Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel

Similar documents
Installation, Operation and Maintenance Instructions Buffer Vessel OM006

Installation, Operation and Maintenance Instructions for Direct Hot Water Storage Vessels

Installation, Operation and Maintenance Instructions for Pacific PA Non-Storage Heat Exchanger

Installation, Operation and Maintenance Instructions for Chemical Dosing Pots

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

SCA Series Inverted Bucket Steam Traps

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Installation, Operation and Maintenance Manual for Back Pressure Regulator

Eaton Filtration, LLC

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

TSS21 Sealed Thermostatic Steam Tracer Trap

Vertical Bladder Tanks

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

Model MTB-ASME Vertical Bladder Tanks

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

TITAN FLOW CONTROL, INC.

Engineering Data Sheet

HIGH RATE BASKET STRAINER

FV Flash Vessel Installation and Maintenance Instructions

Horizontal Bladder Tanks

Model MTB-ASME Vertical Bladder Tanks

Model MTB-ASME Horizontal Bladder Tanks

Eaton Filtration, LLC

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A

Manual Actuated Boiler Blowdown Valves

GESTRA Steam Systems AK 45. Installation Instructions Condensate Drain Valve AK 45

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

Cast iron swing check valve. BS EN 12334:2001 PN16

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

UNVENTED HOT WATER SYSTEMS HAVE BECOME EXTREMELY POPULAR FOR BUILDING APPLICATIONS. WITH ALL THE MANDATORY

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

AVM7 Stainless Steel Thermostatic Air Vent

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

KTM 50 (DN ) Installation, maintenance and operating instructions

AVC32 Carbon Steel Air Vent for Steam Systems

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

TP1 and TP2 Temporary Cone Shaped Strainers

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

1. Preface Important Safety Notes Brief Product Information Product Working Principle Installation Guidelines...

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

PC10HP Pipeline Connector (ASME 600)

MFP14-PPU (Vented) Automatic Packaged Pump Units

INSTALLATION, MAINTENANCE & OPERATING INSTRUCTIONS 2-4 REDUCED PORT/ FULL PORT (5700/6700) ANSI CLASS 150/300/600/900/1500/2500 TRUNNION BALL VALVES

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

Expansion Vessels for Potable Installations

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

WHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual

ENERGY BLADE 3K4. Energy Blade Installation Instructions

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS. This work covers part of outcome 2 of the Edexcel standard module:

GUIDELINES. Systems. Pressure. Guidelines Acceptance of equipment, establishment of safe operating limits and fitness for service

STD Spray Type Desuperheater

System Pressure Manager Standard & System Pressure Manager Plus

Pilot Operated Pressure Reducing Valve

Installation / Operation / Maintenance Manual KLINGER Reflex Level Gauge Type R 25

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

Steam Trap BK 15 (DN40, DN 50) Original Installation Instructions English

Installation and commissioning instructions 255 series and 256 series

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

Easy-Pro Installation & Operations Guide

CA10S, CA14 and CA14S Air and Gas Traps

DECLARATION OF INCORPORATION

MODEL 200 KNIFE GATE VALVES INSTALLATION & MAINTENANCE MANUAL

Materials : Stainless steel ASTM A351 CF8M

Airfix D-E-B Installation and operating instructions

CVS10 Sanitary Check Valves

DF1 and DF2 Diffusers

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

WORCESTER GREENSTORE. Indirect Unvented Cylinder with Solar Coil FOR USE WITH WORCESTER GREENSTORE SYSTEM HEATPUMP ONLY GB/IE

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

SRV66 Sanitary Pressure Reducing Valve

Spilt body Flange ball valve. TC-205MFF-PN1640 User Manual English Version. Document No: TC-205MFF-PN1640.Ur-manual. Date: 2007/04/2617. Version: 1.

FloWash. Industrial Filter Cart

Thermocirc Installation and Maintenance Instructions

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

Instructions for SILEX 1C Mixed bed cartridge filter

Atmospheric relief valve type 1100 Installation and maintenance instructions

30T A/Manual Hydraulic Shop Press

Size : Ends : Min Temperature : Max Temperature : Materials : Cast iron body

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

DESIGN AND PRE - INSTALLATION INFORMATION

OPERATION AND MAINTENANCE MANUAL

Installation, operation & maintenance manual - original version

INSTALLATION, OPERATING & MAINTENANCE MANUAL WATER DRAIN VALVE

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

LAKOS Waterworks. PWC Series Sand Separators. Installation & Operation Manual LS-829 (10/12)

Installation, commissioning and servicing instructions

PV4 and PV6 Piston Valves

Transcription:

OM006 Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel The operating and maintenance instructions contained within this package are for standard mild steel buffer vessels (suitable for chilled and heating water). Please note that an electronic version of these instructions is available from our website and also on a CD. Please contact our sales office for further information. Rev Date By Details A 20/11/12 SR PED note Revision Details

Contents 1.0 Standard Unit Information and Description 3 2.0 PED Information. 4 3.0 Installation 5 4.0 Commissioning and Operation. 6 5.0 Maintenance 7 6.0 Recommended Spares.. 8 [T:\gms\Word\GMSO&M\Word Format\OM006.doc] Page 2

1.0 Standard Unit Information & Description The standard range of chilled water buffer vessels range from 230 litres to 9000 litres. These are mostly used in heating and chilled water systems. Other applications may also arise with different water temperatures and materials of construction. This manual covers mild steel vessels. Standard Material Options Schedule Shell Mild Steel (Other materials on request) Design Data Maximum Working Pressure Hydraulic Test Pressure Design Code Shell Side Refer to Vessel Nameplate Refer to Vessel Nameplate Refer to Vessel Nameplate Please refer to our brochure for standard connection and dimensional data. [T:\gms\Word\GMSO&M\Word Format\OM006.doc] Page 3

