Installation, use and maintenance instructions. Gas burner (5)

Similar documents
Forced draught gas burner

Forced draught gas burner

Dual fuel Gas-Oil/Gas burner

STG

TANDEM MODULATOR FOR OUTLET GAS FLOW: STEPPED (836 TANDEM) - CONTINUOUS (837 TANDEM) SERVO-CONTROLLED PRESSURE REGULATOR

RS 28/1-38/1 On - Off Operation

RS 70/M - 100/M - 130/M Low-High-Low or Modulating Operation

Installation- and maintenance instruction BG200-2

Installation- and maintenance instruction BG400LN

BG 300M

Forced draught gas burners Quemadores de gas Queimadores a gás

Installation & Maintenance Manual

GM Series Dual-Block Multi-Function Gas Control Valves

SIT Group 710 MINISIT MULTI-FUNCTIONAL GAS CONTROL THERMOELECTRIC FLAME SUPERVISION DEVICE PRESSURE REGULATOR TEMPERATURE CONTROL PIN 0085AQ0287

RS 45/M LN Low-High-Low or Modulating Operation

Forced draught natural gas/propane burner

24L OIL FREE AIR COMPRESSOR MODEL NO: TIGER 7/250 PART NO: OPERATION & MAINTENANCE INSTRUCTIONS LS10/13

INSTALLATION & MAINTENANCE MANUAL FOR RIVERSIDE HYDRONICS BG400 GAS BURNER 140,000 thru 1,400,000 Btu/h

Single stage operation forced draught natural gas/propane burner

GAS BURNERS. techniques for energy saving MODELS G A S T E C BLU P AB BLU P AB. Natural gas mbar LB 1045

Tightness controls TC 1 3 and TC 4

Dual Fuel Gas / Light Oil Burners

Operator: Save these instructions for future use!

SPECIFICATIONS ATTENTION

VR46.5V(A)/VR86.5V(A) SERIES

MULTIFUNCTIONAL CONTROL FOR GAS BURNING APPLIANCE

100L AIR COMPRESSOR MODEL NO: TIGER 16/1010 PART NO: OPERATION & MAINTENANCE INSTRUCTIONS LS01/13

Operator: Save these instructions for future use!

24L AIR COMPRESSOR MODEL NO: TIGER 11/250 PART NO: OPERATION & MAINTENANCE INSTRUCTIONS LS01/13

Forced draught gas burners Quemadores de gas Queimadores a gás

444C DUAL PERFORMANCE VALUE PACK

Automatic Valve Proving Control

Operator: Save these instructions for future use!

24L AIR COMPRESSOR OPERATION & MAINTENANCE INSTRUCTIONS MODEL NO: RANGER 7/240 PART NO: LS0913

400C & 450C DUAL PERFORMANCE VALUE PACKS

Providing sustainable energy solutions worldwide. Installation- and maintenance instruction STG 146

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

200 PSI COMPRESSORS - MODEL NUMBERS

100C Air Compressor Kit

AIR COMPRESSOR OPERATION & MAINTENANCE INSTRUCTIONS MODEL NO: CHAMP 3 PART NO: LS0115

Installation- and maintenance instruction BG450-2

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

Forced draught gas burners

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

Operator: Save these instructions for future use!

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

Operator: Save these instructions for future use!

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

36H SERIES Combination Gas Valve

VERTICAL AIR COMPRESSORS

Budget Range Operators Handbook

Operator: Save these instructions for future use!

IMPORTANT SAFETY INSTRUCTIONS

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO

Installation & Maintenance Manual

Propane Conversion Kit Instruction

Forced draught gas burners

Model PSI Compressor with 3-Gallon Air Tank 12VDC

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO

1. PARTS INTRODUCTION ELECTRICAL NOTES INSTALLATION 5/6. 5. START UP 6/7. 6. MAINTENANCE 7/8/9. 7. PRESSURE SWITCH ADJUSTMENTS 9/10.

INSTALLATION & MAINTENANCE MANUAL FOR PVI FIREPOWER BG600 GAS BURNER 1,200,000 thru 2,400,000 Btu/h

COMPRESSOR OPERATION & MAINTENANCE INSTRUCTIONS MODEL NO: WARRIOR 55 PART NO: (110V) , (230V) , LS0512

Operator: Save these instructions for future use!

