electronic but, for the purposes of this course, we will consider

Similar documents
Gerald D. Anderson. Education Technical Specialist

Measurement And Control Appreciation

Instrumentation & Data Acquisition Systems

PROCESS MONITORING AND CONTROL

INDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR NPTEL ONLINE CERTIFICATION COURSE. On Industrial Automation and Control

Instructions for SMV 3000 Multivariable Configuration (MC) Data Sheets

Exercise 8. Closed-Loop Pressure Control, Proportional-Plus-Integral Mode EXERCISE OBJECTIVE

Process Dynamics, Operations, and Control Lecture Notes - 20

Model 4000 Pressure Controller

The Discussion of this exercise covers the following points:

SINGLE VALVE WITH LOW-FLOW BYPASS

The Discussion of this exercise covers the following points:

Hydronic Systems Balance

The Discussion of this exercise covers the following points: Range with an elevated or suppressed zero Suppressed-zero range Elevated-zero range

Digital Level Control One and Two Loops Proportional and Integral Control Single-Loop and Cascade Control

IE039: Practical Process Instrumentation & Automatic Control

Characterizers for control loops

Model 130M Pneumatic Controller

M-System s I/P and P/I Transducers

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Exercise 2-2. Second-Order Interacting Processes EXERCISE OBJECTIVE DISCUSSION OUTLINE. The actual setup DISCUSSION

Measuring range Δp (span = 100%) Pa

IE011: Process Control & Instrumentation Technology

The Ins and Outs of I/P Transducers

CHEMICAL ENGINEERING LABORATORY CHEG 239W. Control of a Steam-Heated Mixing Tank with a Pneumatic Process Controller

ACTUATORS AND INSTRUMENTS

The benefits of the extended diagnostics feature. Compact, well-proven, and flexible

Process Control Loops

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Unit 55: Instrumentation and Control Principles

COMPARISON OF DIFFERENTIAL PRESSURE SENSING TECHNOLOGIES IN HOSPITAL ISOLATION ROOMS AND OTHER CRITICAL ENVIRONMENT APPLICATIONS

INSTRUMENTATION EQUIPMENT

COMPAFLOW. Compressed Air. Volumetric flow. Gas. Mass flow. Steam. Net volumetric flow. Liquid

How to specify a product. Process Sensors and Mechanical Instruments

Application Worksheet

PositionMaster EDP300 Extended Diagnostics. Compact, well-proven, and flexible

CONTROL and INSTRUMENTATION

CHAPTER 7: THE FEEDBACK LOOP

CONTROL VALVE WHAT YOU NEED TO LEARN?

LABORATORY EXERCISE 1 CONTROL VALVE CHARACTERISTICS

BAPI Pressure Line of Products - FAQs

OIL & GAS. 20th APPLICATION REPORT. SOLUTIONS for FLUID MOVEMENT, MEASUREMENT & CONTAINMENT. Q&A: OPEC Responds to SHALE BOOM

CVI Valve Line. Exceeds the industry s highest standards for reliability and performance

Control Valve : The Final Control Element. Nimish Shah

SB AXIAL FLOW VALVES

IE068: Process Instrumentation Technology

Design Features. General Description

Level MEASUREMENT 1/2016

Fail Operational Controls for an Independent Metering Valve

Drilling Efficiency Utilizing Coriolis Flow Technology

SSL. Smart Valve Positioner.

DPC-30 DPC-100. Reference Manual

Pressure Measurement

Installation and Operation Manual

MANUAL KPS Pressure Control Valve

Instrumentation & Data Acquisition Systems

Lab 1c Isentropic Blow-down Process and Discharge Coefficient

RC 195 Receiver-Controller

SSR. Smart Valve Positioner.

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

STICTION: THE HIDDEN MENACE

Smart Water Application Technologies (SWAT)

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions

Exercise 2-3. Flow Rate and Velocity EXERCISE OBJECTIVE C C C

TESTING OF BELIMO PRESSURE INDEPENDENT CHARACTERIZED CONTROL VALVES

Shanghai AEAD Technology Co., Ltd Professional Manufacturer of Flow, Level, Pressure, Temperature

Control Valves, Actuators, & Pressure Safety Valves

Bubble Tube Installations

Improving distillation tower operation

Sensors and Detectors Part 1

ACV-10 Automatic Control Valve

Cascade control. Cascade control. 2. Cascade control - details

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

TECHNICAL INSTRUCTIONS Iron Body Series 597 SI

AFC. SDPROC and AFC Analog Mass Flow Controller ANALOG MASS FLOW CONTROLLERS. Principles of Operation. Design Features

