Sapag Control valve MONOVAR

Similar documents
Pressure and Flow Control Valves DBGM, German and European Patents

Cavitation in Valves

for Building facilities Industrial facilities etc.,multipurpose Pilot operated type(high capacity)

SINGLE VALVE WITH LOW-FLOW BYPASS

BACK PRESSURE / SUSTAINING

KTM 50 (DN ) Installation, maintenance and operating instructions

BACK PRESSURE / SUSTAINING

Series 42 Self-operated Regulators Differential Pressure Regulators with Type 2424/Type 2428 Actuator (closing) Type Type 42-28

Pressure Reducing Valve for Steam Type 2333 A

COMPAFLOW. Compressed Air. Volumetric flow. Gas. Mass flow. Steam. Net volumetric flow. Liquid

PRESSURE REDUCING VALVE RP45 (EN)

Pressure Independent Control Series

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

3-way control valves VK 3

CAST IRON SAFETY VALVE TYPE 6301

Engineering / Technical Section

Reduce pressure zone device suitable for high and medium hazard rated applications Flanged end connections

THE INFLOW OF UNWANTED AIR

T 2523 EN Type 2406 Excess Pressure Valve Self-operated Pressure Regulators ANSI version

Description. Functions. Technical data. Applications. Tests. On-Off 2 levels float control valve, closing at high level and opening at low level.

Bermad Pressure Reducing. Model: 42T

Seated valve for steam (PN 25)

553 Series.

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

Seated valve for steam (PN 25) VFS 2 2-way valve, flange

Versions. Benefits. Balancing DN15-32 DN40 DN50 DN15, DN20, DN25, DN32, DN40, DN50. Dimensions

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump.

Flanged pressure reducer/stabilizer VRCD

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

Air Eliminators and Combination Air Eliminators Strainers

Integral type Differential pressure flowmeter VNT Series

The Discussion of this exercise covers the following points:

Application Worksheet

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

6301 TYPE CAST IRON SAFETY VALVES

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

MANUFACTURING - WATER VALVES - INDUSTRIAL VALVES - PENSTOCKS AND GATES - RADIAL GATES - SPECIAL APPLICATIONS

2-Port Seat Valves with Flange, PN 16

CAST IRON VALVES FLOAT VALVE

Self-operated Pressure Regulators for special applications

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

Pressure reducing valves Index

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

Seated valves (PN 6) VL 2 2-way valve, flange VL 3 3-way valve, flange

Size : Connection Ends : Min Temperature : Max Temperature : Materials : Cast iron body

Coriolis Mass Flow Meter

700 SIGMA SERIES ENGINEERING DATA

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

Reduce pressure zone device suitable for high and medium hazard rated applications BSP screwed connections

Vortex Flow Meter Wafer or Flange Connection. - Steam - Liquid - Gas

CA10S, CA14 and CA14S Air and Gas Traps

Exercise 4-2. Centrifugal Pumps EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Pumps

S and SF Inverted Bucket Steam Traps

Deltaflux Control Valve

Rate of Flow Valve Series 120

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

Differential Pressure Control Valve (DPCV)

Self-operated Pressure Regulators Type 2405 Pressure Reducing Valve

SCA Series Inverted Bucket Steam Traps

Radar, Ultrasonic and RF Level Transmitters

Operating Manual FSV, FSÖV, SSVF

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

Model: 43T. Bermad Pressure Relief Valve

STAINLESS STEEL LOW PRESSURE REDUCING VALVE LPRV ELITE

Pressure reduction controller (PN 16, 25, 40)

Mounting and Operating Instructions EB 3017 EN. Self-operated Regulators

94270 Vapor Guard Tank Blanketing Valve Vapor Guard Tank Blanketing Valve What is Tank Blanketing? Features How does it work?

Pressure Reducing Valve for steam RP 45

Installation, operation & maintenance manual - original version

POP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

Pressure reducing station. ARI-Pressure reducing station, self-acting or with electro-pneumatic control. ARI-PREsys -S. Pressure reducing station

Pressure independent control valve (PICV) FLOWMATIC

STAP. Differential pressure controllers DN , ANSI flanges

V43 Pressure Actuated Water Regulating Valve

P-04 Stainless Steel Corrugated Hoses and Metal Bellows Expansion Joints

Pressure and/or Temperature Pilot Operated Steam Regulators Series 2000

776 Cryogenic Safety Valve

CONTROL VALVE TESTING

Pressure reducing station. ARI-Pressure reducing station, self-acting or with electro-pneumatic control. ARI-PREsys -S. Pressure reducing station