2.0 PED Information The standard range of buffer vessels are designed in accordance with the requirements of the Pressure Equipment Directive 97/23/EC. Units classed as SEP in the PED category are not supplied with a CE mark. Units in category I & above are CE marked and appropriate markings and certification is supplied with each unit. It is the responsibility of the user and/or installer to ensure that the unit is installed and operated safely, and in accordance with the instructions supplied within this manual. [T:\gms\Word\GMSO&M\Word Format\OM006.doc] Page 4

3.0 Installation Lifting & Handling: Use lifting eyes where fitted. Do not lift a vessel using the insulation (if fitted). Straps may crush the insulation. The shell of the vessel may be made of relatively light gauge metal and care should be exercised when handling and moving the unit not to damage the shell. Do not lift the vessel using chains directly in contact with the shell. Do not allow operatives to stand on the vessel Siting: Unless specifically ordered for outside siting the vessel must be sited indoors. Foundations must be firm and level to prevent settling, pipe strain or distortion of the calorifier. Unless specifically ordered differently, the vessel should be installed in a level position. For vessels with inspection openings ensure enough room exists to gain access to the opening. Protective covers/plugs may be fitted to connections to protect them in transit. These must be removed prior to use. If a connection is not required seal it appropriately. Check for and remove any foreign material which may have got into the vessel. Pipe-work connected to the calorifier should be supported to prevent loads being transmitted to the vessel. Provide for thermal expansion with bends and expansion joints. To avoid corrosion do not use copper pipework with galvanised steel vessel or vice-versa. Fit isolation valves prior to vessel connections to facilitate servicing (NOT TO THE VENT). For flanged connections tighten bolts in a diametrically opposite sequence to load the flanges evenly onto the gasket. For screwed connections use a thread sealant approved for use with potable water by the local water authority. The vent must not be blocked so, if the vessel may need to be isolated from the vent, fit a 3-way vent valve. Ensure adequate venting for air removal during filling and operation ("sealed" systems should have an auto-air-vent and a manual air vent valve for this). Pressure relief valves should have their outlets piped away to a safe disposal point, preferably via an air-break and tun-dish so that discharge is unrestricted and easily visible. Water expansion must be accommodated by separate expansion vessel on the cold feed side (on sealed systems) or via the vent pipe on vented systems. Allowing expanded water back into the cold feed tank on vented systems is not recommended as the resultant warm water will encourage bacterial growth. [T:\gms\Word\GMSO&M\Word Format\OM006.doc] Page 5

4.0 Commissioning and Operation Do not operate the equipment at pressures or temperatures in excess of those specified on the nameplate of the vessel marking. Do not subject the equipment to conditions of vacuum or partial vacuum. For example partial vacuum can be caused if the cold feed or the vent are restricted during draw off or drain down. It is assumed here that the secondary pipework is already full of water. For sealed systems it is assumed here that any cold water booster set and/or pressure reducing valve is already commissioned and set to the correct pressure. Start with primary, secondary flow, return and cold feed valves closed and secondary recirculation pumps off. Close the drain valve. For sealed systems ensure auto-air vent is operational For sealed systems open manual vent valves For sealed systems open expansion vessel isolation valve Open the fill connection valve and slowly fill the vessel with cold water. For sealed systems when water reaches the manual vent valve, close it. If the cylinder is open vented and shares a vent with other cylinders, connect it to the common vent using the 3-way valve Carefully open the flow and return valves Check that all gaskets are effective when the unit is operating - some bolt tightening may be necessary after the unit has been first heated and subsequently from time to time. Following installation and commissioning it is advisable to remove, clean and re-assemble any strainers. All fluids must be drained when the unit is out of operation to prevent freezing or possible corrosion. [T:\gms\Word\GMSO&M\Word Format\OM006.doc] Page 6

5.0 Maintenance Annual maintenance should include cleaning debris from the base of the vessel to comply with guidelines on prevention of legionella bacteria proliferation. Also the site insurers may require annual inspection of the internal shell condition. To drain the cylinder down Obtain a complete set of replacement gaskets from GMS Thermal Products Ltd. It is assumed here that all isolation valves (except drain) are open at the start. Switch off any secondary system pumps and isolate connections to vessel. For sealed systems reduce the residual vessel pressure by manually operating the safety valve - some water will come out For sealed systems open the manual vent valve to allow air in during drain-down If the vessel is open vented and shares a vent with other vessel, isolate it from the common vent using the 3-way valve (it will now vent to atmosphere). Pipe the drain to a drain point and open the drain valve. The vessel internal condition can be inspected by removing the inspection cover to allow visual examination Re-fit new gaskets and re-fill the calorifier according to the commissioning instructions above. [T:\gms\Word\GMSO&M\Word Format\OM006.doc] Page 7

6.0 Recommended Spares Please contact our sales department for recommended spares prices and availability. The recommended quantities given are per unit supplied. Description Part Ref. 230-550 Litres 600-2000 Litres 2000-9000 Litres All Copper Lined Inspection Gasket TBA 1 Inspection Gasket TBA 1 Inspection Gasket TBA 1 1 [T:\gms\Word\GMSO&M\Word Format\OM006.doc] Page 8

OM006 Calorifiers Heat Exchangers Pressurisation Units Sales Tel: 01457 835700 Sales Fax: 01457 832700 E-mail: sales@gmsthermal.co.uk Riverside Works, Egmont Street, Mossley [T:\gms\Word\GMSO&M\Word Format\OM006.doc] Page 9 Ashton-Under-Lyne, OL5 9NE