Pressure and/or Temperature Pilot Operated Steam Regulators Series 2000

Gas Measurement Fundamentals Certification. Curriculum

FUNDAMENTAL PRINCIPLES OF SELF-OPERATED PRESSURE REDUCING REGULATORS. John R. Anderson Emerson Process Management Fluid Controls Institute

AMT-Ex Dewpoint Transmitter

Advanced Pump Control for Irrigation Applications

CSC-2000 SERIES. Reset Volume Controllers MADE IN U.S.A. DESCRIPTION MODELS SPECIFICATIONS ORDERING

Process Simulator Evaluates Blower and Valve Control Strategies for WWTP Aeration

INSTRUMENTS A THERMAL MASS FLOW SENSOR USING A CONSTANT DIFFERENTIAL TEMPERATURE ABOVE THE AMBIENT GAS TEMPERATURE

Differential Pressure Transmiter

my SYSTEM A guide to common applications in water distribution systems

Pressure on Demand. Air Pressure Amplifiers

Series 2G Diaphragm Actuators

Radar, Ultrasonic and RF Level Transmitters

The Use of a Process Simulator to Model Aeration Control Valve Position and System Pressure

[Instruments for vacuum measurement, checking and adjustment] 3

Multiple Pressure Booster Systems With Variable Speed Controller Type BL

EXPERIMENT 1 AIR PRESSURE CONTROL SYSTEM

Reset Volume Controller 2 Reversing Relay 3 Air Valve Actuator 4 Lower-of-Two-Pressures Relay 4 Diverting Relay 5 Higher-of-Two-Pressures Relay 5

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

Powers Controls RC 195 Single Input Receiver-Controller

Pressure Measurement. Introduction. Engr325 Instrumentation. Dr Curtis Nelson 3/12/18

The Next Generation for Level Control. By Ryan Spooner, Singer Valve

SUPER PRECISION AIR RELAYS

Chapter 10: Bidirectional Flow Controls

ACCURATE PRESSURE MEASUREMENT FOR STEAM TURBINE PERFORMANCE TESTING

Transcription:

Instrumentation an9 Control - Course 136 CONTROL EQUIPMENT REVIEW The equipment in a basic process control loop can be divided into three main categories: 1. The measuring Element. 2. Controllers 3. Final Control Element. The measuring element will usually consist of a primary element (temperature or pressure measurement) coupled to a transmitter. This combination can be either pneumatic or electronic but, for the purposes of this course, we will consider only the electronic system. (The pneumat,ic system can be reviewed by reference to 430.31-1 and 430.31-2.) For pressure will (also flow and have some form level) measurement the primary element of position detector to produce final electronic signals of 4-20 rna from the applied force. This position detector will take the form of a variable resistive, capacitive or inductive element depending upon manufacturer. The inductive detectors are generally of two types. One, a standard variable inductance, (Figure 1) as used by F&P and Honeywell and the other which takes the form of a variable mutual inductance, or Linear Variable Differential Transducer (LVDT), as used by Foxboro (Figure 2). Both types of inductive sensor will be operated from a frequency source of a few kilohertz. This ensures relative immunity from the effects of stray 60 Hz magnetic fields and also reduces the physical size of the inductive components. Resistive elements, usually in the form of gauges, can be employed to produce a resistive change tional to the applied force. These strain gauges are used in a Wheatstone Bridge configuration. A typical or system as used by Statham-Gould is shown in Figure strain proporusually detect 3 If the pressure capsule element is used to move the plates of a variable capacitor, the capactive reactance (Xc = 1/2 7T fc) can be made proportional to the appl ied pressure. This is the principle used in the Rosemount transmitter (Figure 4). february 1982-1 -

1 v, Ll: Ad r- lffiit }o A. Primary Voltage Vp Secondary v s Ex j ~ t F Voltage 1 2 Detector I errite Disc AD Figure 1: Inductive Sensor. Figure 2: Linear Variable Differential Transformer. :> < >RS 1 R, de RS2 R 2 ~ J: V F.B. 4-20 ma Figure 3: Resistive Sensor. 4-20 ma Figure 4: Capacitive Sensor. - 2 -

It should be noted that all electronic transmitters will produce a 4-20 rna signal when used in the standard current loop configuration. ' For temperature measurement the primary element in an electronic system will be either a thermocouple (TC) or a Resistance Temperature Detector {RTD). The thermocouple generates a millivolt level signal proportional to temperature and type of materials used as the hot junction. RTD's exhibit a resistance charge proportional to temperature. The RTD is usually incorporated as one arm in a Wheqtstone Bridge configuration. Controllers The signal from an electronic transmitter will usually be fed to a controller. This will compare the signal with a predetermined setpoint to produce an error signal. The controller must be capable of changing the amplitude and direction of this signal in order to restore t~e controlled variable to its ~etpoint following a process variation. It will therefore have adjustable proportional and intergral modes as standard and derivative mode as an additional extra option. These features are usually achieved by using operational amplifiers and methods of obtaining these are shown in 336.2. A representative electronic controller is shown Figure 5. The optimum settings of P, I and D will in be discussed in a later lesson. DERIVATIVE AMPliFIER <"2OmA D'RECTI""""RS. --..--,...,,,..., ;~ 250tl.;: 1_!V --...--.. ' ourput METER REMon SU!'OINT' REMOrE J OEV, "'HER CURREm" oot"ut sration, ' IOmA r---~ SET FO'N' Figure 5: Representative Electronic Controller.