Exercise 2-2. Second-Order Interacting Processes EXERCISE OBJECTIVE DISCUSSION OUTLINE. The actual setup DISCUSSION

Technical data sheet. Type overview. Technical data. Safety notes. T5-R2.. Open-close en v Subject to changes 1 / 3

TSS21 Sealed Thermostatic Steam Tracer Trap

Products no longer available

Serie 06-M6. Swing wafer check valve. made in. Application fields. Check valves E U R O P E WATER CONDITIONING INDUSTRY

VPPL VARIABLE DISPLACEMENT AXIAL-PISTON PUMPS FOR INTERMEDIATE PRESSURE SERIES 10

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

FITTINGS AND VALVES Düker Plunger Valve RKV Type 7015 Professional control of flow rates, reservoir levels and pressures Safe, hygienic and durable!

NAF-Trimball Control Ball Valves

Bubble Tube Installations

High Performance BSP Dial Up Pattern Pressure Reducing Valve

IndustrialValves 2017/ HIGH PERFORMANCE BALL VALVES

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

Fisher DVI Desuperheater Venturi Inline

Dival 500 Pressure Regulators

Mounting and Operating Instructions EB 3009 EN. Self-operated Regulators. Type RS Check Valve (backflow protection)

PRESSURE REDUCING VALVE RP45 (ANSI)

Transcription:

MONOVAR MONOVAR is the energy dissipating valve Features MONOVAR DN 2000 (80 ) Extremely simple design (patented) Excellent cavitation characteristics Very accurate flow or pressure control Manual or automatic control Suitable for flow measurement Small sizes are available Minimum flow disturbance The flow is divided equally over a larger number of jets. This ensures an accurate and stable performance These unique features, together with the wide range of construction materials make MONOVAR valves an automatic choice in all severe industrial and water-supply situations requiring fluid flow control or of some associated characteristic, e.g. pressure, temperature and level The design suppresses vibration, cavitation, pressure fluctuations and excess noise Suitable for high velocity applications Suitable for high pressure drop applications General application Application of MONOVAR : - Water supply systems (reliability, pressure, cavitation), - Industrial flow, cooling and mixing systems (cavitation, sensitivity, pressure, reliability), - Head works of water treatment plant (reduced civil works, cavitation, reliability), - Laboratory test-rigs (sensitivity, absence of disturbances), - Turbine bypass (dams), - End of line, free discharge, - Replace variable speed pumps with constant flow or constant pressure pumps in combination with MONOVAR, - Seawater applications on request. Technical data Size range: DN 100 - DN 2000 (NPS 4 - NPS 80) Pressure range: 50 bar (725 psi) Temperature range: -50 to +200 C (-60 F to +390 F) Flange accommodation: EN 1092-1 PN10/16/20/25 ASMEB16.5 class 150 MSS SP 44 class 150 AWWA C207 Others on request www.pentair.com/valves 2012 Pentair plc. All rights reserved. VCTDS-02619-EN 15/07

MONOVAR Operating principle Pipe flange The simplicity of the MONOVAR design is explained in Figure 1. Components are simply two circular perforated plates, and an annular body (1) mounted between pipe flanges. Plate (2) is fixed. Plate (3) on the upstream side is free to slide up and down. In the fully open position the orifices in the plates are in line. The fully closed position is obtained by displacing the mobile plate (3) by one full orifice diameter. Under specified flow conditions, the position is intermediate, with the orifices in the fixed plate partly blocked off by those of the mobile plate. The valve can be operated both manually or by using pneumatic, hydraulic or preferably electric modulating actuators. Flow Pipe Advantages Figure 1 The energy released by a fluid when it flows through a valve often causes disturbance in the flow. Examples are: flow and pressure fluctuations liable cause vibration in the pipework, cavitation bubbles (i.e. fluid vapor bubbles), and noise. Noise is caused by sudden implosion of cavitation bubbles. In MONOVAR valves, energy dissipation is controlled by multiple distributed jets which divide the flow. This means that disturbing effects are considerably reduced, as described below: - Flow fluctuations are reduced by the jet design and the quick flow stabilization. Consequently, devices such as flow meters may be placed much closer to the control valve than usual, so the system can be constructed more compact. - MONOVAR control valves have better cavitation indexes which are more favorable than those of conventional valves. Due to its design MONOVAR copes better with cavitation than traditional control valves. - Fully developed cavitation does not damage MONOVAR valves since the implosions occur in the fluid and not in the valve its vital parts. This unique design outperforms the design of conventional valves where cavitation is frequently observed on the obturator and seat. Vapor bubbles are not formed when MONOVAR valves are properly selected. A final point for operational reliability: MONOVAR valves do not have a natural tendency to open or close while controlling flow or pressure. 1. Annular body 2. Downstream, fixed plate 3. Upstream, mobile plate 2