Two stage operation forced draught natural gas/propane burner

Gas Check. Short testing time, with automatic start-up if no leakage was detected from previous operation.

24L AIR COMPRESSOR MODEL NO: TIGER 8/260 PART NO:

Installation, operating and maintenance Instructions for Seemag bypass level indicator

VERTICAL AIR COMPRESSORS

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

200L BELT DRIVEN AIR COMPRESSOR

Code AWC20HP Air Compressor

VK41../VK81.. GAS CONTROLS FOR COMBINED VALVE AND IGNITION SYSTEM SPECIFICATIONS APPLICATION DESCRIPTION INSTRUCTION SHEET

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

Installation, use and maintenance instructions. Gas Burners. RS 68/M LN - RS 120/M LN Low-High-Low or Modulating Operation

Forced draught gas burners

Dual fuel gas oil/gas burners

Safety. Operating instructions Excess air burner BIC..L DANGER. Contents WARNING CAUTION Elster GmbH Edition 06.17

QPL... Pressure Switches. Siemens Building Technologies HVAC Products

Instructions for High Altitude Conversion

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

50L BELT DRIVEN AIR COMPRESSOR

480C DUAL PERFORMANCE VALUE PACK

G92 Series BASOTROL Automatic Pilot Gas Valve

Inoxair. Repair Manual. Content. Edition: 12/2010. Subject to technical changes for reasons of the continous development.

Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage.

Installation- and maintenance instruction BG550/BG650

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

IMPORTANT SAFETY INSTRUCTIONS

VR400/VR800 SERIES. Honeywell CLASS A SERVO REGULATED COMBINATION VALVES APPLICATION DESCRIPTION INSTRUCTION SHEET

Model 130M Pneumatic Controller

DUCT BURNERS INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Flamco Flamco-Fill STA Flamco-Fill STM

INSTALLATION & OPERATING INSTRUCTIONS FOR THE DS300 BRAZING HEARTH FLAMEFAST (UK) LIMITED

ACCESSORY KIT INSTALLATION INSTRUCTIONS

AIR COMPRESSOR MANUAL INSTALLATION, OPERATION AND MAINTENANCE GUIDE

Gas Burners RS 190/M Low-High-Low or Modulating Operation

Operating Instructions

Propane Conversion Kit Instruction

Installation & Maintenance Manual

Propane Conversion Kit Instruction

Transcription:

Installation, use and maintenance instructions Gas burner MODEL GAS 4 TYPE 516 T80 291 (5)

TECHNICAL FEATURES Thermal output 180-470 kw 154.800-404.200 kcal/h Fuel Natural gas Pci 8-10 kwh/m 3 = 7000-8600 kcal/m 3 Minimum gas pressure Maximum gas pressure Electrical supply Motor Ignition transformer Absorbed electrical power For maximum output 9.8 mbar are needed measured at the coupling with nil pressure in the combustion chamber and gas with calorific value of 8600 kcal/m 3 150 mbar Three phase 380 V + 10% - 10% ~ 60Hz with neutral 1.5 A / 380 V Primary: 1.8A / 220V - Secondary: 1 x 8 kv - 30 ma 0.6 kw 1 Air shutter control 6 7 8 2 Air shutter lock-nut 3 Control box re-set button 5 4 Fair leads 4 5 Wiring terminal block 6 Re-set push-button of the motor overload relay 3 7 Air pressure switch 8 Gas pressure test-point 2 1 Fig. 1 S7513 DIMENSIONS Boiler front-plate drilling 160 410 Burner ø 150 187 * 320 610 160 292 165 397 Rp 1 1/2 165 M10 D1785 S7497 97 S7498 *Length available with special blast tube to be separately required. 1