-. - 136.00-1 Note that it may also be necessary to incorporate other items of electronic equipment with the controller. These will include: high, low or median select circuitry, square root extractors, (when flow measurement is involved), and signal summing and averaging relays. In addition, high or low level alarms in the form of pressure switches or current alarms may be included. All these items are fully described in 230.30-4. Final Control Element We shall consider only the control valve as a final control element since it is by far the most widely used device. We will not consider the many and differing types of valves that exist but there are two important factors that require more detailed discussion. These are the flow capacity and flow characteristic of the valve. Flow Capacity is the maximum volume of, gas, liquid, or steam that may be passed through the valve in 'unit time with the valve fully open. This is more usually related to the flow coefficient (CV) which is defined as the volume of water (in us gallons) that will flow 'through the valve at maximum opening with a pressure drop, across the valve, of one psi. The Basic Flow Equation is based upon the general equation: Q = KI2Ip where a is the flow rate, lip is the pressure head across the orifice or valve and K is a constant. For valves the constant (K) is associated with the valve coefficient (CV). Q = C v /is p (l) Now lip is a measurement of head and must be converted to pressure. 1'Ip = sh where, Ap = s = h = pressure specific weight head h = A pis substituting in equation (1) Q = cvlkp/s or C v = 0/s/1'I P

Valve Characteristics Inherent Flow Characteristic of a valve is defined as the relationship between fractional valve lift and the relative flow through the valve at a constant pressure drop. Installed characteristic unique to each Characteristic is the actual lift versus flow unqer system operating conditions and is specific installed system. Most commerically available valves have inherent flow characteristics that fall between the quick opening and equal percentage curves as shown in Figure 7. These are based upon characteristics provided by the manufacturer and are determined by experimental methods. The valve gain can be assessed from these curves and is equal to the slope of the characteristic. The linear valve has a constant gain of 1 while the equal percentage valve has a low gain at the near closed position that increases to a higher gain at full capacity. The quick openi,ng valve provides essentially the opposite conditions. If we consider a typical control loop diagram, Figure 6', we can illustrate the relationship of valve gain to controllability. K ~ Galli Gz Oman*: or IinIt CCIlIIIIIII Figure 6: Representative Control Loop.

loop Ideally the open loop gain, is constant and equal to: KL = K.KaoKv Kp.Kt of a stable control where K, (controller gain) K a (actuator gain) and K t (transmitter gain) are almost constant over wide ranges of operation. Thus the process gain, Kp, and the valve gain, K v ' must compensate for each other if the loop is to remain stable and linear. If these gains are not compensating it would be necessary to continually adj ust the controller gain to, correct the differences. Thus good design d ietates that the valve must compensate for the change's in gain over as wide an operating range as possible. To match the gains by selecting the control valve characteristic can be aocomplished relatively easily by considering the types of systems most often encountered. Consider first the case where the control valve is throttling flow between a stable high pressure system and an almost constant lower pressure system with low frictional losses other than those of the valve itself, ie, the loop has a relatively constant process gain. A linear characteristic would be the obvious choice for this application. An example would be-the feed valves in the Heat Transport System. For a second example, consider a system with piping losses relatively higher than the pressure drop across the valve. This type of system is more repsonsive at low flows and more restricted at higher flows due to the increased frictional losses. The control valve should have a characteristic which compensates for the decay in process gain at high flows, ie, an equal percentage valve should be used. For a typical example consider the light water zone level control valve. The quick opening valve is naturally used for applications where on/off type of control is required, eg, liquid poison injection for shut down System 2. It must be remembered however that installed characteristics cali be decidedly different from inherent characteristics, as supplied by the manufacturer, which were determined under laboratory conditions. The general form of typical flow characteristics is shown in Figure 7. - 6 -

l 40 zo 40 60 80 roo Slem posifion, pet'unf Ftgure 7: Typical valve Flow Characteristics. Ii a SUfficiently high pressure drop can be a~located to the valve, then the installed characteristic would be very near the inherent characteristic. But as a lower ~alve ~essure ratio i~ applied, the inherent characteristic will tend 1:0 linearize for an equal percentage valve and approach a quick-~pening ~haract~ristic for a linear valve, ie, the flow versus travel, graphs move to the left.. If this trend is continued (111 chat'acteristics approach the quick openil)g and on/off curves which lead to unstable loop conditians and which will requir~ frequent controller tuning to accommodate load changes. The design must therefore include sufficient pressure drop~ say 10-30 percent of the system fr~ctional losses in ~ pumped system, to maintain. the required installed characteristic. - 7 -