MONOVAR - Hydraulic characteristics This section gives a brief overview of the hydraulic design data and selection criteria for MONOVAR control valves. The data come from measurements made on the Sapag test rigs, from experience gained on Sapag turbine test installations, and from feedback from MONOVAR users in the industry and in the water resources field. Cavitation The flow-path contractions, sudden expansions and changes of direction encountered by a fluid as it passes through a valve tend to create -locally- a reduction of pressure. If the local pressure drops below the vapor pressure of the liquid, then the liquid boils. Vapor bubbles and their implosions appear in the liquid. This phenomenon is called cavitation. The tendency of a valve to cavitate is usually characterized by a cavitation number defined as: σ = P 2 - P v - P 2 P 2 P v absolute upstream pressure measured in practice one pipe diameter above the valve, absolute pressure measured 10 pipe diameters below the valve and corrected for friction losses between points 1 and 2, vapor pressure of the liquid at the operating temperature. These pressure values are generally expressed as meters head of liquid. Some valve manufacturers utilize a cavitation number defined as: K = - P 2 - P V with the same notations. Simple algebra shows that the two numbers are related by K = 1 1 + σ and σ = 1 - K K For a given valve opening various values of σ are established by the manufacturer corresponding to various degrees of cavitation. Also defined for a given valve is how the σ values vary with opening. These values may be plotted in the form of so-called required sigma curves which indicate the degree of cavitation risk which will be encountered by users of the manufacturer s valve. MONOVAR index cavitation 1,4 1,2 Area 1 σ 1 0,8 Area 2 0,6 0,4 0,2 Area 3 Forbidden area 0 0 20 40 60 80 % opening 3

MONOVAR - Hydraulic characteristics Specific flow Typical flow characteristics Specific flow is defined as the flow passing through a one meter diameter MONOVAR, which causes a head loss equal to one meter head of water. Specific flow may be written in terms of head loss as: = Q ΔH D D 2 Q H specific π g flow in m 3 /s at a given valve opening, the total flow passing through the valve in m 3 /s, the head loss in water column meters liquid at the same valve opening, is the nominal MONOVAR diameter in meters. The graph shows how varies with valve opening at constant headloss. 100 80 60 40 20 Flow % Note that may be expressed in terms of the head loss coefficient for example in the fully open position, the specific of a MONOVAR valve with maximum perforated area installed in a pipe whose diameter is equal to the nominal diameter of the valve is 1.3 m 3 /s. The specific flow value drops to 0.95 m 3 /s for an end-mounted valve. 10 10 20 40 60 80 100 % valve opening = π 2 g 8k Head loss The pressure drop caused by flow through MONOVAR valves is written as: H = k V 2 2g k 1000 Headloss coefficient / % valve opening ΔH k V g the pressure drop in meters water column at a given valve opening, the (dimensionless) head loss coefficient at the same valve opening, the velocity of the liquid in meters per second computed on the basis of the nominal flowsection of the valve, gravitational acceleration in meters per square second. 100 The graph shows an example curve of k values for maximum perforated area of the MONOVAR plates. 10 10 20 40 60 80 100 % valve opening 4

MONOVAR - Hydraulic characteristics Graphic method of determining available sigma The available cavitation figures may be calculated quite simply by graphic means. The example calculation shown in the Figure below is based on flow between tanks at different levels. The figure depicts the connecting pipe and included control valve and, to below, a head versus flow chart. Pressures are expressed here as heads of flowing liquid because this is the usual procedure. However, variables H 1, H 2, H V have the same basic meanings as, P 2, P V cited above, e.g., H V is the vapor pressure of the flowing liquid expressed in meters head of that liquid. Vertical a b c d conveniently depicts the head loss components at the maximum value of discharge Q. The head losses above and below the valve are ab and cd respectively. The intermediate distance bc, i.e. (H 1 - H 2 ) represents the head loss which may be throttled out by the valve. The (quadratic) curves leading down to b and up to c show how head is lost by friction effects along the two lengths of pipe. H a, the head at point a, corresponds to the pressure at the surface of the upper tank, I.e. atmospheric. Having drawn out the essentials of the figure thus far, it only remains to add a further horizontal line labeled e. This should be drawn at a distance equal to (H a - H V ) below the zero head axis. The numerator (P 2 - P V ) of the sigma expression is represented by the length ce, which is evidently equivalent to H 2 + H a - H V, the denominator being bc. The desired sigma cavitation number is therefore ce/bc. Head H in meters versus flow rate Q Upstream tank Headloss a H 1 b H 2 c 1 2 0 (H a H v ) d e Q Flow MONOVAR valve Downstream tank 5