EQUIPMENT Quantity Burner accessories 1 Flange 1 Gasket 8 Screws 1 Flange gasket FIXING TO THE BOILER 2 3 5 4 1 Separate the combustion head from the burner body by loosening the screws 1) and 2) and with drawing the group A) from the holding bars 3). Fix the group B) to the boiler front plate 4) using the gasket 5) provided as accessory. A B S7499 GAS SUPPLY 5 7 10 9 5 5 4 3 11 2 1 8 1 - Gas pipe line 7 - Gas shut off valve 2 - Cock valve 8 - Burner 3 - Filter 9 - Gas safety shut off valve 4 - Pressure stabilizer 10 - Gas leak control device 5 - Pressure test-point 11 - Isolator joint 6 - Minimal gas pressure switch 6 S7514 2

WORKING RANGE COMBUSTION CHAMBER PRESSURE - MAXIMUM OUTPUT (in compliance with DIN 4788) mbar D1786 kw Kcal/h MINIMUM GAS PRESSURE - OUTPUT Pressure: detected at the pressure test-point 7) (fig. 1) with nil mbar into the combustion chamber. Should the combustion chamber be pressurized, the pressure necessary will be that of the graph plus the pressurization value. Example: to obtain 350 kw it is necessary a gas pressure of 7 mbar and the combustion head set as indicated at page 7. If the combustion chamber is pressurized at 2 mbar, the pressure detected at the test-point 7) is: 7 + 2 = 9 mbar. If this value is too high, for very low gas pipework pressures, the gas gear 6) (page 7) could be more open. Do not decrease the pressure at the coupling under the values shown in the diagram. Output: the maximum value is obtainable with gas Pci 8600 kcal/m 3. CORRELATION BETWEEN GAS PRESSURE AND BURNER OUTPUT mbar D1787 kw Kcal/h 3

BURNER ELECTRICAL WIRING (carried out in the factory) Ignition transformer Ionisation probe Burner earth Air pressure switch Motor CONTROL BOX 509 SE/K S7516 Wiring terminal block (see page 5) 4

ELECTRICAL CONNECTIONS TO THE WIRING TERMINAL BLOCK (to be carried out by the installer) MB KEY: 6A 1mm 2 PE L1 L2 L3 3 ~ 60 Hz - 380 V M 3 ~ TS 6A N L 60 Hz - 220 V S LANDIS LDU II TL 1 2 1 2 V1 PG P P PC S7517 VS MB : Burner terminal strip. TS : Safety remote control system. TL : Limit control system. S : Remote lock signal. PG : Min. gas pressure switch. PC : Check pressure switch. V1 : Gas shut off valve. VS : Gas safety shut off valve. Notice - Leads minimal section 1 mm 2. - The electric wiring carried out by the installer must be in compliance with the rules in force in the Country. FIXING OF THE ELECTRICAL WIRES All the electrical wires, which are to be connected to the terminal block 5) (fig. 1) shall pass through the fair leads 4) (fig. 1) as for this scheme. 1 - Single phase supply : fair lead Pg 13.5 2 - Adjustment thermostat : fair lead Pg 13.5 3 - Safety thermostat : fair lead Pg 13.5 4 - Gas train : fair lead Pg 13.5, sheath ø 13 5 / 6 / 7 /8 - Pre-sheared holes S7505 Further prospective signals or controls can be connected to the burner wiring terminal board by removing the metal weldnuts from the pre-sheared holes and inserting a commun fair lead for the passage and the clamping of the leads. NOTES - Do not exchange the neutral wire with the phase (avoid the plug-pin connection). - Carry out a safe earth connection. - Check the stop of the burner, by opening the boiler thermostat and the burner lock-out, by disconnecting the lead from the flame probe. WARNING When closing the burner on its slide-bars, pull towards the outside the high voltage cable and the cable of the flame detection probe, till to little tension. 5

BURNER START-UP CYCLE Air-purge: loosen the screw placed on the minimal gas pressure switch mounted on the gas train. Screw Plug for pressure measure Pressure switch S7506 AIR PRESSURE SWITCH 7) (fig.1) The air pressure switch setting shall be carried out after having set all other adjustment of the burner and the air pressure switch shall be at its lowest set-point. When the burner is operating, increase the adjustment pressure by turning - slowly - clockwise the knob till reaching the burner lock-out. Thereafter, turn the knob anticlockwise for 1 mbar and repeat the burner start-up for checking the regularity: if lock-out intervenes turn the knob anticlockwise for 0.5 mbar. 1 10 mbar Adjustment knob S7507 Probe position Ignition electrode position 2-4 mm 0-1 mm S7508 CAUTION: do not turn the ionization probe, maintain the drawing position; should it be close to the ignition electrode, damage may occur to the control box amplifier. 6