/10 r:t------~~ :M~==;::~""'... 0 Figure 8: Typical Pump and system Cutves. Consider Figure 8 which shows a typical pump curve where head decays as flow increases. The frictional losses, PSI increase with flow rate and are proportional to the square of the flow. The remaining element, static head, will be essentially constant for any particular system. Note that the pressure available for the control valve is represented by the difference between the pump head and the sum of the static head and dynamic losses. From the data available the curve of the installed characteristic for the ideal control valve for the system can be developed. For the example above, it can be seen that at 100% flow the total dynamic system losses equal 60% of the system pressure, and 33% of the total system losses, (PR)' appear across the valve. C v can be calculated and at 100% flow equals 22. The' C v is then calculated for varying flows and the control valve characteristic can be drawn. For the case illustrated above therefore an equal percentage valve of Cv approximately 50 would be a reasonable choice for a design flow of 100 % with maximum and minimum flows of 110% and 25%. If the pressure drop for the val ve was decreased to 10% of the system frictional losses, only 6 psi of the total system pressure would appear across the val ve. This would allow a pump with a 14 psi lower head to be used to meet the same maximum flow conditions and a required C v of approximately 40. Note that the design flow C v has increased by - 8 -

approximately 100% because of the reduced pressure drop and the valve size would have to be increased to achieve the desired reduction in pump size. Remember that in the vast majority of systems an equal percentage value will be used, but in cases where the major system losses are in the control valve a linear characteristic should be selected. Valve Actuators Actuators are available in a wide range of forms, the common spring diaphragm actuator is, however, by far the most economical and widely used because of its simplicity and proven reliability. A control signal range of 20-100 kpag is usually selected to operate control valves. When the system is electronic, a transducer is therefore required to convert the 4-20 rna signal to a 20-100 kpa pneumatic signal for input to the valve. Traditionally the nominal 5:1 signal range with live zero, has been utilized to allow the 0-20 kpa and 100-120 kpa regions to provide excess stern loading to assure tight shut off. It should be remembered that wi th electronic controllers and electronic/pneumatic transducers there will be little, if any, over-ranging capability to provide tight shut-off. This condition must be either allowed for when specifying the valve type, or by off-setting the shutoff at either end of the range and thereby limiting the signal span. Dynamic Response The speed of response of an actuator is determined by the volumes of the signal tubing and diaphragm housing. Valves over about three inches in body size with standard actuators will generally exhibit a slower response and a volume booster or positioner should be provided to overcome this problem. A volume booster is a pneumatic relay that has a small volume at the inlet side and a high capacity regulator to provide a larger volume output signal. It is often 1:1, but can be 1: 2 or 1: 3. It will help to overcome lags caused by long signal tubing and large volume actuators. The valve positioner is a valve mounted accessory that drives the control valve plug to the precise position requested by the input signal. In doing so it also overcomes hysterisis effects caused by packing friction, increafi,es the speed of response, provides improved sensitivity, allows a signal reversal option and split ranged control. - 9 -

Most positioners incorporate a by-pass switch which removes the positioner from the signal path between controller and valve actuator. This is sometimes necessary f,?r maintenance purposes. Before operating the by-pass it 15 advisable to establish whether or not the positioner is being used in a reverse acting role, is providing amplification, or split ranging. Operating the by-pass switch under these conditions will cause loss of control. Fail Safe Action During the design of process loops, it is usual to consider each valve for failure positioning. This should be reviewed from two standpoints, one in the event of a total plant failure and secondly if a single valve loses its signal source. Three choices are available: 1. Fail Open, 2. Fail Close, 3. Lock-Up In Last Position. The first two options are usually achieved through selection of spring action that will drive the valve to its desired position when opposing power is lost. Lock-up is accomplished with a system of air reservoirs and valves. The spring technique is the most reliable and should be used if possible. - 10 -

ASSIGNMENT 1. Describe the two types of inductive sensing elements used in the pressure transmitter. Why is the driving voltage at a frequency of a few kilohertz. 2. Sketch and label a typical representative electronic controller. 3. Define the flow co-efficient of a valve. 4. Describe a typical system in which a valve with the following flow characteristic could be used: (a) Linear, (b) Quick-Opening, (0) Equal-Percentage. 5. Why is it necessary to allocate a sufficiently high proportion of the total system pressure losses to a control valve (linear or equal percentage). D. Tennant - 11 -