Computer Graphics, DataMining and Power Apparatus Protection. She is currently assisting one Government of India Project in her Department. Dr. M.Rajaram is the Vice Chancellor of Anna University of Technology, Tirunelveli, South India. He has more than 30years of experience in teaching and more than20 years of experience in research. His current area of research includes power Systems, Control Systems, Computer Communication and Software Testing.. He has published more than fifty papers in referred international journals. He has also presented more than one hundred and fifty research articles in national and international conferences. He has written few books for the benefit of the UG Students under Anna University Curriculum. He is currently dealing with few projects sponsored by government of India. He has produced 13 Ph.D Scholars and six researchers are on nearing completion under his guidance. 13