COMBUSTION HEAD ADJUSTMENT Two separate adjustments have to be made: air and gas. These adjustments can be carried out when the burner is still open, during the installation (see page 2 - Fixing to the boiler). Air setting Loosen the two screws 1) and move the internal part of the combustion head 2) so that its rear edge 3) is coincident with the desired set-point on the plate 4). Tighten the screws 1). 1 8 6 5 2 Gas setting Loosen the screw 5), move the ring 6) so that the pointer 7) is coincident with the desired set-point 8). Tighten the screw 5). Attention: the set-point number is the same for air and gas setting and is given by the following diagram. 3 7 4 S7518 Example: the burner is installed on a boiler of 270 kw, assuming an efficiency of 90% the burner output should be 300 kw. From the diagram it can be seen that the air and gas settings for this rating should be no. 3. Kcal/h kw Burner output D1792 Set-point number = for air and gas 7

COMBUSTION CHECKS CO2 It is advisable to not exceed 10% of CO 2 (gas with calorific value of 8600 kcal/m 3 ), in order to avoid the risk that small changes of the adjustments due, for instance, at draught variation, may cause combustion with insufficient air and consequently formation of CO. CO For safety reason the value of 0.1% (one thousand p.p.m.) must not be exceeded. IONIZATION CURRENT The minimum current necessary for the control box operation is 3 µa. The burner normally supplies a higher current value, so that no check is needed. However, if a measurement of the ionization current is required, it is necessary to disconnect the probe lead and insert a d.c. microamperometer. + - Lead S7511 Probe MOTOR LOCK-OUT This is caused by the thermal protector relay, in case of overloading, or by the lacking of the phase. To clear, pushdown the appropriate knob, after having removed the protective cover BURNER START-UP Thermostat Motor Ignition transf. Start valve Adjust. valve Lock-out Normal Lock-out because no ignition 4 s 53 s 8 s 4 s 53 s 2 s max. D1798 If during operation the flame shuts off, lock-out occurs within 1 sec. 8

BURNER STARTING DIFFICULTIES AND THEIR CAUSES DIFFICULTIES The burner goes through the purge period normally, the flame ignites, but the burner goes to lock-out, within two seconds after the ignition if: The burner goes to lockout, after the purge period, because the flame does not ignite; the causes may be: CAUSES The ionization probe is earthed or not in contact with the flame, or its wiring to the control box is broken, or there is a fault on its insulation to earth. The ionization current is weak (lower than 3 µa). The valve is passing too little gas (low pressure in the gas pipework). The valve is defective. The pipe has not been purged from the air. The ignition arc is irregular or has failed. The burner does not pass through the pre-purge period and the control box goes to lock-out: The air pressure switch does not change over: it has failed or the air pressure is too low (combustion head bad set). Flame simulation exists (or the flame really lights). Gas is not supplied. The burner does not start at the thermostat closing, because of: The gas pressure switch does not close: incorrectly adjusted. The air pressure switch is changed over to the operational position. The fuse of the control box is broken. The burner repeats the start-up cycle without occurring the lock-out: This particular trouble is caused by the gas pipework pressure that is very close to the value of the gas pressure switch setting, owing to the sudden pressure decrease the valve opens and actuates - only temporaneously - the opening of the pressure switch, thereafter the valve closes, the motor stops and the pressure increases again; the pressure switch closes and the start-up cycle is repeated and so forth. To prevent this trouble, setting the gas pressure switch at a lower value. OPERATING FAULTS Lock-out may occur, because of: - flame failure; - ionization probe earthed; - air pressure switch open. Shut-off may depend on the gas pressure switch opening. 9

RIELLO S.p.A. Via degli Alpini 1 I - 37045 Legnago (VR) Tel.: +39.0442.630111 Fax: +39.0442.630375 http:// www.rielloburners.com Con riserva di modifiche