MONOVAR - Hydraulic characteristics Operating limits Temperature MONOVAR valves made from the standard materials should not be operated outside the temperature range 0 to 80 C. Seal effectiveness may be maintained up to 200 C by using special seal material. Elastomer and plastomer seals cater to low temperatures down to -50 C. The temperature limits above are only approximate and depend on fluid and operating pressure. Pressure PN64 DN 100 PN40 DN 150 PN25 DN 200 to DN 600 PN16 DN 700 to DN 800 PN10 DN 900 to DN 2000 Tightness Valve is not bubble tight as it is recommended to install the MONOVAR between two isolation valves. The MONOVAR is unidirectional. In case of backflow, please contact factory. 6

Monovar - flow and cavitation characteristics Characteristics MONOVAR flow and cavitation characteristics are shown in Figure 2 in terms of specific flow in m 3 /s. = D 2 Q H Q m 3 /s D m ΔH headloss in m σ = P 2 - P v - P 2 K = - P 2 - P V Area 1: Excellent operation Area 2: Acceptable operation Area 3: Possible operation Area 4: Forbidden area Please contact factory for applications in area 3 and 4. Figure 2 MONOVAR DN 450 Opening % MONOVAR DN 400 Possible Impossible MONOVAR end of line valve Forbidden area Area 3 Area 1 Area 2 7

Monovar - flow and cavitation characteristics Diameter choice 1. Input data liquid Flow rate adjustable between Q and Q Range of absolute upstream pressure and P 1 Range of absolute downstream pressure P 2 and P 2 Available MONOVAR throttling range ΔH and ΔH Vapor pressure of liquid at operating temperature P V Nominal diameter of pipe D Example (water) Q= 0.150 m 3 /s Q = 0.250 m 3 /s = 50 mwc P 1 = 48 mwc P 2 = 25 mwc P 2 = 28 mwc ΔH= 25 mwc ΔH = 20 mwc P V = 0.2 mwc D= 0.3 m 2. First computation stage calculate Q Q = and = q 11 D 2 H D 2 H Example (water) 0.15 0.25 = = 0.33 = q 11 = 0.62 0.3 2 25 0.3 2 20 if q 11 < 1.3 the MONOVAR diameter will be less than or equal to D if q 11 > 1.3 the MONOVAR diameter will be greater than D, and the new valve should be chosen so that q 11 1.3 0.62 < 1.3: the MONOVAR will therefore have a diameter 0.3 NOTE: Pipe fittings such as bends, cones or any other mechanical equipment will alter the MONOVAR s specifications. In that case, please contact factory. 3. Second computation stage Example (water) P σ 2 - P v = σ = - P 2 P 2 - P v - P 2 25-0.2 = 0.99 28-0.2 = 1.39 50-25 48-28 σ = σ = If points (, σ) are situated in cavitation area 1 (excellent) in Figure 2, then there is no risk of cavitation and the MONOVAR diameter initially assumed may be selected - or even reduced. If points (, σ) are situated in areas 2 or 3 (acceptable or possible), the effective cavitation risk will depend on operating life and it may be necessary to choose a larger MONOVAR. As both points lie in area 1, a 0.3 m diameter MONOVAR may be chosen. If D were reduced to 0.25 m, then = 0.48 q 11 = 0.89 and the valve would be subject to cavitation in certain cases. 8

MONOVAR MONOVAR - Valve dimensions Manual actuators Electric actuators Valve dimensions (mm) Weights DN NPS C ød G H K L M P R S Manual Electric 100 4 60 162 313 446 404 309 64 296 125 125 11 30 150 6 80 220 348 516 428 309 110 558 148 374 73 67 200 8 80 290 348 541 428 309 110 583 148 374 86 79 250 10 84 350 348 576 428 309 110 618 148 374 105 80 300 12 95 400 348 636 428 309 110 678 148 374 127 115 350 14 110 438 589 1266 428 309 178 1210 178 530 258 286 400 16 110 516 589 1271 428 309 178 1215 178 530 290 318 450 18 140 560 589 1276 428 309 178 1220 178 530 320 350 500 20 150 594 589 1296 428 309 178 1240 178 530 351 390 600 24 160 696 589 1366 428 309 178 1310 178 530 432 470 700 28 160 806 589 1396 428 309 178 1340 178 530 494 510 800 32 160 914 589 1456 428 309 178 1400 178 530 614 610 900 36 160 1017 589 1519 428 309 178 1460 178 530 662 690 1000 40 160 1124 589 1596 428 309 178 1540 178 530 778 806 1200 48 160 1342 589 1666 283 160 178 1610 178 530 1015 1043 1400 56 160 1580 589 1816 283 160 178 1760 178 530 1336 1364 1500 60 250 1660 589 1866 283 160 178 - - - - 2100 1600 64 330 2032 331 2510 994 254 384 - - - - 5500 2000 80 450 2345 352 3767 368 437 913 - - - - 8500 Materials of construction Standard materials are as follows: - Body: EN GJS 500-7 nodular cast iron - Fixed plate: EN GJS 700-2 nodular cast iron or 13% Cr stainless steel (X20 C13) - Moving plate: EN GJS 500-7 nodular cast iron or 13% Cr stainless steel (X20 C13) - Support: EN GJS 500-7 nodular cast iron - Stem: 13% Cr stainless steel - Flange and stem seals: 70 Shore-hardness Perbunan Other construction materials are available on request to suit particular operating conditions. Notes: Dimensions in mm, weights in kg Dimensions and weights are given as a guide 9

MONOVAR Valve actuators MONOVAR control valves may be controlled manually (handwheel with micrometer position indicator) or by electric, pneumatic or hydraulic powered actuators. Information on the large range of actuator possibilities is available on request. Recommended installation standard position General installation instructions - Allow the MONOVAR to be removed at a later stage (observe clearances, use sliding joints and unions, etc.). - Install the pipeline, or use the appropriate fittings, so that the MONOVAR does not have to withstand any abnormal loads, resulting from mechanical pipe stresses or from thermal expansions. - Check that the pipe sections are in line, that the flanges are parallel, that any sliding flanges are working correctly and that the holes in mating flanges coincide. - Depending on the kind of water carried, provide a screen, a filter or sludge trap upstream of the valve in order to prevent it from jamming or suffering any mechanical damage. - Check that the valve is installed correctly with respect to the direction of fluid flow. An arrow on the body of the MONOVAR shows the correct direction; this direction must be followed, in order to prevent failure. - Before installing the MONOVAR, clean it with a jet of compressed air. Ensure that the pipes are perfectly clean and especially that there is no material inside them likely to cause serious damage (lumps of rust, welding pearls, slag, etc.). - Bear in mind that proper installation of the MONOVAR is a precondition for satisfactory working of the valve. - MONOVAR valves may be mounted between pipe flanges with the help of tie-rods, which ensure correct alignment. They may also be mounted at the end of a pipe. To facilitate mounting and disassembly, the use of sliding flanges or sleeves are recommended. - The valves may be installed in both vertical and horizontal pipes. In vertical pipes the flow should preferably be downwards. Valves mounted horizontally should be placed with the actuator upwards to make proper use of the drain orifice, which will then be situated on the lower side. Flow Free from any mechanical equipment 5 x DN Straight lengths of pipe Free from any mechanical equipment 3 x DN 10

MONOVAR Control details A controller is designed to control a valve that will regulate the flow or the pressure in an installation. The controller is a PID type (Proportional, Integral, Derivative). In addition to regulation, the controller can accept input data, relevant to the process, from various sources (pressure sensors, etc.). The controller can analyze them (alarm etc.) The controller can be installed on its own (self managing) or be part of a centralized system. Example of regulation - Upstream pressure - Upstream level - Downstream pressure - Downstream level - Flow (with head loss measurement) - Flow (with flow meter) - Upstream pressure and flow totals - Downstream pressure and flow totals - Upstream level and flow totals - Downstream level and flow totals Operating diagram: Power supply Controller Power supply 220 V AC Box positioner and local control Electric actuator MONOVAR valve Control output analog output (4-20 ma) Digital output travel and torque limit switches Valve position analog output (4-20 ma) (7) Mounting plate or box Controller Value transmitter input analog input (4-20 ma) (6) Terminal blocks Digital output: alarms Analog output (4-20 ma): MONOVAR flow External value input (4-20 ma): Pressure value analog input (4-20 ma) Upstream Flow Size Downstream Upstream pressure transmitter Differential pressure transmitter * Downstream pressure transmitter * For proper pressure transmitter installation details, please contact factory. 11

PENTAIR VALVES & CONTROLS www.pentair.com/valves All Pentair trademarks and logos are owned by Pentair plc. All other brand or product names are trademarks or registered marks of their respective owners Because we are continuously improving our products and services, Pentair reserves the right to change product designs and specifications without notice. Pentair is an equal opportunity employer. 2015 Pentair plc. All rights reserved. 12